FORM NO. STZ-958
SELF-CONTAINED AIR CONDITIONERS
Manufactured for
Thermal Zone®
Philadelphia, PA
Featuring Industry Standard R-410A Refrigerant
TZCAC- STANDARD EFFICIENCY SERIESNOMINAL SIZES 6 TONS [21.1 kW]
(3 PHASE MODELS ONLY)
2
TABLE OF CONTENTSUnit Features & Benefits ..............................................................................3-4
Selection Procedure ........................................................................................5
Model Number Identification ............................................................................6
Options ....................................................................................................................7
General Data
TZCAC-Series ............................................................................................8
Gross Systems Performance Data
TZCAC-Series ............................................................................................9
Airflow Performance
TZCAC-Series ..........................................................................................10
Electrical Data
TZCAC-Series ..........................................................................................11
Electric Heater Kits
TZCAC-Series ......................................................................................12-13
Dimensional Data ....................................................................................14-16
Accessories ............................................................................................17-24
Mechanical Specifications ............................................................................25
Wiring Diagrams............................................................................................26
Limited Warranty ..........................................................................................27
Table of ContentsTZCAC Series
3
Optional Electric Heater Kit
Compressor Access
Control Box Access
Evaporator Coil/Filter Access
• Return air filters, normallyprovided, are removed inthis photo.
Blower Access
• Belt drive model shown.(Available on 3-phasemodels only.)
• Non-corrosiveplastic condensate pan
[ ] Designates Metric Conversions
Unit Features & BenefitsTZCAC Series
4
• R-410A HFC refrigerant.• Complete factory charged, wired and run tested.• Scroll compressors with internal line break overload and
high-pressure protection.• Single stage compressor on all models.• Convertible airflow.• TXV refrigerant metering system on each circuit.• High Pressure and Low Pressure/Loss of charge protection
standard on all models.• Solid Core liquid line filter drier on each circuit.• Single slab, single pass designed evaporator coil facilitates
easy cleaning for maintained high efficiencies.• Cooling operation up to 125 degree F ambient.• Easily removable filter, blower, electric heat, and control
access panels permits prompt service.• Powder Paint Finish meets ASTMB117 steel coated on each
side for maximum protection. G90 galvanized.• One piece top cover and one piece base pan with drawn
supply and return opening for superior water management.
• Externally mounted refrigerant gauge ports for easy servicediagnostics.
• Factory or field-installed electric heat kits available upto 24 kW.
• Easy to install plug-in; slip in, 100% fully modulatingeconomizer.
• Forkable base rails for easy handling and lifting.• Single point electrical and gas connections.• Direct drive or high performance belt drive motor with
variable pitch pulleys and quick adjust belt system.• Permanently lubricated evaporator, condenser and gas heat
inducer motors.• Condenser motors are internally protected, totally enclosed
with shaft down design.• 1 inch filter standard with slide out design.• Colored and labeled wiring.• Copper tube/Aluminum Fin coils.• Molded compressor plug.
STANDARD FEATURES INCLUDE:
Unit Features & BenefitsTZCAC Series
5
TZCAC- SELECTION PROCEDURES1. Determine cooling and heating requirements at design
conditions.Example:
Total cooling capacity ............65,000 BTUH [19.04 kW]Sensible cooling capacity ......49,000 BTUH [14.36 kW]Condenser entering air ..........95°F [35°C]Evaporator entering air............63°F [17°C] wb/76°F [24°C] dbIndoor air flow ........................2050 CFM [967 L/s]External static pressure..........2.0 in wg
2. Select unit to meet cooling requirements.Since total cooling is within the range of 6 ton [21.1 kW] unitenter cooling performance from the TZCAC072 table, at 95°F[35°C] outdoor temperature, 63°F [17°C] wb entering indoorair, and 2050 CFM [967 L/s]:
Total capacity..........................68,800 BTUH [20.17 kW]Power input ............................5.2 kW
And also, at 76°F [24°C] db indoor entering air, and using the formula at the bottom of the page:
Sensible capacity....................52,304 BTUH [15.33 kW]
3. Determine blower speed and power to meet the systemrequirements.At the given external static pressure of 2.0 in wg, the beltmodel must be selected. Enter the belt drive blower perfor-mance table at 2050 CFM [967 L/s] and 2.0 in wg ESP:
RPM....................793Watts ..................690Drive ..................L
4. Calculate indoor blower BTUH heat effect.BTUH = Watts x 3.413 = 2355
5. Calculate net cooling capacities.Net total cooling = 67,500 – 2355 = 65,145 BTUH [19.09 kW]Net sensible cooling = 52,304 – 2355 = 49,949 BTUH [19.08 kW]
[ ] Designates Metric Conversions
Selection Procedure TZCAC Series
6
072AC LC C
ELECTRICALDESIGNATION
C = 208-230 V,3 PH, 60 Hz
D = 460 V, 3 PH, 60 HzY = 575 V, 3 PH, 60 Hz
BTZ
COOLING CAPACITY(BTUH) [kW]
072 = 72,000 [21.10]
AIRCONDITIONINGCONVERTIBLE
DESIGNSERIES
L = R410ARefrigerant
COMMERCIAL RevisionTHERMALZONE®
—
[ ] Designates Metric Conversions
Model Number IdentificationTZCAC Series
7
Option Code Non-PoweredConvenience Outlet
Low Ambient/Freeze Stat
ADAG xAP x
Hail Guard
x
xBY
x
x
CX x xxBJ x
JC x x
FACTORY INSTALLED OPTION CODES FOR TZCAC- (6 Ton) [21.1 kW](B072)
No Economizer Single Enthalpy EconomizerWith Barometric Relief
A xF x
ECONOMIZER SELECTION FOR TZCAC
“x” indicates factory installed option.
[ ] Designates Metric Conversions
OptionsTZCAC Series
8
Model TZCAC- Series 072CLB 072DLB 072YLCooling Performance1
Gross Cooling Capacity Btu [kW] 73,000 [21.39] 73,000 [21.39] 73,000 [21.39]EER/SEER2 11.2/NA 11.2/NA 11.2/NANominal CFM/AHRI Rated CFM [L/s] 2400/2050 [1133/967] 2400/2050 [1133/967] 2400/2050 [1133/967]AHRI Net Cooling Capacity Btu [kW] 70,000 [20.51] 70,000 [20.51] 70,000 [20.51]Net Sensible Capacity Btu [kW] 49,700 [14.56] 49,700 [14.56] 49,700 [14.56]
Net System Power kW 6.21 6.21 6.21
Net Weight lbs. [kg] 569 [258] 569 [258] 569 [258]
CompressorNo./Type 1/Scroll 1/Scroll 1/Scroll
Outdoor Sound Rating (dB)4 83 83 83Outdoor Coil—Fin Type Louvered Louvered Louvered
Tube Type Rifled Rifled RifledTube Size in. [mm] OD 0.375 [9.5] 0.375 [9.5] 0.375 [9.5]Face Area sq. ft. [sq. m] 16.56 [1.54] 16.56 [1.54] 16.56 [1.54]Rows / FPI [FPcm] 2 / 22 [9] 2 / 22 [9] 2 / 22 [9]
Net Latent Capacity Btu [kW] 20,300 [5.95] 20,300 [5.95] 20,300 [5.95]
Indoor Coil—Fin Type Corrugated Corrugated CorrugatedTube Type Rifled Rifled RifledTube Size in. [mm] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5]Face Area sq. ft. [sq. m] 6.5 [0.6] 6.5 [0.6] 6.5 [0.6]Rows / FPI [FPcm] 4 / 12 [5] 4 / 12 [5] 4 / 12 [5]Refrigerant Control TX Valves TX Valves TX ValvesDrain Connection No./Size in. [mm] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4]
Outdoor Fan—Type Propeller Propeller PropellerNo. Used/Diameter in. [mm] 1/24 [609.6] 1/24 [609.6] 1/24 [609.6]Drive Type/No. Speeds Direct/1 Direct/1 Direct/1CFM [L/s] 4000 [1888] 4000 [1888] 4000 [1888]No. Motors/HP 1 at 1/3 HP 1 at 1/3 HP 1 at 1/3 HPMotor RPM 1075 1075 1075
Indoor Fan—Type FC Centrifugal FC Centrifugal FC CentrifugalNo. Used/Diameter in. [mm] 1/11x10 [279x254] 1/11x10 [279x254] 1/11x10 [279x254]Drive Type/No. Speeds Belt/Variable Belt/Variable Belt/VariableNo. Motors 1 1 1Motor HP 1 1/2 1 1/2 1 1/2Motor RPM 1725 1725 1725Motor Frame Size 0 0 0
Filter—Type Disposable Disposable DisposableFurnished Yes Yes Yes(No.) Size Recommended in. [mm] (4)2x16x16 [51x406x406] (4)2x16x16 [51x406x406] (4)2x16x16 [51x406x406]
Refrigerant Charge Oz. [g] 191 [5415] 191 [5415] 191 [5415]Weights
Ship Weight lbs. [kg] 576 [261] 576 [261] 576 [261]
IEER3 11.7 11.7 11.7
NOMINAL SIZES 6 TONS [21.1 kW] ASHRAE 90.1-1989 COMPLIANT MODELS
[ ] Designates Metric Conversions
NOTES:1. Cooling Performance is rated at 95° F ambient, 80° F entering dry bulb, 67° F entering wet bulb. Gross capacity does
not include the effect of fan motor heat. AHRI capacity is net and includes the effect of fan motor heat. Units aresuitable for operation to �20% of nominal cfm. Units are certified in accordance with the Unitary Air ConditionerEquipment certification program, which is based on AHRI Standard 210/240 or 360.
2. EER and/or SEER are rated at AHRI conditions and in accordance with DOE test procedures.3. IEER is rated in accordance with AHRI Standard 210/240 or 360.4. Outdoor Sound Rating shown is tested in accordance with AHRI Standard 270.
General DataTZCAC Series
9
GROSS SYSTEMS PERFORMANCE DATA—TZCAC-072ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀
wbE 71°F [21.7°C] 67°F [19.4°C] 63°F [17.2°C]CFM [L/s] 2460 [1161] 2050 [967] 1660 [783] 2460 [1161] 2050 [967] 1660 [783] 2460 [1161] 2050 [967] 1660 [783]
DR ➀ .0 .06 .12 .0 .06 .12 .0 .06 .12
OUTDOOR
DRY
BULB
TEMPERATURE
°F[°C]
75[23.9]
Total BTUH [kW]Sens BTUH [kW]Power
80.9 [23.7]47.6 [14.0]
4.0
78.0 [22.9]40.6 [11.9]
4.0
75.3 [22.1]34.5 [10.1]
3.9
78.8 [23.1]61.1 [17.9]
4.0
76.1 [22.3]53.2 [15.6]
3.9
73.4 [21.5]46.0 [13.5]
3.9
74.2 [21.7]68.3 [20.0]
4.0
71.6 [21.0]59.9 [17.6]
3.9
69.2 [20.3]52.4 [15.4]
3.8
80[26.7]
Total BTUH [kW]Sens BTUH [kW]Power
80.8 [23.7]48.0 [14.1]
4.3
77.9 [22.8]41.0 [12.0]
4.3
75.2 [22.0]34.9 [10.2]
4.2
78.7 [23.1]61.6 [18.1]
4.3
76.0 [22.3]53.6 [15.7]
4.2
73.3 [21.5]46.4 [13.6]
4.2
74.1 [21.7]68.8 [20.2]
4.3
71.5 [21.0]60.3 [17.7]
4.2
69.0 [20.2]52.7 [15.5]
4.1
85[29.4]
Total BTUH [kW]Sens BTUH [kW]Power
80.2 [23.5]48.0 [14.1]
4.7
77.4 [22.7]41.1 [12.1]
4.6
74.7 [21.9]35.0 [10.3]
4.5
78.2 [22.9]61.8 [18.1]
4.6
75.5 [22.1]53.8 [15.8]
4.6
72.8 [21.3]46.6 [13.7]
4.5
73.6 [21.6]68.9 [20.2]
4.6
71.0 [20.8]60.4 [17.7]
4.5
68.6 [20.1]52.9 [15.5]
4.4
90[32.2]
Total BTUH [kW]Sens BTUH [kW]Power
79.3 [23.2]47.8 [14.0]
5.0
76.5 [22.4]40.9 [12.0]
4.9
73.9 [21.7]34.9 [10.2]
4.8
77.3 [22.7]61.4 [18.0]
5.0
74.6 [21.9]53.5 [15.7]
4.9
72.0 [21.1]46.4 [13.6]
4.8
72.7 [21.3]68.7 [20.1]
4.9
70.1 [20.5]60.2 [17.7]
4.9
67.7 [19.8]52.7 [15.5]
4.8
95[35]
Total BTUH [kW]Sens BTUH [kW]Power
78.0 [22.9]47.2 [13.8]
5.4
75.2 [22.0]40.4 [11.9]
5.3
72.6 [21.3]34.4 [10.1]
5.2
75.9 [22.2]60.8 [17.8]
5.3
73.3 [21.5]53.0 [15.5]
5.2
70.7 [20.7]45.9 [13.5]
5.2
71.3 [20.9]68.0 [19.9]
5.3
68.8 [20.2]59.7 [17.5]
5.2
66.5 [19.5]52.3 [15.3]
5.1
100[37.8]
Total BTUH [kW]Sens BTUH [kW]Power
76.2 [22.3]46.1 [13.5]
5.8
73.6 [21.6]39.6 [11.6]
5.7
71.0 [20.8]33.7 [9.9]
5.6
74.2 [21.7]59.8 [17.5]
5.7
71.6 [21.0]52.1 [15.3]
5.6
69.1 [20.3]45.2 [13.3]
5.5
69.6 [20.4]67.0 [19.6]
5.7
67.2 [19.7]58.9 [17.3]
5.6
64.8 [19.0]51.5 [15.1]
5.5
105[40.6]
Total BTUH [kW]Sens BTUH [kW]Power
74.1 [21.7]44.8 [13.1]
6.2
71.5 [21.0]38.4 [11.3]
6.1
69.0 [20.2]32.7 [9.6]
6.0
72.1 [21.1]58.5 [17.2]
6.1
69.5 [20.4]50.9 [14.9]
6.0
67.1 [19.7]44.2 [13.0]
5.9
67.5 [19.8]65.7 [19.3]
6.1
65.1 [19.1]57.7 [16.9]
6.0
62.8 [18.4]50.5 [14.8]
5.9
110[43.3]
Total BTUH [kW]Sens BTUH [kW]Power
71.6 [21.0]43.2 [12.7]
6.6
69.1 [20.3]37.0 [10.9]
6.5
66.7 [19.5]31.5 [9.2]
6.4
69.5 [20.4]56.7 [16.6]
6.5
67.1 [19.7]49.5 [14.5]
6.4
64.8 [19.0]43.0 [12.6]
6.3
64.9 [19.0]64.0 [18.8]
6.5
62.6 [18.3]56.2 [16.5]
6.4
60.5 [17.7]49.3 [14.5]
6.3
115[46.1]
Total BTUH [kW]Sens BTUH [kW]Power
68.6 [20.1]41.1 [12.1]
7.0
66.2 [19.4]35.2 [10.3]
6.9
63.9 [18.7]30.0 [8.8]
6.8
66.6 [19.5]54.8 [16.1]
7.0
64.2 [18.8]47.7 [14.0]
6.9
62.0 [18.2]41.5 [12.2]
6.8
62.0 [18.2]62.0 [18.2]
6.9
59.8 [17.5]54.5 [16.0]
6.8
57.7 [16.9]47.7 [14.0]
6.7
DR —Depression ratiodbE —Entering air dry bulbwbE—Entering air wet bulb
Total —Total capacity x 1000 BTUHSens —Sensible capacity x 1000 BTUHPower —KW input
NOTES: ¿ When the entering air dry bulb is other than 80°F [27°C], adjust the sensiblecapacity from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)].
[ ] Designates Metric Conversions
Gross Systems Performance DataTZCAC Series
10
CO
MP
ON
EN
T A
IR R
ES
ISTA
NC
E
NOTE
S:1.
Perfo
rman
ce s
how
n w
ith d
ry c
oil &
sta
ndar
d 2"
[50.
8 m
m] f
ilter
s.2.
Stan
dard
CFM
@ .0
75 lb
s./c
u. ft
.3.
Mot
or e
ffici
ency
= 8
0%4.
BHP
=W
atts
x M
otor
Eff.
746
5.Ad
d co
mpo
nent
resi
stan
ce to
duc
t sta
tic to
det
erm
ine
E.S.
P. as
sho
wn
on c
harts
.
[ ]
Des
igna
tes
Met
ric
Co
nver
sio
ns
Com
pone
ntSt
anda
rd In
door
Airf
low
—CF
M [L
/s]
2200
[944
]24
00 [1
133]
2600
[122
7]28
00 [1
321]
3200
[151
0]34
00 [1
605]
Resi
stan
ce—
Inch
es W
ater
[kPa
]W
et C
oil
.079
.090
.102
.118
.128
.135
Dow
nflo
w.0
61.0
79.0
89.1
00.1
08.1
12R.
S.I.
Econ
omize
rR.
A. D
ampe
r.0
9.1
0.1
1.1
2.1
3.1
5
BE
LT-D
RIV
E A
IRFL
OW
PE
RFO
RM
AN
CE
—6
TON
[21.
10 k
W] M
OD
EL
Driv
e Pa
ckag
eL
MM
otor
H.P.
[w]
1-1/
2 [1
118.
5]1-
1/2
[111
8.5]
Blow
er S
heav
e6.
4 Pi
tch
Diam
eter
6.4
Pitc
h Di
amet
erM
otor
She
ave
Adju
stab
le 2
.8-3
.8 P
itch
Diam
eter
Adju
stab
le 3
.4-4
.4 P
itch
Diam
eter
Turn
s Op
en0
12
34
56
01
23
45
6RP
M11
0010
5010
0094
589
584
578
012
9512
3011
9511
4511
0010
5010
00
Air
Flow
CFM
[L/s
]
Capa
city
6 To
n [2
1.10
kW
]Vo
ltage
208/
230-
460
& 5
75—
3 Ph
ase
2500
[118
0]87
085
591
091
594
597
598
010
2010
2010
8510
4511
4010
8012
0011
1012
6011
3513
0011
7513
9012
0514
5012
3015
3012
5015
8012
9516
30—
—26
00 [1
227]
900
945
940
1005
975
1060
1005
1105
1040
1175
1065
1225
1100
1295
1135
1350
1165
1425
1200
1505
1225
1580
1240
1635
1270
1665
——
Exte
rnal
Sta
tic P
ress
ure—
Inch
es o
f Wat
er [k
Pa]
——
2700
[127
4]93
010
7597
011
0010
0011
4510
3012
0010
6012
6010
9013
3511
2513
9511
5514
7011
8515
4012
2016
1512
3516
7512
5517
30—
——
0.1
[.02
]
—
0.2
[.05
]
—
0.3
[.07
]
—
0.4
[.10
]
2800
[132
1]
0.5
[.12
]
960
0.6
[.15
]
1150
0.7
[.17
]
1000
0.8
[.20
]
1195
0.9
[.22
]
1025
1.0
[.25
]
1240
1.1
[.27
]
1055
1.2
[.30
]
1305
1.3
[.32
]
1085
1.4
[.35
]
1350
1.5
[.37
]
1115
1440
RPM
WRP
MW
RPM
WRP
MW
RPM
WRP
MW
RPM
WRP
MW
RPM
WRP
MW
RPM
WRP
MW
RPM
WRP
MW
RPM
W18
00
[850
]—
——
——
—78
556
085
060
589
565
093
067
097
572
010
1076
010
5080
010
9085
011
2089
011
5094
011
8098
012
1010
1519
00
[897
]—
——
—78
558
083
061
587
566
091
570
095
574
099
077
010
2081
510
7085
511
0592
511
3596
011
6510
1511
9510
7512
2011
1520
00
[944
]—
—77
560
081
562
586
067
589
572
093
075
097
580
010
1584
010
5090
010
8594
011
2010
0011
4510
3511
7510
9012
0511
5012
3012
0521
00
[991
]—
—81
065
084
068
088
074
092
078
095
582
099
588
010
3092
010
6596
011
0010
2511
3010
6011
6011
3011
9011
8012
2012
5012
4012
9522
00 [1
038]
780
660
825
700
865
750
910
810
945
850
980
880
1015
930
1050
1000
1080
1045
1120
1100
1145
1160
1180
1220
1205
1260
1230
1330
1255
1380
2300
[108
5]81
572
085
576
089
083
093
087
096
091
010
0096
010
3510
0510
6510
6011
0011
3011
3511
8011
6012
5012
0013
2512
2013
7012
4014
25—
—24
00 [1
133]
845
780
880
835
920
900
950
945
990
990
1025
1050
1055
1110
1085
1155
1120
1215
1150
1335
1185
1355
1220
1430
1235
1470
1255
1525
——
1145
1510
1180
1560
1210
1620
1235
1740
1250
1775
1295
——
——
——
—29
00 [1
369]
1000
1245
1025
1290
1055
1350
1080
1400
1120
1480
1145
1550
1180
1640
1210
1720
1225
1700
1250
1850
1290
1895
——
——
——
——
3000
[141
6]10
2513
2510
5013
9510
8014
5511
1515
4011
4516
2011
7516
5512
1017
5512
2518
4012
4519
1012
9519
70—
——
——
——
——
—
NOTE
: L-D
rive
left
of b
old
line,
M-D
rive
right
of b
old
line.
Fact
ory
shea
ve s
ettin
gs a
re s
how
n in
bol
d pr
int.
Airflow PerformanceTZCAC Series
11
ELECTRICAL DATA – TZCAC SERIES
Minimum Circuit Ampacity 33/33
Unit
Info
rmat
ion
Unit OperatingVoltage Range 187-253
Minimum OvercurrentProtection Device Size 40/40
Maximum OvercurrentProtection Device Size 50/50
Com
pres
sor M
otor
No. 1Volts 208/230Phase 3RPM 3450
HP, Compressor 1 5Amps (RLA), Comp. 1 19.1/0Amps (LRA), Comp. 1 123/0
Cond
ense
r Mot
or
No. 1Volts 208/230Phase 1
HP 1/3Amps (FLA, each) 2.6/2.6Amps (LRA, each) 4.7/4.7
Evap
orat
or F
an
No. 1Volts 208/230Phase 3
HP 1 1/2Amps (FLA, each) 5.8/5.8Amps (LRA, each) 34/34
072CLB
Volts 208/230 460
17
20
20
14603
34505
9.862
414-506
14601
1/31.252.41
4603
1 1/22.817
072DLB
575
13
15
15
15753
34505
7.550
518-632
15751
1/30.91.51
5753
1 1/22.113.1
072YLB
Electrical DataTZCAC Series
12
072C
L
No H
eat
——
33/3
340
/50
40/5
0
A10C
24.5
6/32
.75
20/2
3.1
33/3
740
/50
40/5
0A0
6C14
.33/
19.1
11.7
/13.
533
/33
40/5
040
/50
25/2
925
/30
——
—
——
33/3
340
/50
40/5
015
/17
15/2
0—
——
RXJJ
-He
ater
Kit
Nom
inal
kW
Heat
erKB
TU/H
r@
208
-240
V
Heat
erAm
p.@
208
-240
V
Unit
Min
. Ckt
.Am
paci
ty@
208
-240
V
Over
Cur
rent
Prot
ectiv
e De
vice
Siz
eM
in./M
ax.
@ 2
08 V
Min
./Max
.@
240
V
Min
. Ckt
.Am
paci
ty20
8/24
0V
Max
. Fus
eSi
ze20
8/24
0V
Min
. Circ
uit
Ampa
city
208-
240
V
Over
Cur
rent
Prot
ectiv
e De
vice
Siz
eM
in./M
ax.
@ 2
08 V
Min
./Max
.@
240
V
7.2/
9.6
—4.
2/5.
6
Rate
dHe
ater
kW
@ 2
08-2
40 V
1— 1
No. o
fSe
quen
ceSt
eps
208-
240
VOLT
, THR
EE P
HASE
, 60
HZ, A
UXIL
IARY
ELE
CTRI
C HE
ATER
KIT
S CH
ARAC
TERI
STIC
S AN
D AP
PLIC
ATIO
N
Heat
er K
itAi
r Con
ditio
ner
Unit
Mod
elNo
.TZ
CAC-
Heat
er K
itAi
r Con
ditio
ner
Sing
le P
ower
Sup
ply
For B
oth
Unit
and
Heat
er K
itSe
para
te P
ower
Sup
ply
For B
oth
Unit
and
Heat
er K
it
18/2
4A2
4C61
.41/
81.8
850
/57.
770
/80
70/7
0
10.8
/14.
414
.4/1
9.2
80/8
0
A15C
36.8
4/49
.13
30.1
/34.
745
/51
45/5
060
/60
A20C
49.1
3/65
.540
/46.
358
/66
60/6
070
/70
11 163
/73
70/8
0—
——
38/4
440
/45
——
—50
/58
50/6
0—
——
072D
L
No H
eat
——
1720
/20
—
A10D
32.7
511
.619
20/2
5—
A06D
19.1
6.8
1720
/25
—15
15—
——
——
1720
/20
—9
15—
——
RXJJ
-He
ater
Kit
Nom
inal
kW
Heat
erKB
TU/H
r@
480
V
Heat
erAm
p.@
480
V
Unit
Min
. Ckt
.Am
paci
ty@
480
V
Over
Cur
rent
Prot
ectiv
e De
vice
Siz
eM
in./M
ax.
@ 4
80 V
Min
./Max
.@
480
V
Min
. Ckt
.Am
paci
ty48
0V
Max
. Fus
eSi
ze48
0V
Min
. Circ
uit
Ampa
city
480
V
Over
Cur
rent
Prot
ectiv
e De
vice
Siz
eM
in./M
ax.
@ 4
80 V
Min
./Max
.@
480
V
9.6
— 5.6
Rate
dHe
ater
kW
@ 4
80 V
1— 1
No. o
fSe
quen
ceSt
eps
480
VOLT
, THR
EE P
HASE
, 60
HZ, A
UXIL
IARY
ELE
CTRI
C HE
ATER
KIT
S CH
ARAC
TERI
STIC
S AN
D AP
PLIC
ATIO
N
Heat
er K
itAi
r Con
ditio
ner
Unit
Mod
elNo
.TZ
CAC-
Heat
er K
itAi
r Con
ditio
ner
Sing
le P
ower
Sup
ply
For B
oth
Unit
and
Heat
er K
itSe
para
te P
ower
Sup
ply
For B
oth
Unit
and
Heat
er K
it
24A2
4D81
.88
28.9
4040
/40
14.4
19.2
—
A15D
49.1
317
.426
30/3
0—
A20D
65.5
23.3
3335
/35
—11 1
3740
——
—
2225
——
—30
30—
——
*= F
or C
anad
ian
use
only
. Use
s “P
” fu
ses
for i
nduc
tive
circ
uit.
+ =
Fie
ld in
stal
led
only
.
Electric Heater KitsTZCAC Series
13
072Y
L
No H
eat
——
1315
/15
—
A20Y
65.5
18.8
2730
/30
—A1
5Y49
.13
13.9
2020
/20
—24
25—
——
——
1315
/15
—18
20—
——
RXJJ
-He
ater
Kit
Nom
inal
kW
Heat
erKB
TU/H
r@
600
V
Heat
erAm
p.@
600
V
Unit
Min
. Ckt
.Am
paci
ty@
600
V
Over
Cur
rent
Prot
ectiv
e De
vice
Siz
eM
in./M
ax.
@ 6
00 V
Min
./Max
.@
600
V
Min
. Ckt
.Am
paci
ty60
0V
Max
. Fus
eSi
ze60
0V
Min
. Circ
uit
Ampa
city
600
V
Over
Cur
rent
Prot
ectiv
e De
vice
Siz
eM
in./M
ax.
@ 6
00 V
Min
./Max
.@
600
V
19.2
— 14.4
Rate
dHe
ater
kW
@ 6
00 V
1— 1
No. o
fSe
quen
ceSt
eps
600
VOLT
, THR
EE P
HASE
, 60
HZ, A
UXIL
IARY
ELE
CTRI
C HE
ATER
KIT
S CH
ARAC
TERI
STIC
S AN
D AP
PLIC
ATIO
N
Heat
er K
itAi
r Con
ditio
ner
Unit
Mod
elNo
.TZ
CAC-
Heat
er K
itAi
r Con
ditio
ner
Sing
le P
ower
Sup
ply
For B
oth
Unit
and
Heat
er K
itSe
para
te P
ower
Sup
ply
For B
oth
Unit
and
Heat
er K
it
24A2
4Y81
.88
23.1
3235
/35
—1
2930
——
—*=
For
Can
adia
n us
e on
ly. U
ses
“P”
fuse
s fo
r ind
uctiv
e ci
rcui
t.+
= F
ield
inst
alle
d on
ly.
Electric Heater KitsTZCAC Series
14
[ ] Designates Metric Conversions
TZCAC 6 TON [21.1 kW] MODEL
BACK VIEW
Dimensional DataTZCAC Series
15
[ ] Designates Metric Conversions
TZCAC 6 TON [21.1 kW] MODEL
FRONT VIEW
BOTTOM VIEW
SIDE VIEW
Dimensional DataTZCAC Series
16
Accessory
Economizer with Single Enthalpy, Downflow/SideflowPower ExhaustFresh Air Damper (Manual)Fresh Air Damper (Motorized)Roof Curb 14"Roof Curb 24"Concentric Diffuser 18" FlushConcentric Diffuser 20" Flush
14 [6]21 [10]80 [36]
6 Ton [21.1 kW]
92 [42]
37 [17]
16 [7]
108 [49]
54 [24]
12 [5]17 [8]70 [32]
88 [40]
26 [12]
14 [6]
104 [47]
42 [19]
Operatinglbs [kg]
Operatinglbs [kg]
Side Discharge Concentric Diffuser RXRN-FA60Side Discharge Concentric Diffuser RXRN-FA65
—55 [25]
—40 [18]
WEIGHTS
39 [991] 261/8 [664]6 [21.1]Capacity Tons [kW] A in. [mm] B in. [mm]
CENTER OF GRAVITY (C.G.)
A B C D23% 29% 21% 27%
6 [21.1]
Capacity Tons [kW] Corner Weights by Percentage
CLEARANCESThe following minimum clearances are recommendedfor proper unit performance and serviceability.
NOTE: Supply duct maybe installed with “0” inchclearance to combustiblematerials, provided 1" [25.4 mm] minimum.Fiberglass insulation isapplied either inside or onthe outside of the duct.
RecommendedClearance in. [mm] Location
48 [1219] A - Front18 [457] B - Condenser Coil
*12 [305] C - Duct Side36 [914] D - Evaporator End60 [1524] E - Above
*57" [1448 mm] With Economizer
CLEARANCES6 Ton [21.1 kW] Models [ ] Designates Metric Conversions
Dimensional DataTZCAC Series
17
AccessoryDescription Model Application Accessory
Model No. Factory Installed
Roofcurb, 14" TZCAC-072 RXKG-CAD14 NoRoofcurb, 24" TZCAC-072 RXKG-CAD24 NoRoofcurb adapters TZCAC-072 RXRX-CCCE50 NoEconomizer, downflow/horizontal, single enthalpy TZCAC-072 AXRD-MCCM3 YesDual enthalpy kit for economizer TZCAC-072 RXRX-AV02 NoCO2 sensor TZCAC-072 RXRX-AR02 NoPower exhaust (C, D, Y voltages) TZCAC-072 AXRX-BGF03 (C,D,Y) NoFresh air damper, manual TZCAC-072 AXRF-FCA1 NoFresh air damper, motorized TZCAC-072 AXRF-FCB1 NoRectangular-to-round 20" duct adapters for concentric diffuser TZCAC-072 RXMC-CC04 No
Concentric diffuser 20", step type TZCAC-072 RXRN-FA65 NoConcentric diffuser 20", flush type TZCAC-072 RXRN-FA75 NoLouver kit, 3-sided TZCAC-072 AXRX-AAD01B YesCompressor time delay TZCAC-072 RXMD-B04 NoLow ambient control TZCAC072 RXRZ-A85 YesConvenience outlet (requires separate power supply) TZCAC-072 RXRX-AN02 YesFreeze stat control TZCAC-072 RXRX-AM01 Yes
ACCESSORY EQUIPMENT
*VoltageC = 208-230 VAC-3PH-60HZD = 460 VAC-3PH-60HZY = 575 VAC-3PH-60HZ
AccessoriesTZCAC Series
18
ROOFCURB ADAPTER
Old Models OLD CURB MODEL ROOFCURB ADAPTER NEW MODEL
COMMERCIAL PACKAGE UNIT(6 TON [21.1 kW]) RXRK-E50 RXRX-CCCE50 TZCAC-072(-)RCF, (-)REF, (-)RGF131 & 201, RGF150
[ ] Designates Metric Conversions (1) SLOPE TYPE (2) FULL PERIMETER TYPE
Accessories TZCAC Series
19
ROOFCURBS (Full Perimeter)n Thermal Zone’s new roofcurb design can be utilized on
3 through 7.5 ton [21.1 kW] models.
n Two available heights (14" [356 mm] and24" [610 mm]) for ALL models.
n Quick assembly corners for simple and fast assembly.
n Opening provided in bottom pan to match the “Thru the Curb” electrical connection opening provided on the unit base pan.
n 2" [51 mm] x 4" [102 mm] Nailer provided.
n Insulating panels provided.
n Sealing gasket (28" [711 mm]) providedwith Roofcurb.
n Packaged for easy field assembly.
Roofcurb Model Height of CurbRXKG-CAD14 14" [356 mm]RXKG-CAD24 24" [610 mm]
[ ] Designates Metric Conversions
TYPICAL INSTALLATION
AccessoriesTZCAC Series
20
[ ] Designates Metric Conversions
n Features Honeywell Controlsn Available factory installed or field accessoryn Gear Driven Direct Drive Actuatorn Fully Modulating (0-100%)n Low Leakage Dampersn Horizontal or Downflow Applicationsn Slip-In Design for Easy Installationsn Plug-In Polarized Electrical Connectionsn Pre-configured—No Field Adjustments Necessaryn Standard Barometric Relief Damper Providedn Single Enthalpy with Dual Enthalpy Upgrade Kitn CO2 Input Sensor Available (Field Installed)n Economizer slips in complete for Downflow or
Horizontal Duct applicationn Field Assembled Hood Ships with Economizern Optional Remote Minimum Position (Honeywell
#S963B1128) is Available from ProStockn Field Installed Power Exhaust Available
ECONOMIZERSAXRD-MCCM3—TZCAC- 6 Ton [21.1 kW] Models
RXRX-AV02—Dual Enthalpy Kit6 Ton [21.1 kW] Models
RXRX-AR02—6 Ton [21.1 kW] Models Optional CO2 Sensor
AXRD-MCCM3TZCAC- 6 Ton [21.1 kW] Models
AXRD-MCCM3TZCAC- 6 Ton [21.1 kW] Models
Accessories TZCAC Series
21
[ ] Designates Metric Conversions
FRESH AIR DAMPERTZCAC 6 Ton [21.1 kW] ModelsAXRF-FCA1 (Manual)AXRF-FCB1 (Motorized)
Model No. Volts
AXRX-BGF03C 208/230
AXRX-BGF03Y ¡ 575
No. of Fans
1
1 1
1
Phase
800
1000
Watts (ea.)
2370
2500
High Speed
1620
1725
1.5
4.4
FLA (ea.)
3.3
23.7
LRA (ea.)CFM ¿ RPM
AXRX-BGF03D 4601 1 800 2370 1620 1.8 4.1
AXRX-BGF04D 4601 1 800 2370 1620 1.8 4.1
AXRX-BGF04C 208/2301 1 1000 2500 1725 4.4 23.7
AXRX-BGF04Y ¡ 5751 1 800 2370 1620 1.5 3.3
¿ CFM is at 0" w.c. external static pressure¡ Unit includes 575 to 460 Volt step-down transformer
POWER EXHAUST KIT FOR RXRD-MCCM(-), RXRD-MECM(-) ECONOMIZERS
Shippinglbs [kg]70 [32]
Operatinglbs [kg]67 [30]
FRESH AIR DAMPER
I319.DGN
INTEGRAL POWER EXHAUST FOR ECONOMIZER(FIELD INSTALLED ONLY)AXRX-BGF03—TZCAC- 6 Ton [21.1 kW] Model
n For Honeywell Economizern Downflow or horizontal applicationsn Requires separate 208-230 volt – 1 PH power
supply with disconnect or requires separate 460V - 1 PH power supply with disconnect.
n Adjustable switch on economizer, factory preset toenergize power exhaust at 95% outside air position
n Polarized plug connects power exhaust relay to economizer
AccessoriesTZCAC Series
22
DUCT ADAPTERS (TZCAC 6 TON [21.1 kW] MODELS)Rectangular to RoundTransitions (Downflow)
Accessory Model No. Size in. [mm]RXMC-CC04 20 [508] Round
Model Application Tons [kW]6 [21.1]
[ ] Designates Metric Conversions
Accessories TZCAC Series
23
SIDE DISCHARGE CONCENTRIC DIFFUSERRXRN-FA65 (6 Ton [21.1 kW] Models)
For Use With Duct Adapter (RXMC)
Model No. A B C D E F G H I J K DuctSize
RXRN-FA65 475/8"[1210 mm]
295/8"[752 mm]
143/8"[365 mm]
271/2"[699 mm]
451/2"[1156 mm]
221/2"[572 mm]
111/2"[292 mm]
133/4"[349 mm]
451/2"[1156 mm]
271/2"[699 mm]
81/8"[206 mm] 20RD
Model No. CFM [L/s] StaticPressure
ThrowFeet
NeckVel.
JetVel.
NoiseLevel
RXRN-FA65
2600 [1227] .17 24-29 669 669 202800 [1321] .20 25-30 720 720 253000 [1416] .25 27-33 772 772 253200 [1510] .31 28-35 823 823 253400 [1605] .37 30-37 874 874 30
DIMENSIONAL DATA
ENGINEERING DATA
[ ] Designates Metric Conversions
AccessoriesTZCAC Series
24
FLUSH MOUNT CONCENTRIC DIFFUSERRXRN-FA75 (6 Ton [21.1 kW] Models)
For Use With Duct Adapter (RXMC)
DIMENSIONAL DATA
ENGINEERING DATA
Model No. A B C D E F G H DuctSize
RXRN-FA75 475/8"[1210 mm]
295/8"[752 mm]
165/8"[422 mm]
27"[686 mm]
451/2"[1156 mm]
221/2"[572 mm]
111/4"[286 mm]
131/2"[343 mm] 20RD
Model No. CFM [L/s] StaticPressure
ThrowFeet
NeckVel.
JetVel.
NoiseLevel
RXRN-FA75
2600 [1227] .17 19-24 663 1294 302800 [1321] .20 20-28 714 1393 353000 [1416] .25 21-29 765 1492 353200 [1510] .31 22-29 816 1592 403400 [1605] .37 22-30 867 1692 40
[ ] Designates Metric Conversions
Accessories TZCAC Series
25
SAMPLESPECIFICATIONSUnit shall be completely factory assembledand performance tested to provide therequired cooling and heating functionssuitable for outdoor installations. Unit shallbe UL/cUL listed and rated in accordanceto AHRI Standard 210.
CabinetUnit casing, base pan and framework shallbe manufactured of galvanized sheet metalprimed and finished with powder paintcapable of withstanding a 1000-hour saltspray test per ASTM B 117. Unit interiorcabinet surfaces shall be insulated with aminimum 1/2-inch thick foil faced insula-tion. Access panels shall be easily remov-able providing access to the blower, filter,heating compartment, and compressor/control box. Unit base rails shall be pro-vided with fork insertion slots and riggingholes. Condensate drain pan shall be ofsloped design to conform to ASHRAE 62.Unit shall be supplied ready for verticalairflow and be easily convertible tohorizontal airflow at or before installation.
Compressor(s)Unit shall be provided with fully hermeticscroll compressor(s) with internallyprotected safety controls.
CoilsThe evaporator and condenser coilsshall be fabricated of copper tubes withmechanically bonded aluminum platefins. They shall be pressure tested prior toassembly into the unit, and electronicallyleak tested after assembly.
Condenser FanA single direct drive propeller fan shalldischarge air vertically upward. The fanmotor shall be permanently lubricatedand have built-in overload protection.
Evaporator BlowerA single, double inlet, centrifugal wheelshall rotate in permanently lubricated ballbearings. The wheel shall be made fromsteel with corrosion resistant finish andshall be statically and dynamicallybalanced.
ACCESSORIESROOF CURBCurb shall be full perimeter type, comply-ing with the standards of the NationalRoofing Contractors Association. Designshall provide for drop-in of supply andreturn ducts prior to setting unit, andinclude an insulating panel for the rest ofthe curb area.
EconomizerEconomizer shall be completely assem-bled for field installation. Unit shall includeall controls and dampers including thebaro metric relief damper.
Manual Fresh Air DamperDamper shall consist of damper and rain-hood which is manually preset to admit upto 35% of outside air for field installation.
Motorized Fresh Air DamperDamper shall consist of motor, damper,and rainhood which can admit up to 35%of outside air for field installation.
Electric Heat KitsElectric heat kits shall be available in awide range of capacity with branch circuitfusing allowing single point wiring. Kitsshall be UL/cUL approved. Each kit shallbe offered as a field or factory installedoption.
Pressure ControlsHigh and low pressure controls shall beincluded for field or factory installation.
Low Ambient ControlLow ambient control shall be provided tocycle the condenser fan in response to condensing pressure and allow operation to 0 degrees F. The option shall be field orfactory installed.
Louver Panel KitsField or factory installed louver kits shall be provided for condenser coil protectionagainst hail or flying debris.
Mechanical SpecificationsTZCAC Series
27
GENERAL TERMS OF LIMITED WARRANTY*Thermal Zone® will furnish a replacement for any part of thisproduct which fails in normal use and service within theapplicable periods stated, in accordance with the terms ofthe limited warranty.*For complete details of the Limited and Conditional Warranties, includingapplicable terms and conditions, contact your local contractor or theManufacturer for a copy of the product warranty certificate.
Compressor3 Phase, Commercial Applications................Five (5) Years
Parts3 Phase, Commercial Applications..................One (1) Year
BEFORE PURCHASING THIS APPLIANCE, READ IMPORTANT ENERGY COST AND EFFICIENCY INFORMATION AVAILABLEFROM YOUR RETAILER.
Limited WarrantyTZCAC Series
Before proceeding with installation, referto installation instructions packagedwith each model, as well as complyingwith all Federal, State, Provincial, andLocal codes, regulations, and practices.
“In keeping with its policy of continuous progress and product improvement, the right is reserved to make changes without notice.”
PRINTED IN U.S.A. 10-12 QG FORM NO. STZ-958Supersedes Form No STZ 941 Rev 3