Sanitary Sewer Construction Notes 1. All public sanitary sewer systems shall be constructed in accordance with the latest edition of the Washington State Department of Transportation Standard Specifications for Road, Bridge, and Municipal Construction and the City of Longview Standard Plans and Specifications. 2. All public sanitary sewer system construction is subject to inspection and approval by the City Department of Public Works. The Contractor shall notify the City a minimum of two full working days prior to the start of any construction. 3. The Contractor shall be responsible for determining the location of all underground utilities prior to the start of construction/excavation and shall notify the engineer of any potential conflicts. The Contractor is required to contact the Northwest Utility Notification Center a minimum of two full business days prior to the start of construction and/or any excavation at 811 or www.callbeforeyoudig.org. 4. Tracer wire shall be installed with all non-conductive pipes in one continuous strand. Tracer wire shall be minimum #12 AWG steel reinforced copper wire. The insulation color shall be green and its material shall be a minimum 30 mil composed of high density polyethylene (HDPE) or high molecular weight polyethylene (HMWPE). Secure the wire on the pipe with tape every 8-10 feet as needed to keep the wire straight and on top of the pipe. Install a green warning tape 12-18 inches above the pipe in the same orientation to the installed pipe. See SS-260 for locator box detail and requirements. 5. Continuity testing of tracer wire is required. 6. The existing sanitary sewer system shall stay isolated from the new system via mechanical plug until the new system is cleaned, tested, video inspected and approved for use. 7. Sanitary sewer pipe shall be cleaned by use of high pressure nozzle and vacuum truck prior to video inspection of testing. Video inspection shall be performed in an operational and sequential order as approved by the City Engineer. All video work shall be completed with no piecemeal or skipping around the system. Video recordings shall be submitted on a CD, DVD, flash drive or similar media approved and accepted by the City. There shall be no debris in the lines or further cleaning will be required prior to acceptance. 8. All sanitary sewer pipe shall be tested for deflection. Sanitary sewer constructed of flexible pipe (e.g. thermoplastic pipe) shall be tested in accordance with 7-17 of the Standard Specifications. 9. Bellies shall not exceed 0.03 feet. SANITARY SEWER GENERAL NOTES SS - 000 JAN 2017 C.B.

SANITARY SEWER GENERAL NOTES - Official Website

  • Upload
    others

  • View
    27

  • Download
    0

Embed Size (px)

Citation preview

Page 1: SANITARY SEWER GENERAL NOTES - Official Website

Sanitary Sewer Construction Notes

1. All public sanitary sewer systems shall be constructed in accordance with the latestedition of the Washington State Department of Transportation Standard Specificationsfor Road, Bridge, and Municipal Construction and the City of Longview Standard Plansand Specifications.

2. All public sanitary sewer system construction is subject to inspection and approval bythe City Department of Public Works. The Contractor shall notify the City a minimum oftwo full working days prior to the start of any construction.

3. The Contractor shall be responsible for determining the location of all undergroundutilities prior to the start of construction/excavation and shall notify the engineer of anypotential conflicts. The Contractor is required to contact the Northwest UtilityNotification Center a minimum of two full business days prior to the start ofconstruction and/or any excavation at 811 or www.callbeforeyoudig.org.

4. Tracer wire shall be installed with all non-conductive pipes in one continuous strand.Tracer wire shall be minimum #12 AWG steel reinforced copper wire. The insulationcolor shall be green and its material shall be a minimum 30 mil composed of high densitypolyethylene (HDPE) or high molecular weight polyethylene (HMWPE). Secure the wireon the pipe with tape every 8-10 feet as needed to keep the wire straight and on top ofthe pipe. Install a green warning tape 12-18 inches above the pipe in the sameorientation to the installed pipe. See SS-260 for locator box detail and requirements.

5. Continuity testing of tracer wire is required.

6. The existing sanitary sewer system shall stay isolated from the new system viamechanical plug until the new system is cleaned, tested, video inspected and approvedfor use.

7. Sanitary sewer pipe shall be cleaned by use of high pressure nozzle and vacuum truckprior to video inspection of testing. Video inspection shall be performed in anoperational and sequential order as approved by the City Engineer. All video work shallbe completed with no piecemeal or skipping around the system. Video recordings shallbe submitted on a CD, DVD, flash drive or similar media approved and accepted by theCity. There shall be no debris in the lines or further cleaning will be required prior toacceptance.

8. All sanitary sewer pipe shall be tested for deflection. Sanitary sewer constructed offlexible pipe (e.g. thermoplastic pipe) shall be tested in accordance with 7-17 of theStandard Specifications.

9. Bellies shall not exceed 0.03 feet.

SANITARY SEWER GENERAL NOTES

SS - 000JAN 2017

C.B.

AutoCAD SHX Text
CITY ENGINEER APPROVAL:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
Longview:
AutoCAD SHX Text
STANDARD PLAN:
Page 2: SANITARY SEWER GENERAL NOTES - Official Website

Sanitary Sewer Construction Notes

Pressure testing of all sanitary sewer pipe including laterals is required in accordancewith the Standard Specifications Section 7-17.

Vacuum testing all new sanitary sewer manholes is required in accordance with ASTMDesignation C 1244-93.

As-built drawings shall be submitted and approved prior to project acceptance.

Pipe bedding shall be per standard plan SS-240.

If subgrade conditions are substandard, foundation material shall be installed to thedepth as directed by the City Engineer.

Geosynthetic materials shall meet the requirements of WSDOT Standard Specifications9-33.Geosynthetic materials shall be installed with all pipe and manholes and shall beplaced on undisturbed subgrade and below fill materials as directed by the Engineer.

All sanitary sewer laterals shall be a minimum of 6” with a minimum slope of 2% or asapproved by the Engineer. Laterals shall have a minimum cover of 36” over the top ofthe pipe within the Right of Way, or shall require ductile iron pipe and approval fromthe Engineer.

All sanitary sewer pipe which crosses water pipe shall be in accordance with StandardPlans W-290, W-295 or W-300 as applicable to the situation and approved by theEngineer.

Laterals shall be installed a minimum of five feet from the nearest manhole. No lateralconnection shall be made to manholes unless approved by the Engineer. Inserta-teesare not allowed on pipe 18 inch or less in diameter unless approved by the Engineer.

All stainless steel shall be of sufficient grade to be non-magnetic.

SANITARY SEWER GENERAL NOTES

SS - 001JAN 2017

C.B.

10.

11.

12.

13.

14.

15.

16.

17.

18.

19.

AutoCAD SHX Text
CITY ENGINEER APPROVAL:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
Longview:
AutoCAD SHX Text
STANDARD PLAN:
Page 3: SANITARY SEWER GENERAL NOTES - Official Website

NO

TE

S:

1.

PR

EC

AS

T M

AN

HO

LE

S S

HA

LL

M

EE

T T

HE

R

EQ

UIR

EM

EN

TS

O

F A

ST

M C

47

8.

JO

IN

TS

S

HA

LL

B

E N

EO

PR

EN

E O

R R

UB

BE

R G

AS

KE

TE

D C

ON

FO

RM

IN

G T

O

AS

TM

C

44

3. L

IF

T H

OL

ES

S

HA

LL

B

E G

RO

UT

ED

F

RO

M T

HE

O

UT

SID

E A

ND

IN

SID

E O

F T

HE

M

AN

HO

LE

.

2.

MA

NH

OL

ES

T

O B

E C

ON

ST

RU

CT

ED

IN

A

CC

OR

DA

NC

E W

IT

H A

AS

HT

O M

-1

99

UN

LE

SS

O

TH

ER

WIS

E S

HO

WN

O

N P

LA

NS

O

R N

OT

ED

IN

T

HE

S

TA

ND

AR

D

SP

EC

IF

IC

AT

IO

NS

.

3.

ST

EP

S IN

M

AN

HO

LE

S

HA

LL

H

AV

E 6

" M

IN

IM

UM

C

LE

AR

AN

CE

. S

EE

ST

AN

DA

RD

P

LA

N S

S - 1

40

"M

IS

CE

LL

AN

EO

US

M

AN

HO

LE

D

ET

AIL

S".

4.

AL

L R

EIN

FO

RC

ED

C

AS

T IN

P

LA

CE

C

ON

CR

ET

E S

HA

LL

B

E C

LA

SS

4

00

0.

NO

N-R

EIN

FO

RC

ED

C

ON

CR

ET

E IN

C

HA

NN

EL

A

ND

S

HE

LF

S

HA

LL

B

E C

LA

SS

30

00

. A

LL

P

RE

CA

ST

C

ON

CR

ET

E S

HA

LL

B

E C

LA

SS

4

00

0.

5.

KO

R-N

-S

EA

L A

SS

EM

BL

IE

S O

R A

PP

RO

VE

D E

QU

AL

R

EQ

UIR

ED

F

OR

A

LL

CO

NN

EC

TIO

NS

.

6.

MA

XIM

UM

H

OL

E S

IZ

E IS

3

6" F

OR

4

8" M

AN

HO

LE

. 4

2" F

OR

5

4" M

AN

HO

LE

.

MIN

IM

UM

D

IS

TA

NC

E B

ET

WE

EN

H

OL

ES

IS

8

".

7.

AL

L B

AS

E R

EIN

FO

RC

IN

G S

TE

EL

S

HA

LL

H

AV

E A

M

IN

IM

UM

Y

IE

LD

ST

RE

NG

TH

O

F 6

0,0

00

P

SI &

B

E P

LA

CE

D IN

T

HE

U

PP

ER

H

AL

F O

F T

HE

BA

SE

W

IT

H 1

" M

IN

IM

UM

C

LE

AR

AN

CE

.

8.

FO

R D

ET

AIL

S S

HO

WIN

G G

RA

DE

R

IN

GS

, L

AD

DE

R, S

TE

PS

, H

AN

DH

OL

DS

&

TO

P S

LA

BS

, S

EE

S

TA

ND

AR

D P

LA

N S

S - 1

40

"M

IS

CE

LL

AN

EO

US

M

AN

HO

LE

DE

TA

IL

S".

9.

GR

OU

T K

OR

-N

-S

EA

L B

OO

TS

F

LU

SH

T

O M

AN

HO

LE

.

10

. W

AT

ER

T

IG

HT

M

AN

HO

LE

IN

SE

RT

R

EQ

UIR

ED

, S

EE

S

TA

ND

AR

D P

LA

N

SS

-1

30

.

11

.A

LL

JO

IN

TS

T

O B

E G

RO

UT

ED

IN

SID

E M

AN

HO

LE

.

12

.A

LL

P

IP

ES

T

O B

E T

RIM

ME

D T

O A

M

AX

IM

UM

1

" P

EN

ET

RA

TIO

N IN

TO

MA

NH

OL

E.

13

.F

OU

ND

AT

IO

N M

AT

ER

IA

L T

O B

E P

LA

CE

D A

S R

EQ

UIR

ED

A

ND

A

S D

IR

EC

TE

D

BY

T

HE

E

NG

IN

EE

R.

14

. M

AN

HO

LE

C

AS

TIN

GS

T

O B

E W

SD

OT

IN

SP

EC

TE

D A

ND

A

PP

RO

VE

D.

15

. N

O S

TE

PS

A

LL

OW

ED

IN

M

AN

HO

LE

S L

ES

S T

HA

N 4

' IN

D

EP

TH

.

ST

AN

DA

RD

F

RA

ME

A

ND

C

OV

ER

SE

E S

TD

. P

LA

N S

S-0

90

, S

S-1

00

, S

S-1

20

&

S

S-1

30

AD

JU

ST

ME

NT

S

EC

TIO

N

19" MAX.

PR

EC

AS

T C

ON

E (E

CC

EN

TR

IC

UN

LE

SS

O

TH

ER

WIS

E S

PE

CIF

IE

D)

AL

L JO

IN

TS

S

HA

LL

B

E N

EO

PR

EN

E O

R

RU

BB

ER

G

AS

KE

TE

D &

B

E P

AC

KE

D

IN

SID

E &

O

UT

W

IT

H M

OR

TA

R. G

RO

UT

NO

T T

O E

XC

EE

D 1

" O

UT

SID

E O

F JO

IN

T

(A

BO

VE

&

B

EL

OW

)

HD

PE

S

TE

PS

PR

EC

AS

T R

IS

ER

S

EC

TIO

NS

SE

E N

OT

E 1

SL

OP

E =

1

2

" P

ER

F

T. (T

YP

.)

CO

NS

TR

UC

T IN

F

IE

LD

C

HA

NN

EL

AN

D S

HE

LF

12

"

CR

US

HE

D S

UR

FA

CIN

G T

OP

C

OU

RS

E 6

" M

IN

.

CO

MP

AC

TE

D D

EP

TH

, F

OR

P

RE

CA

ST

B

AS

ES

ON

LY

, 9

5%

C

OM

PA

CT

IO

N

GE

OT

EX

TIL

E

RE

IN

FO

RC

IN

G S

TE

EL

(F

OR

P

RE

CA

ST

B

AS

E &

IN

TE

GR

AL

R

IS

ER

O

NL

Y)

0.1

5 S

Q IN

/ F

T IN

E

AC

H D

IR

EC

TIO

N F

OR

4

8" D

IA

.

0.1

9 S

Q IN

/ F

T IN

E

AC

H D

IR

EC

TIO

N F

OR

5

4" D

IA

.

0.2

5 S

Q IN

/ F

T IN

E

AC

H D

IR

EC

TIO

N F

OR

6

0" D

IA

.

6"

1" M

IN

.

2

1

2

" M

AX

.

12

"

48

" D

IA

. - 6

"

54

" D

IA

. - 8

"

MAX. HEIGHT = 25'

DESIGN REQUIRED FOR MH EXCEEDING 25' HEIGHT

12

" M

AX

.

1

MO

RT

OR

FIL

L

SE

CT

IO

N R

EIN

FO

RC

IN

G S

TE

EL

(F

OR

S

EP

AR

AT

E B

AS

E O

NL

Y)

0.2

3 S

Q IN

/ F

T IN

E

AC

H D

IR

EC

TIO

N F

OR

4

8" D

IA

. (N

O. 3

B

AR

S 6

" C

/ C

)

0.1

9 S

Q IN

/ F

T IN

E

AC

H D

IR

EC

TIO

N F

OR

5

4" D

IA

. (N

O. 4

B

AR

S 1

2" C

/ C

)

0.2

5 S

Q IN

/ F

T IN

E

AC

H D

IR

EC

TIO

N F

OR

6

0" D

IA

. (N

O. 4

B

AR

S 1

2" C

/ C

)

S

EP

AR

AT

E

C

AS

T IN

P

LA

CE

B

AS

E

P

RE

CA

ST

B

AS

E

W

IT

H IN

TE

GR

AL R

IS

ER

1N

PC

F

LE

X R

IB

S

EA

L

OR

A

PP

RO

VE

D

EQ

UA

L A

LL

JO

IN

TS

16

. G

EO

TE

XT

IL

E S

HA

LL

M

EE

T T

HE

R

EQ

UIR

EM

EN

TS

O

F S

EC

TIO

N 9

-3

3 &

A

S

NO

TE

D IN

T

HE

C

IT

Y S

PE

CIA

L P

RO

VIS

IO

NS

H

ER

EIN

.

17

. G

RO

UT

IN

G S

HA

LL

B

E S

UF

FIC

IE

NT

T

O P

RE

VE

NT

L

EA

KS

B

ET

WE

EN

T

HE

PR

EC

AS

T C

OM

PO

NE

NT

S O

F T

HE

C

OM

PL

ET

ED

S

TR

UC

TU

RE

&

S

HA

LL

B

E

PE

RF

OR

ME

D IN

SID

E, B

ET

WE

EN

&

O

UT

SID

E O

F A

LL

R

IS

ER

S, JO

IN

TS

&

PIP

E P

EN

ET

RA

TIO

NS

.

MA

NH

OL

E D

IM

EN

SIO

N T

AB

LE

DIA

.

WA

LL

TH

IC

KN

ES

S

BA

SE

TH

IC

KN

ES

S

MA

XIM

UM

KN

OC

KO

UT

SIZ

E

DIS

TA

NC

E

BE

TW

EE

N

KN

OC

KO

UT

S

MIN

IM

UM

in /ft. IN

E

AC

H D

IR

EC

TIO

N

BA

SE

R

EIN

FO

RC

IN

G S

TE

EL

2

SE

PA

RA

TE

B

AS

EIN

TE

GR

AL B

AS

E

48"

4"

6"

36"

8"

0.23

0.15

54"

4.5"

8"

42"

8"

0.19

.019

72"

6"

8"

60

12"

0.35

0.24

84"

8"

12"

72"

12"

0.39

.029

60"

5"

8"

48"

8"

0.25

.025

96"

8"

12"

84"

12"

0.39

0.29

SANITARY SEWER MANHOLE

SS - 020JAN 2017

C.B.

AutoCAD SHX Text
CITY ENGINEER APPROVAL:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
Longview:
AutoCAD SHX Text
STANDARD PLAN:
Page 4: SANITARY SEWER GENERAL NOTES - Official Website

NOTES: 1. MANHOLES TO BE CONSTRUCTED IN ACCORDANCE WITH AASHTO M-199

(ASTM C 478) UNLESS OTHERWISE SHOWN ON PLANS OR NOTED IN THE

STANDARD SPECIFICATIONS.

2. HANDHOLES IN ADJUSTMENT SECTION SHALL HAVE 3' MIN. CLEARANCE.

STEPS IN MANHOLE SHALL HAVE 6" MIN. CLEARANCE. FOR DETAILS

SHOWING GRADE RINGS, LADDER, STEPS, HANDHOLDS, AND TOP SLAB

SEE STANDARD PLAN SS - 140 "MISCELLANEOUS MANHOLE DETAILS".

3. ALL REINFORCED CAST IN PLACE CONCRETE SHALL BE CLASS 4000.

NON-REINFORCED CONCRETE IN CHANNEL AND SHELF SHALL BE CLASS

3000. ALL PRECAST CONCRETE SHALL BE CLASS 4000.

4. PRECAST BASES SHALL BE FURNISHED WITH CUTOUTS OR KNOCKOUTS

WITH A WALL THICKNESS OF 2" MIN.

5. ALL BASE REINFORCING STEEL SHALL HAVE A MINIMUM YIELD STRENGTH

OF 60,000 AND BE PLACED IN THE UPPER HALF OF THE BASE WITH 1" MIN.

CLEARANCE.

6. NPC SEALS OR APPROVED EQUAL AT ALL JOINTS.

7. KOR-N-SEAL BOOTS OR APPROVED EQUAL REQUIRED FOR ALL

CONNECTIONS.

8. CHANNEL CONSTRUCTED FOR SANITARY SEWER MANHOLES ONLY.

9. FOR END OF LINE MANHOLE LOCATE FRAME AND LID OVER OUTFALL LINE.

FOR INLINE MANHOLES LOCATE FRAME AND LID OVER UPSTREAM LINE.

10. MANHOLE FRAME TO BE CENTERED OVER FLOW.

11. GROUT KOR-N-SEAL BOOTS FLUSH TO MANHOLE.

12. FOUNDATION MATERIAL TO BE PLACED AS REQUIRED AND AS DIRECTED

BY THE ENGINEER.

24"

48", 54", 60", 72", 96"

42" MIN.

SHELF

SLOPES =

1

2

" / FT.

CONSTRUCT CHANNEL

AND SHELF IN FIELD

MORTAR FILLET

MA

X. H

EIG

HT

=

6'

DE

IS

GN

R

EQ

UIR

ED

F

OR

M

AN

HO

LE

S E

XC

EE

DIN

G 6'

8"

TOP SLAB

48" DIA. - 6"

54" DIA. - 8"

72" DIA. - 8"

96" DIA. - 12"

12"

REINFORCING STEEL (FOR PRECAST BASE

WITH INTEGRAL RISER)

0.15 SQ. IN / FT IN EACH DIRECTION FOR 48" DIA.

0.19 SQ. IN / FT IN EACH DIRECTION FOR 54" DIA.

0.24 SQ. IN / FT IN EACH DIRECTION FOR 72" DIA.

0.29 SQ. IN / FT IN EACH DIRECTION FOR 96" DIA.

REINFORCING STEEL (FOR SEPARATE BASE ONLY)

0.23 SQ. IN / FT IN EACH DIRECTION FOR 48" DIA. (NO. 3 BARS 6" C / C)

0.19 SQ. IN / FT IN EACH DIRECTION FOR 54" DIA. (NO. 4 BARS 12" C / C)

0.35 SQ. IN / FT IN EACH DIRECTION FOR 72" DIA. (NO. 4 BARS 12" C / C)

0.39 SQ. IN / FT IN EACH DIRECTION FOR 96" DIA. (NO. 4 BARS 12" C / C)

"O" RING

FOR 48" & 54" DIA. - 1' - 0"

FOR 72" & 96" DIA. - 2' - 0"

PRECAST BASE WITH INTEGRAL RISER

CRUSHED SURFACING TOP COURSE 6"

MIN. COMPACTED DEPTH. FOR PRECAST

BASES ONLY. 95% COMPACTION

CONCRETE COLLAR

SEE STD. PLAN SS-090

16"

FRAME & COVER

SEE STD. PLAN SS-100

WATER TIGHT MANHOLE INSERT

SEE STD. PLAN SS-120 & SS-130

GEO-FABRIC

13. GEOTEXTILE SHALL MEET THE REQUIREMENTS OF SECTION 9-33 & AS

NOTED IN THE CITY SPECIAL PROVISIONS HEREIN.

14. GROUTING SHALL BE SUFFICIENT TO PREVENT LEAKS BETWEEN THE

PRECAST COMPONENTS OF THE COMPLETED STRUCURE & SHALL BE

PERFORMED INSIDE, BETWEEN & OUTSIDE OF ALL RISERS, JOINTS &

PIPE PENETRATIONS.

SEE NOTE 8

SEE NOTE 2

15. NPC FLEX RIB SEALS REQUIRED ON JOINTS & RISERS OR APPROVED

EQUAL.

16. POURED IN PLACE BASINS NEED CITY APPROVAL.

FLAT TOP SANITARY SEWER MANHOLE

SS - 030JAN 2017

C.B.

AutoCAD SHX Text
CITY ENGINEER APPROVAL:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
Longview:
AutoCAD SHX Text
STANDARD PLAN:
Page 5: SANITARY SEWER GENERAL NOTES - Official Website

1. CONCRETE BENCHES SHALL BE SLOPED FROM THE CROWN OF THE PIPE @ A 4% UPWARD TO THE MANHOLE

WALL.

2. ENTRIES SHALL BE KOR-N-SEAL, AS APPROVED BY THE CITY.

3. RADIUS MUST HAVE ENOUGH ROOM TO BE ABLE TO INSERT AIR PLUGS AND STANDARD TRACTOR TV

EQUIPMENT.

NOTES:

STANDARD SEWER INVERT PLANS FOR MANHOLE

NOTE 1

NOTE 3

4%

STANDARD SEWER INVERT PLANS FOR MANHOLES

SS - 060JAN 2017

C.B.

AutoCAD SHX Text
CITY ENGINEER APPROVAL:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
Longview:
AutoCAD SHX Text
STANDARD PLAN:
Page 6: SANITARY SEWER GENERAL NOTES - Official Website

MAINLINE

1

2

" ANCHOR

BOLTS (4)

2" SS STRAPS

MAXIMUM 3' C / C

MINIMUM 2 STRAPS

TYPICAL MANHOLE FOUNDATION

CONSTRUCTION AS DIRECTED

BY CITY

LINK SEAL

OR AS APPROVED

BY THE CITY

1. DROP SHALL REQUIRE A 45° BEND TO CHANNEL

FLOWS TO THE MANHOLE CHANNEL.

2. GROUT KOR-N-SEAL BOOTS FLUSH TO MANHOLE.

3. DROP SIZE TO BE SAME SIZE AS MAINLINE SEWER.

NOTES:

1

2

" ANCHOR BOLT

STAINLESS STEEL (4)

MANHOLE DIMENSION TABLE

DIA.

WALL

THICKNESS

BASE

THICKNESS

MAXIMUM

KNOCKOUT

SIZE

DISTANCE

BETWEEN

KNOCKOUTS

MINIMUM

in /ft. IN EACH DIRECTION

BASE REINFORCING STEEL

2

SEPARATE BASE INTEGRAL BASE

48" 4" 6" 36" 8" 0.23 0.15

54" 4.5" 8" 42" 8" 0.19 .019

72" 6" 8" 60 12" 0.35 0.24

84" 8" 12" 72" 12" 0.39 .029

60" 5" 8" 48" 8" 0.25 .025

96" 8" 12" 84" 12" 0.39 0.29

4. MANHOLE MINIMUM SIZE TO BE 60" OR AS

DETERMINED BY CITY ENGINEER.

5. GROUTING SHALL BE SUFFICIENT TO PREVENT

LEAKS BETWEEN THE PRECAST COMPONENTS OF

THE COMPLETED STRUCTURE & SHALL BE

PERFORMED INSIDE, BETWEEN & OUTSIDE OF ALL

RISERS, JOINTS & PIPE PENETRATIONS.

45° BEND

4" MIN

CLEARANCE

SANITARY SEWER AND STORM DROP CONNECTION

SS - 070JAN 2017

C.B.

AutoCAD SHX Text
CITY ENGINEER APPROVAL:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
Longview:
AutoCAD SHX Text
STANDARD PLAN:
Page 7: SANITARY SEWER GENERAL NOTES - Official Website

MAINLINE

DROP PIPE TO BE

SAME SIZE AS

MAINLINE SEWER

1. COMPLETE CORROSION PROTECTION MUST BE ASSURED.

2. GROUT KOR-N-SEAL BOOTS FLUSH TO MANHOLE.

NOTE:

NOTE:

TYPICAL MANHOLE FOUNDATION

CONSTRUCTION AS DIRECTED

BY CITY

CONCRETE BLOCKING

SEE TABLE FOR MIN.

BEARING AREA

D.I. 90° MJ BEND

LINK SEAL

OR APPROVED EQUAL

1

2

" ANCHOR BOLT

STAINLESS STEEL (4)

DUCTILE IRON PIPE

2" STAINLESS STEEL STRAPS

MAXIMUM 3" CC

MINIMUM 2 STRAPS

HEIGHT OF

DROP (FT.)

2.5 - 5

5.1 - 10

10.1 - 15

15.1 - 20

20.1 - 25

MAXIMUM BEARING

AREA (SF.)

1.0

2.0

2.5

3.0

4.0

3. GROUTING SHALL BE SUFFICIENT TO PREVENT LEAKS

BETWEEN THE PRECAST COMPONENTS OF THE

COMPLETED STRUCTURE & SHALL BE PERFORMED

INSIDE, BETWEEN & OUTSIDE OF ALL RISERS, JOINTS

& PIPE PENETRATIONS.

CHANNEL

AS DIRECTED

OUTSIDE DROP CONNECTION

SS - 080JAN 2017

C.B.

AutoCAD SHX Text
CITY ENGINEER APPROVAL:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
Longview:
AutoCAD SHX Text
STANDARD PLAN:
Page 8: SANITARY SEWER GENERAL NOTES - Official Website

DIR

EC

TIO

N

OF

T

RA

VE

L

1. COVER MANHOLE WITH BUILDING PAPER AND CONST. ASPHALT CONCRETE BASE COURSE AND WEARING

COURSES.

2. SAW SQUARE AROUND MANHOLE 12" MIN. FROM MANHOLE FRAME.

3. RAISE MANHOLE FRAME AND COVER TO FINISH GRADE BY INSTALLING CONCRETE RINGS AND LEVELING

MORTAR.

4. BACKFILL WITH EARLY STRENTH P.C. CONCRETE TO FINISH GRADE.

5. PROTECT FROM TRAFFIC LOADING UNTIL CONCRETE HAS CURED TO 80% OF DESIGN STRENGTH.

6. APPLY TACK COAT TO EDGES OF EXISTING PAVEMENT BEFORE INSTALLING PATCH.

7. FINISH JOINT WITH ASPHALT SEAL AND SAND.

8. MAXIMUM GRADE ADJUSTMENT IS 19" FROM CASTING TO TOP OF CONE.

NOTES:

PLAN

SECTION

#4 BAR OR HOOP

2 EACH

12" MIN.

12" MIN.

4

'

M

I

N

.

-

5

'

M

A

X

.

4

'

M

I

N

.

-

5

'

M

A

X

.

CUT LINE

MANHOLE

12" MIN.12" MIN.

NO. 4 REBAR

EXISTING AC

PAVEMENT

CUT LINE

CUT LINE

MH RING & COVER

CONCRETE COLLAR

8"

19"

9. CONCRETE SHALL BE CLASS 4000 COMMERCIAL.

DIR

EC

TIO

N

OF

T

RA

VE

L

#4 BAR

OR HOOP

2 EACH

12" MIN.

12" MIN.

6

'

M

A

X

.

6

'

M

A

X

.

CUT LINE

MANHOLE

WITH LOCATE WIRE BOX

SEWER

6" MIN.

LOCATE

WIRE

BOX

10. COLLARS ARE REQUIRED FOR ALL PAVED TRAVEL WAYS.

CONCRETE COLLAR

SS - 090JAN 2017

C.B.

AutoCAD SHX Text
CITY ENGINEER APPROVAL:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
Longview:
AutoCAD SHX Text
STANDARD PLAN:
Page 9: SANITARY SEWER GENERAL NOTES - Official Website

TOP VIEW

SECTION A-A

AA

2 7/8" MAX LIFT (4" SCREW)(SHORTER SCREWS AVAILABLE)

25"23 3/4"

8 1/2"

7"

31"

23"

DETAIL A

(4) 5 8" BY 4" JACK SCREWWITH 5 8" HEX HEAD

7" ADJUSTABLE RING

(4) 5 8" SLOT NUT INSERT

NOTES:1. CASTING ASSEMBLY TO BE H20 LOAD RATING OR AS APPROVED BY CITY ENGINEER.2. SCREWS SHALL BE ZINC-PLATED, MILD STEEL CONFORMING TO ASTM A 1018.3. NUTS SHALL BE ZINC ALLOY CONFORMING TO ASTM C41A.4. GAPS SHALL BE FILLED WITH NON-SHRINK GROUT PER THE MOST CURRENT WSDOT STD. SPECIFICATION 9-20.3(2).5. MANHOLE RING SHALL BE SHIMLESS ADJUST-TO-GRADE FOLLOWING MANUFACTURER'S REQUIREMENTS. ADJUST

SCREWS TO MEET FINISHED GRADE.6. SEE LONGVIEW STD. PLAN SS-120 FOR MANHOLE COVERS.

23" x 8 1/2" MANHOLE FRAME

SS - 100FEB 2021

K. H.

Page 10: SANITARY SEWER GENERAL NOTES - Official Website

TOP VIEW

SECTION A-A

25"

23 1/4"

24 47/64"

7/8"

31"

6"

2 1/8"

2"

3"

NOTES:1. CASTING ASSEMBLY TO BE H20 LOAD RATING OR AS APPROVED BY CITY ENGINEER.2. SCREWS SHALL BE ZINC-PLATED, MILD STEEL CONFORMING TO ASTM A 1018.3. NUTS SHALL BE ZINC ALLOY CONFORMING TO ASTM C41A.4. GAPS SHALL BE FILLED WITH NON-SHRINK GROUT PER THE MOST CURRENT WSDOT STD. SPECIFICATION 9-20.3(2).5. MANHOLE RING SHALL BE SHIMLESS ADJUST-TO-GRADE FOLLOWING MANUFACTURER'S REQUIREMENTS. ADJUST

SCREWS TO MEET FINISHED GRADE.6. SEE LONGVIEW STD. PLAN SS-120 FOR MANHOLE COVERS.7. USE OF THIS SIZE FRAME ONLY PERMISSIBLE WITH CITY ENGINEERS APPROVAL. SS-100 TO BE USED FOR NORMAL

CIRCUMSTANCES.

3" ADJUSTABLE RING

(4) 5 8" SLOT NUT INSERT

(4) 5 8" BY 4" JACK SCREWWITH 5 8" HEX HEAD

23" x 6" MANHOLE FRAME

SS - 110FEB 2021

K.H.

Page 11: SANITARY SEWER GENERAL NOTES - Official Website

MACHINE TO A TRUE

BEARING ALL AROUND

CAST IRON OR DUCTILE

W/ H20 LOAD RATING

APPROVED BY CITY ENGINEER

MANHOLES

SANITARY SEWER

BOTTOM VIEW

SECTION A-A

TOP VIEW

A

A

24

3

4

"

1"

1

1

2

"

7

8

"

1"

24 3/4" DIAMETER MANHOLE COVER

SS - 120JAN 2017

C.B.

AutoCAD SHX Text
CITY ENGINEER APPROVAL:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
Longview:
AutoCAD SHX Text
STANDARD PLAN:
Page 12: SANITARY SEWER GENERAL NOTES - Official Website

EXISTING MANHOLE

WALLS

MAN PAN SHALLOW DISH

MANHOLE INSERT

OR APPROVED EQUAL

EXISTING MANHOLE FRAME

EXISTING MANHOLE COVER

4"

WATERTIGHT MANHOLE INSERT

SS - 130JAN 2017

C.B.

AutoCAD SHX Text
CITY ENGINEER APPROVAL:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
Longview:
AutoCAD SHX Text
STANDARD PLAN:
Page 13: SANITARY SEWER GENERAL NOTES - Official Website

1. P

RO

PR

IE

TA

RY

M

AN

HO

LE

S

TE

PS

A

RE

A

CC

EP

TA

BLE

, P

RO

VID

ED

TH

AT

T

HE

Y C

ON

FO

RM

T

O S

EC

TIO

N R

. A

ST

M C

478 (A

AS

HT

O M

-199)

AN

D M

EE

T A

LL W

IS

HA

R

EQ

UIR

EM

EN

TS

.

2. M

AN

HO

LE

S

TE

P LE

GS

S

HA

LL B

E P

AR

ALLE

L O

R A

PP

RO

XIM

AT

ELY

RA

DIA

L A

T T

HE

O

PT

IO

N O

F T

HE

M

AN

UF

AC

TU

RE

R, E

XC

EP

T T

HA

T

ALL S

TE

PS

IN

A

NY

M

AN

HO

LE

S

HA

LL B

E S

IM

ILA

R. P

EN

ET

RA

TIO

N

OF

T

HE

O

UT

ER

W

ALL B

Y A

LE

G IS

P

RO

HIB

IT

ED

.

NO

TE

S:

5"

24"

5"

4"

1" C

LE

AR

AN

CE

#4 B

AR

9

1

2

"

MIN

.

12" M

IN

.

6"

12" M

IN

.

6

1

2

"

MIN

.

3"

6"

9

1

2

"

MIN

.

3

1

2

"

12" M

IN

.

#8 H

DP

E S

TE

PS

H

AN

DH

OLD

M

AN

HO

LE

S

TE

P

D

RO

P R

UN

G

G

RA

DE

R

IN

G

M

AN

HO

LE

S

TE

P

8"

24"

2" C

LR

(T

YP

.)

#4 B

AR

S @

6" C

EN

TE

RS

BO

TT

OM

F

AC

E

WIT

H 1" M

IN

. C

OV

ER

48" &

54" T

OP

S

LA

B

48"

8"

2" C

LR

(T

YP

.)

#5 B

AR

S @

6" C

EN

TE

RS

BO

TT

OM

F

AC

E

WIT

H 1" M

IN

. C

OV

ER

72" T

OP

S

LA

B

48"

12"

#6 B

AR

S @

7" C

EN

TE

RS

BO

TT

OM

F

AC

E

WIT

H 1" M

IN

. C

OV

ER

2" C

LR

(T

YP

.)

96" T

OP

S

LA

B

MISCELLANEOUS MANHOLE AND VAULT DETAILS

SS - 140JAN 2017

C.B.

AutoCAD SHX Text
CITY ENGINEER APPROVAL:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
Longview:
AutoCAD SHX Text
STANDARD PLAN:
Page 14: SANITARY SEWER GENERAL NOTES - Official Website

SID

EW

ALK

P

L

4" TO 6" SANITARY SEWER SERVICE LATERAL

45° M

AX

.

PIP

E B

ED

DIN

G

6" P

VC

T

EE

O

R

RO

MA

C S

AD

DLE

NO

S

IZ

E O

N

SIZ

E T

AP

S

AT

TA

CH

T

O S

AD

DLE

OR

T

O E

XIS

TIN

G T

RA

CE

R

WIR

E

45° M

AX

. B

EN

D

LA

TE

RA

L A

T 2%

M

IN

6" X

6" X

6" W

YE

NO

T

EE

'S

PV

C C

LE

AN

OU

T

RT

-1 C

ON

CR

ET

E

BO

X &

C

LE

AN

-O

UT

TO

B

E P

LU

MB

WA

TE

RT

IG

HT

C

AP

O

R

CO

NN

EC

TIO

N T

O

HO

US

E LA

TE

RA

L

NO

. 12 S

OF

T D

RA

WN

G

RE

EN

CO

PP

ER

W

IR

E F

OR

LO

CA

TIO

N.

(3' LO

OP

T

O R

EA

CH

A

BO

VE

FIN

IS

H G

RA

DE

) R

UN

W

IR

E

IN

SID

E O

F R

T-1 B

OX

.

6'

2'

VA

RIE

SV

AR

IE

S

3' E

XC

ES

S W

IR

E C

OILE

D IN

RT

-1 B

OX

A

S R

EQ

UIR

ED

B

Y

TH

E C

IT

Y E

NG

IN

EE

R O

R

AP

PR

OV

ED

P

LA

NS

.

36" MIN.

36" MIN.

RO

AD

P

AV

EM

EN

T S

EC

TIO

N

CR

US

HE

D S

UR

FA

CIN

G T

OP

CO

UR

SE

P

IP

E B

ED

DIN

G

CO

MP

AC

TIO

N IN

SP

EC

TIO

N

RE

QU

IR

ED

D

UR

IN

G P

LA

CE

ME

NT

BR

OO

KS

R

T-1 C

LE

AN

OU

T &

C

OV

ER

P

ER

S

TD

. P

LA

N S

S-160

CO

NC

RE

TE

C

OLLA

R P

ER

S

TD

. P

LA

N W

-280

6" S

CR

EW

C

AP

P

LU

G

W/ M

ALE

IR

ON

P

IP

E T

HR

EA

DS

W/ 2" x 2" R

AIS

ED

N

UT

PR

ES

SU

RE

T

RE

AT

ED

2x4,

PA

IN

TE

D G

RE

EN

&

E

XT

EN

DE

D

4' A

BO

VE

F

IN

IS

H G

RA

DE

, IF

HO

OK

U

P IS

N

OT

T

AK

IN

G P

LA

CE

IM

ME

DIA

TE

LY

.

IN

VE

RT

M

EA

SU

RE

D

OW

N T

O B

E

PO

ST

ED

O

N 2x4 P

OS

T.

PR

IV

AT

E

(P

LU

MB

IN

G C

OD

E)

PU

BLIC

W

OR

KS

ST

AN

DA

RD

S

BA

CK

O

F W

ALK

6" D

-3034 P

VC

45° B

EN

D

6" SANITARY SEWER SERVICE LATERAL

SS - 150MARCH 2018

C.B.

AutoCAD SHX Text
CITY ENGINEER APPROVAL:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
Longview:
AutoCAD SHX Text
STANDARD PLAN:
Page 15: SANITARY SEWER GENERAL NOTES - Official Website

SEWER

NO. RT-1 CAST IRON COVER

NO. RT-1 BODY

CAST IRON

RING WITH

LIFTING

SOCKETS

NOTES: 1. NOT INTENDED FOR USE IN TRAFFIC AREAS.

2. COVER TO BE MARKED "SEWER" FOR CLEAN OUT.

3. FOR 6" SEWER LATERAL ONLY. LARGER LATERALS SHALL USE

SS-170 OR APPROVED EQUAL.

4. 3' EXCESS TRACER WIRE COILED IN BOX AS REQUIRED BY THE CITY

ENGINEER OR APPROVED PLANS.

5. CONCRETE COLLAR PER STD. PLAN W-280.

9

5

/

8

"

3 1/4"

6

3

/

4

"

8

1

/

2

"

6"

6

3

/

4

"

7

/

8

"

8

"

SEWER CLEAN-OUT BODY & COVER

SS - 160MARCH 2018

C.B.

AutoCAD SHX Text
CITY ENGINEER APPROVAL:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
Longview:
AutoCAD SHX Text
STANDARD PLAN:
Page 16: SANITARY SEWER GENERAL NOTES - Official Website

SEWER

SEWER TO BE EMBOSSED ON LID

12

1

4

"

13

1

2

"

26" x 26" MIN.

1"

4"

20"

CONCRETE COLLAR

A CONCRETE COLLAR SHALL BE INSTALLED AROUND THE CAST IRON CLEAN OUT BOX.

COLLAR SHALL BE 26" x 26"L x 8"D.

COLLAR SHALL BE EDGED WITH

3

8

" FELT IF INSTALLED IN A CONCRETE AREA.

CONCRETE SHALL BE CLASS 4000.

3' EXCESS TRACER WIRE COILED IN BOX AS REQUIRED BY THE CITY ENGINEER OR

APPROVED PLANS.

LIFT HANDLE

OLYMPIC FOUNDRY, INC.

11" x 4" FLANGE DOWN

FRAME AND COVER PART

NO. MH5 (OR APPROVED

EQUAL)

PICK HOLE

8"

CLEAN OUT FOR 8" LINES

SS - 170MARCH 2018

C.B.

AutoCAD SHX Text
CITY ENGINEER APPROVAL:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
Longview:
AutoCAD SHX Text
STANDARD PLAN:
Page 17: SANITARY SEWER GENERAL NOTES - Official Website

SIDE SEWER PLUG DETAIL

TRENCHLESS SIDE SEWER PLUG DETAIL

ABANDON AT PROPERTY LINE/RIGHT OF WAY LINE

AND MAIN

P

L

R/W

CITY MAY ALLOW TRENCHLESS

APPLICATION UNDER CERTAIN

SITUATIONS AS SHOWN.

NOTE:

5

3

2

1

4

1 SST-316 SLEEVE

POLYETHYLENE FOAM

POLYESTER BLEND-NEEDLED FELT

SATURATED WITH EPOXY RESIN

O-RINGS

SEWER PIPE

2

3

4

5

SIDE SEWER PLUG OR SLEEVE

1

2

"

2

'

M

I

N

.

1

2

"

M

A

X

.

NONSHRINK GROUT

4" MIN. AROUND PIPE (TYP.)

MECHANICAL PLUG W/

SHOULDER TIED TO

CONCRETE

REMOVE

SECTION

EXIST. SIDE LATERAL

EXIST. SEWER MAIN

NONSHRINK GROUT

4" MIN. AROUND PIPE (TYP.)

MECHANICAL PLUG W/

SHOULDER TIED TO

CONCRETE

6" MIN.

BOTH SIDES

24" MIN. LENGTH

EXIST. SEWER MAIN

SIDE LATERAL TO

BE ABANDONED AND

SAND OR GROUT FILLED

SIDE SEWER PLUG OR SLEEVE

SS - 180JAN 2017

C.B.

AutoCAD SHX Text
CITY ENGINEER APPROVAL:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
Longview:
AutoCAD SHX Text
STANDARD PLAN:
Page 18: SANITARY SEWER GENERAL NOTES - Official Website

ABANDON AT MANHOLE

FOR SEWERS 15" AND SMALLER DIAMETER, DISCONNECT SEWERS AS SHOWN, INSERT MECHANICAL

PLUGS, AND PLACE GROUT.

FOR SEWERS 18" AND LARGER DIAMETER SAME PROCEDURE AS NOTE 1 EXCEPT MASONRY

BULKHEAD MAY BE SUBSTITUTED FOR MECHANICAL PLUG.

RESHAPE AND FILL EXISTING CHANNEL AS NECESSARY TO PROVIDE SMOOTH CONTOUR BETWEEN

INCOMING AND OUTGOING PIPES.

1.

2.

3.

NOTES:

1

8

"

2

'

M

I

N

.

1

8

"

REMOVE

SECTION

NONSHRINK GROUT

4" MIN. AROUND PIPE (TYP.)

MECHANICAL PLUG

FILL PIPE WITH GROUT

FLUSH TO INSIDE OF

MANHOLE WALL

EXIST. SEWER MAIN

EXIST. SEWER MANHOLE

REFILL & SHAPE

CHANNEL, SEE

NOTE 3

ABANDONMENT OF PIPE AT MANHOLE

SS - 190JAN 2017

C.B.

AutoCAD SHX Text
CITY ENGINEER APPROVAL:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
Longview:
AutoCAD SHX Text
STANDARD PLAN:
Page 19: SANITARY SEWER GENERAL NOTES - Official Website

FOR SEWER 15" AND SMALLER DIAMETER, SET

MECHANICAL PLUGS INTO ALL PIPES ENTERING

MANHOLES AS SHOWN. FOR SEWERS 18" AND LARGER

DIAMETER PROVIDE MASONRY BULKHEAD IN LIEU OF

MECHANICAL PLUGS

FILL MANHOLE SOLID WITH CDF.

MIX TO BE APPROVED BY CITY.

REMOVE MANHOLE TO 4'-0"

MINIMUM BELOW FINISH

GRADE. (ALL GRADE RINGS

AND TOP SECTION OF PRECAST

MANHOLE)

REMOVE MANHOLE FRAME,

COVER AND CONE AND RETURN

TO OPERATIONS BUILDING

EXISTING FINISH GRADE

NOTE:

1) ABANDONMENT BY THIS

METHOD REQUIRES CITY APPROVAL.

2) CITY MAY REQUIRE COMPLETE

REMOVAL.

COMPLETE MANHOLE ABANDONMENT

SS - 200JAN 2017

C.B.

AutoCAD SHX Text
CITY ENGINEER APPROVAL:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
Longview:
AutoCAD SHX Text
STANDARD PLAN:
Page 20: SANITARY SEWER GENERAL NOTES - Official Website

NOTES:THE METHOD OF CONNECTING NEW PVC MAIN SEWER PIPE TO

EXISTING MAIN SEWER PIPE SHOWN ON THIS DETAIL APPLIES TO

ALL SUCH CONNECTIONS REQUIRED FOR MAIN SEWER, SIDE

SEWER, AND MANHOLE REPLACEMENT WORK.

PIPE ENDS SHALL BE CUT TRUE AND FLUSH AND SHALL BUTT

TOGETHER EVENLY AND TIGHT.

IF THE EXISTING PIPE IS ALSO PVC, THE EXISTING PIPE CAN BE

BEVELED, THE NEW STUB SLID INTO THE MANHOLE SPIGOT FIRST

THEN SLID BACK ONTO THE EXISTING PIPE.

CRUSHED SURFACING TOP COURSE SHALL BE PLACED AND

COMPACTED AROUND CONNECTION TO ASSURE PIPE STAYS

TRUE AND NO SETTLEMENT OCCURES.

THIS APPLICATION MAY BE USED FOR GRAVITY SYSTEMS FOR

REPAIRS OR NEW INSTALLATIONS.

NOT FOR PRESSURE SYSTEMS.

SPLICE EXISTING TRACE WIRE AS REQUIRED.

FLO

W C

HA

NN

EL

KOR-N-SEAL BOOT

NEW MANHOLE

3' MINIMUM

FERNCO OR CITY APPROVED EQ.

TRANSITION COUPLING

EXISTING SEWER MAIN

NEW PVC PIPE

GROUT KOR-N-SEAL BOOTS

FLUSH TO MANHOLE

CONNECTION BETWEEN NEW MANHOLE & EX'ST SEWER MAIN

SS - 210JAN 2017

C.B.

AutoCAD SHX Text
CITY ENGINEER APPROVAL:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
Longview:
AutoCAD SHX Text
STANDARD PLAN:
Page 21: SANITARY SEWER GENERAL NOTES - Official Website

FERNCO OR CITY APPROVED EQUIVALENT

TRANSITION COUPLING

TYPICAL PIPE ADAPTER

NOTES:THE METHOD OF CONNECTING NEW PVC MAIN SEWER PIPE TO

EXISTING MAIN SEWER PIPE SHOWN ON THIS DETAIL APPLIES TO

ALL SUCH CONNECTIONS REQUIRED FOR MAIN SEWER, SIDE

SEWER, AND MANHOLE REPLACEMENT WORK.

PIPE ENDS SHALL BE CUT TRUE AND FLUSH AND SHALL BUTT

TOGETHER EVENLY AND TIGHT.

CRUSHED SURFACING TOP COURSE SHALL BE PLACED AND

COMPACTED AROUND CONNECTION TO ASSURE PIPE STAYS

TRUE AND NO SETTLEMENT OCCURES.

THIS APPLICATION MAY BE USED FOR GRAVITY SYSTEMS FOR

REPAIRS OR NEW INSTALLATIONS.

NOT FOR PRESSURE SYSTEMS.

SPLICE EXISTING TRACE WIRE AS REQUIRED.

TYPICAL PIPE ADAPTER/REPAIR

SS - 220JAN 2017

C.B.

AutoCAD SHX Text
CITY ENGINEER APPROVAL:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
Longview:
AutoCAD SHX Text
STANDARD PLAN:
Page 22: SANITARY SEWER GENERAL NOTES - Official Website

SANITARY SEWER TAP

BOLTS, NUTS AND WASHERS,

1

2

" UNC

ROLL THREAD TEFLON COATED.

3

1

2

" WIDE BAND FOR SPREADING OUT

CLAMP FORCE ON PIPE.

THE STAINLESS WELDS ARE FULLY

PASSIVATED.

EXCESS STRAP GOES BETWEEN PIPE

AND BAND

NOTE:

STAINLESS STEEL 304ADJUSTABLE STRAP

SANITARY SEWER SADDLECONFORMING TO PIPE

1) PIPE TO BE TAPPED USING A HOLE SAW OR APPROVED EQUAL, NO SIZE ON SIZE TAPS.

2) INSERT-A-TEES ARE NOT ALLOWED ON PIPE 18 INCH OR LESS IN DIAMETER UNLESS

APPROVED BY THE CITY.

NOTE:

EXISTING SANITARY SEWER MAIN

SEWER LATERAL

STAINLESS STEEL 304

ADJUSTABLE STRAP

SEWER SADDLE

ROMAC STYLE CB

(OR EQUAL)

SANITARY SEWER TAP

SS - 230JAN 2017

C.B.

AutoCAD SHX Text
CITY ENGINEER APPROVAL:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
Longview:
AutoCAD SHX Text
STANDARD PLAN:
Page 23: SANITARY SEWER GENERAL NOTES - Official Website

FOUNDATION MATERIAL:

DEPTH AS DIRECTED BY THE CITY

6" MIN.

6" MIN.

A APIPE O.D.

TRENCH

A = 12" FOR PIPE 24" O.D. AND SMALLER

18" FOR PIPE GREATER THAN 24" O.D.

GEOTEXTILE

PIPE ZONE

C.S.T.C. FILL

COMPACTED

TO 95% MAX.

DENSITY

PIPE ZONE

C.S.T.C. FILL

COMPACTED

TO 95% MAX.

DENSITY

SEE STANDARD PLAN ST-010

TO ST-040 FOR TRENCH BACKFILL

REQUIREMENTS ABOVE THE

PIPE ZONE

NOTES:

1. GEOTEXTILE SHALL MEET THE REQUIREMENTS OF SECTION 9-33

& AS NOTED IN THE CITY SPECIAL PROVISIONS. AS APPROVED BY THE CITY.

PIPE BEDDING

SS - 240JAN 2017

C.B.

AutoCAD SHX Text
CITY ENGINEER APPROVAL:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
Longview:
AutoCAD SHX Text
STANDARD PLAN:
Page 24: SANITARY SEWER GENERAL NOTES - Official Website

NORMAL TRENCH BOTTOM

SEWER

PIPE

PIPE O.D. + 12" ABOVE

AND BELOW PIPE

12"

MIN. WIDTH

MIN. TRENCH

MIN.

12"

12" MIN.

12" MIN.

12" MIN.

SEWER PIPE

POUR CONCRETE

AGAINST NATURAL

UNDISTURBED SOIL

4000psi CONCRETE

12" MIN.

1. COLLAR REQUIRED EVERY 50' MAX.. CITY MAY

REQUIRE ADDITIONAL COLLARS.

2. ALL PIPE TO BE RESTRAINED JOINT.

3. CONTRACTOR SHALL PROVIDE MATERIAL

SUBMITTALS ON PROPOSED PIPE RESTRAINT & PIPE

ANCHOR PRIOR TO CONSTRUCTION.

NOTES:

SEE NOTE 2

SEE STD. PLAN SS-240

FOR TRENCH WIDTH

PIPE ANCHOR

SEWER PIPE ANCHOR

SS - 250JAN 2017

C.B.

(SLOPES 15% OR MORE)

AutoCAD SHX Text
CITY ENGINEER APPROVAL:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
Longview:
AutoCAD SHX Text
STANDARD PLAN:
Page 25: SANITARY SEWER GENERAL NOTES - Official Website

CONCRETE COLLARTOP VIEW

2

4

"

x

2

4

"

M

I

N

.

DIR

EC

TIO

N

OF

T

RA

VE

L

MAIN

TRACER WIRE

CONCRETE COLLAR

24" x 24"

SNAKEPIT TRACER WIRE BOX

#31077 & GREEN IN COLOR

(OR APPROVED EQUAL)

WIRE TO COME UP INSIDE ABS RISER

SECTION TO ATTACH TO TERMINALS

ON BOTTOM OF LID

1. A CONCRETE COLLAR SHALL BE INSTALLED

AROUND THE SNAKEPIT BOX, COLLAR SHALL BE

24"W x 24"L x 8"D. COLLAR SHALL BE EDGED WITH

3

8

" FELT IF INSTALLED IN A CONCRETE AREA.

2. WIRE SHALL BE 12 GAUGE SOFT DRAWN COPPER

WITH INSULATION.

3. INSULATION COLOR SHALL BE GREEN.

4. WIRE SHALL BE ATTACHED TO PIPE EVERY 20',

WIRE SHALL BE CENTERED ON TOP OF PIPE WITH

ONE FOOT OF STACK FOR EVERY 20' OF PIPE.

5. 1500 FEET MAXIMUM SPACING FOR TRACER WIRE

BOXES ALONG MAIN. TRACER WIRE BOX SHALL BE

PLACED AT ALL MANHOLES AND MAINLINE

CLEAN-OUTS; UNLESS OTHERWISE APPROVED OR

DIRECTED BY THE CITY ENGINEER. BOXES PLACED

AT MANHOLES SHALL BE POURED IN MANHOLE

COLLAR.

NOTES:

THIS DETAIL SHALL BE USED FOR COLLARS ON SNAKE PITS, SEWER CLEAN-OUTS & WATER VALVE BOXES

LOCATOR BOX DETAIL

SS - 260MARCH 2018

C.B.

AutoCAD SHX Text
CITY ENGINEER APPROVAL:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
Longview:
AutoCAD SHX Text
STANDARD PLAN:
Page 26: SANITARY SEWER GENERAL NOTES - Official Website

MANHOLE (NOT TO SCALE) SEE

STANDARD MANHOLE DRAWING

FINISH

GRADE

1. AS DIRECTED THE POST SHALL BE LOCATED ON THE STRAIGHT SIDE OF MANHOLE

CONE.

2. POSTS SHALL BE SET IN CONCRETE.

3. POSTS SHALL BE PAINTED COLOR AS DIRECTED.

4. CARSONITE MARKERS TO BE USED AS DIRECTED BY CITY OR AS SHOWN ON PLANS.

NOTES

LOCATOR POST - FOR NON-TRAFFIC AREAS

18" MIN.

36"

12" - 18"

CONCRETE FOR POST TO BE 12"

DEEP x 12" DIA. CL 3000

5. MARKERS ARE REQUIRED ON ALL WATER/SEWER UNDERGROUND FACILITIES AT

INTERVALS DETERMINED BY THE CITY AND/OR AS SHOWN ON THE PLANS.

LOCATOR POST - FOR NON-TRAFFIC AREAS

SS - 270JAN 2017

C.B.

AutoCAD SHX Text
CITY ENGINEER APPROVAL:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
Longview:
AutoCAD SHX Text
STANDARD PLAN:
Page 27: SANITARY SEWER GENERAL NOTES - Official Website

R/W

WATER METER MAY NOT BE LOCATED WITHIN

DRIP LINE OF TREE'S, IN CONCRETE, OR IN DRIVEWAY

R/W

PL

PL

PRIVATE PROPERTY

5' WALK

PR

OP

ER

TY

L

IN

E

ST

R. L

TG

.

PW

R

T.V

.

GA

S

TE

LE

WA

TE

R

SA

N. S

EW

.

ST

OR

M

PUBLIC RIGHT OF WAY

PRIVATE PROPERTY

STREET LIGHT

36" MIN.

48" MIN.

18" MIN.

36" MIN.

* SIDEWALK WITH OR WITHOUT

PLANTER STRIP (SEE DETAIL ST - 200)

* MINIMUM BURY DEPTHS ARE FROM

GUTTER ELEVATIONS

2' BACK OF WALK (TYP.)

5'

UTILITY EASEMENT

1' MIN. SPACING

BETWEEN UTILITIES

BURY DEPTH

PER UTILITY CODE

(TYP. BOTH SIDES)

PUBLIC RIGHT OF WAY

10' MIN. 5' MIN. 5' MIN.5' CLEAR SPACE BETWEEN

EDGE OF DRIVEWAY AND

WATER METER

5' CLEAR SPACE BETWEEN

EDGE OF DRIVEWAY AND

STREET LIGHT

PL

PLPL

PL

SEWER LATERAL

CLEANOUT

WATER METER

GAS SERVICE

P.U.D., PHONE,

CABLE

TYPICAL UTILITY LOCATIONS

SS - 300JAN 2017

C.B.

AutoCAD SHX Text
CITY ENGINEER APPROVAL:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
Longview:
AutoCAD SHX Text
STANDARD PLAN: