Configuration Manual ZTE RMS (ZNV) Real Monitoring System for Generator and Batteries.
Citation preview
USMSStep 3: choose internet protocol (TCP/IP), double click it.Step 4: set local laptop IP Address, and click OK IP Address: 10.72.88.100, subnet mask:255.255.0.02 2/2
USMSStep 5: click okStep 6: click support3 3/3
USMSStep 7: check IP setting is successful or not, then click closePart 2: Install EISU config softwareStep 1: Find the file ZXM10-EISUConfig software in your laptop, Double click it.4 4/4
USMSStep 2: Click NextStep 3: click Next5 5/5
USMSStep 4: Click InstallStep 5: Click Finish6 6/6
USMSPart 3 : Download "v2para.tar.gz"Step 1: Connect LAN cable between EISU MIP port and laptop LAN port.Step 2: Open Eisuconfig softwareStep 3: Click scan server IP7 7/7
USMSStep 4: Wait a few seconds, Then IP will be obtained and show it in right interfaceStep 5: Input password(11111111),and then click login8 8/8
Step 6: Please check the Channal Param configmenu . If the "1" position data, please skip "Part 3: Download" v2para.tar.gz " If the "1" position no data, perform "Step 7".
Step 7: SelectDevice Mangement.
Step8: SelectDevice Mangement.
2 position,please select "Download configuration. Download "v2para.tar.gz",Select FTP, FTP window will pop up. Please do not close.
Step8: Restart EISU.
Part4 : Download "ATS Upgrade package"
Step 1: Login EISUconfig.
Step 2: SelectDevice Mangement.
2 position,please select "Updata package. Please select the appropriate ATS.
Step 3: Click to download.
Step4: Restart EISU.
Step5: Check the ATS download situation, SelectVAS Configure. If the "1" position data, the download was successful
Part 5 : Check the fluid level,AC meter and DC meter. Check the fluid levelStep 1: Login EISUconfig.
Step 2: SelectSerial Port Management, Select "COM1" Click Read Serial Port Para.
1. "1" position Select "COM1"2. Click Read Serial Port Para.
Step 3: Check protocol.( The default protocol has been downloaded) If there is an protocol to skip "Step 4" If you did not. Click "Select DLL File", download protocol.
Step 4: Click "Select DLL File", download protocol. ClickSet Smart Port
Step 5: Click Read Serial Port Para,2 position Data needs and picture consistent, if not modify.( Configuration is complete, you need to restart EISU.)
Step 6: Click Read,Data is 1. If it is not "1", click "Set" to modify.
Step 6: ClickSmart Channel DataClick Read Data.
If the "3" position display " DI-3000=1": Description sensor failure, check the wiring,Check Step 5. If a large number of data, device is working properly.
Check AC meter
Step 1: Login EISUconfig.
Step 2: SelectSerial Port Management, Select "COM3" Click Read Serial Port Para.
Check protocol.( The default protocol has been downloaded) If not, please download protocol.( Reference fluid level Download protocol.)
Step 3: Click Read Serial Port Para,2 position Data needs and picture consistent, if not modify.( Configuration is complete, you need to restart EISU.)
Step 4: Click Read,Data is 1. If it is not "1", click "Set" to modify.
Step 5: ClickSmart Channel DataClick Read Data.
If the "3" position display " DI-3000=1": Description sensor failure, check the wiring,Check Step 3. If a large number of data, device is working properly.
Check DC meter Step 1: Login EISUconfig. Step 2: SelectSerial Port Management, Select "Access Control" Click Read Serial Port Para.
Check protocol.( The default protocol has been downloaded) If not, please download protocol.( Reference fluid level Download protocol.)
Step 3: Click Read Serial Port Para,2 position Data needs and picture consistent, if not modify.( Configuration is complete, you need to restart EISU.)
Step 4: Click Read, Please set DC meter last 4 bit number.
Step 5: ClickSmart Channel DataClick Read Data.
If the "3" position display "DI-3000=1": Description sensor failure, check the wiring,Check Step 3. If a large number of data, device is working properly.
Part 6: Set VAS and FuelStep 1: Login EISUconfig.
Step 2: SelectSerial Port ManagementMenu.
Step 2: Selectgassline_monitorMenu. ClickParam Config.
Step 3: Tank configuration parameters. Need to configure four positions. Reference Picture Settings.
1. Position 1 Set the tank parameters
2. Position2 Set No use
3. Position3 Reference Picture Settings.
4. Position4 Set Fuel Sensor Para.
Select DeviceName
SelectChannal 1
5. Position5 Set Oil Engine para. Reference Picture Settings.
Step 4: In the lower right corner,First click "Save", the second click "Download".Step5: Restart EISU.
Step5: Reboot is complete, you need to wait 5 minutes.Step5: Check the channel.( Channel correctly, do not perform Step6 Step8)
Step6: If the channel is incorrect, please reconfigure the VAS.
Step7: Delete "gassline_monitor".
Step8:Add gassline_monitor.
Step8: Repeat Step 3--- Step 4.
Part 7: Set EISU IDStep 1: Login EISUconfig.Step 2: SelectNetwork Setting, Reading Network Information.
Step 3: Set EISU ID.
Step5: Restart EISU.
Part 8: RMS server information and SIM card
Step 1: Login EISUconfig.Step 2: SelectWirless Management, set picture parameter.
Server IP:10.218.207.7 Server port:9999(10 model site configure 9999, Other sites configured to 9998) APN:zterms
Step 3: Test SIM card. Display "OK" normal network.
Complete all configuration,Please contact "SyedTufailMazhar", he will configure the site in NMS