Senturion TM I Wall System 1. Senturion I Wall System Application (Plan VIew) 2. Senturion I Wall System Application (Isometric View) 3. Aesthetic Groove (Plan View) 4. Insulation Boards / Reinforcing Mesh Application at Openings 5. Clad Window Jamb With Aesthetic Band 6. Clad Window Head With Aesthetic Band 7. Clad Window Sill With Aesthetic Band 8. Clad Window Jamb 9. Clad Window Head 10. Clad Window Sill 11. Primed Window Jamb 12. Primed Window Head 13. Primed Window Sill 14. Expansion Joint Detail at Floorline of Wood Frame Construction 15. Expansion Joint at Change in Substrate (Plan View) 16. Termination at Soffit/Gable End 17. Downspout Application (Plan View) 18. Pipe Penetration 19. Light Fixture 20. Dryer Vent 21. Termination at Top of Deck 22. Termination at Bottom of Deck 23. Termination at Foundation 24. Termination at Foundation 25. Termination at Brick or Stone 26. Termination at Brick or Stone 27. Kick-out Flashing Detail 1017662 TYPICAL DETAILS

Senturion TM IWallSystem 1017662 - BASF...kick-out flashing min .100mm(4") min.50mm(2") tyvek ® stuccowrap ® senergylamina: •senergybasecoat •senergyreinforcingmesh •senergyfinishcoat

  • Upload
    others

  • View
    4

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Senturion TM IWallSystem 1017662 - BASF...kick-out flashing min .100mm(4") min.50mm(2") tyvek ® stuccowrap ® senergylamina: •senergybasecoat •senergyreinforcingmesh •senergyfinishcoat

SenturionTM I Wall System

1. Senturion I Wall SystemApplication (Plan VIew)

2. Senturion I Wall SystemApplication (Isometric View)

3. Aesthetic Groove (Plan View)

4. Insulation Boards / ReinforcingMesh Application at Openings

5. Clad Window Jamb WithAesthetic Band

6. Clad Window Head WithAesthetic Band

7. Clad Window Sill WithAesthetic Band

8. Clad Window Jamb

9. Clad Window Head

10. Clad Window Sill

11. Primed Window Jamb

12. Primed Window Head

13. Primed Window Sill

14. Expansion Joint Detail atFloorline of Wood FrameConstruction

15. Expansion Joint at Change inSubstrate (Plan View)

16. Termination at Soffit/Gable End

17. Downspout Application(Plan View)

18. Pipe Penetration

19. Light Fixture

20. Dryer Vent

21. Termination at Top of Deck

22. Termination at Bottom of Deck

23. Termination at Foundation

24. Termination at Foundation

25. Termination at Brick or Stone

26. Termination at Brick or Stone

27. Kick-out Flashing Detail

1017662TYPICAL DETAILS

Page 2: Senturion TM IWallSystem 1017662 - BASF...kick-out flashing min .100mm(4") min.50mm(2") tyvek ® stuccowrap ® senergylamina: •senergybasecoat •senergyreinforcingmesh •senergyfinishcoat

SI-01 TYPICAL SENTURION I WALL SYSTEM APPLICATION (PLAN VIEW)

SI-02 TYPICAL SENTURION I WALL SYSTEM APPLICATION(ISOMETRIC VIEW)

ACCEPTABLE SHEATHING

SENERGY INSULATION BOARD

FRAMING

SENERGY REINFORCING MESH

SENERGY BASE COAT

SENERGY FINISH COAT

ACCEPTABLE SHEATHING

SENERGY INSULATION BOARD

MECHANICAL FASTENER

FRAMING

SENERGY LAMINA:• SENERGY BASE COAT• SENERGY REINFORCINGMESH

• SENERGY FINISH COAT

FLASHING

MECHANICAL FASTENER

TYVEK® STUCCOWRAP®

TYVEK® STUCCOWRAP®

12/07

FRAMING, ACCEPTABLE SHEATHINGAND SEALANT BY OTHERS

NOTE:

Page 3: Senturion TM IWallSystem 1017662 - BASF...kick-out flashing min .100mm(4") min.50mm(2") tyvek ® stuccowrap ® senergylamina: •senergybasecoat •senergyreinforcingmesh •senergyfinishcoat

SENERGY LAMINA:• SENERGY BASE COAT• SENERGY REINFORCINGMESH

• SENERGY FINISH COAT

SI-03 TYPICAL AESTHETIC GROOVE (PLAN VIEW)

SI-04 TYPICAL INSULATION BOARDS/REINFORCING MESHAPPLICATION AT OPENINGS

WRAP SENERGY BASE COAT ANDFLEXGUARD 4 REINFORCING MESHAT INSULATION BOARD EDGES

SENERGY INSULATION BOARD

STAGGER INSULATION BOARDJOINTS AT CORNER OF OPENINGS

FLEXGUARD 4 REINFORCING MESH EMBED-DED IN SENERGY BASE COAT

ACCEPTABLE SHEATHING

SENERGY INSULATIONBOARD

FRAMING

AESTHETIC GROOVE

MIN. 19 mm (3/4")

MECHANICAL FASTENER

TYVEK® STUCCOWRAP®

NOTE:• TYPICAL AT WINDOWS, DOORS, ETC.• MAINTAIN A MIN. 13 mm (1/2") PERIMETERSEALANT JOINT

• FLASHINGS ARE BY OTHERS AND SHALL BEAS PER DESIGN/CODE REQUIREMENTS

229 mm (9")

305 mm (12")

12/07

FRAMING, ACCEPTABLE SHEATHINGAND SEALANT BY OTHERS

NOTE:

Page 4: Senturion TM IWallSystem 1017662 - BASF...kick-out flashing min .100mm(4") min.50mm(2") tyvek ® stuccowrap ® senergylamina: •senergybasecoat •senergyreinforcingmesh •senergyfinishcoat

WRAP BASE COAT ANDSENERGY REINFORCING MESH

SENERGY LAMINA:• SENERGY BASE COAT• SENERGY REINFORCING MESH• SENERGY FINISH COAT

SI-05 TYPICAL CLAD WINDOW JAMB WITH AESTHETIC BAND

SI-06 TYPICAL CLAD WINDOW HEAD WITH AESTHETIC BAND

ACCEPTABLE SHEATHING

SENERGY INSULATION BOARD

FLASHING W/ SEALANT

EPS AESTHETIC BAND

FRAMING

CLAD WINDOW

SENERGY LAMINA:• SENERGY BASE COAT• SENERGY REINFORCING MESH• SENERGY FINISH COAT

ACCEPTABLE SHEATHING

SENERGY INSULATION BOARD

SENERGY BASE COAT

FRAMING

CLAD WINDOW

BACKER ROD AND SEALANT

SENERGY ASAP

MECHANICAL FASTENER

TYVEK® STUCCOWRAP®

TYVEK® STUCCOWRAP®

WRAP BASE COAT ANDSENERGY REINFORCING MESHMECHANICAL FASTENER

SENERWRAP/SENERFLASHWITH FLASHING PRIMER

SENERGY BASE COAT

NOTE:FLASHINGS ARE BY OTHERS ANDSHALL BE AS PER DESIGN/CODEREQUIREMENTS

EPS AESTHETIC BAND

12/07

FRAMING, ACCEPTABLE SHEATHINGAND SEALANT BY OTHERS

NOTE:

MIN 6:12 SLOPE

Page 5: Senturion TM IWallSystem 1017662 - BASF...kick-out flashing min .100mm(4") min.50mm(2") tyvek ® stuccowrap ® senergylamina: •senergybasecoat •senergyreinforcingmesh •senergyfinishcoat

SENERGY LAMINA:• SENERGY BASE COAT• SENERGY REINFORCING MESH• SENERGY FINISH COAT

SENERGY LAMINA:• SENERGY BASE COAT• SENERGY REINFORCING MESH• SENERGY FINISH COAT

SENERWRAP/SENERFLASH WITHFLASHING PRIMER

SI-07 TYPICAL CLAD WINDOW SILL WITH AESTHETIC BAND

SI-08 TYPICAL CLAD WINDOW JAMB

ACCEPTABLE SHEATHING

SENERGY INSULATION BOARD

BACKER ROD AND SEALANT

SENERGY ASAP

ACCEPTABLE SHEATHINGSENERGY INSULATION BOARD

SENERGY BASE COAT

BACKER ROD AND SEALANT

SENERGY ASAP

CLAD WINDOW

FRAMING

EPS AESTHETIC BAND

MECHANICAL FASTENER

MIN. 6:12 SLOPE

FRAMING

CLAD WINDOW

MECHANICAL FASTENER

TYVEK® STUCCOWRAP®

TYVEK® STUCCOWRAP®

WRAP BASE COAT ANDSENERGY REINFORCING MESH

WRAP BASE COAT ANDSENERGY REINFORCING MESH

SENERWRAP/SENERFLASH WITHFLASHING PRIMER

12/07

FRAMING, ACCEPTABLE SHEATHINGAND SEALANT BY OTHERS

NOTE:

Page 6: Senturion TM IWallSystem 1017662 - BASF...kick-out flashing min .100mm(4") min.50mm(2") tyvek ® stuccowrap ® senergylamina: •senergybasecoat •senergyreinforcingmesh •senergyfinishcoat

SENERGY LAMINA:• SENERGY BASE COAT• SENERGY REINFORCING MESH• SENERGY FINISH COAT

SENERGY LAMINA:• SENERGY BASE COAT• SENERGY REINFORCING MESH• SENERGY FINISH COAT

SI-09 TYPICAL CLAD WINDOW HEAD

SI-10 TYPICAL CLAD WINDOW SILL

ACCEPTABLE SHEATHING

FRAMING

SENERGY INSULATION BOARD

CLAD WINDOW

ACCEPTABLE SHEATHING

FRAMING

SENERGY INSULATION BOARD

FLASHING W/ SEALANT

CLAD WINDOW

MECHANICAL FASTENER

BACKER ROD AND SEALANT

MECHANICAL FASTENER

SENERGY ASAP

TYVEK® STUCCOWRAP®

TYVEK® STUCCOWRAP®

NOTE:FLASHINGS ARE BY OTHERS ANDSHALL BE AS PER DESIGN/CODEREQUIREMENTS

WRAP BASE COAT ANDSENERGY REINFORCING MESH

WRAP BASE COAT ANDSENERGY REINFORCING MESH

SENERWRAP/SENERFLASH WITHFLASHING PRIMER

12/07

FRAMING, ACCEPTABLE SHEATHINGAND SEALANT BY OTHERS

NOTE:

Page 7: Senturion TM IWallSystem 1017662 - BASF...kick-out flashing min .100mm(4") min.50mm(2") tyvek ® stuccowrap ® senergylamina: •senergybasecoat •senergyreinforcingmesh •senergyfinishcoat

SENERGY LAMINA:• SENERGY BASE COAT• SENERGY REINFORCING MESH• SENERGY FINISH COAT

SI-12 TYPICAL PRIMED WINDOW HEAD

ACCEPTABLE SHEATHING

FRAMING

SI-11 TYPICAL PRIMED WINDOW JAMB

ACCEPTABLE SHEATHING

FRAMING

SENERGY INSULATION BOARD

BACKER ROD AND SEALANT

MECHANICAL FASTENER

SENERGY ASAP

PRIMED WINDOW

FLASHING W/ SEALANT

PRIMED WINDOW

MECHANICAL FASTENER

TYVEK® STUCCOWRAP®

TYVEK® STUCCOWRAP®

WRAP BASE COAT ANDSENERGY REINFORCING MESH

SENERWRAP/SENERFLASH WITHFLASHING PRIMER

SENERGY INSULATION BOARD

SENERGY LAMINA:• SENERGY BASE COAT• SENERGY REINFORCING MESH• SENERGY FINISH COAT

WRAP BASE COAT ANDSENERGY REINFORCING MESH

NOTE:FLASHINGS ARE BY OTHERS ANDSHALL BE AS PER DESIGN/CODEREQUIREMENTS

12/07

FRAMING, ACCEPTABLE SHEATHINGAND SEALANT BY OTHERS

NOTE:

Page 8: Senturion TM IWallSystem 1017662 - BASF...kick-out flashing min .100mm(4") min.50mm(2") tyvek ® stuccowrap ® senergylamina: •senergybasecoat •senergyreinforcingmesh •senergyfinishcoat

SI-13 TYPICAL PRIMED WINDOW SILL

SI-14 TYPICAL EXPANSION JOINT DETAIL AT FLOORLINE OFWOOD FRAME CONSTRUCTION

ACCEPTABLE SHEATHING

TYPICAL WOOD FRAMING

SENERGY INSULATION BOARD

BACKER ROD AND SEALANT

MIN. 19 mm (3/4")

ACCEPTABLE SHEATHING

FRAMING

SENERGY INSULATION BOARD

BACKER ROD AND SEALANT

MECHANICAL FASTENER

SENERGY ASAP

PRIMED WINDOW

SENERGY ASAP

TYVEK® STUCCOWRAP®

SENERGY LAMINA:• SENERGY BASE COAT• SENERGY REINFORCING MESH• SENERGY FINISH COAT

WRAP BASE COAT ANDSENERGY REINFORCING MESH

SENERWRAP/SENERFLASH WITHFLASHING PRIMER

TYVEK® STUCCOWRAP®

SENERFLASH 9 W/ FLASHINGPRIMER

WRAP BASE COAT ANDSENERGY REINFORCING MESH

MECHANICAL FASTENER

SENERGY LAMINA:• SENERGY BASE COAT• SENERGY REINFORCING MESH• SENERGY FINISH COAT

12/07

FRAMING, ACCEPTABLE SHEATHINGAND SEALANT BY OTHERS

NOTE:

Page 9: Senturion TM IWallSystem 1017662 - BASF...kick-out flashing min .100mm(4") min.50mm(2") tyvek ® stuccowrap ® senergylamina: •senergybasecoat •senergyreinforcingmesh •senergyfinishcoat

SI-15 TYPICAL EXPANSION JOINT AT CHANGE IN SUBSTRATE(PLAN VIEW)

SI-16 TYPICAL TERMINATION AT SOFFIT/GABLE END

ACCEPTABLE SHEATHING

BLOCKING

FRAMING

SENERGY INSULATIONBOARD

SOFFIT

FRIEZE BOARD

ACCEPTABLE SHEATHING

SENERGY INSULATION BOARD

BACKER ROD AND SEALANT

SENERGY ASAP

NOTE: JOINT WIDTH PER DESIGN

TRIM

TYVEK® STUCCOWRAP®

TYVEK® STUCCOWRAP®

SENERGY LAMINA:• SENERGY BASE COAT• SENERGY REINFORCING MESH• SENERGY FINISH COAT

WRAP BASE COAT ANDSENERGY REINFORCING MESH

SENERFLASH 9/SENERWRAPW/ FLASHING PRIMER

ACCEPTABLE SUBSTRATE

SENERGY LAMINA:• SENERGY BASE COAT• SENERGY REINFORCING MESH• SENERGY FINISH COAT

WRAP BASE COAT ANDSENERGY REINFORCINGMESH

MIN. 50 mm (2")

12/07

FRAMING, ACCEPTABLE SHEATHINGAND SEALANT BY OTHERS

NOTE:

Page 10: Senturion TM IWallSystem 1017662 - BASF...kick-out flashing min .100mm(4") min.50mm(2") tyvek ® stuccowrap ® senergylamina: •senergybasecoat •senergyreinforcingmesh •senergyfinishcoat

SI-17 TYPICAL DOWNSPOUT APPLICATION (PLAN VIEW)

SI-18 TYPICAL PIPE PENETRATION

ACCEPTABLE SHEATHING

FRAMING

SENERGY INSULATION BOARD

SEALANT AT PERIMETER OFPENETRATION

BACKER RODAND SEALANT

SENERGY ASAP

MIN. 13 MM (1/2")

ACCEPTABLE SHEATHING

FRAMING

SENERGY INSULATION BOARD

DOWNSPOUT

SLEEVE

DOWNSPOUT STRAP

SEALANT

FASTENER SET IN SEALANT

TYVEK® STUCCOWRAP®

TYVEK® STUCCOWRAP®

SENERGY LAMINA:• SENERGY BASE COAT• SENERGY REINFORCING MESH• SENERGY FINISH COAT

SENERGY LAMINA:• SENERGY BASE COAT• SENERGY REINFORCING MESH• SENERGY FINISH COAT

WRAP BASE COAT ANDSENERGY REINFORCING MESH

12/07

FRAMING, ACCEPTABLE SHEATHINGAND SEALANT BY OTHERS

NOTE:

Page 11: Senturion TM IWallSystem 1017662 - BASF...kick-out flashing min .100mm(4") min.50mm(2") tyvek ® stuccowrap ® senergylamina: •senergybasecoat •senergyreinforcingmesh •senergyfinishcoat

SI-19 TYPICAL LIGHT FIXTURE

SI-20 TYPICAL DRYER VENT

ACCEPTABLE SHEATHING

DRYER VENT

FRAMING

SENERGY INSULATION BOARD

ACCEPTABLE SHEATHING

FRAMING

SENERGY INSULATION BOARD

SET FLANGE IN SEALANT

SMALL LIGHT FIXTURE

FASTENER SET IN SEALANT

SET FLANGE IN SEALANT

FASTENER THROUGHNYLON SLEEVE

TYVEK® STUCCOWRAP®

SENERGY LAMINA:• SENERGY BASE COAT• SENERGY REINFORCING MESH• SENERGY FINISH COAT

WRAP BASE COAT ANDSENERGY REINFORCING MESH

WIRE OPENING

TYVEK® STUCCOWRAP®

SENERGY LAMINA:• SENERGY BASE COAT• SENERGY REINFORCING MESH• SENERGY FINISH COAT

WRAP BASE COAT ANDSENERGY REINFORCING MESH

SEALANT AT PERIMETER OFPENETRATION

12/07

FRAMING, ACCEPTABLE SHEATHINGAND SEALANT BY OTHERS

NOTE:

Page 12: Senturion TM IWallSystem 1017662 - BASF...kick-out flashing min .100mm(4") min.50mm(2") tyvek ® stuccowrap ® senergylamina: •senergybasecoat •senergyreinforcingmesh •senergyfinishcoat

SI-21 TYPICAL TERMINATION AT TOP OF DECK

SI-22 TYPICAL TERMINATION AT BOTTOM OF DECK

ACCEPTABLE SHEATHING

FRAMING

SENERGY INSULATION BOARD

FLASHING

FRAMING

SENERGY INSULATION BOARD

JOIST

MECHANICAL FASTENER

FLASHING SET IN SEALANT

DECK

FLASHING

JOIST

MECHANICAL FASTENER

SEALANT

MIN. 50 mm (2")

ACCEPTABLE SHEATHING

SENERGY LAMINA:• SENERGY BASE COAT• SENERGY REINFORCING MESH• SENERGY FINISH COAT

WRAP BASE COAT ANDSENERGY REINFORCING MESH

TYVEK® STUCCOWRAP®

MIN. 25 mm (1")

MIN. 50 mm (2")

MIN. 50 mm (2")

SENERGY LAMINA:• SENERGY BASE COAT• SENERGY REINFORCING MESH• SENERGY FINISH COAT

TYVEK® STUCCOWRAP®

TYVEK® STUCCOWRAP®

12/07

FRAMING, ACCEPTABLE SHEATHINGAND SEALANT BY OTHERS

NOTE:

Page 13: Senturion TM IWallSystem 1017662 - BASF...kick-out flashing min .100mm(4") min.50mm(2") tyvek ® stuccowrap ® senergylamina: •senergybasecoat •senergyreinforcingmesh •senergyfinishcoat

SENERGY LAMINA:• SENERGY BASE COAT• SENERGY REINFORCING MESH• SENERGY FINISH COAT

SENERGY LAMINA:• SENERGY BASE COAT• SENERGY REINFORCING MESH• SENERGY FINISH COAT

SI-23 TYPICAL TERMINATION AT FOUNDATION

SI-24 TYPICAL TERMINATION AT FOUNDATION

ACCEPTABLE SHEATHING

FRAMING

FOUNDATION

SENERGY INSULATION BOARD

FLASHING

MECHANICAL FASTENER

SEALANT

STARTER TRACK W/ WEEPHOLES

TYVEK® STUCCOWRAP®

SENERWRAP/SENERFLASH 4W/FLASHING PRIMER

WRAP BASE COAT ANDSENERGY REINFORCING MESH

NOTE:TERMINATE SENTURION I DESIGNSYSTEM MIN. 203 mm (8") ABOVEGRADE.

MIN. 50 mm (2")MAX. 305 mm (12")

ACCEPTABLE SHEATHING

FRAMING

FOUNDATION

SENERGY INSULATION BOARD

MECHANICAL FASTENER

SEALANT

TYVEK® STUCCOWRAP®

SENERFLASH 4 W/ FLASHINGPRIMER

NOTE:TERMINATE SENTURION I DESIGNSYSTEM MIN. 203 mm (8") ABOVEGRADE.

MIN. 50 mm (2")MAX. 305 mm (12")

12/07

FRAMING, ACCEPTABLE SHEATHINGAND SEALANT BY OTHERS

NOTE:

Page 14: Senturion TM IWallSystem 1017662 - BASF...kick-out flashing min .100mm(4") min.50mm(2") tyvek ® stuccowrap ® senergylamina: •senergybasecoat •senergyreinforcingmesh •senergyfinishcoat

SI-25 TYPICAL TERMINATION AT BRICK OF STONE

ACCEPTABLE SHEATHING

FRAMING

SENERGY INSULATION BOARD

MECHANICAL FASTENER

FLASHING SET IN SEALANT

BRICK OR STONE

SENERGY LAMINA:• SENERGY BASE COAT• SENERGY REINFORCING MESH• SENERGY FINISH COAT

SENERWRAP/SENERFLASH 4 W/FLASHING PRIMER

TYVEK® STUCCOWRAP®

WRAP BASE COAT ANDSENERGY REINFORCING MESH

SI-26 TYPICAL TERMINATION AT BRICK OF STONE

ACCEPTABLE SHEATHING

FRAMING

SENERGY INSULATION BOARD

MECHANICAL FASTENER

BACKER ROD AND SEALANT

SENERGY ASAP

BRICK OR STONE

SENERGY LAMINA:• SENERGY BASE COAT• SENERGY REINFORCING MESH• SENERGY FINISH COAT

SENERSHIELD-R OR SECONDARYMOISTURE PROTECTION BARRIER

WRAP BASE COAT ANDSENERGY REINFORCING MESH

NOTE:TERMINATION OF BRICK OR STONEMUST HAVE A MEANS FOR MOISTURETO ESCAPE.

12/07

FRAMING, ACCEPTABLE SHEATHINGAND SEALANT BY OTHERS

NOTE:

Page 15: Senturion TM IWallSystem 1017662 - BASF...kick-out flashing min .100mm(4") min.50mm(2") tyvek ® stuccowrap ® senergylamina: •senergybasecoat •senergyreinforcingmesh •senergyfinishcoat

SI-27 TYPICAL KICK-OUT FLASHING DETAIL

ACCEPTABLE SHEATHING

SENTURION I WALL SYSTEM

STEP FLASHING

BACKER ROD AND SEALANT

ROOF SHINGLES

BUILDING PAPER

DRIP EDGE

KICK-OUT FLASHING

MIN. 100 mm (4")

MIN. 50 mm (2")

TYVEK® STUCCOWRAP®

SENERGY LAMINA:• SENERGY BASE COAT• SENERGY REINFORCING MESH• SENERGY FINISH COAT

NOTE:• KICK-OUT FLASHING MUST BEANGLED 100˚ MIN.TO ALLOW FORPROPER DRAINAGE.• KICK-OUT FLASHING SEAMS MUST

BE SOLDERED OR SEALED WITHAPPROPRIATE SEALANT.

• TERMINATE SENTURION I WALLSYSTEM MIN. 50 mm (2")ABOVE ROOF.

12/07

FRAMING, ACCEPTABLE SHEATHINGAND SEALANT BY OTHERS

NOTE:

Page 16: Senturion TM IWallSystem 1017662 - BASF...kick-out flashing min .100mm(4") min.50mm(2") tyvek ® stuccowrap ® senergylamina: •senergybasecoat •senergyreinforcingmesh •senergyfinishcoat

BASF Wall Systems

3550 St. Johns Bluff Road SouthJacksonville, FL 32224-2614Phone 800 • 221 • 9255Fax 904 • 996 • 6300www.senergy.basf.com

©2007 BASF Construction Chemicals, LLC.

Printed in U.S.A. 12/07

General NotesBASF Wall Systems is an operating unit ofBASF Construction Chemicals, LLC. (hereinafter referred to as “BASF Wall Systems”).These details are presented in good faith byBASF Wall Systems and represent typicaland/or general conditions. They are offered asa guide for consideration to assist the designer,specifier, installer and/or owner. The responsibilityremains with the user for the design of anysystem. For conditions not shown, consultBASFWall Systems for specific recommendations.Consult current Senergy technical bulletins forsuch information as acceptable sealants,insulation attachment methods, installationof air/weather barriers, residential policy, codeand test reports, geo-climatic considerations,etc. Installation requirements for sealant (jointsize configuration, primers, bond breakers)shall be in accordance with sealantmanufacturer’s specifications and instructions.

Technical SupportConsult the BASF Wall Systems TechnicalServices Department for specific recommendationsconcerning all other applications. Consult theSenergy website, www.senergy.basf.com, foradditional information about products andsystems and for updated literature.

Residential PolicyOn one and two-family residential framedconstruction, BASF Wall Systems requiresthat the wall system selected be one thatincludes provisions for water drainage.The choices include Senturion® line ofwater drainage EIFS, commercial Senerflex®Channeled Adhesive or Channeled InsulationDesign, Senergy Stucco Wall System, andSenergy Cement-Board StuccoTM Systems.There are no exceptions to this policy. Underno circumstances will BASF Wall Systemswarrant the use of any other system onthis type of construction without expressedwritten authorization from BASF Wall Systems[Residential construction using EIFS on masonry(CMU) or poured concrete does not requirethe additional water drainage provisionsdescribed above. Senergy Exterior SurfacingSystems for insulating concrete forms arealso acceptable.] See the Senergy ResidentialPolicy Bulletin for a more detailed discussion ofthis topic. Consult our Technical ServicesDepartment for specific recommendationsconcerning all other applications. Consult theSenergy website, www.senergy.basf.com foradditional information about products andsystems and for updated literature.

DisclaimerThis information and all further technicaladvice are based on BASF Wall Systems’present knowledge and experience. However,BASF assumes no liability for providing suchinformation and advice including the extentto which such information and advice mayrelate to existing third party intellectual propertyrights, especially patent rights. In particular,BASF Wall Systems disclaims any and allCONDITIONS AND WARRANTIES, WHETHEREXPRESS OR IMPLIED, INCLUDING THEIMPLIED WARRANTIES OF FITNESS FOR APARTICULAR PURPOSE OR MERCHANTABILITY.BASF WALL SYSTEMS SHALL NOT BERESPONSIBLE FOR CONSEQUENTIAL, INDIRECTOR INCIDENTAL DAMAGES (INCLUDING LOSSOF PROFITS) OF ANY KIND. BASF Wall Systemsreserves the right to make any changesaccording to technological progress or furtherdevelopments. It is the customer’s responsibilityand obligation to carefully inspect and test anyincoming goods. Performance of the product(s)described herein should be verified by testingand carried out only by qualified experts. It isthe sole responsibility of the customer to carryout and arrange for any such testing. Referenceto trade names used by other companies isneither a recommendation, nor an endorsementof any product and does not imply that similarproducts could not be used.