Home About MODBUS fc01 fc02 fc03 fc04 fc05 fc06 fc15 fc16 ASCII TCP exceptions About Enron MODBUS RTU Master RTU Slave TCP Client Download Purchase Contact Read Input Registers (FC=04) Request This command is requesting the content of analog input register # 30009 from the slave device with address 17. 11 04 0008 0001 B298 11: The Slave Address (17 = 11 hex) 04: The Function Code (read Analog Input Registers) 0008: The Data Address of the first register requested. (30009-30001 = 8) 0001: The total number of registers requested. (read 1 register) B298: The CRC (cyclic redundancy check) for error checking. Response 11 04 02 000A F8F4 11: The Slave Address (17 = 11 hex) 04: The Function Code (read Analog Input Registers) 02: The number of data bytes to follow (1 registers x 2 bytes each = 2 bytes) 000A: The contents of register 30009 F8F4: The CRC (cyclic redundancy check). Home FAQ Enron Download Purchase Contact Copyright © 2013 Simply Modbus. All rights reserved Simply Modbus - Function Code 04 - Read Input Registers http://www.simplymodbus.ca/FC04.htm 1 of 1 3/5/2015 8:55 PM

Simply Modbus - Function Code 04 - Read Input Registers

Embed Size (px)

DESCRIPTION

Simply Modbus - Function Code 04 - Read Input Registers

Citation preview

  • Home

    About

    MODBUSfc01

    fc02

    fc03

    fc04

    fc05

    fc06

    fc15

    fc16

    ASCII

    TCP

    exceptions

    About

    Enron

    MODBUS

    RTU Master

    RTU Slave

    TCP Client

    Download

    Purchase

    Contact

    Read Input Registers (FC=04)Request

    This command is requesting the content of analog input register # 30009from the slave device with address 17.

    11 04 0008 0001 B298

    11: The Slave Address (17 = 11 hex)04: The Function Code (read Analog Input Registers)0008: The Data Address of the first register requested. (30009-30001 = 8)0001: The total number of registers requested. (read 1 register) B298: The CRC (cyclic redundancy check) for error checking.

    Response

    11 04 02 000A F8F4

    11: The Slave Address (17 = 11 hex)04: The Function Code (read Analog Input Registers)02: The number of data bytes to follow (1 registers x 2 bytes each = 2 bytes)000A: The contents of register 30009F8F4: The CRC (cyclic redundancy check).