Upload
boyzes
View
215
Download
0
Embed Size (px)
Citation preview
7/29/2019 Seismic Load.pdf
1/2
Reference Calculation Output
Name Date
Prepared by
Checked by
Approved by
Seismic Load Design Calculation per BS EN 1998-1 & 1998-6
Criteria for Regularity in Plan
For a building to be categorised as being regular in plan, it shall
satisfy all the conditions listed in the following paragraphs:
a. With respect to the lateral stiffness and mass distribution, the
building structure shall be approximately symmetrical in plan
with respect to two orthogonal axes.
b. The plan configuration shall be compact, i.e., each floor shall
be delimited by a polygonal convex line. If in plan set-backs
(re-entrant corners or edge recesses) exist, regularity in planmay still be considered as being satisfied, provided that these
setbacks do not affect the floor in-plan stiffness and that, for
each set-back, the area between the outline of the floor and a
convex polygonal line enveloping the floor does not exceed
5% of the floor area.
c. The in-plan stiffness of the floors shall be sufficiently large in
comparison with the lateral stiffness of the vertical structural
elements, so that the deformation of the floor shall have a
small effect on the distribution of the forces among the vertical
structural elements. In this respect, the L, C, H, I, and X plan
shapes should be carefully examined, notably as concerns thestiffness of the lateral branches, which should be comparable
to that of the central part, in order to satisfy the rigid
diaphragm condition. The application of this paragraph should
be considered for the global behaviour of the building.
d. The slenderness = Lmax/Lmin of the building in plan shall be
not higher than 4, where Lmax and Lmin are respectively the
larger and smaller in plan dimension of the building, measured
in orthogonal directions.
e. At each level and for each direction of analysis x and y, the
eccentricity eo and the torsional radius r shall be in accordancewith the two conditions below, which are expressed for the
direction of analysis y:
eox 0,30 rx and r x ls where,
eox is the distance between the centre of stiffness and the centre
of mass, measured along the x direction, which is normal to the
direction of analysis considered; rx is the square root of the ratio
of the torsional stiffness to the lateral stiffness in the y direction
(torsional radius); and ls is the radius of gyration of the floor
mass in plan (square root of the ratio of (a) the polar moment
of inertia of the floor mass in plan with respect to the centre ofmass of the floor to (b) the floor mass).
Hence, building is categorised as regular in plan.
Yes
Yes
Yes
Yes
Yes
3.0
compliance
Regularity
Seismic Page 3 of 17
7/29/2019 Seismic Load.pdf
2/2
Reference Calculation Output
Name Date
Prepared by
Checked by
Approved by
Seismic Load Design Calculation per BS EN 1998-1 & 1998-6
Criteria for Regularity in Elevation
For a building to be categorised as being regular in elevation, it
shall satisfy all the conditions listed in the following paragraphs:
a. All lateral load resisting systems, such as cores, structural
walls, or frames, shall run without interruption from their
foundations to the top of the building or, if setbacks at
different heights are present, to the top of the relevant zone of
the building.
b. Both the lateral stiffness and the mass of the individual storeysshall remain constant or reduce gradually, without abrupt
changes, from the base to the top of a particular building.
c. In framed buildings the ratio of the actual storey resistance to
the resistance required by the analysis should not vary
disproportionately between adjacent storeys.
Hence, building is categorised as non-regular in elevation.
Criteria for Structural Regularity
Yes Yes Planar Lateral force **
Yes No Planar Modal
No Yes Spatial Lateral force **
No No Spatial Modal
Category of Seismicity
ag = g
ag S = x
= g
If ag 0.04g (or) agS 0.05g, the site is categorised as 'very low seismicity'. NO
If ag 0.08g (or) agS 0.10g, the site is categorised as 'low seismicity'. NO
If ag > 0.08g (and) agS > 0.10g, the site is categorised as 'high seismicity'. YES
In this case, the site falls under 'high seismicity' category.
4.0
compliance
Regularity
Yes
Yes
No
Min.
appli-
cabi-
lity
5.0
Regularity
Method of Analysis
(Linear-elastic analysis)
Allowed Simplification
ModelElevationPlan
Behaviour Factor
(for linear analysis)
Table A: Recommended Structural Analysis Approach
Reference value
Reference value
Decreased value *
Decreased value *
Note: * basic behaviour factor, q o shall be reduced by 20% (see Table C for reduced value)
** applicable only if natural period, T1 4TC & 2s
6.0
0.1125
0.1125 1.35
0.15
Seismic Page 4 of 17