hou le e lect r ic l im i ted #19-831 Devonshire Road, Victoria V9A 4T5
TEL: (250) 388-5665 · FAX (250) 388-5811
www.houle.ca
THE POWER IN ELECTRICAL CONTRACTING – Building Strength Through Successful Partnerships OPERATING THROUGHOUT WESTERN CANADA SINCE 1944
CORPORATE HEAD OFF ICE · VANCOUVER BRANCH OFF ICES IN · NANAIMO · PR INCE GEORGE · V ICTORIA
·TRANSMITTAL·
To: Windly Contracting Ltd. Date: March 29, 2006 Attn: Cliff Thompson Page(s): 1 Address: 3711 Shenton Road Nanaimo, BC V9T 2H1 Project: SCHOOL OF MGT CENTRE, MALASPINA Job No.: 3004-0004 We transmit: Action Required:
Via Courier Drawings For Your Information
Via Mail Shop Drawings Review & Comment
Via Fax Correspondence Returned As Requested
Via Hand Other As Noted
Copies: Description: 1 Control shop drawings in hard and soft format
Joe LeRoy, P.Eng. Controls Project Manager/Estimator HOULE ELECTRIC LIMITED
Malaspina University-College School of Management Centre 900 Fifth Street, Nanaimo BC
DDC Controls Shop Drawing Submittal
Submitted To:
Windley Contracting Ltd. 3711 Shenton Road Nanaimo, British Columbia V9T 2H1
Submitted By: Joe LeRoy, P.Eng 19-831 Devonshire Rd. Victoria, BC V9A 4T5 250 388-5665
Submittal Details:
Date Submitted: 3/30/2006 Date Resubmitted: Specification Section: 15900.2.7&2.8 Description: Valve Schedule Model:
Supplier info:
Name: Address:
Manufacturer info: Name: Address: Website
houle controls (a div. of houle electric ltd.)
3/29/2006
Level 1 VAV Valve L/s GPM PD Type Return FailDesign
CVActual
CV Size Model Actuator1 VAV-101 0.12 1.902 3 2m non-spring 1.1 1.2 12 b210 tr24-sr-t us2 VAV-102 0.16 2.536 3 2m non-spring 1.5 1.9 12 b211 tr24-sr-t us3 VAV-103 0.12 1.902 3 2m non-spring 1.1 1.2 12 b210 tr24-sr-t us4 VAV-104 0.85 13.4725 3 2m non-spring 7.8 10.0 12 b215 tr24-sr-t us5 VAV-105 0.14 2.219 3 3m non-spring 1.3 1.9 12 b311 tr24-sr-t us6 VAV-106 0.06 0.951 3 2m non-spring 0.5 0.8 12 b209 tr24-sr-t us7 VAV-107 0.13 2.0605 3 3m non-spring 1.2 1.2 12 b310 tr24-sr-t us8 VAV-108 0.13 2.0605 3 2m non-spring 1.2 1.2 12 b210 tr24-sr-t us9 VAV-109 0.06 0.951 3 2m non-spring 0.5 0.8 12 b209 tr24-sr-t us
Level 2 VAV Valve L/s GPM PD Type Return FailDesign
CVActual
CV Size Model Actuator10 VAV-201 0.11 1.7435 3 2m non-spring 1.0 1.2 12 b210 tr24-sr-t us11 VAV-202 0.13 2.0605 3 2m non-spring 1.2 1.2 12 b210 tr24-sr-t us12 VAV-203 0.19 3.0115 3 2m non-spring 1.7 1.9 12 b211 tr24-sr-t us13 VAV-204 0.1 1.585 3 3m non-spring 0.9 1.2 12 b310 tr24-sr-t us14 VAV-205 0.11 1.7435 3 3m non-spring 1.0 1.2 12 b310 tr24-sr-t us15 VAV-206 0.08 1.268 3 2m non-spring 0.7 0.8 12 b209 tr24-sr-t us16 VAV-207 0.1 1.585 3 2m non-spring 0.9 1.2 12 b210 tr24-sr-t us17 VAV-208 0.1 1.585 3 2m non-spring 0.9 1.2 12 b210 tr24-sr-t us18 VAV-209 0.2 3.17 3 2m non-spring 1.8 1.9 12 b211 tr24-sr-t us
Level 3 VAV Valve L/s GPM PD Type Return FailDesign
CVActual
CV Size Model Actuator19 VAV-301 0.15 2.3775 3 3m non-spring 1.4 1.9 12 b311 tr24-sr-t us20 VAV-302 0.08 1.268 3 2m non-spring 0.7 0.8 12 b209 tr24-sr-t us21 VAV-303 0.07 1.1095 3 2m non-spring 0.6 0.8 12 b209 tr24-sr-t us22 VAV-304 0.09 1.4265 3 2m non-spring 0.8 0.8 12 b209 tr24-sr-t us23 VAV-305 0.09 1.4265 3 2m non-spring 0.8 0.8 12 b209 tr24-sr-t us24 VAV-306 0.01 0.1585 3 2m non-spring 0.1 0.3 12 b207 tr24-sr-t us25 VAV-307 0.06 0.951 3 2m non-spring 0.5 0.8 12 b209 tr24-sr-t us26 VAV-308 0.07 1.1095 3 2m non-spring 0.6 0.8 12 b209 tr24-sr-t us27 VAV-309 0.08 1.268 3 3m non-spring 0.7 0.8 12 b309 tr24-sr-t us28 VAV-310 0.03 0.4755 3 2m non-spring 0.3 0.3 12 b207 tr24-sr-t us29 VAV-311 0.03 0.4755 3 2m non-spring 0.3 0.3 12 b207 tr24-sr-t us30 VAV-312 0.04 0.634 3 2m non-spring 0.4 0.5 12 b208 tr24-sr-t us
Level 4 VAV Valve L/s GPM PD Type Return FailDesign
CVActual
CV Size Model Actuator31 VAV-401 0.04 0.634 3 2m non-spring 0.4 0.5 12 b208 tr24-sr-t us32 VAV-402 0.05 0.7925 3 2m non-spring 0.5 0.8 12 b209 tr24-sr-t us33 VAV-403 0.05 0.7925 3 2m non-spring 0.5 0.8 12 b209 tr24-sr-t us34 VAV-404 0.11 1.7435 3 2m non-spring 1.0 1.2 12 b210 tr24-sr-t us35 VAV-405 0.03 0.4755 3 2m non-spring 0.3 0.3 12 b207 tr24-sr-t us36 VAV-406 0.09 1.4265 3 2m non-spring 0.8 0.8 12 b209 tr24-sr-t us37 VAV-407 0.06 0.951 3 2m non-spring 0.5 0.8 12 b209 tr24-sr-t us38 VAV-408 0.08 1.268 3 3m non-spring 0.7 0.8 12 b309 tr24-sr-t us39 VAV-409 0.13 2.0605 3 3m non-spring 1.2 1.2 12 b310 tr24-sr-t us40 VAV-410 0.03 0.4755 3 2m non-spring 0.3 0.3 12 b207 tr24-sr-t us41 VAV-411 0.05 0.7925 3 2m non-spring 0.5 0.8 12 b209 tr24-sr-t us42 VAV-412 1.08 17.118 3 2m non-spring 9.9 10.0 12 b215 tr24-sr-t us43 VAV-413 0.07 1.1095 3 2m non-spring 0.6 0.8 12 b209 tr24-sr-t us44 VAV-414 0.05 0.7925 3 2m non-spring 0.5 0.8 12 b209 tr24-sr-t us
Convectors Valve L/s GPM PD Type Return FailDesign
CVActual
CV Size Model Actuator45 CNVT-1 0.03 0.4755 3 2m non-spring 0.3 0.3 12 b207 tr24-sr-t us46 CNVT-2 0.03 0.4755 3 2m non-spring 0.3 0.3 12 b207 tr24-sr-t us47 CNVT-3 0.03 0.4755 3 2m non-spring 0.3 0.3 12 b207 tr24-sr-t us48 CNVT-4 0.03 0.4755 3 2m non-spring 0.3 0.3 12 b207 tr24-sr-t us49 CNVT-7 0.03 0.4755 3 2m non-spring 0.3 0.3 12 b207 tr24-sr-t us50 CNVT-8 0.03 0.4755 3 2m non-spring 0.3 0.3 12 b207 tr24-sr-t us51 CNVT-9 0.03 0.4755 3 2m non-spring 0.3 0.3 12 b207 tr24-sr-t us52 CUH-1 0.11 1.7435 3 2m spring open 1.0 1.2 12 b210 tr24-sr-t us
MISC Valve L/s GPM PD Type Return FailDesign
CVActual
CV Size Model Actuator53 2ndry mix 6.14 97.319 4 3m spring atoab 48.7 65.0 65 g765 af24-mft us54 trap 1 0 3 2p spring close 0.0 12 ZONE215N-35 ZONE24NC55 trap 2 0 3 2p spring close 0.0 12 ZONE215N-36 ZONE24NC56 trap 3 0 3 2p spring close 0.0 12 ZONE215N-37 ZONE24NC57 trap 4 0 3 2p spring close 0.0 12 ZONE215N-38 ZONE24NC58 trap 5 0 3 2p spring close 0.0 12 ZONE215N-39 ZONE24NC
Malaspina School of Mgt Pts List 29Mar06.xls Control Valve Schedule 1 of 1
Malaspina University-College School of Management Centre 900 Fifth Street, Nanaimo BC
DDC Controls Shop Drawing Submittal
Submitted To:
Windley Contracting Ltd. 3711 Shenton Road Nanaimo, British Columbia V9T 2H1
Submitted By: Joe LeRoy, P.Eng 19-831 Devonshire Rd. Victoria, BC V9A 4T5 250 388-5665
Submittal Details:
Date Submitted: 3/30/2006 Date Resubmitted: Specification Section: 15900.2.7&2.8 Description: 65mm 3-way mod spring return characterized control valve Model: G765 c/w AF24-MFT US
Supplier info:
Name: Belimo Aircontrols (CAN), Inc. Address: 20893 Yeomans Cres., Langley, BC V1M 2P8
Manufacturer info: Name: Belimo Aircontrols (CAN), Inc. Address: 20893 Yeomans Cres., Langley, BC V1M 2P8 Website www.belimo.com
houle controls (a div. of houle electric ltd.)
G204
94 -
03/0
5 - S
ubje
ct to
cha
nge.
© B
elim
o Ai
rcon
trols
(USA
), In
c.
19
®
Options (add to list price) AF24 US AF24-MFT US 2x AF24 US 2x AF24-MFT USbuilt-in aux. switch* AF…-S US120 VAC power supply AF120…0-135Ω control AF24-MFT95 US
* For tandem actuators – only one of the two actuators is provided with switch.‡ Add to …-MFT price.
AF… 2x AF…
G7 Series Flanged Globe Valve, Spring Return ActuatorThree-way Valve with Bronze Trim – ANSI 125 Flanged, Mixing and Diverting
G7… D Three-way Diverting Flanged Globe Valve with Spring Return ActuatorValve Spring Return Actuator
Model Cv Valve On/Off Proportional / MFT# Nominal Size Close-
Flanged Off AF24 US AF24-MFT US†Valve Inches Type psi 2x AF24 US 2x AF24-MFT US†
G765D 68 2-1/2” ANSI 125 100 Pg 80 Pg 80G780D 85 3” ANSI 125 100 Pg 80 Pg 80G7100D 154 4” ANSI 125 100 Pg 80 Pg 80G7125D 195 5” ANSI 125 100 Pg 80 Pg 80G7150D 248 6” ANSI 125 100 Pg 80 Pg 80
For fail safe operation where AF actuator is not available or close-off is too low, use GM actuator with NSV battery backup.† Specify when ordering proportional (P-10001) 2-10 VDC, floating point (P-30001), on/off (P-40002) for AF actuators.
AF24
US
2x
AF24
-MFT
US
2x
G7 Three-way Mixing Flanged Globe Valve with Spring Return ActuatorValve Spring Return Actuator
Model Cv Valve On/Off Proportional / MFT# Nominal Size Close-
Flanged Off AF24 US AF24-MFT US†Valve Inches Type psi 2x AF24 US 2x AF24-MFT US†G765 68 2-1/2” ANSI 125 41 Pg 68 Pg 68G780 91 3” ANSI 125 28 Pg 68 Pg 68G7100 190 4” ANSI 125 9 Pg 68 Pg 68G765 68 2-1/2” ANSI 125 82 Pg 68 Pg 68G780 91 3” ANSI 125 57 Pg 68 Pg 68G7100 190 4” ANSI 125 16 Pg 68 Pg 68G7125 280 5” ANSI 125 10 Pg 68 Pg 68G7150 340 6” ANSI 125 7 Pg 68 Pg 68
† Specify when ordering proportional (P-10001) 2-10 VDC, floating point (P-30001), on/off (P-40002) for AF actuators.
AF24
US
2x A
F24
US
AF24
-MFT
US2x
AF2
4-M
FT U
S
‡
Malaspina University-College School of Management Centre 900 Fifth Street, Nanaimo BC
DDC Controls Shop Drawing Submittal
Submitted To:
Windley Contracting Ltd. 3711 Shenton Road Nanaimo, British Columbia V9T 2H1
Submitted By: Joe LeRoy, P.Eng 19-831 Devonshire Rd. Victoria, BC V9A 4T5 250 388-5665
Submittal Details:
Date Submitted: 3/30/2006 Date Resubmitted: Specification Section: 15900.2.7&2.8 Description: 12mm 2-way mod non-spring return characterized control valve Model: B207 to B215 c/w TR24-SR-T US
Supplier info:
Name: Belimo Aircontrols (CAN), Inc. Address: 20894 Yeomans Cres., Langley, BC V1M 2P8
Manufacturer info: Name: Belimo Aircontrols (CAN), Inc. Address: 20894 Yeomans Cres., Langley, BC V1M 2P8 Website www.belimo.com
houle controls (a div. of houle electric ltd.)
14
G204
93 -
03/0
5 - I
G-Su
bjec
t to
chan
ge. ©
Bel
imo
Airc
ontro
ls (U
SA),
Inc.
®
NM24
US
B2 Series Characterized Control Valve,™ Non-Spring Return Actuator Two-way Valve with Stainless Steel Ball and Stem, NPT female ends
AM…
TR24-3-T USOptions (add to list price) TR24-SR-T US LR24-3 USbuilt-in aux. switch LR…-S US Pg 443-foot cable TR24-3 US, TR24-SR US Pg 40/426-foot cable TR…/200 US, LR…/200 US Pg 40/42 Pg 4410-foot cable TR…/300 US, LR…/300 US Pg 40/42 Pg 44
NM…LR…TR…
B2 Two-way Characterized Control Valve, Stainless Steel Ball and StemValve Non-Spring Return Actuator
On/Off, Floating On/Off, Floating Proportional Proportional Proportional / MFT
Model Cv Valve Close-# Rating Nominal Size Off LR24-3 US LR24-SR US LR24-MFT US
CCV DN psi TR24-3-T US NM24 US TR24-SR-T US NM24-SR US NM24-MFT USValve Inches mm AM24 US AM24-MFT USB207 0.3 1/2” 15 200 Pg 40 Pg 44 Pg 42 Pg 46 Pg 48B208 0.46 1/2” 15 200 Pg 40 Pg 44 Pg 42 Pg 46 Pg 48B209 0.8 1/2” 15 200 Pg 40 Pg 44 Pg 42 Pg 46 Pg 48B210 1.2 1/2” 15 200 Pg 40 Pg 44 Pg 42 Pg 46 Pg 48B211 1.9 1/2” 15 200 Pg 40 Pg 44 Pg 42 Pg 46 Pg 48B212 3.0 1/2” 15 200 Pg 40 Pg 44 Pg 42 Pg 46 Pg 48B213 4.7 1/2” 15 200 Pg 40 Pg 44 Pg 42 Pg 46 Pg 48B214 7.4 1/2” 15 200 Pg 40 Pg 44 Pg 42 Pg 46 Pg 48B215* 10 1/2” 15 200 Pg 40 Pg 44 Pg 42 Pg 46 Pg 48B217 4.7 3/4” 20 200 Pg 40 Pg 44 Pg 42 Pg 46 Pg 48B218 7.4 3/4” 20 200 Pg 40 Pg 44 Pg 42 Pg 46 Pg 48B219 10 3/4” 20 200 Pg 40 Pg 44 Pg 42 Pg 46 Pg 48B220* 24 3/4” 20 200 Pg 40 Pg 44 Pg 42 Pg 46 Pg 48B222 7.4 1” 25 200 Pg 44 Pg 46 Pg 48B223 10 1” 25 200 Pg 44 Pg 46 Pg 48B224 19 1” 25 200 Pg 44 Pg 46 Pg 48B225* 30 1” 25 200 Pg 44 Pg 46 Pg 48B229 10 1-1/4” 32 200 Pg 44 Pg 46 Pg 48B230* 19 1-1/4” 32 200 Pg 44 Pg 46 Pg 48B231 25 1-1/4” 32 200 Pg 50 Pg 52 Pg 54B232* 37 1-1/4” 32 200 Pg 50 Pg 52 Pg 54B238 19 1-1/2” 40 200 Pg 50 Pg 52 Pg 54B239 29 1-1/2” 40 200 Pg 50 Pg 52 Pg 54B240* 37 1-1/2” 40 200 Pg 50 Pg 52 Pg 54B248 29 2” 50 200 Pg 50 Pg 52 Pg 54B249 46 2” 50 200 Pg 50 Pg 52 Pg 54B250* 57 2” 50 200 Pg 50 Pg 52 Pg 54B251 65 2” 50 100 Pg 56 Pg 58B252 85 2” 50 100 Pg 56 Pg 58B253 120 2” 50 100 Pg 56 Pg 58B254* 240 2” 50 100 Pg 56 Pg 58B261 60 2.5” 65 100 Pg 56 Pg 58B262 75 2.5” 65 100 Pg 56 Pg 58B263 110 2.5” 65 100 Pg 56 Pg 58B264 150 2.5” 65 100 Pg 56 Pg 58B265* 210 2.5” 65 100 Pg 56 Pg 58B277 70 3” 80 100 Pg 56 Pg 58B278 130 3” 80 100 Pg 56 Pg 58B280* 170 3” 80 100 Pg 56 Pg 58Electrical Covered 3 ft cable, Covered Terminal 3 ft cable, 3 ft cable,Connection Terminal Strip 1/2” conduit Strip 1/2” conduit 1/2” conduit
fitting fitting fitting
* Models without characterizing discs. See pg 11 for corrected Cvs with piping reduction factor. See pg 132 for MFT Configuration.
TR24
-3-T
US
LR24
-3 U
S
TR24
-SR-
T US
LR24
-SR
US
LR24
-MFT
US
AM24
-MFT
US
NM24
-SR
US
NM24
-MFT
US
AM24
US
42
G204
93 -
03/0
5 - I
G-Su
bjec
t to
chan
ge. ©
Bel
imo
Airc
ontro
ls (U
SA),
Inc.
®B2 Two-way Characterized Control Valve, Stainless Steel Ball and StemTR Actuators, ProportionalTechnical Data/Submittal
Actuator Specifications
TR24-SR-T USReversing switch under cover
Control ProportionalInput Impedance 100 kΩNominal voltage 24 VAC 50/60 Hz, 24VDC
Nominal voltage range 19.2…28.8 VAC, 21.6…28.8 VDCPower Consumption 0.5 WTransformer Sizing 1VA (Class 2 power source)Electrical Connection Screw Terminals accessible after
removal of small cover (3 ft, 6 ft, 10 ft cables optional)
Angle of Rotation 90°Torque 18 in-lbs (2Nm)Position Indication Integrated into handleManual override: Push down handleRunning Time 90 seconds Humidity 5 to 95% non-condensingAmbient Temperature 19°F to 122°F (-7°C to +50°C)Storage Temperature -40°F to 176°F (-40°C to +80°C)Housing NEMA 1Housing Rating UL94-5V(B)Agency Listing CE, UL 60730-1
EMC CE according to 89/336/EECMode of Operation Type 1 to UL 60730-1
Noise Level max. 35 db (A)Quality Standard ISO 9001
Additional Models
TR24-SR US TR24-SR-T US with 3 ft plenum rated cable
TR24-SR/200 US TR24-SR-T US with 6 ft plenum rated cable
TR24-SR/300 US TR24-SR-T US with 10 ft plenum rated cable
©
Valve Specifications
Service chilled or hot water, 60% glycolFlow characteristic A port equal percentage Action Max 95° rotationSizes 1/2”, 3/4”Type of end fitting female, NPTMaterials:
Body forged brass, nickel platedBall stainless steel Stem stainless steel Seats fiberglass reinforced teflon® PTFECharacterizing disc TEFZEL®
Packing 2 EPDM O-rings, lubricatedPressure rating 600 psi Media temp. range 0°F to 212°F [-18°C to 100°C]Close off pressure 200 psiMaximum differential: For Characterized A-port pressure (∆P) 20 psi for typical applications
30 psi max for quiet service
For full flow versions only (no A-disc) On/Off control 150 psi
Leakage 0%Cv rating A port: see product chart for values
Tefzel® is a registered trademark of DuPont
See Selection Chart Pg 14 for Control Valve No., Cv and Close-off
Application
This valve is typically used in air handling units on heating orcooling coils, and fan coil unit heating or cooling coils. Someother common applications include Unit Ventilators, VAV Boxreheat coils and bypass loops. This valve is suitable for use ina hydronic system with variable flow. This valve is designedfor modulating control using 2...10VDC or 4...20mA. (for4...20mA control input a 500 ohm resistor is required).
The valve is designed to fit in compact areas where propor-tional control is required using 24 VAC/VDC.
Malaspina University-College School of Management Centre 900 Fifth Street, Nanaimo BC
DDC Controls Shop Drawing Submittal
Submitted To:
Windley Contracting Ltd. 3711 Shenton Road Nanaimo, British Columbia V9T 2H1
Submitted By: Joe LeRoy, P.Eng 19-831 Devonshire Rd. Victoria, BC V9A 4T5 250 388-5665
Submittal Details:
Date Submitted: 3/30/2006 Date Resubmitted: Specification Section: 15900.2.7&2.8 Description: 12mm 3-way mod non-spring return characterized control valve Model: B309 to B311 c/w TR24-SR-T US
Supplier info:
Name: Belimo Aircontrols (CAN), Inc. Address: 20895 Yeomans Cres., Langley, BC V1M 2P8
Manufacturer info: Name: Belimo Aircontrols (CAN), Inc. Address: 20895 Yeomans Cres., Langley, BC V1M 2P8 Website www.belimo.com
houle controls (a div. of houle electric ltd.)
G204
93 -
03/0
5 - I
G-Su
bjec
t to
chan
ge. ©
Bel
imo
Airc
ontro
ls (U
SA),
Inc.
15
®
TR24-3-T USOptions (add to list price) TR24-SR-T US LR24-3 USbuilt-in aux. switch LR…-S US Pg 643-foot cable TR24-3 US, TR24-SR US Pg 60/626-foot cable TR…/200 US, LR…/200 US Pg 60/62 Pg 6410-foot cable TR…/300 US, LR…/300 US Pg 60/62 Pg 64
LR… NM…
B3 Series Characterized Control Valve,™ Non-Spring Return Actuator Three-way Valve with Stainless Steel Ball and Stem, NPT female ends
TR…
B3 Three-way Characterized Control Valve, Stainless Steel Ball and StemValve Non-Spring Return Actuator
Model Cv Valve On/Off, Floating On/Off, Floating Proportional Proportional Proportional / MFT
# Rating Nominal Size Close-CCV DN Off TR24-3-T US LR24-3 US TR24-SR-T US LR24-SR US LR24-MFT USValve Inches mm psi NM24 US NM24-SR US NM24-MFT USB307 0.3 1/2” 15 200 Pg 60 Pg 64 Pg 62 Pg 66 Pg 68B308 0.46 1/2” 15 200 Pg 60 Pg 64 Pg 62 Pg 66 Pg 68B309 0.8 1/2” 15 200 Pg 60 Pg 64 Pg 62 Pg 66 Pg 68B310 1.2 1/2” 15 200 Pg 60 Pg 64 Pg 62 Pg 66 Pg 68B311 1.9 1/2” 15 200 Pg 60 Pg 64 Pg 62 Pg 66 Pg 68B312 3.0 1/2” 15 200 Pg 60 Pg 64 Pg 62 Pg 66 Pg 68B313 4.7 1/2” 15 200 Pg 60 Pg 64 Pg 62 Pg 66 Pg 68B315* 10 1/2” 15 200 Pg 60 Pg 64 Pg 62 Pg 66 Pg 68B317 4.7 3/4” 20 200 Pg 60 Pg 64 Pg 62 Pg 66 Pg 68B318 7.4 3/4” 20 200 Pg 60 Pg 64 Pg 62 Pg 66 Pg 68B320* 24 3/4” 20 200 Pg 60 Pg 64 Pg 62 Pg 66 Pg 68B322 7.4 1” 25 200 Pg 64 Pg 66 Pg 68B323 10 1” 25 200 Pg 64 Pg 66 Pg 68B325* 30 1” 25 200 Pg 64 Pg 66 Pg 68B329 10 1-1/4” 32 200 Pg 64 Pg 66 Pg 68B330* 19 1-1/4” 32 200 Pg 64 Pg 66 Pg 68B331 25 1-1/4” 32 200 Pg 70 Pg 72 Pg 74B332* 37 1-1/4” 32 200 Pg 70 Pg 72 Pg 74B338 19 1-1/2” 40 200 Pg 70 Pg 72 Pg 74B339 29 1-1/2” 40 200 Pg 70 Pg 72 Pg 74B340* 37 1-1/2” 40 200 Pg 70 Pg 72 Pg 74B348 29 2” 50 200 Pg 70 Pg 72 Pg 74B349 46 2” 50 200 Pg 70 Pg 72 Pg 74B350* 57 2” 50 200 Pg 70 Pg 72 Pg 74Electrical Covered 3 ft cable, Covered Terminal 3 ft cable, 3 ft cable,Connection Terminal Strip 1/2” conduit Strip 1/2” conduit 1/2” conduit
fitting fitting fitting
* Models without characterizing discs.
See pg 132 for MFT Configuration.
TR24
-3-T
US
LR24
-3 U
S
TR24
-SR-
T US
LR24
-SR
US
LR24
-MFT
US
NM24
-MFT
US
NM24
-SR
US
NM24
US
62
G204
93 -
03/0
5 - I
G-Su
bjec
t to
chan
ge. ©
Bel
imo
Airc
ontro
ls (U
SA),
Inc.
®B3 Three-way Characterized Control Valve, Stainless Steel Ball and StemTR Actuators, ProportionalTechnical Data/Submittal
Actuator Specifications
TR24-SR-T USReversing switch under cover
Control ProportionalInput Impedance 100 kΩNominal voltage 24 VAC 50/60 Hz, 24VDC
Nominal voltage range 19.2…28.8 VAC, 21.6…28.8 VDCPower Consumption 0.5 WTransformer Sizing 1VA (Class 2 power source)Electrical Connection Screw Terminals accessible after
removal of small cover (3 ft, 6 ft, 10 ft cables optional)
Angle of Rotation 90°Torque 18 in-lbs (2Nm)Position Indication Integrated into HandleManual override: Push down handleRunning Time 90 seconds Humidity 5 to 95% non-condensingAmbient Temperature 19°F to 122°F (-7°C to +50°C)Storage Temperature -40°F to 176°F (-40°C to +80°C)Housing NEMA 1Housing Rating UL94-5V(B)Agency Listing CE, UL 60730-1
EMC CE according to 89/336/EECMode of Operation Type 1 to UL 60730-1
Noise Level max. 35 db (A)Quality Standard ISO 9001
Additional Models
TR24-SR US TR24-SR-T US with 3 ft plenum rated cable
TR24-SR/200 US TR24-SR-T US with 6 ft plenum rated cable
TR24-SR/300 US TR24-SR-T US with 10 ft plenum rated cable
©
Valve Specifications
Service chilled or hot water, 60% glycolFlow characteristic A port equal percentage
B port modified linear for constant AB flow
Action Max 95° rotationSizes 1/2”, 3/4”Type of end fitting female, NPTMaterials:
Body forged brass, nickel platedBall stainless steelStem stainless steelSeats fiberglass reinforced teflon® PTFECharacterizing disc TEFZEL®
Packing 2 EPDM O-rings, lubricatedPressure rating 600 psi Media temp. range 0°F to 212°F [-18°C to 100°C]Close off pressure 200 psiMaximum differential: For Characterized A-port pressure (∆P) 20 psi for typical applications
30 psi max for quiet service
For full flow versions only (no A-disc) On/Off control 150 psi
Leakage A port: 0%B port: 0.5% - 2% of full rated CVAB port: 0%
Cv rating A port: see product chart for valuesB port: 70% of A port flow
Tefzel® is a registered trademark of DuPont
See Selection Chart Pg 15 for Control Valve No., Cv and Close-off
Application
This valve is typically used in air handling units on heating orcooling coils, and fan coil unit heating or cooling coils. Someother common applications include Unit Ventilators, VAV Boxreheat coils and bypass loops. This valve is suitable for use ina hydronic system with variable or constant flow. This valve isdesigned for modulating control using 2...10VDC or 4...20mA.(for 4...20mA control input a 500 ohm resistor is required).
The valve is designed to fit in compact areas where propor-tional control is required using 24 VAC/VDC.
Malaspina University-College School of Management Centre 900 Fifth Street, Nanaimo BC
DDC Controls Shop Drawing Submittal
Submitted To:
Windley Contracting Ltd. 3711 Shenton Road Nanaimo, British Columbia V9T 2H1
Submitted By: Joe LeRoy, P.Eng 19-831 Devonshire Rd. Victoria, BC V9A 4T5 250 388-5665
Submittal Details:
Date Submitted: 3/30/2006 Date Resubmitted: Specification Section: 15900.2.7&2.8 Description: 12mm 2-way 2 pos'n spring return zone valve Model: ZONE215N-35
Supplier info:
Name: Belimo Aircontrols (CAN), Inc. Address: 20896 Yeomans Cres., Langley, BC V1M 2P8
Manufacturer info: Name: Belimo Aircontrols (CAN), Inc. Address: 20896 Yeomans Cres., Langley, BC V1M 2P8 Website www.belimo.com
houle controls (a div. of houle electric ltd.)
®
8
H205
18-0
3/05
- Su
bjec
t to
chan
ge. ©
Bel
imo
Airc
ontro
ls (U
SA),
Inc.
†Three-way valve can be NC or NO depending on installation always using the NC actuator. See technical literature for details.
Electronic Zone Valves, Spring Return ActuatorTwo-way and Three-way valves with NPT or sweat ends
Valve Actuator
Nominal Close- 24 V 24 V 120 V 120 VModel # Cv Size off Normally Closed Normally Open Normally Closed Normally OpenValve Rating Inches mm (psi) ZONE24NC ZONE24NO ZONE120NC ZONE120NO
Two-way with NPT Female Connection
ZONE215N-10 1.0 1/2” 15 75 Pg 10 Pg 10 Pg 10 Pg 10
ZONE215N-25 2.5 1/2” 15 50 Pg 10 Pg 10 Pg 10 Pg 10
ZONE215N-35 3.5 1/2” 15 30 Pg 10 Pg 10 Pg 10 Pg 10
ZONE220N-35 3.5 3/4” 20 30 Pg 10 Pg 10 Pg 10 Pg 10
ZONE220N-50 5.0 3/4” 20 25 Pg 10 Pg 10 Pg 10 Pg 10
ZONE225N-80 8.0 1” 35 20 Pg 10 Pg 10 Pg 10 Pg 10
Three-way with NPT Female Connection
ZONE315N-10 1.0 1/2” 15 75 Pg 10 † Pg 10 †
ZONE315N-25 2.5 1/2” 15 50 Pg 10 † Pg 10 †
ZONE315N-35 3.5 1/2” 15 30 Pg 10 † Pg 10 †
ZONE320N-35 3.5 3/4” 20 30 Pg 10 † Pg 10 †
ZONE320N-50 5.0 3/4” 20 25 Pg 10 † Pg 10 †
ZONE325N-80 8.0 1” 35 20 Pg 10 † Pg 10 †
Two-way with Sweat Connection
ZONE215S-10 1.0 1/2” 15 75 Pg 10 Pg 10 Pg 10 Pg 10
ZONE215S-25 2.5 1/2” 15 50 Pg 10 Pg 10 Pg 10 Pg 10
ZONE215S-35 3.5 1/2” 15 30 Pg 10 Pg 10 Pg 10 Pg 10
ZONE220S-35 3.5 3/4” 20 30 Pg 10 Pg 10 Pg 10 Pg 10
ZONE220S-50 5.0 3/4” 20 25 Pg 10 Pg 10 Pg 10 Pg 10
ZONE225S-80 8.0 1” 35 20 Pg 10 Pg 10 Pg 10 Pg 10
Three-way with Sweat Connection
ZONE315S-10 1.0 1/2” 15 75 Pg 10 † Pg 10 †
ZONE315S-25 2.5 1/2” 15 50 Pg 10 † Pg 10 †
ZONE315S-35 3.5 1/2” 15 30 Pg 10 † Pg 10 †
ZONE320S-35 3.5 3/4” 20 30 Pg 10 † Pg 10 †
ZONE320S-50 5.0 3/4” 20 25 Pg 10 † Pg 10 †
ZONE325S-80 8.0 1” 35 20 Pg 10 † Pg 10 †
Built-in auxiliary switch ZONE215N-10+ZONE24NC-S Pg 10 Pg 10 Pg 10 Pg 10
(add -S to model number)
ZONE
24NC
ZONE
24NO
ZONE
120N
C
ZONE
24NC
ZONE
120N
C
ZONE
24NC
ZONE
120N
C
ZONE
120N
O
ZONE
24NC
ZONE
24NO
ZONE
120N
C
ZONE
120N
O
®
10
H205
18-0
3/05
- Su
bjec
t to
chan
ge. ©
Bel
imo
Airc
ontro
ls (U
SA),
Inc.
Electronic Zone ValvesZONE… SeriesTechnical Data/Submittal
Valve Specifications
Service chilled or hot water, 50% glycolFlow characteristic Two-way on/off Three-way on/off, divertingSizes 1/2”, 3/4” and 1”Type of end fitting female, NPT or SweatMaterials:
Body forged brassStem stainless steelSeals EPDM
Pressure rating 300 psi Media temp. range 32°F to 212°F [0°C to 100°C]Close off pressure 20 – 75 psiLeakage Class III 0.1%Cv rating 1.0 – 8.0
U.S. & Foreign Patent Pending
Actuator Specifications
Control On/offNominal voltage 24 VAC 50/60 Hz ± 10%
or 120 VAC 50/60 Hz ± 10%Power Consumption 6.5 WTransformer Sizing 7VA (Class 2 power source)Electrical Connection Wire lead length, 120V 6”
24V 18”Position Indication Integrated into lever (NC only)Running Time Motor: 20-40 seconds
Spring: 5 secondsHumidity 5 to 95% non-condensingAmbient Temperature 32°F to 104°F (0°C to + 40°C)Storage Temperature -40°F to 176°F (-40°C to +80°C)Housing Rating UL94-5V(B)Agency Listing CE, cULus Noise Level max. 35 db (A)Quality Standard ISO 9001Built-in Auxiliary Switch 1 x SPDT, 5A resistive (5A inductive)(optional) @ 24 VAC
1 x SPDT, 5A resistive (5A inductive)@ 120 VAC
Application
This valve is typically used on fan coil units, baseboards orother hydronic applications where fail safe operation or 2-wirecontrol is required. This valve is suitable for use in a hydronicsystem with variable or constant flow.
This valve is designed to fit in compact areas where on/off orcontrol is required using 24 VAC or 120 VAC.
®
9
H205
18-0
3/05
- Su
bjec
t to
chan
ge. ©
Bel
imo
Airc
ontro
ls (U
SA),
Inc.
Electronic Zone ValvesInstallation
3-way installed on the return
(NO) B
AB
A
B A
LoadAB
AB Load
A
A B
Load
InstallationThe valve can be installed vertically or horizontally, but not turned upside down.
– A 3-way valve cannot be transformed into a 2-way valve andvisa versa.
– The flow is from A to B (see diagram below) and must beinstalled so the paddle closes against the direction of flowas indicated in the following diagrams.
– The 2-way valves can be installed on the supply or on thereturn; for correct installation it is necessary to respect thedirection of flow indicated from the arrow on the body valve.
360°
2-way valve normally closed actuator
3-way valve normally closed actuator(Note: 3-way uses only normally closed actuator)
3-way installed on the supply in diverting configuration
2-way installed on the supply
2-way installed on the return
(NC)
B A Load
AB
2-way 3-way
Port “A” closedN.C. without power Port”A” closed Port “B” open
Port “AB” open
N.C. open with power Port”A” open Port “A” openPort “B” closedPort “AB” open
N.C. manually open Port”A” open Port “A” openPort “B” open
Port “AB” open
B
Malaspina University-College School of Management Centre 900 Fifth Street, Nanaimo BC
DDC Controls Shop Drawing Submittal
Submitted To:
Windley Contracting Ltd. 3711 Shenton Road Nanaimo, British Columbia V9T 2H1
Submitted By: Joe LeRoy, P.Eng 19-831 Devonshire Rd. Victoria, BC V9A 4T5 250 388-5665
Submittal Details:
Date Submitted: 3/30/2006 Date Resubmitted: Specification Section: 15900.2.2.1 Description: Room temperature sensor Model: TE200AD7
Supplier info:
Name: Pacific Controls Ltd. Address: 440 Garbally Road, Victoria, BC V8T 2S9
Manufacturer info: Name: Greystone Energy Systems Inc. Address: 150 English Drive, Moncton, NB E1E 4G7 Website www.greystoneenergy.com
houle controls (a div. of houle electric ltd.)
FEATURES: The TE Series Space Temperature sensors are available in four different enclosure styles. They are available with a choice of precision RTD’s, IC’s, or thermistors. A number of options, such as momentary override and setpoint adjustment are also available for various configurations. A transmitter option is also available to be used with the 1000 ohm platinum sensor which provides either 4 -20mA, 0 – 5 VDC or 0 – 10 VDC output proportional to a selected temperature span. A 100 ohm platinum sensor transmitter is optional. The transmitters provide high accuracy, long-term
stability, low hysteresis, fast response and a wide operating temperature range. Every transmitter offers accuracy of 0.1% of span or better and are highly stable due to excellent RFI rejection and are also virtually immune to power supply noise and input voltage fluctuations. Transmitter General Specifications: Supply Voltage: 24 VDC/VAC Output: 4 – 20mA, 0–5 VDC or 0-10 VDC Accuracy: ±0.1% of span Operating temp: 0°C – 70°C (32°F – 158°F) Calibration In compliance with ANSI/NCSL 2540-11994
AS) Surface - A stainless steel plate which can be mounted to a wall box used where tamper-proof or protection is required. Available with various options, including push button overrides, etc.
SPACE/WALL MOUNT TRANSMITTER:
A) Micro – Includes a compact snap-mounted cover for ease of installation, available with various temperature sensors.
AD) Designer – Features include a three-piece enclosure that mounts directly to a wall box or on any wall. Available with various options. Including set point adjustments, push button overrides, etc.
Display Type LCD Display LED Display
Power Supply 12 – 30 VAC/DC at 2mA max 12 – 30 VAC/DC at 30mA max
Display Units °C or °F (factory set) °C or °F (jumper selectable)
Display Range 0.0 – 35.0°C (32.0 – 95.0°F) 10.0 – 35.5°C (50.0 – 96.0°F)
Display Resolution 0.1°C (0.1°F) 0.5°C (1.0°F)
Display Size 23 mm W x 11 mm H (0.9” W x 0.45” H) 3 digit x 30 mm W x 7.6 mm H (1.18” W x 0.3” H)
Available Options Various sensors, set points, push buttons, external jacks, and logos.
GREYSTONE ENERGY SYSTEMS INC. Q M I
ISO 9002
MODEL Product Description
TE200 TE500
Sensor assembly Sensor assembly c/w transmitter (sensor type 12 is standard)
CODE Enclosure
A AD AS
Micro (not available with transmitter or options) Designer S/S plate
CODE Sensor
2 5 6 7 8 9 11 12 13 14 20 21 24
PT100-100 ohm Platinum, IEC 751, 385 Alpha, thin film 1801 ohm, NTC Thermistor, ±0.2°C 3,000 ohm, NTC Thermistor, ±0.2°C 10,000 ohm, type 3, NTC Thermistor, ±0.2°C 2.252 K ohm NTC Thermistor, ±0.2°C 100,000 ohm, NTC Thermistor, ±0.2°C LM334 IC, 1.0uA/°C PT1000-1000 ohm Platinum, IEC 751, 0.385 Alpha, thin film 1000 ohm nickel 10,000 ohm type 3, NTC Thermistor, ±0.2°C c/w 11k shunt resistor 20,000 ohm, NTC Thermistor, ±0.2°C LM335 IC, 10mv/°C 10,000 ohm, type 2, NTC Thermistor, ±0.2°C
CODE Options (TE200AD assembly only) AP
AS BS AM BC BF AC AF LY LR LG CJ AE AI
20-30K linear slide pot for set point control Concealed push button momentary switch (NO) Exposed push button momentary switch (NO) Alcohol thermometer °C & °F Bi-metal thermometer °C Bi-metal thermometer °F 3-digit LCD temperature indicator °C 3-digit LCD temperature indicator °F Yellow LED Red LED Green LED External jack for remote system access (phono jack) External jack for remote system access (4-pin header) Internal jack (RJ-45)
CODE TE500 Transmitter Power Supply 1 24 VAC/DC CODE TE500 Transmitter Output Option
A D E
Current 4 – 20mA Voltage 0 – 5 VDC Voltage 0 – 10 VDC
CODE TE500 Transmitter Range Option
1 2
0°C – 35°C (32°F – 95°F) 0°C – 50°C (32°F – 122°F)
TE500 AD 12 - 1 A 2
Greystone Energy Systems, Inc. reserves the right to make design modifications without prior notice.
SPACE TEMPERATURE SENSORS/TRANSMITTERS: PRODUCT ORDERING INFORMATION
EXAMPLE: Designer space, c/w PT1000Ω RTD, 4–20mA transmitter with a 0°C – 50°C (32°F – 122°F) range.
NOTE: Due to the many possible configurations, special part numbers may be required, please contact Greystone for more information.
GREYSTONE ENERGY SYSTEMS INC. Q M I
ISO 9002
Malaspina University-College School of Management Centre 900 Fifth Street, Nanaimo BC
DDC Controls Shop Drawing Submittal
Submitted To:
Windley Contracting Ltd. 3711 Shenton Road Nanaimo, British Columbia V9T 2H1
Submitted By: Joe LeRoy, P.Eng 19-831 Devonshire Rd. Victoria, BC V9A 4T5 250 388-5665
Submittal Details:
Date Submitted: 3/30/2006 Date Resubmitted: Specification Section: 15900.2.3 Description: Room temperature sensor c/w two button adjust Model: RT
Supplier info:
Name: Reliable Controls Corporation Address: 207-3375 Whittier Avenue, Victoria, BC V8Z 3R11
Manufacturer info: Name: Reliable Controls Corporation Address: 207-3375 Whittier Avenue, Victoria, BC V8Z 3R11 Website www.reliable-controls.com
houle controls (a div. of houle electric ltd.)
Malaspina University-College School of Management Centre 900 Fifth Street, Nanaimo BC
DDC Controls Shop Drawing Submittal
Submitted To:
Windley Contracting Ltd. 3711 Shenton Road Nanaimo, British Columbia V9T 2H1
Submitted By: Joe LeRoy, P.Eng 19-831 Devonshire Rd. Victoria, BC V9A 4T5 250 388-5665
Submittal Details:
Date Submitted: 3/30/2006 Date Resubmitted: Specification Section: 15900.2.2.2 Description: Room temperature sensor S/S plate Model: TE200AS7
Supplier info:
Name: Pacific Controls Ltd. Address: 440 Garbally Road, Victoria, BC V8T 2S9
Manufacturer info: Name: Greystone Energy Systems Inc. Address: 150 English Drive, Moncton, NB E1E 4G7 Website www.greystoneenergy.com
houle controls (a div. of houle electric ltd.)
FEATURES: The TE Series Space Temperature sensors are available in four different enclosure styles. They are available with a choice of precision RTD’s, IC’s, or thermistors. A number of options, such as momentary override and setpoint adjustment are also available for various configurations. A transmitter option is also available to be used with the 1000 ohm platinum sensor which provides either 4 -20mA, 0 – 5 VDC or 0 – 10 VDC output proportional to a selected temperature span. A 100 ohm platinum sensor transmitter is optional. The transmitters provide high accuracy, long-term
stability, low hysteresis, fast response and a wide operating temperature range. Every transmitter offers accuracy of 0.1% of span or better and are highly stable due to excellent RFI rejection and are also virtually immune to power supply noise and input voltage fluctuations. Transmitter General Specifications: Supply Voltage: 24 VDC/VAC Output: 4 – 20mA, 0–5 VDC or 0-10 VDC Accuracy: ±0.1% of span Operating temp: 0°C – 70°C (32°F – 158°F) Calibration In compliance with ANSI/NCSL 2540-11994
AS) Surface - A stainless steel plate which can be mounted to a wall box used where tamper-proof or protection is required. Available with various options, including push button overrides, etc.
SPACE/WALL MOUNT TRANSMITTER:
A) Micro – Includes a compact snap-mounted cover for ease of installation, available with various temperature sensors.
AD) Designer – Features include a three-piece enclosure that mounts directly to a wall box or on any wall. Available with various options. Including set point adjustments, push button overrides, etc.
Display Type LCD Display LED Display
Power Supply 12 – 30 VAC/DC at 2mA max 12 – 30 VAC/DC at 30mA max
Display Units °C or °F (factory set) °C or °F (jumper selectable)
Display Range 0.0 – 35.0°C (32.0 – 95.0°F) 10.0 – 35.5°C (50.0 – 96.0°F)
Display Resolution 0.1°C (0.1°F) 0.5°C (1.0°F)
Display Size 23 mm W x 11 mm H (0.9” W x 0.45” H) 3 digit x 30 mm W x 7.6 mm H (1.18” W x 0.3” H)
Available Options Various sensors, set points, push buttons, external jacks, and logos.
GREYSTONE ENERGY SYSTEMS INC. Q M I
ISO 9002
MODEL Product Description
TE200 TE500
Sensor assembly Sensor assembly c/w transmitter (sensor type 12 is standard)
CODE Enclosure
A AD AS
Micro (not available with transmitter or options) Designer S/S plate
CODE Sensor
2 5 6 7 8 9 11 12 13 14 20 21 24
PT100-100 ohm Platinum, IEC 751, 385 Alpha, thin film 1801 ohm, NTC Thermistor, ±0.2°C 3,000 ohm, NTC Thermistor, ±0.2°C 10,000 ohm, type 3, NTC Thermistor, ±0.2°C 2.252 K ohm NTC Thermistor, ±0.2°C 100,000 ohm, NTC Thermistor, ±0.2°C LM334 IC, 1.0uA/°C PT1000-1000 ohm Platinum, IEC 751, 0.385 Alpha, thin film 1000 ohm nickel 10,000 ohm type 3, NTC Thermistor, ±0.2°C c/w 11k shunt resistor 20,000 ohm, NTC Thermistor, ±0.2°C LM335 IC, 10mv/°C 10,000 ohm, type 2, NTC Thermistor, ±0.2°C
CODE Options (TE200AD assembly only) AP
AS BS AM BC BF AC AF LY LR LG CJ AE AI
20-30K linear slide pot for set point control Concealed push button momentary switch (NO) Exposed push button momentary switch (NO) Alcohol thermometer °C & °F Bi-metal thermometer °C Bi-metal thermometer °F 3-digit LCD temperature indicator °C 3-digit LCD temperature indicator °F Yellow LED Red LED Green LED External jack for remote system access (phono jack) External jack for remote system access (4-pin header) Internal jack (RJ-45)
CODE TE500 Transmitter Power Supply 1 24 VAC/DC CODE TE500 Transmitter Output Option
A D E
Current 4 – 20mA Voltage 0 – 5 VDC Voltage 0 – 10 VDC
CODE TE500 Transmitter Range Option
1 2
0°C – 35°C (32°F – 95°F) 0°C – 50°C (32°F – 122°F)
TE500 AD 12 - 1 A 2
Greystone Energy Systems, Inc. reserves the right to make design modifications without prior notice.
SPACE TEMPERATURE SENSORS/TRANSMITTERS: PRODUCT ORDERING INFORMATION
EXAMPLE: Designer space, c/w PT1000Ω RTD, 4–20mA transmitter with a 0°C – 50°C (32°F – 122°F) range.
NOTE: Due to the many possible configurations, special part numbers may be required, please contact Greystone for more information.
GREYSTONE ENERGY SYSTEMS INC. Q M I
ISO 9002
Malaspina University-College School of Management Centre 900 Fifth Street, Nanaimo BC
DDC Controls Shop Drawing Submittal
Submitted To:
Windley Contracting Ltd. 3711 Shenton Road Nanaimo, British Columbia V9T 2H1
Submitted By: Joe LeRoy, P.Eng 19-831 Devonshire Rd. Victoria, BC V9A 4T5 250 388-5665
Submittal Details:
Date Submitted: 3/30/2006 Date Resubmitted: Specification Section: 15900.2.2.1 Description: Room temperature sensor with pushbutton override Model: TE200AD7BS
Supplier info:
Name: Pacific Controls Ltd. Address: 440 Garbally Road, Victoria, BC V8T 2S9
Manufacturer info: Name: Greystone Energy Systems Inc. Address: 150 English Drive, Moncton, NB E1E 4G7 Website www.greystoneenergy.com
houle controls (a div. of houle electric ltd.)
FEATURES: The TE Series Space Temperature sensors are available in four different enclosure styles. They are available with a choice of precision RTD’s, IC’s, or thermistors. A number of options, such as momentary override and setpoint adjustment are also available for various configurations. A transmitter option is also available to be used with the 1000 ohm platinum sensor which provides either 4 -20mA, 0 – 5 VDC or 0 – 10 VDC output proportional to a selected temperature span. A 100 ohm platinum sensor transmitter is optional. The transmitters provide high accuracy, long-term
stability, low hysteresis, fast response and a wide operating temperature range. Every transmitter offers accuracy of 0.1% of span or better and are highly stable due to excellent RFI rejection and are also virtually immune to power supply noise and input voltage fluctuations. Transmitter General Specifications: Supply Voltage: 24 VDC/VAC Output: 4 – 20mA, 0–5 VDC or 0-10 VDC Accuracy: ±0.1% of span Operating temp: 0°C – 70°C (32°F – 158°F) Calibration In compliance with ANSI/NCSL 2540-11994
AS) Surface - A stainless steel plate which can be mounted to a wall box used where tamper-proof or protection is required. Available with various options, including push button overrides, etc.
SPACE/WALL MOUNT TRANSMITTER:
A) Micro – Includes a compact snap-mounted cover for ease of installation, available with various temperature sensors.
AD) Designer – Features include a three-piece enclosure that mounts directly to a wall box or on any wall. Available with various options. Including set point adjustments, push button overrides, etc.
Display Type LCD Display LED Display
Power Supply 12 – 30 VAC/DC at 2mA max 12 – 30 VAC/DC at 30mA max
Display Units °C or °F (factory set) °C or °F (jumper selectable)
Display Range 0.0 – 35.0°C (32.0 – 95.0°F) 10.0 – 35.5°C (50.0 – 96.0°F)
Display Resolution 0.1°C (0.1°F) 0.5°C (1.0°F)
Display Size 23 mm W x 11 mm H (0.9” W x 0.45” H) 3 digit x 30 mm W x 7.6 mm H (1.18” W x 0.3” H)
Available Options Various sensors, set points, push buttons, external jacks, and logos.
GREYSTONE ENERGY SYSTEMS INC. Q M I
ISO 9002
MODEL Product Description
TE200 TE500
Sensor assembly Sensor assembly c/w transmitter (sensor type 12 is standard)
CODE Enclosure
A AD AS
Micro (not available with transmitter or options) Designer S/S plate
CODE Sensor
2 5 6 7 8 9 11 12 13 14 20 21 24
PT100-100 ohm Platinum, IEC 751, 385 Alpha, thin film 1801 ohm, NTC Thermistor, ±0.2°C 3,000 ohm, NTC Thermistor, ±0.2°C 10,000 ohm, type 3, NTC Thermistor, ±0.2°C 2.252 K ohm NTC Thermistor, ±0.2°C 100,000 ohm, NTC Thermistor, ±0.2°C LM334 IC, 1.0uA/°C PT1000-1000 ohm Platinum, IEC 751, 0.385 Alpha, thin film 1000 ohm nickel 10,000 ohm type 3, NTC Thermistor, ±0.2°C c/w 11k shunt resistor 20,000 ohm, NTC Thermistor, ±0.2°C LM335 IC, 10mv/°C 10,000 ohm, type 2, NTC Thermistor, ±0.2°C
CODE Options (TE200AD assembly only) AP
AS BS AM BC BF AC AF LY LR LG CJ AE AI
20-30K linear slide pot for set point control Concealed push button momentary switch (NO) Exposed push button momentary switch (NO) Alcohol thermometer °C & °F Bi-metal thermometer °C Bi-metal thermometer °F 3-digit LCD temperature indicator °C 3-digit LCD temperature indicator °F Yellow LED Red LED Green LED External jack for remote system access (phono jack) External jack for remote system access (4-pin header) Internal jack (RJ-45)
CODE TE500 Transmitter Power Supply 1 24 VAC/DC CODE TE500 Transmitter Output Option
A D E
Current 4 – 20mA Voltage 0 – 5 VDC Voltage 0 – 10 VDC
CODE TE500 Transmitter Range Option
1 2
0°C – 35°C (32°F – 95°F) 0°C – 50°C (32°F – 122°F)
TE500 AD 12 - 1 A 2
Greystone Energy Systems, Inc. reserves the right to make design modifications without prior notice.
SPACE TEMPERATURE SENSORS/TRANSMITTERS: PRODUCT ORDERING INFORMATION
EXAMPLE: Designer space, c/w PT1000Ω RTD, 4–20mA transmitter with a 0°C – 50°C (32°F – 122°F) range.
NOTE: Due to the many possible configurations, special part numbers may be required, please contact Greystone for more information.
GREYSTONE ENERGY SYSTEMS INC. Q M I
ISO 9002
Malaspina University-College School of Management Centre 900 Fifth Street, Nanaimo BC
DDC Controls Shop Drawing Submittal
Submitted To:
Windley Contracting Ltd. 3711 Shenton Road Nanaimo, British Columbia V9T 2H1
Submitted By: Joe LeRoy, P.Eng 19-831 Devonshire Rd. Victoria, BC V9A 4T5 250 388-5665
Submittal Details:
Date Submitted: 3/30/2006 Date Resubmitted: Specification Section: 15900.2.4.3 Description: Duct temperature sensor Model: TE200B7D2
Supplier info:
Name: Pacific Controls Ltd. Address: 440 Garbally Road, Victoria, BC V8T 2S9
Manufacturer info: Name: Greystone Energy Systems Inc. Address: 150 English Drive, Moncton, NB E1E 4G7 Website www.greystoneenergy.com
houle controls (a div. of houle electric ltd.)
FEATURES:
The TE Series Temperature sensors offer a choice of precision platinum RTD’s, IC, or NTC thermistor sensors which can be interfaced with a computerized monitoring or control system. The sensors are available in different housings, with various configurations and options for duct, immersion, duct averaging, remote strap-on and outside air applications. The single point sensors are encapsulated in a 6.35 mm (0.25”) OD 304 stainless steel probe. All probes are constructed to provide good heat transfer and fast response. The averaging sensors are available in both plenum rated cable or with a copper probe.
The TE500 transmitter option is standard with the 1000Ω platinum sensor and provides either 4 – 20mA, 0 – 5 VDC or 0 – 10 VDC output over a selected range. It is powered by either 24 VAC or VDC. A 100Ω platinum sensor transmitter is optional. Transmitter General Specifications: Supply Voltage: 24 VDC/VAC Output: 4–20mA, 0–5 VDC or 0-10 VDC Accuracy: ±0.1% of span Operating temp: 0ºC – 70ºC (32ºF – 158ºF) OSA operating temp: -40°C – 85°C (-40°F – 185°F) Calibration: In compliance with ANSI/NCSL 2540-11994
E) Strap-on Sensor – Is a stainless steel probe and is used in remote applications where an immersion sensor can not be installed.
F) OSA Sensor – Comes in an aluminum LB c/w ½” NPT fitting for connection to conduit. It incorporates a sun/wind shield to protect the sensor
B) Duct Sensor – For single point monitoring. It is available with various probe lengths and enclosures to fit any application.
C) Immersion Sensor – Comes in two configurations. It has either spring loaded or non-spring loaded probes and has a ½” NPT fitting to be mounted into a thermowell. It is available in various lengths and enclosures styles.
TRANSMITTER:
PROBE SENSORS
GREYSTONE ENERGY SYSTEMS INC. Q M I
ISO 9002
FD) Flex-Duct Sensor – Is made of flexible plenum rated cable which incorporates numerous sensors along the assembly. It acts as a single sensor averaging any temperature change across the sensors.
D) Duct Average Sensor – Incorporates numerous sensors inside a copper tube. It acts as a single sensor, averaging any temperature change across the sensors.
NOTE: Standard probe assemblies are rated at -40°C – 105°C (-40°F - 221°F). For higher or lower temperature applications, please contact Greystone.
MODEL Product Description
TE200 TE500
Sensor assembly Sensor assembly c/w transmitter (sensor type 12 is standard)
CODE Style
AP B
BB C D E F
FD G H
HC
All purpose Duct mount Duct probe w/ mounting bracket only Immersion Duct average (copper) Strap-on Outside Air Duct average (flexible plenum rated cable) Glass Stack Clip
CODE Enclosure (GES ABS enclosure is standard) CODE Flex Duct Only
- M R W
ABS enclosure, standard (no code required, leave blank) Metal utility box No box Aluminum weatherproof box
A B C D
CODE Sensor
2 4 5 6 7 8 9
11 12 13 20 21 24
PT100-100Ω Platinum,IEC 751, 385 Alpha, thin film PT100–100Ω Platinum, IEC 751, 385 Alpha, wire wound-ceramic* (see below) 1801Ω, NTC Thermistor, ±0.2°C 3000Ω, NTC Thermistor, ±0.2°C 10,000Ω, type 3, NTC Thermistor, ±0.2°C 2.252KΩ, NTC Thermistor, ±0.2°C 100,000Ω, NTC Thermistor, ±0.2°C LM334 IC, 1.0uA/°C PT1000Ω Platinum, IEC 751, 385 Alpha, thin film 1000Ω Nickel 20,000Ω, NTC Thermsitor, ±0.2°C LM335 IC, 10mv/°C 10,000Ω, type 2, NTC Thermistor, ±0.2°C *must use for high temp. applications over 400°C (752°F)
CODE Probe Length CODE Copper Avg. (D) CODE Flex Avg. (FD)
A B C D E F
50 mm (2”) 100 mm (4”) 150 mm (6”) 200 mm (8”) 300 mm (12”) 450 mm (18”)
G H I J
1800 mm (6’) 3600 mm (12’) 6100 mm (20’) 7300 mm (24’)
A B C D
1800 mm (6’) 3600 mm (12’) 6100 mm (20’) 7300 mm (24’)
CODE Probe Material (not required for F, FD, G, HC)
2 3
Stainless steel Copper (rigid duct average only)
CODE Fitting (only required for immersion)
A E
Spring loaded 1/2” NPT Non-spring loaded 1/2” NPT
CODE TE500 Transmitter Power Supply
1 24 VAC/VDC
CODE TE500 Transmitter Output Option
A D E
4 – 20mA 0 – 5 VDC 0 – 10 VDC
CODE TE500 Transmitter Range Option
1 2 3 4 5 6
0°C – 35°C (32°F – 95°F) 0°C – 50°C (32°F – 122°F) 0°C – 100°C (32°F – 212°F) 50°C – 150°C (122°F – 302°F) 50°C – 250°C (122°F – 482°F) -50°C – +50°C (-58°F – 122°F)
Custom ranges available upon request.
TE200 D - 7 I 3 - - - -
Greystone Energy Systems, Inc. reserves the right to make design modifications without prior notice.
Lead only, no box ABS enclosure Aluminum weatherpoof box Metal utility box
PROBE TEMPERATURE SENSORS/TRANSDUCERS: PRODUCT ORDERING INFORMATION
GREYSTONE ENERGY SYSTEMS INC. Q M I
ISO 9002
Malaspina University-College School of Management Centre 900 Fifth Street, Nanaimo BC
DDC Controls Shop Drawing Submittal
Submitted To:
Windley Contracting Ltd. 3711 Shenton Road Nanaimo, British Columbia V9T 2H1
Submitted By: Joe LeRoy, P.Eng 19-831 Devonshire Rd. Victoria, BC V9A 4T5 250 388-5665
Submittal Details:
Date Submitted: 3/30/2006 Date Resubmitted: Specification Section: 15900.2.4.5 Description: 4" immersion temperature sensor Model: TE200C7B2E
Supplier info:
Name: Pacific Controls Ltd. Address: 440 Garbally Road, Victoria, BC V8T 2S9
Manufacturer info: Name: Greystone Energy Systems Inc. Address: 150 English Drive, Moncton, NB E1E 4G7 Website www.greystoneenergy.com
houle controls (a div. of houle electric ltd.)
FEATURES:
The TE Series Temperature sensors offer a choice of precision platinum RTD’s, IC, or NTC thermistor sensors which can be interfaced with a computerized monitoring or control system. The sensors are available in different housings, with various configurations and options for duct, immersion, duct averaging, remote strap-on and outside air applications. The single point sensors are encapsulated in a 6.35 mm (0.25”) OD 304 stainless steel probe. All probes are constructed to provide good heat transfer and fast response. The averaging sensors are available in both plenum rated cable or with a copper probe.
The TE500 transmitter option is standard with the 1000Ω platinum sensor and provides either 4 – 20mA, 0 – 5 VDC or 0 – 10 VDC output over a selected range. It is powered by either 24 VAC or VDC. A 100Ω platinum sensor transmitter is optional. Transmitter General Specifications: Supply Voltage: 24 VDC/VAC Output: 4–20mA, 0–5 VDC or 0-10 VDC Accuracy: ±0.1% of span Operating temp: 0ºC – 70ºC (32ºF – 158ºF) OSA operating temp: -40°C – 85°C (-40°F – 185°F) Calibration: In compliance with ANSI/NCSL 2540-11994
E) Strap-on Sensor – Is a stainless steel probe and is used in remote applications where an immersion sensor can not be installed.
F) OSA Sensor – Comes in an aluminum LB c/w ½” NPT fitting for connection to conduit. It incorporates a sun/wind shield to protect the sensor
B) Duct Sensor – For single point monitoring. It is available with various probe lengths and enclosures to fit any application.
C) Immersion Sensor – Comes in two configurations. It has either spring loaded or non-spring loaded probes and has a ½” NPT fitting to be mounted into a thermowell. It is available in various lengths and enclosures styles.
TRANSMITTER:
PROBE SENSORS
GREYSTONE ENERGY SYSTEMS INC. Q M I
ISO 9002
FD) Flex-Duct Sensor – Is made of flexible plenum rated cable which incorporates numerous sensors along the assembly. It acts as a single sensor averaging any temperature change across the sensors.
D) Duct Average Sensor – Incorporates numerous sensors inside a copper tube. It acts as a single sensor, averaging any temperature change across the sensors.
NOTE: Standard probe assemblies are rated at -40°C – 105°C (-40°F - 221°F). For higher or lower temperature applications, please contact Greystone.
MODEL Product Description
TE200 TE500
Sensor assembly Sensor assembly c/w transmitter (sensor type 12 is standard)
CODE Style
AP B
BB C D E F
FD G H
HC
All purpose Duct mount Duct probe w/ mounting bracket only Immersion Duct average (copper) Strap-on Outside Air Duct average (flexible plenum rated cable) Glass Stack Clip
CODE Enclosure (GES ABS enclosure is standard) CODE Flex Duct Only
- M R W
ABS enclosure, standard (no code required, leave blank) Metal utility box No box Aluminum weatherproof box
A B C D
CODE Sensor
2 4 5 6 7 8 9
11 12 13 20 21 24
PT100-100Ω Platinum,IEC 751, 385 Alpha, thin film PT100–100Ω Platinum, IEC 751, 385 Alpha, wire wound-ceramic* (see below) 1801Ω, NTC Thermistor, ±0.2°C 3000Ω, NTC Thermistor, ±0.2°C 10,000Ω, type 3, NTC Thermistor, ±0.2°C 2.252KΩ, NTC Thermistor, ±0.2°C 100,000Ω, NTC Thermistor, ±0.2°C LM334 IC, 1.0uA/°C PT1000Ω Platinum, IEC 751, 385 Alpha, thin film 1000Ω Nickel 20,000Ω, NTC Thermsitor, ±0.2°C LM335 IC, 10mv/°C 10,000Ω, type 2, NTC Thermistor, ±0.2°C *must use for high temp. applications over 400°C (752°F)
CODE Probe Length CODE Copper Avg. (D) CODE Flex Avg. (FD)
A B C D E F
50 mm (2”) 100 mm (4”) 150 mm (6”) 200 mm (8”) 300 mm (12”) 450 mm (18”)
G H I J
1800 mm (6’) 3600 mm (12’) 6100 mm (20’) 7300 mm (24’)
A B C D
1800 mm (6’) 3600 mm (12’) 6100 mm (20’) 7300 mm (24’)
CODE Probe Material (not required for F, FD, G, HC)
2 3
Stainless steel Copper (rigid duct average only)
CODE Fitting (only required for immersion)
A E
Spring loaded 1/2” NPT Non-spring loaded 1/2” NPT
CODE TE500 Transmitter Power Supply
1 24 VAC/VDC
CODE TE500 Transmitter Output Option
A D E
4 – 20mA 0 – 5 VDC 0 – 10 VDC
CODE TE500 Transmitter Range Option
1 2 3 4 5 6
0°C – 35°C (32°F – 95°F) 0°C – 50°C (32°F – 122°F) 0°C – 100°C (32°F – 212°F) 50°C – 150°C (122°F – 302°F) 50°C – 250°C (122°F – 482°F) -50°C – +50°C (-58°F – 122°F)
Custom ranges available upon request.
TE200 D - 7 I 3 - - - -
Greystone Energy Systems, Inc. reserves the right to make design modifications without prior notice.
Lead only, no box ABS enclosure Aluminum weatherpoof box Metal utility box
PROBE TEMPERATURE SENSORS/TRANSDUCERS: PRODUCT ORDERING INFORMATION
GREYSTONE ENERGY SYSTEMS INC. Q M I
ISO 9002
Malaspina University-College School of Management Centre 900 Fifth Street, Nanaimo BC
DDC Controls Shop Drawing Submittal
Submitted To:
Windley Contracting Ltd. 3711 Shenton Road Nanaimo, British Columbia V9T 2H1
Submitted By: Joe LeRoy, P.Eng 19-831 Devonshire Rd. Victoria, BC V9A 4T5 250 388-5665
Submittal Details:
Date Submitted: 3/30/2006 Date Resubmitted: Specification Section: 15900.2.4.5 Description: 4" Brass thermowell Model: T1-1/2BR4
Supplier info:
Name: Pacific Controls Ltd. Address: 440 Garbally Road, Victoria, BC V8T 2S9
Manufacturer info: Name: Greystone Energy Systems Inc. Address: 150 English Drive, Moncton, NB E1E 4G7 Website www.greystoneenergy.com
houle controls (a div. of houle electric ltd.)
OPTIONS: Immersion Wells
ASSEMBLIES: ENCLOSURES:
G) Glass
W) Aluminum Weatherproof Box
AP) All Purpose
BB) Duct probe c/w mounting bracket
GES ABS Enclosure
H) Stack
M) Stamped Metal Utility Box
Greystone Energy Systems Inc., established in 1983, is Canada’s largest manufacturer of HVAC sensors and
transducers for Building Automation Management Systems. We have conscientiously established a worldwide reputation
as an industry leader by maintaining leading-edge design technology, prompt technical support, and a commitment to
on-time deliveries. We take pride in our Quality Management System which is ISO 9002 certified, assuring
our customers of consistent product reliability.
GREYSTONE IS AN ISO 9002 REGISTERED COMPANY
Greystone Energy Systems Inc. 150 English Drive, Moncton, NB Canada E1E 4G7 (506) 853-3057 Fax: (506) 853-6014 e-mail: [email protected] www.greystoneenergy.com
Q M I
ISO 9002
Malaspina University-College School of Management Centre 900 Fifth Street, Nanaimo BC
DDC Controls Shop Drawing Submittal
Submitted To:
Windley Contracting Ltd. 3711 Shenton Road Nanaimo, British Columbia V9T 2H1
Submitted By: Joe LeRoy, P.Eng 19-831 Devonshire Rd. Victoria, BC V9A 4T5 250 388-5665
Submittal Details:
Date Submitted: 3/30/2006 Date Resubmitted: Specification Section: 15900.2.4.2 Description: Outdoor air temperature sensor Model: TE200F7
Supplier info:
Name: Pacific Controls Ltd. Address: 440 Garbally Road, Victoria, BC V8T 2S9
Manufacturer info: Name: Greystone Energy Systems Inc. Address: 150 English Drive, Moncton, NB E1E 4G7 Website www.greystoneenergy.com
houle controls (a div. of houle electric ltd.)
FEATURES:
The TE Series Temperature sensors offer a choice of precision platinum RTD’s, IC, or NTC thermistor sensors which can be interfaced with a computerized monitoring or control system. The sensors are available in different housings, with various configurations and options for duct, immersion, duct averaging, remote strap-on and outside air applications. The single point sensors are encapsulated in a 6.35 mm (0.25”) OD 304 stainless steel probe. All probes are constructed to provide good heat transfer and fast response. The averaging sensors are available in both plenum rated cable or with a copper probe.
The TE500 transmitter option is standard with the 1000Ω platinum sensor and provides either 4 – 20mA, 0 – 5 VDC or 0 – 10 VDC output over a selected range. It is powered by either 24 VAC or VDC. A 100Ω platinum sensor transmitter is optional. Transmitter General Specifications: Supply Voltage: 24 VDC/VAC Output: 4–20mA, 0–5 VDC or 0-10 VDC Accuracy: ±0.1% of span Operating temp: 0ºC – 70ºC (32ºF – 158ºF) OSA operating temp: -40°C – 85°C (-40°F – 185°F) Calibration: In compliance with ANSI/NCSL 2540-11994
E) Strap-on Sensor – Is a stainless steel probe and is used in remote applications where an immersion sensor can not be installed.
F) OSA Sensor – Comes in an aluminum LB c/w ½” NPT fitting for connection to conduit. It incorporates a sun/wind shield to protect the sensor
B) Duct Sensor – For single point monitoring. It is available with various probe lengths and enclosures to fit any application.
C) Immersion Sensor – Comes in two configurations. It has either spring loaded or non-spring loaded probes and has a ½” NPT fitting to be mounted into a thermowell. It is available in various lengths and enclosures styles.
TRANSMITTER:
PROBE SENSORS
GREYSTONE ENERGY SYSTEMS INC. Q M I
ISO 9002
FD) Flex-Duct Sensor – Is made of flexible plenum rated cable which incorporates numerous sensors along the assembly. It acts as a single sensor averaging any temperature change across the sensors.
D) Duct Average Sensor – Incorporates numerous sensors inside a copper tube. It acts as a single sensor, averaging any temperature change across the sensors.
NOTE: Standard probe assemblies are rated at -40°C – 105°C (-40°F - 221°F). For higher or lower temperature applications, please contact Greystone.
MODEL Product Description
TE200 TE500
Sensor assembly Sensor assembly c/w transmitter (sensor type 12 is standard)
CODE Style
AP B
BB C D E F
FD G H
HC
All purpose Duct mount Duct probe w/ mounting bracket only Immersion Duct average (copper) Strap-on Outside Air Duct average (flexible plenum rated cable) Glass Stack Clip
CODE Enclosure (GES ABS enclosure is standard) CODE Flex Duct Only
- M R W
ABS enclosure, standard (no code required, leave blank) Metal utility box No box Aluminum weatherproof box
A B C D
CODE Sensor
2 4 5 6 7 8 9
11 12 13 20 21 24
PT100-100Ω Platinum,IEC 751, 385 Alpha, thin film PT100–100Ω Platinum, IEC 751, 385 Alpha, wire wound-ceramic* (see below) 1801Ω, NTC Thermistor, ±0.2°C 3000Ω, NTC Thermistor, ±0.2°C 10,000Ω, type 3, NTC Thermistor, ±0.2°C 2.252KΩ, NTC Thermistor, ±0.2°C 100,000Ω, NTC Thermistor, ±0.2°C LM334 IC, 1.0uA/°C PT1000Ω Platinum, IEC 751, 385 Alpha, thin film 1000Ω Nickel 20,000Ω, NTC Thermsitor, ±0.2°C LM335 IC, 10mv/°C 10,000Ω, type 2, NTC Thermistor, ±0.2°C *must use for high temp. applications over 400°C (752°F)
CODE Probe Length CODE Copper Avg. (D) CODE Flex Avg. (FD)
A B C D E F
50 mm (2”) 100 mm (4”) 150 mm (6”) 200 mm (8”) 300 mm (12”) 450 mm (18”)
G H I J
1800 mm (6’) 3600 mm (12’) 6100 mm (20’) 7300 mm (24’)
A B C D
1800 mm (6’) 3600 mm (12’) 6100 mm (20’) 7300 mm (24’)
CODE Probe Material (not required for F, FD, G, HC)
2 3
Stainless steel Copper (rigid duct average only)
CODE Fitting (only required for immersion)
A E
Spring loaded 1/2” NPT Non-spring loaded 1/2” NPT
CODE TE500 Transmitter Power Supply
1 24 VAC/VDC
CODE TE500 Transmitter Output Option
A D E
4 – 20mA 0 – 5 VDC 0 – 10 VDC
CODE TE500 Transmitter Range Option
1 2 3 4 5 6
0°C – 35°C (32°F – 95°F) 0°C – 50°C (32°F – 122°F) 0°C – 100°C (32°F – 212°F) 50°C – 150°C (122°F – 302°F) 50°C – 250°C (122°F – 482°F) -50°C – +50°C (-58°F – 122°F)
Custom ranges available upon request.
TE200 D - 7 I 3 - - - -
Greystone Energy Systems, Inc. reserves the right to make design modifications without prior notice.
Lead only, no box ABS enclosure Aluminum weatherpoof box Metal utility box
PROBE TEMPERATURE SENSORS/TRANSDUCERS: PRODUCT ORDERING INFORMATION
GREYSTONE ENERGY SYSTEMS INC. Q M I
ISO 9002
Malaspina University-College School of Management Centre 900 Fifth Street, Nanaimo BC
DDC Controls Shop Drawing Submittal
Submitted To:
Windley Contracting Ltd. 3711 Shenton Road Nanaimo, British Columbia V9T 2H1
Submitted By: Joe LeRoy, P.Eng 19-831 Devonshire Rd. Victoria, BC V9A 4T5 250 388-5665
Submittal Details:
Date Submitted: 3/30/2006 Date Resubmitted: Specification Section: 15900.2.4.4 Description: Average duct temperature sensor 20' Model: TE200FDB7C
Supplier info:
Name: Pacific Controls Ltd. Address: 440 Garbally Road, Victoria, BC V8T 2S9
Manufacturer info: Name: Greystone Energy Systems Inc. Address: 150 English Drive, Moncton, NB E1E 4G7 Website www.greystoneenergy.com
houle controls (a div. of houle electric ltd.)
FEATURES:
The TE Series Temperature sensors offer a choice of precision platinum RTD’s, IC, or NTC thermistor sensors which can be interfaced with a computerized monitoring or control system. The sensors are available in different housings, with various configurations and options for duct, immersion, duct averaging, remote strap-on and outside air applications. The single point sensors are encapsulated in a 6.35 mm (0.25”) OD 304 stainless steel probe. All probes are constructed to provide good heat transfer and fast response. The averaging sensors are available in both plenum rated cable or with a copper probe.
The TE500 transmitter option is standard with the 1000Ω platinum sensor and provides either 4 – 20mA, 0 – 5 VDC or 0 – 10 VDC output over a selected range. It is powered by either 24 VAC or VDC. A 100Ω platinum sensor transmitter is optional. Transmitter General Specifications: Supply Voltage: 24 VDC/VAC Output: 4–20mA, 0–5 VDC or 0-10 VDC Accuracy: ±0.1% of span Operating temp: 0ºC – 70ºC (32ºF – 158ºF) OSA operating temp: -40°C – 85°C (-40°F – 185°F) Calibration: In compliance with ANSI/NCSL 2540-11994
E) Strap-on Sensor – Is a stainless steel probe and is used in remote applications where an immersion sensor can not be installed.
F) OSA Sensor – Comes in an aluminum LB c/w ½” NPT fitting for connection to conduit. It incorporates a sun/wind shield to protect the sensor
B) Duct Sensor – For single point monitoring. It is available with various probe lengths and enclosures to fit any application.
C) Immersion Sensor – Comes in two configurations. It has either spring loaded or non-spring loaded probes and has a ½” NPT fitting to be mounted into a thermowell. It is available in various lengths and enclosures styles.
TRANSMITTER:
PROBE SENSORS
GREYSTONE ENERGY SYSTEMS INC. Q M I
ISO 9002
FD) Flex-Duct Sensor – Is made of flexible plenum rated cable which incorporates numerous sensors along the assembly. It acts as a single sensor averaging any temperature change across the sensors.
D) Duct Average Sensor – Incorporates numerous sensors inside a copper tube. It acts as a single sensor, averaging any temperature change across the sensors.
NOTE: Standard probe assemblies are rated at -40°C – 105°C (-40°F - 221°F). For higher or lower temperature applications, please contact Greystone.
MODEL Product Description
TE200 TE500
Sensor assembly Sensor assembly c/w transmitter (sensor type 12 is standard)
CODE Style
AP B
BB C D E F
FD G H
HC
All purpose Duct mount Duct probe w/ mounting bracket only Immersion Duct average (copper) Strap-on Outside Air Duct average (flexible plenum rated cable) Glass Stack Clip
CODE Enclosure (GES ABS enclosure is standard) CODE Flex Duct Only
- M R W
ABS enclosure, standard (no code required, leave blank) Metal utility box No box Aluminum weatherproof box
A B C D
CODE Sensor
2 4 5 6 7 8 9
11 12 13 20 21 24
PT100-100Ω Platinum,IEC 751, 385 Alpha, thin film PT100–100Ω Platinum, IEC 751, 385 Alpha, wire wound-ceramic* (see below) 1801Ω, NTC Thermistor, ±0.2°C 3000Ω, NTC Thermistor, ±0.2°C 10,000Ω, type 3, NTC Thermistor, ±0.2°C 2.252KΩ, NTC Thermistor, ±0.2°C 100,000Ω, NTC Thermistor, ±0.2°C LM334 IC, 1.0uA/°C PT1000Ω Platinum, IEC 751, 385 Alpha, thin film 1000Ω Nickel 20,000Ω, NTC Thermsitor, ±0.2°C LM335 IC, 10mv/°C 10,000Ω, type 2, NTC Thermistor, ±0.2°C *must use for high temp. applications over 400°C (752°F)
CODE Probe Length CODE Copper Avg. (D) CODE Flex Avg. (FD)
A B C D E F
50 mm (2”) 100 mm (4”) 150 mm (6”) 200 mm (8”) 300 mm (12”) 450 mm (18”)
G H I J
1800 mm (6’) 3600 mm (12’) 6100 mm (20’) 7300 mm (24’)
A B C D
1800 mm (6’) 3600 mm (12’) 6100 mm (20’) 7300 mm (24’)
CODE Probe Material (not required for F, FD, G, HC)
2 3
Stainless steel Copper (rigid duct average only)
CODE Fitting (only required for immersion)
A E
Spring loaded 1/2” NPT Non-spring loaded 1/2” NPT
CODE TE500 Transmitter Power Supply
1 24 VAC/VDC
CODE TE500 Transmitter Output Option
A D E
4 – 20mA 0 – 5 VDC 0 – 10 VDC
CODE TE500 Transmitter Range Option
1 2 3 4 5 6
0°C – 35°C (32°F – 95°F) 0°C – 50°C (32°F – 122°F) 0°C – 100°C (32°F – 212°F) 50°C – 150°C (122°F – 302°F) 50°C – 250°C (122°F – 482°F) -50°C – +50°C (-58°F – 122°F)
Custom ranges available upon request.
TE200 D - 7 I 3 - - - -
Greystone Energy Systems, Inc. reserves the right to make design modifications without prior notice.
Lead only, no box ABS enclosure Aluminum weatherpoof box Metal utility box
PROBE TEMPERATURE SENSORS/TRANSDUCERS: PRODUCT ORDERING INFORMATION
GREYSTONE ENERGY SYSTEMS INC. Q M I
ISO 9002
Malaspina University-College School of Management Centre 900 Fifth Street, Nanaimo BC
DDC Controls Shop Drawing Submittal
Submitted To:
Windley Contracting Ltd. 3711 Shenton Road Nanaimo, British Columbia V9T 2H1
Submitted By: Joe LeRoy, P.Eng 19-831 Devonshire Rd. Victoria, BC V9A 4T5 250 388-5665
Submittal Details:
Date Submitted: 3/30/2006 Date Resubmitted: Specification Section: 15900.2.9 Description: CO2 detector Duct Mounted Model: CCD1A6000
Supplier info:
Name: Pacific Controls Ltd. Address: 440 Garbally Road, Victoria, BC V8T 2S9
Manufacturer info: Name: Greystone Energy Systems Inc. Address: 150 English Drive, Moncton, NB E1E 4G7 Website www.greystoneenergy.com
houle controls (a div. of houle electric ltd.)
Environmental, industrial and commercial indoor Carbon Dioxide (CO2) gas detector. Available in both a space and duct mount version.
APPLICATION: To sense and transmit to any compatible electronic analog control, DDC/PLC controller or automation system for the control of ventilation equipment. Designed to meet ventilation requirements specified in ASHRAE Standard 62-1989. FEATURES:
• Setup/calibration fully menu driven (requires LCD option)
• Monitors CO2 over range 0-2000 PPM (factory default)
• Field adjustable range from 0-1500 PPM up to 10,000 PPM without re-calibration!
• NDIR single beam with patented ACLP self- calibration algorithm
• Guaranteed 5 year calibration interval • Optional on board relay with field adjustable trip
point • Optional LCD for displaying PPM level and menu
options • Powered by either AC or DC source with no
change to circuit required • Choice of two field adjustable analog output
signals, linearized over full range • Easy to calibrate in the field
CO2 DETECTOR
SPECIFICATIONS CO2 DETECTOR – Product # CDD
Gas Detected Carbon Dioxide (CO2)
Range 0 – 2000 ppm standard, programmable from 1500 up to 10,000 ppm in 500 ppm increments
Standard Accuracy ±75 PPM or3% of reading (whichever is greater) 15-32 C (59-90 F) for 0-2000 ppm range ±5% of reading for 2000-10,000 ppm
Extended Accuracy ±150 ppm or 5% of reading (whichever is greater) 0-50 C (32-122 F) for 0-2000 ppm range ±7% of reading for 2000-10,000 ppm
Sensing Element Non-Dispersive Infrared (NDIR)
Operation Conditions 0-50C(32-122F), 0-95% RH non-condensing
Repeatability ±20 PPM
Stability ±20 PPM typical, 5 year calibration interval
Manufacturing Process ISO 9002 certified
Output Signal 4-20 mA active (sourcing), 0-5Vdc and 0-10Vdc, jumper selectable (Note correct part number)
Output Drive Capability 550 ohm max for current output, 10 Kohm min for voltage output
Output Resolution 10 bit PWM
LCD Display (optional) LCD for displaying PPM level (required for field programming) 1 ppm resolution, 1.1” w x 0.5” h (28 x 13 mm) alpha-numeric 2 line x 8 characters
Field Calibration Calibration, applying calibration gas standards (Contact Greystone for Calibration kit)
External Dimensions Corporate Space – 91mm W x 127mm H x 43 mm D (3.6” x 5” x 1.7”) Duct ABS – 124 mm W x 183 mm H x 43 mm D (4.9” x 7.22” x 1.69”)
GREYSTONE ENERGY SYSTEMS INC. Q M I
ISO 9002
Duct Mount ABS Enclosure with Sampling Tube
GREYSTONE ENERGY SYSTEMS INC. Q M I
ISO 9002
SPECIFICATIONS (Con’t) CO2 DETECTOR – Product # CDD
Pressure Dependence 0.13% of reading per mm Hg
Altitude Correction Programmable from 0-5000 ft in 500 ft increments
Response Time < 60 seconds for 90% step change
Warm-up Time < two (2) minutes
Power Supply 20-30 Vac/dc (non-isolated half-wave rectified)
Consumption 80 mA max @ 24 Vdc, 36 mA avg @24 Vdc
Input Voltage Effect Negligible over specified operating range
Protection Circuitry Reverse voltage protected and output limited
Optional Relay Output One Form C contact (N.O. and N.C.), status LED, 5 amps @ 250 Vac, 5 amps @ 30Vdc, p.f. = 1 Relay Trip Point – Programmable 500-1500 ppm in 50 ppm increments Relay Hysteresis – Programmable 25-200 ppm in 25 ppm increments
Programming and Selection Via internal push-buttons and jumper
Wiring Connections Screw terminal block (14 to 22 AWG)
MODEL Description
CDD Carbon Dioxide Detector (CO2)
CODE
1 Non-Dispersive Infrared (NDIR)
CODE Gas Type Range
A
CO2 – Carbon Dioxide Detector (CDD)
0-2000 PPM Standard User programmable up to 10,000 PPM
CODE Enclosure and Outputs
1 2 6
Corporate Space c/w 4-20 mA and 0-5 Vdc outputs Corporate Space c/w 4-20 mA and 0-10 Vdc outputs Duct ABS c/w Sampling Tube, 4-20 mA, 0-5 Vdc and 0-10 Vdc outputs
CODE Circuit Board Relay
00 10
No Relay One Relay (DPDT, N.O. or N.C., 5A @ 24 VDC)
CODE Options
0 1 2
No options LCD RS-485 Communication (Please contact Greystone)
CDD 1 A 1 00 0 Typical Model Number
Example: NDIR CO2 Corporate No Relay No Options
Greystone Energy Systems, Inc. reserves the right to make design modifications without prior notice.
Sensing Element
CARBON DIOXIDE (CO2): PRODUCT ORDERING INFORMATION
Greystone Energy Systems Inc., established in 1983, is Canada’s largest manufacturer of HVAC sensors and
transducers for Building Automation Management Systems. We have conscientiously established a worldwide
reputation as an industry leader by maintaining leading- edge design technology, prompt technical support, and
a commitment to on-time deliveries. We take pride in our Quality Management System which is ISO 9002 certified,
assuring our customers of consistent product reliability.
Q M I
ISO 9002
GREYSTONE IS AN ISO 9002 REGISTERED COMPANY
Greystone Energy Systems Inc. 150 English Drive, Moncton, NB Canada E1E 4G7 (506) 853-3057 Fax: (506) 853-6014 e-mail: [email protected] www.greystoneenergy.com
DIMENSIONS nts
ACLP SOFTWARE AND 5 YEAR CALIBRATION GUARANTEE ACLP SOFTWARE ACLP (Automatic Calibration Logic Program) software utilizes the computing power in the sensor’s on-board micro-processor to remember the lowest CO2 concentration that takes place every 24 hours. The sensor assumes this low point is at outside levels. The sensor is also smart enough to discount periodic elevated readings that might occur if for example a space was used 24 hours per day over a few days. Once the sensor has collected 14 days worth of low concentration points it performs a statistical analysis to see if there has been any small changes in the sensor reading over background levels that could be attributable to sensor drift. If the analysis concludes there is drift, a small correc-tion factor is made to the sensor calibration to adjust for this change. 5 YEAR CALIBRATION GUARANTEE Based on the results of years of testing of ACLP software, Greystone now offers a 5 year calibration guarantee on all its CDD series wall and duct mount sensors used for CO2 based ventilation control when operated in an environment that can utilize ACLP software. If the sensor is found to be out of calibration more than 150 ppm as compared to a calibration gas or recently calibrated reference, Greystone will provide a free factory calibration of the sensor if re-turned to Greystone. This guarantee only applies if the sensor is operated in an environment where inside levels peri-odically drop to outside concentrations (i.e. during evenings or weekends when there is no occupancy) as is required by ACLP software. If a space does not experience a periodic drop to outside levels (e.g. where occupancy is 24 hours, 7 days/week), ACLP software should be deactivated off. With ACLP deactivated (via menu buttons) calibration may be required every 2 to 3 years.
42.9 mm (1.69”)
124.5 mm (4.90”)
183.4 mm (7.22”)
92.7 mm (3.65”)
127 mm (5.00”)
43.8 mm (1.69”)
Malaspina University-College School of Management Centre 900 Fifth Street, Nanaimo BC
DDC Controls Shop Drawing Submittal
Submitted To:
Windley Contracting Ltd. 3711 Shenton Road Nanaimo, British Columbia V9T 2H1
Submitted By: Joe LeRoy, P.Eng 19-831 Devonshire Rd. Victoria, BC V9A 4T5 250 388-5665
Submittal Details:
Date Submitted: 3/30/2006 Date Resubmitted: Specification Section: 15900.2.9 Description: CO2 detector Wall Mounted Model: Ventostat 8001-L
Supplier info:
Name: Tinsmith Mechanical Address:
Manufacturer info: Name: Telaire Address: 6860 Cortona Drive - Suite B, Golete, CA 93117 Website www.telaire.com
houle controls (a div. of houle electric ltd.)
!" #$$%&'(((
!")*+,(-(,(%,#-...'
!'
"!#$
"#
%&'(%) *
$$*$
!"
$+" *
, - .
./012*3-
"#-"
!
!!!!
"!$
!"#"$%& '$( ")(*+ %,- %. & /!" # $%/ & #'0*)12.31#$4( ' 53"0 (200-#0 607
80 ,915#:4 );':04<#6)(=%&;5:0 "#:>&% "#:8% & ':0*+ .5*49>?#+ . &@+@0 *%%.> A5:0 *%,- %8. # !;;BC % % %* +,&4' %-0 %,-8" !; -#
; ; ; ;
DE 0+ % & %& D D % & % &
& D %&%0+ 8% D 0+ &0+ D DE 09F %
Light Source
COP87L88GGV-X
E
Gas PermeableMembrane
CO2 MicroprocessorCorrects Drift
Using ABC Logic™
Single ChannelDetector
Signal toMicroprocessor
Sends CO Signalto Equipment
2
!"
#$D: ;; > <: :
%!&DE -
& % 8
-09F * 09 .
D>
C
&% %8 G
<%8& H8 % 0% ,7>
C % & %
98 % &
*:I.
+* .%
01J K
% %= & 6 &
-0 %
+ ; % H8 =*; .
+ &%&
+ * .#
D;6;*80 . -0%,915#: &
.%/ 012<
.%% ! 7 (
7&
.%%. & 7 D
L2*1L0.
$2$ "+20 =
0
$2% - 32-M
0 "&!
024"#
C
'&%!
(
)*D0+ & ;; & D
*;#1)5)11. D &%& & % D & & & D & 09F*80. % ! D &!"#"$*%& . & > &4N5#8 D; 2 & %% D > : <: +,-+,.
: ; -0 ,-" B% 4N5#8 &
> %8& 8
2 7/8"
2 3/8"
5 1/16"
4 1/4"
3 1/4"
2 3/8"
3 1/4"
5 5/8"
1 1/8"
/0"&01(&#((((**1
0"1(&#((((**1
0"&01(&#((((**1
% 7 ",-0O = = 8 8 ,915#:4
&%8& &
4 /. 4 /.0 4 /$ 4 /$0
/0"1(&#((((**1
%)"; 0+ &H =# % & = % ,--
/#0"!D 8 : ;; %# D; & 8D 2 &%&
DE ;;0+
0 56*80. 0 & %0+& & * & . 0 56 %
8 5 && 056%%8 % % 0+ % %
1200
1100
1000
900
800
700
600600 200 400 600
Days
800 1000 1200
CO
PP
MR
ead
ing
Usin
g980
PP
MC
alib
rati
on
Gas
2
!"
#$D: ;; > <: :
%!&DE -
& % 8
-09F * 09 .
D>
C
&% %8 G
<%8& H8 % 0% ,7>
C % & %
98 % &
*:I.
+* .%
01J K
% %= & 6 &
-0 %
+ ; % H8 =*; .
+ &%&
+ * .#
D;6;*80 . -0%,915#: &
.%/ 012<
.%% ! 7 (
7&
.%%. & 7 D
L2*1L0.
$2$ "+20 =
0
$2% - 32-M
0 "&!
024"#
C
'&%!
(
)*D0+ & ;; & D
*;#1)5)11. D &%& & % D & & & D & 09F*80. % ! D &!"#"$*%& . & > &4N5#8 D; 2 & %% D > : <: +,-+,.
: ; -0 ,-" B% 4N5#8 &
> %8& 8
2 7/8"
2 3/8"
5 1/16"
4 1/4"
3 1/4"
2 3/8"
3 1/4"
5 5/8"
1 1/8"
/0"&01(&#((((**1
0"1(&#((((**1
0"&01(&#((((**1
% 7 ",-0O = = 8 8 ,915#:4
&%8& &
4 /. 4 /.0 4 /$ 4 /$0
/0"1(&#((((**1
%)"; 0+ &H =# % & = % ,--
/#0"!D 8 : ;; %# D; & 8D 2 &%&
DE ;;0+
0 56*80. 0 & %0+& & * & . 0 56 %
8 5 && 056%%8 % % 0+ % %
1200
1100
1000
900
800
700
600600 200 400 600
Days
800 1000 1200
CO
PP
MR
ead
ing
Usin
g980
PP
MC
alib
rati
on
Gas
2
!" #$$%&'(((
!")*+,(-(,(%,#-...'
!'
"!#$
"#
%&'(%) *
$$*$
!"
$+" *
, - .
./012*3-
"#-"
!
!!!!
"!$
!"#"$%& '$( ")(*+ %,- %. & /!" # $%/ & #'0*)12.31#$4( ' 53"0 (200-#0 60780 ,915#:4
);':04<#6)(=%&;5:0 "#:>&% "#:8% & ':0*+ .5*49>?#+ . &@+@0 *%%.> A5:0 *%,- %8. # !;;BC % % %* +,&4' %-0 %,-8" !; -#
; ; ; ;
DE 0+ % & %& D D % & % &
& D %&%0+ 8% D 0+ &0+ D DE 09F %
Light Source
COP87L88GGV-X
E
Gas PermeableMembrane
CO2 MicroprocessorCorrects Drift
Using ABC Logic™
Single ChannelDetector
Signal toMicroprocessor
Sends CO Signalto Equipment
2
Malaspina University-College School of Management Centre 900 Fifth Street, Nanaimo BC
DDC Controls Shop Drawing Submittal
Submitted To:
Windley Contracting Ltd. 3711 Shenton Road Nanaimo, British Columbia V9T 2H1
Submitted By: Joe LeRoy, P.Eng 19-831 Devonshire Rd. Victoria, BC V9A 4T5 250 388-5665
Submittal Details:
Date Submitted: 3/30/2006 Date Resubmitted: Specification Section: 15900.1.1.4 Description: Web Access Software Model: RC Webview
Supplier info:
Name: Reliable Controls Corporation Address: 207-3375 Whittier Avenue, Victoria, BC V8Z 3R6
Manufacturer info: Name: Reliable Controls Corporation Address: 207-3375 Whittier Avenue, Victoria, BC V8Z 3R6 Website www.reliable-controls.com
houle controls (a div. of houle electric ltd.)
The Reliable Controls®
environments
control building
access, monitor, and
economical solution to
simple, flexible, and
operators yet another
software gives building
RC-WebView™ Web
based system access
Reliable Controls® MACH-System server based Web access
Distributed system access and manipulation through IE 5.5 or higher
Real-time, dynamic display of System Group screens
Configuration utility for ease-of-setup
Unlimited number of simultaneous user connections
Password protection for system integrity
The Reliable Controls® RC-WebView™ Web server software is part of the software suite for the Reliable Controls® MACH-System.
© 2003 Reliable Controls CorporationReliable Controls® Corporation, 207-3375 Whittier Ave., Victoria BC, V8Z 3R1
Toll Free: 1 (877) 475-9301 Tel: (250) 475-2036 Fax: (250) 475-2096
RCW-09/03 © 2003 Reliable Controls® Corporation Designed and Manufactured in Canada
F E A T U R E SEasy Setup• Configuration utility provides
easy setup • Password security protection• Tree view feature provides
intuitive navigation• Mulltiple systems supported
Easy Operator Use• Dynamic system data displayed
in intuitive graphical screens• Right click access to edit and
manually override points• Single click access to view and
adjust weekly schedules, annual schedules, trend and runtime logs, and current system alarms
• Custom functionality achieved through the inclusion of system keywords
Dynamic Data• Data synchronization between
RC-WebView™ and the systems connected to RC-Studio®
• Automatic translation of graphics. No need to perform custom exports
Easy Connectivity• Use any copy of Microsoft
Internet Explorer 5.5 or higher to display Web sites created in RC-WebView™
• Unlimited number of users can access site simultaneously
O R D E R I N GRC-WEB-SRV• RC-WebView™ Server
configured with single system license of RC-WebView™ Software
RC-WEB-A• RC-WebView™ Software -
additional system license
PC Requirements• Intel Pentium IV 1.8 Ghz
Processor• Gigabyte GA-8INXP Server
Motherboard• 2 x Maxtor 40.0 GB, 7,200 RPM
ATA/133 Hard Drive• 1.44 MB Floppy Drive, LG 52x
CDROM Drive
• 2 x 256 MB DDR RAM• Nvidia GeForce Video Card• Windows 2000 Server License,
IIS Service• 19” 4U Rackmount Chassis,
300W Power Supply• Keyboard• Logitech Wheel Mouse
RC-WebView™ SoftwareRc-WebView™ enhances the Reliable Controls® suite of building automation software by providing a Web-based access solution that uses Microsoft Internet Explorer 5.5 in place of client side software. RC-WebView™ resides on a dedicated server connected anywhere in the World Wide Web. The software configuration is easy and the number of users connected to RC-WebView™ is only limited by the capability of the server hosting the application.
RC-WebView™ is designed to user the same file structure as RC-Studio®, enabling the two applications to present system group data in the same manner. A common file structure allows the two applications to dynamically synchronize data so that the display is the same in either application.RC-WebView™ allows the operator to user a browser to view and manually override points, adjust weekly schedules and annual schedules, view graph and print trend and runtime logs, and view and print current alarms.
Configuration Utility
System In Browser
Trend Log in Browser
AdministrationWeb Site
RC-WebView™
Web Site # 01
RC-WebView™ SERVER
RC-WebView™
Web Site # xx
INTERNET Ethernet Hub
Router/Firewall
Operator Workstation Off-Site
School
Hospital
Office Tower
Operator Workstation
Router/Firewall
Current Alarms
WAN Network Architecture
Malaspina University-College School of Management Centre 900 Fifth Street, Nanaimo BC
DDC Controls Shop Drawing Submittal
Submitted To:
Windley Contracting Ltd. 3711 Shenton Road Nanaimo, British Columbia V9T 2H1
Submitted By: Joe LeRoy, P.Eng 19-831 Devonshire Rd. Victoria, BC V9A 4T5 250 388-5665
Submittal Details:
Date Submitted: 3/30/2006 Date Resubmitted: Specification Section: 15900.2.13 Description: Building Controller Model: Mach Global (MG)
Supplier info:
Name: Reliable Controls Corporation Address: 207-3375 Whittier Avenue, Victoria, BC V8Z 3R10
Manufacturer info: Name: Reliable Controls Corporation Address: 207-3375 Whittier Avenue, Victoria, BC V8Z 3R10 Website www.reliable-controls.com
houle controls (a div. of houle electric ltd.)
The Reliable Controls®
environments
control building
access, monitor, and
economical solution to
simple, flexible, and
operators yet another
controller gives
MACH-Global™ building
Ultimate, intelligent, networkable complete building controller
Completely programmable DDC controller
Modular Input, Output cards provide up to 128 points of measurement
Trend logs with historical tracking
Ideal for high-point applications requiring unrestricted programming
Support provided for two subnetworks
Multiple, simultaneous communication channels
The Reliable Controls® MACH-Global™ building controller is a super solution to any new or replacement equipment application, and ships with the Reliable Controls®industry best 5 year warranty.
© 2003 Reliable Controls CorporationReliable Controls® Corporation, 207-3375 Whittier Ave., Victoria BC, V8Z 3R1
Toll Free: 1 (877) 475-9301 Tel: (250) 475-2036 Fax: (250) 475-2096
Dimensions:31.4 cm L x 19.9 cm W x 3.8 cm H
(12.4” L x 7.9” W x 1.25” H)
MG-11/04-RAR © 2003 Reliable Controls® Corporation Designed and Manufactured in Canada
The Reliable Controls® MACH-Global™ building controller is a
powerful, central-point DDC controller designed to support
multiple BACnet® LAN communication technologies
simultaneously through nine ports; 1-IEEE802.3 (Ethernet), 3-
EIA-232 (PC/Modem), 2-EIA-485 (token passing), 2-EIA-422/
485 and 1-MSP (SMART-Net™). This flexible and powerful
controller also supports up to 128 universal input/output hard
points directly onboard using a combination of eight modular
16-point expansion cards. The MACH-Global™ controller is a
dual-protocol device, supporting BACnet® and Reliable
Controls® protocols. A fully configured Reliable-Controls®
MACH-System supports over 2,000,000 points of
measurement.
F E A T U R E SProtocol• BACnet®
- PTP (EIA-232)- MS/TP (EIA-485)- B/IP (Ethernet)- ISO 8802-3
• Reliable Controls®- Ethernet (IP)- PC & Modem (EIA-232)- Network (EIA-485/Token Bus)
128 Control-BASIC™ Programs• User programmable control
strategy in a readable, BASIC-like language
• 2500 bytes per program
128 Inputs/Outputs• Universal ranges
256 Variables• Selectable standard and custom
ranges, as well as fixed or program-driven values
64 PID Loops• Standard P, PI, or PID controllers
for closed loop control
96 Trend Logs• Each trend log stores 512
samples of 6 points at programmable time intervals
128 Runtime Logs• Totals the on time and records
the on/off times of a digital point
64 System Groups• Allows related points to be
grouped on one display• 160 points per group
32 Weekly Schedules• 4 on/off times for each weekday
and 2 override days
8 Annual Schedules• Days of the year designated as
holidays
48 Variable Arrays• Up to 128 elements in a
one-dimensional array
128 User Passwords• Protects access to system• Each user is assigned a user
name and an access level
20 Custom Tables• For creating custom input
ranges
16 Custom Units• 8 analogue engineering units• 8 digital engineering units
SMART-Net™ Port• Networks up to 16
SMART-Sensors™
127 Network In Points
127 Network Out Points
Warranty• 5 years
O R D E R I N GMG• MACH-Global™ controller
Processor• 16-bit embedded microcontroller
Memory• 2 MB of NV RAM
user database• 1 MB Flash EEPROM for
operating system firmware
Supply Voltages• 24 VAC Class 2, 75 VA • 3.15 A slow blow fuse
Communications• 1-IEEE 802.3 Ethernet 10BaseT• 3-EIA-232 @ 115 kbps• 2-EIA-422/485 @ 115 kbps• 2-EIA-485 @ 115 kbps• 1 -SMART-Net™
(16 SMART-Sensors™ max)
Inputs/Outputs• 8 ports, each addressing 16
Input points or Output points
Converters• 12 bit A-D for inputs
• 12 bit D-A for outputs
Real-Time Clock• +/-1 second per day
Memory/RTC Backup• 48 hours by zero maintenance
capacitor
Dimensions• 31.4 cm L x 19.9 cm W x
3.8 cm H (12.4” L x 7.9” W x 1.25” H)
Mounting• #6 clearance holes on
30.0 cm L x 18.5 cm W(11.8” L x 7.25” W) centers
Weight• 1.0 kg (2.5 lb.)
Ambient Limits• Operating: 0 °C to 40 °C
(32 °F to 104 °F)• Shipping: -40 °C to 60 °C
(-40 °F to 140 °F)• Humidity: 10% to 90%
RH non-condensing
MACH-Global™ Control ler
MACH1™ MACH2™ MACH-Air™
MACH-Zone™
Modem
MACH-Global™
Operator WorkStation
MACH-Air™
MACH-Global™ InputExpansion Cards
MACH-Global™ OutputExpansion Cards
Main network toother controllers
Ethernet
MACH2™
Sub network ASub network B
SMART-Sensor™ Printer
24 VAC/VDCPower switch
Malaspina University-College School of Management Centre 900 Fifth Street, Nanaimo BC
DDC Controls Shop Drawing Submittal
Submitted To:
Windley Contracting Ltd. 3711 Shenton Road Nanaimo, British Columbia V9T 2H1
Submitted By: Joe LeRoy, P.Eng 19-831 Devonshire Rd. Victoria, BC V9A 4T5 250 388-5665
Submittal Details:
Date Submitted: 3/30/2006 Date Resubmitted: Specification Section: 15900.2.13 Description: Input Card for Building Controller Model: Mach Global Input Card (MGX-I)
Supplier info:
Name: Reliable Controls Corporation Address: 207-3375 Whittier Avenue, Victoria, BC V8Z 3R11
Manufacturer info: Name: Reliable Controls Corporation Address: 207-3375 Whittier Avenue, Victoria, BC V8Z 3R11 Website www.reliable-controls.com
houle controls (a div. of houle electric ltd.)
The Reliable Controls®
environments
control building
access, monitor, and
economical solution to
simple, flexible, and
operators yet another
expansion cards give
MACH-Global™ Input
Ultimate modularity for MACH-Global™ building controller
Universal inputs, 16 per card
Expansion cards provide up to 128 Inputs
Pulse counting @ 40 HZ provides support for flow meters
Status LEDs glow proportionally
Powered by MACH-Global™ building controller
The Reliable Controls® MACH-Global™ Input expansion cards offer a super solution to any new or expanding equipment application, and ship with the Reliable Controls®industry best 5 year warranty.
Dimensions:22.3 cm L x 11.4 cm W x 4.5 cm H
(8.75” L x 4.5” W x 1.75” H)
© 2003 Reliable Controls CorporationReliable Controls® Corporation, 207-3375 Whittier Ave., Victoria BC, V8Z 3R1
Toll Free: 1 (877) 475-9301 Tel: (250) 475-2036 Fax: (250) 475-2096
MGI-11/04-RAR © 2003 Reliable Controls® Corporation Designed and Manufactured in Canada
The Reliable Controls® MACH-Global™ input card is a
general purpose universal input expansion card that is
designed for use with the MACH-Global™ controller. The
expansion card accepts analogue, digital or pulsed
signals at each of its 16 inputs. Each input has two dip
switch poles for configuring the input to be a 0-5 Volt, 4-
20 mA, or themistor/dry contact. A maximum of eight
input cards can be connected to one MACH-Global™
controller. Each input has an LED that glows
proportionally to the input value.
F E A T U R E S16 Universal Inputs• 0-5 VDC pulse, thermistor/dry
contact, or 4-20 mA • Software configured as analogue
or digital
Folded Metal Enclosure• Strong powder coated steel
metal enclosure protects circuitry and adds to the ease of installation
Removable Connectors• Two 16-pole removable
connectors for easy change out
Warranty• 5 years
O R D E R I N GMGX-I• MACH-Global™ input expansion
card
MGX-RC-B• MACH-Global™ expansion card
ribbon cable - base
MGX-RC-C• MACH-Global™ expansion card
ribbon cable - cable per 30 cm/1 ft. up to a max. of 120 cm/4 ft.
MACH-Global™ Input Expansion Card
Supply Voltage• Supplied by MACH-Global™
controller
Inputs• 16 universal inputs• 12 bit A-D converter• Analogue: 0-5 VDC, 4-20 mA,
thermistor• Digital: dry contact• Impedance:
15k Ω on 0-5 VDC range,250 Ω on 4-20 mA range,10k Ω on thermistor range
• 40 Hz pulse counting(supports flow meters)
• 24 VAC over voltage protection
Connectors• Two 16-pole removable
connectors for inputs• One 20-pole ribbon cable
header
Status LEDs• One LED per input,
intensity proportional to input value
Dimensions• 22.3 cm L x 11.4 cm W x
4.5 cm H (8.75” L x 4.5” W x 1.75” H)
Mounting• #6 clearance holes on
20.5 cm L x 10.0 cm W(8.12” L x 4” W)
Weight• 0.7 kg (1.2 lb.)
Ambient Limits• Operating: 0 °C to 40 °C
(32 °F to 104 °F)• Shipping: -20 °C to 60 °C
(-40 °F to 140 °F)• Humidity: 10% to 90%
RH non-condensingMACH-Global™ Input Expansion Cards
Expansion Ports
MACH-Global™ Controller
Ribbon Cable to Expansion Cards
Malaspina University-College School of Management Centre 900 Fifth Street, Nanaimo BC
DDC Controls Shop Drawing Submittal
Submitted To:
Windley Contracting Ltd. 3711 Shenton Road Nanaimo, British Columbia V9T 2H1
Submitted By: Joe LeRoy, P.Eng 19-831 Devonshire Rd. Victoria, BC V9A 4T5 250 388-5665
Submittal Details:
Date Submitted: 3/30/2006 Date Resubmitted: Specification Section: 15900.2.13 Description: Output Card for Building Controller Model: Mach Global Output Card (MGX-O)
Supplier info:
Name: Reliable Controls Corporation Address: 207-3375 Whittier Avenue, Victoria, BC V8Z 3R12
Manufacturer info: Name: Reliable Controls Corporation Address: 207-3375 Whittier Avenue, Victoria, BC V8Z 3R12 Website www.reliable-controls.com
houle controls (a div. of houle electric ltd.)
The Reliable Controls®
environments
control building
access, monitor, and
economical solution to
simple, flexible, and
operators yet another
expansion cards give
MACH-Global™ Output
Ultimate modularity for MACH-Global™ building controller
Universal outputs, 16 per card, HOA switches standard
Expansion cards provide up to 128 outputs
Output signal configured in RC-Studio® software
Status LEDs glow proportionally
Separate power supply for maximum efficiency
The Reliable Controls® MACH-Global™ Output expansion cards offer a super solution to any new or expanding equipment application, and ship with the Reliable Controls®industry best 5 year warranty.
Dimensions:22.3 cm L x 11.4 cm W x 4.5 cm H
(8.75” L x 4.5” W x 1.75” H)
© 2003 Reliable Controls CorporationReliable Controls® Corporation, 207-3375 Whittier Ave., Victoria BC, V8Z 3R1
Toll Free: 1 (877) 475-9301 Tel: (250) 475-2036 Fax: (250) 475-2096
MGO-11/04-RAR © 2003 Reliable Controls® Corporation Designed and Manufactured in Canada
MACH-Global™ Output Expansion Card
The Reliable Controls® MACH-Global™ output card is a
general purpose universal output expansion card that is
designed for use with the MACH-Global™ controller. Each
of the expansion cards 16 outputs can be independently
configured to deliver an analogue or digital signal. Every
output comes standard with a Hand/Off/Auto switch for
convenient override in the field, and position feedback to
RC-Studio® software. A maximum of eight output cards
can be connected to one
MACH-Global™ controller. Each MACH-Global™ output
card requires its own 24 VAC power source.
F E A T U R E S16 Universal Outputs• 0-12 VDC, analogue• 0-12 VDC, digital • Software configured as analogue
or digital
HOA Switches• Standard for each output• Convenient override in the field• Switch position feedback to
RC-Studio® software
Proportional LEDs• LED brilliance is proportional to
output signal
Metal Enclosure• Strong powder coated steel
metal enclosure protects circuitry and adds to the ease of installation
Removable Connectors• Two 16-pole and one 2-pole
removable connectors for easy change out
Warranty• 5 years
O R D E R I N GMGX-O• MACH-Global™ output expansion
card
MGX-RC-B• MACH-Global™ expansion card
ribbon cable - base
MGX-RC-C• MACH-Global™ expansion card
ribbon cable - cable per 30 cm/1 ft. up to a max. of 120 cm/4 ft.
Supply Voltage• 24 VAC 50 VA Class 2
Outputs• 16 universal outputs• 12 bit D-A converter• Analogue: 0-12 VDC• Digital: 0-12 VDC• Manual ON provides 15 VDC • LED indicator• Output power: 75 mA @ 12 VDC• 24 VAC over voltage and short
protection
Switches• HOA toggle switch• Switch position feedback to
RC-Studio® software
Connectors• Two 16-pole removable
connectors for output• One 20-pole ribbon cable
header• One 2-pole power connector
Status LEDs• One LED per output,
intensity proportional to output value
Dimensions• 22.3 cm L x 11.4 cm W x
4.5 cm H (8.75” L x 4.5” W x 1.75” H)
Mounting• #6 clearance holes on
20.5 cm L x 10.0 cm W(8.12” L x 4” W)
Weight• 0.7 kg (1.2 lb.)
Ambient Limits• Operating: 0 °C to 40 °C
(32 °F to 104 °F)• Shipping: -20 °C to 60 °C
(-40 °F to 140 °F)• Humidity: 10% to 90%
RH non-condensing
Fuse• 3.15 A slow blow• 5 A ground protection fuse
MACH-Global™ Output Expansion Cards
Expansion Ports
MACH-Global™ Controller
Ribbon Cable to Expansion Cards
Malaspina University-College School of Management Centre 900 Fifth Street, Nanaimo BC
DDC Controls Shop Drawing Submittal
Submitted To:
Windley Contracting Ltd. 3711 Shenton Road Nanaimo, British Columbia V9T 2H1
Submitted By: Joe LeRoy, P.Eng 19-831 Devonshire Rd. Victoria, BC V9A 4T5 250 388-5665
Submittal Details:
Date Submitted: 3/30/2006 Date Resubmitted: Specification Section: 15900.2.14 Description: VAV Controller Model: Mach Air (MAH-T)
Supplier info:
Name: Reliable Controls Corporation Address: 207-3375 Whittier Avenue, Victoria, BC V8Z 3R13
Manufacturer info: Name: Reliable Controls Corporation Address: 207-3375 Whittier Avenue, Victoria, BC V8Z 3R13 Website www.reliable-controls.com
houle controls (a div. of houle electric ltd.)
Ultimate, intelligent, networkable VAV box controller
Completely programmable DDC controller
Relocatable Belimo damper actuator
Mounted directly to your VAV equipment
Trend logs with historical tracking
Accessible environmental building controls
Onboard velocity sensors for flow measurement
BACnet® MS/TP communications (BTL Listed)
The Reliable Controls®
environments
control building
access, monitor, and
economical solution to
simple, flexible, and
operators yet another
controller gives
MACH-Air™ VAV
The Reliable Controls® MACH-Air™ VAV controller is a super solution to any new or replacement air handling application, and ships with the Reliable Controls® industry best 5 year warranty.
© 2003 Reliable Controls Corporation
Dimensions:22.9 cm L x 13.4 cm W x 6.3 cm H
(9.0” L x 4.8” W x 2.5” H)
Reliable Controls® Corporation, 207-3375 Whittier Ave., Victoria BC, V8Z 3R1
Toll Free: 1 (877) 475-9301 Tel: (250) 475-2036 Fax: (250) 475-2096
MA-11/04-RAR © 2003 Reliable Controls® Corporation Designed and Manufactured in Canada
The Reliable Controls® MACH-Air™ controller is a
programmable, 6 input, 5 output, DDC controller and
shaft-mount damper actuator, combined together into
one device to meet the needs of variable air volume
(VAV) control. The MACH-Air™ controller features
onboard velocity measurement, a 35 in-lb Belimo
actuator, three user specified universal inputs/outputs,
and optional triac outputs. Removable connectors are
standard on the MACH-Air™ controller.
Processor• 25 MHz, high-performance
16-bit embedded microcontroller
Memory• 32k RAM• 128k Flash EEPROM operating
system firmware and controller configurations
Supply Voltages• 24 VAC/VDC, 25 VA max.
Communications• EIA-485 @ 76.8 kbps max.• SMART-Net™
(4 SMART-Sensors™ max.)
SETUP-Tool™• SETUP-Tool™ used for
configuration
Inputs• 3 universal inputs• 10 bit A-D converter• Analogue: 0-5 VDC, 4-20 mA,
thermistor• Digital: dry contact• Impedance: 15k Ω on 0-5 VDC
range• 40 Hz pulse counting
(supports flow meters)• 24 VAC over voltage protection
Outputs• 3 universal outputs• 8 bit D-A converter• Analogue: 0-12 VDC
• Digital: 0-12 VDC• Output power: 75 mA @ 12 VDC• 24 VAC over voltage and short
protection
Single Stage Triac Outputs• 24 VAC @ 1 A
Dual Stage Triac Outputs• 24 VAC @ 1 A• Common return
Velocity Sensors• Flow-through thermistor• 0-1” W.C.
Actuator• Torque: 35 in-lb.
Enclosure• NEMA type 1• UL94-5V
Dimensions• 22.9 cm L x 13.4 cm W x 6.3 cm
H (9” L x 4.8” W x 2.5” H)
Weight• 0.7 kg (1.8 lb.)
Ambient Limits• Operating: 0 °C to 40 °C
(32 °F to 104 °F)• Shipping: -20 °C to 60 °C)
(-40 °F to 140 °F)• Humidity: 10% to 90%
RH non-condensing
F E A T U R E SProtocols• BACnet®
- MS/TP (EIA-485)• Reliable
- Network (EIA-485/Token Bus)
8 Control-BASIC™ Programs• User programmable control
strategy in a readable, BASIC-like language
• 2000 bytes per program
6 Inputs• 3 Inputs with universal ranges • Jumper selectable 0-5 VDC,
4-20 mA, thermistor/dry contact• Input #4 dedicated to the flow
sensor• Input #5 dedicated to the damper
position feedkback• Input #6 dedicated to indicate
damper at end of position
5 Outputs• 3 Outputs with universal ranges• Scalable 0-12 VDC• Output #4 dedicated to damper
motor• Output #5 dedicated to control
direction of rotation to close• Single stage triac (T model only)• Dual stage triac (T model only)
48 Variables• Selectable standard and custom
ranges, as well as fixed or program-driven values
• Variable #1 dedicated to flow calibration
4 Controllers• Standard P, PI, or PID controllers
for closed loop control
2 Trend Logs• Each trend log stores 150 samples
of 6 points at programmable time intervals
4 Runtime Logs• Totals the on time and records the
on/off times of a digital point
2 System Groups• Allows related points to be grouped
on to one display
• 50 points/group
1 Weekly Schedule• 4 on/off times for each weekday
and 2 override days
1 Annual schedule• Days of the year designated as
holidays
5 Custom Tables• For creating custom input ranges
and Control-BASIC™ lookup tables
SMART-Net™ Port• Networks up to 4 SMART-Sensors™ • SMART-Sensor™ #5 is dedicated
to SETUP-Tool™
32 Network In Points
32 Network Out Points
Warranty• 5 years
Certi f icat ion• UL listed 916
OPEN ENERGY MANAGEMENT EQUIPMENT
O R D E R I N GMA• MACH-Air™ controller with 3
universal inputs and 3 universal outputs
MA-T• MACH-Air™ controller with 3
universal inputs and 1 universal output, 1 single stage triac output, 1 dual stage triac output.
MA-P• MACH-Air™ controller with
potentiometer position feedback
MA-TP• MACH-Air-T™ controller with
potentiometer position feedback
MA-WA• MACH-Air™ without actuator
MA-WF• MACH-Air™ without flow sensor
MA-C• MACH-Air™ connector cover
MAZ-ST• SETUP-Tool (required for
configuration)
MACH-Air™ VAV Control ler
24VAC
GND
A-
B+
AOUT+
AOUT-TRIAC1RTN-T1DS1-T1DS1-T2RTN-DS1IN 1+
GND
IN 2+
IN 3+
GND
24VAC
GND
A-
B+
OUT 1+
OUT 1-OUT 2+
OUT 2-OUT 3+
OUT 3-IN 1+
IN 1-
IN 2+
IN 2-
IN 3+
IN 3-
MACH-Air™-TConnector Wiring
MACH-Air™
Connector Wiring
24 VAC 60Hz PowerEIA-485 NetworkOutput-1Output-2Output-3Input-1Input-2Input-3
SMART-Sensor™
BACnet is a registered trademark of ASHRAE. ASHRAE does not endorse, approve or test productsfor compliance with ASHRAE standards. Compliance of listed products to requirements of ASHRAE
Standard 135 is the responsibility of the BACnet Manufactures Association (BMA). BTL is a registeredtrademark of the BMA
Malaspina University-College School of Management Centre 900 Fifth Street, Nanaimo BC
DDC Controls Shop Drawing Submittal
Submitted To:
Windley Contracting Ltd. 3711 Shenton Road Nanaimo, British Columbia V9T 2H1
Submitted By: Joe LeRoy, P.Eng 19-831 Devonshire Rd. Victoria, BC V9A 4T5 250 388-5665
Submittal Details:
Date Submitted: 3/30/2006 Date Resubmitted: Specification Section: Description: Line Filter/Surge Suppressor Model: PLF-2
Supplier info:
Name: Reliable Controls Corporation Address: 207-3375 Whittier Avenue, Victoria, BC V8Z 3R3
Manufacturer info: Name: Corcom Address: 844 E. Rockland Road Libertyville, IL 60048-3375 Website www.cor.com
houle controls (a div. of houle electric ltd.)
CORCOM Product Guide
RFI Power Line Filters for Switching Power Supply Noise Suppression
The EP/VP series of RFI filters has been developed toreduce conducted noise to acceptable limits forequipment that must comply with the requirementsof CISPR in Europe and the FCC specifications in the USA.
These filters provide high insertion loss for both line-to-ground and line-to-line emissions throughout thefrequency range. They are particularly well suitedfor equipment to better meet both stringent emissionsspecifications (such as CISPR 22, A-level and FCCPart 15J, Class B) and the EP models meet very lowleakage current requirements.
SpecificationsMaximum leakage current,each line-to-ground
VP Models EP Models@ 120 VAC 60 Hz: .73mA .21mA@ 250 VAC 50 Hz: 1.27mA .36mA
Hipot rating (one minute):line-to-ground 2250 VDCline-to-line 1450 VDC
Operating frequency: 50/60 Hz
Rated voltage (max.): 250 VAC
Rated current:03EP 03A06EP 06A10EP 10A20EP/VP 20A
Minimum insertion loss in dB:Line-to-ground in 50 ohm circuit
Current Frequency–MHzRating .01 .04 .05 .15 .5 1 5 10 30
EP3A 1 1 10 58 65 65 66 60 256A,10A 1 1 10 58 65 65 66 60 2520A 3 6 6 28 50 55 60 55 55
VP20A 3 2 2 42 60 65 65 55 55
Line-to-line in 50 ohm circuitCurrent Frequency–MHzRating .01 .09 .15 .5 1 5 10 20 30
EP1, EP3 3A 1 5 36 65 65 65 65 58 586A,10A 1 5 30 65 65 65 65 35 3520A 8 17 25 60 65 65 58 58 58
VP 20A 8 17 25 60 65 65 58 58 58
50Catalog 1654001 Dimensions are in inches and Dimensions are shown for USA Cust. Svc.: 1-800-468-2023 www.cor.comRevised 03-04 millimeters unless otherwise reference purposes only. CORCOM Prods: 1-847-680-7400 www.tycoelectronics.com
specified. Values in italics Specifications subject 1-508-992-4495are metric equivalents. to change. Germany: 49-89-6089-0
EP/VP Series
EP/VP Series
Electrical Schematic
Resistor location for reference only.
LINE LOAD
Line CordLine Cord No. GA400:71/2 foot, 3-conductor line cord.
EP1/VP1
EP7/VP7
EP3/VP3
UL RecognizedCSA CertifiedVDE Approved
EP3/VP3
CORCOM Product Guide
RFI Power Line Filters for Switching Power Supply Noise Suppression (Continued)
Case Styles
Case DimensionsA B C D E
± .015Part No. (max) (max) (max) (max)± .38
3EP1 3.85 2.07 1.78 2.938 3.3597.8 52.6 45.2 74.63 85.1
3EP3 2.56 2.07 1.78 2.938 3.3565.0 52.6 45.2 74.63 85.1
3EP7 3.21 2.25 1.78 1.575 0.6381.5 57.2 45.2 40.01 12.1
3EP7M 3.21 2.25 1.78 1.575 0.6381.5 57.2 45.2 40.01 12.1
6EP1 6.62 2.07 2.28 5.625 6.03168.1 52.6 57.9 142.88 153.2
6EP3 5.33 2.07 2.28 5.625 6.03135.4 52.6 57.9 142.88 153.2
10EP1 6.62 2.07 2.78 5.625 6.03168.1 52.6 70.6 142.88 153.2
10EP3 5.35 2.07 2.78 5.625 6.03135.9 52.6 70.6 142.88 153.2
20EP1, 20VP1 4.95 2.27 1.8 4.063 4.47125.7 57.7 45.7 103.2 113.5
20EP6, 20VP6 5.09 2.25 1.78 4.063 4.46127.3 57.2 45.2 103.2 129.3
51Catalog 1654001 Dimensions are in inches and Dimensions are shown for USA Cust. Svc.: 1-800-468-2023 www.cor.comRevised 03-04 millimeters unless otherwise reference purposes only. CORCOM Prods: 1-847-680-7400 www.tycoelectronics.com
specified. Values in italics Specifications subject 1-508-992-4495are metric equivalents. to change. Germany: 49-89-6089-0
RFI Power Line Filters
EP/VP Series
Part Numbers
3EP1 10EP13EP3 10EP33EP7 20EP13EP7M 20EP66EP1 20VP16EP3 20VP6
Line Cord No. GA400
DEA C
B
EP1/VP1
EP3
EP7 & EP7M (with metric insert)
20EP/VP6
Typical dimensions:Terminals: .250 [6.35] (5) Holes: .07 [1.8] Dia.(4)Mounting Holes: .188 [4.78] Dia. (2) Slot: .07 x .16 [1.8 x 4.1]
Typical dimensions:Wire leads: 4.0 [101.6] Min. Mounting Holes: .188 [4.78] Dia.(2)
Typical dimensions:Terminals: .250 [6.35] (3) Holes: .07 [1.8] Dia.(2)Slot: .07 x .16 [1.8 x 4.1]
ADE C
B
Brown
Blue
Brown
Blue
Green/Yellow
A
Tapped insert:
D
E
No. 6-32 x 1/4 (2)-EP7No. M-3 x .5 (2)-EP7M
C
B
.2355.96
1.57540.01
.1573.98
.91023.11
Dia. (2)
1.29532.89
R
Panel Cutout (back mount)
C
B
ED
A
Terminals: No. 8-32 (5) Torque: 18 ± 2 in.lb
Tolerance ±.005 [0.13]
†
†
† ±.02 [±.5]
Malaspina University-College School of Management Centre 900 Fifth Street, Nanaimo BC
DDC Controls Shop Drawing Submittal
Submitted To:
Windley Contracting Ltd. 3711 Shenton Road Nanaimo, British Columbia V9T 2H1
Submitted By: Joe LeRoy, P.Eng 19-831 Devonshire Rd. Victoria, BC V9A 4T5 250 388-5665
Submittal Details:
Date Submitted: 3/30/2006 Date Resubmitted: Specification Section: Description: Low voltage relay Model: M15MAH001812VDC c/w ZD35 base
Supplier info:
Name: Carlo Gavazzi (Canada) Inc Address: 2660 Meadowvale Boulevard, Mississauga, ON L5N 6M6
Manufacturer info: Name: Carlo Gavazzi (Canada) Inc Address: 2660 Meadowvale Boulevard, Mississauga, ON L5N 6M6 Website www.GavazziOnline.com
houle controls (a div. of houle electric ltd.)
65CARLO GAVAZZI Automation Components Specifications are subject to change without notice.
Miniature Relays
Dimensions (mm) H x W x DTerminal typesNo. of Contacts
Contact rating
Output SpecificationsMax. load AC1Min. loadElectrical life
Switching power
General SpecificationsVoltage ranges VDC
Voltage ranges VAC
Insulation Coil/ContactConsumptionApprovals/Conformity
ReferencesConsult your Carlo GavazziPartner or Distributor
15.7 x 29 x 12.7PCB1 Change-over (1 pole)2 Change-over (2 poles)
12 A - 16 A (1 pole)8 A (2 poles)
9 A - 13 A - 18 A100 mA at 24 mVDC1x105 cycles
4000/3000/2000 VA
5 - 6 - 12 - 24 - 4860 - 110
4000 VAC5 00 mWcUL - VDE
From 5 to 110 VDC
15 x 29 x 10PCB1 Normally open1 Change-over
8 A
10 A100 mA at 24 mVDC100.000 cycles
2000 VA
3-5-6-8-12-18-24-48110 (M15) 3-5-6-8- 12-18-24-48 (M15R)
4000 VAC 220 mWUL - CSA - VDE - IMQS - N - D - F - SEV
3 to 110 VDC (M15)3 to 48 VDC (M15R)
25.2/26.5 x 29.4 x 12.5PCB2 Normally open
2 Change-over5 A - 10 A
6 A - 12 A100 mA at 24 mVDC2.5 x 105 cycles (5 A)8 x 104 cycles (10 A)1250/2500 VA
3 - 5 - 6 - 9 - 12 24 - 36 - 48 - 6080 - 100 - 1106 - 12 - 24 - 48 - 60110 - 2304000 VACSee PCB General Cat.UL - CSA - VDE - IMQS - N - D - F - SEV
From 2.5 to 260 VDCFrom 6 to 260 VAC
25.2/26.5 x 29.4 x 12.5PCB1 Normally open
1 Change-over5 A - 10 A - 16 A
6 A - 12 A - 20 A100 mA at 24 mVDC3.5 x 105 cycles (5/10A)1.5 x 105 cycles (16A)1250/2500/4000 VA
3 - 5 - 6 - 9 - 12 24 - 36 - 48 - 6080 - 100 - 1106 - 12 - 24 - 48 - 60110 - 2304000 VACSee PCB General Cat.UL - CSA - VDE - IMQS - N - D - F - SEV
From 1.8 to 160 VDCFrom 6 to 264 VAC
MZ MZ M15 - M15 R1/R2 M25(1 Pole) (2 Poles) (1 Pole) (1or 2 Poles)Types
General SpecificationsRated volt. / Rated curr.Insulation voltageSocket materialMounting Protection degreeApprovals
ReferencesFor detailed informationsconsult your Carlo GavazziPartner or Distributor
300 VAC / 12 A 5 / 8 pole socket.> 5 kV Screw terminal Self-ext. PA 6 + GF (V1) connection.DIN-rail Standardized markings.IP 20UL, CSA (12 A 300 VCA)
ZD 25 For relay: M15 F 8 AZD 32 For relay: M15 E 8 AZD 35 For relay: MZ 1P 5/10 A
M15 M 8AM25 1P 12 A
ZD 50 For relay: MZ B 1P 5/10 AMZ 2P 5/10 AMZ 1P 16 AM15 M 8 AM25 1P 16 AM25 2P 8 A
300 VAC / 12 A 5 / 8 pole socket.> 5 kV Screw terminal Self-ext. PA 6 + GF (V1) connection.DIN-rail Standardized markings.IP 20UL, CSA (12 A 300 VCA)
ES 50/3 For relay: MZ B 1P 5/10 AMZ 2P 5/10 AMZ 1P 16 AM15 B 8 A
Types ZD 25 - ZD 32 - ZD 35 - ZD 50 ES 50/3
Malaspina University-College School of Management Centre 900 Fifth Street, Nanaimo BC
DDC Controls Shop Drawing Submittal
Submitted To:
Windley Contracting Ltd. 3711 Shenton Road Nanaimo, British Columbia V9T 2H1
Submitted By: Joe LeRoy, P.Eng 19-831 Devonshire Rd. Victoria, BC V9A 4T5 250 388-5665
Submittal Details:
Date Submitted: 3/30/2006 Date Resubmitted: Specification Section: 15900.2.11 Description: Current transducer Model: CS-450-1
Supplier info:
Name: Pacific Controls Ltd. Address: 440 Garbally Road, Victoria, BC V8T 2S9
Manufacturer info: Name: Greystone Energy Systems Inc. Address: 150 English Drive, Moncton, NB E1E 4G7 Website www.greystoneenergy.com
houle controls (a div. of houle electric ltd.)
Peace of mind through reliable current sensors
CURRENT SENSORS
Detect current fluctuation remotely and reliably
• Solid Core CS-450 & CS-475 Series Current Sensors • Split Core SC-550 & SC-575 Series Current Sensors • CT/PT Input transducer
GREYSTONE IS AN ISO 9002 REGISTERED COMPANY
AC CURRENT SENSORS CS-450 / 475 and SC-550 / 575
• Three ranges per unit reduces inventory
• No field adjustment necessary, factory calibrated
• Average measurement is equivalent to True RMS for pure sine waves for the CS-450 / SC-550 series
• True RMS measurement for sine waves or variable frequency drives for the CS-475 / SC-575 series
• Input / Output isolation via current transformer
• Solid-state reliability
• Small compact size
FEATURES:
SOLID-STATE SENSORS FOR MONITORING AC CIRCUITS.
DESCRIPTION:
CURRENT SENSOR: PRODUCT ORDERING INFORMATION
GREYSTONE ENERGY SYSTEMS INC.
SPECIFICATIONS:
The CS-450 / 475 and SC-550 / 575 series of AC current sensors are solid-state transducers that convert a primary circuit current to a proportional output signal. The sensors can monitor up to 200 Amps continuous and feature three jumper selectable current ranges for the highest accuracy. All sensors are factory calibrated to ensure better than
1% accuracy. The CS-450 and the SC-550 are available with 0-5, 0-10 Vdc or 4-20 mA output signal types. The CS-475 and the SC-575 feature a true RMS 4-20 mA loop-powered output signal. All models are CSA certified, UL Approved and CE compliant.
CS-45X / SC-55X CS-475 / SC-575 Power Supply 0-5/0-10 Vdc models are self-powered, 4-20 mA model
requires 15-42 Vdc at sensor 15-42 Vdc at sensor (loop powered)
Input Current Ranges Three field selectable ranges (see below) Three field selectable ranges (see below)
Maximum Input Current
10/20/50 Amp ranges-80/120/180 Amps continuous 50/100/200 Amp ranges-120/200/325 Amps continuous
2/5/10 Amp ranges – 35/60/90 Amps continuous 10/20/50 Amp ranges – 80/120/200 Amps continuous 50/100/200 Amp ranges – 175/300/400 Amps continuous
Response Time 100 mS (0-90%) 250 mS (0-90%)
AC Conductor Hole
Solid Core – 20mm (0.8”) diameter Split Core – 24 x 19 mm (0.95 x 0.75”)
Solid Core – 20mm (0.8”) diameter Split Core – 24 x 19 mm (0.95 x 0.75”)
Output Loading Error (0-5/0-10) Calibrated with 1 M ohm load, add 1.2% error with 100k ohm load N/A
Enclosure Size (H x W x D)
Solid Core – 49 x 87 x 25 mm (1.95 x 3.45 x 1.0”) Split Core – 70 x 87 x 30 mm (2.75 x 3.45 x 1.2”)
Solid Core – 49 x 87 x 25 mm (1.95 x 3.45 x 1.0”) Split Core – 70 x 87 x 30 mm (2.75 x 3.45 x 1.2”)
Operating Temperature -30 to 70°C (-22 to 158°F) 0 to 70°C (32 to 158°F)
Operating Humidity 0 to 95% RH, non-condensing 0 to 95% RH, non-condensing
Protection Circuitry Reverse voltage protected and output limited Reverse voltage protected and output limited
Wiring Connections
Solid Core – Barrier strip Split Core – Screw terminals (14 to 22 AWG)
Solid Core – Barrier strip Split Core – Screw terminals (14 to 22 AWG)
Enclosure Material UL 94 V-0 flammability rated ABS, Insulation class 600V UL 94 V-0 flammability rated ABS, Insulation class 600V
Manufacturing ISO 9002 Certified ISO 9002 Certified
Output Signal & Accuracy 0-5 Vdc, 0-10 Vdc or 4-20 mA Better than ±1% FS on all three ranges
4 to 20 mA represents 0 to 100% of current span Better than ±1% FS on all three ranges
Solid Core (CS)
Model Output Accuracy Frequency Model Output Accuracy Frequency
CS-450-1 0-5 Vdc ±1% FSO 40 – 100 Hz SC-550-1 0-5 Vdc ±1% FSO 40 – 100 Hz
CS-450-2 0-5 Vdc ±1% FSO 40 – 100 Hz SC-550-2 0-5 Vdc ±1% FSO 40 – 100 Hz
CS-451-1 0-10 Vdc ±1% FSO 40 – 100 Hz SC-551-1 0-10 Vdc ±1% FSO 40 – 100 Hz
CS-451-2 0-10 Vdc ±1% FSO 40 – 100 Hz SC-551-2 0-10 Vdc ±1% FSO 40 – 100 Hz
Split Core (SC)
CS-452-1 4-20 mA ±1% FSO 40 – 100 Hz SC-552-1 4-20 mA ±1% FSO 40 – 100 Hz
CS-452-2 4-20 mA ±1% FSO 40 – 100 Hz SC-552-2 4-20 mA ±1% FSO 40 – 100 Hz
Amp Ranges
0-10/0-20/0-50
0-50/0-100/0-200
0-10/0-20/0-50
0-50/0-100/0-200
0-10/0-20/0-50
0-50/0-100/0-200
Amp Ranges
0-10/0-20/0-50
0-50/0-100/0-200
0-10/0-20/0-50
0-50/0-100/0-200
0-10/0-20/0-50
0-50/0-100/0-200
CS-475-1 4-20 mA ±1% FSO 10 – 400 Hz 0-10/0-20/0-50 SC-575-1 4-20 mA ±1% FSO 10 – 400 Hz 0-10/0-20/0-50
CS-475-2 4-20 mA ±1% FSO 10 – 400 Hz 0-50/0-100/0-200 SC-575-2 4-20 mA ±1% FSO 10 – 400 Hz 0-50/0-100/0-200
CS-475-0 4-20 mA ±1% FSO 10 – 400 Hz 0-2/0-5/0-10 SC-575-0 4-20 mA ±1% FSO 10 – 400 Hz 0-2/0-5/0-10
Greystone Energy Systems Inc. 150 English Drive, Moncton, NB Canada E1E 4G7 (506) 853-3057 Fax: (506) 853-6014 e-mail: [email protected] www.greystoneenergy.com
GREYSTONE IS AN ISO 9002 REGISTERED COMPANY
Split Core SC-550 & SC-575 Series Current Sensor
Cop
yrig
ht ©
Gre
ysto
ne E
nerg
y S
yste
ms
Inc.
All
Rig
hts
Res
erve
d
Solid Core CS-450 & CS-475 Series Current Sensor
87 mm (3.45”)
49 mm (1.95”)
20 mm (0.8”) diam.
24 mm (0.95”)
30 mm (1.2”)
87 mm (3.45”)
70 mm (2.75”) 19 mm
(0.75”)
25 mm (1.0”)
Options Relay Mounting Base CR-112 / CR-124
DESCRIPTION:
SPECIFICATIONS: (NOTE: COMMAND RELAY DOES NOT ACCEPT A VARIABLE ANALOG SIGNAL
Relay Coil CR-112 12 Vac/dc ± 20% @ 18 mA CR-124 24 Vac/dc ± 20% @ 10 mA
Enclosure Size (L x W x D)
102 x 44 x 25 mm (4 x 1.75 x 1”) 125 mm (4.9”) length with mounting tabs
Relay Contacts
SPDT Form C (normally open, common, normally closed) 10 Amp resistive @ 250 Vac (UL508) 8 Amp inductive @ 250 Vac 5 Amp @ 30 Vdc
Mounting Holes Dimension
114 mm (4.5”) spacing, 4.8 mm (0.19”) diameter
Contact Resistance 100 mΩ maximum Enclosure Material UL 94V-0 flammability rated ABS
Oper. Temperature -40 to 85°C (-40 to 185°F) Operating Humidity 20 to 85% RH, non-condensing
Wiring Connections Screw terminal block (12 to 28 AWG) Manufacturing Process
ISO 9002 Certified
• Can be easily mounted to any CS or SC product for easier installation
• Can be used as a stand-alone relay
• Convenient Relay Status LED
• Can be factory assembled with any CS or SC product
• Push-rivets supplied for fast and reliable field assembly
• SPDT Form C relay contacts
• Environmentally-friendly cadmium-free contacts
• Ideal for switching contactors, solenoids and motors
• Small compact size
FEATURES:
The CR-112 and CR-124 Command Relays are line voltage relays for use with the CS and SC current sensors and switches or as
stand-alone devices. All models are CSA certified, UL approved and CE compliant.
Greystone Energy Systems Inc. is one of North America’s largest ISO registered manufacturers of HVAC sensors and transducers for Building Automation Management Systems. We have conscientiously established a worldwide reputation
as an industry leader by maintaining leading-edge design technology, prompt technical support, and a commitment to
on-time deliveries. We take pride in our Quality Management System which is ISO 9002 certified, assuring
our customers of consistent product reliability.
Malaspina University-College School of Management Centre 900 Fifth Street, Nanaimo BC
DDC Controls Shop Drawing Submittal
Submitted To:
Windley Contracting Ltd. 3711 Shenton Road Nanaimo, British Columbia V9T 2H1
Submitted By: Joe LeRoy, P.Eng 19-831 Devonshire Rd. Victoria, BC V9A 4T5 250 388-5665
Submittal Details:
Date Submitted: 3/30/2006 Date Resubmitted: Specification Section: 15900.2.10.2 Description: Differential pressure sensor Model: LP1B00
Supplier info:
Name: Pacific Controls Ltd. Address: 440 Garbally Road, Victoria, BC V8T 2S9
Manufacturer info: Name: Greystone Energy Systems Inc. Address: 150 English Drive, Moncton, NB E1E 4G7 Website www.greystoneenergy.com
houle controls (a div. of houle electric ltd.)
Peace of mind through reliable
pressure transducers
GREYSTONE HAS AN ISO 9001 REGISTERED QUALITY SYSTEM
Each series of Greystone low pressure transducers comes standard with an ABS enclosure. These transducers feature high level outputs, environmental protection, and temperature compensation.
FEATURES: • Jumper selectable 2 wire current and
3 wire voltage outputs standard • 24 Vac/dc power supply standard • Eight variable jumper selectable pressure
range’s, WC and PA • Functional weather resistant ABS Enclosure • Available options include LCD display and
mounted static probe • Two available accuracy's
LOW PRESSURE TRANSDUCERS
LP1 Series
Shown above c/w LCD and mounted static probe options
SPECIFICATIONS: LP1 Series Pressure Ranges See ordering information
Calibration Accuracy ± 1% F.S.O. (LP1A/B Series)
Measurement Type Differential (two port)
Response Time 1 mS maximum
Stability <±1% F.S.O. per year
Thermal Effects <±3% over compensated range
Compensated Range 10 – 50°C (50 – 122°F)
Over Pressure 20 psi or 2 x range (whichever is greater)
Operating Conditions 0 – 60°C (32 – 140°F), 10 – 90% RH non-condensing
Media Compatibility Limited only to those that will not attack polyetherimide, silicon, fluorosilicone, silicone, EPDM, and neoprene seals. Typically dry air or inert gas but liquid is allowed.
Power Supply (at transmitter) 12 – 28 Vac, 16.5 – 35 Vdc (non-isolated half-wave rectified)
Supply Current <4 mA
Input Voltage Effect Negligible over specified operating range
Protection Circuitry Reverse voltage protected and output limited
Output Signal 4 – 20 mA (2-wire), 0 – 5 Vdc or 0 – 10 Vdc (3-wire)
Current Output Drive Capability 400 ohms maximum @ 24 Vdc
Voltage Output Drive Capability 2 Kohms minimum for 0-5 Vdc signal 10 Kohms minimum for 0-10 Vdc signal
Zero Adjustment Pushbutton auto-zero
Wiring Connections Screw terminal block (14 to 22 AWG)
Pressure Connections Barbed ports for 0.170” ID flexible tubing
Conduit Connection Access hole for 1/2” NPT conduit or cable gland
Optional LCD 3½ digit, 0.4” digit height
Enclosure High Impact Black ABS, plenum rated with optional gasket 116 mm W x 84 mm H x 53 mm D (4.55” x 3.3” x 2.1” )
± 1.25% F.S.O. (LP1C Series)
• HVAC/VAV • Process Control • Air Flow Monitoring
• Drop Across Air Filters • Hydraulic Pressures • Pneumatic Pressures
APPLICATIONS:
GREYSTONE ENERGY SYSTEMS INC.
LP1 c/w LCD LP1 c/w LCD & Mounted static probe
JUMPER SELECTABLE LP1 SERIES: PRODUCT ORDERING INFORMATION
GREYSTONE ENERGY SYSTEMS INC.
The LP1 Low Pressure Transmitter can be used to measure positive, negative or differential pres-sure in the ranges of 0.25”wc to 12”wc (50 TO 2000Pa). The piezoresistive sensor is ideal for moni-toring the pressure for air or other clean inert gas and is limited only to those media which will not attack polyetherimide, silicon, fluorosilicone, silicone, EPDM and neoprene seals. The LP1 features field selectable pressure ranges and output signal types for the most flexible ap-plication. Typical HVAC applications include monitoring of filter differential pressure or clean room pressure. The output signal is factory calibrated and temperature compensated for highest startup accuracy and trouble-free operation. Available options include accuracy’s, LCD, mounted static pressure probes and access options for room pressure monitoring. Please read the installation instructions carefully before commissioning the pressure transmitter. Failure to follow the instructions may result in product damage. A qualified technician must install this device. The LP1 Pressure Transmitter mounts on any surface using the two holes provided on the base of the unit. Make sure there is enough space around the unit to connect the pressure tubing without kinking and avoid locations where severe vibrations or excessive moisture are present. Mount the enclosure with two user-supplied screws but do not over-tighten. The unit may be mounted in any position but typically is installed on a vertical surface with the pres-sure ports on the right and the cable entrance on the left. The enclosure has a standard ½” conduit opening and may be installed with either conduit and a conduit coupler or a cable gland type fitting. Do not use in an explosive or hazardous environment, with combustible or flammable gasses, as safety or emergency stop devices or in any other application where failure of the product could result in personal injury. Use electrostatic discharge precautions during installation and do not ex-ceed the device ratings.
DESCRIPTION:
Model Description
LP1 Jumper Selectable Low Pressure Transducer
CODE Optional accuracy's
A B C
± 1% F.S.O. LCD Display (Only available in ± 1% configuration) ± 1.25 % F.S.O.
CODE Jumper Selectable Pressure Ranges
00 01 02 03
±0.25”, ±0.5“, ±1”, ±2”, 0-0.5”, 0-1”, 0-2”, 0-4” wc ±0.75”, ±1.5”, ±3”, ±6”, 0-1.5”, 0-3”, 0-6”, 0-12” wc ±50, ±100, ±200, ±400, 100, 200, 400, 800 Pa ±125, ±250, ±500, ±1000, 250, 500, 1000, 2000 Pa
LP1 B 00
Example: LCD, ±0.25” to 0-4” wc, Static Pressure Probe
S
CODE
S R
Options
Mounted Static Pressure Probe (N/A with LP1C series) Room Pressure Model, all electrical and pressure connections on back
Typical Model Number
Greystone Energy Systems Inc. is one of North America’s largest ISO registered manufacturers of HVAC sensors and transducers for Building Automation Management Systems.
We have conscientiously established a worldwide reputation as an industry leader by maintaining leading- edge design technology, prompt technical support, and
a commitment to on-time deliveries. We take pride in our Quality Management System which is ISO 9001 certified,
assuring our customers of consistent product reliability.
150 English Drive, Moncton, NB, Canada E1E 4G7 e-mail: [email protected] Tel.: (506) 853-3057 Fax: (506) 853-6014 web site: www.greystoneenergy.com
DIMENSIONS:
84 mm (3.3")
116 mm (4.55") 53 mm (2.1")
OPTIONS:
Pitot Tube HFO & HSO Series
Differential Pressure Probe SSS Series
The SS series DP probe is used for sensing velocity pressure in the duct. Available in 4”, 6”, 8” & 10” lengths. Kits are available that come complete with pneumatic tubing.
The HFO and HSO series are used to sense velocity pressure or static pressure respectively. Available in 6” length. Kits are available for differential and static that are complete with pneumatic tubing.
ABS enclosure dimensions
Static Probe Option The S option is a high accuracy static tube. It is available as an option on the LP1A / B Series low pressure transducer.
Malaspina University-College School of Management Centre 900 Fifth Street, Nanaimo BC
DDC Controls Shop Drawing Submittal
Submitted To:
Windley Contracting Ltd. 3711 Shenton Road Nanaimo, British Columbia V9T 2H1
Submitted By: Joe LeRoy, P.Eng 19-831 Devonshire Rd. Victoria, BC V9A 4T5 250 388-5665
Submittal Details:
Date Submitted: 3/30/2006 Date Resubmitted: Specification Section: 15900.4.10.2 Description: Light Sensor Model: PSR-1
Supplier info:
Name: Pacific Controls Ltd. Address: 440 Garbally Road, Victoria, BC V8T 2S9
Manufacturer info: Name: Greystone Energy Systems Inc. Address: 150 English Drive, Moncton, NB E1E 4G7 Website www.greystoneenergy.com
houle controls (a div. of houle electric ltd.)
DESCRIPTION: The PSR-1 is a Light Sensitive Resistor that may be used as an input to indicate the presence of light at the sensor location. The PSR-1-T is a PSR-1 coupled with a B420-P transmitter. The PSR-1-T produces a 4 – 20mA ouput signal. The sensor is designed to be mounted in the end of a weatherproof conduit box.
APPLICATION: The PSR-1 has a resistance in darkness in excess of 1 MΩ and resistance in bright light of less than 1.5 kΩ. The PSR-1 and PSR-1-T indicate the presence of absence of light. They should not be used for footcandle control of occupied spaces. The PSR-1-T is calibrated for 4mA in bright light > 100 foot-candles and 20mA in darkness < 0.1 foot-candles.
SPECIFICATIONS: PSR-1 Output (non-linear) >1 MΩ in dark <1.5 kΩ in bright light Temperature -25°C to 75°C (-13°F to 167°F) PSR-1-T Power 12 – 35 VDC Max current draw 22 mA Output (linear) 4–20mA (current limited to 22 mA) Temperature -25°C to 75°C (-13°F to 167°F)
MODEL PRODUCT DESCRIPTION
PSR
CODE OPTIONS
1 Sensor only
T 4 – 20mA Transmitter
E Weatherproof Enclosure
RESISTIVE LIGHT SENSOR
PSR: PRODUCT ORDERING INFORMATION
EXAMPLE: Light sensor c/w 4 – 20mA output in weatherproof enclosure
PSR-1-T-E
DESCRIPTION: The WD100 is a microchip-based device that uses gold-plated sensing probes to detect the presence of water or other conductive liquid. The WD100 is powered by an AC or DC source, 14 – 30 volts. It features normally open and normally closed (form C) relay contacts rated at 5A@120VAC/30DC for connection to a monitoring system, or direct control of another device. The mounting legs will allow a sensing height adjustment from 0” to 1/2”. The WD100 is designed to signal an alarm if one or more of three conditions are met: water is detected, power is lost to the unit, or if there is an internal failure. The WD100 provides the highest level of water detection confidence. The WD-102 operates on the same principle as the WD-100 but comes with a 5 ft. remote probe. For custom lead lengths please contact Greystone. The WD-100-xx Series c/w the specified length of conductivity cable. See ordering information for available lengths. SPECIFICATIONS: Power supply: 14 – 30 VAC/DC Supply current 60mA @ 24 VDC, (no water) Operating temperature: -40° to 85°C(-40° to 185°F) Enclosure dimension 127 x 127 x 102 mm (L x W x H) 5-3/8“ x 5-3/8“ x 4” (max) (mounting legs@ 127 x 127 x 102mm max/min height): 5-3/8“ x 5-3/8“ x 3½”(min) Alarm output: Form C relay, rated @ 5 amps @ 120VAC / 30VDC (resisitive load)
APPLICATIONS: The following chart gives examples of what types of fluids the WD100 can and can not be used to detect.
OTHER FEATURES: Fail-safe circuitry
Reverse acting contacts Reverse voltage protection
RFI/EMI noise immunity
ORDERING INFORMATION: WD-100 – Stand Alone WD-102 – Remote Probe (5‘) WD-100-5 – c/w 5’ conductivity cable WD-100-10 – c/w 10’ conductivity cable WD-100-25 – c/w 25’ conductivity cable WD-100-50 – c/w 50’ conductivity cable WD-100-100 – c/w 100’ conductivity cable
LIGHT SENSOR – PSR SERIES
WATER DETECTOR – WD100 SERIES
Fluids than can be detected
Fluids that can’t be detected
City water Pure water
Sea water Gasoline
Copper sulfate solution Oil
Weak acid Brake fluid
Weak base Alcohol
Household ammonia Ethylene glycol
Water & glycol mixture Paraffin
Wet soil Dry soil
Coffee Whiskey
GREYSTONE ENERGY SYSTEMS INC.
Malaspina University-College School of Management Centre 900 Fifth Street, Nanaimo BC
DDC Controls Shop Drawing Submittal
Submitted To:
Windley Contracting Ltd. 3711 Shenton Road Nanaimo, British Columbia V9T 2H1
Submitted By: Joe LeRoy, P.Eng 19-831 Devonshire Rd. Victoria, BC V9A 4T5 250 388-5665
Submittal Details:
Date Submitted: 3/30/2006 Date Resubmitted: Specification Section: 15900.2.16 Description: Water flow meter Model: TX81B Insertion Turbine Meter with FT420 Flow Computer
Supplier info:
Name: Van Isle Water Address: 461 Dupplin Rd., Victoria BC V8Z 1B8
Manufacturer info: Name: Seametrics Address: 20419 80th Ave. So., Kent WA 98032 Website www.seametrics.com
houle controls (a div. of houle electric ltd.)
SensorHall Effect Sensor 12 VDC current
sinking pulseMaterials
Sensor Body Polypro, Brass, 316 SSRotor Polypro, PVDF optionalShaft Nickel-bound tungsten
carbide,zirconia ceramicoptional
Bearings RubyRange 0.2 - 30 FPS (0.06-9.14M/s)Acuracy ± 1% FSMaximum Pressure
Polypro 175 psi @ 75° F (12 bar)Brass 200 (14 bar)316 SS 250 psi (17 bar)
Maximum TemperaturePolypro 130° F (55° C) at 0 psiBrass, SS 200° F (93° C)
Power 6-24VDC, 8 mANominal K-factor 11 Hz/FPS (3.6 HzM/s)Cable #22 AWG 3-con 18' (6m)Maximum Cable Run 2,000' (650m)Flow Range (GPM)
SpecificationsGeneral Information
The TX80 Series are turbine-type insertion meters de-signed for use in pipe sizes 1" to 8". High-quality jewelbearings and nickel-bound tungsten carbide shaft areused for maximum life and extreme low friction. Bodiesare machined from solid rod for maximum precision. Low-flow performance is superior. The rotation of the rotor isdetected by a non-drag Hall-effect sensor. Output is apulse-type square wave, which can be sent long dis-tances (up to 2,000 feet) without a transmitter. This sig-nal can be connected directly to SeaMetrics controls, aswell as PLC's, counters, and computer cards.
SeaMetrics TX80 meters are ideal for chemical propor-tioning applications. If no display is required, a simpledivider such as the PD10 provides adjustable pump pac-ing. For rate and total display, as well as pump pacing,the FT420 flow indicator can be mounted directly on theTX80 Series, or remotely on a wall or panel.
The TX80 Series require special fittings, since they arenot depth-adjustable, installation in the fitting ensurescorrect depth placement in the pipe. Fittings are avail-able in PVC, brass, and stainless steel. Sensors are avail-able in brass, 316 stainless steel, and polypropylene. Inplastic pipe 3"-8", use an IP82 sensor, which is 1.00"longer than the IP81 to accommodate the larger fittings.
LT-10614APage 1 of 4
Features
TX80 Series FlowSensor Instructions
Pipe stubs providedfor ease of installation.Solvent weld or
male NPT
Each fitting individuallycalibrated and marked
with K-factor(Pulses per Gallon)
Fitting automaticallysets probe at correctdepth and orientation
Jewel bearings forsuperior low-flow
performance.Threaded housings
allow for field repair
MO
DE
LS
ER
IAL
High level (12 VDC)signal can be sentup to 2000+ feetwithout transmitter
Meter mount optionfor electronics:Rate/Total4- 20 mA blind transmitterPulse DividerBattery Rate/Total
Min.
Max.
1" 1-1/2" 2" 3" 4" 6" 8"
0.8 1.9 3.1 6.9 12 27 47
80 190 314 691 1200 2700 4700
Installation
Fitting Installation. TX80 Series meters require spe-cial fittings. The meter fitting must first be installed in thepipeline. Straight pipe of at least ten times the diameterupstream of the meter and five diameters downstreamare strongly recommended. Inadequate straight pipe,especially downstream of an elbow, change in pipe di-ameter, or partially-opened valves, can result in signifi-
cant inaccuracy. Typically this inaccuracy is in the formof the meter reading "high". TX80 Series meter fittingsare supplied with some upstream straight pipe. In thelarger sizes, the length provided is less than ten diam-eters upstream and five downstream. It is not advisableto connect directly to the end of these fittings with a flow-disturbing device such as a valve or elbow. If possible,straight pipe should be added to these fittings.
A PVC fitting is usually installed by solvent welding. Thestainless steel and brass meter fittings have female pipethreads, requiring the appropriate male threaded fittings.Saddle fittings (size 3" and above) require a hole to becut in the pipe. The recommended hole size is 1-3/4".
!Caution: Never remove the u-clip retainer when the pipe isunder pressure. Always removepressure from the pipe beforeattempting to remove the meter.
Removal under pressure may result in damageor serious injury.
Meter Installation. After the meter fitting is installed inthe pipeline, the meter can be installed in the fitting. Pressthe meter into the fitting as far as it will go. Then retainthe meter in place by inserting the u-pin. This pincan be installed from either side. It is sometimes neces-sary to rotate the probe back and forth slightly to startthe pin into the slots on the probe. Slide the pin in as faras it will go.
Meter Connection. See the “TX80 Series Connections”diagram for meter connections. Unless the meter is sup-plied pre-connected to a meter-mounted FT420 flow in-dicator, three leads must be connected. These threeleads are color coded. The red wire is positive, the blackis negative, and the white wire is the signal lead.
Okay, if no air in pipe
Okay, if no sediment inpipe.
TX80 Series Connections
Red (+)White (SIG)Blac k (-)
BEST
2 of 4
10 5Diameters Diameters
K-factor. If the TX80 Series meter is ordered with itsfitting, the meter is factory calibrated in the fitting. A K-factor (meter factor) is indicated on the side of the fitting.This represents the actual number of pulses per gallonthe meter produced during the factory flow test. Thisnumber can entered into an FT420 or FT520 flow indi-cator to make it read properly. If a pulse divider is beingused, the K-factor is the starting point for calculating thedivider number.
These water meters are not recom-mended for installation downstream ofthe boiler feedwater pump where instal-lation fault may expose the meter toboiler pressure and temperature. Maxi-
mum recommended temperature is 130ºF (Plastic),200ºF (Metal).
!
Maintenance and Repair
Rotor Replacement. It is unusual for a rotor to requirereplacement due to damage sustained in normalservice. More commonly, the meter is dropped while itis out of the pipe. Another reason for rotor replacementis shaft wear after long service. Rotors are easily field-replaced. Shaft and rotor are not a single unit, if theyare using Kynar/ceramic. If replacement is due only tonormal shaft wear, bearing replacement is probablynot necessary. If the rotor has been damaged byimpact, the bearings should also be replaced. Rotorand bearings can be ordered as a kit, Part No.25930.To install a rotor, follow these steps:
1. Unscrew the threaded bearing housings to exposethe shaft ends. If bearings are being replaced, backthem completely out.
2. Remove the rotor. Put the new rotor in its place.
3. Thread in one bearing housing part way, then theother. Take care to start the end of the shaft into thebearing hole before tightening further.
4. Screw in bearing housings until they bottom. Note:Do not use excessive force.
5. Check for free spin. Blowing lightly on the rotorshould result in it spinning rapidly and coasting to asmooth stop.
Sensor Replacement. It is very unusual for a sensorto require replacement in normal use. The primary causeof sensor failure is overvoltage (inadvertent connectionof line voltage, for example) or incorrect polarity onhookup. The sensor is replaced by removing the strainrelief, then threading out the sensor retainer plug. Re-move the entire sensor capsule by pulling on the cable.The new sensor capsule can then be installed. It isimportant to orient the sensor capsule properly. Re-place the retainer plug, and then replace and tightenthe strain relief.
3 of 4
ediuGgnitoohselbuorT
melborP esuaCelbaborP kcehCoT riapeRoT
noitallatsniretfalangisoN wolftneiciffusnI ezisrofMPG.niMeeS scirteMaeStcatnoC
lortnocotsnoitcennocdaBscinortcele
.lortnoctasnoitcennockcehC,)-(kcalb,)+(der:ytiralopkcehC
)langis(etihwyrassecenfitcennoc-eR
lortnocelbitapmocnICDV42-6edivorp)1:lortnocseoD
gniknistnerructpecca)2;rewopstupni
scirteMaeStcatnoC
rotorgnissimrodegamaD yllausivkcehcdnaretemevomeRgninnipseerfrof ecalperdnarotorwenniatbO
gniretemetaruccanI neewtebepipthgiartshguonetoNecnabrutsidwolfdnaretem erusaem,snoitadnemmocereeS wolfmorfyawaretemevoM
etarbilacdleifroecnabrutsid
Part No. Description25930 Rotor repair kit(tungsten carbide)
25945 Rotor repair kit (ceramic)
25946 Rotor & shaft assy. (tungsten
carbide)
25947 Rotor & shaft assy. (ceramic)
11015 Sensor assy.
16439 O-Ring, Viton
16455 O-Ring, Viton
25081 O-Ring, EPDM
Spare Parts List
KYNAR is a registered trademark of Elf Atochem North America Inc.
20419 80th Ave. So., Kent WA. 98032 USAPhone: 253-872-0284 Fax: 253-872-0285www.seametrics.com 1-800-975-81534 of 4
gnitsiLstraP28,18XT
1 gnisuohreppU 18162
2 teksaG 11262
3 gnisuohrewoL 03992
4 wercsgnisuoH 92262
5 leets,gulP 37062
6 citsalp,gulP 97062
7 feilerniartS 5567
8 wercsgniniaterrosneS 12352
9 rosneS 01362
01 gnir-O 18052
11 )dradnats(ylbmessagniraeB 10952
21 )tfahscimareclanoitpo(wercstfahS 01761
31 )dradnats(rotorenibruT 64952
31 )21#htiwesu-lanoitpo(rotorenibruT 74952
41 pilc-U 72551
7
8
9
11
10
14
12
13
(Standard)
(Optional)
3
7
654
2
1
trahCytilibitapmoCsgnittiF
lairetaM 18XT 28XT
eznorB eeT"4-"1 gnittifezarB"8-"3
CVP eeT"2-"2/1 elddaS"8-"3
orpyloP A/N eeT"8-"3
leetssselniatS eeT"2-"2/1 gnittifdleW"8-"3
leetsnobraC eeT"2-"2/1 gnittifdleW"8-"3
FT420 Flow ComputerInstructions
The FT420 is a loop-powered microcontroller-basedtransmitter/indicator. It displays rate and total, and pro-vides a 4-20 mA analog signal proportional to flow. Aprogrammable pulse output, high flow or low flow alarmare also standard for metering pump control or datalogging.
The rugged cast-aluminum housing is gasketed for maxi-mum environmental protection, and the electronics arepotted into a solid block of urethane. A membrane key-pad allows settings to be changed without removing thecover. The wall mount version comes with brackets formounting. An adapter kit (part No. MK20) allows fieldmounting on 80-series flow sensors. The FT420 canalso be factory installed on a TX100/200 series sensoror WT meter.
SET
Features
Sturdy gasketed coverwith electronics
potted in
Removeable foot bracketsfor wall mounting
Large rate numerals
Easy set-upprompts Triple bosses for
watertight input/outputconnections
10.52341678.9
SET K RESET
Two wire4-20 mA output standard
SpecificationsGeneral Information
Power 4 mA DC (4-20 mA loop),12-32 VDC
DisplayRate 6-digit autorange, 1/2"
character heightTotal 8-digit, 5/16" character
height
Pulse Output • 0.1 second open collectorpulse (scaled)• high alarm or low alarm• sensor pulse (unscaled)
Input Pulse frequency + 5 VDCK factor Range 0.050 - 999999.9Pulse Output Range 0.1 - 200,000 units/pulseFlow Alarm Output Range
0.1 - 999999.99Temperature 0 C - 70 CEnvironmental NEMA 4X
LT-10605APage 1 of 4
012
3
456
RUN
BATT
CPU
POWER
CPU
7
OUTPUT 24VDCOUTPUT RELAY
A B
INPUT 4-20mA
A B
Installation
To mount the FT420 on a wall, hold the unit in the de-sired position, mark the holes in the mounting feet, drill,and mount with screws.
This unit can also be mounted directly on a flow sensorfor local reading. If the unit was ordered as an FT420,factory mounted to the top of a 100 or 200 Series flowsensor, no further installation is required.
To mount the unit on a flow sensor, remove the hous-ing cover. Place the lower half of the housing in thegroove on the top of the flow sensor. An adapter is in-cluded in the packaging of the FT420 which threadsinto the top of any 80-Series flow sensor. Pull the sen-sor wires through the hole in the center of this adapter,then thread the adapter into place. Tighten the adapterusing a screwdriver. (See diagram). Connect the wires,then replace the housing cover, orienting it any direc-tion as desired for viewing convenience.
Connection
To connect to the FT420 to a flow sensor, follow thediagram marked “Connections”. This diagram alsoshows the connections for an external device, suchas a chemical metering pump.
If the 4-20 mA current signal is not required, connectthe power terminals to any 12-30 VDC currentsource.
Programming
At a minimum, every FT420 must be programmed withthe “K-factor”. This is simply the number of pulses pergallon which the meter or flow sensor produces. (If youwish the FT420 to read in another unit, enter the num-ber of pulses per that unit. For example, if the desiredunits are liters, the K-factor is the number of pulses perliter that the flow sensor produces.)
To find the K-factor on any SeaMetrics flow sensor fit-ting or in-line meter, look on the model-serial label. Theline reading K = xxxx is the desired number. For adjust-able sensors (101,201,115,215) look in the instructionmanual under your pipe size.
Set K. Begin by pressing the key SET once. The promptSET K should appear on the display. The digit to the farright will be blinking. Use the up arrow key to reachyour desired digit. Then press the left arrow key to moveto the next digit. Repeat the process until the entirenumber is entered. (Note that the decimal is fixed atthree places. If you only have two decimal places foryour K-factor, enter a zero for the third digit.)
2 of 4
Typical 4-20 mA Application
!Caution: If output is being usedto control an external device, suchas a metering pump, do not con-nect the device until programmingis completed. If malfunction or in-
correct programming of the output could causepersonal injury or property damage, separatesafeguards must be installed to prevent such in-jury or damage.
powersupply
Chemical
FT420on TX81
Control Pulses
Flow
ProportionalChemical
Typical Chemical Metering PumpApplications
Loop power supply(if not providedon PLC)
Sensor Mount: Step 1 Sensor Mount: Step 2
Sensor Wires
Sensor Wires
3 of 4
Standard Connections
To OtherControl
Pulse ResponsiveMetering Pump
PU
LSE
SC
ALE
DP
ULS
EPA
SS
THR
U
-
+ -+12-30 VDC
Loop Power,4-20 mA Output
PO
WE
R4-20 m
A
RedWhiteBlack
SE
NS
OR
INP
UT
TX81Flow Sensor
Optional ChartRecorder or Other 4-20 mA Device
Operation
To return to normal operation after entering settings,press SET for a sixth time. The rate and total indicatornumbers should appear in the display. If the unit is con-nected to an operating flow sensor, the larger-sized dig-its indicate flow rate and the smaller-sized digitsindicate total.
Unless the unit has been ordered with the non-reset op-tion, a RESET prompt is constantly visible in the lowerright corner, above the up arrow key. Press this key atany time to reset the totalizer to zero.
Set P. The second time the SET key is pressed, SET Pwill appear. Follow the same process as above to enterthe desired pulse rate. This is the number of gallons (orother units, if you are using them) between pulses. Note:If the pulse output feature is not being used, thisstep can be skipped. The P (pulse output) settingdoes not affect anything if it is not being used.
Special Function: Flow Alarm. If a flow alarm isneeded, pressing all three buttons at once willbring up the appropriate settings while Set P isshowing. Pressing the up arrow key changes fromP (pulse output) to AL HI (high flow alarm). Pressthe up arrow key again changes to AL LO (lowflow alarm). Press the SET key to set the alarmrate. Use the up arrow and left arrow as above toreach the desired digits. Note: Using flow ratealarms eliminates the pulse output function.
Set 20 mA. Press the SET key the third time, to set theflow rate, in units per time unit, at which 20 mA is de-sired. The processor will automatically scale the 4-20mA loop accordingly, with 4 mA at zero flow.
Set Decimal Point. The fourth time the SET key ispressed, a D prompt appears. Pressing the up arrowkey switches between no decimal place, one decimalplace or two decimal places.
DimensionsFT420
Sensor-MountFT420
with Wall Mount Brackets
20419 80th Ave. So., Kent, WA 98032 USAPhone: 253-872-0284 Fax: 253-872-0285www.seametrics.com 1-800-975-8153 4 of 4
2.78"
2.57"
SET
3.93"
4.52"
3.93"
2.06"2341678.910.5
SET
SECMINHRDAY
10.52341678.9
RESET
Set Time Unit. The fifth time the SET key is pressed, ablinking time unit appears. Press the up arrow keyto select SEC (seconds), MIN (minutes), HR (hours) orDAY (days).
Malaspina University-College School of Management Centre 900 Fifth Street, Nanaimo BC
DDC Controls Shop Drawing Submittal
Submitted To:
Windley Contracting Ltd. 3711 Shenton Road Nanaimo, British Columbia V9T 2H1
Submitted By: Joe LeRoy, P.Eng 19-831 Devonshire Rd. Victoria, BC V9A 4T5 250 388-5665
Submittal Details:
Date Submitted: 3/30/2006 Date Resubmitted: Specification Section: 15900.2.15 Description: Variable Frequency Drives Model: VLT-6000
Supplier info:
Name: Olympic International Agencies Ltd. Address: 344 Harbour Ave, North Vancouver, BC V7J 2E9
Manufacturer info: Name: Danfoss Address: 8800 W. Bradley Road Milwaukee, WI 53224-9541 Website www.grahamdrives.com
houle controls (a div. of houle electric ltd.)
Project: Malaspina College
Contractor: Houle Electric Limited
Customer P.O. TBA Olympic Ref. HP
2- Danfoss Model VLT6000 -575/3/60 - NEMA 3R Enclosure - 5% input line reactor - Input DC Link Reactors - 3 Contactor Manual Bypass - Disconnect - Fuses on drive and bypass - Drive fuses are Semi-conductor rated - 3 year drive warranty
1@ 20 HP 575/3/601@ 40 HP 575/3/60
1 October 2005
600 Volt Qty. Tag Numbers Model VLT Type Nominal
Voltage Max. Amps Output Motor(s) Horsepower/kW
SIDE-BY-SIDE BYPASS and FUSED/DISCONNECT 1 20 HP VLT6000J22 6022 600 22 20 1 40 HP VLT6000J41 6042 600 41 40
Drive Input Power
Input voltage, 3 phase ............................................. 600 VAC
Input voltage range for full output ............................Nominal ±10%
Undervoltage trip point ............................................394 VAC
Overvoltage trip point ..............................................690 VAC
Input frequency........................................................60 Hz, ± 2 Hz
Displacement Power factor......................................0.98 or greater at full load and nominal motor speed
Drive Output Power
Output frequency .....................................................Selectable 0 to 120 Hz
Motor voltages .........................................................575 VAC
Continuous output current .......................................100% rated current
Output current limit setting.......................................Adjustable to 110% of drive rating
Current limit timer ....................................................0 to 60 seconds or infinite
Adjustable maximum speed ....................................From minimum speed setting to 120 Hz
Adjustable minimum speed .....................................From maximum speed setting to 0 Hz
Acceleration time .....................................................To 3,600 seconds to base speed
Deceleration time.....................................................To 3,600 seconds from base speed
Breakaway torque time............................................0.0 to 0.5 seconds (1.6 times motor nameplate current)
Start voltage.............................................................0 to 10%
DC braking time.......................................................0 to 60 seconds
DC braking start.......................................................0 to maximum frequency
DC braking current ..................................................0 to 50% of rated motor current
Control Connections
Follower signal.........................................................0 to 5 V DC, 1 to 5 V DC, 0 to 10 V DC, 2 to 10 V DC, 0 to 20 mA, 4 to 20 mA, direct and inverse acting
Number of programmable digital inputs ..................8
Number of programmable analog inputs .................3; 2 voltage, 1 current
Analog input voltage, current ratings.......................0 to 5 V DC, 1 to 5 V DC, 0 to 10 V DC, 2 to 10 V DC, 0 to 20 mA, 4 to 20 mA, direct and inverse acting
Number of programmable analog outputs...............2
Number of programmable relay outputs..................(1) standard Form A 30 V AC, 1 A, (1) standard Form 240 V AC, 2 A, (1) or (4) additional optional
Auxiliary voltage.......................................................+24 V DC, maximum 200 mA
2 October 2005
Software
Lost speed reference action ....................................Selectable to go to a preset speed, go to maximum speed, stay at last speed, stop, turn off, or stop and trip
Time delay for lost speed reference action .............1 to 99 seconds
Adjustable auto restart time delay ...........................0 to 600 seconds
Automatic restart attempts.......................................0 to 20 or infinite
Automatic restart time delay ....................................0 to 600 seconds between each attempt
Relay ON delay and relay OFF delay......................0 to 600 seconds
Maximum number of preset speeds ........................16
Maximum number of frequency stepovers ..............4
Maximum stepover width.........................................100 Hz
Maximum number of accel rates .............................4
Maximum number of decel rates .............................4
Delayed Start ...........................................................0 to 120 seconds
Environmental limits:
Efficiency .................................................................97% or greater at full load and nominal motor speed
Ambient operating temperature...............................14°F to 104°F (-10°C to 40°C)
Humidity .................................................................< 95%, non-condensing
Altitude: maximum without derating.........................3,300 ft. (1,000 m)
Drive and options enclosure(s)................................NEMA Types 3R
Protections:
Low frequency and high frequency warnings..........0 to 120 Hz
Low current and high current warnings ...................0 to maximum current
Low reference and high reference warnings ...........-999,999 to 999,999
Low feedback and high feedback warnings ............-999,999 to 999,999
Ground fault .............................................................Protected
Motor stall ................................................................Protected
Motor overtemperature ............................................Protected (Predictive motor temperature)
Motor Condensation ................................................Protected (Motor pre-heat circuit)
Agency listing:
All drives and option packages are factory-built and carry UL and C-UL listings.
All drives and option packages are built in ISO 9000 and 14001 certified facilities.
3 October 2005
DRIVE FEATURES - OPERATOR INTERFACE
THE VLT®6000 DRIVE The VLT 6000 Series microprocessor-based, high frequency IGBT-based, PWM AC drive has control functions and software designed solely for the unique needs of HVAC systems. The VLT 6000 drive uses state-of-the-art Voltage Vector Control to supply full-rated motor voltage at rated load and frequency, full motor performance without derating, high efficiency for both drive and motor, and a nearly perfect output sine wave. The diode-bridge rectifier and DC link reactor provide a high displacement power factor at all speeds and loads and minimize power line harmonics. The VLT 6000 drive utilizes a common user interface with a four-line alphanumeric display and a quick setup feature to allow fast, easy installation.
4-Line, 68-Character, Multilingual Alphanumeric Display The VLT 6000 drive uses a large, bright, back-lit liquid crystal display (LCD) to provide complete drive information at a glance. The logical arrangement of all elements simplifies the setup, operation and monitoring of the drive. Choose from 25 different items to display, including input reference, motor current, hours run, output frequency, horsepower, kW or kWh. Or select from custom units, such as GPM or HP and calibrate the maximum value to the maximum frequency of the unit. After programming one drive, the keypad can be used to transfer the same settings to all other drives. Drive can run without the keypad in place to assure tamper-proof operation. Drive status is shown even with the keypad removed.
First Line - 20 Characters Displays up to three measurements (volts, amps, kW, etc.) continuously in normal operating status or the title of the meter shown on the second display line.
Second Line - 8 Characters Continuously shows a measurement (volts, amps, kW, etc.) with relation to the unit, regardless of status (except in the case of alarm/warning).
Third Line - 20 Characters For use in the menu mode to show the selected parameter group, parameter number and name.
Fourth Line - 20 Characters Displays the status (Local, Remote, Run OK, etc.) when in operation or the mode or value of the selected parameter when in the change mode.
LED Indication Three LEDs are provided on the VLT 6000 drive for indication of power applied, warning and fault. Upon power up, all LEDs will briefly light as a lamp test. Alarm - Will flash red when the drive has registered a fault condition which has caused the drive to shut down. Warning - Will flash yellow to indicate a situation exists that exceeds the normal drive/system parameters, and if that condition continues, a trip may be imminent. On - Will glow green to indicate that the VFD is connected to AC power (line voltage is present).
4 October 2005
Operating Keys Hand/Start - Starts the drive regardless of remote start/stop contact (assuming safety interlock is closed). The
speed of the drive will generally be controlled manually via the keypad "+" and "-" buttons. Off/Stop - Shuts drive down regardless of other commands. Auto/Start - Drive will start and stop via the external contact closure (building automation time clock). The speed
is generally controlled via the building automation signal (4 to 20 mA, 0 to 10 V DC, etc.). Reset - Will reset any trip level fault (not trip lock) if the drive is not set for infinite automatic fault resets.
Directional Keys “+/-” - Used as the electronic potentiometer to manually control the speed in the Hand/Start mode. All four keys are active during operation as well as programming. They provide the ability to move the cursor
around the LCD display, or sequence through display values.
Programming Keys Change Data - Used to change the data value of a parameter when programming the drive. Cancel - Used to cancel the last programming command so the change is not carried out. OK - Used to confirm that the last programming change should be saved to memory. Display Mode - Used to select the mode of display and to change from any programming mode back to the
display mode. Quick Menu - Used for programming the VLT 6000 drive using the 12 parameters in the quick setup menu. Can
switch directly between extended menu mode and quick menu mode. Extended Menu - Used to access all parameters for programming. It can switch directly from this mode to quick
menu. PROGRAM OPTIONS
Setup - Application specific The VLT 6000 drive was designed specifically for the HVAC market. This specialization has allowed Danfoss Graham to factory program and configure the VLT 6000 drive to make it ready to use out of the box. This eliminates the time consuming and often confusing job of selecting the right parameters in the field. For the advanced user, the parameters are logically grouped making modifications simple. Customized text (2 lines, 20 characters-first line, 8 characters-second line) can be programmed into the drive using the EIA-485 port.
Quick Menu - Contains the 12 required setup parameters to easily start the application.
Extended Menu – Used to access all parameters for programming. It can switch directly form this mode to quick menu.
Programmable Analog and Digital Inputs and Outputs Three analog (2 voltage, 1 current) and eight digital inputs along with two analog and two relay (1 Form A 30 V AC, 1 A; 1 Form C 240 V AC, 2 A) outputs, all programmable, are standard on the VLT 6000 drive.
5 October 2005
DRIVE FEATURES - MOTOR AND DRIVE INTERACTION Constant Torque Start The VLT 6000 drive provides a constant-torque start mode to provide full torque to accelerate different loads until the drive reaches the set point. Breakaway current can be set up to 160% for up to 0.5 seconds for starting high friction loads Current limit circuit Adjustable from 0 to 110% of the VLT 6000 drive's rated current (factory set at 110%). If during acceleration the current required to accelerate the load exceeds the current limit, the VLT 6000 drive will stop accelerating until the motor current is reduced to normal levels, at which time the load will continue to accelerate at the rate set by the acceleration time. Three phase output current measurement The VLT 6000 drive’s sophisticated software measures output current on all three phases. Phase grounding is instantly detected. Output contactors may be repeatedly used with no damage to the drive. Multiple motors may be run from one drive. Advanced motor protection The VLT 6000 drive features integrated electronic, thermal motor protection. The VFD calculates the motor temperature based on current, frequency, and time. This system allows for changing cooling conditions as speed and load vary. The drive can predict motor over-heating and reports a % of thermal load. Motor Pre-heat circuit This pre-heat function can be activated to avoid condensation on the motor windings when it is stopped. Stall Protection The VLT 6000 drive provides protection against a stalled motor. When activated, this function can provide a warning or a fault condition caused by excessive motor current at low speeds. DRIVE FEATURES DC Link Reactor A dual, 5% DC link reactor on the positive and negative rails of the DC bus is standard equipment on the VLT 6000 drive. This reactor reduces the level of harmonics reflected back into the building power system without causing a voltage loss at the drives input and reducing efficiency as an external AC line reactor would. This reactor also improves input power factor. The reactor is non-saturating (linear) to provide full harmonic filtering throughout the entire load range. In performance, the DC link reactor is equivalent to a 5% AC line reactor Power Line Protection Power line voltage surge protection is provided by means of input Metal Oxide Varistors (MOVs). This protects the diodes in the VLT 6000 drive’s 3-phase full wave diode bridge. The DC link reactor also acts to reduce input current caused by power line disturbances. Sleep Mode Automatically stops the drive when speed drops below set "sleep" level for specified time. Automatically restarts when speed command exceeds set "wake" level. Saves energy and reduces wear on driven equipment. Run Permissive Circuit Ability to accept a "system ready" signal assures that dampers or other auxiliary equipment are in the proper state for drive operation. This feature also provides the ability for the drive to send a “start signal applied” signal to the system to notify the auxiliary equipment of the drive’s request to start. Firefighter’s Override Mode Overrides all other commands to provide desired operation. Ignores most alarms including over load, over current, over temperature, phase loss. When used with bypass, selectable to run from drive, from bypass, or switch from drive to bypass in the event of a drive failure. Acceleration / Deceleration Rates The VLT 6000 drive can provide four individually controlled sets of acceleration/deceleration rates each from 1 to
6 October 2005
3600 seconds. The shape of these curves may be automatically contoured to prevent tripping. Plenum Rated The VLT 6000 NEMA 1 or NEMA 12 drive is recognized by UL for installation in air handling compartments. Auto Restarts The VLT 6000 drive can be automatically restarted up to 20 times or infinitely at 0 to 600 second intervals. If the application causes the drive to trip more than the number of trials set, the drive will stop operating and display the fault on the display screen. A manual reset will be required by means of the reset key, a digital input, or EIA-485 command. In cases of severe trips, as a safety feature, the drive's input power may have to be cycled to restart a fault. Carrier Frequency By using IGBTs, the VLT 6000 drive can employ high switching frequencies, so the motor current is practically sinusoidal. Audible motor noise can also be minimized by adjusting the switching frequency. These frequencies can be set or adjust themselves automatically to fit the application. Input Power
The VLT 6000 drive is equipped with an automatic sustained power or phase loss circuit. The VLT 6000 drive will provide a full rated output with an input voltage as low as 90% of the nominal. The drive will continue to operate with reduced output with an input voltage as low as 164 volts for 208/230 volt units, 313 volts for 460 volt units, and 394 volts for 600 volt units. Automatic Motor Adaptation (AMA) Knowing motor stator resistance, the drive automatically optimizes performance and efficiency. The motor does not have to be run or decoupled from the load for the AMA setup to be performed. Critical Frequency Lockouts For applications where it may be necessary to avoid specific frequencies due to mechanical resonance problems in the driven equipment, the VLT 6000 drive, with its Critical Frequency Lockout Function, makes it possible to set up to four different frequency ranges which will be avoided during operation of the drive.
• Each critical frequency setting can avoid a frequency band which is from 1 to 100 Hz wide. If the
reference signal defines that the VLT 6000 drive is to operate within this critical frequency range, the critical frequency lockout function will keep the drive operating continuously within this range.
• When the frequency reference signal rises above the critical frequency maximum limit, the VLT 6000 drive will allow the motor to accelerate through the critical frequency at the rate set by the acceleration rate.
Automatic Energy Optimization Circuitry The Automatic Energy Optimization (AEO) function adapts the output of the drive to the specific motor and load connected. This circuit optimizes the system efficiency as system loads change. The AEO function regulates the output voltage on the basis of the reactive current and the effective current. A savings of 3 to 10% in power consumption can be obtained with this function. Preset Speeds The VLT 6000 drive allows for a maximum of sixteen programmable preset speeds to be selected from the digital inputs. Proportional Integral Derivative (PID) Setpoint Controller The VLT 6000 drive is equipped with an internal PID Controller. This controller can be used to control pumping, or ventilation applications. The drive uses four inputs. Two set point signals which indicate the desired value of a process variable and two feedbacks of the actual value of the process variable. This could be pressure, flow, temperature, CO2 level, or anything that can be metered in the HVAC environment.
• Proportional: The proportional gain dictates the rate at which the deviation between actual and desired feedback signal is corrected. The higher the gain, the faster the response, but too high a gain can cause hunting and a large overshoot.
• Integral Time: The integral time continually compares the feedback value with the desired set point over time
7 October 2005
to make sure the setpoint is reached. The greater the integral time, the longer it takes to actually achieve the set point, but improves the system stability.
• Derivative: The derivative function monitors the rate at which the feedback is closing on the desired setpoint and slows the rate of approach to prevent overshooting. This function allows rapid accurate system control.
Built-in Communications The VLT 6000 drive is fully equipped for serial communication (EIA-485). Up to 31 drives can be connected to one serial bus up to 5,000 feet long.
Communicates directly with Johnson Controls Metasys (N2), Landis & Staefa System 600 (FLN), and Modbus RTU systems with no hardware changes or additional costs. Broken Belt, Loss of load A minimum motor current value can be set to indicate the motor is not using any more current than to run at idle. This can be used to indicate a broken belt or coupler. This feature can also be used to detect when a motor is disconnected from the drive. WARRANTY
The VLT 6000 drive carries a 36-month on-site warranty from the date of shipment. This warranty includes parts, labor, travel, and expenses.
VLT® 6000 DRIVE OPTIONAL FEATURES Bypass Enclosure
Drive options:
Interlocked Three-contactor Bypass Common Run/Stop Input Disconnect Switch
This bypass consists of a bypass contactor interlocked with a drive output contactor, a drive input contactor, an overload relay and the associated logic circuitry mounted and wired in the auxiliary enclosure. An enclosure mounted drive/off/line/test switch is used to electrically select whether the motor is driven by the drive, the line, or disconnected from both. The input contactor disconnects power automatically when in the "off" and "line" modes.
Includes drive fuses. Requires input fuses. Common run/stop will allow remote run/stop in either drive or bypass mode if specified.
Fusing Input Drive Input fusing fuses the entire panel from the line; drive fusing fuses the drive from the line. .