PACKAGE-II PART-IV ELECTRICAL WORKS- ELECTRIFICATION FOR SERVICES BLOCK Sl.No QTY DESCRIPTION OF ITEM IV.2.1 SERVICES BLOCK I INTERNAL ELECTRIFICATION FOR SERVICES BLOCK 1 Supply and Wiring for Primary Light point with FRLS 1.5sq.mm, 1.1KV grade, ISI marked, PVC insulated single core, stranded copper conductor cable conforming to IS:694 (with latest amendments) in 20 mm dia, 16SWG MS conduit concealed in ceiling, or wall, or column, or floor including supply and fixing of 1No 5Amp Modular(plate) control switch fixed in a suitable size metal sheet flush boxes suitable for modular switch plates and all necessary components, and earthing with 14SWG bare copper wire run continuously along the conduit including supply of all fixing materials, accessories and interconnections complete as required. Notes: 1. Rates for all the point wiring items are inclusive of necessary circuit mains with 3Runs of 2.5sqmm FRLS Copper conductor wires from the distribution board to the first switch board and also sub circuits from one switch board to the subsequent switch boards in the same circuit. 2. The secondary point in case of point wiring shall include necessary wiring looped from the primary light point as indicated in the electrical layout drawings. 3. Rates for the power point wiring items are inclusive of necessary power circuit from the DB to the power socket. 4. All 16A power Switch Sockets shall be with Built in LED indication 2 Supply and wiring generally same as item 1 above but without control switch. 28 Primary Light points 23 Secondary Point

Service Block

Embed Size (px)

DESCRIPTION

Service Block

Citation preview

Page 1: Service Block

PACKAGE-II PART-IV ELECTRICAL WORKS- ELECTRIFICATION FOR SERVICES BLOCK

Sl.No QTY DESCRIPTION OF ITEM

IV.2.1 SERVICES BLOCK

I INTERNAL ELECTRIFICATION FOR SERVICES BLOCK

1

Supply and Wiring for Primary Light point with FRLS

1.5sq.mm, 1.1KV grade, ISI marked, PVC insulated

single core, stranded copper conductor cable

conforming to IS:694 (with latest amendments) in 20

mm dia, 16SWG MS conduit concealed in ceiling, or

wall, or column, or floor including supply and fixing of

1No 5Amp Modular(plate) control switch fixed in a

suitable size metal sheet flush boxes suitable for modular

switch plates and all necessary components, and

earthing with 14SWG bare copper wire run continuously

along the conduit including supply of all fixing materials,

accessories and interconnections complete as required.

Notes:

1. Rates for all the point wiring items are inclusive of necessary

circuit mains with 3Runs of 2.5sqmm FRLS Copper conductor

wires from the distribution board to the first switch board and

also sub circuits from one switch board to the subsequent

switch boards in the same circuit.

2. The secondary point in case of point wiring shall include

necessary wiring looped from the primary light point as

indicated in the electrical layout drawings.

3. Rates for the power point wiring items are inclusive of

necessary power circuit from the DB to the power socket.

4. All 16A power Switch Sockets shall be with Built in LED

indication

2

Supply and wiring generally same as item 1 above but without

control switch.

28 Primary Light points

23 Secondary Point

Page 2: Service Block

Page 1 of 8

PACKAGE-II PART-IV ELECTRICAL WORKS- ELECTRIFICATION FOR SERVICES BLOCK

Sl.No QTY DESCRIPTION OF ITEM

3

Supply and Wiring for ceiling fan point with FRLS 1.5sq.mm,

1.1KV grade, ISI marked, PVC insulated single core, stranded

copper conductor cable conforming to IS:694

amendments)in 20 mm dia, 16SWG MS conduit concealedin

ceiling, or wall, or column, or floor including supply and fixing of

1No 5Amp modular (plate) control switch & 100W step type

electronic regulator fixed in suitable size metal sheet Box

suitable for modular switches and regulator and covered with

modular switch plates and earthing with 14SWG bare copper

wire run continuously along the conduit including supply of all

fixing materials, accessories like fan hook box, terminal box ,

interconnections complete as required.

4 Cabin Fan Point

cabin fan point

5

6

switches.

7 8

8 5

Supply and fixing of modular 5A 3pin combined switch socket

outlet in the metal sheet Box of lighting control switch board

4 Ceiling Fan Point

4 Exhaust Fan Point

2 Staircase Light Point

Page 3: Service Block

including interconnections complete as required.

Page 2 of 8

PACKAGE-II PART-IV ELECTRICAL WORKS- ELECTRIFICATION FOR SERVICES BLOCK

Sl.No QTY

9 13

Supply and Wiring with FRLS 2.5sq.mm, 1.1KV grade, ISI

marked, PVC insulated single core, stranded copper conductor

cable conforming to IS:694 (with latest amendments)in 20 mm

dia, 16SWG MS conduit concealed in ceiling, or wall, or

column, or floor including supply and fixing of modular

16Amp/5Amp modularuniversal switch socket outlet and LED

indication fixed in a suitable size metal sheet box suitable for

switches and sockets and covered with modular switch plate

and earthing with 12SWG bare copper wire run continuously

along the conduit including supply of fixing materials,

interconnections complete as required.

10 Run of mains

10.1

dia

With 1no of 16A control Switch)

10.2

pvc insulated, single core stranded copper conductor cable

confirming to IS:694 (with latest amendments)in 32mm dia MS

conduit concealed in wall/ceiling, or floor and earthing with 2

run of 10SWG bare copper wire run continuously along the

conduit including supply of all fixing materialsand accessories,

interconnections complete as required. (from panel to LDBs)

Page 4: Service Block

10.3 150 Supply and wiring with 5runs of 6sq.mm,

pvc insulated, single core stranded copper conductor cable

confirming to IS:694 (with latest amendments)in 32mm dia MS

conduit concealed in wall/ceiling, or floor and earthing with

2RX 4Sq.mminsulatedwire run continuously along the conduit

including supply of all fixing materials and accessories,

interconnections complete as required (from panel to UDBs)

Page 3 of 8

PACKAGE-II PART-IV ELECTRICAL WORKS- ELECTRIFICATION FOR SERVICES BLOCK

Sl.No QTY DESCRIPTION OF ITEM

10.4 250 Supply and wiring with 2runs of 2.5sq.mm

pvc insulated, single core stranded copper conductor cable

confirming to IS:694 (with latest amendments)in 20mm dia MS

conduit concealed in wall/ceiling, or floor and earthing with 1

run of 12SWG bare copper wire run continuously along the

conduit including supply of all fixing materialsand accessories,

interconnections completeas required (from LDB to each BAY

Lights in DG Room controlled by SPMCBs)

11 Distribution Boards

Supply installation Testing and commissioning of TPN MCB

Double Door Distribution boards dust and vermin protected

and rated for 440V Three phase 50hz AC supply operation,

including of bus bar suitable capacity, neutral link with required

outgoings, din bar, fully factory fabricated with powder coated

incoming ELMCB as per specifications and required capacity

and Earth terminal complete as required and installed in flush

with wall including all fixing materials required. (All MCB's in

11.1 1

UDBs shall be of 'D' Curve & other MCB's shall be 'C' Curve.

Page 5: Service Block

11.2 3

12

concealed in wall floor/ ceiling including supply and drawing of

12SWG wire as fish wire including supply of all fixing materials

as required and as directed by EIC. (100Mtr for Telephone

system)

II Supply & Installation of Light Fixtures & Fans

13 Supply &Installation of Light Fixtures

Supply, installation, testing & commissioning of the following

light fittings with electronic ballast and all other accessories

including supply of lamps. Installation of light fittings complete

with supply of all materials like balancing socket, conduit pipe,

nipples, check nuts, bolts, nuts, metallic flexible hose,

suspension rod/ Chain, clamps etc., required for such

installation as per specifications for the following fittings

including painting with approved synthetic paint, necessary

interconnections in an approved manner. (CFL fixtures with

low loss copper ballast)

Page 4 of 8

PACKAGE-II PART-IV ELECTRICAL WORKS- ELECTRIFICATION FOR SERVICES BLOCK

Sl.No QTY DESCRIPTION OF ITEM

13.1 1X150W industrial Metal halide luminary with integral type

copper wound ballast vizor glass assembly with lamp surface

mounted(similar to Philips make: MPF922/150CST 1XMHN-

TD 150W)

10 Supply

10 Installation on surface of ceiling by providin

fasteners, in ceiling with all fixing modular complete as

required.

13.2 1X250W integrated Flood Light fitting with 250W Metal halide

luminary with integral type copper wound ballast vizor glass

Page 6: Service Block

assembly with lamp wall mounted including all fixing materials

such as fasteners, brackets, fixing screws etc on wall(similarto

Philips make MWF330-SK/250SYM 1XHPI-T

Pressure Metal Halide Lamp)).- for transformer yard lighting.

5 Supply

13.3 2X28W T5

26 Supply

13.4

3 Supply

required.

13.5

11 Supply

required.

Page 5 of 8

PACKAGE-II PART-IV ELECTRICAL WORKS- ELECTRIFICATION FOR SERVICES BLOCK

Sl.No QTY DESCRIPTION OF ITEM

13.6 1X11W CFL type fitting for mirror light fixture (Wall/ceiling

mounted) (similar to philips make :FMS200/111 1XPL=S 11W)

1 Supply

1 Installation

13.7 Telephone sockets(RJ11)

2 Supply

2 Installation

14 JUNCTION BOXES

Supply and fixing of RJ 11 telephone socket in a suitable size

Page 7: Service Block

modular type box covered with plate concealed in wall.

complete as required.

14.1 Telephone sockets(RJ11)

2 Supply & Installation

14.2 LAN sockets ( RS 45 socket)

2 Supply & Installation

14.3 Supply and installation of the following telephone tag blocks in

a suitable size sheet steel enclosure including supply of all

fixing materials painting complete s required.(krone type)

1 10 Pair

14.4 100 Supply and drawing of 2pair 2pair 0.5mm d

annealed and tinned copper conductor unarmored telephone

cables in the already laid conduits including making

interconnections at the telephone tag box end and telephone

junction box end end complete.

Exhaust Fans:

15 Supply, installation, testing and commissioning of light duty,

totally enclosed motor type exhaust fans suitable for operation

on 230Volts, 50Hz single phase AC supply complete with

3core flexible copper conductor cable, gravity louvers shutters

rigid frame with rubber mountings and of following sizes

confirming to IS-2312 (with latest amendments)

380mm sweep and 900rpm with ball Bearin

Page 6 of 8

PACKAGE-II PART-IV ELECTRICAL WORKS- ELECTRIFICATION FOR SERVICES BLOCK

Sl.No QTY DESCRIPTION OF ITEM

4 Supply

Installation of exhaust fans with gravity louvers of all sizes on

wall including grouting of bolts for installation, supply of all

materials interconnections complete as required as per

Page 8: Service Block

Drawing No CED/ELE/S/17

4 Installation

Ceiling Fans:

16 Supply of

suitable for operation on

supply conforming to IS-374

terminal block.

4 Supply

Installationof ceiling fans of all sizes having standard down rod

with all materials required for installation complete with

necessary interconnections, earthing as per Drawing No.

CED/ELE/S/19

4 Installation

Cabin Fans:

17

operation on

following sizes.

2 305mm sweep Supply

2 Installation

18 MV Cables

Supply and laying dressing and clamping of 1.1KV grade,PVC

insulated Aluminum conductor armored Underground cables

including all fixing accessories such as clamps for fixing the

cable.

18.1 3core 2.5 Sq.mm CU. Conductor Armored cable.(from LDB to

Flood Lights on roof)

120 Supply

30 Laying in Wall

Page 7 of 8

Page 9: Service Block

PACKAGE-II PART-IV ELECTRICAL WORKS- ELECTRIFICATION FOR SERVICES BLOCK

Sl.No QTY

19 END TERMINATIONS

11 Providing end terminations for

PVC/XLPE insulated armored/ unarmored,copper/Aluminum

conductor cables including supply of cable gland, lugs,

neoprene bushed and other materials and tolls required

complete with material connections, earthing of glands and as

required.

19.1 3core 2.5sq.mm

11 Supply & Installation

III

20 6

38mm dia. G.I. pipe including construction Of brick pedestal,

providing meshed funnel, cover and other civil Engineering

works, CI Spreading a homogeneous mixture of Salt charcoal

around the pipe etc, completelyAs per IS 3043, 1987. (As per

drg no:CED/ELE/S/3)

21

21.1 300

21.2 235

21.3 100

Page 8 of 8

Page 10: Service Block

UNIT RATE (in

Figures& Words)

INTERNAL ELECTRIFICATION FOR SERVICES BLOCK

PT

PT

Page 11: Service Block

UNIT RATE

PT

Supply and Wiring for ceiling fan point with FRLS 1.5sq.mm,

1.1KV grade, ISI marked, PVC insulated single core, stranded

(with latest

2 Supply and wiring generally same as item 3 above but for

Supply and wiring generally same as item 1 above but for

exhaust fan with 6 Amp modular SPMCB for control.

Supply and wiring generally same as item 1 above, but for

staircase light point with 2nos 2 way, 5

5 Amp 3 Pin Socket outlet

Supply and fixing of 2nos of 6amps 3pin modular sockets with

1no 16A modular switch in a suitable modular MS box for all

necessary complete as required.

5A 3pin socket outlet in lighting switch board

Page 12: Service Block

DESCRIPTION OF ITEM UNIT RATE

16A Combined Switch socket outlet PT

16SWG MS conduit concealed in ceiling, or wall, or

280 Supply and wiring with 2 runs of 2.5sq.mm Mtr

FRLS pvc insulated, single core stranded copper conductor

cable conforming to IS:694 (with latest amendments) in 20mm

16SWG MS conduit concealed in wall or ceiling, or

floor/Tray and earthing with 1 run of 1.5sq.mm copper PVC

insulated wire run continuously along the conduit including

supply of all fixing materials and accessories, interconnections

complete as required(For UPS Socket 2nos.of 5A Sockets

100 Supply and wiring with 4runs of 6sq.mm, Mtr

Page 13: Service Block

Mtr

UNIT RATE (in

Figures& Words)

Mtr

6way TPNMCBDB with 63A,100mA leakage current sensitivity

FP ELMCB as incomer and 18nos 6A SPMCBs as

outgoings.(1no.Main Pcc room DBs)

Page 14: Service Block

4way TPNMCBDB with 40A,100mA leakage current

sensitivity FP ELMCB as incomer and 12nos 6A SPMCBs as

outgoings. (2no s LDBs &1no UDB)

100 Supply and embedment of 20mm dia HGMS conduit

Supply & Installation of Light Fixtures & Fans

UNIT RATE (in

Figures& Words)

1X150W industrial Metal halide luminary with integral type

copper wound ballast vizor glass assembly with lamp surface

mounted(similar to Philips make: MPF922/150CST 1XMHN-

Each

Each

fasteners, in ceiling with all fixing modular complete as

1X250W integrated Flood Light fitting with 250W Metal halide

luminary with integral type copper wound ballast vizor glass

Page 15: Service Block

assembly with lamp wall mounted including all fixing materials

such as fasteners, brackets, fixing screws etc on wall(similarto

250W(High

Pressure Metal Halide Lamp)).- for transformer yard lighting.

5 Installation on the roof projecting towards the Transformer

yard, with fixing materials such as MS brackets, nuts & bolts

with all accessories associated civil work complete as required.

type fitting (suspension

(similar to Philips make :TPH828 D8 DI HF 2XTLS 28W)

26 Installationon ceiling using fasteners to suspended fitting with

chains with all fixing materials

2X18W CFL type fitting (ceiling

(similar to Philips make :FCS518/218 2XPL=L 18W)

3 Installation on ceiling by with all fixing materials complete as

2X11W CFL type fitting for Emergency light fixture (ceiling

mounted) (similar to Philips make :FCS31/211 2XPL-S 11W)

11 Installation on ceiling by with all fixing materials complete as

UNIT RATE (in

Figures& Words)

1X11W CFL type fitting for mirror light fixture (Wall/ceiling

mounted) (similar to philips make :FMS200/111 1XPL=S 11W)

Each

Each

Each

Each

Supply and fixing of RJ 11 telephone socket in a suitable size

Page 16: Service Block

modular type box covered with plate concealed in wall.

Each

Each

Supply and installation of the following telephone tag blocks in

a suitable size sheet steel enclosure including supply of all

fixing materials painting complete s required.(krone type)

Each

Rmt

annealed and tinned copper conductor unarmored telephone

cables in the already laid conduits including making

interconnections at the telephone tag box end and telephone

Supply, installation, testing and commissioning of light duty,

UNIT RATE (in

Figures& Words)

Each

Page 17: Service Block

Each

1200mm sweep ceiling fans, capacitor type

complete with 300mm down rod, canopies, shackle, rubber

bush,blades and step type Electronic type speed regulator

230Volts,50HZ single phase AC

completely pre wired up to

Each

Each

Supply of capacitor type cabin fan along with chromium plated

fan guard, 3core flexible copper conductor cable, 3pin plug to

built-in speed regulator, tilting and oscillating arrangements,

base plate etc., complete with all materialsrequired suitable for

230V. Single phase, 50HZ AC supply, of

Each

Each

3core 2.5 Sq.mm CU. Conductor Armored cable.(from LDB to

Mtr

Mtr

Page 18: Service Block

DESCRIPTION OF ITEM

2/3/3.5/4 core, 1.1grade

Each

LIGHTNING PROTECTION

(CONVENSATIONAL SYSTEM TYPE)

Providing standard G.I. Pipe Earth station, with Nos

GI strip- Supply and laying of following size strips including

excavation and refilling of earth when laid in ground and with

all fixing accessories when laid on roof including all necessary

interconnections with of the building earth stations

25X3mm Hot dip GI strip on GI flat spacers On r RMT

Test link.

32X6mm Hot dip GI strip Buried in Ground RMT

25X6mm GI strip for panels & cable trays RMT

TOTAL RS

Page 19: Service Block

AMOUNT

Page 20: Service Block

(in AMOUNT

Figures& Words)

PT

PT

PT

Amps. Modular

PT

PT

Page 21: Service Block

(in AMOUNT

Figures& Words)