60
Second Revision No. 137-NFPA 101-2013 [ Section No. 18.1.4.2 ] 18.1.4.2 Special Definitions. The following is a list of special terms used in this chapter: (1) Ambulatory Health Care Occupancy. (See 3.3.190.1 3.3.188.1 .) (2) Deep-fat Frying.A cooking method that involves fully immersing food in hot oil. (See 3.3.56 .) (3) Hospital. (See 3.3.143 3.3.143 3.3.1433.3.142 .) (4) Limited Care Facility. (See 3.3.90.2 3.3.88.2 .) (5) Nursing Home. (See 3.3.142.2 3.3.140.2 .) Submitter Information Verification Submitter Full Name: [ Not Specified ] Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Thu Jun 27 14:19:35 EDT 2013 Committee Statement Committee Statement: The definition is in Chapter 3 and can simply be referenced. Response Message: Page 131 of 331 National Fire Protection Association Report 8/26/2013 http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment... SAF-HEA SECOND REVISIONS WITH STATEMENTS Page 1 of 60

Second Revision No. 137-NFPA 101-2013 [ Section No. 18.1.4.2 ]

  • Upload
    others

  • View
    5

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Second Revision No. 137-NFPA 101-2013 [ Section No. 18.1.4.2 ]

Second Revision No. 137-NFPA 101-2013 [ Section No. 18.1.4.2 ]

18.1.4.2 Special Definitions.The following is a list of special terms used in this chapter:

(1) Ambulatory Health Care Occupancy. (See 3.3.190.1 3.3.188.1 .)

(2) Deep-fat Frying.A cooking method that involves fully immersing food in hot oil. (See 3.3.56 .)

(3) Hospital. (See 3.3.143 3.3.143 3.3.1433.3.142 .)

(4) Limited Care Facility. (See 3.3.90.2 3.3.88.2 .)

(5) Nursing Home. (See 3.3.142.2 3.3.140.2 .)

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 27 14:19:35 EDT 2013

Committee Statement

Committee Statement: The definition is in Chapter 3 and can simply be referenced.

Response Message:

Page 131 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-HEA SECOND REVISIONS WITH STATEMENTS

Page 1 of 60

Page 2: Second Revision No. 137-NFPA 101-2013 [ Section No. 18.1.4.2 ]

Second Revision No. 105-NFPA 101-2013 [ Section No. 18.2.2.2.7 ]

18.2.2.2.7*Doors permitted to be locked in accordance with 18.2.2.2.5.1 shall be permitted to have murals on the egress doors to disguise the doors, provided all of the following are met:

(1) Staff can readily unlock the doors at all times in accordance with 18.2.2.2.6.

(2)

(3)

(4) The murals shall not impair the operation of the doors.

(5) The location and operation of doors disguised with murals shall be identified in the fire safety plan and shall be included in staff training.

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jun 26 11:41:41 EDT 2013

Committee Statement

Committee Statement:

Since the operation of these doors will be the responsibility of facility staff, an additional requirement is being proposed to have these doors with murals clearly identified in the fire safety plan, and to have staff be required to become familiar with the location and operation of all such doors.

ResponseMessage:

Public Comment No. 76-NFPA 101-2013 [Section No. 18.2.2.2.7]

* The door- releasing hardware, where provided, is readily accessible for staff use.

* Door leaves, windows, and door hardware, other than door- releasinghardware, shall be permitted to be covered by the murals.

Page 132 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-HEA SECOND REVISIONS WITH STATEMENTS

Page 2 of 60

Page 3: Second Revision No. 137-NFPA 101-2013 [ Section No. 18.1.4.2 ]

Second Revision No. 139-NFPA 101-2013 [ Section No. 18.2.2.2.11.1 ]

18.2.2.2.11.1Special-purpose horizontally sliding accordion or folding door assemblies Horizontal sliding doors , that are not automatic-closing shall be limited to a single leaf and shall have a latch or other mechanism that ensures that the doors will not rebound into a partially open position if forcefully closed.

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 27 14:22:52 EDT 2013

Committee Statement

Committee Statement:

The global replacement of the term horizontal sliding door should not have been done at this location.

ResponseMessage:

Page 133 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-HEA SECOND REVISIONS WITH STATEMENTS

Page 3 of 60

Page 4: Second Revision No. 137-NFPA 101-2013 [ Section No. 18.1.4.2 ]

Second Revision No. 108-NFPA 101-2013 [ Section No. 18.2.3.4 ]

18.2.3.4*Aisles, corridors, and ramps required for exit access in a hospital or nursing home shall be not less than 8 ft (2440 mm) in clear and unobstructed width, unless otherwise permitted by one of the following:

(1)

(2)

(3)

(4) Projections into the required width shall be permitted for wheeled equipment, provided that all of the following conditions are met:

(a) The wheeled equipment does not reduce the clear unobstructed corridor width to less than 60 in. (1525 mm).

(b) The health care occupancy fire safety plan and training program address the relocation of the wheeled equipment during a fire or similar emergency.

(c)

(5)

* Aisles, corridors, and ramps in adjunct areas not intended for the housing, treatment, or use of inpatients shall be not less than 44 in. (1120 mm) in clear and unobstructed width.

* Noncontinuous projections not more than 6 in. (150 mm) from the corridor wall, positioned not less than 38 in. (965 mm) above the floor, shall be permitted.

* Exit access within a room or suite of rooms complying with the requirements of 18.2.5 shall be permitted.

i. Equipment in use and carts in use

ii. Medical emergency equipment not in use

iii. Patient lift and transport equipment

* The wheeled equipment is limited to the following:

(a) The fixed furniture is securely attached to the floor or to the wall.

(b) The fixed furniture does not reduce the clear unobstructed corridor width to less than 6 ft (1830 mm), except as permitted by 18.2.3.4(2).

(c) The fixed furniture is located only on one side of the corridor.

(d) The fixed furniture is grouped such that each grouping does not exceed an area of 50 ft2 (4.6 m2).

(e) The fixed furniture groupings addressed in 18.2.3.4(5)(d) are separated from each other by a distance of at least 10 ft (3050 mm).

(f)

(g) Corridors throughout the smoke compartment are protected by an electrically supervised automatic smoke detection system in accordance with 18.3.4, or the fixed furniture spaces are arranged and located to allow direct supervision by the facility staff from a nurses’ station or similar space.

* Where the corridor width is at least 8 ft (2440 mm), projections into the required width shall be permitted for fixed furniture, provided that all of the following conditions are met:

* The fixed furniture is located so as to not obstruct access to building service and fire protection equipment.

Page 134 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-HEA SECOND REVISIONS WITH STATEMENTS

Page 4 of 60

Page 5: Second Revision No. 137-NFPA 101-2013 [ Section No. 18.1.4.2 ]

(6)

(7) Nursing home corridors shall be permitted to be not less than 6 ft (1830 mm) wide in smoke compartments housing not more than 30 patients.

(8) Cross-corridor door openings in corridors with a required minimum width of 6 ft (1830 mm) shall have a clear width of not less than 64 in. (1625 mm) for pairs of doors or a clear width of not less than 32 in. (810 mm) 41 1 ⁄2 in. (1055 mm) for a single door.

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jun 26 12:04:32 EDT 2013

Committee Statement

Committee Statement:

Clear width of door openings is covered in 18.2.3.6 and the new requirements in (8) appear to conflict with those requirements.

Response Message:

Public Comment No. 101-NFPA 101-2013 [Section No. 18.2.3.4]

* Cross-corridor door openings in corridors with a required minimum width of 8 ft (2440 mm) shall have a clear width of not less than 6 ft 11 in. (2110 mm) for pairs of doors or a clear width of not less than 411⁄2 in. (1055 mm) for a singledoor.

Page 135 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-HEA SECOND REVISIONS WITH STATEMENTS

Page 5 of 60

Page 6: Second Revision No. 137-NFPA 101-2013 [ Section No. 18.1.4.2 ]

Second Revision No. 129-NFPA 101-2013 [ Section No. 18.2.5.7.2.4 ]

18.2.5.7.2.4 Sleeping Suite Travel Distance.(A)Travel distance between any point in a sleeping suite and an exit access door to another suite, an exit access corridor door, or a horizontal exit door from that suite shall not exceed 100 ft (30 m).(B)Travel distance between any point in a sleeping suite and an exit shall not exceed 200 ft (61 m).

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 27 12:26:23 EDT 2013

Committee Statement

Committee Statement:

Change made at first revision inadvertently deleted the option to measure travel to an adjacent suite.

ResponseMessage:

Page 136 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-HEA SECOND REVISIONS WITH STATEMENTS

Page 6 of 60

Page 7: Second Revision No. 137-NFPA 101-2013 [ Section No. 18.1.4.2 ]

Second Revision No. 130-NFPA 101-2013 [ Section No. 18.2.5.7.3.3 ]

18.2.5.7.3.3 Patient Care Non-Sleeping Suite Travel Distance.(A)Travel distance within a non-sleeping suite to an exit access door to another suite, an exit access corridor door, or a horizontal exit door from the suite shall not exceed 100 ft (30 m).(B)Travel distance between any point in a non-sleeping suite and an exit shall not exceed 200 ft (61 m).

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 27 12:28:07 EDT 2013

Committee Statement

Committee Statement:

Change made at first revision inadvertently deleted the option to measure travel to an adjacent suite.

ResponseMessage:

Page 137 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-HEA SECOND REVISIONS WITH STATEMENTS

Page 7 of 60

Page 8: Second Revision No. 137-NFPA 101-2013 [ Section No. 18.1.4.2 ]

Second Revision No. 109-NFPA 101-2013 [ Section No. 18.3.2.1.2 ]

18.3.2.1.2The following areas shall be considered hazardous areas and shall be protected by fire barriers having a minimum 1-hour fire resistance rating in accordance with Section 8.3:

(1) Boiler and fuel-fired heater rooms

(2) Central/bulk laundries larger than 100 ft2 (9.3 m2)

Laboratories that use hazardous materials that would be classified as a severe hazard in accordance with NFPA 99 , Standard for Health Care Facilities

(3) Paint shops employing hazardous substances and materials in quantities less than those that would be classified as a severe hazard

(4) Physical plant maintenance shops

(5) Rooms with soiled linen in volume exceeding 64 gal (242 L)

(6) Rooms with collected trash in volume exceeding 64 gal (242 L)

(7) Storage rooms larger than 100 ft2 (9.3 m2) and storing combustible material

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jun 26 12:42:03 EDT 2013

Committee Statement

Committee Statement:

The section deleted had a requirement for "Laboratories that use hazardous materials that would be classified as a severe hazard in accordance with NFPA 99..." but NFPA 99, 2012 Edition doesn't classify laboratories in such a manner.

ResponseMessage:

Public Comment No. 103-NFPA 101-2013 [Section No. 18.3.2.1.2]

Page 138 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-HEA SECOND REVISIONS WITH STATEMENTS

Page 8 of 60

Page 9: Second Revision No. 137-NFPA 101-2013 [ Section No. 18.1.4.2 ]

Second Revision No. 111-NFPA 101-2013 [ Section No. 18.3.2.2 ]

Global SR-113 Hide Deleted

18.3.2.2 Laboratories.

Global SR-113 Hide Deleted

Laboratories employing quantities of flammable, combustible, or hazardous materials that are considered as a severe hazard shall be protected in accordance with NFPA 99 , Health Care Facilities Code . in which chemicals are handled or stored shall comply with NFPA 45 , Standard on Fire Protection for Laboratories Using Chemicals .

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jun 26 13:25:01 EDT 2013

Committee Statement

Committee Statement: Laboratories are covered under NFPA 45.

Response Message:

Public Comment No. 102-NFPA 101-2013 [Section No. 18.3.2.2]

Page 139 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-HEA SECOND REVISIONS WITH STATEMENTS

Page 9 of 60

Page 10: Second Revision No. 137-NFPA 101-2013 [ Section No. 18.1.4.2 ]

Second Revision No. 114-NFPA 101-2013 [ Section No. 18.3.2.4 ]

18.3.2.4 Medical Gas.Medical gas storage and administration areas shall be protected Areas where medical gas is stored or administered, and the operation, testing, and maintenance of medical gases shall be in accordance with NFPA 99, Health Care FacilitiesCode.

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jun 26 14:06:09 EDT 2013

Committee Statement

Committee Statement:

Clarification that the word administration applies to areas where medical gas is administered and not to administration (business) areas.

Response Message:

Public Comment No. 28-NFPA 101-2013 [Section No. 18.3.2.4]

Page 140 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-HEA SECOND REVISIONS WITH STATEMENTS

Page 10 of 60

Page 11: Second Revision No. 137-NFPA 101-2013 [ Section No. 18.1.4.2 ]

Second Revision No. 123-NFPA 101-2013 [ Section No. 18.3.7.1 ]

18.3.7.1Buildings containing health care facilities shall be subdivided by smoke barriers (see 18.2.4.3), unless otherwise permitted by 18.3.7.2, as follows:

(1) To divide every story used by inpatients for sleeping or treatment into not lessthan two smoke compartments

(2) To divide every story having an occupant load of 50 or more persons, regardless of use, into not less than two smoke compartments

(3) To limit the size of each smoke compartment required by 18.3.7.1(1) and 18.3.7.1(2) to an area not exceeding 40,000 ft2 (3720 m2) in hospitals , unless the area is an atrium separated in accordance with 8.6.7, in which case no limitation in size is required

(4) To limit the size of each smoke compartment required by 18.3.7.1(1) and 18.3.7.1(2) (2) to an area not exceeding 22,500 ft 2 (2100 m 2 ) in nursing homes and limited care facilities, unless the area is an atrium separated in accordance with 8.6.7 , in which case no limitation in size is required

(5) To limit the travel distance from any point to reach a door in the required smoke barrier to a distance not exceeding 200 ft (61 m)

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 27 11:24:03 EDT 2013

Committee Statement

Committee Statement:

The substantiation submitted for increasing smoke compartment size to 40,000 sq ft was based on hospitals. The 22,500 sq ft limitation needs to be retained for nursing homes and limited care facilities.

Response Message:

Page 141 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-HEA SECOND REVISIONS WITH STATEMENTS

Page 11 of 60

Page 12: Second Revision No. 137-NFPA 101-2013 [ Section No. 18.1.4.2 ]

Second Revision No. 119-NFPA 101-2013 [ Section No. 18.3.7.6 ]

18.3.7.6*Doors in smoke barriers shall be substantial doors, such as non- rated 1 3⁄4 in. (44 mm) thick, solid-bonded wood-core doors, or shall be of construction that resists fire for a minimum of 20 minutes, and shall meet the following requirements:

(1) Nonrated factory- or field-applied protective plates, unlimited in height, shall be permitted.

(2) Cross-corridor openings in smoke barriers shall be protected by a pair of swinging doors or a special-purpose horizontally sliding accordion or folding door assembly complying with 7.2.1.14, unless otherwise permitted by 18.3.7.7.

(3) The swinging doors addressed by 18.3.7.6(2) shall be arranged so that each door swings in a direction opposite from the other.

(4) The minimum clear width for of swinging doors shall be as follows:

(a) Hospitals and nursing homes Where the corridor is required to be a minimum of 8 ft (2440 mm) wide — 411⁄2 in. (1055 mm)

(b) Psychiatric hospitals and limited care facilities Where the corridor isrequired to be a minimum of 6 ft (1830 mm) wide — 32 in. (810 mm)

(5) The minimum clear width opening for horizontal-sliding horizontal slidingdoors shall be as follows:

(a) Hospitals and nursing homes Where the corridor is required to be a minimum of 8 ft (2440 mm) wide — 6 ft 11 in. (2110 mm)

(b) Psychiatric hospitals and limited care facilities Where the corridor isrequired to be a minimum of 6 ft (1830 mm) wide — 64 in. (1625 mm)

(6) The clearance under the bottom of smoke barrier doors shall not exceed 3⁄4 in. (19 mm).

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jun 26 18:33:16 EDT 2013

Committee Statement

Page 142 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-HEA SECOND REVISIONS WITH STATEMENTS

Page 12 of 60

Page 13: Second Revision No. 137-NFPA 101-2013 [ Section No. 18.1.4.2 ]

Committee Statement:

Correlative change relative to new provision permitting 6 ft corridor width in small smoke compartments.

ResponseMessage:

Page 143 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-HEA SECOND REVISIONS WITH STATEMENTS

Page 13 of 60

Page 14: Second Revision No. 137-NFPA 101-2013 [ Section No. 18.1.4.2 ]

Second Revision No. 110-NFPA 101-2013 [ Section No. 18.4.4.5 ]

18.4.4.5 Hazardous Area Protection (Nonsprinklered Smoke Compartment Rehabilitation).18.4.4.5.1Where a new hazardous area is formed in an existing nonsprinklered smoke compartment, the hazardous area itself shall be protected as indicated in Table 18.4.4.5.1 .Table 18.4.4.5.1 Hazardous Area Protection (Nonsprinklered Buildings)

Hazardous Area Description Protection * /Separation

Boiler and fuel-fired heater rooms 1 hour and sprinklers

Central/bulk laundries larger than 100 ft 2 (9.3 m 2 )

1 hour and sprinklers

Paint shops employing hazardous substances and materials in quantities less than those that would be classified as a severe hazard

1 hour and sprinklers

Physical plant maintenance shops 1 hour and sprinklers

Soiled linen rooms 1 hour and sprinklers

Storage rooms larger than 50 ft 2 (4.6 m 2 ) but not exceeding 100 ft 2 (9.3 m 2 ) and storing combustible material

1 hour or sprinklers (Also see18.4.4.7.2.2.)

Storage rooms larger than 100 ft 2 (9.3 m 2 ) and storing combustible material

1 hour and sprinklers

Trash collection rooms 1 hour and sprinklers

*Minimum fire resistance rating.

18.4.4.5.2Laboratories in which chemicals are handled or stored shall comply with NFPA 45 , Standard on Fire Protection for Laboratories Using Chemicals .

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jun 26 12:56:39 EDT 2013

Committee Statement

Committee Statement: Laboratories are addressed by NFPA 45.

Response Message:

Page 144 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-HEA SECOND REVISIONS WITH STATEMENTS

Page 14 of 60

Page 15: Second Revision No. 137-NFPA 101-2013 [ Section No. 18.1.4.2 ]

Second Revision No. 104-NFPA 101-2013 [ Section No. 18.7.2.2 ]

18.7.2.2 Fire Safety Plan.A written health care occupancy fire safety plan shall provide for all of the following:

(1) Use of alarms

(2) Transmission of alarms to fire department

(3) Emergency phone call to fire department

(4) Response to alarms

(5) Isolation of fire

(6) Evacuation of immediate area

(7) Evacuation of smoke compartment

(8) Preparation of floors and building for evacuation

(9) Extinguishment of fire

(10) Location and operation of doors disguised with murals as permitted by 18.2.2.2.7

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jun 26 11:39:07 EDT 2013

Committee Statement

Committee Statement: Recognition of new item required by 18.2.2.2.7.

Response Message:

Page 145 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-HEA SECOND REVISIONS WITH STATEMENTS

Page 15 of 60

Page 16: Second Revision No. 137-NFPA 101-2013 [ Section No. 18.1.4.2 ]

Second Revision No. 117-NFPA 101-2013 [ Section No. 18.7.3.3 ]

18.7.3.3*For smoke compartments having spaces not separated from the corridor by partitions, a written Where required by the authority having jurisdiction, a floor plan shall be provided to indicate the location of all required means of egress corridors in that smoke compartments having spaces not separated from the corridor bypartitions .

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jun 26 17:54:06 EDT 2013

Committee Statement

Committee Statement:

There are spaces where it may not be obvious where the required corridor runs. In such cases, the AHJ can require that a plan be provided.

Response Message:

Page 146 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-HEA SECOND REVISIONS WITH STATEMENTS

Page 16 of 60

Page 17: Second Revision No. 137-NFPA 101-2013 [ Section No. 18.1.4.2 ]

Second Revision No. 138-NFPA 101-2013 [ Section No. 19.1.4.2 ]

19.1.4.2 Special Definitions.The following is a list of special terms used in this chapter:

(1) Ambulatory Health Care Occupancy. (See 3.3.190.1 3.3.188.1 .)

(2) Deep-fat Frying.A cooking method that involves fully immersing food in hot oil. (See 3.3.56 .)

(3) Hospital. (See 3.3.144 3.3.144 3.3.142 .)

(4) Limited Care Facility. (See 3.3.90.2 3.3.88.2 .)

(5) Nursing Home. (See 3.3.142.2 3.3.140.2 .)

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 27 14:20:43 EDT 2013

Committee Statement

Committee Statement: The definition is in Chapter 3 and can simply be referenced.

Response Message:

Page 147 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-HEA SECOND REVISIONS WITH STATEMENTS

Page 17 of 60

Page 18: Second Revision No. 137-NFPA 101-2013 [ Section No. 18.1.4.2 ]

Second Revision No. 120-NFPA 101-2013 [ Section No. 19.2.2.2.5.2 ]

19.2.2.2.5.2*Door-locking arrangements shall be permitted where patient special needs require specialized protective measures for their safety, provided that all of the following are met:

(1) Staff can readily unlock doors at all times in accordance with 19.2.2.2.6.

(2) A total (complete) smoke detection system is provided throughout the locked space in accordance with 9.6.2.9, or locked doors can be remotely unlocked at an approved, constantly attended location within the locked space.

(3)

(4) The locks are electrical locks that fail safely so as to release upon loss of power to the device.

(5) The locks release by independent activation of each of the following:

(a) Activation of the smoke detection system required by 19.2.2.2.5.2(2)

(b) Waterflow in the automatic sprinkler system required by 19.2.2.2.5.2(3)

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jun 26 18:38:01 EDT 2013

Committee Statement

Committee Statement:

Section 19.3.5.1 only references sprinklering requirements for nursing homes. The intent is that the sprinkler system be installed per 19.3.5.7.

Response Message:

* The building is protected throughout by an approved, supervised automatic sprinkler system in accordance with 19.3.5.7 19.3.5.7 19.3.5.1 .

Page 148 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-HEA SECOND REVISIONS WITH STATEMENTS

Page 18 of 60

Page 19: Second Revision No. 137-NFPA 101-2013 [ Section No. 18.1.4.2 ]

Second Revision No. 106-NFPA 101-2013 [ Section No. 19.2.2.2.7 ]

19.2.2.2.7*Doors permitted to be locked in accordance with 19.2.2.2.5.1 shall be permitted to have murals on the egress doors to disguise the doors, provided all of the following are met:

(1) Staff can readily unlock the doors at all times in accordance with 19.2.2.2.6.

(2)

(3)

(4) The murals shall not impair the operation of the doors.

(5) The affected smoke compartments are protected throughout by an approved, supervised automatic sprinkler system in accordance with 19.3.5.7.

(6) The location and operation of doors disguised with murals shall be identified in the fire safety plan and shall be included in staff training .

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jun 26 11:46:50 EDT 2013

Committee Statement

Committee Statement:

Since the operation of these doors will be the responsibility of facility staff, an additional requirement is being proposed to have these doors with murals clearly identified in the fire safety plan, and to have staff be required to become familiar with the location and operation of all such doors.

ResponseMessage:

Public Comment No. 79-NFPA 101-2013 [Section No. 19.2.2.2.7]

* The door-releasing hardware, where provided, is readily accessible for staff use.

* Door leaves, windows, and door hardware, other than door-releasing hardware, shall be permitted to be covered by the murals.

Page 149 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-HEA SECOND REVISIONS WITH STATEMENTS

Page 19 of 60

Page 20: Second Revision No. 137-NFPA 101-2013 [ Section No. 18.1.4.2 ]

Second Revision No. 140-NFPA 101-2013 [ Section No. 19.2.2.2.11.1 ]

19.2.2.2.11.1Special-purpose horizontally sliding accordion or folding door assemblies Horizontal-sliding doors that are not automatic-closing shall be limited to a single leaf and shall have a latch or other mechanism that ensures that the doors will not rebound into a partially open position if forcefully closed.

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 27 14:24:49 EDT 2013

Committee Statement

Committee Statement:

The global replacement of the term horizontal sliding door should not have been done at this location.

ResponseMessage:

Page 150 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-HEA SECOND REVISIONS WITH STATEMENTS

Page 20 of 60

Page 21: Second Revision No. 137-NFPA 101-2013 [ Section No. 18.1.4.2 ]

Second Revision No. 131-NFPA 101-2013 [ Section No. 19.2.5.7.2.4 ]

19.2.5.7.2.4 Sleeping Suite Travel Distance.(A)Travel distance between any point in a sleeping suite and an exit access door to another suite, an exit access corridor door, or a horizontal exit door from that suite shall not exceed 100 ft (30 m).(B)Travel distance between any point in a sleeping suite and an exit shall not exceed the following:

(1) 150 ft (46 m) if the building is not protected throughout by an approved electrically supervised sprinkler system complying with 19.3.5.7

(2) 200 ft (61 m) if the building is protected throughout by an approved electrically supervised sprinkler system complying with 19.3.5.7

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 27 12:29:05 EDT 2013

Committee Statement

Committee Statement:

Change made at first revision inadvertently deleted the option to measure travel to an adjacent suite.

ResponseMessage:

Page 151 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-HEA SECOND REVISIONS WITH STATEMENTS

Page 21 of 60

Page 22: Second Revision No. 137-NFPA 101-2013 [ Section No. 18.1.4.2 ]

Second Revision No. 132-NFPA 101-2013 [ Section No. 19.2.5.7.3.3 ]

19.2.5.7.3.3 Patient Care Non-Sleeping Suite Travel Distance.(A)Travel distance within a non-sleeping suite to an exit access door to another suite, an exit access corridor door, or a horizontal exit door from the suite shall not exceed 100 ft (30 m).(B)Travel distance between any point in a non-sleeping suite and an exit shall not exceed the following:

(1) 150 ft (46 m) if the building is not protected throughout by an approved electrically supervised sprinkler system complying with 19.3.5.7

(2) 200 ft (61 m) if the building is protected throughout by an approved electrically supervised sprinkler system complying with 19.3.5.7

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 27 12:29:49 EDT 2013

Committee Statement

Committee Statement:

Change made at first revision inadvertently deleted the option to measure travel to an adjacent suite.

ResponseMessage:

Page 152 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-HEA SECOND REVISIONS WITH STATEMENTS

Page 22 of 60

Page 23: Second Revision No. 137-NFPA 101-2013 [ Section No. 18.1.4.2 ]

Second Revision No. 112-NFPA 101-2013 [ Section No. 19.3.2.2 ]

19.3.2.2* Laboratories.Laboratories employing quantities of flammable, combustible, or hazardous materials that are considered as a severe hazard shall be in accordance with Section 8.7 and the provisions of NFPA 99 , Health Care Facilities Code , applicable to administration, maintenance, and testing.19.3.2.2.1Laboratories in which chemicals are handled or stored shall comply with the operational requirements of NFPA 45 , Standard on Fire Protection for Laboratories Using Chemicals .19.3.2.2.2Laboratories employing quantities of flammable, combustible, or hazardous materials that are considered as a severe hazard shall be protected in accordance with 8.7.1.1 .

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jun 26 13:33:26 EDT 2013

Committee Statement

Committee Statement:

As currently written, 19.3.2.2 is only applicable to certain laboratories. Adding the reference to NFPA 45 broadens 19.3.2.2 to include operational requirements for all laboratories. The annex note is being deleted.

Response Message:

Public Comment No. 105-NFPA 101-2013 [Section No. 19.3.2.2]

Page 153 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-HEA SECOND REVISIONS WITH STATEMENTS

Page 23 of 60

Page 24: Second Revision No. 137-NFPA 101-2013 [ Section No. 18.1.4.2 ]

Second Revision No. 133-NFPA 101-2013 [ Section No. 19.3.2.4 ]

19.3.2.4 Medical Gas.Medical gas storage and administration areas shall be in accordance with Section 8.7 and the provisions of NFPA 99, Health Care Facilities Code, applicable to administration operation , maintenance, and testing.

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 27 13:47:40 EDT 2013

Committee Statement

Committee Statement:

Clarification that operation, maintenance, and testing needs to be in accordance with NFPA 99.

ResponseMessage:

Page 154 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-HEA SECOND REVISIONS WITH STATEMENTS

Page 24 of 60

Page 25: Second Revision No. 137-NFPA 101-2013 [ Section No. 18.1.4.2 ]

Second Revision No. 124-NFPA 101-2013 [ Section No. 19.3.7.1 ]

19.3.7.1Smoke barriers shall be provided to divide every story used for sleeping rooms for more than 30 patients into not less than two smoke compartments (see 19.2.4.4),and the following also shall apply:

(1) The size of any such smoke compartment shall not exceed one of the following:

(a) 22,500 ft2 (2100 m2), and the travel distance from any point to reach a door in the required smoke barrier shall not exceed 200 ft (61 m), for health care occupancies not meeting 19.3.7.1(1)(b)

(b) 40,000 ft2 (3720 m2), and for hospitals where the travel distance from any point to reach a door in the required smoke barrier shall does not exceed 200 ft (61 m), for buildings and the building is protectedthroughout by an approved, supervised automatic sprinkler system inaccordance 19.3.5.8

(2) Where neither the length nor width of the smoke compartment exceeds 150 ft (46 m), the travel distance to reach the smoke barrier door shall not be limited.

(3) The area of an atrium separated in accordance with 8.6.7 shall not be limited in size.

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 27 11:49:43 EDT 2013

Committee Statement

Committee Statement:

Correlation with smoke compartment area increase made in chapter 18.

Response Message:

Page 155 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-HEA SECOND REVISIONS WITH STATEMENTS

Page 25 of 60

Page 26: Second Revision No. 137-NFPA 101-2013 [ Section No. 18.1.4.2 ]

Second Revision No. 125-NFPA 101-2013 [ Section No. 19.4.2 ]

19.4.2 High-Rise Buildings.19.4.2.1All high-rise buildings containing health care occupancies shall be protected throughout by an approved, supervised automatic sprinkler system installed in accordance with Section 9.7 within 12 years of the adoption of this Code, except as otherwise provided in 19.4.2.2 or 19.4.2.3 .19.4.2.2*Where a jurisdiction adopts this edition of the Code and previously adopted the 2012 edition, the sprinklering required by 19.4.2.1 shall be installed within 9 9 years of the adoption of this Code .19.4.2.3*Where a jurisdiction adopts this edition of the Code and previously adopted the 2009 edition, the sprinklering required by 19.4.2.1 shall be installed within 9 6years of the adoption of this Code.

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 27 12:04:15 EDT 2013

Committee Statement

Committee Statement:

Jurisdictions that adopted the 2012 edition and started the 12 year period should not be given a new 12 years to sprinkler. Similarly, jurisdictions that adopted the 2009 edition and started the 12 year period should not be given the 9years to sprinkler as detailed in the 2012 edition.

Response Message:

Page 156 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-HEA SECOND REVISIONS WITH STATEMENTS

Page 26 of 60

Page 27: Second Revision No. 137-NFPA 101-2013 [ Section No. 18.1.4.2 ]

Second Revision No. 107-NFPA 101-2013 [ Section No. 19.7.2.2 ]

19.7.2.2 Fire Safety Plan.A written health care occupancy fire safety plan shall provide for all of the following:

(1) Use of alarms

(2) Transmission of alarms to fire department

(3) Emergency phone call to fire department

(4) Response to alarms

(5) Isolation of fire

(6) Evacuation of immediate area

(7) Evacuation of smoke compartment

(8) Preparation of floors and building for evacuation

(9) Extinguishment of fire

(10) Location and operation of doors disguised with murals as permitted by 19.2.2.2.7

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jun 26 11:47:42 EDT 2013

Committee Statement

Committee Statement: Recognition of new item required by 19.2.2.2.7.

Response Message:

Page 157 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-HEA SECOND REVISIONS WITH STATEMENTS

Page 27 of 60

Page 28: Second Revision No. 137-NFPA 101-2013 [ Section No. 18.1.4.2 ]

Second Revision No. 118-NFPA 101-2013 [ Section No. 19.7.3.3 ]

19.7.3.3*For smoke compartments having spaces not separated from the corridor by partitions, a written Where required by the authority having jurisdiction, a floor plan shall be provided to indicate the location of all required means of egress corridors in that smoke compartments having spaces not separated from the corridor bypartitions .

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jun 26 17:58:23 EDT 2013

Committee Statement

Committee Statement:

There are spaces where it may not be obvious where the required corridor runs. In such cases, the AHJ can require that a plan be provided.

Response Message:

Page 158 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-HEA SECOND REVISIONS WITH STATEMENTS

Page 28 of 60

Page 29: Second Revision No. 137-NFPA 101-2013 [ Section No. 18.1.4.2 ]

Second Revision No. 244-NFPA 101-2013 [ Section No. 20.2.3.2 ]

20.2.3.2Street floor exits shall be sufficient for the occupant load of the street floor plus the required capacity of open stairs and ramps discharging through the street floor.

Submitter Information Verification

Submitter Full Name: Ron Coté

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 03 07:04:31 EDT 2013

Committee Statement

CommitteeStatement:

Vertical openings are restricted to the point that there will not be many open stairs or open ramps connecting to the street floor.

ResponseMessage:

Page 159 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-HEA SECOND REVISIONS WITH STATEMENTS

Page 29 of 60

Page 30: Second Revision No. 137-NFPA 101-2013 [ Section No. 18.1.4.2 ]

Second Revision No. 245-NFPA 101-2013 [ Section No. 20.2.3.4 ]

20.2.3.3Where minimum corridor width is 6 ft (1830 mm), projections not more than 6 in. (150 mm) from the corridor wall, above the handrail height, shall be permitted for the installation of hand-rub dispensing units in accordance with 20.3.2.8.

Submitter Information Verification

Submitter Full Name: Ron Coté

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 03 07:07:12 EDT 2013

Committee Statement

Committee Statement: Asterisk added to denote the presence of annex text.

Response Message:

Page 160 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-HEA SECOND REVISIONS WITH STATEMENTS

Page 30 of 60

Page 31: Second Revision No. 137-NFPA 101-2013 [ Section No. 18.1.4.2 ]

Second Revision No. 134-NFPA 101-2013 [ New Section after

20.3.2.4 ]

20.3.2.5 Medical Gas.Areas where medical gas is stored or administered, and the operation, management, and maintenance of medical gases shall be in accordance with NFPA 99 , Health Care Facilities Code .

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 27 14:11:40 EDT 2013

Committee Statement

Committee Statement:

Clarification that the word administration applies to areas where medical gas is administered and not to administration (business) areas.

Response Message:

Public Comment No. 29-NFPA 101-2013 [New Section after 20.3.2.4]

Page 161 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-HEA SECOND REVISIONS WITH STATEMENTS

Page 31 of 60

Page 32: Second Revision No. 137-NFPA 101-2013 [ Section No. 18.1.4.2 ]

Second Revision No. 249-NFPA 101-2013 [ Section No. 20.3.2.4 ]

20.3.2.4 Laboratories.Laboratories in which chemicals are handled or stored shall comply with NFPA 45 , Standard on Fire Protection for Laboratories Using Chemicals . employingquantities of flammable, combustible, or hazardous materials that are consideredas a severe hazard shall be protected in accordance with NFPA 99 , Health Care Facilities Code .

Submitter Information Verification

Submitter Full Name: Ron Coté

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 03 08:06:58 EDT 2013

Committee Statement

Committee Statement: Laboratories are covered under NFPA 45.

Response Message:

Page 162 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-HEA SECOND REVISIONS WITH STATEMENTS

Page 32 of 60

Page 33: Second Revision No. 137-NFPA 101-2013 [ Section No. 18.1.4.2 ]

Second Revision No. 250-NFPA 101-2013 [ Section No. 20.7.1 ]

20.7.1 Evacuation and Relocation Plan and Fire Drills.20.7.1.1The administration of every ambulatory health care facility shall have, in effect and available to all supervisory personnel, written copies of a plan for the protection of all persons in the event of fire, for their evacuation to areas of refuge, and for their evacuation from the building when necessary.20.7.1.2All employees shall be periodically instructed and kept informed with respect to their duties under the plan required by 20.7.1.1.20.7.1.3A copy of the plan required by 20.7.1.1 shall be readily available at all times in the telephone operator’s location or at the security center when the facility is open .20.7.1.4*Fire drills in ambulatory health care facilities shall include the transmission of a fire alarm signal and simulation of emergency fire conditions.20.7.1.5Patients shall not be required to be moved during drills to safe areas or to the exterior of the building.20.7.1.6Drills shall be conducted quarterly on each shift to familiarize facility personnel (nurses, interns, maintenance engineers, and administrative staff) with the signalsand emergency action required under varied conditions.20.7.1.7When drills are conducted between 9:00 p.m. and 6:00 a.m. (2100 hours and 0600 hours), a coded announcement shall be permitted to be used instead of audible alarms.20.7.1.7Employees of ambulatory health care facilities shall be instructed in life safety procedures and devices.

Submitter Information Verification

Submitter Full Name: Ron Coté

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 03 08:09:14 EDT 2013

Committee Statement

Page 163 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-HEA SECOND REVISIONS WITH STATEMENTS

Page 33 of 60

Page 34: Second Revision No. 137-NFPA 101-2013 [ Section No. 18.1.4.2 ]

CommitteeStatement:

Staff will be trained in what to do in emergencies so they can be expected to know the sound of the alarm. The allowance of 20.7.1.7 that is being deleted is not needed as there is no patient sleeping. Also, the alarm will not be required to be sounded during the fire drill, so there is no noise to be concerned about.

ResponseMessage:

Page 164 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-HEA SECOND REVISIONS WITH STATEMENTS

Page 34 of 60

Page 35: Second Revision No. 137-NFPA 101-2013 [ Section No. 18.1.4.2 ]

Second Revision No. 251-NFPA 101-2013 [ Section No. 20.7.2.3.2 ]

20.7.2.3.2All health care personnel shall be instructed in the use of the code phrase toensure transmission of an alarm under any of the following conditions:

(1) When the individual who discovers a fire must immediately go to the aid of anendangered person

(2) During a malfunction of the building fire alarm system

Submitter Information Verification

Submitter Full Name: Ron Coté

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 03 08:17:17 EDT 2013

Committee Statement

CommitteeStatement:

It is important that all personnel be familiar with alarm transmission protocol.

Response Message:

Page 165 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-HEA SECOND REVISIONS WITH STATEMENTS

Page 35 of 60

Page 36: Second Revision No. 137-NFPA 101-2013 [ Section No. 18.1.4.2 ]

Second Revision No. 256-NFPA 101-2013 [ Section No. 21.2.2.2.5 ]

21.2.2.2.5The re-entry provisions of 7.2.1.5.8 shall not apply to any of the following:

(1) Existing ambulatory health care occupancies that are not in high-risebuildings

(2) Existing high-rise ambulatory health care occupancy buildings that are protected throughout by an approved automatic sprinkler system in accordance with 9.7.1.1(1)

(3) Existing high-rise ambulatory health care occupancy buildings having approved existing means for providing stair re-entry

Submitter Information Verification

Submitter Full Name: Ron Coté

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 03 08:38:17 EDT 2013

Committee Statement

CommitteeStatement:

The ambulatory health care occupancy might occupy only a portion of the building.

Response Message:

Page 166 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-HEA SECOND REVISIONS WITH STATEMENTS

Page 36 of 60

Page 37: Second Revision No. 137-NFPA 101-2013 [ Section No. 18.1.4.2 ]

Second Revision No. 257-NFPA 101-2013 [ Section No. 21.2.2.9 ]

21.2.2.9 Fire Escape Stairs.Reserved Fire escape stairs complying with 7.2.8 shall be permitted.

Submitter Information Verification

Submitter Full Name: Ron Coté

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 03 08:48:07 EDT 2013

Committee Statement

CommitteeStatement:

Fire escape stairs are not an acceptable egress route for ambulatory health care occupancies.

Response Message:

Page 167 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-HEA SECOND REVISIONS WITH STATEMENTS

Page 37 of 60

Page 38: Second Revision No. 137-NFPA 101-2013 [ Section No. 18.1.4.2 ]

Second Revision No. 258-NFPA 101-2013 [ Section No. 21.2.3.2 ]

21.2.3.2Street floor exits shall be sufficient for the occupant load of the street floor plus the required capacity of open stairs, ramps, escalators, and moving walks discharging through the street floor.

Submitter Information Verification

Submitter Full Name: Ron Coté

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 03 08:49:34 EDT 2013

Committee Statement

CommitteeStatement:

Vertical openings are restricted to the point that there will not be many open stairs or open ramps connecting to the street floor.

ResponseMessage:

Page 168 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-HEA SECOND REVISIONS WITH STATEMENTS

Page 38 of 60

Page 39: Second Revision No. 137-NFPA 101-2013 [ Section No. 18.1.4.2 ]

Second Revision No. 248-NFPA 101-2013 [ Section No. 21.2.3.4 ]

21.2.3.3Where minimum corridor width is 6 ft (1830 mm), projections not more than 6 in. (150 mm) from the corridor wall, above the handrail height, shall be permitted for the installation of hand-rub dispensing units in accordance with 21.3.2.8.

Submitter Information Verification

Submitter Full Name: Ron Coté

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 03 08:02:21 EDT 2013

Committee Statement

Committee Statement: Asterisk added to denote presence of annex text.

Response Message:

Page 169 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-HEA SECOND REVISIONS WITH STATEMENTS

Page 39 of 60

Page 40: Second Revision No. 137-NFPA 101-2013 [ Section No. 18.1.4.2 ]

Second Revision No. 135-NFPA 101-2013 [ New Section after

21.3.2.4 ]

21.3.2.4 Medical Gas.Medical gas storage shall be in accordance with Section 8.7 and the provisions of NFPA 99 , Health Care Facilities Code , applicable to operation, maintenance, and testing.

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 27 14:13:57 EDT 2013

Committee Statement

Committee Statement:

Clarification that operation, maintenance, and testing needs to be in accordance with NFPA 99.

ResponseMessage:

Public Comment No. 30-NFPA 101-2013 [New Section after 21.3.2.4]

Page 170 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-HEA SECOND REVISIONS WITH STATEMENTS

Page 40 of 60

Page 41: Second Revision No. 137-NFPA 101-2013 [ Section No. 18.1.4.2 ]

Second Revision No. 259-NFPA 101-2013 [ Section No. 21.3.2.4 ]

21.3.2.5 Laboratories.Laboratories employing quantities of flammable, combustible, or hazardous materials that are considered as a severe hazard shall be protected in accordance with NFPA 99 , Health Care Facilities Code .21.3.2.5.1Laboratories in which chemicals are handled or stored shall comply with the operational requirements of NFPA 45 , Standard on Fire Protection for Laboratories Using Chemicals .21.3.2.5.2Laboratories employing quantities of flammable, combustible, or hazardous materials that are considered as a severe hazard shall be protected in accordance with 8.7.1.1 .

Submitter Information Verification

Submitter Full Name: Ron Coté

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 03 08:53:16 EDT 2013

Committee Statement

Committee Statement: Laboratories are addressed by NFPA 45.

Response Message:

Page 171 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-HEA SECOND REVISIONS WITH STATEMENTS

Page 41 of 60

Page 42: Second Revision No. 137-NFPA 101-2013 [ Section No. 18.1.4.2 ]

Second Revision No. 260-NFPA 101-2013 [ Section No. 21.4.2.1 ]

21.4.2.1All high-rise ambulatory health care occupancy buildings shall be provided with a reasonable degree of safety from fire, and such degree of safety shall be accomplished by one of the following means:

(1) Installation of a complete, approved, supervised automatic sprinkler system in accordance with 9.7.1.1(1)

(2) Installation of an engineered life safety system complying with all of the following:

(a) The engineered life safety system shall be developed by a registered professional engineer experienced in fire and life safety systems design.

(b) The life safety system shall be approved by the authority having jurisdiction and shall be permitted to include any or all of the following systems:

i. Partial automatic sprinkler protection

ii. Smoke detection alarms

iii. Smoke control

iv. Compartmentation

v. Other approved systems

Submitter Information Verification

Submitter Full Name: Ron Coté

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 03 08:58:17 EDT 2013

Committee Statement

CommitteeStatement:

The ambulatory health care occupancy might not occupy the entire building.

Response Message:

Page 172 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-HEA SECOND REVISIONS WITH STATEMENTS

Page 42 of 60

Page 43: Second Revision No. 137-NFPA 101-2013 [ Section No. 18.1.4.2 ]

Second Revision No. 261-NFPA 101-2013 [ Section No. 21.7.1 ]

Global SR-261 Hide Deleted

21.7.1 Evacuation and Relocation Plan and Fire Drills.21.7.1.1The administration of every ambulatory health care facility shall have, in effect and available to all supervisory personnel, written copies of a plan for the protection of all persons in the event of fire, for their evacuation to areas of refuge, and for their evacuation from the building when necessary.21.7.1.2All employees shall be periodically instructed and kept informed with respect to their duties under the plan required by 21.7.1.1.21.7.1.3A copy of the plan required by 21.7.1.1 shall be readily available at all times in the telephone operator’s location or at the security center when the facility is open .21.7.1.4*Fire drills in ambulatory health care facilities shall include the transmission of a fire alarm signal and simulation of emergency fire conditions.21.7.1.5Patients shall not be required to be moved during drills to safe areas or to the exterior of the building.21.7.1.6Drills shall be conducted quarterly on each shift to familiarize facility personnel (nurses, interns, maintenance engineers, and administrative staff) with the signalsand emergency action required under varied conditions.

Global SR-261 Hide Deleted

21.7.1.7When drills are conducted between 9:00 p.m. and 6:00 a.m. (2100 hours and 0600 hours), a coded announcement shall be permitted to be used instead of audible alarms.21.7.1.7Employees of ambulatory health care facilities shall be instructed in life safety procedures and devices.

Submitter Information Verification

Submitter Full Name: Ron Coté

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 03 08:59:44 EDT 2013

Committee Statement

Page 173 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-HEA SECOND REVISIONS WITH STATEMENTS

Page 43 of 60

Page 44: Second Revision No. 137-NFPA 101-2013 [ Section No. 18.1.4.2 ]

CommitteeStatement:

Staff will be trained in what to do in emergencies so they can be expected to know the sound of the alarm. The allowance of 21.7.1.7 that is being deleted is not needed as there is no patient sleeping. Also, the alarm will not be required to be sounded during the fire drill, so there is no noise to be concerned about.

ResponseMessage:

Page 174 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-HEA SECOND REVISIONS WITH STATEMENTS

Page 44 of 60

Page 45: Second Revision No. 137-NFPA 101-2013 [ Section No. 18.1.4.2 ]

Second Revision No. 262-NFPA 101-2013 [ Section No. 21.7.2.3.2 ]

21.7.2.3.2All health care personnel shall be instructed in the use of the code phrase toensure transmission of an alarm under any of the following conditions:

(1) When the individual who discovers a fire must immediately go to the aid of anendangered person

(2) During a malfunction of the building fire alarm system

Submitter Information Verification

Submitter Full Name: Ron Coté

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 03 09:02:44 EDT 2013

Committee Statement

CommitteeStatement:

It is important that all personnel be familiar with alarm transmission protocol.

Response Message:

Page 175 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-HEA SECOND REVISIONS WITH STATEMENTS

Page 45 of 60

Page 46: Second Revision No. 137-NFPA 101-2013 [ Section No. 18.1.4.2 ]

Second Revision No. 127-NFPA 101-2013 [ Section No. A.18.2.3.4(2) ]

A.18.2.3.4(2)The intent of 18.2.3.4(2) is to permit limited noncontinuous projections along the corridor wall. These include hand-rub dispensing units complying with 18.3.2.6,nurse charting units, wall-mounted computers, telephones, artwork, bulletin boards, display case frames, cabinet frames, fire alarm boxes, and similar items. It is not the intent to permit the narrowing of the corridor by the walls themselves. The provision of 7.3.2.2 permits projections up to 41⁄2 in. (114 mm) to be present at and below the 38 in. (965 mm) height specified in 18.2.3.4(2), and it is not the intent of 18.2.3.4(2) to prohibit such projections. Permitting projections above the 38 in. (965 mm) handrail height complies with the intent of the requirement, as such projections will not interfere with the movement of gurneys, beds, and wheelchairs.Projections below handrail height for limited items, such as fire extinguishercabinets and recessed water coolers, also will not interfere with equipmentmovement.

Building codes and accessibility codes might require cane detection below projections that exceed 4 in. (102 mm).

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 27 12:18:49 EDT 2013

Committee Statement

Committee Statement:

Clarification that the 6 in. encroachment can be made compatible with more stringent accessibility requirements. Projections in excess of 4 in. can be made compatible with accessibility codes if cane detection is provided below the projection.

ResponseMessage:

Page 301 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-HEA SECOND REVISIONS WITH STATEMENTS

Page 46 of 60

Page 47: Second Revision No. 137-NFPA 101-2013 [ Section No. 18.1.4.2 ]

Second Revision No. 128-NFPA 101-2013 [ Section No. A.18.2.3.5(2) ]

A.18.2.3.5(2)The intent of 18.2.3.5 is to permit limited noncontinuous projections along the corridor wall. These include hand-rub dispensing units complying with 18.3.2.6,nurse charting units, wall-mounted computers, telephones, artwork, bulletin boards, display case frames, cabinet frames, fire alarm boxes, and similar items. It is not the intent to permit the narrowing of the corridor by the walls themselves. The provision of 7.3.2.2 permits projections up to 41⁄2 in. (114 mm) to be present at and below the 38 in. (965 mm) height specified in 18.2.3.5(2), and it is not the intent of 18.2.3.5(2) to prohibit such projections. Permitting projections above the 38 in. (965 mm) handrail height complies with the intent of the requirement, as such projections will not interfere with the movement of gurneys, beds, and wheelchairs.Projections below handrail height for limited items, such as fire extinguishercabinets and recessed water coolers, also will not interfere with equipmentmovement. Other codes and standards, such as NFPA 5000 ®, Building Construction and Safety Code ® other building codes, and the Federal 2010 ADAStandards for Accessible Design might require cane protection for projectionsgreater than 4 in. It is not the intent of 18.2.3.5.2 to limit or preclude requirements found in other applicable codes and standards.

Building codes and accessibility codes might require cane detection below projections that exceed 4 in. (102 mm).

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 27 12:20:45 EDT 2013

Committee Statement

Committee Statement:

Clarification that the 6 in. encroachment can be made compatible with more stringent accessibility requirements. Projections in excess of 4 in. can be made compatible with accessibility codes if cane detection is provided below the projection.

ResponseMessage:

Page 302 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-HEA SECOND REVISIONS WITH STATEMENTS

Page 47 of 60

Page 48: Second Revision No. 137-NFPA 101-2013 [ Section No. 18.1.4.2 ]

Second Revision No. 122-NFPA 101-2013 [ Section No. A.18.2.5.7.2.2

(C)(1) ]

A.18.2.5.7.2.3(C)(1)The alternative of 18.2.5.7.2.1(D)(1)(b) is not to be applied, since 18.2.5.7.2.3(B)(C) (2) requires total coverage automatic smoke detection for the suite that exceeds 5000 7500 ft2 (460 700 m2) but does not exceed 7500 10,000 ft2 (700 930 m2).

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jun 26 19:27:57 EDT 2013

Committee Statement

Committee Statement: Correction of an error.

Response Message:

Page 303 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-HEA SECOND REVISIONS WITH STATEMENTS

Page 48 of 60

Page 49: Second Revision No. 137-NFPA 101-2013 [ Section No. 18.1.4.2 ]

Second Revision No. 113-NFPA 101-2013 [ Section No. A.18.3.2.2 ]

A.18.3.2.2The hazard level of a laboratory is considered severe if quantities of flammable, combustible, or hazardous materials are present that are capable of sustaining a fire of sufficient magnitude to breach a 1-hour fire separation. See the NFPA Fire Protection Handbook for guidance.

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jun 26 13:53:54 EDT 2013

Committee Statement

Committee Statement: Current annex conflicts with changes made to 18.3.2.2.

Response Message:

Page 304 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-HEA SECOND REVISIONS WITH STATEMENTS

Page 49 of 60

Page 50: Second Revision No. 137-NFPA 101-2013 [ Section No. 18.1.4.2 ]

Second Revision No. 115-NFPA 101-2013 [ Section No. A.18.3.2.5.2 ]

A.18.3.2.5.2This provision is intended to permit small appliances used for reheating, limited cooking , and food preparation, such as microwave ovens, hot plates, electric skillets, toasters, and and nourishment centers to be exempt from the requirements for commercial cooking equipment and hazardous area protection.Limited quantities of butter, cooking spray , or oil may can be used.

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jun 26 16:19:34 EDT 2013

Committee Statement

Committee Statement: To clarify the intent of 18.3.2.5.2.

Response Message:

Public Comment No. 65-NFPA 101-2013 [New Section after 18.3.2.5.2]Public Comment No. 67-NFPA 101-2013 [New Section after A.18.3.2.5.2]

Page 305 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-HEA SECOND REVISIONS WITH STATEMENTS

Page 50 of 60

Page 51: Second Revision No. 137-NFPA 101-2013 [ Section No. 18.1.4.2 ]

Second Revision No. 136-NFPA 101-2013 [ Section No. A.19.2.3.4(2) ]

A.19.2.3.4(2)The intent of 19.2.3.4(2) is to permit limited noncontinuous projections along the corridor wall. These include hand-rub dispensing units complying with 19.4.3,nurse charting units, wall-mounted computers, telephones, artwork, bulletin boards, display case frames, cabinet frames, fire alarm boxes, and similar items. It is not the intent to permit the narrowing of the corridor by the walls themselves. The provision of 7.3.2.2 permits projections up to 41⁄2 in. (114 mm) to be present at and below the 38 in. (965 mm) handrail height, and it is not the intent of 19.2.3.4(2) to prohibit such projections.

Building codes and accessibility codes might require cane detection below projections that exceed 4 in. (102 mm).

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 27 14:16:36 EDT 2013

Committee Statement

Committee Statement:

Clarification that the 6 in. encroachment can be made compatible with more stringent accessibility requirements. Projections in excess of 4 in. can be made compatible with accessibility codes if cane detection is provided below the projection.

ResponseMessage:

Page 306 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-HEA SECOND REVISIONS WITH STATEMENTS

Page 51 of 60

Page 52: Second Revision No. 137-NFPA 101-2013 [ Section No. 18.1.4.2 ]

Second Revision No. 121-NFPA 101-2013 [ Section No. A.19.2.5.7.2.3

(C)(1) ]

A.19.2.5.7.2.3(C)(1)The alternative of 19.2.5.7.2.1(D)(1)(b) is not to be applied, since 19.2.5.7.2.3(C)(2) requires total coverage automatic smoke detection for the suite that exceeds5000 7500 ft2 (460 700 m2) but does not exceed 7500 10 , 000 ft2 (700 930 m2).

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jun 26 19:23:54 EDT 2013

Committee Statement

Committee Statement: Correction of error.

Response Message:

Page 307 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-HEA SECOND REVISIONS WITH STATEMENTS

Page 52 of 60

Page 53: Second Revision No. 137-NFPA 101-2013 [ Section No. 18.1.4.2 ]

Second Revision No. 116-NFPA 101-2013 [ Section No. A.19.3.2.5.2 ]

A.19.3.2.5.2This provision is intended to permit small appliances used for reheating, limited cooking, and food preparation, such as microwave ovens, hot plates, electric skillets, toasters, and nourishment centers, tobe exempt from the requirements forcommercial cooking equipment and hazardous area protection. Limited quantities of butter, cooking spray, or oil can be used.

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jun 26 16:21:38 EDT 2013

Committee Statement

Committee Statement: To clarify the intent of 19.3.2.5.2.

Response Message:

Public Comment No. 66-NFPA 101-2013 [New Section after 19.3.2.5.2]Public Comment No. 68-NFPA 101-2013 [New Section after A.19.3.2.5.2]

Page 308 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-HEA SECOND REVISIONS WITH STATEMENTS

Page 53 of 60

Page 54: Second Revision No. 137-NFPA 101-2013 [ Section No. 18.1.4.2 ]

Second Revision No. 126-NFPA 101-2013 [ Section No. A.19.4.2.2 ]

A.19.4.2.2The provision of 19.4.2.2 is intended to prevent the phase-in period for the installation of sprinklers from being reset to 12 years upon adoption of the 2015 edition of the Code in jurisdictions where the 12-year period had already begun via the adoption of the 2012 edition.A.19.4.2.3The provision of 19.4.2.3 is intended to prevent the phase-in period for the installation of sprinklers from being reset to 12 years upon adoption of the 2012 2015 edition of the Code in jurisdictions where the 12-year period had already begun via the adoption of the 2009 edition.

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 27 12:09:31 EDT 2013

Committee Statement

Committee Statement: Explanation of provisions of 19.4.2.

Response Message:

Page 309 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-HEA SECOND REVISIONS WITH STATEMENTS

Page 54 of 60

Page 55: Second Revision No. 137-NFPA 101-2013 [ Section No. 18.1.4.2 ]

Second Revision No. 246-NFPA 101-2013 [ New Section after

A.20.2.2.2.4 ]

A.20.2.3.4Building codes and accessibility codes might require cane detection below projections that exceed 4 in. (102 mm).

Submitter Information Verification

Submitter Full Name: Ron Coté

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 03 07:08:56 EDT 2013

Committee Statement

CommitteeStatement:

Projections in excess of 4 in. can be made compatible with accessibility codes if cane detection is provided below the projection.

ResponseMessage:

Page 310 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-HEA SECOND REVISIONS WITH STATEMENTS

Page 55 of 60

Page 56: Second Revision No. 137-NFPA 101-2013 [ Section No. 18.1.4.2 ]

Second Revision No. 252-NFPA 101-2013 [ Section No. A.20.7 ]

A.20.7Ambulatory h H ealth care occupants have, in large part, varied degrees of physical disability, and their removal to the outside, or even their disturbance caused by moving, is inexpedient or impractical in many cases, except as a last resort. Similarly, recognizing that there might be an operating necessity for the restraint of the mentally ill, often by use of barred windows and locked doors, fire exit drills are usually extremely disturbing, detrimental, and frequently impracticable.

In most cases, fire exit drills, as ordinarily practiced in other occupancies, cannot be conducted in ambulatory health care occupancies. Fundamentally, superior construction, early discovery and extinguishment of incipient fires, and prompt notification need to be relied on to reduce the occasion for evacuation of buildings of this class to a minimum.

Submitter Information Verification

Submitter Full Name: Ron Coté

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 03 08:21:05 EDT 2013

Committee Statement

CommitteeStatement:

Relative to this chapter, the text is addressing ambulatory health care occupancies.

Response Message:

Page 311 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-HEA SECOND REVISIONS WITH STATEMENTS

Page 56 of 60

Page 57: Second Revision No. 137-NFPA 101-2013 [ Section No. 18.1.4.2 ]

Second Revision No. 253-NFPA 101-2013 [ Section No. A.20.7.1.4 ]

A.20.7.1.4Many ambulatory health care occupancies conduct fire drills without disturbingpatients by choosing the location of the simulated emergency in advance and byclosing the doors to patients’ rooms or wards in the vicinity prior to the initiation of the drill. The purpose of a fire drill is to test and evaluate the efficiency, knowledge, and response of institutional personnel in implementing the facility fire emergency plan. Its purpose is not to disturb or excite patients. Fire drills should be scheduled on a random basis to ensure that personnel in ambulatory health care facilities are drilled not less than once in each 3-month period.

Drills should consider the ability to move patients to an adjacent smoke compartment. Relocation can be practiced using simulated patients or emptywheelchairs.

Submitter Information Verification

Submitter Full Name: Ron Coté

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 03 08:23:25 EDT 2013

Committee Statement

CommitteeStatement:

Relative to this chapter, the text is addressing ambulatory health care (AHC) occupancies. AHCs are less institutional than hospitals. In AHCs there are no patient sleeping rooms or wards.

Response Message:

Page 312 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-HEA SECOND REVISIONS WITH STATEMENTS

Page 57 of 60

Page 58: Second Revision No. 137-NFPA 101-2013 [ Section No. 18.1.4.2 ]

Second Revision No. 247-NFPA 101-2013 [ New Section after

A.21.2.2.2.12 ]

A.21.2.3.4Building codes and accessibility codes might require cane detection below projections that exceed 4 in. (102 mm).

Submitter Information Verification

Submitter Full Name: Ron Coté

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 03 07:57:46 EDT 2013

Committee Statement

CommitteeStatement:

Clarification that the 6 in. encroachment can be made compatible with more stringent accessibility requirements. Projections in excess of 4 in. can be made compatible with accessibility codes if cane detection is provided below the projection.

Response Message:

Page 313 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-HEA SECOND REVISIONS WITH STATEMENTS

Page 58 of 60

Page 59: Second Revision No. 137-NFPA 101-2013 [ Section No. 18.1.4.2 ]

Second Revision No. 254-NFPA 101-2013 [ Section No. A.21.7 ]

A.21.7Health Ambulatory health care occupants have, in large part, varied degrees of physical disability, and their removal to the outside, or even their disturbance caused by moving, is inexpedient or impractical in many cases, except as a last resort. Similarly, recognizing that there might be an operating necessity for the restraint of the mentally ill, often by use of barred windows and locked doors, fire exit drills are usually extremely disturbing, detrimental, and frequentlyimpracticable.

In most cases, fire exit drills, as ordinarily practiced in other occupancies, cannot be conducted in ambulatory health care occupancies. Fundamentally, superior construction, early discovery and extinguishment of incipient fires, and prompt notification need to be relied on to reduce the occasion for evacuation of buildings of this class to a minimum.

Submitter Information Verification

Submitter Full Name: Ron Coté

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 03 08:34:21 EDT 2013

Committee Statement

CommitteeStatement:

Relative to this chapter, the text is addressing ambulatory health care occupancies.

Response Message:

Page 314 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-HEA SECOND REVISIONS WITH STATEMENTS

Page 59 of 60

Page 60: Second Revision No. 137-NFPA 101-2013 [ Section No. 18.1.4.2 ]

Second Revision No. 255-NFPA 101-2013 [ Section No. A.21.7.1.4 ]

A.21.7.1.4Many ambulatory health care occupancies conduct fire drills without disturbingpatients by choosing the location of the simulated emergency in advance and byclosing the doors to patients’ rooms or wards in the vicinity prior to initiation of the drill. The purpose of a fire drill is to test and evaluate the efficiency, knowledge, and response of institutional personnel in implementing the facility fire emergency plan. Its purpose is not to disturb or excite patients. Fire drills should be scheduled on a random basis to ensure that personnel in ambulatory health care facilities are drilled not less than once in each 3-month period.

Drills should consider the ability to move patients to an adjacent smoke compartment. Relocation can be practiced using simulated patients or emptywheelchairs.

Submitter Information Verification

Submitter Full Name: Ron Coté

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 03 08:35:57 EDT 2013

Committee Statement

CommitteeStatement:

Relative to this chapter, the text is addressing ambulatory health care (AHC) occupancies. AHCs are less institutional than hospitals. In AHCs there are no patient sleeping rooms or wards.

Response Message:

Page 315 of 331National Fire Protection Association Report

8/26/2013http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=%28Comment...

SAF-HEA SECOND REVISIONS WITH STATEMENTS

Page 60 of 60