SenturionTM I Wall System
1. Senturion I Wall SystemApplication (Plan VIew)
2. Senturion I Wall SystemApplication (Isometric View)
3. Aesthetic Groove (Plan View)
4. Insulation Boards / ReinforcingMesh Application at Openings
5. Clad Window Jamb WithAesthetic Band
6. Clad Window Head WithAesthetic Band
7. Clad Window Sill WithAesthetic Band
8. Clad Window Jamb
9. Clad Window Head
10. Clad Window Sill
11. Primed Window Jamb
12. Primed Window Head
13. Primed Window Sill
14. Expansion Joint Detail atFloorline of Wood FrameConstruction
15. Expansion Joint at Change inSubstrate (Plan View)
16. Termination at Soffit/Gable End
17. Downspout Application(Plan View)
18. Pipe Penetration
19. Light Fixture
20. Dryer Vent
21. Termination at Top of Deck
22. Termination at Bottom of Deck
23. Termination at Foundation
24. Termination at Foundation
25. Termination at Brick or Stone
26. Termination at Brick or Stone
27. Kick-out Flashing Detail
1017662TYPICAL DETAILS
SI-01 TYPICAL SENTURION I WALL SYSTEM APPLICATION (PLAN VIEW)
SI-02 TYPICAL SENTURION I WALL SYSTEM APPLICATION(ISOMETRIC VIEW)
ACCEPTABLE SHEATHING
SENERGY INSULATION BOARD
FRAMING
SENERGY REINFORCING MESH
SENERGY BASE COAT
SENERGY FINISH COAT
ACCEPTABLE SHEATHING
SENERGY INSULATION BOARD
MECHANICAL FASTENER
FRAMING
SENERGY LAMINA:• SENERGY BASE COAT• SENERGY REINFORCINGMESH
• SENERGY FINISH COAT
FLASHING
MECHANICAL FASTENER
TYVEK® STUCCOWRAP®
TYVEK® STUCCOWRAP®
12/07
FRAMING, ACCEPTABLE SHEATHINGAND SEALANT BY OTHERS
NOTE:
SENERGY LAMINA:• SENERGY BASE COAT• SENERGY REINFORCINGMESH
• SENERGY FINISH COAT
SI-03 TYPICAL AESTHETIC GROOVE (PLAN VIEW)
SI-04 TYPICAL INSULATION BOARDS/REINFORCING MESHAPPLICATION AT OPENINGS
WRAP SENERGY BASE COAT ANDFLEXGUARD 4 REINFORCING MESHAT INSULATION BOARD EDGES
SENERGY INSULATION BOARD
STAGGER INSULATION BOARDJOINTS AT CORNER OF OPENINGS
FLEXGUARD 4 REINFORCING MESH EMBED-DED IN SENERGY BASE COAT
ACCEPTABLE SHEATHING
SENERGY INSULATIONBOARD
FRAMING
AESTHETIC GROOVE
MIN. 19 mm (3/4")
MECHANICAL FASTENER
TYVEK® STUCCOWRAP®
NOTE:• TYPICAL AT WINDOWS, DOORS, ETC.• MAINTAIN A MIN. 13 mm (1/2") PERIMETERSEALANT JOINT
• FLASHINGS ARE BY OTHERS AND SHALL BEAS PER DESIGN/CODE REQUIREMENTS
229 mm (9")
305 mm (12")
12/07
FRAMING, ACCEPTABLE SHEATHINGAND SEALANT BY OTHERS
NOTE:
WRAP BASE COAT ANDSENERGY REINFORCING MESH
SENERGY LAMINA:• SENERGY BASE COAT• SENERGY REINFORCING MESH• SENERGY FINISH COAT
SI-05 TYPICAL CLAD WINDOW JAMB WITH AESTHETIC BAND
SI-06 TYPICAL CLAD WINDOW HEAD WITH AESTHETIC BAND
ACCEPTABLE SHEATHING
SENERGY INSULATION BOARD
FLASHING W/ SEALANT
EPS AESTHETIC BAND
FRAMING
CLAD WINDOW
SENERGY LAMINA:• SENERGY BASE COAT• SENERGY REINFORCING MESH• SENERGY FINISH COAT
ACCEPTABLE SHEATHING
SENERGY INSULATION BOARD
SENERGY BASE COAT
FRAMING
CLAD WINDOW
BACKER ROD AND SEALANT
SENERGY ASAP
MECHANICAL FASTENER
TYVEK® STUCCOWRAP®
TYVEK® STUCCOWRAP®
WRAP BASE COAT ANDSENERGY REINFORCING MESHMECHANICAL FASTENER
SENERWRAP/SENERFLASHWITH FLASHING PRIMER
SENERGY BASE COAT
NOTE:FLASHINGS ARE BY OTHERS ANDSHALL BE AS PER DESIGN/CODEREQUIREMENTS
EPS AESTHETIC BAND
12/07
FRAMING, ACCEPTABLE SHEATHINGAND SEALANT BY OTHERS
NOTE:
MIN 6:12 SLOPE
SENERGY LAMINA:• SENERGY BASE COAT• SENERGY REINFORCING MESH• SENERGY FINISH COAT
SENERGY LAMINA:• SENERGY BASE COAT• SENERGY REINFORCING MESH• SENERGY FINISH COAT
SENERWRAP/SENERFLASH WITHFLASHING PRIMER
SI-07 TYPICAL CLAD WINDOW SILL WITH AESTHETIC BAND
SI-08 TYPICAL CLAD WINDOW JAMB
ACCEPTABLE SHEATHING
SENERGY INSULATION BOARD
BACKER ROD AND SEALANT
SENERGY ASAP
ACCEPTABLE SHEATHINGSENERGY INSULATION BOARD
SENERGY BASE COAT
BACKER ROD AND SEALANT
SENERGY ASAP
CLAD WINDOW
FRAMING
EPS AESTHETIC BAND
MECHANICAL FASTENER
MIN. 6:12 SLOPE
FRAMING
CLAD WINDOW
MECHANICAL FASTENER
TYVEK® STUCCOWRAP®
TYVEK® STUCCOWRAP®
WRAP BASE COAT ANDSENERGY REINFORCING MESH
WRAP BASE COAT ANDSENERGY REINFORCING MESH
SENERWRAP/SENERFLASH WITHFLASHING PRIMER
12/07
FRAMING, ACCEPTABLE SHEATHINGAND SEALANT BY OTHERS
NOTE:
SENERGY LAMINA:• SENERGY BASE COAT• SENERGY REINFORCING MESH• SENERGY FINISH COAT
SENERGY LAMINA:• SENERGY BASE COAT• SENERGY REINFORCING MESH• SENERGY FINISH COAT
SI-09 TYPICAL CLAD WINDOW HEAD
SI-10 TYPICAL CLAD WINDOW SILL
ACCEPTABLE SHEATHING
FRAMING
SENERGY INSULATION BOARD
CLAD WINDOW
ACCEPTABLE SHEATHING
FRAMING
SENERGY INSULATION BOARD
FLASHING W/ SEALANT
CLAD WINDOW
MECHANICAL FASTENER
BACKER ROD AND SEALANT
MECHANICAL FASTENER
SENERGY ASAP
TYVEK® STUCCOWRAP®
TYVEK® STUCCOWRAP®
NOTE:FLASHINGS ARE BY OTHERS ANDSHALL BE AS PER DESIGN/CODEREQUIREMENTS
WRAP BASE COAT ANDSENERGY REINFORCING MESH
WRAP BASE COAT ANDSENERGY REINFORCING MESH
SENERWRAP/SENERFLASH WITHFLASHING PRIMER
12/07
FRAMING, ACCEPTABLE SHEATHINGAND SEALANT BY OTHERS
NOTE:
SENERGY LAMINA:• SENERGY BASE COAT• SENERGY REINFORCING MESH• SENERGY FINISH COAT
SI-12 TYPICAL PRIMED WINDOW HEAD
ACCEPTABLE SHEATHING
FRAMING
SI-11 TYPICAL PRIMED WINDOW JAMB
ACCEPTABLE SHEATHING
FRAMING
SENERGY INSULATION BOARD
BACKER ROD AND SEALANT
MECHANICAL FASTENER
SENERGY ASAP
PRIMED WINDOW
FLASHING W/ SEALANT
PRIMED WINDOW
MECHANICAL FASTENER
TYVEK® STUCCOWRAP®
TYVEK® STUCCOWRAP®
WRAP BASE COAT ANDSENERGY REINFORCING MESH
SENERWRAP/SENERFLASH WITHFLASHING PRIMER
SENERGY INSULATION BOARD
SENERGY LAMINA:• SENERGY BASE COAT• SENERGY REINFORCING MESH• SENERGY FINISH COAT
WRAP BASE COAT ANDSENERGY REINFORCING MESH
NOTE:FLASHINGS ARE BY OTHERS ANDSHALL BE AS PER DESIGN/CODEREQUIREMENTS
12/07
FRAMING, ACCEPTABLE SHEATHINGAND SEALANT BY OTHERS
NOTE:
SI-13 TYPICAL PRIMED WINDOW SILL
SI-14 TYPICAL EXPANSION JOINT DETAIL AT FLOORLINE OFWOOD FRAME CONSTRUCTION
ACCEPTABLE SHEATHING
TYPICAL WOOD FRAMING
SENERGY INSULATION BOARD
BACKER ROD AND SEALANT
MIN. 19 mm (3/4")
ACCEPTABLE SHEATHING
FRAMING
SENERGY INSULATION BOARD
BACKER ROD AND SEALANT
MECHANICAL FASTENER
SENERGY ASAP
PRIMED WINDOW
SENERGY ASAP
TYVEK® STUCCOWRAP®
SENERGY LAMINA:• SENERGY BASE COAT• SENERGY REINFORCING MESH• SENERGY FINISH COAT
WRAP BASE COAT ANDSENERGY REINFORCING MESH
SENERWRAP/SENERFLASH WITHFLASHING PRIMER
TYVEK® STUCCOWRAP®
SENERFLASH 9 W/ FLASHINGPRIMER
WRAP BASE COAT ANDSENERGY REINFORCING MESH
MECHANICAL FASTENER
SENERGY LAMINA:• SENERGY BASE COAT• SENERGY REINFORCING MESH• SENERGY FINISH COAT
12/07
FRAMING, ACCEPTABLE SHEATHINGAND SEALANT BY OTHERS
NOTE:
SI-15 TYPICAL EXPANSION JOINT AT CHANGE IN SUBSTRATE(PLAN VIEW)
SI-16 TYPICAL TERMINATION AT SOFFIT/GABLE END
ACCEPTABLE SHEATHING
BLOCKING
FRAMING
SENERGY INSULATIONBOARD
SOFFIT
FRIEZE BOARD
ACCEPTABLE SHEATHING
SENERGY INSULATION BOARD
BACKER ROD AND SEALANT
SENERGY ASAP
NOTE: JOINT WIDTH PER DESIGN
TRIM
TYVEK® STUCCOWRAP®
TYVEK® STUCCOWRAP®
SENERGY LAMINA:• SENERGY BASE COAT• SENERGY REINFORCING MESH• SENERGY FINISH COAT
WRAP BASE COAT ANDSENERGY REINFORCING MESH
SENERFLASH 9/SENERWRAPW/ FLASHING PRIMER
ACCEPTABLE SUBSTRATE
SENERGY LAMINA:• SENERGY BASE COAT• SENERGY REINFORCING MESH• SENERGY FINISH COAT
WRAP BASE COAT ANDSENERGY REINFORCINGMESH
MIN. 50 mm (2")
12/07
FRAMING, ACCEPTABLE SHEATHINGAND SEALANT BY OTHERS
NOTE:
SI-17 TYPICAL DOWNSPOUT APPLICATION (PLAN VIEW)
SI-18 TYPICAL PIPE PENETRATION
ACCEPTABLE SHEATHING
FRAMING
SENERGY INSULATION BOARD
SEALANT AT PERIMETER OFPENETRATION
BACKER RODAND SEALANT
SENERGY ASAP
MIN. 13 MM (1/2")
ACCEPTABLE SHEATHING
FRAMING
SENERGY INSULATION BOARD
DOWNSPOUT
SLEEVE
DOWNSPOUT STRAP
SEALANT
FASTENER SET IN SEALANT
TYVEK® STUCCOWRAP®
TYVEK® STUCCOWRAP®
SENERGY LAMINA:• SENERGY BASE COAT• SENERGY REINFORCING MESH• SENERGY FINISH COAT
SENERGY LAMINA:• SENERGY BASE COAT• SENERGY REINFORCING MESH• SENERGY FINISH COAT
WRAP BASE COAT ANDSENERGY REINFORCING MESH
12/07
FRAMING, ACCEPTABLE SHEATHINGAND SEALANT BY OTHERS
NOTE:
SI-19 TYPICAL LIGHT FIXTURE
SI-20 TYPICAL DRYER VENT
ACCEPTABLE SHEATHING
DRYER VENT
FRAMING
SENERGY INSULATION BOARD
ACCEPTABLE SHEATHING
FRAMING
SENERGY INSULATION BOARD
SET FLANGE IN SEALANT
SMALL LIGHT FIXTURE
FASTENER SET IN SEALANT
SET FLANGE IN SEALANT
FASTENER THROUGHNYLON SLEEVE
TYVEK® STUCCOWRAP®
SENERGY LAMINA:• SENERGY BASE COAT• SENERGY REINFORCING MESH• SENERGY FINISH COAT
WRAP BASE COAT ANDSENERGY REINFORCING MESH
WIRE OPENING
TYVEK® STUCCOWRAP®
SENERGY LAMINA:• SENERGY BASE COAT• SENERGY REINFORCING MESH• SENERGY FINISH COAT
WRAP BASE COAT ANDSENERGY REINFORCING MESH
SEALANT AT PERIMETER OFPENETRATION
12/07
FRAMING, ACCEPTABLE SHEATHINGAND SEALANT BY OTHERS
NOTE:
SI-21 TYPICAL TERMINATION AT TOP OF DECK
SI-22 TYPICAL TERMINATION AT BOTTOM OF DECK
ACCEPTABLE SHEATHING
FRAMING
SENERGY INSULATION BOARD
FLASHING
FRAMING
SENERGY INSULATION BOARD
JOIST
MECHANICAL FASTENER
FLASHING SET IN SEALANT
DECK
FLASHING
JOIST
MECHANICAL FASTENER
SEALANT
MIN. 50 mm (2")
ACCEPTABLE SHEATHING
SENERGY LAMINA:• SENERGY BASE COAT• SENERGY REINFORCING MESH• SENERGY FINISH COAT
WRAP BASE COAT ANDSENERGY REINFORCING MESH
TYVEK® STUCCOWRAP®
MIN. 25 mm (1")
MIN. 50 mm (2")
MIN. 50 mm (2")
SENERGY LAMINA:• SENERGY BASE COAT• SENERGY REINFORCING MESH• SENERGY FINISH COAT
TYVEK® STUCCOWRAP®
TYVEK® STUCCOWRAP®
12/07
FRAMING, ACCEPTABLE SHEATHINGAND SEALANT BY OTHERS
NOTE:
SENERGY LAMINA:• SENERGY BASE COAT• SENERGY REINFORCING MESH• SENERGY FINISH COAT
SENERGY LAMINA:• SENERGY BASE COAT• SENERGY REINFORCING MESH• SENERGY FINISH COAT
SI-23 TYPICAL TERMINATION AT FOUNDATION
SI-24 TYPICAL TERMINATION AT FOUNDATION
ACCEPTABLE SHEATHING
FRAMING
FOUNDATION
SENERGY INSULATION BOARD
FLASHING
MECHANICAL FASTENER
SEALANT
STARTER TRACK W/ WEEPHOLES
TYVEK® STUCCOWRAP®
SENERWRAP/SENERFLASH 4W/FLASHING PRIMER
WRAP BASE COAT ANDSENERGY REINFORCING MESH
NOTE:TERMINATE SENTURION I DESIGNSYSTEM MIN. 203 mm (8") ABOVEGRADE.
MIN. 50 mm (2")MAX. 305 mm (12")
ACCEPTABLE SHEATHING
FRAMING
FOUNDATION
SENERGY INSULATION BOARD
MECHANICAL FASTENER
SEALANT
TYVEK® STUCCOWRAP®
SENERFLASH 4 W/ FLASHINGPRIMER
NOTE:TERMINATE SENTURION I DESIGNSYSTEM MIN. 203 mm (8") ABOVEGRADE.
MIN. 50 mm (2")MAX. 305 mm (12")
12/07
FRAMING, ACCEPTABLE SHEATHINGAND SEALANT BY OTHERS
NOTE:
SI-25 TYPICAL TERMINATION AT BRICK OF STONE
ACCEPTABLE SHEATHING
FRAMING
SENERGY INSULATION BOARD
MECHANICAL FASTENER
FLASHING SET IN SEALANT
BRICK OR STONE
SENERGY LAMINA:• SENERGY BASE COAT• SENERGY REINFORCING MESH• SENERGY FINISH COAT
SENERWRAP/SENERFLASH 4 W/FLASHING PRIMER
TYVEK® STUCCOWRAP®
WRAP BASE COAT ANDSENERGY REINFORCING MESH
SI-26 TYPICAL TERMINATION AT BRICK OF STONE
ACCEPTABLE SHEATHING
FRAMING
SENERGY INSULATION BOARD
MECHANICAL FASTENER
BACKER ROD AND SEALANT
SENERGY ASAP
BRICK OR STONE
SENERGY LAMINA:• SENERGY BASE COAT• SENERGY REINFORCING MESH• SENERGY FINISH COAT
SENERSHIELD-R OR SECONDARYMOISTURE PROTECTION BARRIER
WRAP BASE COAT ANDSENERGY REINFORCING MESH
NOTE:TERMINATION OF BRICK OR STONEMUST HAVE A MEANS FOR MOISTURETO ESCAPE.
12/07
FRAMING, ACCEPTABLE SHEATHINGAND SEALANT BY OTHERS
NOTE:
SI-27 TYPICAL KICK-OUT FLASHING DETAIL
ACCEPTABLE SHEATHING
SENTURION I WALL SYSTEM
STEP FLASHING
BACKER ROD AND SEALANT
ROOF SHINGLES
BUILDING PAPER
DRIP EDGE
KICK-OUT FLASHING
MIN. 100 mm (4")
MIN. 50 mm (2")
TYVEK® STUCCOWRAP®
SENERGY LAMINA:• SENERGY BASE COAT• SENERGY REINFORCING MESH• SENERGY FINISH COAT
NOTE:• KICK-OUT FLASHING MUST BEANGLED 100˚ MIN.TO ALLOW FORPROPER DRAINAGE.• KICK-OUT FLASHING SEAMS MUST
BE SOLDERED OR SEALED WITHAPPROPRIATE SEALANT.
• TERMINATE SENTURION I WALLSYSTEM MIN. 50 mm (2")ABOVE ROOF.
12/07
FRAMING, ACCEPTABLE SHEATHINGAND SEALANT BY OTHERS
NOTE:
BASF Wall Systems
3550 St. Johns Bluff Road SouthJacksonville, FL 32224-2614Phone 800 • 221 • 9255Fax 904 • 996 • 6300www.senergy.basf.com
©2007 BASF Construction Chemicals, LLC.
Printed in U.S.A. 12/07
General NotesBASF Wall Systems is an operating unit ofBASF Construction Chemicals, LLC. (hereinafter referred to as “BASF Wall Systems”).These details are presented in good faith byBASF Wall Systems and represent typicaland/or general conditions. They are offered asa guide for consideration to assist the designer,specifier, installer and/or owner. The responsibilityremains with the user for the design of anysystem. For conditions not shown, consultBASFWall Systems for specific recommendations.Consult current Senergy technical bulletins forsuch information as acceptable sealants,insulation attachment methods, installationof air/weather barriers, residential policy, codeand test reports, geo-climatic considerations,etc. Installation requirements for sealant (jointsize configuration, primers, bond breakers)shall be in accordance with sealantmanufacturer’s specifications and instructions.
Technical SupportConsult the BASF Wall Systems TechnicalServices Department for specific recommendationsconcerning all other applications. Consult theSenergy website, www.senergy.basf.com, foradditional information about products andsystems and for updated literature.
Residential PolicyOn one and two-family residential framedconstruction, BASF Wall Systems requiresthat the wall system selected be one thatincludes provisions for water drainage.The choices include Senturion® line ofwater drainage EIFS, commercial Senerflex®Channeled Adhesive or Channeled InsulationDesign, Senergy Stucco Wall System, andSenergy Cement-Board StuccoTM Systems.There are no exceptions to this policy. Underno circumstances will BASF Wall Systemswarrant the use of any other system onthis type of construction without expressedwritten authorization from BASF Wall Systems[Residential construction using EIFS on masonry(CMU) or poured concrete does not requirethe additional water drainage provisionsdescribed above. Senergy Exterior SurfacingSystems for insulating concrete forms arealso acceptable.] See the Senergy ResidentialPolicy Bulletin for a more detailed discussion ofthis topic. Consult our Technical ServicesDepartment for specific recommendationsconcerning all other applications. Consult theSenergy website, www.senergy.basf.com foradditional information about products andsystems and for updated literature.
DisclaimerThis information and all further technicaladvice are based on BASF Wall Systems’present knowledge and experience. However,BASF assumes no liability for providing suchinformation and advice including the extentto which such information and advice mayrelate to existing third party intellectual propertyrights, especially patent rights. In particular,BASF Wall Systems disclaims any and allCONDITIONS AND WARRANTIES, WHETHEREXPRESS OR IMPLIED, INCLUDING THEIMPLIED WARRANTIES OF FITNESS FOR APARTICULAR PURPOSE OR MERCHANTABILITY.BASF WALL SYSTEMS SHALL NOT BERESPONSIBLE FOR CONSEQUENTIAL, INDIRECTOR INCIDENTAL DAMAGES (INCLUDING LOSSOF PROFITS) OF ANY KIND. BASF Wall Systemsreserves the right to make any changesaccording to technological progress or furtherdevelopments. It is the customer’s responsibilityand obligation to carefully inspect and test anyincoming goods. Performance of the product(s)described herein should be verified by testingand carried out only by qualified experts. It isthe sole responsibility of the customer to carryout and arrange for any such testing. Referenceto trade names used by other companies isneither a recommendation, nor an endorsementof any product and does not imply that similarproducts could not be used.