elproLOG MONITOR Operation Manual

SM3002Ee elproLOG MONITOR

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: SM3002Ee elproLOG MONITOR

elproLOG MONITOROperation Manual

Page 2: SM3002Ee elproLOG MONITOR

2 - EN elproLOG MONITORSM3002Ee

Table of Contents

1. Introduction to elproLOG MONITOR ............................................. 5

2. How to Start Monitoring Tasks ......................................................... 6

2.1 New Task ......................................................................................................... 6

2.2 Change Group ................................................................................................. 6

3. Menus - Functions - Icons .................................................................... 7

3.1 Menus - Functions ........................................................................................... 7

3.2 Icons ................................................................................................................ 8

4. Configuration ................................................................................................. 9

4.1 Basic Settings .................................................................................................. 9

4.1.1 Values........................................................................................... 10

4.2 Group Settings ............................................................................................... 10

5. Alarm Settings............................................................................................. 11

5.1 Notification Settings ....................................................................................... 11

5.2 Acknowledgement.......................................................................................... 12

5.3 Repeat Notification......................................................................................... 13

5.4 Alarm Sound .................................................................................................. 13

5.5 Alarm Interface 1/2......................................................................................... 14

5.5.1 Alarm Interface Scheduler ............................................................ 15

5.6 E-Mail Settings............................................................................................... 15

5.6.1 Alarm E-Mail ................................................................................. 16

5.6.2 Warning E-Mail ............................................................................. 16

5.6.3 Keep Alive E-Mail ......................................................................... 17

5.6.4 Send Queue E-Mail ...................................................................... 18

5.7 SMS Settings ................................................................................................ 18

5.7.1 Alarm SMS ................................................................................... 19

5.7.2 Warning SMS ............................................................................... 19

5.7.3 Keep Alive SMS............................................................................ 20

5.7.4 Send Queue SMS......................................................................... 20

5.8 Alarm Printer .................................................................................................. 21

5.9 Alarm Protocol ............................................................................................... 21

5.9.1 Alarm Protocol Structure............................................................... 22

5.10 Group Protocol............................................................................................... 23

5.10.1 Group Protocol Structure.............................................................. 24

5.11 Logger Protocol.............................................................................................. 25

5.11.1 Logger Protocol Structure............................................................. 26

Page 3: SM3002Ee elproLOG MONITOR

EN - 3elproLOG MONITORSM3002Ee

IT

ES

EN

EN

FR

IT

ES

5.12 Autosave as MDF ...........................................................................................27

5.12.1 Autosave Scheduler ......................................................................28

6. Alarm Text Editor .......................................................................................29

7. Data Representation ................................................................................30

8. Alarm / Warning ..........................................................................................31

8.1 Alarm Window.................................................................................................32

8.1.1 Notes About the Alarm Reason.....................................................32

8.2 Time Responds - Alarm Sequence.................................................................33

9. Error messages ...........................................................................................34

9.1 Sensor Error ...................................................................................................34

9.2 Communication Problem ................................................................................34

9.3 Configuration Messages .................................................................................34

9.4 Information for Customer Support............................................................................35

Page 4: SM3002Ee elproLOG MONITOR

4 - EN elproLOG MONITORSM3002Ee

Used Symbols & Designation Key

Information

IMPORTANT INFORMATION AND WARNINGS

Reference to resuming chapter [xxx / yyy / zzz; e.g. 5.9.1 Alarm Protocol Structure / Title / PC time] or document

In the interest of our customers we reserve the right to make any changes resulting from tech-nical advancement. Therefore, schemes, descriptions and extent of delivery are subject to change without any notice! The release of this document is available on the printed and archived original only.This manual is valid as from software release 3.6x

Page 5: SM3002Ee elproLOG MONITOR

EN - 5elproLOG MONITORSM3002Ee

Introduct ion to e lproLOG MONITOR

IT

ES

EN

EN

FR

IT

ES

1. Introduction to elproLOG MONITOR

elproLOG ANALYZE

This application is used to supervise, to display and archiving data of network dataloggers (ECOLOG-NET) as well as forwarding limit values violations.For the configuration of the dataloggers the software elproLOG ANALYZE is required. Opera-tion manuals SE3401E & SE3002E

elproLOG CON-FIG

The dataloggers to be monitored are put into different groups according to customer facility structures. For this organizational work elproLOG CONFIG is used. Operation manual SU3001E

elproLOG USER To controll user access, all entries are supervised by elproLOG USER. Operation Manual SU3001E

elproEVENT elproEVENT is an audit trail, which allows to trace easily and quickly all manipulations and events related to the ELPRO datalogging system. elproEVENT is the memory of the ELPRO softwareelproEVENT. Operation manual SU3001E

The following functions are part of the elproLOG MONITOR programm:• Datalogger supervision and regularly updated measurement values.• Alarm monitoring and log files.• Automatic data backup to an mdf file, readable with elproLOG ANALYZE (21CFR11 compliant

file).

Page 6: SM3002Ee elproLOG MONITOR

6 - EN elproLOG MONITORSM3002Ee

How to Start Moni tor ing Tasks

2. How to Start Monitoring Tasks

2.1 New Task elproLOG CON-FIG

1. Define a group with the loggers to be monitored. The result of this work is a group configuration file with the file ending .gcf

2. Select the desired gcf-file and configure the monitoring task

4.1 Basic Settings & 5. Alarm Settings

3. Setup a new monitoring task

3. Menus - Functions - Icons / File / New

4. Select the group, define "Measuring" and "View"

4.2 Group SettingsExamples for the two representation possi-bilities 7. Data Representation

2.2 Change GroupSelect the group, define the cycle time and the data representation possibility 4.2 Group Set-tings & 7. Data Representation

Only not selected groups are listed.

Page 7: SM3002Ee elproLOG MONITOR

EN - 7elproLOG MONITORSM3002Ee

Menus - Funct ions - Icons

IT

ES

EN

EN

FR

IT

ES

3. Menus - Functions - Icons

3.1 Menus - Functions

The following functions are available in the elproLOG MONITOR software:

New

Open a new group which has to be monitored

4.2 Group Settings

Settings

Used to change the monitored group and to assign the independent cycle time for each group.

4.2 Group Settings

After a restart of the program, the last selected groups will be monitored auto-matically.

Options

This function is used for all possible program settings.

4.1 Basic Settings

Start autosave manual

This function is used to perform an autosave as mdf-file right now

5.12 Autosave as MDF

Font....

Use these settings to match the used fonts of the main window

Hide disabled...

Sensors / digital inputs which are disabled in elproLOG CONFIG, are not repre-sented in the in the elproLOG MONITOR main screen.

Show alarm at the top

Alarm conditions are shown on top of the list and not in a simple alphabetic order.

Function to organize your screen

About elproLOG MONITOR

Detailed information about the installed software version

Page 8: SM3002Ee elproLOG MONITOR

8 - EN elproLOG MONITORSM3002Ee

Menus - Funct ions - Icons

3.2 IconsAcoustic alarm

Switches the local (pc), acoustic alarm off

Alarm Window

Used to open the alarm windowThis icon is going to blink red, as soon as an alarm has been released. It stays active till the alarm has been confirmed even the alarm has vanished.

Page 9: SM3002Ee elproLOG MONITOR

EN - 9elproLOG MONITORSM3002Ee

Conf igurat ion

IT

ES

EN

EN

FR

IT

ES

4. Configuration

4.1 Basic SettingsSelect in the "Tools" menu "Options" to open the window

Group Configura-tion File

Location where the configurations from elproLOG CONFIG (gcf files) are stored. 4.1.1 Values

Values to be moni-tored

Default Cycle timeTime between 2 scans over the selected group of dataloggers. This parameter may be changed for each group individually in the "Settings" window. It does not influence the measurement logging inter-val of the dataloggers!Default: 3 Minutes

4.2 Group Settings

Default ViewSwitch between logger based or sensor based representation

LanguageCurrent application languages: German, English or French

For further details see also the window related comment

Confirm all entries by pressing the OK button and continue the settings with the selection of the dat-alogger group to be monitored.

Page 10: SM3002Ee elproLOG MONITOR

10 - EN elproLOG MONITORSM3002Ee

Conf igurat ion

4.1.1 Values

4.2 Group SettingsSelect in the "Group" menu "Settings" to open the window

Measuring This is the time between 2 scans applied for the selected group only.

View Switch between logger based or sensor based representation

For a safe monitoring of a data logger the following information should be taken into consideration

Value Setting Comment

Last measured value Default setting

For an easy evaluation of the dif-ferent protocols, the logging interval of the data loggers being monitored, should not be longer than half of the cycle time. For logging intervals (> 2 minutes) the data of the loggers will be updated at least once per min-ute. In this case the cycle time should not be faster than 2 min-utes.

Last stored valueRequired for the first series of ECO-LOG-NET data loggers or for log-gers with serial interface only.

The data for elproLOG MONI-TOR will be up-dated in the log-ging interval regardless of the data logger settings.

Store B1 In4.1 Basic Settings selected group configuration file.

Cooling Shelf

Group names of the data logger groups defined in elproLOG CONFIG. The selected group name is used to refer the monitoring window.

Page 11: SM3002Ee elproLOG MONITOR

EN - 11elproLOG MONITORSM3002Ee

Alarm Sett ings

IT

ES

EN

EN

FR

IT

ES

5. Alarm Settings

The following settings are part of the "Tools / Options" menu. They are used to define the alarm parameters and alarm reactions.

5.1 Notification Settings

Alarms are recog-nized by elproLOG MONITOR only, if they are active at the time of cycle reading!

Sensor AlarmAn alarm indicated by the logger limit values will be recognized.

Sensor WarningAn alarm indicated by the elproLOG CONFIG limit values.

No connection to logger

If the communication with a particular logger gets lost, it will be treated as an alarm (network prob-lems).

Sensor errorA cable break or short circuit is treated as an alarm.

Digital Input 1 / 2The digital inputs off the logger could be forwarded as an alarm from an external device hooked up to the logger

Autosave failedThis message will be treated as an alarm in cases where autosave of logger data failed.5.12 Autosave as MDF

Warning of low battery power wire-less sensor

If one of the wireless sensors of an ECOLOG-NET LR8 reaches a critical battery level, this is treated as a warning.

Alarm if Input = 1 Switch between Digital Input 1/2 and GND closed

Alarm if Input = 0 Switch between Digital Input 1/2 and GND open

Page 12: SM3002Ee elproLOG MONITOR

12 - EN elproLOG MONITORSM3002Ee

Alarm Sett ings

5.2 AcknowledgementDefinition of up to 3 text fields and their title row for the documentation of an alarm or a warning mes-sage.

Fill in comment mandatory

To acknowledge an alarm, a comment has to be entered into the "Alarm Acknowledgement" win-dow.8.1.1 Notes About the Alarm Reason

Deviation Limit value Notification State Example

++ Logger (see status) Alarm 28°C

+ elproLOG CONFIG Warning 22°C

o.k. 20°C

- elproLOG CONFIG Warning 17°C

-- Logger (see status) Alarm 9°C

Page 13: SM3002Ee elproLOG MONITOR

EN - 13elproLOG MONITORSM3002Ee

Alarm Sett ings

IT

ES

EN

EN

FR

IT

ES

5.3 Repeat NotificationDelay time in number of cycles till an active alarm- warning notification will be repeated.Active alarms and warnings are repeated only.

5.4 Alarm Sound

PathDirectory which contains the desired acoustic alarm.

Page 14: SM3002Ee elproLOG MONITOR

14 - EN elproLOG MONITORSM3002Ee

Alarm Sett ings

5.5 Alarm Interface 1/2

Enable Alarm Inter-face

This check box activates the features of the optional Alarm Interface (part no 2355-A). For technical details see: user manual of the alarm interface D-AD-2102E.

ComPort To select the communication port where the Alarm Interface is connected to.

Alarm ForwardingWarning Forwarding

This check box activates the alarm interface

5.1 Notification Settings / Conditions.

Watchdog This check box activates a watchdog function that will release an alarm as soon as the communication between the PC and the Alarm Interface breaks down or the software elproLOG MONITOR stops run-ning.

Test Alarm Inter-face

Test of the 2 relay contacts.

Alarm Interface Version

Service function to identify the firmware version (old V1.2 / current V1.7) of the alarm interface used

Page 15: SM3002Ee elproLOG MONITOR

EN - 15elproLOG MONITORSM3002Ee

Alarm Sett ings

IT

ES

EN

EN

FR

IT

ES

5.5.1 Alarm Interface Scheduler

Start delayDelay time between the registration of an alarm by elproLOG MONITOR and the activation of the alarm interface.

Switch on timeSwitch off time

Change over switch function during the period of an alarm

For details about the delay times 8.2 Time Responds - Alarm Sequence

5.6 E-Mail Settings

AVAILABLE FROM FIRMWARE VERSION 1.7 OR HIGHER

IF THESE INFORMATION ARE INCORRECT, THE ALARM E-MAILS WILL NOT REACH THEIR RECIPIENTS!

Page 16: SM3002Ee elproLOG MONITOR

16 - EN elproLOG MONITORSM3002Ee

Alarm Sett ings

5.6.1 Alarm E-Mail

Enable Alarm E-Mail

This check box activates the e-mail forwarding feature

Subject, TO, CC These are common used information for addressing an e-mail.All information needed to identify a troubled measurement is automatically enclosed in the e-mail

Text / Button: Edit This block contains information like: process information, responsibilities and instructions and will be added to each alarm e-mail.

6. Alarm Text Editor

5.6.2 Warning E-Mail

Use Alarm E-Mail settings

If this check box is activated, the settings from the alarm e-mail are used for the warning e-mail.

Subject, TO, CC These are common used information for addressing an e-mail.All information needed to identify a troubled measurement is automatically enclosed in the e-mail

Text / Button: Edit This block contains information like: process information, responsibilities and instructions and will be added to each warning e-mail.

6. Alarm Text Editor

Page 17: SM3002Ee elproLOG MONITOR

EN - 17elproLOG MONITORSM3002Ee

Alarm Sett ings

IT

ES

EN

EN

FR

IT

ES

5.6.3 Keep Alive E-Mail

Enable Keep Alive E-Mail

This function is used to send a repeated check e-mail. This ensures that the notification works in case of alarm.

Maximal Time between E-Mails

Delay time between the Keep Alive E-Mails

Subject, TO, CCThese are common used information for addressing an e-mail.All information needed to identify a troubled measurement is automatically enclosed in the e-mail

Text / Button: EditThis block contains information like: process information, responsibilities and instructions and will be added to each "Keep Alive E-Mail".

6. Alarm Text Editor

Server Address (Host or IP) mail.gmx.com

Server requires authentication select check box

User [email protected]

Password Your GMX password

Application Name Any sender name

e-Mail [email protected]

Page 18: SM3002Ee elproLOG MONITOR

18 - EN elproLOG MONITORSM3002Ee

Alarm Sett ings

5.6.4 Send Queue E-Mail

Enable Send Queue E-Mail

Until the successful mailing, this function repeats the sending of the e-mail.The queue of pending messages is cleared by disabling this function.

Repeat time interval Delay time between the repeated e-mails.

5.7 SMS Settings

IF THESE INFORMATION ARE INCORRECT, OR THE SIGNAL STRENGTH IS TOO LOW THE ALARM SMS WILL NOT REACH THEIR RECIPIENTS!

Page 19: SM3002Ee elproLOG MONITOR

EN - 19elproLOG MONITORSM3002Ee

Alarm Sett ings

IT

ES

EN

EN

FR

IT

ES

5.7.1 Alarm SMS

Enable Alarm SMSThis check box activates this SMS feature.

Text / Button: EditThis block contains information like: process information, responsibilities and instructions and will be added to each alarm SMS.

6. Alarm Text Editor

5.7.2 Warning SMS

Use Alarm SMS Settings

If this check box is activated, the settings from the alarm SMS are used for the warning SMS.

Text / Button: EditThis block contains information like: process information, responsibilities and instructions and will be added to each warning SMS.

6. Alarm Text Editor

Page 20: SM3002Ee elproLOG MONITOR

20 - EN elproLOG MONITORSM3002Ee

Alarm Sett ings

5.7.3 Keep Alive SMSImportant for prepaid SIM card

Some providers are going to lock the mobile abo, if it is not used for a certain period of time. This func-tion is used to send a repeated SMS which avoids the locking of the mobile abo.

Enable Keep Alive SMS

This check box activates this SMS feature.

Maximal Time between SMS

Delay time between the keep alive SMS

Text / Button: Edit This block contains information like: process information, responsibilities and instructions and will be added to each "Keep Alive SMS".

6. Alarm Text Editor

5.7.4 Send Queue SMS

Enable Send Queue SMS

Until the successful sending, this function repeats the sending of the SMS.The queue of pending messages is cleared by disabling this function.

Repeat time interval Delay time between the repeated SMS.

Page 21: SM3002Ee elproLOG MONITOR

EN - 21elproLOG MONITORSM3002Ee

Alarm Sett ings

IT

ES

EN

EN

FR

IT

ES

5.8 Alarm Printer

Enable Alarm Printer

This check box activates the alarm printer function. Each alarm event is going to lead to a print out on the selected printer.

Text / Button: EditThis block contains information like: process information, responsibilities and instructions and will be added to each alarm printout.

6. Alarm Text Editor

5.9 Alarm Protocol

Path & File NameLocation where all the alarm protocols (csv-files; plain text) will be kept.

GDI Win Printer e. g. Canon S520 only works as an alarm printer if an additional software like: www.printfil.com will be used!

Page 22: SM3002Ee elproLOG MONITOR

22 - EN elproLOG MONITORSM3002Ee

Alarm Sett ings

5.9.1 Alarm Protocol Structure

Column Titel Note

Ala

rm

1 PC time

Reason for alarm

2 Logger time

3 Alarm Info

4 Logger group

5 Logger name

6 Logger ID

7 Sensor noThis entry refers to the sensor number of the log-ger

8 Sensor Name Name of the alarm releasing sensor

Sen

sor

9 S1-Name

10 S1-Value

11 S1-Unit

12 S1-Status

0 ok

1Sensor deactivated(in elproLOG CONFIG)

2 Warning

3 Warning confirmed

4 Alarm

5 Alarm confirmed

6 u.f./o.f./n.c.

7 u.f./o.f./n.c. confirmed

u.f.Value under stepping measurement range

o.f.Value over stepping measurement range

n.c. Sensor not connected / wire brake

13 - 40 Corresponds to the above information for sensor 2 - 8

Dig

ital

inp

ut

41 D1-Name Name of digital input 1

42 D1-Value 0 / 1Current state of D1 (see alarm protocol for more details)

43 D1-Text value Describes the state of D1

44 D1-Status

0 ok

1Digital input deactivated(in elproLOG CONFIG)

2 ---

3 ---

4 Alarm

5 Alarm confirmed

45 - 48 Corresponds to the above information for digital input D2

Page 23: SM3002Ee elproLOG MONITOR

EN - 23elproLOG MONITORSM3002Ee

Alarm Sett ings

IT

ES

EN

EN

FR

IT

ES

5.10 Group ProtocolA group protocol is a text file (csv-file; plain text) with the content of the last scan. All alarm monitor information is stored.

Path & File NameLocation where the group protocols will be kept.

Ack

no

wle

dg

e In

form

atio

n 49 User nameFor alarm confirmation

50 Host Name

51 Comment title 1For alarm confirmation

52 Comment text 1

53 - 56 Corresponds to the above information for digital input D2

Page 24: SM3002Ee elproLOG MONITOR

24 - EN elproLOG MONITORSM3002Ee

Alarm Sett ings

5.10.1 Group Protocol Structure

Column Titel Note

1 Logger ID

2 Logger name

3 PC time

4 Logger time

5 Logger state

0 Communication ok

1Data logger deactivated(in elproLOG CONFIG)

4 No connection

5 No connection confirmed

6 S1-Name

7 S1-Value

8 S1-Unit

9 S1-Status

0 ok

1Sensor deactivated(in elproLOG CONFIG)

2 Warning

3 Warning confirmed

4 Alarm

5 Alarm confirmed

6 u.f./o.f./n.c.

7 u.f./o.f./n.c. confirmed

u.f.Value under stepping measurement range

o.f. Value over stepping measurement range

n.c. Sensor not connected / wire brake

10 - 37 Corresponds to the above information for sensor 2 - 8

38 D1-Name Name of digital input 1

39 D1-Value 0 / 1Current state of D1 (see alarm protocol for more details)

40 D1-Text value Describes the state of D1

41 D1-Status

0 ok

1 Digital input deactivated (in elproLOG CONFIG)

2 ---

3 ---

4 Alarm

5 Alarm confirmed

42 - 45 Corresponds to the above information for digital input D2

Page 25: SM3002Ee elproLOG MONITOR

EN - 25elproLOG MONITORSM3002Ee

Alarm Sett ings

IT

ES

EN

EN

FR

IT

ES

5.11 Logger ProtocolA logger protocol is a text file (csv-file; plain text) with the content of the last scan. Each logger in the selected group gets its own logger protocol.

Number of cycles stored

This entry determines the number of measurement cycles kept in the logger protocol file.

Path & File NameLocation where the logger protocols will be kept.

Page 26: SM3002Ee elproLOG MONITOR

26 - EN elproLOG MONITORSM3002Ee

Alarm Sett ings

5.11.1 Logger Protocol Structure

Column Titel Note

1 Logger ID

2 Logger name

3 PC time

4 Logger time

5 Logger state

0 Communication ok

1Data logger deactivated(in elproLOG CONFIG)

4 No connection

5 No connection confirmed

6 S1-Name

7 S1-Value

8 S1-Unit

9 S1-Status

0 ok

1Sensor deactivated(in elproLOG CONFIG)

2 Warning

3 Warning confirmed

4 Alarm

5 Alarm confirmed

6 u.f./o.f./n.c.

7 u.f./o.f./n.c. confirmed

u.f.Value under stepping measurement range

o.f. Value over stepping measurement range

n.c. Sensor not connected / wire brake

10 - 37 Corresponds to the above information for sensor 2 - 8

38 D1-Name Name of digital input 1

39 D1-Value 0 / 1Current state of D1 (see alarm protocol for more details)

40 D1-Text value Describes the state of D1

41 D1-Status

0 ok

1 Digital input deactivated (in elproLOG CONFIG)

2 ---

3 ---

4 Alarm

5 Alarm confirmed

42 - 45 Corresponds to the above information for digital input D2

Page 27: SM3002Ee elproLOG MONITOR

EN - 27elproLOG MONITORSM3002Ee

Alarm Sett ings

IT

ES

EN

EN

FR

IT

ES

5.12 Autosave as MDF

Enable AutosaveThis check box activates the Autosave function.

PathThis is the place where the Autosave files will be kept.

Synchronize Logger Time before Autosave

The datalogger clock will be regularly adjusted to the pc clock. This results in e.g. automatic daylight saving time change.

This function requires elproLOG ANALYZE 3.63

Synchronizing the data logger clock requires at least the following firmware versions:

Logger Firmware Version

ECOLOG-NET LH2 / WH2 1.00

ECOLOG-NET LP4 / WP4 1.05

ECOLOG-NET LA8 / WA8 1.03

ECOLOG-NET LR8 1.00

THE ALARM RELEASED BY A FAILED AUTOSAVE, WILL BE REGISTERED IN THE ALARM PROTOCOL AND PRINTED OUT!

Page 28: SM3002Ee elproLOG MONITOR

28 - EN elproLOG MONITORSM3002Ee

Alarm Sett ings

5.12.1 Autosave SchedulerAutosave file name definition:ID-Number - Module Tag - Date - Increas-ing number

THE DATA ARE NOT AUTOSAVE AT THE INDICATED AUTOSAVE TIME BUT ON THE NEXT FOLLOWING ELPROLOG MONITOR READ OUT CYCLE!

Page 29: SM3002Ee elproLOG MONITOR

EN - 29elproLOG MONITORSM3002Ee

Alarm Text Editor

IT

ES

EN

EN

FR

IT

ES

6. Alarm Text Editor

Allows you to setup the contend of your text messages. For further details see the window related comment.

Page 30: SM3002Ee elproLOG MONITOR

30 - EN elproLOG MONITORSM3002Ee

Data Representat ion

7. Data Representation

The following 2 data representation modes are possible on the elproLOG MONITOR main screen

Sensor based representation

Logger based representation

Cycle time Time between two scans

Remaining time Time left till the next scan

Next autosave Date and time till the next autosave

Page 31: SM3002Ee elproLOG MONITOR

EN - 31elproLOG MONITORSM3002Ee

Alarm / Warning

IT

ES

EN

EN

FR

IT

ES

8. Alarm / Warning

By the flashing icon: "Show Alarm Win-dow", and the alarm window (pop-up) an alarm makes atten-tive.

The background color in the corresponding field / row is going to change:- If a limit value is violated- The alarm state on one of the digital inputs (D1 / D2) is indicated- A malfunction is detected

Acoustic Alarm- Alarm- Malfunction of a sensor- Communication Problem

triggers an acoustic alarm until they are acknowledged 5.4 Alarm Sound.

elproLOG MONITOR as symbol

If the program is visible as symbol in the task border only, nevertheless the alarm window becomes visible on screen.

Sensor based representation

Logger based representation

white normal:

red Alarm: The defined alarm limit of the data logger has been over-/ understepped.

orangeWarning: The warning limit defined in elproLOG CONFIG has been over-/ under-stepped.

yellow• Malfunction of a sensor• Communication Problem

9. Error messages

cyan Warning of low battery power wireless sensor

gray with measurement values, sensor is disabled in elproLOG CONFIG

Page 32: SM3002Ee elproLOG MONITOR

32 - EN elproLOG MONITORSM3002Ee

Alarm / Warning

8.1 Alarm Window

1. Warning2. e.g. communication error3. Alarm4. Row-wise alarm acknowledge

8.1.1 Notes About the Alarm Reason5. Alarm6. Alarm Value back to normal

This line will be removed from the list, after the alarm has been acknowledged7. Warning of low battery power wireless sensor

8.1.1 Notes About the Alarm ReasonThis window appears after an alarm has been confirmed, if it was activated in accordance with chapter 5.2 Acknowledgement.

After an acknowledgement "Date/Time Acknowledged" and "Acknowledged by" are registered in the alarm window and the alarm protocol.Acknowledged messages are represented in the alarm window (background color is white) till their conditions are set back to normal.

NOT ACTIVATED ALARM CONDITIONS IN ACCORDANCE WITH CHAPTER 5.1 NOTIFI-CATION SETTINGS, ARE NOT REPRESENTED IN THE "ALARM WINDOW", AND NO ALARM WILL BE RELEASED.

Page 33: SM3002Ee elproLOG MONITOR

EN - 33elproLOG MONITORSM3002Ee

Alarm / Warning

IT

ES

EN

EN

FR

IT

ES

8.2 Time Responds - Alarm Sequence

Page 34: SM3002Ee elproLOG MONITOR

34 - EN elproLOG MONITORSM3002Ee

Error messages

9. Error messages

9.1 Sensor Error

If a sensor is defective or not connected, the background color of the sensor gets yellow.

9.2 Communication Problem

If a data logger is not connected to LAN or communication is disturbed, the background color of the logger name and id gets yellow and no measurement values are available

9.3 Configuration MessagesConfig file error

A gcf-file of a former version of elproLOG CONFIG has been tried to open.Open this gcf-file with the new version of elproLOG CONFIG and convert it into the new format.

No alert option

No alert options have been selected 5.1 Notification Settings.The available protocols (Alarm, Group, Logger) are not recognized as alert options

U.F Value under stepping measurement range or sensor wire shorted

O.F. Value over stepping measurement range / sensor cable break

n.def Missing or wrong measurement data

Page 35: SM3002Ee elproLOG MONITOR

EN - 35elproLOG MONITORSM3002Ee

Error messages

IT

ES

EN

EN

FR

IT

ES

9.4 Information for Customer SupportIf you need assistance from the ELPRO - Customer support, supply us with the following information please:

Select in menu "Help" the menu item "Info" for the required sup-port details.

• Release number of the used software.The software is delivered on a CD-ROM with the following designation: 3.x.y. The current version number of the software is shown by the ReadMe file.

• Used operating system.• Designation of the used elproLOG software modules and / or datalogger with which problems

arise. • Do the same problems arise with other elproLOG application and / or datalogger?• Which were the preceding actions, before problems arose? (accurate description of your data-

logger application: time, temperature, shock .....).• Exact definition of the error occurred

Page 36: SM3002Ee elproLOG MONITOR

36 - EN elproLOG MONITORSM3002Ee

Error messages

Index

AAcoustic alarm 31Alarm 11, 16, 19Alarm colors 31Alarm Forwarding 14

CConnection check e-mail 17Connection check SMS 20Customer support 35

DData representation 30Data representation with alarm 31Datalogger groups 5Datalogger Setup 5EelproLOG ANALYZE 5elproLOG CONFIG 5elproLOG USER 5Error - Config file error 34Error - No alert option 34

GGroup Configuration File 9Group name 10

LLogin 5QQueue 18, 20

RRelease 35

SSensor based representation 10, 31Symbol in task border 31

TTime synchronisation 27

VValue U.F. / O.F. / n.def 34View - logger based 10, 31View - sensor based 31

WWarning 11, 16, 19

Page 37: SM3002Ee elproLOG MONITOR

EN - 37elproLOG MONITORSM3002Ee

IT

ES

EN

EN

FR

IT

ES

Revision history

Author Date Version Description

A. Gubler 30. 07.2008 -- 1. 1st edition; replaces SM3001Ea; rework for release 3.6x

A. Gubler 02.12. 2008 a small changes (spelling)

A. Gubler 16. 09. 2009 b Chapter 5.13 deleted; Delay time in cycles deleted

A. Gubler 24. 06. 2010 d New: Keep Alive E-Mail, A4 Layout

A. Gubler 29.10.2012 e New: E-Mail and SMS queue

Page 38: SM3002Ee elproLOG MONITOR

Operation ManualelproLOG MONITORSM3002Ee 11.2012

ELPRO-BUCHS AG

Langäulistrasse 62

CH-9470 Buchs SG

Switzerland

e-mail: [email protected]

For local representatives see:

www.elpro.com