11
4" AND 6" MODEL RCW WATER CONTROL VALVE FOR DRY, PREACTION AND DELUGE APPLICATIONS Globe is proud to introduce the new Model RCW Water Control Valve for dry pipe, preaction and deluge applications. It is uniquely engineered to minimize many of the field issues historically seen with hydraulically operated differential-style valves. All system types use one common valve body — and its lighter weight and smaller size make it easier and faster to install. 1 VALVE 10 TRIM CONFIGURATIONS One valve comes in 10 different cULus-Listed/FM-Approved trim configurations, lowering your inventory costs. The 4" and 6" RCW is lighter than any other manufacturer’s valve currently on the market. In each trim configuration, it is lighter than other makers’ versions. The RCW has the shortest end-to-end dimensions of any water control valve on the market. Double-seat design means no additional check valve is needed for preaction systems. Single-bolt clapper seal replacement, easy access to hinge pin and minimal bolts for handhole cover removal make the RCW easier to maintain and inspect. Diaphragm-to-clapper latching mechanism uses our unique, patent-pending “roller arm” design, offering lower friction loss and ensuring dependable performance unimpeded by corrosion or debris. SHORTER. LIGHTER. MORE VERSATILE.

SHORTER. LIGHTER....valve currently on the market. In each trim configuration, it is lighter than other makers’ versions. • The RCW has the shortest end-to-end dimensions of any

  • Upload
    others

  • View
    3

  • Download
    0

Embed Size (px)

Citation preview

Page 1: SHORTER. LIGHTER....valve currently on the market. In each trim configuration, it is lighter than other makers’ versions. • The RCW has the shortest end-to-end dimensions of any

4" AND 6" MODEL RCW WATER CONTROL VALVE FOR DRY, PREACTION AND DELUGE APPLICATIONS

Globe is proud to introduce the new Model RCW Water Control Valve for dry pipe, preaction and deluge applications.

It is uniquely engineered to minimize many of the field issues historically seen with hydraulically operated differential-style valves. All system types use one common valve body — and its lighter weight and smaller size make it easier and faster to install.

1 VALVE 10 TRIM CONFIGURATIONS• One valve comes in 10 different cULus-Listed/FM-Approved

trim configurations, lowering your inventory costs.

• The 4" and 6" RCW is lighter than any other manufacturer’s valve currently on the market. In each trim configuration, it is lighter than other makers’ versions.

• The RCW has the shortest end-to-end dimensions of any water control valve on the market.

• Double-seat design means no additional check valve is needed for preaction systems.

• Single-bolt clapper seal replacement, easy access to hinge pin and minimal bolts for handhole cover removal make the RCW easier to maintain and inspect.

• Diaphragm-to-clapper latching mechanism uses our unique, patent-pending “roller arm” design, offering lower friction loss and ensuring dependable performance unimpeded by corrosion or debris.

SHORTER. LIGHTER. MORE VERSATILE.

Page 2: SHORTER. LIGHTER....valve currently on the market. In each trim configuration, it is lighter than other makers’ versions. • The RCW has the shortest end-to-end dimensions of any

As an installer, you need only stock one valve for a variety of different system configurations. The RCW’s compact design makes it lighter and shorter in size than any other comparable valve on the market. This makes installation easier and, often, faster. The completed assembly takes up a smaller footprint in the building. The RCW’s double-seat design means no additional check valve is required. And you are backed by Globe’s renowned customer service and technical support every step of the way.

ONE VALVE. MANY APPLICATIONS.

The Globe RCW Water Control Valve — and each of its trim options — have been engineered to meet the most important needs of both the installer and end user.

The RCW is designed to perform. Its diaphragm-to-clapper mechanism is a unique new design featuring a low-friction roller arm. It uses a positive action spring force to assist movement of the diaphragm away from the clapper when diaphragm chamber water pressure is evacuated. Coupled with the minimal movement of the roller assembly, this results in faster operation on pressure drop and more dependable operation. The robust design allows for free movement of the lever arm assembly, even if debris or corrosion are present.

The RCW is a differential latching valve with a convenient external reset knob. Internal inspections and maintenance are easier, thanks to unique features such as one-bolt clapper seal replacement and easy handhole cover removal. And color-coded handles make it easy to identify, at a glance, if trim valves are in their proper positions.

OPERATION

INSTALLATION

Page 3: SHORTER. LIGHTER....valve currently on the market. In each trim configuration, it is lighter than other makers’ versions. • The RCW has the shortest end-to-end dimensions of any

External reset

Patent-pending low-resistance roller arm

The Globe RCW Valve is available pre-trimmed or loose-trimmed in the following system configurations:

Dry System

• Available with Standard or Low Pressure Actuator

• Optional Accelerator

Deluge System

• Electric Actuation

• Dry Pilot Actuation

• Wet Pilot Actuation

Single Interlock Preaction System

• Electric Actuation

• Dry Pilot Actuation

• Wet Pilot Actuation

Double Interlock Preaction System

• Electric/Electric Actuation

• Electric/Pneumatic Actuation

- Available with Standard or Low Pressure Actuator

Non Interlock Preaction System

Easy access hinge pin

Page 4: SHORTER. LIGHTER....valve currently on the market. In each trim configuration, it is lighter than other makers’ versions. • The RCW has the shortest end-to-end dimensions of any

DRY SYSTEMS

Dry Pipe Systems

Dry pipe sprinkler systems are typically used in unheated areas and other locations exposed to freezing temperatures, where water-filled pipe cannot be used. When set for service, a dry pipe sprinkler system incorporating automatic sprinklers (closed) is pressurized with air or nitrogen. In response to heat from a fire, an operated automatic sprinkler causes a loss of air pressure and permits the dry pipe valve to open. This allows a flow of water into the sprinkler system piping.

Dry systems are used in any unheated portion of a building:

• Warehouses

• Loading Docks

• Unheated Attic Spaces

• Shipping Platforms

• Cold Storage

• Parking Garages

• Outdoor Piers

• Unheated Attic Spaces

Robert C. Worthington was a pioneer in fire sprinkler system engineering, with a long and successful career before he purchased Globe in 1988. Mr. Worthington made a commitment to producing a high-quality product in the U.S. This valve is named in honor of his spirit of innovation and his life-long dedication to saving lives and protecting property from fire.

IN HONOR OF

Robert C. Worthington, PE

RCW

Page 5: SHORTER. LIGHTER....valve currently on the market. In each trim configuration, it is lighter than other makers’ versions. • The RCW has the shortest end-to-end dimensions of any

DELUGE SYSTEMS

SINGLE INTERLOCK PREACTION SYSTEMS

Deluge systems are used for special hazards where there are easily ignitable and fast-burning substances which promote rapid fire development. They are typically used for fire extinguishment, fire control or exposure protection in applications such as:

Single interlock preaction systems are used in any portion of a building where it is undesirable to have water-filled pipes over the hazard being protected. Such systems typically employ air or nitrogen under pressure, with a supplemental detection system installed in the same area as the sprinkler system.

• With materials having high rates of heat release

• Conveyors

• Water Curtains

• Fuel Storage Tanks

• Electrical Transformers

• Aircraft Hangars

• Chemical Plants

Electric Actuation

Single Interlock Electric Actuation

Dry Pilot Actuation

Single Interlock Dry Pilot Actuation

Wet Pilot Actuation

Single Interlock Wet Pilot Actuation

These valves are activated by a single event, an electrical detector activation, an activation of a pilot sprinkler connected to pilot lines under air pressure (dry pilot), or an activation of a pilot sprinkler connected to pilot lines under water pressure (wet pilot). They are commonly used in:

• Computer Rooms

• Archives• Libraries

• Document Storage Centers

Page 6: SHORTER. LIGHTER....valve currently on the market. In each trim configuration, it is lighter than other makers’ versions. • The RCW has the shortest end-to-end dimensions of any

Double interlock preaction systems are used in any portion of a building where flooding or inadvertent discharge of water would be especially damaging. These valves are activated by two separate events: an electric activation plus a sprinkler activation.

In the case of Electric/Pneumatic Actuation, a detector activation sends an electrical signal to the release panel, opening a solenoid valve. This event would typically be followed by a sprinkler activation, releasing air pressure in the sprinkler piping, allowing the pneumatic actuator to open, and tripping the RCW valve.

The simplicity and versatility of the Globe RCW make it an excellent choice for every application. With it, it’s truly “one and done.”

To learn more about the Globe RCW Water Control Valve, contact your local Globe territory manager, contact our customer service team at (989) 846-4583 or visit globesprinkler.com/RCW.

DOUBLE INTERLOCK PREACTION SYSTEMS

In the case of Electric/Electric Actuation, a detector activation will send the first electrical signal to the release panel. The activation of a sprinkler will allow air pressure in the sprinkler piping to escape, activating a low air pressure switch. This sends a second signal to the release panel, which opens the solenoid valve, tripping the RCW valve. They are commonly used in applications such as:

• Freezers

• Valuable Archives

• Critical Document Storage

Double Interlock Electric/Pneumatic Actuation

Double Interlock Electric/Electric Actuation

AND DONE!

Page 7: SHORTER. LIGHTER....valve currently on the market. In each trim configuration, it is lighter than other makers’ versions. • The RCW has the shortest end-to-end dimensions of any

Approvals: cULus and FM

Maximum System Working Pressure: 300 psi (20.6 bar)

Materials of Bonstruction: See Table Below

Model RCW Cross-Section

4" (DN100) Valve 13.13" (333,5 mm)

4" (DN100) Valve w/ Model GLR300G 17.66" (448,5 mm)

6" (DN150) Valve 14.47" (367,5 mm)

6" (DN150) Valve w/ Model GLR300G 19.69" (500 mm)

ITEM DESCRIPTION MATERIAL

1 “RCW-2” Body (groove/groove) Ductile Iron

2 Seat Ring Bronze

3 Clapper Bronze

4 Retaining Ring Stainless

5 Retaining Bolt Steel

6 Clapper Facing Disc EPDM

7 Latch Arm Bronze

8 Clapper Latch Bronze

9 Reset Plunger Bronze

10 Push Rod Bronze

11 Roller Stainless

12 Diaphragm Retainer Ductile Iron

13 Diaphragm Rubber

14 Diaphragm Cover Ductile Iron

15 Clapper Hinge Pin Stainless

16 Clapper Hinge Pin Bushing Bronze

17 Handhole Cover Gasket Rubber

18 Handhole Cover Ductile Iron

19 Diaphragm Spring Stainless

20 Reset Bushing Bronze

21 Cover Bolt Steel

22 Clapper Latch Hinge Pin Stainless

23 Roller Arm Hinge Pin Stainless

24 Roller Arm Hinge Pin Clip Stainless

25 Reset Plunger Knob Bronze

26 Plunger O-Ring Rubber

27 Name Plate Aluminum

28 Return Spring Stainless

29 Reset Plunger Spring Stainless

30 Roller Bushing Bronze

31 1/2" NPT Plug Steel

32 Drive Screw Stainless

33 Clapper Latch Bushing Bronze

TECHNICAL SPECIFICATIONS

Take out dimensions (end to end):

21

16

2424

17

32

18

16

27

31

1

A A

B B

4

4

3

3

2

2 1

23

4

28

8

26

10

19

21

22

31

34

11

15

9

20

30

6

14

25

12

13

5

7

29

2

33

21

16

2424

17

32

18

16

27

31

1

A A

B B

4

4

3

3

2

2 1

23

4

28

8

26

10

19

21

22

31

34

11

15

9

20

30

6

14

25

12

13

5

7

29

2

33

Page 8: SHORTER. LIGHTER....valve currently on the market. In each trim configuration, it is lighter than other makers’ versions. • The RCW has the shortest end-to-end dimensions of any

© 2017 Globe Fire Sprinkler Corporation. All Rights Reserved.

Customer Service

989-846-4583 [email protected] [email protected]

Technical Support

989-414-2600 [email protected]

globesprinkler.com

Page 9: SHORTER. LIGHTER....valve currently on the market. In each trim configuration, it is lighter than other makers’ versions. • The RCW has the shortest end-to-end dimensions of any

JUNE 2017 GFV-200 (Formerly H-1) PAGE 1 OF 3

GENERAL DESCRIPTIONThe Globe Model RCW* Water Control Valve is a hydrau-lically operated external resetting differential latching style valve designed for use where quick-opening and total flood-ing of sprinkler system piping is desired. It is used as an automatic water control valve in Deluge, Dry Pipe, or Preac-tion systems, as well as foam-water sprinkler systems.Setting of the Model RCW Valve requires water pressure in the diaphragm chamber provided via a connection from the main water supply from a point upstream of the system main control valve, through a restricted orifice. Water pressure on the diaphragm is transferred to the plunger rod which forces the roller arm mechanism against the clapper, preventing the supply water from entering the sprinkler system piping. Actuation (tripping) of the Model RCW Valve is accom-plished by releasing water from downstream of the re-stricted orifice. Water pressure release can be caused by a va-riety of types of actuation trim and devices. For example the supply can be fed to a line of wet pilot sprinklers for wet pilot type Deluge or Preaction systems. Other devices which can be used for valve actuation include a dry pilot actuator, or an electric solenoid valve with an as-sociated releasing control panel.

TECHNICAL DATAApprovals• cULus• FM

Note: When trimmed in accordance with Technical Literature:

1 GFV-205- Deluge System Technical Data Sheet2 GFV-305- Dry System Technical Data Sheet3 GFV-400- Single Interlock Preaction Technical Data Sheet4 GFV-410- Double Interlock Preaction Technical Data Sheet5 GFV-420- Non Interlock Preaction Technical Data Sheet

Maximum System Working Pressure• 300 psi (20.6 Bar)

Materials of Construction• See Figure 1

Friction Loss Information• See Figure 2 for Friction Loss Data

4" (DN100) Valve 13.13" (333,5mm)

4" (DN100) Valve w/ Model GLR300G 17.66" (448,5mm)

6" (DN150) Valve 14.47" (367,5mm)

6" (DN150) Valve w/ Model GLR300G 19.69" (500mm)

Note: Take Out Dimensions (End to End)

*Patents Pending

MAINTENANCENote:• All valves should be carefully inspected, tested, and

maintained in accordance with NFPA 25 or other applicable Standard.

• It is important to ensure a clean water supply free of debris and solid particles such as sand, gravel, or mud.

• If, during an inspection of a water control valve, sediment or free particles of matter are noted, a further examination of internal valve parts is necessary.

• All valves should be carefully inspected, tested, and maintained in accordance with NFPA 25 or other applicable Standard.

• It is important to ensure a clean water supply free of debris and solid particles such as sand, gravel, or mud.

• If, during an inspection of a water control valve, sediment or free particles of matter are noted, a further examination of internal valve parts is necessary.

• All deposits should be removed from all operating parts and ports. Vent holes through intermediate chamber should be thoroughly cleaned and flushed with clean water.

MODEL RCW FLOW CONTROL VALVE

MODEL RCW FLOW CONTROL VALVE

MODEL RCW FLOW CONTROL VALVE MODEL RCW FLOW CONTROL VALVEGFV-200 (Formerly H-1)

GFV-200 (Formerly H-1)

4077 Airpark Dr. Standish, MI 48658 • 989-846-4583 • www.globesprinkler.comTechnical Support • 989-414-2600 • [email protected]

Page 10: SHORTER. LIGHTER....valve currently on the market. In each trim configuration, it is lighter than other makers’ versions. • The RCW has the shortest end-to-end dimensions of any

JUNE 2017 GFV-200 (Formerly H-1) PAGE 2 OF 3

28

29

19

11

6

2

10

SECTION A-A

1

13

27

14

15

7

9

24

12

23

26

20

3

5

33

8

30

34

4

31

A A

16

35

17

18

22

21

25

32

AA

1

2

3

4

5

6

15

24 19

7

30

8

2320

3427

9

31

26

12

33

1410

13

36

REV. REVISION DATE BY APR

REVISIONS

317400 FOR JOHN

SHEET 1 OF 1SCALE: NOT TO SCALE

4077 AIRPARK DRIVESTANDISH, MI 48658

METRIC UNITS SHOWN IN BRACKETS, DUE TO THE CONVERSION, METRIC VALUESMAY BE APPROXIMATE. LIMITS ON: FRACTIONS 1/64 [.4mm];

2 PLC. DEC. .010 [ .3mm]; 3 PLC. DEC .005 [ .1mm]; ANGLES 1/2

DR.BY: APR. BY:

SECTION VIEW ISOMETRIC VIEW

FIGURE 1:MODEL RCW MATERIALS OF CONSTRUCTION

NOTE: SOME PARTS ARE NOT FIELD SERVICEABLE, CONTACT CUSTOMER SERVICE FOR AVAILABILITY

ITEM DESCRIPTION MAT'L.4"

[100mm]P/N

6" [150mm]

P/NITEM DESCRIPTION MAT'L.

4" [100mm]

P/N

6" [150mm]

P/N

1 RCW BODY DI SEE ORDERING INFORMATION 19 CLAPPER BRONZE 317403 317462

2 MACHINED SEAT RING BRASS 317421 317467 20 RESET BUSHING BRASS 317406 317469

3 DIAPHRAGM TAPER SPRING STAINLESS 317432 317432 21 HEX HEAD CAP SCREW,

1/2-13 STEEL 3174331 IN

3175531.5 IN

4 CLAPPER RETAINER PLATE STAINLESS 317417 317470 22 TOP ARM BUSHING BRONZE 317411 317548

5 HEX HEAD CAP SCREW 1/2-13 X .75 STAINLESS 317552 317552 23 TOP ARM PIN STAINLESS 317412 317472

6 CLAPPER GASKET EPDM 317416 317547 24 ROLLER ARM PIN STAINLESS 317409 3174747 ROLLER ARM BRONZE 317413 317466 25 ROLLER PIN E-CLIP STAINLESS 317427 3174798 RCW CLAPPER LATCH BRONZE 317422 317422 26 RESET PLUNGER KNOB BRONZE 317407 3174079 RESET PLUNGER BRONZE 317408-4 317408-6 27 PLUNGER 0-RING EPDM 317436 317436

10 PUSH ROD BRONZE 317423 317468 28 NAME PLATE STAINLESS 317428 31742811 ROLLER STAINLESS 317410 317478 29 DRIVE SCREW STEEL 323420 32342012 DIAPHRAGM RETAINER BRONZE 317420 317465 30 LATCH RETURN SPRING STAINLESS 317425 31742513 DIAPHRAGM EPDM 317404 317477 31 RESET PLUNGER SPRING STAINLESS 317426 31742614 DIAPHRAGM COVER DI 317405 317463 32 1/2" NPT PIPE PLUG STEEL 311003 31100315 CLAPPER HINGE PIN STAINLESS 317415 317475 33 ROLLER BUSHING BRONZE 317424 317482

16 CLAPPER HINGE PIN BUSHING BRONZE 317414 317414 34 PLUNGER BUSHING

0-RING, #2-014 EPDM 317435 317435

17 COVER GASKET EPDM 317419 317473 35 1/2-13 HEX HEAD CAP SCREW (COVER BOLTS) STEEL 317564

1 IN3175511.25 IN

18 MACHINED HAND HOLE COVER DI 317418 317464 36 RESET PLUNGER END BRONZE 317378 317378

• Where difficulty in performance is experienced, the manufacturer or its authorized representative shall be contacted before any field adjustment is to be made.

Clapper Facing. The rubber clapper facing should be checked for wear or damage to determine that it is free of dirt and other foreign substances. If found to be worn or

damaged (e.g., foreign matter embedded in the surface), the facing should be replaced. If it is dirty, it should be cleaned. Compounds which could damage the rubber fac-ing must never be used.Seat Ring. The seat ring should be checked for nicks and for stones, dirt or other foreign matter lodged in the grooves or holes. It should be cleaned thoroughly. If the seat ring is found to be damaged, valve should be replaced.

Page 11: SHORTER. LIGHTER....valve currently on the market. In each trim configuration, it is lighter than other makers’ versions. • The RCW has the shortest end-to-end dimensions of any

JUNE 2017 GFV-200 (Formerly H-1) PAGE 3 OF 3

FIGURE 2:FRICTION LOSS CURVES

The approximate friction loss, based on the hazen- williams formula; expressed in equivalent length of pipe with c=120, is as follows:

1 11 Ft (3,35 m) of equivalent length of schedule 40 4" (DN100) piping for 4" (DN100) valve2 42 Ft (12,8 m) of equivalent length of schedule 40 6" (DN150) piping for 6" (DN150) valve

4" (D

N100)

6" (D

N150)

Alarm Line Check Valve. The ¾” check valve connected to the intermediate chamber should be checked for clapper and seat condition.RCW Valve. Main Drain Valve and all controlling valves which are normally closed when the deluge valve is in the set position should be checked to be sure that they are fully closed and not leaking.

TESTING / INSTALLATIONSee appropriate system Technical Literature for Testing and Installation Instructions.

ORDERING INFORMATIONRCW Water Control Valve (Groove X Groove)Specify: RCW-2 Valve Only (specify valvesize), PN4 inch RCW GxG . . . . . . . . . . . . 3174006 inch RCW GxG . . . . . . . . . . . . 317550DN 150 (165,1 mm) RCW GXG . . . . 317550-D

GLOBE® PRODUCT WARRANTYGlobe agrees to repair or replace any of its own manufac-tured products found to be defective in material or work-manship for a period of one year from date of shipment.For specific details of our warranty please refer to Price List Terms and Conditions of Sale (Our Price List).

4077 Airpark Dr. Standish, MI 48658 Ph. 989-846-4583

Technical Support 1-800-248-0278

[email protected]