61
UTRAN Installation Node B IMN:NB-440 A50016-G5000-C229-5-7631 ND-57356-701(E)-05

Siemens UMTS Node-B NB440 Installation

  • Upload
    qbit42

  • View
    73

  • Download
    5

Embed Size (px)

DESCRIPTION

Siemens UMTS Node-B NB440 Installation

Citation preview

Page 1: Siemens UMTS Node-B NB440 Installation

UTRAN

Installation

Node B

IMN:NB-440

A50016-G5000-C229-5-7631ND-57356-701(E)-05

Page 2: Siemens UMTS Node-B NB440 Installation

2Siemens AG:A50016-G5000-C229-5-7631NEC Corporation:ND-57356-701(E)-05

IMN:NB-440 InstallationNode B

Trademarks:

All designations used in this document can be trademarks, the use of which by third parties for theirown purposes could violate the rights of their owners.

Copyright (C) Siemens AG / NEC Corporation 2003.

Issued by:Siemens AG, Information and Communications Group, Hofmannstraße 51, 81359 München, Germany andNEC Corporation, 7-1, Shiba 5-chome, Minato-ku, Tokyo, Japan

Technical modifications possible.Technical specifications and features are binding only insofar as they are specifically and expressly agreed upon in a written contract.

Page 3: Siemens UMTS Node-B NB440 Installation

InstallationNode B

IMN:NB-440

Siemens AG: A50016-G5000-C229-5-7631NEC Corporation: ND-57356-701(E)-05 3

Reason for UpdateSummary:Modified and completed description of external interfaces

Details:

Chapter/Section Reason for Update

all Integration of review comments

Chapter 1 and 3 new arrangement and redesign

2.5.5 Revised content with new earthquake mounting kit

2.6.10 Changing of sketch in figure 2.50

2.6.12 Integration of additional system cabling sketches

Issue HistoryIssue

Number

Date of issue Reason for Update

1 04/2002 First issue for acceptance test of release UMR2.0

2 07/2002 Modified and additional graphics

3 10/2002 New issue for release UMR2.0

4 12/2002 Completed description of external interfaces,

new module OPEXAL

5 02/2003 Integration of review comments and revised content

Page 4: Siemens UMTS Node-B NB440 Installation

IMN:NB-440 InstallationNode B

4Siemens AG:A50016-G5000-C229-5-7631NEC Corporation:ND-57356-701(E)-05

Page 5: Siemens UMTS Node-B NB440 Installation

InstallationNode B

IMN:NB-440

Siemens AG: A50016-G5000-C229-5-7631NEC Corporation: ND-57356-701(E)-05 5

This document consists of a total of 61 pages. All pages are issue 5.

Contents

1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111.1 Purpose of the Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111.2 Tasks of the Node B Stations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111.3 System Operating Bands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111.4 Installation Prerequisites. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121.5 Handling of the Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121.6 Safety Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131.7 Installation Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131.8 Ancillary Material. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141.9 Technical Data of NB-440. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141.10 External Interfaces of the NB-440. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

2 NB-440 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 152.1 Position in the System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 152.2 Site Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 152.3 Site Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 162.4 Construction View of NB-440 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 162.4.1 Rack Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 182.5 Equipment Delivery. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 192.5.1 Preliminary Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 192.5.2 Unpacking the Rack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202.5.2.1 Unpacking the rack out the transportation crate . . . . . . . . . . . . . . . . . . . . . 202.5.2.2 Unpacking the rack out the wrapping foil cover . . . . . . . . . . . . . . . . . . . . . 222.5.3 Devices Unpacking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 222.5.4 Rack Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 232.5.5 Setup of Earthquake Mounting Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 272.6 External Cabling Activities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 292.6.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 292.6.2 Ground and Power Supply Connections -48 V DC . . . . . . . . . . . . . . . . . . . 312.6.3 Iub-Interface - Link Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 332.6.3.1 Iub-Interface for 100/120 Ohm Cable Impedance. . . . . . . . . . . . . . . . . . . . 332.6.3.2 Iub-Interface for 75 Ohm Cable Impedance . . . . . . . . . . . . . . . . . . . . . . . . 352.6.3.3 Monitoring Interfaces of the Iub interfaces . . . . . . . . . . . . . . . . . . . . . . . . . 362.6.4 Alarm Collection Terminal - external Signal Sensors . . . . . . . . . . . . . . . . . 372.6.5 Installation of the Mounting Kit OPEXAL . . . . . . . . . . . . . . . . . . . . . . . . . . 392.6.6 Alarm Collection Terminal ACTC - internal Alarms. . . . . . . . . . . . . . . . . . . 422.6.7 Local Maintenance Terminal (LMT) Interface . . . . . . . . . . . . . . . . . . . . . . . 432.6.8 Connection of External Reset Line . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 442.6.9 Antenna Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 452.6.9.1 Preparation of Antenna Jumper Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . 452.6.10 Installation of the Tower Mounted Amplifiers . . . . . . . . . . . . . . . . . . . . . . . 512.6.10.1 Pole Mounting with Hose Clips . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 542.6.10.2 Wall Mounting of TMAF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 562.6.11 Preparation of the Top Cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57

Page 6: Siemens UMTS Node-B NB440 Installation

IMN:NB-440 InstallationNode B

6Siemens AG:A50016-G5000-C229-5-7631NEC Corporation:ND-57356-701(E)-05

2.6.12 Setup of the System Cabling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 582.7 Post Installation Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60

3 Appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 613.1 Checklist for NB-440 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61

Page 7: Siemens UMTS Node-B NB440 Installation

InstallationNode B

IMN:NB-440

Siemens AG: A50016-G5000-C229-5-7631NEC Corporation: ND-57356-701(E)-05 7

IllustrationsFig. 1.1 ESD Symbol. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

Fig. 1.2 Press-stud for ESD wrist-strap connection . . . . . . . . . . . . . . . . . . . . . . 12

Fig. 2.1 Position of a Node B within the System. . . . . . . . . . . . . . . . . . . . . . . . . 15

Fig. 2.2 Site configuration NB-440 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

Fig. 2.3 Fully equipped NB-440 rack. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

Fig. 2.4 ShockwatchTM-label and TIP (N) TELLTM-label . . . . . . . . . . . . . . . . . . 20

Fig. 2.5 Removal of the straps, opening of the top cover . . . . . . . . . . . . . . . . . . 20

Fig. 2.6 Removal of the packing material . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

Fig. 2.7 Opening of the PE-wrap, lifting straps around the rack . . . . . . . . . . . . . 21

Fig. 2.8 Foil- transportation packing of NB-440 . . . . . . . . . . . . . . . . . . . . . . . . . 22

Fig. 2.9 Opening of rack door . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

Fig. 2.10 Removal of top cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

Fig. 2.11 Guideline for crane transport . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

Fig. 2.12 Space necessary for installation of NB-440 . . . . . . . . . . . . . . . . . . . . . . 24

Fig. 2.13 Removal of fastening claws . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

Fig. 2.14 Adjusting of rack foot . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

Fig. 2.15 Mounting bracket for fixing to wall . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

Fig. 2.16 Parts of the earthquake kit S3086-K4119-X . . . . . . . . . . . . . . . . . . . . . 27

Fig. 2.17 Double claw for the rear feet in mounted position . . . . . . . . . . . . . . . . . 28

Fig. 2.18 Claws for the front feet before fixing . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

Fig. 2.19 Drilling sketch for earthquake mounting kit . . . . . . . . . . . . . . . . . . . . . . 28

Fig. 2.20 Interfaces on EMI Panel of the NB-440 . . . . . . . . . . . . . . . . . . . . . . . . . 29

Fig. 2.21 Locations of connection points for external cables . . . . . . . . . . . . . . . . 30

Fig. 2.22 Ground and DC mains connections of the NB-440 . . . . . . . . . . . . . . . . 31

Fig. 2.23 DC mains terminal block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

Fig. 2.24 Connection of the grounding wire . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

Fig. 2.25 Preparation of twisted pair cables, 120 Ohm impedance . . . . . . . . . . . 33

Fig. 2.26 Routing of Iub-cable (example with OVPTE1J1SF). . . . . . . . . . . . . . . . 34

Fig. 2.27 Pinning Iub interface at OVPTE1J1SF / IUBCONSFV1. . . . . . . . . . . . . 34

Fig. 2.28 Iub interface with coaxial connectors (example with OVPTE1CF). . . . . 35

Fig. 2.29 Iub line connectors of OVPTE1CF / IUBCONCFV1. . . . . . . . . . . . . . . . 35

Fig. 2.30 Pinning of the monitoring interfaces. . . . . . . . . . . . . . . . . . . . . . . . . . . . 36

Fig. 2.31 Terminal numbering of the ACTM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

Fig. 2.32 Contents of the MK:OPEXAL. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39

Fig. 2.33 Drilling sketch for MK:OPEXAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

Fig. 2.34 Wall mounted MK:OPEXAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41

Fig. 2.35 Routing of external alarm cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41

Fig. 2.36 Connector arrangement at ACTC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42

Fig. 2.37 Connection of external reset line . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44

Fig. 2.38 Example for cell numbering (top view from the antenna pole). . . . . . . . 45

Fig. 2.39 Tools for jumper fabrication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46

Fig. 2.40 Parts of the connector unit kit (example) . . . . . . . . . . . . . . . . . . . . . . . . 46

Fig. 2.41 Using the trimming tool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47

Page 8: Siemens UMTS Node-B NB440 Installation

IMN:NB-440 InstallationNode B

8Siemens AG:A50016-G5000-C229-5-7631NEC Corporation:ND-57356-701(E)-05

Fig. 2.42 Removal of isolation and deburring of inner conductor. . . . . . . . . . . . . . 47

Fig. 2.43 Removal of metal particles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47

Fig. 2.44 Assembly of the connector unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48

Fig. 2.45 Fixing of connector unit , removal of outer insulation . . . . . . . . . . . . . . . 48

Fig. 2.46 Handling of heat protection tape and shrink sleeve . . . . . . . . . . . . . . . . 48

Fig. 2.47 Shrinkage and removal of the visible heat protection tape . . . . . . . . . . . 49

Fig. 2.48 Max. dimensions of antenna connectors . . . . . . . . . . . . . . . . . . . . . . . . 49

Fig. 2.49 Routing of antenna jumper cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50

Fig. 2.50 Position of TMAF/DTMAF in the system. . . . . . . . . . . . . . . . . . . . . . . . . 51

Fig. 2.51 Bottom view of the TMAF (measures in mm) . . . . . . . . . . . . . . . . . . . . . 51

Fig. 2.52 Fixing facilities of TMAF (measures in mm) . . . . . . . . . . . . . . . . . . . . . . 52

Fig. 2.53 Bottom view of the DTMAF (measures in mm) . . . . . . . . . . . . . . . . . . . . 52

Fig. 2.54 Top view of the DTMAF (measures in mm) . . . . . . . . . . . . . . . . . . . . . . 53

Fig. 2.55 Fixing facilities of DTMAF (measures in mm) . . . . . . . . . . . . . . . . . . . . . 53

Fig. 2.56 Fitting of the hose clips (example with TMAF) . . . . . . . . . . . . . . . . . . . . 55

Fig. 2.57 Pole mounting of the TMAF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55

Fig. 2.58 Antenna cable connection at the TMAF . . . . . . . . . . . . . . . . . . . . . . . . . 56

Fig. 2.59 Drilling sketch for wall mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56

Fig. 2.60 Removable pieces and paint retouch of the top cover . . . . . . . . . . . . . . 57

Fig. 2.61 Cabling between TRX, LPA and DUAMCOF (2 Carrier, 1 Cell) . . . . . . . 58

Fig. 2.62 LPA-DUAMCOF cabling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59

Page 9: Siemens UMTS Node-B NB440 Installation

InstallationNode B

IMN:NB-440

Siemens AG: A50016-G5000-C229-5-7631NEC Corporation: ND-57356-701(E)-05 9

TablesTab. 1.1 External Interfaces of the NB-440 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

Tab. 2.1 Pinning of monitoring interfaces OVPTE1CF / IUBCONCFV1 . . . . . . . 36

Tab. 2.2 Pinning of monitoring interfaces OVPTE1J1SF / IUBCONSFV1. . . . . . 37

Tab. 2.3 Pinning ACTM Connectors X1 ... X4 . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

Tab. 2.4 Pinning ACTM Connectors X10 and X9. . . . . . . . . . . . . . . . . . . . . . . . . 39

Tab. 2.5 Pinning ACTC Connector X12 and X8. . . . . . . . . . . . . . . . . . . . . . . . . . 42

Tab. 2.6 Pinning ACTC Connector X9 and X10. . . . . . . . . . . . . . . . . . . . . . . . . . 42

Tab. 2.7 Pinning ACTC Connector X21 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43

Tab. 2.8 Functionality of system cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59

Tab. 3.1 Checklist for NB-440 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61

Page 10: Siemens UMTS Node-B NB440 Installation

IMN:NB-440 InstallationNode B

10Siemens AG:A50016-G5000-C229-5-7631NEC Corporation:ND-57356-701(E)-05

Page 11: Siemens UMTS Node-B NB440 Installation

InstallationNode B

IMN:NB-440

Siemens AG: A50016-G5000-C229-5-7631NEC Corporation: ND-57356-701(E)-05 11

1 Introduction

1.1 Purpose of the ManualThis document is intended to give the information necessary for the installation of theNode B station in the Radio Network Subsystem (RNS).

It contains a description of all the necessary steps to install the Node B on site andintegrate it into the required infrastructure:– Power supply– E1/J1 - Network– Grounding– Receive / transmit antenna system– Alarm connections– Base constructions

For installation of equipment not supplied by Siemens (battery chargers, antennas,power supplies, microwave etc.) refer to site specific documentation or vendorinstructions provided with other equipment.

1.2 Tasks of the Node B StationsThe Node B Station performs the following main tasks in accordance with the require-ments of the UMTS standards:– Provides the RF-link connection to the User Equipment (UE)– Supports various cell types (omni and sector cells)– Provides the E1/J1 link connection (symmetrical twisted pair or coaxial cable is

used) and/or the STM-1 optical link connection to the Radio Network Controller(RNC)

1.3 System Operating BandsThe Frequency Division Duplex mode (FDD) implemented uses different frequencybands for uplink and downlink thus allowing symmetrical data traffic.– Downlink: 2110 MHz - 2170 MHz– Uplink: 1920 MHz - 1980 MHz– Channel spacing: 5 MHz

!Important!The declaration of CE conformity for the product is fulfilled if the setup and wiring arecarried out as described in the manual and the documents contained therein, such asinstallation instructions, cable lists, etc. Project-specific documentation should be takeninto account as appropriate. Deviations from specifications or unauthorized changes inthe setup, such as the use of cable types with less shielding, can lead to a violation ofCE safety requirements. In such cases, the declaration of conformity is rendered void.The responsibility for the resulting problems passes to the individual who caused the de-viation.

Page 12: Siemens UMTS Node-B NB440 Installation

IMN:NB-440 InstallationNode B

12Siemens AG:A50016-G5000-C229-5-7631NEC Corporation:ND-57356-701(E)-05

1.4 Installation PrerequisitesIt is required that the installer pays attention to all relevant national EMC standards.– EMF (electromagnetic fields) standard relevant for the choice of the antenna, the

placement of the antennasand the max. output power of the Node B (cell coverage).

– Use the correct material as described in this manual.– Installation according to the standards EN 50310 or ETS 300253, EN 50154 and the

statements in this manual.– The other equipment on site have to fulfill the relevant safety- and EMC standards

and must provide interfaces for connecting of external cables conformable to EMCinstructions.

The installation staff must have a basic knowledge of the relevant standards.The installation manual should be available for staff on site.

1.5 Handling of the ModulesAll boards and modules must be handled with extreme care as each one containselectrostatically sensitive devices (ESD).The modules are marked with the ESD-label.

Fig. 1.1 ESD Symbol

The modules are sensitive to static discharge.

Note:– Avoid handling the modules in a high-static environment– When handling the modules, do not touch connector contacts– An earthed high-impedance wrist strap must be worn when handling modules– Use the socket at the racks for wrist strap connection– The modules must be transported in appropriate packaging

Fig. 1.2 Press-stud for ESD wrist-strap connection

Earth Bonding Point

Page 13: Siemens UMTS Node-B NB440 Installation

InstallationNode B

IMN:NB-440

Siemens AG: A50016-G5000-C229-5-7631NEC Corporation: ND-57356-701(E)-05 13

1.6 Safety Instructions

Persons other than the maintenance personnel must not touch the devices inside theAC-Distribution. The AC-Distribution involves a high voltage and high current. Touchingit can lead to an electrical shock or accident.

Make sure not to touch parts of the Node B that contains components with high voltageor current. An inadvertent contact with any of these components can cause injury, death,and/or damage to the system.

Be sure to provide grounding where required. A failure to do so can lead to a systemfailure or electrical shock at the time of lightning.

When measuring voltage or current, take adequate insulating measures, such as cov-ering or winding the superfluous parts of the measuring terminal and tools with insulatingtape. Allowing the measuring terminal to touch another terminal or a short-circuit causedby a tool can lead to an electrical shock or accident.

Before making a connection with the DC-PDB, ensure that the power to the main andbattery circuit breaker is OFF. Making a connection with the DC-PDB when the poweris ON can lead to an electrical shock or accident.

Before making a cable connection, be sure to turn the switch on the power distributionboard to OFF. Otherwise, an electrical shock or accident can result.

Before making a cable connection, confirm the electric polarity. If the cable is connectedwith wrong polarity, an electrical shock or accident can result.

Make sure to follow the additional safety instructions in this manual.

1.7 Installation ToolsThe correct installation is carried out with the aid of the following tools:– Standard toolkit for BSS-installation– Spirit level– Torque spanner for SMC connectors (35 Ncm)– Torque spanner for SMA connectors (100 Ncm)– Screw driver for torx screws T8, T10, T20, T25, T30– Long screw driver for torx screws T30 (length 400 mm)– Engineer‘s spanners open ended for M12, M42 (SW 19, 65 mm)– Ratchet with inserts for nuts M4, M5, M6, M8, M10 (SW 7, 8, 10, 13, 17 mm)– Security torx bit IPR25 (Knürr part no. 4000031 98)– Screw drivers for hexagonal socket screw or hexagonal socket screw key SW 4 mm– Screw driver for slotted screw M3, M4, M5– Screw driver for pozi drive screws M3,M4, M5– A pair of scissors– Stripping knife for RF cables– 90˚ offset screw driver for torx screws T20– Blanket and knee pads (recommended)– Adjuster feed wrench M42 (SW65) (Knürr part no. 01.139.965.7)– Hammer and a suitable piece of wood– Insulated torque wrench for Torx T30 (6 Nm) and an open ended 17mm (20 Nm)– Torque wrench 32 mm (12-35 Nm) for 7/16” connectors

!Pay attention to the following safety instructions on high voltage and high current:

Page 14: Siemens UMTS Node-B NB440 Installation

IMN:NB-440 InstallationNode B

14Siemens AG:A50016-G5000-C229-5-7631NEC Corporation:ND-57356-701(E)-05

– Tool Siemens SNR C39407-A149-A6 (removal of gas filled surge arristors in theOVPT)

For installation of power supply, transmission equipment, antennas, cableways andother infrastructure equipment, additional tools may be necessary.

1.8 Ancillary MaterialThe following ancillary materials are needed :– plumb line– colophony– adhesive tape (yellow/green, green, blue, red, orange, white)– cable fasteners– wire end sleeves for 16 mm and 35 mm2 copper wires– cable lugs M8– wire end sleeves– paint retouch kit (Siemens Serial No. A500-C101-B261)

1.9 Technical Data of NB-440For detailed information about the technical data of the Node B (e.g. mechanical andelectrical specifications) refer to the TED:UTRAN NB-440/441.

1.10 External Interfaces of the NB-440

Connection Interface

TX/RX antenna

IuB lines

mains input DC

ground

external alarms

LMT

System Reset line

7/16”, female

terminal block (100 Ω/120 Ω) or1.0/2.3 coaxial connectors female (75 Ω)WAGO terminal block (max. AWG 000)

bolt M8, copper conductor 16 mm2

(#6 AWG for USA)WAGO terminal blocks for wires 0.5 mm(#28-20 AWG)RJ45 at CC module and Hub (DC panel)

2-pole WAGO terminal block for wires 0.5 mm(#28-20 AWG)

Tab. 1.1 External Interfaces of the NB-440

Page 15: Siemens UMTS Node-B NB440 Installation

InstallationNode B

IMN:NB-440

Siemens AG: A50016-G5000-C229-5-7631NEC Corporation: ND-57356-701(E)-05 15

2 NB-440 Installation

2.1 Position in the SystemNB-440 interconnects the mobile User Equipment (UE) via the Uu interface with theradio network subsystem (RNS).

Fig. 2.1 Position of a Node B within the System

2.2 Site RequirementsThe NB-440 is intended to be installed in a restricted access area.The installation sitemust fulfill installation rules according to ETS 300253 or EN 503010 and EN 50174.The lightning protection measures must be in accordance with IEC 1312 (in the futureseries IEC 61024) and IEC 61000-2-5 to achieve a lightning protection zone 1 interfaceto the communication equipment.Prior to the commencement of installation, the construction of the room which theNode B is to be housed in should be complete and the room in good condition.If necessary, dry heaters should be setup in the room.– Doors and windows must already have been installed and must be lockable.– Openings in wall or ceiling or floor - if required - must be complete.– The floor coverings must have been laid.– Room lighting and wall sockets must have been installed.– Heating or air-conditioning systems should be ready for operation.– Battery ventilation must be ensured.– Walls and ceilings should have been painted. The room must be clean.– A minimum floor space of 1,10 m x 1,40 m must be provided. These are the dimen-

sions for a minimum installation without the possibility for later extension.– optional cable runways have to be installed first– The floor load of the construction room must exceed of 7000 N/m2.– All installation works of -48 V DC power supply equipment should be finished.

External circuit breakers (125 A, medium response time and a contact separation ofat least 3mm) if there is no DC pole grounded, a two-pole disconnect device isnecessary. They have to be fitted in a power distribution panel for each rack.

Uu interface

Iubinterface

Iuinterface

Node B RNC Core Network

mobileUser

Equipment

RNS

Page 16: Siemens UMTS Node-B NB440 Installation

IMN:NB-440 InstallationNode B

16Siemens AG:A50016-G5000-C229-5-7631NEC Corporation:ND-57356-701(E)-05

To prevent subsequent accumulation of dust and dirt, the parts and equipmentunits to be installed should be unpacked outside the room (if possible). It is advanta-geous to install the Node B only after all other installation works to create the requiredinfrastructure are complete.

2.3 Site ConfigurationOperation of the NB-440 requires additional equipment on site:

Fig. 2.2 Site configuration NB-440

2.4 Construction View of NB-440The modules of the NB-440 station are housed in a rack with the dimensions1400 x 600 x 450 mm (H x W x D). The rack can be equipped with up to 6 TRX.The necessary space for installation is shown in Fig. 2.12.

The NB-440 rack contains the following modules:

Core Controller (CC):The Core Controller is built up of 4 boards: CPU board, ATM board, LIU board and theSTM-1 board.

Channel Coding Card (CHC):The main function of CHC is the decoding in uplink direction.

Repeater Card (REP):The REP card provides a multiplexing function for base band signals. The card sorts thedownlink signals from the CHC cards according to antennas and sends them to theTRX cards. The card also sends the signals from the TRX cards to the CHC cards inuplink direction.

TX/RX antennas

external alarms**Iub lines

DC power supply 125 A circuit breakers

microwave outdoor unit *

*dependent on type of network integration**optional

-48 V DC

in power distribution box

~

=

ground connection

link equipment(can be NTPM ormicrowave)

AC mains

terrestrial linesto RNC *

ground bar

LE

Page 17: Siemens UMTS Node-B NB440 Installation

InstallationNode B

IMN:NB-440

Siemens AG: A50016-G5000-C229-5-7631NEC Corporation: ND-57356-701(E)-05 17

Transceiver Card (TRX):

The TRX card features a transceiver base band block (TRX BB) and a radio frequencyblock (RF). The radio frequency block is composed of the transmitter block (TX) and thereceiver block (RX). Both TX and RX have diversity configuration. The transmitter blockconverts baseband signals into RF signals and the receiver block converts RF signalsinto base band signals.

Duplexer Amplifier Multi Coupler (DUAMCOF):A duplexer combines the transmit and receive paths to the common antenna connector.The receive and transmit part of the duplex filter, respectively, provide a substantial partof the transmit and receive band filtering that is required.

Linear Power Amplifier(LPA):The LPA is the RF power amplifier. An LPA is capable of supporting one (LPA-SCF) ortwo carriers (LPA-MCF).In case of the two carrier LPA the signal path consists of a combiner and a poweramplifier enabling two separate signals from TRXs to be combined before application.

Over Voltage Protection and Tracer (OVPT):Protects the E1 and J1 ports of the Iub interface and the external synchronisation clockinput of the Node B from overvoltage and provides interfaces for connection of externalmonitoring equipment without interruption.

Tower Mounted Amplifier( TMAF):The TMAF is an (optional) RF unit (external to the Node B rack) which provides themeans to feed the overall Node B downlink signal to one TX/RX antenna and to amplify,with low noise figure, the overall Node B uplink signal coming from the same TX/RXantenna.

The numbers of installed modules (exepted CC) are subject to modification, it dependson the number of TRXs and the cell configuration on site.

NB-440 is fed by an external -48 V DC source.The required link equipment for the fixed link to the fixed public telephone network(can be microwave or NTPM) must find place in a separate shelf on site. Type and layoutof the shelf depends on customer requirements.

For further information about the hardware architecture refer to the “Technical Descrip-tion UTRAN NB-440/441.

i NOTEAll empty slots in a partially equipped shelf must be closed with adequate dummy boardcassettes, so that the air flow inside the rack will not be affected.Dummy board casettes are available with the dimensions 295 x 20 mm, 295 x 40 mmand 295 x 60 mm (H x W).

Page 18: Siemens UMTS Node-B NB440 Installation

IMN:NB-440 InstallationNode B

18Siemens AG:A50016-G5000-C229-5-7631NEC Corporation:ND-57356-701(E)-05

2.4.1 Rack LayoutThe rack allows a minimal configuration with 1 TRX and can be equipped with up to6 TRX for different cell configurations.

Fig. 2.3 Fully equipped NB-440 rack

FAN#0 FAN#1

FAN#2 FAN#3

LPA

#0

LPA

#1

LPA

#2

LPA

#3

LPA

#4

LPA

#5

DU

AM

CO

F#0

DU

AM

CO

F#1

DU

AM

CO

F#2

EMI Panel

DC Panel

document tray

top coverC

C#0

CH

#0

CH

#9

CH

#0 ...........

RE

P#0

,1T

RX

#0

TR

X#5...

A-s

helf

B-s

helf

Page 19: Siemens UMTS Node-B NB440 Installation

InstallationNode B

IMN:NB-440

Siemens AG: A50016-G5000-C229-5-7631NEC Corporation: ND-57356-701(E)-05 19

2.5 Equipment DeliveryThe NB-440 rack is shipped vertically in a wooden crate.The crate dimensions for the NB-440 are 1600 mm x 800 mm x 650 mm (HxWxD).Depending on the pre-installed modules inside the racks, the crate can weigh up toapprox. 190 kg.The delivery position in case of transportation by airplane or at transportation on thestreet is horizontally. In this case the NB-440 is mounted on a wooden pallet and isprotected through cardboard corner reinforcement at the edges of rack and by a wrap-ping foil cover.

The crate or the packing-foil cover have the following information printed on them foridentification of delivery:– destination, customer order number– serial number of rack– gross and net weight, overall dimensions (cm)– symbol or inprint to identify the "Top" and the "Bottom"– delivery papers

Use handling aids (for example: fork-lift truck, goods elevator) for transportation of theNB-440 from the unloading area into the construction room. A second person is neededfor help. The 4 fastening clamps which are fixing the rack-feet to the bottom of the crateshould be used for fastening the rack to the floor.

2.5.1 Preliminary ChecksThe transportation crate of the NB 440 is equipped with a ShockwatchTM -label and aTIP (N) TELLTM -label. These labels are fixed at the crate for indication of fallover orstrong shocks during the transport from factory to the site.

If the TIP (N) TELLTM arrow is blue, the package has been on the side of tipped over intransit. Indicates the ShockwatchTM -label red color, the package has been shockedduring the transport.

Check that the delivery packing and labels are in proper condition. If there is obvious-damage due to transportation, unpack the equipment in the presence of an insurancecompany representative and promptly claim any damage. Inform the shipper of thespecific damage.Check whether the package is actually addressed to the site and complete.

i NOTEIn the case of horizontal transportation, the fixing plates are not used but are always partof a delivery. Though not needed for horizontal transportation, the claws can be usedfor fixing the Rack to the floor after installation.

!CAUTIONThe rack door must be kept closed during transportation.

Page 20: Siemens UMTS Node-B NB440 Installation

IMN:NB-440 InstallationNode B

20Siemens AG:A50016-G5000-C229-5-7631NEC Corporation:ND-57356-701(E)-05

Fig. 2.4 ShockwatchTM-label and TIP (N) TELLTM-label

2.5.2 Unpacking the RackDuring the unpacking steps, great care must be taken to ensure that the rackis not scratched or damaged in any way.

2.5.2.1 Unpacking the rack out the transportation crate

Unpack the rack according to the following instructions.

Fig. 2.5 Removal of the straps, opening of the top cover

1. Cut the three straps (see Fig. 2.5).

ShockwatchTM-label

TIP (N) TELLTM-label

i NOTEImmediately after unpacking the rack, inspect it for damage and report the extent ofany damage to the transportation company.

!CAUTIONSafety gloves and goggles must be worn when cutting the straps.Pay attention to the tension of the straps. Use only plate shears.

cut

unscrew

Page 21: Siemens UMTS Node-B NB440 Installation

InstallationNode B

IMN:NB-440

Siemens AG: A50016-G5000-C229-5-7631NEC Corporation: ND-57356-701(E)-05 21

2. Unscrew the 10 M4 screws on the top of the crate (see Fig. 2.5).3. Remove the crates top cover .4. Take out the packing material protecting the rack (see Fig. 2.6).5. Open and remove the tubular PE-wrap protecting the rack (see Fig. 2.7).6. Take out the rack from the crate. Use the straps around the rack.7. Lift the rack in vertical position.

Fig. 2.6 Removal of the packing material

Fig. 2.7 Opening of the PE-wrap, lifting straps around the rack

cut

Page 22: Siemens UMTS Node-B NB440 Installation

IMN:NB-440 InstallationNode B

22Siemens AG:A50016-G5000-C229-5-7631NEC Corporation:ND-57356-701(E)-05

2.5.2.2 Unpacking the rack out the wrapping foil cover

Fig. 2.8 Foil- transportation packing of NB-440

Unpack the rack according to the following instructions and in accordance with theFig. 2.8.

1. Cut the two straps (1)2. Open by cutting the foil along the cardboard corner reinforcement (2) the tubular

PE-wrap protecting and remove it3. Remove the cardboard reinforcement on the top and from the corners of rack4. Remove the four fastening claws from the feet of the rack, for further transport to the

installation location as described in chapter 2.5.4.

2.5.3 Devices UnpackingIf neccessary proceed as follows:

1. Open the PVC wrap protecting the carton and withdraw it2. Remove the dehydrating material bag from the box3. Use a suitable knife to cut the adhesive tape sealing the box and take out the device4. Open the PVC wrap protecting the device/board and withdraw it

The packing material should be preserved for possible future re-packing.For this purpose, reverse the procedure described above, taking into account thewarnings specified for the packing.

If the packing material is supplied by the customer, special care should be takento avoid damage during the transport and storage of the devices.

2

1

!CAUTIONSafety gloves and goggles must be worn when cutting the straps.Pay attention to the tension of the straps. Use only plate shears.

Page 23: Siemens UMTS Node-B NB440 Installation

InstallationNode B

IMN:NB-440

Siemens AG: A50016-G5000-C229-5-7631NEC Corporation: ND-57356-701(E)-05 23

2.5.4 Rack InstallationPrior to the commencement of rack installation, consult the site documentationto locate the installation point of the NB-440, the link equipment, power supply unit andthe access of the antenna cables into the construction room.After that, check the proper installation of the ground bar and the necessarycable runways.

If the rack must be moved to the final installation position by crane and for laterconnection works, it is necessary to remove the top cover of the rack.

Proceed as follows:

Fig. 2.9 Opening of rack door

1. Open the rack-door as shown in the figure above: Slide down the protection cover(1), push the button behind the cover (2) and flap out the handle (3). Turn the handlecounterclockwise 45˚ (4).

2. Slide the top cover 20 mm in front direction and lift it up ( see Fig. 2.10.)3. Disconnect the green/yellow ground wire from the pin inside the top cover.

Fig. 2.10 Removal of top cover

!CAUTIONBefore opening the rack door, take measures to prevent the rack falling over!Note the accident prevention regulations, when working with a fork lift truck or crane !

1

2

34

ground wire

1

2

Page 24: Siemens UMTS Node-B NB440 Installation

IMN:NB-440 InstallationNode B

24Siemens AG:A50016-G5000-C229-5-7631NEC Corporation:ND-57356-701(E)-05

Fig. 2.11 Guideline for crane transport

The NB-440 are intended for interior installation only so that they should be free frompossible water ingress, frost, tampering and excessive insect attack.

The following recommendations should be considered:– In order to install the NB-440 below a roof or in a room, a minimum height of

1700 mm is required which is also necessary for removing the top.– Installation next to a wall is possible to the left. A minimum distance of 100 mm to be

maintained at the rear. A clearance of 500 mm on the right is needed to open therack door. In case of back-to-back installation a distance between the rear panelsof the racks of 200 mm is absolutely required.

– The minimum distance to the opposite wall is 750 mm.– It is recommended that an additional working area be considered with an

appropriate emergency exit. The rack has a right hand opening door.

Fig. 2.12 Space necessary for installation of NB-440

min. 65˚

100 mm

600 mm

NB-440

750

mm

500 mm

door

NB-440

1700 mm(minimum room height)

min. distancefor proper air radiation

Page 25: Siemens UMTS Node-B NB440 Installation

InstallationNode B

IMN:NB-440

Siemens AG: A50016-G5000-C229-5-7631NEC Corporation: ND-57356-701(E)-05 25

Fig. 2.13 shows the four fastening claws which fix the rack feet to the crate or woodenpallet during transport. The claws should be used for fixing the NB-440 rack to the floor.

Fig. 2.13 Removal of fastening claws

Fig. 2.14 Adjusting of rack foot

Proceed as described in the list below:

1. Unscrew the 4 fastening claws from the crates base as shown in Fig. 2.13 andcarefully move the rack to the final installation position.

2. Check the correct vertical rack position, using the spirit-level. In case, that theposition is incorrect, compensate differences in the floor height by adjusting the rackfoot. (see Fig. 2.14).

3. Loose the lock nut (1) and screw down or up the rack foot (2) for proper floor contactby using adjuster feed wrench M42 (SW65, Knürr part no. 01.139.965.7).

4. Tighten the lock nut as fast as possible to avoid a gap between the bottom section(3) and the rack frame (4). The electrical contact between lock nut and bottomsection is absolutely required for EMI-closeness of the NB-440 rack.

5. Push a claw on each of the 4 rack foot and mark the drilling point on the floor.6. Remove the clamps and drill the 4 holes and insert the 4 wallplugs (e.g. Fischer

S8GK) into the holes.7. Push the claws on the rack foot and fix them. Use a ratchet with a 10 mm nut.

1

2

3

4

!CAUTIONIt is strictly not allowed, to install the NB-440 without fixing to a concrete

foundation or base construction!

Page 26: Siemens UMTS Node-B NB440 Installation

IMN:NB-440 InstallationNode B

26Siemens AG:A50016-G5000-C229-5-7631NEC Corporation:ND-57356-701(E)-05

Additionally the rack can be affixed to the wall. Mounting brackets (Siemens serial no.C50300-A204-C156) should be used for the wall fixing.

Fig. 2.15 Mounting bracket for fixing to wall

5

20

40

195

100

40

diameter 10length 20

(all measures in mm)

hole for fixing to the wall

hole for fixing at the top of the rack

!CAUTIONWhen the earthquake mounting kit is used, no additional wall mounting of therack is allowed!

Page 27: Siemens UMTS Node-B NB440 Installation

InstallationNode B

IMN:NB-440

Siemens AG: A50016-G5000-C229-5-7631NEC Corporation: ND-57356-701(E)-05 27

2.5.5 Setup of Earthquake Mounting KitIn areas with the possibility of earthquake use the mounting kit for Earthquake Zone 4Rack (MK:EQ4RV2, S30861-K4119-X). The additional brackets improve the robustnessof the rack against earthquake shocks.

The mounting kit consists of the mechanical parts as shown in the figure below.

Fig. 2.16 Parts of the earthquake kit S3086-K4119-X

Fix the rack to the floor in accordance with Fig. 2.19 in steps as follows:– Mark the positions of the drilling holes in.– Drill at right-angle the holes with 18 mm in diameter and a depth of 98 mm. Don‘t

pre-drill the holes!– Produce an undercut of the drilling holes: drill the hole to stop and swivel the

jack hammer 3-5 times keeping stop to concrete.– Clean out the drilling holes by blowing or sucking.– Put dowels (3) (e.g. HILTI - M12*73 / 20) into the inserting tool and hammer into each

hole until the sleeve is flush with surface.– Screw the premounted double claw (1) with the rear dowels on the floor with a torque

of 60Nm tight (see Fig. 2.17).– Shift the rack to the appropriate position, so that each of the rear rack feet is placed

in a cutout of the double claw.– Open the rack door.– Insert a claw (2) on each of the front feet and affix them with the M12 bolts to the

steel plugs in front of the rack (see Fig. 2.18).Tighten the connection with a torque of 60Nm.

See drilling sketch in Fig. 2.19.

1

2

3 3

Page 28: Siemens UMTS Node-B NB440 Installation

IMN:NB-440 InstallationNode B

28Siemens AG:A50016-G5000-C229-5-7631NEC Corporation:ND-57356-701(E)-05

Fig. 2.17 Double claw for the rear feet in mounted position

Fig. 2.18 Claws for the front feet before fixing

Fig. 2.19 Drilling sketch for earthquake mounting kit

sketch without scale, all measures in mm

465

92.5

450

57.5

485

600

Page 29: Siemens UMTS Node-B NB440 Installation

InstallationNode B

IMN:NB-440

Siemens AG: A50016-G5000-C229-5-7631NEC Corporation: ND-57356-701(E)-05 29

2.6 External Cabling Activities

2.6.1 OverviewThis chapter gives information required for installing the external cables betweenthe NB-440 and equipment outside the rack.

The rack can not function without the following cable connections:– DC mains terminal block 2 pole -48 V DC power supply equipment– ground bolt - ground bar– Iub interface - link equipment (can be NTPM or microwave)– microwave indoor units - microwave outdoor units

(if microwave equipment is used for transmission)– transmit / receive antenna connectors - antenna system– ground strip of antenna cable shields - ground bolt

optional:– alarm collection terminal - external alarm sensors

All interfaces exept the antenna connectors are located at the EMI panel below thetop cover.

The top cover needs to be removed for cable installation. For removal of the top coverproceed as described in section 2.5.4 of this manual.

Fig. 2.20 Interfaces on EMI Panel of the NB-440

Some additional hints for the installation of external cabling:– The first cable that has to be installed is the ground cable between the main ground

stud on top of the rack and the nearest ground bar on site.

1 2

3

4

5

3

1 Iub interface on OVPT 02 Iub interface (OVPT 1)3 ground bolts

4 DC terminal5 ACT

6 lightning protection alarms7 external reset

67

Page 30: Siemens UMTS Node-B NB440 Installation

IMN:NB-440 InstallationNode B

30Siemens AG:A50016-G5000-C229-5-7631NEC Corporation:ND-57356-701(E)-05

– After that all other cables like DC mains, RF cabling or alarm wires can be installed.– The screen of the RF jumpers has to be grounded before entering the rack via

the cable feeding module, see Fig. 2.49.– If cables are fed through coaxial cable access located at the top of the rack at the

front, the screen has to be grounded like all other coaxial cables.

The figure below shows the location of the external interfaces.

Fig. 2.21 Locations of connection points for external cables

-48V DCantenna cables

Iub linesexternal alarms / commandsground cableexternal reset switch

EMI Panel

front of rack

NB-440

Page 31: Siemens UMTS Node-B NB440 Installation

InstallationNode B

IMN:NB-440

Siemens AG: A50016-G5000-C229-5-7631NEC Corporation: ND-57356-701(E)-05 31

2.6.2 Ground and Power Supply Connections -48 V DCThe NB-440 racks has to be connected to the site specific ground system before startingthe connection of DC mains cable.

An external ground wire (16 mm2, #AWG 6 for USA, copper conductor) has to beconnected on the left or right side ground stud of the rack, which must be attached tothe ground bar on site.

Grounding of the rack must be done by 16mm2 copper wire which is connected to aground bar or a site grounding ring. In the latter case, the ring must be built using 50mm2

(or more) copper inductor.

Connect the NB-440 rack and ground system as follows:

1. Use the nearest ground bar on site.2. Ascertain the distances between the connection points of the ground system

and the ground bolt of the rack.3. Cut the cables to the required length.4. Remove the cable covering at the end to connect to the ground bolt

(length approx. 10 mm) and fix a cable lug M8.5. Connect the prepared cable end to the ground bolt.6. Tighten the nut firmly.

Fig. 2.22 Ground and DC mains connections of the NB-440

The figure above shows the recommended cabling for the power supply andground connections. The recommended cable types as shown in the figure aboveguarantees the proper function of the NB-440, equipped with up to 6 TRX.

The NB-440 will be powered by -48V DC. A 2-pole terminal block of the MSU, locatedin the top of rack, is the connection point for the DC mains wires.

An easily accessible disconnect device is incorporated into the DC mains supplywiring. To isolate the DC mains supply, a 125 A circuit breaker (medium response timeand a contact separation of at least 3 mm) must be installed in the DC distribution boxfor interruption of the -48 V conductor. If there no DC pole grounded, a two-poledisconnect device is necessary.

AC mains

~

=

-48 V + 0 V

125 A

power distributionwith circuit breaker

50 mm2

ground bar

16 mm2

connectionto ground

site ground ring

35 mm2

16 mm2

Page 32: Siemens UMTS Node-B NB440 Installation

IMN:NB-440 InstallationNode B

32Siemens AG:A50016-G5000-C229-5-7631NEC Corporation:ND-57356-701(E)-05

To connect the NB-440 with the DC mains supply equipment point, proceed withthe following steps:

1. Refer to the site documentation for the required information about type and locationof the DC distribution.

2. Check the actual distance between terminal block of the MSU and DC distribution.3. Cut back the wire insulation at the end that is to be connected to the terminal block.4. Fix both DC wires with straps by using the strain relief clamps at the edge of

EMI Panel.5. Insert the wires into the terminals. Use a screwdriver for opening the terminal

springs. Check that all wires are in fixed position.

Fig. 2.23 DC mains terminal block

Fig. 2.24 Connection of the grounding wire

+ 0 V- 48 V

fixed by straps

Page 33: Siemens UMTS Node-B NB440 Installation

InstallationNode B

IMN:NB-440

Siemens AG: A50016-G5000-C229-5-7631NEC Corporation: ND-57356-701(E)-05 33

2.6.3 Iub-Interface - Link EquipmentThe Iub interfaces, located on the EMI Panel, provide the communication links to theneighbouring Node B stations or the controlling RNC.The Iub interfaces can be terminated with Overvoltage Protections (OVPT) whichprotects the boards inside the NB-440 against overvoltage (residual voltage < 1 kV).Two types of OVPT exist: OVPTE1CF for 75 Ω and OVPTE1J1SF for 100/120 Ω cables.If this function is not needed, the Iub interfaces will be terminated with an Iub connector.The IUBCONSFV1 is the termination for 120 Ω lines and the IUBCONCFV1 for75 Ω lines.

Depending on the different cable impedances it is recommended to:– use screened cable containing 8/10 shielded twisted pairs 0,25 mm2 for

100/120 Ω PCM lines, e.g. S-09YS(ST)CY 8x2x0.6/1.2.– use coaxial cables for 75 Ω wiring, e.g. 2YCCY 0.4/2.5 .

The maximum cable length between the Iub interface and the link equipment on sitemust not exceed 42 metres (140 feet).The cable shielding must be connected to the relevant ground pins as close as possible(in order to avoid EMC/RF interfering effects).

2.6.3.1 Iub-Interface for 100/120 Ohm Cable ImpedanceBefore starting the connection of the cables at the Iub-interface of the OVPTE1J1SFor IUBCONCSFV1, prepare the twisted pair cables as shown in the figure below.

Fig. 2.25 Preparation of twisted pair cables, 120 Ohm impedance

1. Cut the cable to the required length (1).2. Cut back the outer insulation approx.13 cm (2).3. Remove approx. 11 cm of the braided shield (3).4. Cut around the outer insulation and shift the insulation ring to the end of the braided

shield (4). Remove the foil shields and the additional plastic wires.

i NOTEUse only mesh shielded twisted pair or coaxial copper cables.

1 5432

Page 34: Siemens UMTS Node-B NB440 Installation

IMN:NB-440 InstallationNode B

34Siemens AG:A50016-G5000-C229-5-7631NEC Corporation:ND-57356-701(E)-05

5. Remove 6 mm of the wires insulation.6. Wrap the exposed cable screen, which will be fixed at the strain relief.

Fig. 2.26 Routing of Iub-cable (example with OVPTE1J1SF)

1. Use straps to fix the cable to the strain relief.2. Insert the wires into the terminals of the OVPTE1J1SF / IUBCONSFV1.3. Insert the additional wire (shielding potential) into one of the ground terminals.4. Lead the additional wire and the uplink and downlink wires on the shortest route

(that means without sleeves) between the strain relief and the screw terminals.5. All unconnected Iub lines (4 wires per line) must be connected to one of the

ground terminals.

Fig. 2.27 Pinning Iub interface at OVPTE1J1SF / IUBCONSFV1

IUB

5_ULA

IUB

5_DLA

Ground

IUB

2_ULA

IUB

2_DLA

Ground

IUB

3_ULB

IUB

3_DLB

IUB

3_ULA

IUB

3_DLA

IUB

4_ULB

IUB

4_DLB

Ground

IUB

4_ULA

IUB

4_DLA

IUB

5_ULB

IUB

5_DLB

IUB

0_ULB

IUB

0_DLB

IUB

0_ULA

IUB

0_DLA

IUB

1_ULB

IUB

1_DLB

Ground

IUB

1_ULA

IUB

1_DLA

IUB

2_ULB

IUB

2_DLB

IUB

6_ULB

IUB

6_ULA

IUB

6_DLB

IUB

6_DLA

IUB

7_ULB

IUB

7_ULA

IUB

7_DLB

IUB

7_DLA

front side of rack

upper row

lower row

Page 35: Siemens UMTS Node-B NB440 Installation

InstallationNode B

IMN:NB-440

Siemens AG: A50016-G5000-C229-5-7631NEC Corporation: ND-57356-701(E)-05 35

2.6.3.2 Iub-Interface for 75 Ohm Cable ImpedanceThe coaxial interface is realized by use of 16 1,0/2,3 coaxial connectors, located at theOVPTE1CF or IUBCONCFV1.

Fig. 2.28 Iub interface with coaxial connectors (example with OVPTE1CF)

For coax cabling with 75 Ω impedance use coaxial cable e.g. 2YCCY 0.4/2.5.The coaxial cables will be prepared as follows:

1. Fix a 1,0/2,3-female connector for each Iub up- and down-line at the end to beconnected to the OVPTE1CF or IUBCONCSFV1.

2. Connect the prepared cable to the matching connectors.3. Use a torque spanner for 1,0/2,3 connectors (35 Ncm).

Fig. 2.29 Iub line connectors of OVPTE1CF / IUBCONCFV1

holes for stress relieving

IUB-uplink line no.

IUB-downlink line no. 1234567 0

1234567 0

front side of rack

Page 36: Siemens UMTS Node-B NB440 Installation

IMN:NB-440 InstallationNode B

36Siemens AG:A50016-G5000-C229-5-7631NEC Corporation:ND-57356-701(E)-05

2.6.3.3 Monitoring Interfaces of the Iub interfacesThe Overvoltage Protection carries 5 6pin DIN41616 test connectors for monitoringthe Iub lines. The following tables show the pin out of the monitoring interfaces.

Fig. 2.30 Pinning of the monitoring interfaces

connector / pin Signal name connector / pin Signal name

X1-1 Iub 0 - ULA X4-1 Iub 4 - DLA

X1-2 Iub 0 - ULB X4-2 Iub 4 - DLB

X1-3 Iub 0 - DLA X4-3 Iub 5 - ULA

X1-4 Iub 0 - DLB X4-4 Iub 5 - ULB

X1-5 Iub 1 - ULA X4-5 Iub 5 - DLA

X1-6 Iub 1 - ULB X4-6 Iub 5 - DLB

X2-1 Iub 1 - DLA X5-1 Iub 6 - ULA

X2-2 Iub 1 - DLB X5-2 Iub 6 - ULB

X2-3 Iub 2 - ULA X5-3 Iub 6 - DLA

X2-4 Iub 2 - ULB X5-4 Iub 6 - DLB

X2-5 Iub 2 - DLA X5-5 Iub 7 - ULA

X2-6 Iub 2 - DLB X5-6 Iub 7 - ULB

X3-1 Iub 3 - ULA X6-1 Iub 7 - DLA

X3-2 Iub 3 - ULB X6-2 Iub 7 - DLB

X3-3 Iub 3 - DLA X6-3 EXTSYNCA

X3-4 Iub 3 - DLB X6-4 EXTSYNCB

X3-5 Iub 4 - ULA X6-5

X3-6 Iub 4 - ULB X6-6

Tab. 2.1 Pinning of monitoring interfaces OVPTE1CF / IUBCONCFV1

1 23 45 6

X7

X8

X9

X10

X11

X12

X1

X2

X3

X4

X5

X6

1 23 45 6

Page 37: Siemens UMTS Node-B NB440 Installation

InstallationNode B

IMN:NB-440

Siemens AG: A50016-G5000-C229-5-7631NEC Corporation: ND-57356-701(E)-05 37

2.6.4 Alarm Collection Terminal - external Signal SensorsThe access for cabling from external signal sensors on site (site inputs) is theAlarm Collection Terminal for base cabinet, ACTM.

The ACTM provides 6 WAGO terminal blocks for connecting of 24 external input alarmsand 8 output commands. The max. wire diameter is limited to 0.5 mm (AWG 28-20).

The alarm terminals are labelled X1 ... X4 , the terminal blocks X9 and X10 are used forconnection of output commands. At the terminal blocks X9 and X10 up to 8 differentelectrical consumers can be connected.The cables will be fixed as shown in the figure below or by screen clamps (not part ofthe ACTM, WAGO part-no. 790-108 for outer diameter up to 8 mm or 790-116 for outerdiameter up to 16 mm).The following figure and tables give information on the terminal assignment.

connector / pin Signal name connector / pin Signal name

X7-1 Iub 0 - ULA X10-1 Iub 4 - DLA

X7-2 Iub 0 - ULB X10-2 Iub 4 - DLB

X7-3 Iub 0 - DLA X10-3 Iub 5 - ULA

X7-4 Iub 0 - DLB X10-4 Iub 5 - ULB

X7-5 Iub 1 - ULA X10-5 Iub 5 - DLA

X7-6 Iub 1 - ULB X10-6 Iub 5 - DLB

X8-1 Iub 1 - DLA X11-1 Iub 6 - ULA

X8-2 Iub 1 - DLB X11-2 Iub 6 - ULB

X8-3 Iub 2 - ULA X11-3 Iub 6 - DLA

X8-4 Iub 2 - ULB X11-4 Iub 6 - DLB

X8-5 Iub 2 - DLA X11-5 Iub 7 - ULA

X8-6 Iub 2 - DLB X11-6 Iub 7 - ULB

X9-1 Iub 3 - ULA X12-1 Iub 7 - DLA

X9-2 Iub 3 - ULB X12-2 Iub 7 - DLB

X9-3 Iub 3 - DLA X12-3 EXTSYNCA

X9-4 Iub 3 - DLB X12-4 EXTSYNCB

X9-5 Iub 4 - ULA X12-5

X9-6 Iub 4 - ULB X12-6

Tab. 2.2 Pinning of monitoring interfaces OVPTE1J1SF / IUBCONSFV1

Page 38: Siemens UMTS Node-B NB440 Installation

IMN:NB-440 InstallationNode B

38Siemens AG:A50016-G5000-C229-5-7631NEC Corporation:ND-57356-701(E)-05

Fig. 2.31 Terminal numbering of the ACTM

The ACTM provides at the connectors X9 and X10 the possibility to switch up to8 electrical consumers via a relay contact (relays is already integrated on ACTM).

X1X2

X3 X4

X9

X10

1 121 121

121 12 1

8

18

!CAUTIONThe signal source of the external alarms (clamping block X1 ...X4) must be a switchingcontact (relais, open collector for rack internal alarms will be possible).It is not allowed to connect a voltage source to the alarm inputs.

Pin no. connector X1Alarm No.

connector X2Alarm No.

connector X3Alarm No.

connector X4Alarm No.

2,4,6,8,10,12 GND (ground) GND (ground) GND (ground) GND (ground)

1 AL_42 AL_36 AL_30 AL_24

3 AL_43 AL_37 AL_31 AL_25

5 AL_44 AL_38 AL_32 AL_26

7 AL_45 AL_39 AL_33 AL_27

9 AL_46 AL_40 AL_34 AL_28

11 AL_47 AL_41 AL_35 AL_29

Tab. 2.3 Pinning ACTM Connectors X1 ... X4

!CAUTIONThe switched current must not exceed 100 mAAC/DC (contact closed) and the maximumswitched voltage is limited to 30 VAC or 30 VDC (contact open). The maximumswitching power is 10 W.

Page 39: Siemens UMTS Node-B NB440 Installation

InstallationNode B

IMN:NB-440

Siemens AG: A50016-G5000-C229-5-7631NEC Corporation: ND-57356-701(E)-05 39

2.6.5 Installation of the Mounting Kit OPEXALIf external alarm sensors are placed outside the building, the MK:OPEXAL(Overvoltage Protection for external Alarms) is required.Each MK:OPEXAL protects up to 10 alarm lines which are connected to the ACTMagainst over-voltage.

Install the MK:OPEXAL in accordance to the following figures.

Fig. 2.32 Contents of the MK:OPEXAL

Pin no. Signal name X10 Signal name X9

1 CMD0P CMD4P

2 CMD0M CMD4M

3 CMD1P CMD5P

4 CMD1M CMD5M

5 CMD2P CMD6P

6 CMD2M CMD6M

7 CMD3P CMD7P

8 CMD3M CMD7M

Tab. 2.4 Pinning ACTM Connectors X10 and X9

screw, dowel and washers 6 mm

ground wire

10 symmetric pair

OPEXAL

cables

cable ties

Page 40: Siemens UMTS Node-B NB440 Installation

IMN:NB-440 InstallationNode B

40Siemens AG:A50016-G5000-C229-5-7631NEC Corporation:ND-57356-701(E)-05

– Drill two holes with 6 mm in diameter and min. 35 mm depth as shown in Fig. 2.33.– Insert the dowels.– Attach the MK:OPEXAL to the wall in vertical position and fix it with screws and

washers.– Connect the cables coming from the external alarm sensors at the left screw termi-

nals of the overvoltage protectors.– Connect the symmetric pair cables at the right screw terminals of the overvoltage

protectors.– Attach the ground wire to the yellow / green WAGO terminal (see Fig. 2.34).– Fix all cables with cable ties at the bracket of the MK:OPEXAL..– Route the cables to the ACTM and the ground wire to the PE-plate of the EMI-panel

(see Fig. 2.35).

Fig. 2.33 Drilling sketch for MK:OPEXAL

max. 30 mmfrom the rack edge220 mm

700 mm

diameter 6 mmdrill hole depth 35 mm

Page 41: Siemens UMTS Node-B NB440 Installation

InstallationNode B

IMN:NB-440

Siemens AG: A50016-G5000-C229-5-7631NEC Corporation: ND-57356-701(E)-05 41

Fig. 2.34 Wall mounted MK:OPEXAL

Fig. 2.35 Routing of external alarm cables

cables fromexternal alarm sensors

symmetric pair cablesto ACTM

ground wireto PE-plate of EMI Panel

Input side Output side

ground bolt

PE-plate

cable tie

ACTM

stress relieving bracket

Page 42: Siemens UMTS Node-B NB440 Installation

IMN:NB-440 InstallationNode B

42Siemens AG:A50016-G5000-C229-5-7631NEC Corporation:ND-57356-701(E)-05

– Fix external alarm cables with cables ties at the stress relieving bracket, so that aproper electrical contact between the bracket and the cable screens is guaranteed.

– Attach the ground wire to the bolt at the PE-plate.– Connect the external alarm cables at the matching WAGO terminals of the ACTM.

2.6.6 Alarm Collection Terminal ACTC - internal AlarmsAdditionally to the site inputs (external alarms) at ACTM, there exists the ACTC boardwhich is used as a connection board to support single connectors for the internal alarmsand the DC supply for the FANs, heatexchangers, microwave equipment, smoke sensorand battery fuses (see Fig. 2.36).

The following table gives information on the connections for environmental alarmsat ACTC.

Fig. 2.36 Connector arrangement at ACTC

Pin no. X12 Signal name Pin no. X8 Signal name

1 AL_1P 1 AL0_P

2 AL_GND 2 AL_GND

3 DC_SMOKE_PUE

4 DC_SMOKE_MUE

Tab. 2.5 Pinning ACTC Connector X12 and X8

Pin no. X9 Signal name Pin no. X10 Signal name

1 AL10_P 1 BB0_BB1

2 BB0_BB1 2 AL_GND

Tab. 2.6 Pinning ACTC Connector X9 and X10

SMOKE RDO

BB0...BB1

1

meaning of abbrevations:RDO: rack door openSMOKE: smoke sensorBB0...1: battery fuse 0...1

18X12

X10

X21X8

X9

Page 43: Siemens UMTS Node-B NB440 Installation

InstallationNode B

IMN:NB-440

Siemens AG: A50016-G5000-C229-5-7631NEC Corporation: ND-57356-701(E)-05 43

2.6.7 Local Maintenance Terminal (LMT) InterfaceA RJ45 connector, located at the front of the Core Controller is the interface fortemporary connection of a Local Maintenance Terminal (LMT), used for commissioningand maintenance purposes. It is also possible to connect the LMT with one of the Hubports at the DC Panel.

Pin no. X21 Signal name

1, 3, 4, 5, 7, 9, 11, 13, 15 AL_GND

2 AL_15P (cabinet input 8)

4 AL_14P (cabinet input 7)

6 AL_13P (cabinet input 6)

8 AL_12P (cabinet input 5)

10 AL_11P (cabinet input 4/OVP)

12 AL_10P (cabinet input 3/BB)

14 AL_9P (cabinet input 2)

16 AL_8P (cabinet input 1)

17 TEMP_SENSE_GND

18 TEMP_SENSE

Tab. 2.7 Pinning ACTC Connector X21

Page 44: Siemens UMTS Node-B NB440 Installation

IMN:NB-440 InstallationNode B

44Siemens AG:A50016-G5000-C229-5-7631NEC Corporation:ND-57356-701(E)-05

2.6.8 Connection of External Reset LineIf a problem occurs to the application software and the Node B is stuck, an operator caninitiate a remote Node B hardware-restart. The Overvoltage protection for ExternalReset Line (OERF) module is the interface to the remote reset button and is located onthe EMI-panel.

The reset will be activated by use of the remote reset button. The short circuit of theterminal clamp causes a closing of the relay contact and perform a reset of the NB-440by setting the system-restart line to ground potential (active low reset).

The reset is performed as long as the reset button is pushed. As interface connector a2 pin terminal Wago-clamp is used. For connection to the remote push button on site,a 2 wire twisted pair cable with a max. wire diameter of 0.5 mm (#AWG 28-20) will beused.

Fig. 2.37 Connection of external reset line

Page 45: Siemens UMTS Node-B NB440 Installation

InstallationNode B

IMN:NB-440

Siemens AG: A50016-G5000-C229-5-7631NEC Corporation: ND-57356-701(E)-05 45

2.6.9 Antenna ConnectionsThe NB-440 has to be connected to the transmit/receive antennas. The antennaconfiguration and the required cabling are dependent on the conditions found at the site.For detailed information refer to the site-specific documentation or use the correspond-ing customer documents.

For installation and service purposes it is useful to know which hardware is connectedto which cell. The numbering, seen from the top of the antenna pole, starts at anazimuth angle of 0˚ (north) and rotates clockwise.The first existing cell whose beam centre line lies at 0˚ or more is defined ascell 0 or sector 0. The next one following in the same sense of rotation is cell 1, etc.In case of an omni cell the cell no. is 0.

Fig. 2.38 Example for cell numbering (top view from the antenna pole)

2.6.9.1 Preparation of Antenna Jumper CablesShort jumper cables with a max. diameter 1/2” have to be used for connections betweenthe antenna cables and the front connectors of the DUAMCOs, because the thick cablesfrom the antenna are not able to enter the racks.With regard to overvoltage protection it is recommended to ground the outerconductor of antenna feeder cables where they are connected with the jumper cablesoutside the NB-440.

sector width 120˚

sector angle

directional antenna

pole

sector 0

sector 1

sector 2

N

beam centre line

Page 46: Siemens UMTS Node-B NB440 Installation

IMN:NB-440 InstallationNode B

46Siemens AG:A50016-G5000-C229-5-7631NEC Corporation:ND-57356-701(E)-05

These jumper cables must be fabricated of 1/2” highly flexible coaxial cable on-site,if no pre-fabricated cables should be used.Fabricate the jumper cables in steps as shown in the following figures.

Fig. 2.39 Tools for jumper fabrication

Fig. 2.40 Parts of the connector unit kit (example)

– Measure the distance between the end of the antenna feeder cable and the frontconnectors of the combining modules.

– Saw the cable to the required length. Do not deform cable outer conductor, whenusing too much pressure for sawing !

hot air gun(or propane/ butane blow torch)

cable trimming tool

cable knife

open-ended spanners(jaw opening 21mm and25 mm)

connector head

corrugation nut

fitting ring

emery paper

cleaning tissue

heat protection tape

heatshrink sleeve

Page 47: Siemens UMTS Node-B NB440 Installation

InstallationNode B

IMN:NB-440

Siemens AG: A50016-G5000-C229-5-7631NEC Corporation: ND-57356-701(E)-05 47

Fig. 2.41 Using the trimming tool

Fig. 2.42 Removal of isolation and deburring of inner conductor

Fig. 2.43 Removal of metal particles

1

2

rotate clockwise

heatshrink sleeve

fitting ring

Page 48: Siemens UMTS Node-B NB440 Installation

IMN:NB-440 InstallationNode B

48Siemens AG:A50016-G5000-C229-5-7631NEC Corporation:ND-57356-701(E)-05

Fig. 2.44 Assembly of the connector unit

Fig. 2.45 Fixing of connector unit , removal of outer insulation

Fig. 2.46 Handling of heat protection tape and shrink sleeve

corrugation nut

fitting ring

connector head

20 mm

heat protection tape

heat shrink sleeve

Page 49: Siemens UMTS Node-B NB440 Installation

InstallationNode B

IMN:NB-440

Siemens AG: A50016-G5000-C229-5-7631NEC Corporation: ND-57356-701(E)-05 49

Fig. 2.47 Shrinkage and removal of the visible heat protection tape

The antenna cables must be routed through the EMI Panel forward to the 7/16” frontconnectors of DUAMCOF.

Fig. 2.48 Max. dimensions of antenna connectors

Connect the antenna cables to the combining equipment as follows:

1. Unscrew the front part of the cable feeding module.2. Route the antenna jumpers to the DUAMCOF RF connectors.3. For grounding strip back outer insulation approx. 40-45 mm for proper contact with

the metal lids of the cable feeding module (see Fig. 2.49).4. Feed the jumpers through the cable feeding module forward to the front connectors

of antenna combiners and fix them at the connectors TX/RX.5. Bend the jumpers into the correct position for easy closing of cable feeding module.6. Screw the front part of the cable feeding module in its original position.

remove the over lengthof heat protection tape

hot air gun or butane torch

heated air

i NOTENote that being able to close the doors means that the depth of the right angleconnector is not allowed to exceed 45 mm.

max. 45 mm

max. 1/2” jumper cable (high flexible)width across flats 32

Page 50: Siemens UMTS Node-B NB440 Installation

IMN:NB-440 InstallationNode B

50Siemens AG:A50016-G5000-C229-5-7631NEC Corporation:ND-57356-701(E)-05

Fig. 2.49 Routing of antenna jumper cables

i NOTEThe outer insulation of the antenna cables must be removed for proper ground contactat the lids of the cable feeding module (see Fig. 2.49).

unscrew

iNOTEAfter the installation of the antenna system is completed, collect the following antennacable parameters and document them for the customer:length and type of all antenna feeder cableslength and type of all antenna jumper cablesThe same type of antenna feeder cables and jumper cable should be used within thesame sector.The length differences between the main and diversity paths within the same sectorshould be less than < = 1m. A cable length accuracy < = 1/2 m is recommended.Information about the cable parameters supplied by subcontractors may be required.

Page 51: Siemens UMTS Node-B NB440 Installation

InstallationNode B

IMN:NB-440

Siemens AG: A50016-G5000-C229-5-7631NEC Corporation: ND-57356-701(E)-05 51

2.6.10 Installation of the Tower Mounted AmplifiersThe Tower Mounted Amplifiers (TMAF or DTMAF) are the RF units (external to theNodeB rack) which provide the means to feed the overall NodeB downlink signal to oneTX/RX antenna and to amplify, with low noise figure, the overall NodeB uplink signalcoming from the same TX/RX antenna.

The TMAF / DTMAF should be placed as close to the antenna as possible.It will be supplied and supervised by the multicoupling equipment (DUAMCOF) in therack it is connected to.

Fig. 2.50 Position of TMAF/DTMAF in the system

Fig. 2.51 Bottom view of the TMAF (measures in mm)

NodeB

TMAF TMAF

NodeB

Linear-Pol Antennas

Feeder 1 Feeder 2 Feeder 1 Feeder 2

DTMAF

Cross-Pol Antenna

FDDFDD

60.5

78

175

47

68

to Node B to antenna

ground screwdraining pipe

Page 52: Siemens UMTS Node-B NB440 Installation

IMN:NB-440 InstallationNode B

52Siemens AG:A50016-G5000-C229-5-7631NEC Corporation:ND-57356-701(E)-05

Fig. 2.52 Fixing facilities of TMAF (measures in mm)

Fig. 2.53 Bottom view of the DTMAF (measures in mm)

holes for wall mounting

holes for hose clip

24

296

77

78

175

47

68

to Node

ground screwdraining pipe

0 1 30

Page 53: Siemens UMTS Node-B NB440 Installation

InstallationNode B

IMN:NB-440

Siemens AG: A50016-G5000-C229-5-7631NEC Corporation: ND-57356-701(E)-05 53

Fig. 2.54 Top view of the DTMAF (measures in mm)

Fig. 2.55 Fixing facilities of DTMAF (measures in mm)

Two 7/16 female connectors, located at the bottom of the TMAF (lettered ANT andNode B) are the interfaces for connections of the feeder cable towards to Node B andto TX/RX antenna with appropriate antenna jumper cabels 1/2”.

47

to antenna

77

1 030

holes for wall mounting

holes for hose clip

24

340

Page 54: Siemens UMTS Node-B NB440 Installation

IMN:NB-440 InstallationNode B

54Siemens AG:A50016-G5000-C229-5-7631NEC Corporation:ND-57356-701(E)-05

The DTMAF provides two 7/16 female connectors at the bottom for the connection withthe Node B (lettered NodeB 0 and NodeB 1) and on the top both 7/16 connectors forconnecting the jumper cables to the antennas (lettered ANT 0 and ANT 1).

Each TMAF / DTMAF shall be grounded to the pole, therefore a grounding wire has tobe prepared for each device on site.The mounting plate has a screw with a locking washer attached to it and a threaded holefor connection of the grounding wire (see Fig. 2.51 and Fig. 2.53).The grounding wire cable lug must have the right size for the M8 ground screw. Thecross section of the ground wire must be not less than 16 mm2.

The other end of the grounding wire should be safely connected to a well grounded pointon the pole.

Care must be taken that the draining pipe (see Fig. 2.51 and Fig. 2.53) is pointed down-wards. The draining pipe is factory mounted. If it, for any reason, would be loosened, itshould be tightened again with a sufficient torque wrench, however not exeeding2.2 Nm.

The draining pipe must never be obstructed or covered with paint which would impedethe venting and draining of the housing.

2.6.10.1 Pole Mounting with Hose ClipsThe hose clips surrounds the pole and are fitted into the corresponding openings of themounting plate (see Fig. 2.56). This is the situation just before tightening the hose clips.

For the mounting, the following steps can generally be recommended. First connect theTMAF to the antenna feeder cable. Take into consideration that the antenna feeder oftenis very stiff and rather heavy. The position of its coaxial connectors therefore oftendetermines the position of the TMAF on the pole.

1. Open the hose clips by pressing the “button” at the end of the clip lock and thensmoothly pull out the perforated metal band.

2. Move the metal band of the hose clip gently into the openings of the mounting plate.3. Close the hose clip loosely around the pole.4. Shift the TMAF into the correct mounting position.5. Tighten the hose clip screws carefully, but do not over-tighten (see Fig. 2.57).6. Connect the TMAF first to the antenna feeder cable (NodeB) and then to the antenna

jumper cable (ANT). The tightening torque must be 25 - 30 Nm.7. Connect the grounding wire with the TMAF ground screw.

Check the tightening torque, 5 Nm.8. The use of self-vulcanising tape as an environmental protection of the connectors

is recommended.

i NOTEThe TMAF and the DTMAF can be pole-or wall mounted in vertical position only !

i NOTEPay attention to the thermal dimensional changes of the antenna feeder cables.

Page 55: Siemens UMTS Node-B NB440 Installation

InstallationNode B

IMN:NB-440

Siemens AG: A50016-G5000-C229-5-7631NEC Corporation: ND-57356-701(E)-05 55

Fig. 2.56 Fitting of the hose clips (example with TMAF)

Fig. 2.57 Pole mounting of the TMAF

hose clips

tighten

tighten

Page 56: Siemens UMTS Node-B NB440 Installation

IMN:NB-440 InstallationNode B

56Siemens AG:A50016-G5000-C229-5-7631NEC Corporation:ND-57356-701(E)-05

Fig. 2.58 Antenna cable connection at the TMAF

2.6.10.2 Wall Mounting of TMAFThe TMAF may be mounted on a wall by means of suitable screws (not suppliedwith the TMAF).

The corresponding holes in the mounting plate have a diameter of 9 mm. The properway of mounting the TMAF on a wall varies from case to case. The best method canonly be decided by the installer. Please note, however, that the wall itself probably doesnot provide adequate grounding, it may be insulated.

Fig. 2.59 Drilling sketch for wall mounting

to antenna

to NodeBground bolt

130 mm

296

mm

175 mm

278

mm

130 mm

340

mm

175 mm

322

mmDTMAF

TMAF

Page 57: Siemens UMTS Node-B NB440 Installation

InstallationNode B

IMN:NB-440

Siemens AG: A50016-G5000-C229-5-7631NEC Corporation: ND-57356-701(E)-05 57

2.6.11 Preparation of the Top CoverAfter the connection of external cables, prepare the top cover for setup on the top ofthe rack. The top cover features pre-fractured parts which can be removed in order toroute cables through to the infrastructure equipment on site. See figure below.

The required number of pieces can be removed in easy manner by break out at theperforation. After that refinish the paint coat at all cracks with the paint retouch kit(Siemens Serial No. A500-C101-B261).

Fig. 2.60 Removable pieces and paint retouch of the top cover

!CAUTIONIt is absolutely necessary to prepare and connect an adequate grounding cable to theTMAF‘s grounding point.

!CAUTIONPay attention to the thermal dimensional changes of the antenna feeder cables.

paint retouch neccessary

Page 58: Siemens UMTS Node-B NB440 Installation

IMN:NB-440 InstallationNode B

58Siemens AG:A50016-G5000-C229-5-7631NEC Corporation:ND-57356-701(E)-05

2.6.12 Setup of the System CablingThe system cabling consists of connections are installed on the front of the rack.Cabling configurations depend on the different equipping variants and the cellconfiguration of the site.

The system cabling is already installed in the factory. This section provides informationfor setup additional system cables for extension of RF modules or the cell configurationmust be changed.

The list of variant numbers (content of the site specific documentation) is needed forthe correct setup of the cabling between the modules.

Fig. 2.61 Cabling between TRX, LPA and DUAMCOF (2 Carrier, 1 Cell)

LPA 0

TX

RF out

DUAMCOF

TX 0RX 0

RX 1

RX 0

RX 1

TX 1

LPA 1

TX

RF out

TRX 0

TX

RX 0

RX 1

TRX 3

TX

RX 0

RX 1

!CAUTIONTo avoid short circuits, do not pack the overlength of system cables in the free spacebetween the fans of the A-shelf and the EMI-filters of the mains supply unit.

!CAUTIONTo obtain the minimum bending radius of 35 mm (RG 142) and 3,5 mm(semi-rigid .86 AI). A bending tool should be used.Fix the system cables at SMA connectors with a torque wrench set 100 Ncm and atN-type connectors with a torque wrench set 1,10 Nm.Terminate all unused connectors of the antenna combiners with 50 Ohm load resistors!

Page 59: Siemens UMTS Node-B NB440 Installation

InstallationNode B

IMN:NB-440

Siemens AG: A50016-G5000-C229-5-7631NEC Corporation: ND-57356-701(E)-05 59

The following table provides an overview of the types and functionality of theprefabricated cables.

Here a routing sketch for the DUAMCOF and LPA left/right hand cabling is given.

Fig. 2.62 LPA-DUAMCOF cabling

connection code number length path connector cabletype

DUAMCOF-left hand side LPA

C39195-Z80-C221

80 mm TX N-con. 90˚, male/N-con. 90˚; male

RG 142

DUAMCOF-right hand side LPA

C39195-Z80-C222

250 mm TX N-con. 90˚, male/N-con. 90˚; male

RG 142

Semi-rigid System Cable

TRX - LPATRX - DUAMCOF

C39195-Z80-C219

1800 mm TX/RX

SMA,90˚,male/SMA,90˚,male

semi-rigid.86 Al

alternatively: Flexible System Cable

TRX - LPATRX - DUAMCOF

S30864-X217-A20

1800 mm TX/RX

SMA,90˚, male/SMA,90˚, male

coaxcable,flexible

Tab. 2.8 Functionality of system cables

iThe minimum single bending radius of the flexible cables is 20 mm. The minimumrepeated bending radius is 40 mm. The exeptional length of the cables have to be storedinside the vertical space between the subracks and the inside rack wall.The horizontal space below each subrack have not to be used to store the extra lengthof the system cables or anything else. This space is used as an air inlet for cooling.

#0 #0 #1

LPA

DUACOF

LPA

LPA left/right hand cabling

C39195-Z80-C221

C39195-Z80-C222

Page 60: Siemens UMTS Node-B NB440 Installation

IMN:NB-440 InstallationNode B

60Siemens AG:A50016-G5000-C229-5-7631NEC Corporation:ND-57356-701(E)-05

2.7 Post Installation NotesThe following instructions must carried before leaving the site:– At the end of the working day enable any alarms that should be active.– Contact the Network Control Center to announce your departure.– Close and lock the rack doors.– Ensure the site is secure or hand over to the person in charge / caretaker.

If all installation activities are finished, any garbage should be cleared from site.Remove all packing material for recycling.

Page 61: Siemens UMTS Node-B NB440 Installation

InstallationNode B

IMN:NB-440

Siemens AG: A50016-G5000-C229-5-7631NEC Corporation: ND-57356-701(E)-05 61

3 Appendix

3.1 Checklist for NB-440 Installation

Check Item Yes No

Grounding

Node B connected to ground as described in section “Ground andPower Supply Connections -48V DC”

Cable screens of all cables connected to ground at the cablewindow of the building

Power Supply

Cross section of power supply cable sufficient

Proper disconnect and overcurrent device installed

power supply connection correspondend to TNS-or TT Networkrequirements

Cable window of the installation building equipped with lightningconductor

Cross section correspondend to cable length

External Alarms

External alarm cables with braided screen

Cable screen contacted to metal lid of cable feeding module

Cable screen contacted to ground at both ends

Overvoltage protection equipment present and correct installed

IuB cables

IuB cables with braided screen

Cable screens connected with EMI panel of rack

Cable screen contacted to ground at both ends

NTPM connector for cable screens correspondend toEMC requirements

Overvoltage protection equipment present and correct installed

Antenna Cables

Outer conductor of antenna cables connected to ground atantenna window

Grounding of antenna cables between antenna and antenna win-dow correpondend to grounding guideline

Antenna cable conductor protected against humidity

Cable parameter parameters collected and part of the customerdocumentation

Tab. 3.1 Checklist for NB-440 Installation