1. INTRODUCTIONRecent project experiences have shown that small to
medium sized solar arrays, often incorporated into a
building structure and operating in a grid interactive
mode, are one of the faster growing areas of
photovoltaic applications. A local Queensland
example is that up to 200 solar arrays, of up to 5kW
each, to be integrated into shade structures under the
solar schools project funded by Stanwell Corporation
Limited.
Traditional grid interactive inverters use a 50Hz
transformer with a low voltage power conversion
stage to connect to the grid. Although transformerless
designs have been proposed, [1], the isolation
provided by a transformer is highly desirable in a
smaller system. This paper is the result of
Queensland Sustainable Energy Innovation Fund
(QSEIF) grant which will allow CQU and Enertec to
jointly develop a commercial inverter using a high
frequency link during 2000. While this approach has
been used before, [2], converters of this type are only
feasible from an efficiency viewpoint due to recent
developments in switching devices and magnetic
materials, as well as new insights into loss control in
switching power converters.
This inverter design will establish new bench marks
for size, performance and value for grid interactiveinverters. An early indication of the outcomes is
given by the product size, the prototype 1.5 kW
converters, fit into a 170mm by 115mm by 60mm
package. The largest component, the high frequency
transformer, fits comfortably in the palm of the hand.
A Low Cost High Efficiency Inverter for Photovoltaic Applications
P.Wolfs, S.Senini
Central Queensland University
Dale ButlerEnertec Australia Pty Ltd
Abstract
Recent changes within the electricity industry, such as the 2% new renewable energy targets and
green energy marketing schemes will see significant growth in the number of solar generating
systems connected to the grid. The power electronics interfacing these systems to the grid can
become smaller, less costly and more efficient. In this paper a 1.5kW, single phase, grid interactive
inverter is proposed. This commercial inverter uses a high frequency link rather than the traditional
50Hz output transformer. Great care has been taken to achieve efficiency improvements that
justify the additional complexity. This paper presents the results of a simulation study which was
conducted to develop and verify the operation of the key control systems required by the inverter.
PV
Array
Switching
Stage
HF
Transformer
Rectification
StageUnfolding
Stage
Connection
to Mains
Figure 1. Topology of proposed grid interactive inverter.
7/29/2019 Solar Invertre
2/6
2. INVERTER TOPOLOGYThe proposed grid interactive system is shown in
Figure 1. The DC voltage at the array terminals is
converted to a rectified sinusoidal AC current
waveform at the output of the switching converter.This waveform is then unfolded to produce a unity
power factor AC current at the mains terminals.
The array voltage in this system is chosen to be
nominally 120V. The high frequency transformer has
a ratio of 3.2:1 so that the peak voltage available at
the output is 384V, which is sufficient to produce a
240VRMS+6% voltage at the inverter terminals.
Several unique features have been added. While these
will be discussed in detail in a future paper, points of
interest include:
Primary inverter leg inductors which prevent theMosfet body diodes from carrying anytransformer current during the bridge dead time,
allowing a better recovery of energy from the
transformer leakage inductance
Tapped output inductors, which divert theflywheel current from the output bridge to a
single extremely fast recovery diode, this allows
a reduction in total conduction and reverse
recovery loss.
As space is limited, this paper concentrates on the
control features of the converter.
3. INVERTER CONTROLThe inverter uses five major control loops which
operate at widely differing time scales. Discussion on
the inverter control is broken up into the following
sections:
Current Mode Control Sinusoidal Current Regulation DC Balance Control Phase locking and islanding detection
Array Voltage Regulation Maximum Power Point Tracking
3.1 Current Mode ControlThe inverter output current is controlled, in the first
instance by an analogue current mode controller,
(CMC). The current control loop on the switching
stage operates at 75 kHz and is implemented in
analogue circuitry using a LT3846 current mode
controller. The CMC controls the currents flowing in
the two 750 H filter inductors by adjusting theconduction times of the power Mosfet devices.
These Mosfets conduct in diagonally opposite pairs.A fixed frequency oscillator triggers the conduction
of a pair. Conduction normally finishes when the
inductor current reaches a set current demand. A
sinusoidal inverter current can be generated if the
inductor currents are forced to follow a suitably
shaped demand signal. This demand signal, a series
of sinusoidal half cycles of controlled peak
magnitude, is generated by an outer current loop.
The CMC is fully isolated from the power circuit,
transformer based drivers operate the Mosfets, while
the controlled current is detected at the transformer
primary via a current transformer (CT).
3.2 Sinusoidal Current RegulationAn outer current loop is required to reduce some
minor current distortion components that will occur
with a simple CMC control loop. These include
current errors due to:
Inductor current ripple, a CMC controls the peakrather than the average inductor current
Minimum switch on times and pulse dropping.
The average current is measured by a CT after theunfolding stage and compared with the desired
sinusoidal reference. The error is then passed into a
proportional-integral controller to generate a
correction signal. This correction signal is added to
the feed forward current demand signal sent to the
current mode controller. The control loop is shown in
Figure 2.
SetpointCurrent
Measured
Output Current
Current
Error
Proportional plus
Integral Controller
Current Control
Signal for CMC
+
- +
+
Figure 2. Control loop for outer current control.
The outer current loop is digitally implemented and
mains synchronised. The nominal sample rate is
200S. The input reference signal is taken from asinusoidal look up table and multiplied by a
7/29/2019 Solar Invertre
3/6
magnitude controlling factor which determines the
converter output power. This factor is generated by
the maximum power tracking system.
3.3 DC Balance ControlThe DC current injected into the mains must be
below a level specified by the relevant standards,
[3,4]. At this time in Australia the standards specify
7/29/2019 Solar Invertre
4/6
perturbation frequency. A larger capacitor masks any
fast changes in array power and hence requires a
lower frequency perturbation. Power measurements
are taken at the maximum and minimum points of
this perturbing sinusoid. Thus we have a change in
voltage and can measure the respective change inpower output.
The control law to provide continuous tracking of the
maximum power point is given by equation (1).
== dtV
PKdt
dV
dPKVshift (1)
where: Vshift is the change in operating point to
move closer to the maximum power point.
Kis a proportional gain constant
dV
dPis the differential change in power with
respect to voltage.P is the difference in power between two
operating points.
V is the difference in voltage betweentwo operating points.
Figure 4 shows the typical power versus voltage
curve for a solar array. Using this curve the operation
of equation (1) may be explained.
A
B
C
Voltage
Power
Figure 4. Typical Power versus Voltage curve for a
solar array.
Consider the system operating at points A, B and C.
The Table 1 indicates the control signal which willresult for each case: As Table 1 clearly shows, the net
movement for any operating condition is towards the
maximum power point. The control block diagram is
shown in Figure 5.
Table 1. Summary of control action for different
operating points on the power versus voltage curve of
Figure 4.
Operating
Point
V PV
P
ControlAction
A +
-
+
-
+
+
Increase V
Increase V
B +
-
-
+
-
-
Decrease V
Decrease V
C +
-
NC
NC
Zero
Zero
NC
NC
NC = No Change
SetpointVoltage
Measured
Array Voltage
VoltageError
Proportional plus
Integral Controller
Current MagnitudeSetpoint (A)
+
-
Limit Current to
Positive Demand only
Perturbation
Voltage
+
V
P
K
Measured
Array Voltage
Measured
Output Power
Sampled at maximum
and minimum of
perturbation
Figure 5. Complete maximum power tracker and
voltage regulation algorithm.
4. SIMULATION MODELThe control loops within the system operate over
widely varying time constants. The MPPT and
voltage regulation loops operate over times from
10ms to tens of seconds, while the current mode
control and current regulation operate on time scales
of microseconds to milliseconds. It is not feasible to
try to model all of these control loops in the same
simulation as the time required to run the simulation
may extend into weeks. Consequently the simulation
model is broken into two levels.
4.1 Level One ModelLevel one considers the operation of the array voltage
regulation and the MPPT algorithm. The model is
shown in Figure 6. The array is modeled according
to the physical equations which describe its
7/29/2019 Solar Invertre
5/6
operation, [9]. These equations are implemented in
SIMULINK in block diagram form. The equations
capture the relationship between input variables such
as luminance and temperature, and the output
variables voltage and current. This level of model
allows testing of the MPPT algorithm and the voltageregulation algorithm.
Solar
Array
Model
Average Load Current
i =Asin2(t)
Capacitor Filter
5000F
Figure 6. Level 1 model of grid connected inverter.
For the purpose of this model the current drawn bythe load is represented by its average value. The
average current has a function described by Equation
(2).
( ) ( )tAtiload 2sin= (2)
where: A is the magnitude of the current drawn
is the fundamental frequency inradians/second
Expansion of equation 2 shows that the inverter
current has a DC component, which is responsible for
the real power transfers from the array to the load,
and a double frequency 100Hz component. This100Hz component is characteristic of all single phase
power transfers. This current component will cause a
100Hz ripple voltage. The array voltage regulator
attempts to maintain the array voltage at the
maximum power point but cannot respond to the
100Hz ripple components. These ripples will move
the array off the maximum power point. Some of the
generation capacity is lost and this reduces the
overall system efficiency. The prediction of the
actual loss is complicated by the nonlinearity and
asymmetry of the Power-Voltage relationship. The
loss of power due to these 100Hz excursions may be
reduced by increasing the capacitor size. A larger
capacitor decreases the voltage regulator bandwidth
and raises the possibility of loss if the array insolation
changes frequently. These requirements are
conflicting.
The capacitor size should be large enough to limit the
100Hz voltage variation to a few percent of the
nominal bus voltage. The simulation model has been
used to predict the effects of increasing capacitor size
on the losses. Our simulations show that 5000 Flimits the losses from this effect to less than 0.5% of
the array rating at maximum power.
4.2 Level 2 ModelThe level two model allows testing of the control
algorithms and switching control for the inverter.
This model provides a more detailed representation
of the switching stages and therefore requires a much
greater time to run. The functions of maximum power
tracking and voltage regulation, which require several
seconds in real time to realize cannot be included in
this model, without requiring simulation times in
excess of several days. This model will be used to
verify the switching characteristics and the output
wave shape of the inverter.
The array in this model is modeled as a constant
source, which can supply any current. Over a few
mains cycles this is a valid representation. The
inverter model includes the switching stage, the
transformer and rectifier, and the unfolding stage as
exists in the real system. The circuit topology is
shown in Figure 1.
The simulation model has topological similarity to
the actual circuit. Each element (inductor, capacitor,
switches) has a mathematical representation in the
model. For example a switch may be represented as a
two valued resistance, which is low when the switch
is on and high when the switch is off. Individual
elements in the model are connected to form the
complete system. Switching controls are
implemented as logical functions in the simulation.
The generic switching behaviour of the circuit can be
represented, however the higher order models of
switches, which include true switching characteristics
are not included. Analysis to this degree requires yet
another level of simulation.
This model can be used to verify that the inverter and
proposed control algorithm will produce an
appropriate output. The output should have minimal
distortion so as to meet the standards for such aninstallation.
5. SIMULATION RESULTSFigure 7 shows the output current waveform for a
simulation at rated output power. As can be seen
from Figure 7 the current wave shape is sinusoidal
7/29/2019 Solar Invertre
6/6
with a small distortion around the zero crossings of
the waveform. This distortion is caused by the
requirement that the switches, once turned on, remain
on for a minimum time period, (the minimum on
time).
0 0.005 0.010.015 0.020.0250.03 0.0350.04-10
-8
-6
-4
-2
0
2
4
6
8
10
Time (seconds)
Current(Amps)
Graph of two cycles of mains current for Inverter
Figure 7. Output line current over two mains cycles
at full load.
As the current demand reduces the switch on time
becomes smaller than the minimum on time and the
wave shape deviates from sinusoidal. This is the
main cause of the waveform distortion and is largely
corrected by pulse dropping which is forced by the
secondary control loop. Increasing the secondary
controller bandwidth can reduce the magnitude of the
deviation, however too high a bandwidth will
produce instability. A tradeoff is required. The
simulation results are required to demonstrate the
stability of the system and verify that the distortion is
within acceptable limits.
0 100 200 300 400 500 600 700 800 900 10000
1
2
3
4
5
6
7
8
9
Frequency (Hz)
CurrentMagnitude
(Amps)
Spectrum of line current up to 1kHz
Figure 8. Spectrum of output line current at full load.
A spectral analysis of the current waveform is shown
in Figure 8 for frequencies up to 1kHz. The total
harmonic distortion level is found to be below 0.15%.
This is well within the allowable criteria for this
installation.
6. CONCLUSIONSThis simulation study has successfully been used to:
Develop control algorithms that deliver therequired levels of performance prior to the
actual construction of the converter hardware.
Even though high levels of detail have not beenprovided here, provided critical insights into the
sizing and ratings of key components such as
power devices, power inductors and capacitors.
Hardware prototypes are expected to available in the
last quarter of 2000. These will provide an interesting
opportunity to test the validity of the simulation
outcomes.
7. REFERENCES[1]. S.J.Chiang, K.T.Chang, C.Y.Yen, Residential
Photovoltaic Energy Storage System, IEEE
TIE, Vol 45, No 3, June, 1998, pp 385-394.
[2]. U.Herrmann, H.G.Langer,Low Cost DC to ACConverter for Photovoltaic Power Conversion
in Residential Applications, PESC93, 1993, pp
588-594.
[3]. Australian Guidelines for Grid Connection ofEnergy Systems via Inverters, ESAA, 1998.
[4]. IEEE P929/D11,Draft Recommended Practicefor Utility Interface of Photovoltaic (PV)
Systems, IEEE, November, 1999.
[5]. K.Masoud, G.Ledwich, Grid Connectionwithout Mains Frequency Transformers, JEEA,
Australia, Vol 19, No 1, June, 1999, pp 31-36.
[6]. S.Pang, Digital Signal Processor Basedcontroller for an AC traction Drive System,
Master of Engineering Thesis, CQU, 1995.
[7]. G.A.Smith,P.A.Onions,D.G.Infield, PredictingIslanding Operation of Grid Connected PV
Inverters, IEE Proceedings on Electric Power
Applications, Vol 147, No 1, Jan, 2000, pp 1-6.
[8]. P.Midya, P.T.Krein, R.J.Turnbull, R.Reppa,J.Kimball, Dynamic Maximum Power PointTracker for Photovoltaic Applications, PESC,
1996, pp 1710-1716.
[9]. C.Hua, J.Lin, C.Shen, Implementation of aDSP-Controlled Photovoltaic System with
Peak Power Tracking, IEEE TIE, Vol 45, N0
1, Feb, 1998, pp 99-107.