Alberta Infrastructure School Facilities Branch School Facility Evaluation Project Part II - Physical Condition School: Publique Gabrielle - Roy Date: Dec. 1, 1999 School Name: Ecole Publique Gabrielle Roy School Code: 8002 (SCHOOL SHARED WITH Location: Edmonton Facility Code: 2352 PERE LACOMBE) Region: Central Superintendent: Mr. Henri Lemire Jurisdiction: Greater North Central Contact Person: Robert Nantel Francophone Education Telephone: (780) 468-6440 Region No. 2 Grades: K - 6 School Capacity: 100 Year of Compl. No. of Floors Gross Bldg Area (Sq.M.) Type of Construction (i.e., structure, roof, cladding) Description of Mechanical Systems (incl. major upgrades) Comments/Notes 1962 2+ Base- ment See Pere Lacombe Concrete slab on grade, concrete block walls. Assumed wood roof. Not sprinklered Consists of Hot Water Heating system and ventilation system. The ventilation system consists of Classroom unit ventilators served by hot water coil and no glycol system. Gymnasium is served by one (1) indoor, air handling unit, which is in very poor condition. This school building is shared with Pere Lacombe. The ventilation system can not meet the present code requirements, and will have to be replaced. A new ventilation system with glycol system, must be introduced, to allow for the air handling units to supply sufficient amount of outside air to each 1964 1 680 M 2 Concrete slab on grade, concrete block walls. Assumed wood roof. Not sprinklered Each classroom is heated and ventilated by unit ventilators complete with hot water coil (no glycol). Therefore, each unit ventilator cannot provide sufficient outside air during winter. Each unit ventilator is at the end of its life expectancy and in very poor condition. All of which creates Health and Safety concern. The system serving the entire school has to be replaced with a new hot water heating and ventilation system capable to meet present codes. The Mechanical System is in poor condition and can not provided minimum fresh air recommended by the present codes. The air handling unit serving the Gymnasium is corroded, has exceeded its life expectancy and cannot provide outside air required by codes. The hot water piping system is corroded and must be replaced. Evaluator's Name: John Murray & Company: John Murray Architectural Associates Building Section Original Building Additions/ Expansions Condition Ratings: 1-Emergency/Critical 2-Poor/Unsatisfactory 3-Marginal 4-Good 5-Excellent F.I.-Further investigation required 1

School Facility Audits - Alberta · Classroom unit ventilators served by hot water coil and no glycol system. Gymnasium is served by ... School Facility Evaluation Project Part II

Embed Size (px)

Citation preview

Page 1: School Facility Audits - Alberta · Classroom unit ventilators served by hot water coil and no glycol system. Gymnasium is served by ... School Facility Evaluation Project Part II

Alberta InfrastructureSchool Facilities Branch

School Facility Evaluation ProjectPart II - Physical Condition

School: Publique Gabrielle - RoyDate: Dec. 1, 1999

School Name: Ecole Publique Gabrielle Roy School Code: 8002 (SCHOOL SHARED WITH Location: Edmonton Facility Code: 2352 PERE LACOMBE)

Region: Central Superintendent: Mr. Henri LemireJurisdiction: Greater North Central Contact Person: Robert Nantel

Francophone Education Telephone: (780) 468-6440Region No. 2

Grades: K - 6 School Capacity: 100

Year of Compl.

No. of Floors

Gross Bldg Area (Sq.M.)

Type of Construction (i.e., structure, roof, cladding)

Description of Mechanical Systems (incl. major upgrades) Comments/Notes

1962 2+Base-ment

See Pere Lacombe

Concrete slab on grade, concrete block walls. Assumed wood roof.Not sprinklered

Consists of Hot Water Heating system and ventilation system. The ventilation system consists of Classroom unit ventilators served by hot water coil and no glycol system. Gymnasium is served by one (1) indoor, air handling unit, which is in very poor condition.

This school building is shared with Pere Lacombe. The ventilation system can not meet the present code requirements, and will have to be replaced. A new ventilation system with glycol system, must be introduced, to allow for the air handling units to supply sufficient amount of outside air to each

1964 1 680 M2 Concrete slab on grade, concrete block walls. Assumed wood roof.Not sprinklered

Each classroom is heated and ventilated by unit ventilators complete with hot water coil (no glycol). Therefore, each unit ventilator cannot provide sufficient outside air during winter. Each unit ventilator is at the end of its life expectancy and in very poor condition. All of which creates Health and Safety concern. The system serving the entire school has to be replaced with a new hot water heating and ventilation system capable to meet present codes.

The Mechanical System is in poor condition and can not provided minimum fresh air recommended by the present codes. The air handling unit serving the Gymnasium is corroded, has exceeded its life expectancy and cannot provide outside air required by codes. The hot water piping system is corroded and must be replaced.

Evaluator's Name: John Murray& Company: John Murray Architectural Associates

Building SectionOriginal Building

Additions/ Expansions

Condition Ratings: 1-Emergency/Critical 2-Poor/Unsatisfactory 3-Marginal 4-Good 5-Excellent F.I.-Further investigation required 1

Page 2: School Facility Audits - Alberta · Classroom unit ventilators served by hot water coil and no glycol system. Gymnasium is served by ... School Facility Evaluation Project Part II

Alberta InfrastructureSchool Facilities Branch

School Facility Evaluation ProjectPart II - Physical Condition

School: Publique Gabrielle - RoyDate: Dec. 1, 1999

Nil

Nil

No reports available.

List of Reports/ Supplementary Information

Portable Struct. (identify whether attached/perman. or free-standing/ relocatable)

Upgrading/ Modernization (identify whether minor or major)

Condition Ratings: 1-Emergency/Critical 2-Poor/Unsatisfactory 3-Marginal 4-Good 5-Excellent F.I.-Further investigation required 2

Page 3: School Facility Audits - Alberta · Classroom unit ventilators served by hot water coil and no glycol system. Gymnasium is served by ... School Facility Evaluation Project Part II

Alberta InfrastructureSchool Facilities Branch

School Facility Evaluation ProjectPart II - Physical Condition

School: Publique Gabrielle - RoyDate: Dec. 1, 1999

Evaluation Components Summary Assessment Estim. Cost

1 Site Conditions Site drainage from the school is poor. Slab movements, pedestrian access from parking is remote. 31,000

2 Building Exterior New re-roof and insulaton is required. Some stucco replacement is required. Doors and windows need replacement.Site drainage from the school is poor. Slab movements, pedestrian access from parking is remote.

130,000

3 Building Interior Floors need new finishes - combustible tile in ceiling needs replacement.Doors not to code - Administration is small and a long way from the main entry.

75,500

4 Mechanical Systems The existing Mechanical System consists of a hot water heating system using the perimeter radiation system for general office area, and unit ventilators for classroom application. The gymnasium is heated and ventilated by an air handling unit and cannot meet present ventilation code requirements. Therefore, this system will have to be replaced with a new hot water heating and ventilation code requirements.

Included under Pere Lacombe

493,000

5 Electrical Systems Upgrade telephone and P.A. New fire alarm panel, change lights and increase classroom receptacles.

49,000.00

6 Portable Buildings Nil

7 Space Adequacy: This school shares facilities with Pere Lacombe.

7.1 Classrooms Adequate

7.2 Science Rooms/Labs Adequate

7.3 Ancillary Areas Adequate

7.4 Gymnasium Adequate, shared space.

7.5 Library/Resource Areas Adequate, shared space.

7.6 Administration/Staff Areas Small, needs enlargement 180M2 and relocation near an entry.

7.7 CTS Areas

7.8 Other Non-Instructional Areas (incl. gross-up)

Hard to separate this school from Ecole Pere lacombe because of shared functions.. Some F.I. needed.

See item 4. Does not include mechanical upgrade costs. 285,500Overall School Conditions & Estim. Costs

Condition Ratings: 1-Emergency/Critical 2-Poor/Unsatisfactory 3-Marginal 4-Good 5-Excellent F.I.-Further investigation required 3

Page 4: School Facility Audits - Alberta · Classroom unit ventilators served by hot water coil and no glycol system. Gymnasium is served by ... School Facility Evaluation Project Part II

Alberta InfrastructureSchool Facilities Branch

School Facility Evaluation ProjectPart II - Physical Condition

School: Publique Gabrielle - RoyDate: Dec. 1, 1999

Section 1 Site Conditions Rating Comments/Concerns Estim. Cost

1.1 General Site Condions

1.1.1 Overall site size.

4 Adequate for School size.

_

1.1.2 Outdoor athletic areas.

4Grassed playing fields and hard surface area - one main soccer, two small soccer, three basketball play hoops, two baseball diamonds. Shared

_

1.1.3 Outdoor playground areas, including condition of equipment and base.

4 One playground activity area. Shared.

_

1.1.4 Site landscaping.

4 Some mature trees and lawn is acceptable. See photo # 1.

_

1.1.5 Site accessories (i.e., perimeter and other fencing, guard rails, bike stands, flag poles).

4 Chain link perimeter fence.

_

1.1.6 Surface drainage conditions (i.e., drains away from building, signs of ponding).

3 Surface drainage poor, particularly at building. Needs site re-grade.

4,000

1.1.7 Evidence of sub-soil problems.

3 Slab movement to walks - lots of mud jacking in recent years.

2,000

1.1.8 Safety and security concerns due to site conditions.

4 Appears acceptable.

_

Other

Condition Ratings: 1-Emergency/Critical 2-Poor/Unsatisfactory 3-Marginal 4-Good 5-Excellent F.I.-Further investigation required 4

Page 5: School Facility Audits - Alberta · Classroom unit ventilators served by hot water coil and no glycol system. Gymnasium is served by ... School Facility Evaluation Project Part II

Alberta InfrastructureSchool Facilities Branch

School Facility Evaluation ProjectPart II - Physical Condition

School: Publique Gabrielle - RoyDate: Dec. 1, 1999

Section 1 Site Conditions Rating Comments/Concerns Estim. Cost

1.2 Access/Drop-Off Areas/Roadways/Bus Lanes

1.2.1 Vehicular and pedestrian access points (i.e., size, number, visibility, safety).

3Bus student access good. Signage hidden by trees. Parking has good entry and exit separation.Pedestrian access from parking remote without changing main entry location this is difficult to solve. Complete detailed design study.

10,000

1.2.2 Surfacing of on-site road network (note whether asphalt or gravel).

3 Gravel parking - 25 stalls - no curbs. No handicap stall designated. Shared.

10,000

1.2.3 Bus lanes/drop-off areas (note whether on-site or off-site).

4 Off site on 131st Avenue - 6 buses. Serves both schools

_

1.2.4 Fire vehicle access.

4 Good fire fighting accessibility.

_

1.2.5 Signage.

3 No sign for this school.

2,000

Other

Condition Ratings: 1-Emergency/Critical 2-Poor/Unsatisfactory 3-Marginal 4-Good 5-Excellent F.I.-Further investigation required 5

Page 6: School Facility Audits - Alberta · Classroom unit ventilators served by hot water coil and no glycol system. Gymnasium is served by ... School Facility Evaluation Project Part II

Alberta InfrastructureSchool Facilities Branch

School Facility Evaluation ProjectPart II - Physical Condition

School: Publique Gabrielle - RoyDate: Dec. 1, 1999

Section 1 Site Conditions Rating Comments/Concerns Estim. Cost

1.3 Parking Lots and Sidewalks

1.3.1 Number of parking spaces for staff, students and visitors (including stalls for disabled persons).

2 Parking for 25 cars - No handicap stall.

Included in Section 1.2.2.

1.3.2 Layout and safety of parking lots.

4 Entry and exit from parking good - double banked stalls.

_

1.3.3 Surfacing and drainage of parking lots (note whether asphalt or gravel).

3 Gravel lot, no curbs - grading seems acceptable.

See 1.2.2.

1.3.4 Layout and safety of sidewalks.

3 Poor from parking.

See 1.3.5.

1.3.5 Surfacing and drainage of sidewalks (note type of material).

3Concrete walks - some cracking, some movement. This has prevented door opening. Lots of mud jacking done in 1999.

3,000

1.3.6 Curb cuts and ramps for barrier free access.

2 No handicapped easy access - parking a little remote from entry.

See 1.2.2.

Other

Overall Site Conditions & Estimated Costs31,000

Condition Ratings: 1-Emergency/Critical 2-Poor/Unsatisfactory 3-Marginal 4-Good 5-Excellent F.I.-Further investigation required 6

Page 7: School Facility Audits - Alberta · Classroom unit ventilators served by hot water coil and no glycol system. Gymnasium is served by ... School Facility Evaluation Project Part II

Alberta InfrastructureSchool Facilities Branch

School Facility Evaluation ProjectPart II - Physical Condition

School: Publique Gabrielle - RoyDate: Dec. 1, 1999

Section 2 Building Exterior Rating Estim. Cost

2.1 Overall Structure Bldg. Section Description/Condition

2.1.1 Floor structure and beams (i.e., signs of bending, cracking, heaving, settlement, voids, rust, stains).

4 1964 Appears acceptable. Concrete slab on grade.

_

2.1.2 Wall structure and columns (i.e., signs of bending, cracking, settlement, voids, rust, stains).

4 1964 Appears acceptable.Masonry.

_

2.1.3 Roof structure (i.e., signs of bending, cracking, voids, rust, stains).

4 1964 Appears acceptable.Wood frame assumed.

_

Other

Comments/Concerns

Condition Ratings: 1-Emergency/Critical 2-Poor/Unsatisfactory 3-Marginal 4-Good 5-Excellent F.I.-Further investigation required 7

Page 8: School Facility Audits - Alberta · Classroom unit ventilators served by hot water coil and no glycol system. Gymnasium is served by ... School Facility Evaluation Project Part II

Alberta InfrastructureSchool Facilities Branch

School Facility Evaluation ProjectPart II - Physical Condition

School: Publique Gabrielle - RoyDate: Dec. 1, 1999

Section 2 Building Exterior Rating Estim. CostComments/Concerns

2.2 Roofing and Skylights Identify the availability of an up-to-date inspection report or roofing program. Note if roof sections are of different ages and/or in varying states of repair.

Bldg. Section or Roof Section Description/Condition/Age

2.2.1 Based on the inspection report (and to the extent possible, direct observation), assess and rate roof conditions and estimate costs for required improvements (i.e., covering materials, membrane, insulation, other components).

2 1964 Felt and gravel built up asphalt roof - flat. New torch-on roofing and sloped insulation required with V.B.

(700 M2).Some of this area is shared with Ecole Pere Lacombe.

Lots of leaks.

60,000

2.2.2 Roof accessories (i.e., ladders, stairs, hatches, masts, exhaust hoods, chimneys, gutters, downspouts, splashpads).

4 1964 Rain water leaders intenal discharge to concrete splash pad. _

2.2.3 Control of ice and snow falling from roof. 4 1964 Not a problem - flat roof. _

2.2.4 Skylights (i.e., signs of distress, leaks, ice build-up, condensation, deteriorated materials/seals).

Nil _

Other

Condition Ratings: 1-Emergency/Critical 2-Poor/Unsatisfactory 3-Marginal 4-Good 5-Excellent F.I.-Further investigation required 8

Page 9: School Facility Audits - Alberta · Classroom unit ventilators served by hot water coil and no glycol system. Gymnasium is served by ... School Facility Evaluation Project Part II

Alberta InfrastructureSchool Facilities Branch

School Facility Evaluation ProjectPart II - Physical Condition

School: Publique Gabrielle - RoyDate: Dec. 1, 1999

Section 2 Building Exterior Rating Estim. CostComments/Concerns

2.3 Exterior Walls/Building Envelope Bldg. Section Description/Condition

2.3.1 Exterior wall finishes (i.e., signs of deterioration, cracks, brick spalling, effluorescence, water stains).

2 1964 Painted concrete block, needs some repair and repaint or insulation and stucco, panels under windows need replacement.

45,000

2.3.2 Fascias, soffits, parapets (i.e., signs of looseness, stains, rust, peeling paint).

3 1964 Paint peeling - needs re-painting. 3,000

2.3.3 Building envelope (i.e., evidence of air infiltration/ exfiltration through the exterior wall or ice build up on wall, eaves, canopy).

2 1964 Fascia stucco - replaced under 2.3.1. See 2.3.1.

2.3.4 Interface of roof drainage and ground drainage systems.

F.I. 1964 Should be reviewed during re-roofing. See 2.2.1

2.3.5 Inside faces of exterior walls (i.e., signs of cracks, water stains, dust spots).

4 1964 Appears acceptable. _

Other

Condition Ratings: 1-Emergency/Critical 2-Poor/Unsatisfactory 3-Marginal 4-Good 5-Excellent F.I.-Further investigation required 9

Page 10: School Facility Audits - Alberta · Classroom unit ventilators served by hot water coil and no glycol system. Gymnasium is served by ... School Facility Evaluation Project Part II

Alberta InfrastructureSchool Facilities Branch

School Facility Evaluation ProjectPart II - Physical Condition

School: Publique Gabrielle - RoyDate: Dec. 1, 1999

Section 2 Building Exterior Rating Estim. CostComments/Concerns

2.4 Exterior Doors and Windows Bldg. Section Description/Condition

2.4.1 Doors (i.e., signs of deterioration, rusting metal, glass cracks, peeling paint, damaged seals, sealed unit failure).

4 1964 Steel doors and frames acceptable. _

2.4.2 Door accessories (i.e., latches, hardware, screens, locks, alarms, holders, closers, security devices).

3 1964 Some hardward is in poor condition. 2,000

2.4.3 Exit door hardware (i.e., safety and/or code concerns). 3 1964 Some hardware in poor condition. Included in Section 2.4.2.

2.4.4 Windows (i.e., signs of deterioration, rusting metal, glass cracks, peeling paint, damaged seals, sealed unit failure).

3 1964 Windows of poor quality - prefinished metal, some all fixed, some with horizontal sliders.Some windows have mesh protection. Replace all windows.

20,000

2.4.5 Window accessories (i.e., latches, hardware, screens, locks, alarms, holders, closers, security devices).

3 1964 Poor quality. See 2.4.4.

2.4.6 Building envelope (i.e., signs of heavy condensation on doors or windows).

4 1964 Not apparent. _

Other

Overall Bldg Exterior Condition & Estim Costs 130,000

Condition Ratings: 1-Emergency/Critical 2-Poor/Unsatisfactory 3-Marginal 4-Good 5-Excellent F.I.-Further investigation required 10

Page 11: School Facility Audits - Alberta · Classroom unit ventilators served by hot water coil and no glycol system. Gymnasium is served by ... School Facility Evaluation Project Part II

Alberta InfrastructureSchool Facilities Branch

School Facility Evaluation ProjectPart II - Physical Condition

School: Publique Gabrielle - RoyDate: Dec. 1, 1999

Section 3 Building Interior - Overall Conditions Rating Estim. Cost

3.1 Interior Structure Bldg. Section Description/Condition

3.1.1 Interior walls and partitions (i.e., signs of cracks, spalling, paint peeling).

4 1964 No apparent cracks.

_

3.1.2 Floors (i.e., signs of cracks, heaving, settlement).

4 1964Some mud jacking carried out.Seems acceptable.

_

Other

3.2 Materials and Finishes Description/Condition

3.2.1 Floor materials and finishes. 1 1964 9x9 Vinyl asbestos tile some carpet to administration. Poor - needs replacement. 12,000

3.2.2 Wall materials and finishes. 1 1964 Appears acceptable except lockers are needed in corridor. 14,000

3.2.3 Ceiling materials and finishes. 1 1964 12 x 12 fibreboard tile probably above 'T' - bar. 'T' bar is poor. 8,000

Comments/Concerns

Condition Ratings: 1-Emergency/Critical 2-Poor/Unsatisfactory 3-Marginal 4-Good 5-Excellent F.I.-Further investigation required 11

Page 12: School Facility Audits - Alberta · Classroom unit ventilators served by hot water coil and no glycol system. Gymnasium is served by ... School Facility Evaluation Project Part II

Alberta InfrastructureSchool Facilities Branch

School Facility Evaluation ProjectPart II - Physical Condition

School: Publique Gabrielle - RoyDate: Dec. 1, 1999

Section 3 Building Interior - Overall Conditions Rating Estim. CostComments/Concerns

3.2 Materials and Finishes (cont'd) Bldg. Section Description/Condition

3.2.4 Interior doors and hardware. 2 1964 Natural birch wood, metal frames, door fixed panels over do not provide a 20 minute rating. Needs replacement.

Replace doors and frames to corridors including hardware

8,000

3.2.5 Millwork 3 1964 Inadequate to classrooms. See photo # 3 and shared computer lab and library with Ecole Pere Lacombe photo # 9.

11,500

3.2.6 Fixed/wall mounted equipment (i.e., writing boards, tackboards, display boards, signs).

3 1964 Some additional tack boards needed. Chalk board seems acceptable.

2,000

3.2.7 Any other fixed/mounted specialty items (i.e., CTS equipment, gymnasium equipment).

N/A 1964 Gymnasium shared with Pere Lacombe. _

3.2.8 Washroom materials and finishes. N/A 1964 Washroom shared with Pere Lacombe. _

Other _

Condition Ratings: 1-Emergency/Critical 2-Poor/Unsatisfactory 3-Marginal 4-Good 5-Excellent F.I.-Further investigation required 12

Page 13: School Facility Audits - Alberta · Classroom unit ventilators served by hot water coil and no glycol system. Gymnasium is served by ... School Facility Evaluation Project Part II

Alberta InfrastructureSchool Facilities Branch

School Facility Evaluation ProjectPart II - Physical Condition

School: Publique Gabrielle - RoyDate: Dec. 1, 1999

Section 3 Building Interior - Overall Conditions Rating Estim. CostComments/Concerns

3.3 Bldg. Section Description/Condition

1 1964 Inflammable ceiling tile. See 3.2.3

3.3.1 Building construction type - combustible or non-combustible, sprinklered or non-sprinklered.

4 1964 Non-combustible except for roof assumed as wood.Unsprinklered.

_

3.3.2 Fire separations (i.e., between buildings, wings, zones if non-sprinklered).

3 1964 Hard to evaluate what separation is required between 2 schools when many areas are shared.Complete detailed code review.

5,000

3.3.3 Fire resistance rating of materials (i.e., corridor walls and doors).

1 1964 Coats in corridors need to be in lockers.Inflammable ceiling tile.

See photo # 2.

Covered under 3.2.2.

3.3.4 Exiting distances and access to exits. 4 1964 Appears acceptable.

3.3.5 Barrier-free access. 2 1964 If this school considers separate access entry point, then assist door is needed. 5,000

3.3.6 Availability of hazardous materials audit (i.e., evidence of safety concerns with respect to asbestos, PCB's, chemicals).

1964

REPORTS NOT AVAILABLE: An audit should be carried out.

10,000

3.3.7 Other health and safety concerns (i.e., evidence of excessive noise conditions, air quality problems)

4 1964 This section of the school has no lavatories, but it is assumed sharing with Pere Lacombe, acceptable.

Other

Overall Bldg Interior Condition & Estim Costs 75,500

Health and Safety Concerns --- Intent is to identify renovations considered necessary to meet applicable codes, primarily due to safety concerns. Basis of evaluation should be an up-to-date inspection report from the authority having jurisdiction together with direct observations as appropriate. Evaluator should note if in his opinion a comprehensive code evaluation is required.

Condition Ratings: 1-Emergency/Critical 2-Poor/Unsatisfactory 3-Marginal 4-Good 5-Excellent F.I.-Further investigation required 13

Page 14: School Facility Audits - Alberta · Classroom unit ventilators served by hot water coil and no glycol system. Gymnasium is served by ... School Facility Evaluation Project Part II

Alberta InfrastructureSchool Facilities Branch

School Facility Evaluation ProjectPart II - Physical Condition

School: Publique Gabrielle - RoyDate: Dec. 1, 1999

Section 4 Mechanical Systems Rating Estim. Cost

4.1 Mechanical Site Services

4.1.1 Site drainage systems (i.e., surface and underground systems, catch basins).

5The site drainage system is a surface type system and is in good condition. No water accumulation was identified around the building

4.1.2 Exterior plumbing systems (i.e., irrigation systems, hose bibs).

5 An irrigation system does not exist. The NFHB are in fair condition.

4.1.3 Outside storage tanks.

N/A None

Other

4.2 Fire Suppression Systems Bldg. Section Description/Condition

4.2.1 Fire hydrants and siamese connections.

None

4.2.2 Fire suppression systems (i.e., pumps, sprinklers, piping, reservoirs, hoses, stand pipes, CO2 systems).

None

4.2.3 Hand extinguishers, blankets and showers (i.e., in CTS areas).

4all

sectionsFire extinguishers are in fair condition.

4.2.4 Other special situations (e.g., flammable storage areas, science labs, CTS areas).

None

Other

Comments/Concerns

Condition Ratings: 1-Emergency/Critical 2-Poor/Unsatisfactory 3-Marginal 4-Good 5-Excellent F.I.-Further investigation required 14

Page 15: School Facility Audits - Alberta · Classroom unit ventilators served by hot water coil and no glycol system. Gymnasium is served by ... School Facility Evaluation Project Part II

Alberta InfrastructureSchool Facilities Branch

School Facility Evaluation ProjectPart II - Physical Condition

School: Publique Gabrielle - RoyDate: Dec. 1, 1999

Section 4 Mechanical Systems Rating Estim. CostComments/Concerns

4.3 Water Supply and Plumbing Systems Bldg. Section Description/Condition

4.3.1 Domestic water supply (i.e., pressure, volume, quality - note whether municipal or well supply).

4All

sections

Domestic water supply is from the water main in the street (municipal water supply ). There is no problem with water pressure, volume and water quality.

4.3.2 Water treatment system(s).

4All

sectionsIs in fair condition

4.3.3 Pumps and valves (including backflow prevention valves).

4All

sectionsAre in fair condition

4.3.4 Piping and fittings.

4All

sectionsAre in fair condition

4.3.5 Plumbing fixtures (i.e., toilets, urinals, sinks)

4All

sectionsAre in fair condition.

4.3.6 Domestic hot water system (i.e., heater, storage tanks, failure alarms, pressure, volume, recirculation).

4All

sectionsAre in fair condition

4.3.7 Sanitary and storm sewers, including sumps and pits (note whether sewage system is municipal or septic).

4All

sectionsThe sanitary sewer system including sumps and pits is municipal type of system and is in fair condition. Storm system inside of the building is also in fair condition.

Other

Condition Ratings: 1-Emergency/Critical 2-Poor/Unsatisfactory 3-Marginal 4-Good 5-Excellent F.I.-Further investigation required 15

Page 16: School Facility Audits - Alberta · Classroom unit ventilators served by hot water coil and no glycol system. Gymnasium is served by ... School Facility Evaluation Project Part II

Alberta InfrastructureSchool Facilities Branch

School Facility Evaluation ProjectPart II - Physical Condition

School: Publique Gabrielle - RoyDate: Dec. 1, 1999

Section 4 Mechanical Systems Rating Estim. CostComments/Concerns

4.4 Heating Systems Bldg. Section Description/Condition

4.4.1 Heating capacity and reliability (including backup capacity).

2All

sections

The existing hot water heating system is in poor condition. The boiler plant consists of one (1) gas fired original Peerless boiler, which is at the end of its life expectancy and is obsolete. The piping system is

corroded, and leaks are visible in some places. Pumps are obsolete and corroded. A new boiler plant is recommended.

See Pere Lacombe

4.4.2 Heating controls (including use of current energy management technology.

2All

sectionsThe existing mechanical system is not using current energy management technology. A new DDC

control system is recommended.See Pere Lacombe

4.4.3 Fresh air for combustion and condition of the combustion chimney.

5All

sectionsThe existing combustion air is sufficient and chimney is in good condition.

4.4.4 Treatment of water used in heating systems.

2All

sectionsIs in poor condition. A new treatment is required.

See Pere Lacombe

4.4.5 Low water cutoff/pressure relief valves and failure alarms (i.e., hot water heating).

4 1962 Are in fair condition.

4.4.6 Heating air filtration systems and filters.

4All

sectionsAre in fair condition

4.4.7 Heating humidification systems and components.

2All

sectionsHumidification system does not exist. New humidification is recommended.

See Pere Lacombe

Condition Ratings: 1-Emergency/Critical 2-Poor/Unsatisfactory 3-Marginal 4-Good 5-Excellent F.I.-Further investigation required 16

Page 17: School Facility Audits - Alberta · Classroom unit ventilators served by hot water coil and no glycol system. Gymnasium is served by ... School Facility Evaluation Project Part II

Alberta InfrastructureSchool Facilities Branch

School Facility Evaluation ProjectPart II - Physical Condition

School: Publique Gabrielle - RoyDate: Dec. 1, 1999

Section 4 Mechanical Systems Rating Estim. CostComments/Concerns

4.4 Heating Systems (cont'd) Bldg. Section Description/Condition

4.4.8 Heating distribution systems (i.e., piping, ductwork) and associated components (i.e., diffusers, radiators).

2All

sections

The existing supply air and return hot water piping are corroded and need to be replaced. The new heating distribution system is required. However, a glycol system has to be applied to allow for more outside air to be introduced to each classroom. New ductwork is required in the Gymnasium to allow for proper air change.

See Pere Lacombe

4.4.9 Heating piping, valve and/or duct insulation.

2All

sectionsThe thermal insulation is in poor condition. New insulation is required.

See Pere Lacombe

4.4.10 Heat exchangers.

3All

sectionsWill be part ofproposed new Mechanical System

4.4.11 Heating mixing boxes, dampers and linkages.

3All

sections Will be part of proposed new Mechanical System.

4.4.12 Heating distribution/circulation in larger spaces (i.e., user comfort, temperature of outside wall surfaces).

3 1962 The Gymnasium will require a new perimeter radiation and ductwork system.See Pere Lacombe

4.4.13 Zone/unit heaters and controls.

5All

sectionsAre in good condition

Other

Condition Ratings: 1-Emergency/Critical 2-Poor/Unsatisfactory 3-Marginal 4-Good 5-Excellent F.I.-Further investigation required 17

Page 18: School Facility Audits - Alberta · Classroom unit ventilators served by hot water coil and no glycol system. Gymnasium is served by ... School Facility Evaluation Project Part II

Alberta InfrastructureSchool Facilities Branch

School Facility Evaluation ProjectPart II - Physical Condition

School: Publique Gabrielle - RoyDate: Dec. 1, 1999

Section 4 Mechanical Systems Rating Estim. CostComments/Concerns

4.5 Ventilation Systems Bldg. Section Description/Condition

4.5.1 Air handling units capacity and condition.

2all

sections

The existing air handling system consists of one (1) centrally located Trane air handling unit serving the Gymnasium. Each Classroom is served by a unit ventilator with hot water coil. The capacity and condition of unit ventilators are not sufficient to meet the present ventilation code requirements. The air handling unit serving the Gymnasium is in very poor condition, is obsolete, cannot provide minimum air change/hour, and must be replaced. Therefore, a new air handling system is required.

See Pere Lacombe

4.5.2 Outside air for the occupant load (if possible, reference CFM/occupant).

2All

sectionsAre not sufficient at the present time. It is recommended to introduce a glycol system and install new

ventilation system capable of providing outside air min. 15 CFM/occupant.See Pere Lacombe

4.5.3 Air distribution system (if possible, reference number of air changes/hour).

3All

sections

The existing air handling unit serving the Gymnasium is estimated to provide only two (2) air change/hour. It is recommended to replace this unit with, a properly sized, new unit, able to provide min. four (4) air changes/hour, and sufficient amount of outside air for the occupants. Also, it is recommended

to provide two (2) speed fans in the new air handling unit, serving the Gymnasium.

4.5.4 Exhaust systems capacity and condition.

2All

sectionsA new washroom exhust system will be require.

See Pere Lacombe

4.5.5 Separation of out flow from air intakes.

4All

sectionsIt is acceptable

4.5.6 Special/dedicated ventilation and/or exhaust systems (i.e., kitchen, labs, CTS areas).

5All

sectionsAre fine

Other

Condition Ratings: 1-Emergency/Critical 2-Poor/Unsatisfactory 3-Marginal 4-Good 5-Excellent F.I.-Further investigation required 18

Page 19: School Facility Audits - Alberta · Classroom unit ventilators served by hot water coil and no glycol system. Gymnasium is served by ... School Facility Evaluation Project Part II

Alberta InfrastructureSchool Facilities Branch

School Facility Evaluation ProjectPart II - Physical Condition

School: Publique Gabrielle - RoyDate: Dec. 1, 1999

Section 4 Mechanical Systems Rating Estim. CostComments/Concerns

4.5 Ventilation Systems (cont'd) Bldg. Section Description/Condition

Note: Only complete the following items if there are separate ventilation and heating systems.

4.5.7 Ventilation controls (including use of current energy management technology).

2All

sectionsThe existing Ventilation control system is not using current energy management technology. Therefore, a

new DDC control system is recommended.See Pere Lacombe

4.5.8 Air filtration systems and filters.

2All

sectionsThe existing filters are in poor condition. A new filters shall be provided

See Pere Lacombe

4.5.9 Humidification system and components.

2All

sectionsA humidification system does not exist. A new evaporative type humidifiers are recommended with new

air handling units.See Pere Lacombe

4.5.10 Heat exchangers.

Not applicable.

4.5.11 Ventilation distribution system and components (i.e., ductwork, diffusers, mixing boxes, dampers, linkages).

2All

sectionsAre in poor condition. A new ventilation system will be provided with a new air handling units.

See Pere Lacombe

Other

Condition Ratings: 1-Emergency/Critical 2-Poor/Unsatisfactory 3-Marginal 4-Good 5-Excellent F.I.-Further investigation required 19

Page 20: School Facility Audits - Alberta · Classroom unit ventilators served by hot water coil and no glycol system. Gymnasium is served by ... School Facility Evaluation Project Part II

Alberta InfrastructureSchool Facilities Branch

School Facility Evaluation ProjectPart II - Physical Condition

School: Publique Gabrielle - RoyDate: Dec. 1, 1999

Section 4 Mechanical Systems Rating Estim. CostComments/Concerns

4.6 Cooling Systems Bldg. Section Description/Condition

4.6.1 Cooling system capacity and condition (i.e., chillers, cooling towers, condensers).

N/A None

4.6.2 Cooling distribution system and components (i.e., ductwork, diffusers, mixing boxes, dampers, linkages)

N/A

4.6.3 Cooling system controls (including use of current energy management technology).

N/A

4.6.4 Special/dedicated cooling systems (i.e., labs, CTS areas).

N/A

Other

N/A

4.7 Building Control Systems Bldg. Section Description/Condition

4.7.1 Building wide/system wide control systems and/or energy management systems.

2All

sections

The existing control system is at the end of its life expectancy. The control system is not using the current energy management technology. The new DDC control system will be required to accommodate proposed renovations to Mechanical System.

See Pere Lacombe

Overall Mech Systems Condition & Estim. Costs

Condition Ratings: 1-Emergency/Critical 2-Poor/Unsatisfactory 3-Marginal 4-Good 5-Excellent F.I.-Further investigation required 20

Page 21: School Facility Audits - Alberta · Classroom unit ventilators served by hot water coil and no glycol system. Gymnasium is served by ... School Facility Evaluation Project Part II

Alberta InfrastructureSchool Facilities Branch

School Facility Evaluation ProjectPart II - Physical Condition

School: Publique Gabrielle - RoyDate: Dec. 1, 1999

Section 5 Electrical Systems Rating Estim. Cost

5.1 Site Services

5.1.1 Primary service capacity and reliability (i.e., access, location, components, installation, bus sizes - note whether overhead or underground). 1

Primary service is underground to padmount transformer. Secondary to building is underground. Rated at 400A, 120/240V, 1 phase, 3W. Service capacity is at 80%. Main

distribution panel bus is sized at 400A. Main panel is mounted in a closet in rear of a storage room off of a stairwell.

Included in Pere Lacombe

40,000

5.1.2 Site and building exterior lighting (i.e., safety concerns).

3Exterior lighting consists of a few H.I.D. wall units with incandescent lights in soffits. Lights are

photocell controlled. Incandescent should be replaced with H.I.D. type.

Included in Pere Lacombe

5,000

5.1.3 Vehicle plug-ins (i.e., number, capacity, condition).

4 There are sufficient number of car plug-ins for staff. Existing are in good condition. -

Other

5.2 Life Safety Systems Bldg. Section Description/Condition

5.2.1 Fire and smoke alarm systems (i.e., safety concerns, up-to-date technology, regularly tested).

3Fire panel is an old Edwards 16 zone panel located in the main vestibule. Panel is not up-to-date

technology. Various rooms (ie. Mechanical rooms) have no detectors. System is tested annually.

$5,000.00

5.2.2 Emergency lighting systems (i.e., safety concerns, condition).

4Emergency lighting is provided by battery operated units with sealed beam heads. Units are in

good condition and working properly. No emergency lighting in stairwells.-

5.2.3 Exit lighting and signage (i.e., safety concerns, condition).

4 Exit lights have D.C. connection and are installed to Code. -

Other

Comments/Concerns

Condition Ratings: 1-Emergency/Critical 2-Poor/Unsatisfactory 3-Marginal 4-Good 5-Excellent F.I.-Further investigation required 21

Page 22: School Facility Audits - Alberta · Classroom unit ventilators served by hot water coil and no glycol system. Gymnasium is served by ... School Facility Evaluation Project Part II

Alberta InfrastructureSchool Facilities Branch

School Facility Evaluation ProjectPart II - Physical Condition

School: Publique Gabrielle - RoyDate: Dec. 1, 1999

Section 5 Electrical Systems Rating Estim. CostComments/Concerns

5.3 Power Supply and Distribution Bldg. Section Description/Condition

5.3.1 Power service surge protection.

2 There is no surge protection on main service.Included in

Pere Lacombe3,000

5.3.2 Panels and wireways capacity and condition.

3Branch circuit panels are at full capacity and of original installation. Will require upgrading if

additional loads are required. Breakers are currently double lugged and trip frequently.

Included in Pere Lacombe

30,000

5.3.3 Emergency generator capacity and condition and/or UPS (if applicable).

N/A There is no generator. -

5.3.4 General wiring devices and methods.

2 There are insufficient number of receptacles in classrooms. $3,000.00

5.3.5 Motor controls.

4Motor starters and controls are of original installation. Units are in reasonable condition and

operating satisfactory.-

Other

Condition Ratings: 1-Emergency/Critical 2-Poor/Unsatisfactory 3-Marginal 4-Good 5-Excellent F.I.-Further investigation required 22

Page 23: School Facility Audits - Alberta · Classroom unit ventilators served by hot water coil and no glycol system. Gymnasium is served by ... School Facility Evaluation Project Part II

Alberta InfrastructureSchool Facilities Branch

School Facility Evaluation ProjectPart II - Physical Condition

School: Publique Gabrielle - RoyDate: Dec. 1, 1999

Section 5 Electrical Systems Rating Estim. CostComments/Concerns

5.4 Lighting Systems Bldg. Section Description/Condition

5.4.1 Interior lighting systems and components (i.e., illumination levels, conditions, controls).

2

A few classrooms have resessed 2 x 4 fluorescent fixtures (4 lamp). Balance of building has lighting in classrooms which consists of surface mounted fluorescent with wrap-around lenses. Fixtures have T12, F40 lamps with magnetic ballasts. Corridors have wrap-around fluorescent fixtures. Recommend replacing all incandescent with PL lamps. All fixtures should be either

retrofitted with T8 and electronic ballasts or replaced. Fixtures are locally controlled. Gymnasium lighting is totally inadequate, low lighting levels and no protection on the fixtures.

$20,000.00

5.4.2 Replacement of ballasts (i.e., health and safety concerns).

3 All magnetic ballasts to be replaced with new. Part of 5.4.1

5.4.3 Implementation of energy efficiency measures and recommendations.

3 Upgrading of existing light fixtures to energy efficient type has not been implemented yet. See 5.4.1.

Other

Condition Ratings: 1-Emergency/Critical 2-Poor/Unsatisfactory 3-Marginal 4-Good 5-Excellent F.I.-Further investigation required 23

Page 24: School Facility Audits - Alberta · Classroom unit ventilators served by hot water coil and no glycol system. Gymnasium is served by ... School Facility Evaluation Project Part II

Alberta InfrastructureSchool Facilities Branch

School Facility Evaluation ProjectPart II - Physical Condition

School: Publique Gabrielle - RoyDate: Dec. 1, 1999

Section 5 Electrical Systems Rating Estim. CostComments/Concerns

5.5 Network and Communication Systems Bldg. Section Description/Condition

5.5.1 Telephone system and components (i.e., capacity, reliability, condition).

3Administrative phone system is the Meridian system and is not capable of interphasing with

sound/P.A. system.$8,000.00

5.5.2 Other communication systems (i.e., public address, intercom, CCTV, satellite or cable TV).

2Sound and P.A. system is by an old antiquated Bogen/Dukane - manual switching system

requires frequent repair. System is to be replaced with an integrated communication system.$10,000.00

5.5.3 Network cabling (if available, should be category 5 or better).

3Classrooms have not been networked with cable as there is not enough dedicated power

circuits.$3,000.00

5.5.4 Network cabling installation (i.e., in conduit, secured to walls or tables).

4Data cables in Office area are run exposed along walls and above T-bar ceiling. One data outlet

per classroom is installed.-

5.5.5 Wiring and telecommunication closets (i.e., size, security, ventilation/cooling, capacity for growth).

2 A separate communication room should be provided for to centralize all of the I.C.S.'s.Included in

Pere Lacombe5,000

5.5.6 Provision for dedicated circuits for network equipment (i.e., hubs, switches, computers).

2 At present, there are not enough dedicated circuits for hubs, computers.Included in

Pere Lacombe3,000

Other

Condition Ratings: 1-Emergency/Critical 2-Poor/Unsatisfactory 3-Marginal 4-Good 5-Excellent F.I.-Further investigation required 24

Page 25: School Facility Audits - Alberta · Classroom unit ventilators served by hot water coil and no glycol system. Gymnasium is served by ... School Facility Evaluation Project Part II

Alberta InfrastructureSchool Facilities Branch

School Facility Evaluation ProjectPart II - Physical Condition

School: Publique Gabrielle - RoyDate: Dec. 1, 1999

Section 5 Electrical Systems Rating Estim. CostComments/Concerns

5.6 Miscellaneous Systems Bldg. Section Description/Condition

5.6.1 Site and building surveillance system (if applicable).

N/A N/A

5.6.2 Intrusion alarms (if applicable).

4 There is a Silent Night Intrusion Alarm System and is monitored.

5.6.3 Master clock system (if applicable).

N/A N/A

Other

5.7 Elevators/Disabled Lifts (If applicable)

5.7.1 Elevator/lift size, access and operating features (i.e., sensing devices, buttons, phones, detectors).

N/A N/A

5.7.2 Condition of elevators/lifts.

N/A N/A

5.7.3 Lighting and ventilation of elevators/lifts.

N/A N/A

Other

Overall Elect. Systems Condition & Estim Costs Excludes costs for work required in Ecole Pere Lacombe - shared areas. $49,000.00

Condition Ratings: 1-Emergency/Critical 2-Poor/Unsatisfactory 3-Marginal 4-Good 5-Excellent F.I.-Further investigation required 25

Page 26: School Facility Audits - Alberta · Classroom unit ventilators served by hot water coil and no glycol system. Gymnasium is served by ... School Facility Evaluation Project Part II

Alberta InfrastructureSchool Facilities Branch

School Facility Evaluation ProjectPart II - Physical Condition

School: Publique Gabrielle - RoyDate: Dec. 1, 1999

Section 6 Portable Buildings Rating Comments/Concerns Estim. Cost

Note: Separate sheets can be completed, if necessary, for portable buildings of different ages and/or conditions.

Nill

6.1.1 Foundation and structure (i.e., signs of bending, cracking, settlement, rust, voids, stains). N/A

6.1.2 Roof materials and components (i.e., signs of deterioration, leaks, ice build-up). N/A

6.1.3 Exterior wall finishes (i.e., signs of deterioration, cracks, water stains). N/A

6.1.4 Doors and windows (i.e., signs of deterioration, rusting hardware, glass cracks, peeling paint, damaged seals). N/A

6.1.5 Interior finishes (i.e., floors, walls, ceiling).

N/A

6.1.6 Millwork (i.e., counters, shelving, vanities, cabinets).

N/A

6.1.7 Fixed/wall mounted equipment (i.e., writing boards, tackboards, display boards, signs) N/A

6.1.8 Heating system.

N/A

6.1.9 Ventilation system.

N/A

6.1.10 Electrical, communication and data network systems.

N/A

6.1.11 Health and safety concerns (i.e., fire and smoke alarms, fire protection systems, exiting, fire resistance rating of materials).

N/A

6.1.12 Barrier-free access.

N/A

Overall Portable Bldgs Condition & Estim Costs

Condition Ratings: 1-Emergency/Critical 2-Poor/Unsatisfactory 3-Marginal 4-Good 5-Excellent F.I.-Further investigation required 26

Page 27: School Facility Audits - Alberta · Classroom unit ventilators served by hot water coil and no glycol system. Gymnasium is served by ... School Facility Evaluation Project Part II

Alberta InfrastructureSchool Facilities Branch

School Facility Evaluation ProjectPart II - Physical Condition

School: Publique Gabrielle - RoyDate: Dec. 1, 1999

No. Size Total Area No. Size Total Area

7.1 Classrooms

3 67 201 2 80 160 41

7.2 Science Rooms/Labs

0 _ 0

7.3 Ancillary Areas (i.e., Art, Computer Labs, Drama, Music,) 1

67

67

11

1301x90 220 <153>

7.4 Gymnasium (incl. gym storage)

1 _ 14111

_ 275 <134>

Shared with Pere Lacombe so space taken as 141

7.5 Library/Resource Areas

1 _ 58 1 _ 80 <22>

Shared with Pere Lacombe so space taken as 58

7.6 Administration/Staff, Physical Education, Storage Areas

40est 1 _ 252

212

Limited area - small space for staff.

7.7 CTS Areas 7.7.1 Business Education

7.7.2 Home Economics

7.7.3 Industrial Arts

7.7.4 Other CTS Programs

7.8 Other Non-Instructional Areas (i.e., circulation, wall area, crush space, wc area)

173 389 <216>

Lavatories shared with Pere Lacombe.

Overall Space Adequacy Assessment 680 1376 <696>Must shared lavatories, Library, Gymnasium, etc.

Section 7 Space Adequacy Comments/ConcernsSurplus/

Deficiency

This Facility Equiv. New Facility

Condition Ratings: 1-Emergency/Critical 2-Poor/Unsatisfactory 3-Marginal 4-Good 5-Excellent F.I.-Further investigation required 27

Page 28: School Facility Audits - Alberta · Classroom unit ventilators served by hot water coil and no glycol system. Gymnasium is served by ... School Facility Evaluation Project Part II

Alberta InfrastructureSchool Facilities Branch

School Facility Evaluation ProjectPart II - Physical Condition

School: Publique Gabrielle - RoyDate: Dec. 1, 1999

Evaluation Component/ Sub-Component

Additional Notes and Comments

Condition Ratings: 1-Emergency/Critical 2-Poor/Unsatisfactory 3-Marginal 4-Good 5-Excellent F.I.-Further investigation required 28

Page 29: School Facility Audits - Alberta · Classroom unit ventilators served by hot water coil and no glycol system. Gymnasium is served by ... School Facility Evaluation Project Part II

Alberta InfrastructureSchool Facilities Branch

School Facility Evaluation ProjectPart II - Physical Condition

School: Publique Gabrielle - RoyDate: Dec. 1, 1999

Evaluation Component/ Sub-Component

Additional Notes and Comments

Condition Ratings: 1-Emergency/Critical 2-Poor/Unsatisfactory 3-Marginal 4-Good 5-Excellent F.I.-Further investigation required 29

Page 30: School Facility Audits - Alberta · Classroom unit ventilators served by hot water coil and no glycol system. Gymnasium is served by ... School Facility Evaluation Project Part II

Alberta InfrastructureSchool Facilities Branch

School Facility Evaluation ProjectPart II - Physical Condition

School: Publique Gabrielle - RoyDate: Dec. 1, 1999

Evaluation Component/ Sub-Component

Additional Notes and Comments

Condition Ratings: 1-Emergency/Critical 2-Poor/Unsatisfactory 3-Marginal 4-Good 5-Excellent F.I.-Further investigation required 30

Page 31: School Facility Audits - Alberta · Classroom unit ventilators served by hot water coil and no glycol system. Gymnasium is served by ... School Facility Evaluation Project Part II

Alberta InfrastructureSchool Facilities Branch

School Facility Evaluation ProjectPart II - Physical Condition

School: Publique Gabrielle - RoyDate: Dec. 1, 1999

Evaluation Component/ Sub-Component

Additional Notes and Comments

Condition Ratings: 1-Emergency/Critical 2-Poor/Unsatisfactory 3-Marginal 4-Good 5-Excellent F.I.-Further investigation required 31

Page 32: School Facility Audits - Alberta · Classroom unit ventilators served by hot water coil and no glycol system. Gymnasium is served by ... School Facility Evaluation Project Part II

Alberta InfrastructureSchool Facilities Branch

School Facility Evaluation ProjectPart II - Physical Condition

School: Publique Gabrielle - RoyDate: Dec. 1, 1999

Evaluation Component/ Sub-Component

Additional Notes and Comments

Condition Ratings: 1-Emergency/Critical 2-Poor/Unsatisfactory 3-Marginal 4-Good 5-Excellent F.I.-Further investigation required 32

Page 33: School Facility Audits - Alberta · Classroom unit ventilators served by hot water coil and no glycol system. Gymnasium is served by ... School Facility Evaluation Project Part II

Alberta InfrastructureSchool Facilities Branch

School Facility Evaluation ProjectPart II - Physical Condition

School: Publique Gabrielle - RoyDate: Dec. 1, 1999

Evaluation Component/ Sub-Component

Additional Notes and Comments

Condition Ratings: 1-Emergency/Critical 2-Poor/Unsatisfactory 3-Marginal 4-Good 5-Excellent F.I.-Further investigation required 33