Version : 052715 SMART SHOT UC T-L INSTALLATION GUIDE Pg. 2-3 T-L ELEC AB PANEL, WATER PRESSURE START (51785) 4-5 T-L ELEC AB PANEL, AUTO RESTART (51790 OR 51795) 6-7 T-L ENGINE DRIVEN HYDRAULIC PUMP 8-9 T-L ELEC PANEL WITH 10 TERM STRIP (PRIOR TO 1998) 10-11 T-L ELEC PANEL 10 TERM STRIP WATER PRESSURE-AUTO RE START (PRIOR TO 1998)

SMART SHOT UC T L INSTALLATION GUIDEzgofw.khfwq.servertrust.com/v/SSmanuals/Smart Shot... · version : 052715 smart shot uc t-l installation guide pg. 2-3 t-l elec ab panel, water

  • Upload
    others

  • View
    3

  • Download
    0

Embed Size (px)

Citation preview

Page 1: SMART SHOT UC T L INSTALLATION GUIDEzgofw.khfwq.servertrust.com/v/SSmanuals/Smart Shot... · version : 052715 smart shot uc t-l installation guide pg. 2-3 t-l elec ab panel, water

Version : 052715

SMART SHOT UC T-L

INSTALLATION GUIDE

Pg.

2-3 T-L ELEC AB PANEL, WATER PRESSURE START (51785)

4-5 T-L ELEC AB PANEL, AUTO RESTART (51790 OR 51795)

6-7 T-L ENGINE DRIVEN HYDRAULIC PUMP

8-9 T-L ELEC PANEL WITH 10 TERM STRIP (PRIOR TO 1998)

10-11 T-L ELEC PANEL 10 TERM STRIP WATER PRESSURE-AUTO RE

START (PRIOR TO 1998)

Page 2: SMART SHOT UC T L INSTALLATION GUIDEzgofw.khfwq.servertrust.com/v/SSmanuals/Smart Shot... · version : 052715 smart shot uc t-l installation guide pg. 2-3 t-l elec ab panel, water

2

SMART SHOT WITH T-L ELECTRIC DRIVEN HYDRAULIC PUMP Used with T-L AB Panel wired for Water Pressure Start (CD51785)

Note: SMART SHOT NEEDS TO BE PROGRAMMED WITH PSR SCRIPT. Call for details. Operation: Hot Shot with Smart Shot is powered by 24vac hot when disconnect is on. Water Pump operation depends on position of the “WELL” Switch in the T-L AB Panel. Wet or Dry operation depends on position of the Wet/Dry switch in the T-L AB Panel. Wet Operation:

• T-L AB Panel Well Switch is up and Wet/Dry Switch is up.

• Remote/Local Switch in Smart Shot is in Remote position.

• Relay #2 of Smart Shot is Well Control at start-up. Closes for 10 min. upon Start cmd to start pump and then opens up. Gets the well started before the pivot starts to pressurize the system. Opens if the Stop cmd is issued before the 10 min timer is finished.

• Relay #3 of Smart Shot is Start/Stop pivot control. Relay is maintained (latched). Closes upon Start cmd, Open upon Stop cmd. Provides power to Term #11 of AB Panel, waiting for water pressure to start the pivot.

• Pivot pressurizes, the WPS closes and connects 11 to 12 in the AB Panel and pivot starts.

• Term #1 of the AB Panel is powered which powers the 24vac Relay in the Smart Shot panel. Sensor Input #1 of the Smart Shot is now closed and shows the pivot is running. 24vac hot is closed to the Well Control circuit, redundant with the Smart Shot Relay #2.

• After 10 min. Smart Shot Relay #2 opens and the well stays running.

To T-L AB PANEL

Page 3: SMART SHOT UC T L INSTALLATION GUIDEzgofw.khfwq.servertrust.com/v/SSmanuals/Smart Shot... · version : 052715 smart shot uc t-l installation guide pg. 2-3 t-l elec ab panel, water

3

T-L Allen Bradley Panel wired for Water Pressure Start (CD51785) -NOT FOR LOAD CONTROL AUTO RESTART-

Note: Change the Well Switch yellow wire. See below Note: Remove the Red wire that goes from the fuse block to Term #11. See below. Dry Operation:

• T-L AB Panel Well switch is down and Wet/Dry switch is down.

• Remote/Local switch in Smart Shot is in Remote position.

• Relay #2 of Smart Shot will close for 10 minutes, but well will not run.

• Relay #3 of Smart Shot will start and stop the pivot.

• Sensor Input #1 of Smart Shot will close indicating the pivot is running. Local Operation:

• Remote/Local switch in Smart Shot is in Local position

• The AB Panel Wet/Dry switch determines if the pivot will start.

• With the pivoted started, Term #1 in the AB Panel will be powered, energizing the Smart Shot 24vac relay allowing the well operation per the Well Switch in the AB Panel.

To Hot Shot

bk

or

rd

br

yw

bl

Move the Well SW. yellow wire from the relay to Term #8.

NOTE:

Page 4: SMART SHOT UC T L INSTALLATION GUIDEzgofw.khfwq.servertrust.com/v/SSmanuals/Smart Shot... · version : 052715 smart shot uc t-l installation guide pg. 2-3 t-l elec ab panel, water

4

SMART SHOT WITH T-L ELECTRIC DRIVEN HYDRAULIC PUMP Used with T-L AB Panel wired for Auto Restart (CD51790 or D51795)

Load Control Water Pressure Auto Restart or Low Water Pressure Safety Time Delay Auto Restart Operation: Hot Shot with Smart Shot is powered by 24vac hot when disconnect is on. Water Pump operation depends on position of the “WELL” Switch in the T-L AB Panel. If Water Pressure Start Switch is used, Wet or Dry operation depends on position of the Wet/Dry switch in the T-L AB Panel. Wet Operation:

• T-L AB Panel Well Switch is up and Wet/Dry Switch is up.

• Remote/Local Switch in Smart Shot is in Remote position.

• Relay #2 of Smart Shot is not used. (Water Pump is controlled by Timer in the T-L Allen Bradley Panel.)

• Relay #3 of Smart Shot is Start/Stop pivot control. Relay is maintained (latched). Closes upon Start cmd, Open upon Stop cmd. Provides power to Term #11 of AB Panel to start or stop the pivot.

• Term #1 of the AB Panel is powered when the pivot starts, which powers the 24vac relay in the Smart Shot panel. Sensor Input #1 of the Smart Shot is now closed and shows the pivot is running.

• Power Company Auto Restart can start/stop the systems per normal Auto Restart function.

• If Load Control stops the system, Sensor Input #1 of the Smart Shot will open and notify the customer. Relay #3 of the Smart Shot will stay latched (Unless STOP is pressed on web site). When the Load Control is closed again, the system will auto restart since Relay #3 of the Smart Shot is still latched.

To T-L AB PANEL

Page 5: SMART SHOT UC T L INSTALLATION GUIDEzgofw.khfwq.servertrust.com/v/SSmanuals/Smart Shot... · version : 052715 smart shot uc t-l installation guide pg. 2-3 t-l elec ab panel, water

5

T-L AB Panel wired for Auto Restart (CD51790 or D51795) Load Control Water Pressure Auto Restart or Low Water Pressure Safety Time Delay Auto Restart

Dry Operation:

• T-L AB Panel Well switch is down and Wet/Dry switch is down.

• Remote/Local switch in Smart Shot is in Remote position.

• Relay #3 of Smart Shot will start and stop the pivot.

• Sensor Input #1 of Smart Shot will close indicating the pivot is moving. Local Operation:

• Remote/Local switch in Smart Shot is in Local position

• Operate the AB Panel per normal operation.

To Hot Shot

Page 6: SMART SHOT UC T L INSTALLATION GUIDEzgofw.khfwq.servertrust.com/v/SSmanuals/Smart Shot... · version : 052715 smart shot uc t-l installation guide pg. 2-3 t-l elec ab panel, water

6

SMART SHOT WITH T-L ENGINE DRIVEN HYDRAULIC PUMP Operation:

• Smart Shot is powered by 12vdc from engine battery.

• When engine is started +12vdc will energize the Smart Shot 12vdc relay and activate Sensor Input #1 on the Smart Shot indicating to the customer that the pivot is running.

• To Stop the pivot press the STOP button on the web site and Relay #3 on the Smart Shot will close for 8 sec-onds stopping the engine.

• The Smart Shot 12vdc relay will de-energize which will deactivate Sensor #1 on the Smart Shot indicating to the customer that the pivot has stopped.

Page 7: SMART SHOT UC T L INSTALLATION GUIDEzgofw.khfwq.servertrust.com/v/SSmanuals/Smart Shot... · version : 052715 smart shot uc t-l installation guide pg. 2-3 t-l elec ab panel, water

7

T-L ENGINE DRIVEN HYDRAULIC PUMP

yw

bk

rd bl yw

bk

rd bl

yw

bk

rd

bl

Page 8: SMART SHOT UC T L INSTALLATION GUIDEzgofw.khfwq.servertrust.com/v/SSmanuals/Smart Shot... · version : 052715 smart shot uc t-l installation guide pg. 2-3 t-l elec ab panel, water

8

SMART SHOT WITH T-L ELECTRIC DRIVEN HYDRAULIC PUMP Used with T-L 10 Term Strip AB Panel, NO Water Pressure Switch.

Operation: Hot Shot with Smart Shot is powered by 24vac hot when disconnect is on. Water Pump operation depends on position of the “WELL” Switch in the T-L Panel. If Water Pressure Start Switch is used, Wet or Dry operation depends on position of the Wet/Dry switch in the T-L Panel. Wet Operation:

• T-L Panel Well Switch is up.

• Remote/Local Switch in Smart Shot is in Remote position.

• Relay #2 of Smart Shot is not used.

• Relay #3 of Smart Shot is Start/Stop pivot control. Relay is maintained (latched). Closes upon Start cmd, Open upon Stop cmd. Provides power to Hand-Off-Auto switch in the T-L Panel to start or stop the pivot.

• Term #1 of the AB Panel is powered when the pivot starts, which powers the Hot Shot 24vac relay in the Smart Shot panel. Sensor Input #1 of the Smart Shot is now closed and shows the pivot is running.

• Power Company Auto Restart can start/stop the systems per normal Auto Restart function with no Water Pres-sure switch.

• If Load Control stops the system, Sensor Input #1 of the Smart Shot will open and notify the customer. Relay #3 of the Smart Shot will stay latched (Unless STOP is pressed on web site). When the Load Control is closed again, the system will auto restart since Relay #3 of the Smart Shot is still latched.

To T-L AB PANEL

Page 9: SMART SHOT UC T L INSTALLATION GUIDEzgofw.khfwq.servertrust.com/v/SSmanuals/Smart Shot... · version : 052715 smart shot uc t-l installation guide pg. 2-3 t-l elec ab panel, water

9

T-L ELECTRIC DRIVEN HYDRAULIC PUMP - 10 TERMINAL (PRIOR TO 1998) No Water Pressure Switch. See wiring change notes below.

Dry Operation:

• Hand/Off Auto Switch on the T-L panel needs to be in the OFF position.

• T-L Panel Well switch is down.

• Remote/Local switch in Smart Shot is in Remote position.

• Relay #2 of Smart Shot is not used.

• Relay #3 of Smart Shot will start and stop the pivot.

• Sensor Input #1 of Smart Shot will close indicating the pivot is running. Local Operation:

• Hand/Off Auto Switch on the T-L panel needs to be in the AUTO position.

• Remote/Local switch in Smart Shot is in Local position.

• Operate the AB Panel per normal operation.

TO Hot Shot

Reroute this red wire from Term #2 to Term #1 on the Hand/Off/Auto Switch.

Remove this factory installed red wire.

bk

rd

bl

or

br

Page 10: SMART SHOT UC T L INSTALLATION GUIDEzgofw.khfwq.servertrust.com/v/SSmanuals/Smart Shot... · version : 052715 smart shot uc t-l installation guide pg. 2-3 t-l elec ab panel, water

10

SMART SHOT WITH T-L ELECTRIC DRIVEN HYDRAULIC PUMP Used with T-L 10 Term Strip AB Panel wired for Auto Restart (CD51795)

Load Control Water Pressure Auto Operation: Hot Shot with Smart Shot is powered by 24vac hot when disconnect is on. Water Pump operation depends on position of the “WELL” Switch in the T-L AB Panel. If Water Pressure Start Switch is used, Wet or Dry operation depends on position of the Wet/Dry switch in the T-L AB Panel. Wet Operation:

• T-L Panel Well Switch is up and Wet/Dry Switch is up.

• Remote/Local Switch in Smart Shot is in Remote position.

• Relay #2 of Smart Shot is not used. Water pump is controlled by timer in the T-L AB Panel.

• Relay #3 of Smart Shot is Start/Stop pivot control. Relay is maintained (latched). Closes upon Start cmd, Open upon Stop cmd. Provides power to Term #3 of the T-L AB Panel to start or stop the pivot.

• Term #1 of the AB Panel provides 24vac hot after 1 min delay and Term#2 of the AB Panel provides 24vac neutral at startup. This powers Sensor Input #1 of the Smart Shot which shows the pivot is running. Once the water pressure is established the T-L pivot will start walking.

• Power Company Auto Restart can start/stop the systems per normal Auto Restart function.

• If Load Control stops the system, Sensor Input #1 of the Smart Shot will open and notify the customer. Relay #3 of the Smart Shot will stay latched (Unless STOP is pressed on web site). When the Load Control is closed again, the system will auto restart since Relay #3 of the Smart Shot is still latched.

To T-L AB PANEL

Page 11: SMART SHOT UC T L INSTALLATION GUIDEzgofw.khfwq.servertrust.com/v/SSmanuals/Smart Shot... · version : 052715 smart shot uc t-l installation guide pg. 2-3 t-l elec ab panel, water

11

T-L ELECTRIC DRIVEN HYDRAULIC PUMP - 10 TERMINAL (PRIOR TO 1998) Water Pressure Actuated Pivot and or Auto Restart—Load Control (CD51795)

Dry Operation:

• Hand/Off Auto Switch on the T-L panel needs to be in the Auto position.

• T-L Panel Well switch is down. Water Pressure switch is down “dry” position.

• Remote/Local switch in Smart Shot is in Remote position.

• Relay #3 of Smart Shot will start and stop the pivot.

• Sensor Input #1 of Smart Shot will close indicating the pivot is running. Local Operation:

• Hand/Off Auto Switch on the T-L panel needs to be in the Auto position.

• Remote/Local switch in Smart Shot is in Local position.

• The AB Panel Wet/Dry switch determines if the pivot will start.

• Operate the T-L AB Panel per normal operation.

To Hot Shot

Remove the red wire from transformer XF to Term #3.

bk

rd

bl

or

Connect to AC Ground Rod Terminal

br

Page 12: SMART SHOT UC T L INSTALLATION GUIDEzgofw.khfwq.servertrust.com/v/SSmanuals/Smart Shot... · version : 052715 smart shot uc t-l installation guide pg. 2-3 t-l elec ab panel, water

12

Warranty

The warranty below constitutes the only warranty in connection with any sale from Hot Shot Systems Inc. and is in lieu of all other warranties, express or implied, written or oral. THERE ARE NO IMPLIED WARRANTIES OF MERCHANT-ABILITY OR FITNESS FOR A PARTICULAR PURPOSE THAT AP-PLY TO ANY SALE FROM HOT SHOT SYSTEMS INC. Hot Shot Systems Inc., warrants to You that Products (Products meaning any item purchased form Hot Shot Systems) will be free from defects in materials and workmanship under normal use and service for one (1) year from the purchase date. A product issue under this Limited War-ranty must be presented during the Limited Warranty period and within thirty (30) days after any covered condition has occurred. A claim un-der this Limited Warranty shall be satisfied by either, in Hot Shot Systems sole discretion, repairing or replacing the Product. Replacement Products may be new or reconditioned.

To make a claim under this Limited Warranty, Hot Shot Systems must first issue You a Returned Material Authorization (RMA) number. This number can be obtained by calling Hot Shot Systems and a RMA number will be provided over the phone. A copy of the RMA number must be included with any materials shipped to Hot Shot Systems . The entirety of Products must be sent back to Hot Shot Systems and properly pack-aged to ensure against damage during shipping. If Hot Shot Systems determines that the claim is covered by this Limited Warranty, Hot Shot Systems will either, in its sole discretion, repair or replace the Products and/or part. Any damages not covered under this Limited Warranty will not be repaired until a purchase order is received.

The Limited Warranty period shall not be extended by the replacement or repair of Products or parts under this Limited Warranty but the re-maining Limited Warranty period shall continue in effect and be applicable to the replaced or repaired Products or parts under conditions of the Limited Warranty.

The term “Nation Wide Coverage” is not a guarantee of cellular coverage everywhere. Wireless service is subject to network and transmission limitations, including cell site unavailability, particularly near boundaries and in remote areas. Customer equipment, weather, topography and other environmental considerations associated with radio technology also affect service and service may vary significantly within buildings. The cellular service provided in conjunction with the purchase and use of Products and Services is not guaranteed, and Hot Shot Systems cannot and does not guarantee or represent that cellular service will be available in Your area nor that cellular service will be continuous and uninterrupted in Your area. It is Your responsibility to determine if cellular coverage is available in Your area and to monitor the Products and Services to determine the cellular signal strength to Products and Services. You should contact Hot Shot Systems for assistance if needed. If cellular service is not available in Your area, then Your sole remedy is to return Products and Services as provided for in Hot Shot Systems’ Return Policy as found at http://store.hotshotsystems.com/returns.asp. As such, Hot Shot Systems is not liable for any causes of action, losses or damages of any kind whatsoever arising out of mistakes, omissions, interruptions, errors, or defects in the provision of cellular service and failures or defects in the cellular network.

Intended Use. Products are intended for non pollutant, non hazardous and non critical use only. Products are to be used and installed per the installation guide and any other instructions provided by Hot Shot Systems (collectively, the “Seller’s Guidelines”). Any use beyond the intend-ed non pollutant, non-hazardous and non critical use or against the Seller’s Guidelines (“Unintended use”) are at the End-User’s own risk, and Hot Shot Systems does not warrant or make any representations whatsoever regarding the use of Products for any unintended use. Hot Shot Systems’ Products are convenience items and are not intended to be a substitute for normal maintenance, monitoring, control and proper upkeep of equipment or property that Products are monitoring or controlling. Hot Shot Systems’ Products are convenience items and are not intended to monitor equipment, control equipment, liquids, chemicals or other items which are pollutants, vital, hazardous, necessary, and/or have life-or-death consequences. The End-User should take care to determine prior to use whether Products are suitable, adequate or safe for the use intend-ed. Since individual applications are subject to great variation, Hot Shot Systems makes no representation or warranty as to suitability or fitness of Products for any specific application.

Upon expiration of the Limited Warranty period, all liability of Hot Shot Systems shall be terminated. This Limited Warranty will also be ter-minated immediate due to any of the following cases: failure to follow installation and operating instructions, misuse or "Unintended use", alteration, abuse, accident or tampering, and repair by anyone other than Hot Shot Systems. THIS LIMITED WARRANTY IS EXCLUSIVE AND EXPRESSLY IN LIEU OF ALL OTHER WARRANTIES, OBLIGATIONS OR LIA-BILITIES, WHETHER WRITTEN, ORAL, EXPRESS OR IMPLIED, INCLUDING ANY WARRANTY OF MERCHANT-ABILITY OR FITNESS FOR A PARTICULAR PURPOSE, OR OTHERWISE. IN NO CASE SHALL HOT SHOT SYSTEMS BE LIABLE TO ANYONE FOR ANY CONSEQUENTIAL OR INCIDENTAL DAMAGES FOR BREACH OF THIS WARRANTY OR ANY OTHER WARRANTIES WHATSOEVER. This Limited Warranty gives specific legal rights.

No employee, agent, dealer or other person is authorized to give any warranties on behalf of Hot Shot Systems Inc., nor to assume for it any other liability in connection with any of its products, except an officer of Hot Shot Systems Inc., in a signed writing. LIABILITY Hot Shot Systems Inc. and its directors, officers, employees, subsidiaries and affiliates shall not be liable for pollution, pollution clean up, per-sonal injury, property damage, hazardous conditions created, fluid spill cleanup, loss of product, loss of profit, or any other loss or expenses based on a claim the product(s) failed to operate properly. Test product daily to see if any malfunctions are present. If using this product in a situation where it is extremely critical to control your device to prevent damage of any kind, you must also use a call out system to notify a person in control of this situation. If this warranty and statement of liability is unacceptable, then do not purchase these products. Hot Shot Systems makes no representation that Products and Services will reduce any risk of property loss, product loss, loss of profit, pollution or personal injury or prolong the life of any equipment or other property; or that Products and Services will in all cases provide adequate warn-ing and protection. You understand that Products if properly installed and maintained may only reduce the risk of property loss or other loss but Products and Services are not an insurance or a guarantee that there will be no property loss, product loss, loss of profit, pollution or personal injury or other loss as a result. CONSEQUENTLY, HOT SHOT SYSTEMS SHALL HAVE NO LIABILITY FOR ANY POLLUTION, PRODUCT LOSS, LOSS OF PROFIT, PROPERTY DAMAGE, PERSONAL INJURY OR OTHER LOSS OR EXPENSES INCURRED BASED ON A CLAIM THE PRODUCTS AND SERVICES FAILED TO GIVE WARNING.