Trip Unit
Closing Push Button
Opening Push Button
Bus Connector
Motor Operator
Charging Handle
Auxiliary Switch
Lifting Tab
Arc Chamber
Lock Out
Secondary Block
Secondary Block
Rating Plug
Push-to-reseton Fault Trip
Accessory Label
Catalog Number
Accessory Cover
Mounting Plate forFixed Circuit Breaker
Trip Unit Battery
Charged/ DischargedIndicatorOpen/ CloseIndicator
Shunt Trip
1.800.476.1486www.southlandelectrical.com
WL
SiemensWL Insulated Case Breaker
ETU725
ETU for WL Series
Overload Protection (Long-Time)
Short-time delayed short circuit protection
Instaneous short-circuit protection
ETU725
ETU725 = Basic Protection
ETU727 = Basic Protection
ETU745 = Basic Protection with Metering/ Communication
ETU748 = Basic Protection with Metering/ Communication
ETU755 = Advanced Protection with Metering/ Communication
ETU727 ETU745 ETU748
ETU727 ETU745 ETU748
ETU745
ETU725 ETU727 ETU745 ETU748
Protection of neutral conductor
Ground fault protection
ZSI (Zone-Selective Interlocking)
LCD 4 lines
Communication via MODBUS or PROFIBUS
Metering Functions
Parameters programmable via communications or locally
ETU727 ETU745 ETU748
ETU725
ETU725 ETU727
ETU727
ETU727
ETU745
ETU745
ETU745
ETU745
ETU745
ETU745
ETU748
ETU748
ETU748
ETU748
ETU748
ETU748
ETU748
WL
SiemensWL Accessory Parts
1.800.476.1486www.southlandelectrical.com
Shunt Trip Part Numbers - Opening Coil Part Numbers
WLST24 24 VDCWLSTC WLST48 48 VDC WLST120 120 VAC
Undervoltage Release Part Numbers
WLUV24 24 VDC
MUVRR 208-240 VAC
WLUV48 48 VDC
MUVRH 48 VDC
WLUV120 120 VAC
MUVRX 380-415 VAC
WLUV240 240VAC
Locking Device Part Numbers
Operating Motor Part Numbers
WLST240 240 VAC WLSTCD24 24 VAC WLSTCD48 48 VDC WLSTCD120 120 VAC
WLSTCD240 240 VAC
Rating Plug Part Numbers
WLELCMTR24 24VDC WLELCMTR48 48 VDC WLELCMTR120 120 VAC WLELCMTR240 240 VAC
WLELCMTR24S 24 VDC WLELCMTR48S 48 VDC WLELCMTR120S 120 VDC WLELCMTR240S 120 VDC
WLRP200 200A WLRP225 225A WLRP250 250A WLRP300 300A
WLRP315 315A WLRP350 350A WLRP400 400A WLRP450 450A
WLRP500 500A WLRP600 600A WLRP700 700A WLRP800 800A
WLRP1000 1000A WLRP1200 1200A WLRP1250 1250A WLRP1600 1600A
WLRP2000 2000A WLRP2500 2500A WLRP3000 3000A WLRP3200 3200A
WLRP4000 4000A WLRP5000 5000A
WLHANDLC WLLKOFFPR WLLKOFFKRK WLLKOFFSUP
WLLKNP WLLKCLKRK1 WLLKCLKRK WLLKCLSUP1
WLLKCLSUP WLLKCKPR
1.800.476.1486www.southlandelectrical.com
WL
SiemensWL Accessory Parts
Rear Vertical Bus Connector Part Numbers
Arc Chute Part Numbers
WLH1R12CONUL
WLC2R30CONUL
WLL2R16CON
WLC3R50CONUL
WLL2R16CON WLL2R30CONUL
WLARC2 WLARC3 WLARCM3
Secondary Disconnect Part Numbers
WLGAUXPLUGP
WLCNMD
WLGAUXPLUGT WLGAUXPLUGR WLGAUXPLUGL
Auxiliary Switch Part Numbers
WLAS2 WLAS4
Closing Coil Part Numbers
WLRCS24 WLRCS48 WLRCS120 WLRCS240
Ground-Fault Part Numbers
WLGFA48 WLGFM48 WLGFA76 WLGFM76
WL
SiemensWL Accessory Parts
1.800.476.1486www.southlandelectrical.com
7.5[190,5]
3.75[95,3]
.39[10]
9.5[241,4]
5.0[127]
5.12[130,0]
5.12[130,0]
14.5[368,4]
1.18[30,0]
Dimensions:in.[]mm
TOP VIEW
SIDE VIEW
Fixed WL Breaker Master Drawing
1.800.476.1486www.southlandelectrical.com
WL
SiemensWL Dimensional Drawing
*Other dimensionaldrawings available
upon request
Type
1st/2nd Description
WL 800-5000A
Inte
rrup
t
3rd Description
N 50kA@240/480/600V
S 65kA@240/480/600V
H 85kA@240/480/600V(FSIII),
65kA@600V(FSI/FSII)
L 100kA@240/480V,85kA@600V(FSII/FSIII),65kA@600V
(FSI)
M 150kA@240/480V,85kA@600V
C 150kA@240/480V,100kA@600V
F 200kA@240/480V,600V(w/fuses)
Fram
e S
ize
4th Description
1 Frame Size I (FSI)
2 Frame Size II (FSII)
3 Frame Size III (FSIII)
Rat
ing/
Mou
nt
5th Description
A ANSI(UL1066)Draw-Out Mount
S ANSI(UL1066)Draw-Out
Non-Automatic Switch
F UL 489 Fixed Mount
D UL489 Draw-Out
Y UL489 Fixed Mount Non-Automatic
Switch
Z UL489 Draw-Out Non-Automatic
Switch
Pol
e 6th Description
3 3 Pole
Fram
e A
mp
7th/8th Description
08 800 Amp (FSI/FSII)
12 1200 Amp (FSI/FSII)
16 1600 Amp (FSII)
20 2000 Amp (FSII)
25 2500 Amp (FSII)
30 3000 Amp (FSII)
32 3200 Amp (FSII/FSIII)
40 4000 Amp (FSIII)
50 5000 Amp (FSIII)
Shu
nt T
rip
12th Description
X None
A 24Vdc Shunt
B 48Vdc Shunt
C 120Vac/125Vdc Shunt
D 240Vac/250Vdc Shunt
E 24Vdc Shunt/1N.O. Signal Contact
F 48Vdc Shunt/1N.O. Signal Contact
G 120Vac/125Vdc Shunt/1N.O. Signal Contact
H 240Vac/250Vdc Shunt/1N.O. Signal Contact
J 24Vdc Interlock Shunt
K 48Vdc Interlock Shunt
L 120Vac/125Vdc Interlock Shunt
M 240Vac/250Vdc Interlock Shunt
N 24Vdc Interlock Shunt/1N.O.Signal Contact
P 48Vdc Interlock Shunt/1N.O.Signal Contact
R 120Vac/125Vdc Interlock Shunt/1N.O.Signal Contact
S 240Vac/250Vdc Interlock Shunt/1N.O.Signal Contact
Rat
ing
Plu
g
9th Description
S Switch
A 200 Amp(FSI/FSII)
B 225 Amp(FSI/FSII)
C 250 Amp(FSI/FSII)
D 300 Amp(FSI/FSII)
E 315 Amp(FSI/FSII)
F 350 Amp(FSI/FSII)
G 400 Amp(FSI/FSII)
H 450 Amp(FSI/FSII)
J 500 Amp(FSI/FSII)
K 600 Amp(FSI/FSII)
L 630 Amp(FSI/FSII)
M 700 Amp(FSI/FSII)
N 800 Amp(FSI/FSII/FSIII)
P 1000 Amp(FSI/FSII/FSIII)
Q 1200 Amp(FSI/FSII/FSIII)
R 1250 Amp(FSII/FSIII)
T 1600 Amp(FSII/FSIII)
U 2000 Amp(FSII/FSIII)
V 2500 Amp(FSII/FSIII)
W 3000 Amp(FSII/FSIII)
Y 3200 Amp(FSII/FSIII)
Z 4000 Amp(FSIII)
1 5000 Amp(FSIII)
Sig
nalin
g
11th Description
X None
A Bell Alarm
B Ready To Close
C 2 N.O./2 N.C. Auxiliary Contact
D 4 N.O./4 N.C. Auxiliary Contact
E Bell Alarm, Ready To Close
F Bell Alarm, 2 N.O./2 N.C. Auxiliary Contact
G Bell Alarm, 4 N.O./4 N.C. Auxiliary Contact
H Ready To Close, 2 N.O./2 N.C. Auxiliary Contact
I Ready To Close, 4 N.O./4 N.C. Auxiliary Contact
J Bell Alarm, Ready To Close, 2 N.O./2 N.C. Auxiliary Contact
K Bell Alarm, Ready To Close, 4 N.O./4 N.C. Auxiliary Contact
L 24Vdc Remote Reset,Bell Alarm
M 48Vdc Remote Reset,Bell Alarm
N 120Vac/125Vdc Remote Reset,Bell Alarm
O 240Vac/250Vdc Remote Reset,Bell Alarm
P 24VDC Remote Reset, Bell Alarm, Ready To Close
Q 48VDC Remote Reset, Bell Alarm, Ready To Close
R 120/125VAC/DC Remote Reset, Bell Alarm, Ready To Close
S 240/250VAC/DC Remote Reset, Bell Alarm, Ready To Close
T 24VDC Remote Reset, Bell Alarm, 2 N.O./2 N.C. Auxiliary Contact
U 48Vdc Remote Reset,Bell Alarm,2N.O./2N.C. Aux
V 120Vac/125Vdc Remote Reset,Bell Alarm,2N.O./2N.C. Aux
W 240Vac/250Vdc Remote Reset,Bell Alarm,2N.O./2N.C. Aux
Y 24Vdc Remote Reset,Bell Alarm,4N.O./4N.C. Aux
Z 48Vdc Remote Reset,4N.O./4N.C. Aux
1 120Vac/125Vdc Remote Reset,Bell Alarm,4N.O./4N.C. Aux
2 240Vac/250Vdc Remote Reset,Bell Alarm,4N.O./4N.C. Aux
3 24Vdc Remote Reset,Bell Alarm,RT-C,2N.O./2N.C. Aux
4 48VDC Remote Reset, Bell Alarm, Ready To Close, 2 N.O./2 N.C. Auxiliary Contact
5 120/125VAC/DC Remote Reset, Bell Alarm, Ready To Close, 2 N.O./2 N.C. Auxiliary Contact
6 240/250VAC/DC Remote Reset, Bell Alarm, Ready To Close, 2 N.O./2 N.C. Auxiliary Contact
7 24VDC Remote Reset, Bell Alarm, Ready To Close, 4 N.O./4 N.C. Auxiliary Contact
8 48VDC Remote Reset, Bell Alarm, Ready To Close, 4 N.O./4 N.C. Auxiliary Contact
9 120/125VAC/DC Remote Reset, Bell Alarm, Ready To Close, 4 N.O./4 N.C. Auxiliary Contact
0 240/250VAC/DC Remote Reset, Bell Alarm, Ready To Close, 4 N.O./4 N.C. Auxiliary Contact
Trip
Uni
t
10th Description
S Non-Auto Switch
A ETU725(LSI)
B ETU727(LSIG)
C ETU745(LSI)
D ETU745(LSI/Display)
E ETU745(LSIA)
F ETU745(LSIA/Display)
G ETU745(LSIG)
H ETU745(LSIG/Display)
J ETU748(LS)
K ETU748(LS/Display)
L ETU748(LSA)
N ETU748(LSA/Display)
P ETU748(LSG)
Q ETU748(LSG/Display)
R ETU755(LSI)
T ETU755(LSIA)
U ETU755(LSIG)
V ETU776(LSI)
W ETU776(LSIA)
Y ETU776(LSIG)
WL L 2 F 3 12 Q C C X1st/2nd 3rd 4th 5th 6th 7th/8th 9th 10th 11th 12th
WL
X X X A N13th 14th 15th 16th 17th
Und
ervo
ltage
Rel
ease
13th Description
X None
A 24Vdc UVR
B 48Vdc UVR
C 120Vac/125Vdc UVR
D 240Vac/250Vdc UVR
E 48Vdc UVR/Delay
F 120Vac/125Vdc UVR/Delay
G 240Vac/250Vdc UVR/Delay
H 24Vdc 2nd Shunt
J 48Vdc 2nd Shunt
K 120Vac/125Vdc 2nd Shunt
L 240Vac/250Vdc 2nd Shunt
M 24Vdc UVR,2nd Shunt(Interlock)
N 48Vdc UVR,2nd Shunt(Interlock)
P 120Vac/125Vdc UVR,
2nd Shunt(Interlock)
Q 240Vac/250Vdc UVR,
2nd Shunt(Interlock)
R 48Vdc UVR/Delay,2nd Shunt(Interlock)
S 120Vac/125Vdc UVR/Delay,
2nd Shunt(Interlock)
T 240Vac/250Vdc UVR/Delay,
2nd Shunt(Interlock)
U 24Vdc 2nd Shunt,2nd Shunt(Interlock)
V 48Vdc 2nd Shunt,2nd Shunt(Interlock)
W 120Vac/125Vdc 2nd Shunt,
2nd Shunt(Interlock)
Y 240Vac/250Vdc 2nd Shunt,
2nd Shunt(Interlock)
Z 2nd Shunt(Interlock)
1 2nd Shunt(Interlock)
2 2nd Shunt(Interlock)
3 2nd Shunt(Interlock)
4 2nd Shunt(Interlock),Signal Contact
5 2nd Shunt(Interlock),Signal Contact
6 2nd Shunt(Interlock),Signal Contact
7 2nd Shunt(Interlock),Signal Contact
Mot
or O
pera
tor
14th Description
X None
A 24Vdc Mtr Oper
B 48Vdc Mtr Oper
C 120Vac/125Vdc Mtr Oper
D 240Vac/250Vdc Mtr Oper
E 24Vdc Mtr Oper,Mtr Cut Off
F 48Vdc Mtr Oper,Mtr Cut Off
G 120Vac/125Vdc Mtr Oper,Mtr Cut Off
H 240Vac/250Vdc Mtr Oper,Mtr Cut Off
J 24Vdc Mtr Oper,Oper Cntr
K 48Vdc Mtr Oper,Oper Cntr
L 120Vac/125Vdc Mtr Oper,Oper Cntr
M 240Vac/250Vdc Mtr Oper,Oper Cntr
N 24Vdc Mtr Oper,Mtr Cut Off,Oper Cntr
P 48Vdc Mtr Oper,Mtr Cut Off,Oper Cntr
Q 120Vac/125Vdc Mtr Oper,Mtr Cut Off,Oper
Cntr
R 240Vac/250Vdc Mtr Oper,Mtr Cut Off,Oper
Cntr
S 24Vdc Mtr Oper,LEC Sealable
T 48Vdc Mtr Oper,LEC Sealable
U 120Vac/125Vdc Mtr Oper,LEC Sealable
V 240Vac/250Vdc Mtr Oper,LEC Sealable
W LEC Sealable
2 24Vdc Mtr Oper,Oper Cntr,LEC Sealable
3 48Vdc Mtr Oper,Oper Cntr,LEC Sealable
4 120Vac/125Vdc Mtr Oper,Oper Cntr,LEC
Sealable
5 240Vac/250Vdc Mtr Oper,Oper Cntr,LEC
Sealable
Com
mun
icat
ions
15th Description
X None
A 24Vdc Remote Close
B 48Vdc Remote Close
C 120Vac/125Vdc Remote Close
D 240Vac/250Vdc Remote Close
F Metering Function Plus
G MODBUS COM 16
H PROFIBUS COM 15
L Metering Function Plus,MODBUS COM 16
M Metering Function Plus,PROFIBUS COM 15
N 24Vdc Remote Close,MODBUS COM 16
P 24Vdc Remote Close,PROFIBUS COM 15
Q 24Vdc Remote Close,Metering Func Plus,MODBUS COM 16
R 24Vdc Remote Close,Metering Func Plus,PROFIBUS COM 15
S 48Vdc Remote Close,MODBUS COM 16
T 48Vdc Remote Close,PROFIBUS COM 15
U 48Vdc Remote Close,Metering Func Plus,MODBUS COM 16
V 48Vdc Remote Close,Metering Func Plus,PROFIBUS COM 15
W 120Vac/125Vdc Remote Close,-MODBUS COM 16
Y 120Vac/125Vdc Remote Close,-PROFIBUS COM 15
Z 120Vac/125Vdc Remote Close,Me-tering Function Plus,MODBUS
COM 16
1 120Vac/125Vdc Remote Close,Me-tering Function Plus,PROFIBUS
COM 15
2 240Vac/250Vdc Mtr Oper,Oper Cntr,LEC Sealable
3 240Vac/250Vdc Remote Close,-PROFIBUS COM 15
4 240Vac/250Vdc Remote Close,Me-tering Function Plus,MODBUS
COM 16
5 240Vac/250Vdc Remote Close,Me-tering Function Plus,PROFIBUS
COM 15
6 24Vdc Remote Close,Metering Function Plus
7 48Vdc Remote Close,Metering Function Plus
8 120Vac/125Vdc Remote Close,Me-tering Function Plus
9 240Vac/250Vdc Remote Close,Me-tering Function Plus
Lock
ing
16th Description
X None
A kirk Key
B Padlock
C Lock Kit
D Rack Handle Lock
E Charge Handle Lock
F kirk Key,Padlock
G kirk Key,Lock Kit
H Padlock,Lock Kit
J kirk Key,Padlock,Lock Kit
K kirk Key,Rack Handle Lock
L Padlock,Rack Handle Lock
M kirk Key,Padlock,Rack Handle Lock
N Lock Kit,Rack Handle Lock
P kirk Key,Lock Kit,Rack Handle Lock
Q Padlock,Lock Kit,Rack Handle Lock
R kirk Key,Padlock,Lock Kit,Rack Handle Lock
S kirk Key,Charge Handle Lock
T Padlock,Charge Handle Lock
U kirk Key,Padlock,Charge Handle Lock
V Lock Kit,Charge Handle Lock
W kirk Key,Lock Kit,Charge Handle Lock
Y Padlock,Lock Kit,Charge Handle Lock
Z kirk Key,Padlock,Lock Kit,Charge Handle Lock
1 Rack Handle Lock,Charge Handle Lock
2 kirk Key,Rack Handle Lock,Charge Handle Lock
3 Padlock,Rack Handle Lock,Charge Handle Lock
4 kirk Key,Padlock,Rack Handle Lock,Charge Handle Lock
5 Lock Kit,Rack Handle Lock,Charge Handle Lock
6 kirk Key,Lock Kit,Rack Handle Lock,Charge Handle Lock
7 Padlock,Lock Kit,Rack Handle Lock,Charge Handle Lock
8 kirk Key,Padlock,Lock Kit,Rack Handle Lock,Charge Handle Lock
Oth
er 17th Description
N No Additional Components
WL
1.800.476.1486www.southlandelectrical.com