Modbus ASCII vs Modbus RTUData formats
To review, we can see that each byte of data can be represented in different ways.
Binary (base2): 10101110 2 characters 0 and 1
Decimal (base10): 174 10 characters 0 through 9
Hexadecimal (base 16): AE 16 characters 0 through F
ASCII (base 256): 256 different characters
Message Delimiting
In Modbus RTU, bytes are sent consecutively with no space in between them with a3-1/2 character space between messages for a delimiter. This allows the software toknow when a new message is starting.
Any delay between bytes will cause Modbus RTU to interpret it as the start of a newmessage. This keeps Modbus RTU from working properly with modems.
Modbus ASCII marks the start of each message with a colon character " : " (hex 3A).The end of each message is terminated with the carriage return and line feedcharacters (hex 0D and 0A). This allows the space between bytes to be variablemaking it suitable for transmission through some modems.
Byte Size
In Modbus RTU each byte is sent as a string of 8 binary characters framed with astart bit, and a stop bit, making each byte 10 bits.
In Modbus ASCII, the number of data bits is reduced from 8 to 7. A parity bit isadded before the stop bit which keeps the actual byte size at 10 bits.
Split Data bytes
In Modbus ASCII, each data byte is split into the two bytes representing the twoASCII characters in the Hexadecimal value. For example,
Modbus Mode data (ASCII) data (hex) data (binary)
Simply Modbus - Data Communication Test Software - Modbus ASCII ... http://www.simplymodbus.ca/ASCII.htm
1 of 4 3/5/2015 8:56 PM
Modbus RTU AE 1010 1110Modbus ASCII A , E 41 , 45 100 0001 , 100 0101
The range of data bytes in Modbus RTU can be any characters from 00 to FF.The range of data bytes in Modbus ASCII represent only the 16 hexadecimalcharacters. Therefore, every data byte in Modbus ASCII must be one of these 16:
ASCII hex binary ASCII hex binary0 30 011 0000 8 38 011 10001 31 011 0001 9 39 011 10012 32 011 0010 A 41 100 00013 33 011 0011 B 42 100 00104 34 011 0100 C 43 100 00115 35 011 0101 D 44 100 01006 36 011 0110 E 45 100 01017 37 011 0111 F 46 100 0110
Error Checksum - LRC Calculation
As mentioned earlier, each Modbus RTU message is terminate with two errorchecking bytes called a CRC or Cyclic Redundancy Check. Similarly, ModbusASCII is terminated with an error checking byte called an LRC or LongitudinalRedundancy Check.
Here is a spreadsheet CRC calculator for messages up to 16 bytes.To download a copy, right click and select Save Target As...
The calculation of the LRC is much easier than the CRC.To calculate the LRC: 1. Add up all the data bytes in the message (before converting to ASCII andwithout the initial colon and final CR/LF). 2. Throw away any bits that carry over 8 bits. 3. Make the result negative (by twos compliment) to get the LRC byte.
The sum of the resulting byte stream with the LRC will then be 0 since adding thenegative subtotal will make the final total zero.
For example, this command shows the data bytes required to request the content ofanalog output holding registers 40108 to 40110 from the slave device with address17.
11 03 00 6B 00 03
Add the bytes:decimal hex binary
17 11 0001 0001
Simply Modbus - Data Communication Test Software - Modbus ASCII ... http://www.simplymodbus.ca/ASCII.htm
2 of 4 3/5/2015 8:56 PM
3 03 0000 00110 00 0000 0000
107 6B 0110 10110 00 0000 00003 03 0000 0011
total:decimal hex binary
130 82 1000 0010
two's compliment (make negative) to get the LRCdecimal hex binary
-130 7E 0111 1110
total of the entire message including the LRCdecimal hex binary
0 00 0000 0000
The single hex LRC byte is 7E
The LRC byte is then split into two ASCII bytes with the rest of the data.
The two ASCII bytes for the LRC are then 37 and 45
ASCII vs RTU example:
Using the same example shown above to request registers 40108 to 40110 from slaveaddress 17.
11 03 00 6B 00 03
The complete ASCII request is made by first adding the message delimitingcharacters. A colon is added to the start of the message, the LRC, carriage returnand line feed are added to the end:
: 1 1 0 3 0 0 6 B 0 0 0 3 7 E CR LF
Each character is now treated as an ASCII character and replaced with it's hex valueto give the final message.
3A 3131 3033 3030 3642 3030 3033 3745 0D 0A
This Modbus ASCII request size is 17 bytes (170 bits)
...............
The equivalent Modbus RTU message would be:
Simply Modbus - Data Communication Test Software - Modbus ASCII ... http://www.simplymodbus.ca/ASCII.htm
3 of 4 3/5/2015 8:56 PM
11 03 00 6B 00 03 76 87
This Modbus RTU request size is 8 bytes (80 bits)