10

Click here to load reader

Simulation of Fault Diagnosis in the Oil Immersed Transformer Using Dissolved Gas Analysis

Embed Size (px)

DESCRIPTION

The IEEE standard classifies transformer conditions into 4 discrete deteriorating states, with the criteria of combustible gases as by product of insulation deterioration .Dissolved Gas Analysis is a diagnostic and maintenance tool used in machinery. In this pr1oject the fault diagnosis is achieved by means of DGA using modified Triangle simulation method with the help of MATLAB software package.

Citation preview

Page 1: Simulation of Fault Diagnosis in the Oil Immersed Transformer Using Dissolved Gas Analysis

Simulation of Fault Diagnosis in the Oil Immersed Transformer using

Dissolved Gas Analysis.

R.Arumugama, Mrs.Indra Getzy David

b and Dr.M.Rajaram

c

Electrical and Electronics Engineering Department,

Government College of Engineering, Tirunelveli,

a [email protected] ,[email protected], crajaramgct@ rediffmail.com

Abstract: The IEEE standard classifies transformer conditions into 4 discrete deteriorating states, with the

criteria of combustible gases as by product of insulation deterioration .Dissolved Gas Analysis is a diagnostic

and maintenance tool used in machinery. Duval has used three hydrocarbon gases to diagnose the faults. In this

paper the fault diagnosis is achieved by means of DGA using modified Duval’s Triangle simulation method. Index terms- dissolved gas analysis (DGA), fault diagnosis, power transformer.

I. INTRODUCTION

Most of our electrical facilities were commissioned in the late 1950’s .In South India the electrical switch gear and

systems are nearly 50 years old in certain substations. Depending upon the environment and application of the equipment

they may be at or nearer the end of their useful lives. Transformers are some of the most efficient Electrical machines with

some large units able to transfer 99.75%of their input power to their output. Small transformers do not generate significant

heat and cooled by air circulation and radiation of heat .Power transformers that are rated up to several hundred kVA can be

adequately cooled by the natural convection air cooling, sometimes assisted by air circulator. In larger transformer part of the

problem is removal of the heat. Some power transformers immersed in the oil that both cooled and insulate the windings.

Temperatures above rated will damage the winding insulation. Mineral oils are used in the transformer tank for insulation

and also as a media for heat transfer .The oils are the mixture of many different hydrocarbon molecules which decompose

under high thermal and electrical stress within the transformer during the period of service .The critical changes are the breaking of carbon-hydrogen and carbon-carbon bonds as a result of which different gases are formed due to the presence of

individual hydrocarbon and the distribution of energy and temperature in the neighborhood of the fault. The IEEE has

provided the interpretation of the gases generated in the transformer oil and the corresponding standards for evaluating the

condition of transformer oil insulation based on Dissolved Gas Analysis results.[1]Dissolved gas Analysis data is used to

estimate the failure rate of deterioration of insulation oil in the transformer. Dissolved gas analysis, or DGA, is a diagnostic

and maintenance tool used in machinery. The study of gases from transformers can be used to give an early indication of

abnormal behavior of transformer and may indicate appropriate action that may be taken on the equipment before it suffers

great damage.

TABLE 1. MAIN GASES ANALYZED BY DGA

Hydrogen H2

Methane CH4

Ethane C2H

6

Ethylene C2H

4

Acetylene C2H

2

Carbon monoxide CO

Carbon dioxide CO2

Oxygen O2

Nitrogen N2

Page 2: Simulation of Fault Diagnosis in the Oil Immersed Transformer Using Dissolved Gas Analysis

The conventional Buchholz relay and gas collector relay are universally used. However, they have limitation that

enough gas must be generated, first to saturate the oil full and then to come out of solution and collect in the relay, typically

10-15% of gas by volume of oil, has to be generated for it to come out of the solution, often by the time the bucholz relay was

never meant to be a diagnostic device. The DGA is a very sensitive technique and detect gas in ppm (microlitre/litre) of oil.

The main gases formed by decomposition of oil and paper are summarized in Table 1. These gases dissolve in oil or

accumulate above it and are analyzed by DGA. Some laboratories also report the contents of C3

and C4

hydrocarbon gases

formed.

II.FAULTS

There are four basic types of faults, which can occur in the transformer:

Arcing or high current break down.

Low energy sparking or partial discharges.

Localized overheating or hot spots

General over heating due to inadequate cooling or sustained overloading.

Each of the fault results in thermal degradation of the oil either alone or in combination with paper insulation. This gives

rise to the evolution of various hydrocarbon gases, hydrogen and oxides of carbon, in quantities depending on the type of

fault. Heavy current arcing is characterized by the evolution of significant quantities of Hydrogen (H2) and acetylene (C2H2).

If the arcing also involves paper insulation, the oxide of carbon will also be present. Partial discharge usually results in

evolution of hydrogen and lower order hydrocarbons. Localized heating or hot spot gives rise to Methane and Ethane in

appreciable amount. Prolonged overloading or impaired heat transfer can cause CO and CO2 to be generated due to

overheating paper insulation. To ensure uninterrupted and economical supply the trouble free performance of vital electrical

equipments like power transformers during service is a matter of great importance. They are often subjected to complex

environmental condition and variable thermal and electrical stresses. Efforts have been made to assess the health of the transformer during service through a series of diagnostic tests. In a new transformer, typical hydrocarbon gases concentration

for good new oil after vacuum filtration would be within 5 ppm DGA shall be repeated once a month after commissioning

and then at intervals as found necessary.

Mineral insulating oils are complex mixtures of hydrocarbon molecules, in linear (paraffinic) or cyclic (cycloaliphatic or

aromatic) form, containing CH3, CH

2 and CH chemical groups bonded together. Scission of some of the C-H and C-C bonds

as a result of thermal or electrical discharges will produce radical or ionic fragment such as H*, CH3*, CH

2*, CH* or C*,

which will recombine to form gas molecules such as hydrogen ( H-H ), methane ( CH3-H ), Ethane ( CH

3-CH

3 ), ethylene (

CH2=CH

2 ) or acetylene ( CH ≡CH ). More and more energy is required to form the above chemical bonds. Hydrogen (H

2),

methane (CH4) and ethane (C

2H

6) are thus favored at low energy level, such as in corona partial discharges or at relatively

low temperatures ( < 500 °C ), ethylene (C2H

4) at intermediate temperatures, and acetylene (C

2H

2) at very high temperatures (

> 1000 °C ) such as in arcs.

III.FAULT DIAGNOSIS

The main diagnostic methods used are:

The IEEE methods ( Dornenburg, Rogers and key gases methods )

The IEC ratio codes

The Duval Triangle

The Dornenburg, Rogers and IEC codes compare gas ratios such as CH4/H

2 , C

2H

2/C

2H

4 and C

2H

4/C

2H

6. The key gas

method is based on the 2 or 3 main gases formed. And the Duval Triangle on the relative proportions of 3 gases (CH4, C

2H

4

and C2H

2). One drawback of the gas ratio methods (Dornenburg, Rogers, IEC) is that some DGA results may fall outside the

ratio codes and no diagnosis can be given (unresolved diagnoses). This does not occur with the Triangle method because it is

a closed system rather than an open one.

Page 3: Simulation of Fault Diagnosis in the Oil Immersed Transformer Using Dissolved Gas Analysis

Fault Codes:

PD Partial Discharge

D1 Low energy electrical discharge

D2 High energy electrical discharge

DT Indeterminate thermal fault or Electrical discharge

T1 Low range thermal fault (below 300C)

T2 Medium range thermal fault (300-700C)

T3 high range thermal fault (above 700C)

The most severe faults, in terms of type and location, are generally considered as :

high-energy arcing D2 in paper (and in oil).

medium-to-high temperature faults T2-T3 in paper (> 250 °C)

low energy arcing D1 in paper (tracking, arcing)

high temperature faults T3 in oil (> 700 °C)

The less severe faults, which can often be tolerated for relatively long periods of time as long as they don’t evolve

into a more severe one are:

low-energy discharges PD/D1 in oil (corona, sparking)

low temperature faults T1 in paper (< 150 °C)

medium temperature faults in oil (< 500 °C).

these faults are difficult to find by visual inspection

IV. TESTING

DGA is one such powerful diagnostic tool which helps to detect faults at an early stage by detecting abnormal

changes in the composition of gasses dissolved in the transformer oil, before the other protective gadgets like buchholz relay and the other respond. DGA has proved to be reliable means of establishing the healthiness of a transformer which have

tripped by suspected maloperation of differential protection (due to charging inrush or C.T Circuit problem) or Buchholz

relay ( due to air suction or control suction problem) can be returned to service with more confidence on the basis of D.G.A

results.

According to the IEC/IEEE standards, eight fault types [5] are identified as shown in the Table2 .In this paper, the

range of gases from the table is taken as reference for a lookup table and the input is tested for diagnosing the faults.

TABLE 2.DGA DATA OF REFERENCE SEQUENCES

No Fault type H2 CH4 C2H6 C2H4 C2H2

1 No fault 0-15 0-4 0-11 0-3 0-0.2

2 T <150

thermal fault

20-160 10-130 15-33 5-96 0-0.4

3 150<T< 300

thermal fault

27-160 20-245 33-39 20-50 0-0.4

4 300<T< 700

thermal fault

27-181 90-262 41-42 28-63 0-0.2

5 T >700…

thermal fault

56-173 260-340 42-172 480-928 7-38

6 Low energy

Partial

43-55 24-58 12-66 300-560 1-3

7 High energy

Partial

340-675 34-66 29-66 10-21 1-3

8 Low energy Discharges

565-980 53-93 34-58 12-47 3-6

9 High energy

Discharges

32-200 6-107 1-11 13-154 13-224

Page 4: Simulation of Fault Diagnosis in the Oil Immersed Transformer Using Dissolved Gas Analysis

The internal inspection of hundreds of faulty equipment has led to the broad classes of faults indicated in Table 3,

detectable by visual inspection and by DGA:

TABLE 3.EXAMPLES OF FAULTS DETECTABLE BY DGA

THE DUVAL TRIANGLE

The Duval Triangle was first developed in 1974 [2]. It uses three hydrocarbon gases only (CH4, C

2H

4 and

C2H

2). These three gases correspond to the increasing levels of energy necessary to generate gases in transformers in

service. The Triangle method is indicated in Figure 1. In addition to the 6 zones of individual faults mentioned in Table

2 (PD, D1, D2, T1, T2 or T3), an intermediate zone DT has been attributed to mixtures of electrical and thermal faults

in the transformer. C

2H

2 and C

2H

4 are used in all interpretation methods to represent high energy faults (such as arcs) and high

temperature faults. H2 is preferred in several of these methods to represent very low energy faults such as PDs, where it

is produced in large quantities. CH

4, however, is also preventative of such faults and always formed in addition to H

2 in these faults, in smaller

but still large enough amounts to be quantified. CH4

has been chosen for the Triangle because it not only allows

identifying these faults, but provides better overall diagnosis results for all the other types of faults than when using H2.

This good performance of the Triangle with CH4 might be related to the fact that H

2 diffuses much more rapidly than

the hydrocarbon gases from the oil through gaskets and even metal welds. Therefore, gas ratios using H2 are probably

more affected by the loss of this gas than those using hydrocarbons gases only, which have much lower and comparable

diffusion rates. The three sides of the Triangle are expressed in triangular coordinates (X, Y, Z) representing the

relative proportions of CH4,

C2H

4 and C

2H

2, from 0% to 100% for each gas. In order to display a DGA result in the

Triangle, one must start with the concentrations of the three gases, (CH4) = A, (C

2H

4) = B and (C

2H

2) = C, in ppm.

Symbol Fault Examples

PD Partial discharges Discharges of the cold plasma (corona) type in gas bubbles or

voids, with the possible formation of X-wax in paper.

D1 Discharges of low energy Partial discharges of the sparking type, inducing pinholes,

carbonized punctures in paper.

Low energy arcing inducing carbonized perforation or surface

tracking of paper, or the formation of carbon particles in oil.

D2 Discharges of high energy Discharges in paper or oil, with power follow-through, resulting in

extensive damage to paper or large formation of carbon particles in

oil, metal fusion, tripping of the equipment and gas alarms.

T1 Thermal fault,

T <300 °C

Evidenced by paper turning brownish (> 200 °C) or carbonized

(> 300 °C).

T2 Thermal fault,

300 <T<700 °C

Carbonization of paper, formation of carbon particles in oil.

T3 Thermal fault,

T >700 °C

Extensive formation of carbon particles in oil, metal coloration

(800

Page 5: Simulation of Fault Diagnosis in the Oil Immersed Transformer Using Dissolved Gas Analysis

First calculate the sum of these three values: (CH4 + C

2H

4 + C

2H

2) = S, in ppm, then calculates the relative proportion

of the three gases, in %: X = % CH

4 = 100 (A/S), Y = % C

2H

4 = 100 (B/S), Z = % C

2H

2 = 100 (C/S).

X, Y and Z are necessarily between 0 and 100%, and (X + Y + Z) should always = 100 %. Plotting X, Y and Z in the

Triangle provide only one point in the Triangle.

Fig.1.Coordinates and Fault zones of the Triangle

Transformer I (10 MVA) Date of DGA H2 CH4 C2H6 C2H4 C2H2 CO2

27.11.’04 2 2 Tr 3 0 991

08.07.’05 1 2 Tr 4 2.01 2536

13.07.’06 1 5 1 6 1.87 1104

12.07.’07 5 7 2 7 0.55 1145

04.10.’08 1 10 4 17 0.23 842

Transformer II (10 MVA) Date of DGA H2 CH4 C2H6 C2H4 C2H2 CO2

27.11.’04 1 2 2 15 0 442

08.07.’05 1 3 5 45 0 2514

13.07.’06 2 16 11 85 0 1006

12.07.’07 4 40 19 52 0.24 965

04.10.’08 1 32 28 32 0 1420

Transformer III (16 MVA)

Date of DGA H2 CH4 C2H6 C2H4 C2H2 CO2

27.11.’ 04 2 1 Tr Tr 0 968

08.07.’05 7 2 1 5 4.76 5138

13.07.’06 4 5 2 14 2.15 1196

12.07.’07 10 6 2 14 3.61 940

04.10.’08 5 3 2 9 1.83 2225

Page 6: Simulation of Fault Diagnosis in the Oil Immersed Transformer Using Dissolved Gas Analysis

Transformer IV (16 MVA)

The above tabulated Data’s from. TEDC/METRO, TRICHY for the four Transformers at Palayamkottai.

VI.CONCLUSION

The data collected from the transformers (DGA test & data) which are located in Palayamkottai and Coimbatore of

south India , were given as inputs to the fault diagnosis coding in JAVA and also to the modified polygon and results are

obtained, i.e. faults are diagnosed.

REFERENCES

[1].IEEE standards C57.104 TM-2008 “IEEE Guide for the Interpretation of Gases generated in Oil Immersed

Transformers”,IEEE power and Energy Society Revision of Std C57,104-1991.

[2]Delta-X Research, “Duval Triangle”,HTML file from Google Search.

[3].Michel Duval IREQ Canada “A Review of faults detectable by Gas – in- Oil Analysis in Transformers”,2002 IEEE

Electrical Insulation Magazine May/June 2002 – vol.18,No.3 Page 8-17.

[4]. Michel Duval, “Dissolved Gas Analysis and the Duval Triangle”,AVO Technical Papers 2006 Conference,New Zealand.

[5]PengZheng-hong,SongBin, “Application of datamining techniques based on Grey Relational Analysis in Oli Immersed

Power Apparatus Fault Diagnosis”,2006,International Conference on Power System Technology.

Date of DGA H2 CH4 C2H6 C2H4 C2H2 CO2

27.11.’04 3 2 1 4 0 1504

11.07.’05 1 2 1 4 1.68 2813

13.07.’06 1 9 3 13 11.21 1356

12.07.’07 3 9 3 12 9.89 1233

04.10.’08 11 22 4 32 53.02 1031

Page 7: Simulation of Fault Diagnosis in the Oil Immersed Transformer Using Dissolved Gas Analysis
Page 8: Simulation of Fault Diagnosis in the Oil Immersed Transformer Using Dissolved Gas Analysis
Page 9: Simulation of Fault Diagnosis in the Oil Immersed Transformer Using Dissolved Gas Analysis
Page 10: Simulation of Fault Diagnosis in the Oil Immersed Transformer Using Dissolved Gas Analysis