10
Simplified generic wind turbine models for HVDC Offshore Projects siemens.tld/keyword restricted © Siemens AG 2018

Simplified generic wind turbine models for HVDC Offshore

  • Upload
    others

  • View
    6

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Simplified generic wind turbine models for HVDC Offshore

Simplified generic wind turbine models for HVDC Offshore Projects

siemens.tld/keywordrestricted © Siemens AG 2018

Page 2: Simplified generic wind turbine models for HVDC Offshore

restricted © Siemens AG 201811.10.2018Seite 2 Ralf Toma / EM TS LTS ENEC-HVDC SE RTS

Simplified generic wind turbine models for HVDC Offshore ProjectsContent

• Motivation 3

• Model example: full scale converter wind turbine generator 4

• Test results 7

• Project Test Configuration 9

Page 3: Simplified generic wind turbine models for HVDC Offshore

restricted © Siemens AG 201811.10.2018Seite 3 Ralf Toma / EM TS LTS ENEC-HVDC SE RTS

Simplified generic wind turbine models for HVDC Offshore ProjectsMotivation

• Wind turbine models from contractors not availableduring project execution

• Single Source (Matlab/Simulink) for offline and realtimesimulation

Page 4: Simplified generic wind turbine models for HVDC Offshore

restricted © Siemens AG 201811.10.2018Seite 4 Ralf Toma / EM TS LTS ENEC-HVDC SE RTS

Simplified generic wind turbine models for HVDC Offshore ProjectsModel example: full scale converter wind turbine generator(1/3)

Detailed model complex focus on system behaviour computational-intensive scaling problematic

Controlled voltage source simple focus on grid behaviour low computational effort scaling simple

Modeling approach:

Page 5: Simplified generic wind turbine models for HVDC Offshore

restricted © Siemens AG 201811.10.2018Seite 5 Ralf Toma / EM TS LTS ENEC-HVDC SE RTS

Simplified generic wind turbine models for HVDC Offshore ProjectsModel example: full scale converter wind turbine generator(2/3)

Clarke-Transformation

Park-Transformation

Power control

Current control

u_MV

i_MV

u_α,β

i_α,β

u_d,q

i_ref

Control mode selection

p_ref p_ref_final

Park/Clarke-Transformation

Generic control:

Page 6: Simplified generic wind turbine models for HVDC Offshore

restricted © Siemens AG 201811.10.2018Seite 6 Ralf Toma / EM TS LTS ENEC-HVDC SE RTS

Simplified generic wind turbine models for HVDC Offshore ProjectsModel example: full scale converter wind turbine generator(3/3)

current / voltage measurement

AC AC

Inverter model choke Dristubtion transformer

Grid transformer

AC equivalent

Generic control signals

0.69kV/33kV 33kV/155kV

Low Voltage (LV) Medium Voltage (MV) High Voltage (HV)

Simple Benchmark model:

Implementation in PSCAD and RTDS

Page 7: Simplified generic wind turbine models for HVDC Offshore

restricted © Siemens AG 201811.10.2018Seite 7 Ralf Toma / EM TS LTS ENEC-HVDC SE RTS

Simplified generic wind turbine models for HVDC Offshore ProjectsTest results (1/2)

Three phase to ground fault on HV bus

Page 8: Simplified generic wind turbine models for HVDC Offshore

restricted © Siemens AG 201811.10.2018Seite 8 Ralf Toma / EM TS LTS ENEC-HVDC SE RTS

Simplified generic wind turbine models for HVDC Offshore ProjectsTest results (2/2)

Single phase to ground fault on HV bus

Page 9: Simplified generic wind turbine models for HVDC Offshore

restricted © Siemens AG 201811.10.2018Seite 9 Ralf Toma / EM TS LTS ENEC-HVDC SE RTS

Simplified generic wind turbine models for HVDC Offshore ProjectsProject Test Configuration

Simulink

Wind Park Control model

HIL – Testconfiguration

RTDS

Electrical Wind Park & HVDC Model

Hardware

HVDC-Control

GTIO Connectionconvert

Offline – Testconfiguration

PSCAD

Electrical Wind Park & HVDC Model

PSCAD

HVDC-Control

convertInt.IO

Connection

Page 10: Simplified generic wind turbine models for HVDC Offshore

restricted © Siemens AG 201811.10.2018Seite 10 Ralf Toma / EM TS LTS ENEC-HVDC SE RTS

Simplified generic wind turbine models for HVDC Offshore Projectscontact page

Thank you for your attention!Any questions?Ralf TomaSystem EngineerEM TS LTS ENEC-HVDC SE RTS

Freyeslebenstraße 191058 Erlangen

Phone: +49 9131 17 37846E-mail: [email protected]