SHEET:TITLE:CLIENT:
PV-1
REVISIONS: DATE:
DESIGNBY:
JOBNO.:
SYSTEM SUMMARY,NIOTES, SITELOCATION ANDHOUSE AERIAL VIEW
DESCRIPTION DATE REVISION
PHOTOVOLTAIC SYSTEMPV SYSTEM SUMMARY: CITY NOTES:
ROOF MOUNT RESIDENTIAL PHOTOVOLTAIC SYSTEM
SYSTEM SIZE : STC: 36 X 265 = 9540W DC
PTC: 36 X 235.6 = 8481.6W DC
MODULE : 36 X SUNMODULE, SW 265 MONO BLACK, 265WMODULES
INVERTER : 1 X SMA SB 5000TL-US-22 & 1 X SMA SB 3000TL-US-22INVERTERS
ROOF : COMP TILE ROOF
TILT : R1 & R2 - 5 PITCH
AZIMUTH : R1 - 270 & R2 - 90
RAFTER/TRUSS SIZE : 2" X 4" RAFTERS @ 24" O.C
ATTACHMENT TYPE : QUICK MOUNT ATTACHMENTS
UTILITY : SOUTHERN CALIFORNIA EDISON (SCE)
SITE LOCATION:
HOUSE AERIAL VIEW:
12/22/2015
XXX
BAC-XXX
XXX XXXX1111, XXX STREETXXXXX, CA XXXXTel: (xxx) xxx xxxx
SITE LOCATION
ALL SOLAR ENERGY SYSTEM EQUIPMENT SHALL BE SCREENED TO THEMAXIMUM EXTENT POSSIBLE AND SHALL BE PAINTED A COLOR SIMILARTO THE SURFACE UPON WHICH THEY ARE MOUNTED
VISIBLE PORTIONS OF THE SOLAR PANEL SUPPORT STRUCTURE AND ANY EXPOSEDELECTRICAL CONDUITS, BOXES AND PANELS WILL NOT BE EXPOSED, AND WILL BECOLORED MATCHED TO EXISTING ROOF OR SURROUNDING HOME.
THIS PROJECT COMPLIES WITH THE FOLLOWING:2013 CALIFORNIA BUILDING CODE (CBC) / 2013 INTERNATIONAL BUILDING CODE (IBC)2013 CALIFORNIA ELECTRICAL CODE (CEC) / 2013 NATIONAL ELECTRICAL CODE (NEC)AS ADOPTED BY CITY OF ONTARIO
INSTALLATION NOTES:THE PV BREAKER SHALL NOT EXCEED 120% OF THE ALLOWABLE BACK FEED OF THE MAINSERVICE BUSS RATING.PV WIRE SHALL BE USED ON DC RUNS FOR UNGROUNDED/TRANSFORMERLESSINVERTERS.INSTALL CREW TO VERIFY ROOF STRUCTURE PRIOR TO COMMENCING WORK.
TABLE OF CONTENTSPV-1 SYSTEM SUMMARY, NOTES, SITE LOCATION ANDHOUSE AERIAL VIEW
PV-2 SITE PLAN / ROOF PLAN WITH MODULES LAYOUT
PV-3 DETAILS, MATERIAL LIST AND LABELS
PV-4 ELECTRICAL CALCULATION, EQUIP. ELEVATION &SINGLE LINE DIAGRAM
PV-5 DATA SHEET: MODULE AND INVERTER
PV-6 DATA SHEET: MOUNT & RAIL
MSP
MSP
ACD
FMLC
INV1
INV2
JB
JB
SHEET:TITLE:
PV-2
REVISIONS: DATE:
DESIGNBY:
JOBNO.:
SITE PLAN / ROOF PLANWITH MODULES LAYOUT
DESCRIPTION DATE REVISION
ROOF PLAN WITH MODULES LAYOUTSCALE: 3/32" = 1'-0" 2SITE PLANSCALE: 1/16" = 1'-0" 1
EXISTING MSPAC DISCONNECTFINANCE METER
EXTERNAL CONDUIT RUN
ROOF AREA STATEMENT
ROOF MODULESQTY PITCH AZIMTUH ROOF AREA ARRAY AREA
1 24 5 270 818.87 SQ FT 421.53 SQ FT2 12 5 90 644.48 SQ FT 211.97 SQ FT
W 4TH ST
DRIVE WAY
EXISTINGMSP
PROPERTY LINE
SMA SB 5000TL-USINVERTER
24 SUNMODULE SW 265MONO BLACK MODULES
ATTACHMENT POINTS@ 48" O.C. MAX (TYP)
12 SUNMODULE SW 265MONO BLACK MODULES
PROPOSED MODULES
ROOF LINE
JUNCTION BOX
LOAD CENTER
12/22/2015
XXX
BAC-XXX
24 SUNMODULE SW 265MONO BLACK MODULES
ATTACHMENT POINTS@ 48" O.C. MAX (TYP)
12 SUNMODULE SW 265MONO BLACK MODULES
3'-3"
3'
17'-10"
R-1
R-2
JUNCTION BOX
SMA SB 3000TL-USINVERTER
3'
3'
11'-8"
CLIENT:
XXX XXXX1111, XXX STREETXXXXX, CA XXXXTel: (xxx) xxx xxxx
SHEET:TITLE:
PV-3
REVISIONS: DATE:
DESIGNBY:
JOBNO.:
DETAILS, MATERIALLIST AND LABELS
DESCRIPTION DATE REVISION
MATERIAL LIST
QTY EQUIPMENT DESCRIPTION
36
SUNMODULESW 265 MONOBLACK, SOLAR
MODULES
OPEN CIRCUIT VOLTAGE (Voc) :MAX. POWER VOLTAGE (Vmp) :
SHORT CIRCUIT CURRENT (Isc) :MAX. POWER CURRENT (Imp) :
PTC RATING :
39.0V30.8V9.31A8.69A235.6V
1
SMA, SB5000TL-US-22
INVERTER WITHINTEGRATEDDISCONNECT
MAX. DC INPUT VOLTAGE :MAX. DC INPUT CURRENT :
MAX. AC OUTPUT VOLTAGE RANGE :MAX. AC OUTPUT CURRENT :
MAX. AC POWER OUPUT :CEC EFFICIENCY :
600V15A211-264V22A5000W96.5%
1
SMA, SB3000TL-US-22
INVERTER WITHINTEGRATEDDISCONNECT
MAX. DC INPUT VOLTAGE :MAX. DC INPUT CURRENT :
MAX. AC OUTPUT VOLTAGE RANGE :MAX. AC OUTPUT CURRENT :
MAX. AC POWER OUPUT :CEC EFFICIENCY :
600V15A211-264V15A3000W96%
2 JUNCTION BOX 600VDC, NEMA 4X, UL LISTED
1 ACDISCONNECT 600VAC, 60A, NEMA 3R, UL LISTED
1 LOAD CENTER 240VAC, 125A UL LISTED
1 PV BREAKER 2 POLE, 240V, 40A
1 METER LGATE 101 CPF METER
70' CONDUIT 3/4" EMT CONDUIT
66 ATTACHMENTS QUICKMOUNTATTACHMENTS
200' RAIL UNIRAC
64 MID CLAMPS
16 END CLAMPS
LABELS
W 4TH ST
LABEL: MAIN SERVICE PANEL
12/22/2015
XXX
BAC-XXX
ENLARGED DETAIL 2
ATTACHMENT DETAIL 1
PV MODULE
QUICK MOUNTATTACHMENTS
"L" BRACKETMODULE
MOUNTINGRAIL
SS LAG BOLT
2" X 6" RAFTERS @ 24" O.C
PV MODULE
MODULEMOUNTING RAIL
"L" BRACKET
SS LAG BOLT
QUICK MOUNTATTACHMENTS
2
PV-4
ROOF
4"
LABEL: MAIN SERVICE PANEL EXISTINGSUBPANEL, AND EXISTING EQUIPMENT TIED INTO.
LABEL: INSTALLED SUBPANELS AND FUSEBOXES.
LABEL: INSTALLED JUNCTION BOXES,COMBINER BOXES AND GUTTER BOXES.
LABEL: AC, DC DISCONNECT OROTHER DISCONNECTING MEANS.
LABEL: INSTALLED INVERTER
LABEL: INSTALLED JUNCTION BOXES,COMBINER BOXES AND GUTTER BOXES.
LABEL: INSTALLED DC JUNCTION BOX
LABEL: INSTALLED AC AND DC DISCONNECTS
ALL PLACARDS SHOULD BE WITH WHITE LETTERING IN RED BACKROUND WITH A MIN. OF 3/8"LETTERING HEIGHT AND USING ARIAL OR SIMILAR FONT, NON-BOLD AND ALL CAPITAL LETTERS
CLIENT:
XXX XXXX1111, XXX STREETXXXXX, CA XXXXTel: (xxx) xxx xxxx
SHEET:TITLE:
PV-4
REVISIONS: DATE:
DESIGNBY:
JOBNO.:
ELECTRICALCALCULATION, EQUIP.ELEVATION & SINGLELINE DIAGRAM
DESCRIPTION DATE REVISION
SINGLE LINE DIAGRAMSCALE: NTS 1
ELECTRICAL CALCULATIONS:STRING 1 CIRCUIT CURRENT CALCULATION:2 X 12 SUNMODULE 265W MODULESCONNECTED TO 1 SMA 5000TL kW INVERTER
MAX. INVERTER OUTPUT POWER: 5000WNOMINAL VOLATGE: 240VRATED OUTPUT CURRENT: 22 AMPS
OVERCURRENT PROTECTION22.0 X 1.25 = 27.50 AMPS
BREAKER CAPACITY = 30 AMPS
UMINVERTER
FINANCE METER
AC DISCONNECT
MAIN SERVICEPANEL
ELECTRICAL EQUIP. ELEVATIONSCALE: NTS 2
FLOOR
DC DISCONNECT
ROOFTOPJUNCTION BOX
TO ARRAYTO UTILITYPOLE
FM
LOAD CENTER
BACKFEED CALCULATION200 X 1.2 = 240 AMPS240 - 200 = 40 MAX. BACKFEED
FM
UM
JB
JB
FROM UTILITYPOLESMA 5kW
INVERTER WITHINTEGRATED
AC/DCDISCONNECT
LGATE 101CPF METER
60A, ACDISCONNECT
TOLOADS
4 - #10 AWG, USE-21 - #8 AWG, BARE COPPER GROUND
4 - #10 AWG, THWN-21 - #8 AWG, THWN-2
3 - #8 AWG, THWN-21 - #8 AWG, THWN-2
2 - #10 AWG, THWN-21 - #8 AWG, THWN-2
JUNCTIONBOX
JUNCTIONBOX
EXISTING 200A,240VAC
DISCONNECT
EXISTING 200A,240VAC, MSP
40A, 2POLE, PVBREAKER
DCAC
DCAC
12/22/2015
XXX
BAC-XXX
STRING-112 SUNMODULE 265W
MODULES
STRING-212 SUNMODULE 265W
MODULES
STRING-112 SUNMODULE 265W
MODULES
2 - #10 AWG, THWN-21 - #8 AWG, COPPER GROUND
SMA 3kWINVERTER WITH
INTEGRATEDAC/DC
DISCONNECT
STRING 2 CIRCUIT CURRENT CALCULATION:1 X 12 SUNMODULE 265W MODULESCONNECTED TO 1 SMA 3kW INVERTER
MAX. INVERTER OUTPUT POWER: 3000WNOMINAL VOLATGE: 240VRATED OUTPUT CURRENT: 15 AMPS
OVERCURRENT PROTECTION12.0 X 1.25 = 15.00 AMPS
BREAKER CAPACITY = 15 AMPS
LOADCENTER
125A,240V
30A, 2P240VAC15A, 2P240VAC
(E) GEC
CLIENT:
XXX XXXX1111, XXX STREETXXXXX, CA XXXXTel: (xxx) xxx xxxx
SHEET:TITLE:
PV-5
REVISIONS: DATE:
DESIGNBY:
JOBNO.:
DATA SHEET:MODULE & INVERTER
DESCRIPTION DATE REVISION 12/22/2015
XXX
BAC-XXX
CLIENT:
XXX XXXX1111, XXX STREETXXXXX, CA XXXXTel: (xxx) xxx xxxx
SHEET:TITLE:
PV-6
REVISIONS: DATE:
DESIGNBY:
JOBNO.:
DATA SHEET:MOUNT & RAIL
DESCRIPTION DATE REVISION 12/22/2015
XXX
BAC-XXX
CLIENT:
XXX XXXX1111, XXX STREETXXXXX, CA XXXXTel: (xxx) xxx xxxx