Sonar Interface Level

Embed Size (px)

Citation preview

  • 8/8/2019 Sonar Interface Level

    1/85

    PRESENTATION

    SONAR INTERFACE LEVEL

    1

    Waste Water

    Sewage Treatment

    Pulp and Paper

    Food Plants

    Steel Plants

    Alumina Refineries

    Chemical Plants

    Fertilizer Plants

    Mining Process

  • 8/8/2019 Sonar Interface Level

    2/85

    PRESENTATION

    SONAR INTERFACE LEVEL

    2

    Index

    Sonar principle of operation

    Applications

    Sewage Treatment Plants (traditional)

    Sewage Treatment Plants (Sequential batch reactor)

    Water Treatment Plants

    Mining Thickeners

    Waste Water Treatment Plants

    Cleaning mechanisms for Sonar Transducers

    Portable Interface Analyser

    SA Sonar Data Sheet

    SA Sonar Instruction Manual

    Advantages of level monitoring interface

    PIA Instruction Manual

    Sonar Diagrams

  • 8/8/2019 Sonar Interface Level

    3/85

    PRESENTATION

    SONAR INTERFACE LEVEL

    3

    Sonar Principals of OperationThe Hawk "SA" Sonar Level Transmitter emits a sound pulse towards the interface blanket (bed level,

    settling solids etc) which is at the bottom of the tank (sedimentation tank, primary clarifier, secondary

    clarifier, humus tank, thickener DAF tank, tailings dam etc).

    The pulse signal is reflected off the interface, back to the sonar transducer. The sonar transducer

    interprets the signal, compensates for temperate and provides a distance reading and output,

    proportional to the distance between the sonar transducer and interface level. The display can read

    from the sonar transducer down to the interface, or from the bottom of the tank to the top of the

    interface.

    Selcting a Sonar Transducer Frequency

    Performance of a Sonar interface transmitter is very dependent on the choice of the sonar transducer

    operating frequency.

    Example (1) Water Treatment Plant(measuring floculent blanket)

    Floc is very light in density and can vary for different water types and the sources of the water.

    To detect the actual interface, we must use a high frequency (short wavelength) sonar transducer to

    detect the small impedance difference between the water and floc interfaces. This frequency range

    could typically be between 300kHz and 700kHz. Floculant is added to encourage settling of solids

    particles

    Note:A lower frequency sonar transducer may not see the floc interface at all and measure the tankbottom only.

    Example (2) Mining Process Thickener(measuring bed level)

    There could be two interface levels that are of interest to metalurgists or process engineers, in a mining

    thickener application.

    Bed Level

    The bed level density is generally high in comparison to other interfaces in the thickener tank.

    To measure the "bed" only and not be affected by the lighter floc level or particles in suspension, we

    must use a lower frequency sonar transducer to "diffract" around the particles and "See through" thelighter densities in suspension. These sonar frequencies can range from 70kHz down depending on the

    size and density

    To measure the "floc layer" interface that sits above the bed level which is lighter in density, we

    use a higher frequency sonar transducer than for the bed level. These sonar frequencies range from

    150kHz to 30 kHz.

    By selecting the appropriate sonar frequency, we optimize the amplitude of the return signal from

    the chosen interface to minimize commissioning time.

    RETURN TO CONTENTS

  • 8/8/2019 Sonar Interface Level

    4/85

    PRESENTATION

    SONAR INTERFACE LEVEL

    4

    The advantages in using sonar interface transmitters on thickener tanks are:

    (1) By controlling the underflow pump rate, the density of the bed can be optimised for

    downstream process requirements.

    (2) The sonar transmitter can measure to the bottom of the tank and is not affected by

    the scraper passing underneath. Other interface technologies eg. displacement float,

    electrical mechanical dipping infra-red can only measure above the scraper.

    (3) When the sonar transmitter is used in conjunction with an underflow density gauge

    there can be a determination if the tank is being over flocced, which can result in a lower

    bed density.

    (a) The underflow density gauge reads a lower density. The sonar interfacemonitors a bed level that is at an "acceptable level".

    Possible cause: over floccing the tank.

    (b) The underflow density gauge reads a lower density, the scraper torque

    amperes are high, the sonar interface monitors a bed level that is low, reduce the underflow

    pump rate and build the bed higher.

    Cause: overpumping rate on the underflow pump.

    (4) When the sonar interface transmitter is used it can provide feedback to the "Floc

    dosing control loop" when there is an increase in suspended solids between the sonarsensor and bed level.

    This could be attributed to,

    (a) Stratified layers at varying densities appearing at different levels.

    (b) Pinfloccing in suspension or other particles in suspension not settling.

    Both problems require further consideration to floc dosing control, where (a) could be

    improved perhaps with an increase floc dose rate, (b) pinfloc in suspension could indicate

    a problem with the bed and other suspended solids in suspension at a high level could

    require higher floc dosing.

    (5) Using scraper torque amperes for controlling underflow pump rates can be a major

    problem.

    (a) Scraper amperes are affected by density changes and do not relate only to

    bed level

    (b) Mechanical wear and tear will affect scraper amperes

    (c) Thickener infeed rate will affect scraper amperes.

    RETURN TO CONTENTS

  • 8/8/2019 Sonar Interface Level

    5/85

    PRESENTATION

    SONAR INTERFACE LEVEL

    5

    Sewage Treatment Plants

    Sludge Interface Level Applications

    Traditional Treatment plants- Primary

    - Secondary

    - Thickener (D.A.F) Dissolved air floatation

    IDEA Sequential Batch Reactors

    Application Notes

    - Sludge level in sedimentation tanks- Interface level in Secondary Clarifiers

    RETURN TO CONTENTS

  • 8/8/2019 Sonar Interface Level

    6/85

  • 8/8/2019 Sonar Interface Level

    7/85

    PRESENTATION

    SONAR INTERFACE LEVEL

    7

    Sewage Treament Plants: Sludge Interface Applications

    (A) Primary sedimentation tank

    Primary Clarifier

    The main application of the sonar interface transmitter for these tanks is to,

    (1) Maintain a bed level in the tank by controlling the settled solids sludge pump.

    The advantages are:

    (A) To optimise the density of the sludge being pumped to the thickener or to the

    DAF tanks (dissolved air floatation tanks).

    (B) To reduce wear of the sludge pump.(C) To reduce running costs eg electricity, maintenance etc.

    (D) Reduce the run time of filter presses.

    (E) Provide alarm status on tanks on continous barsts.

    (B) Secondary Clarifier / Final clarification

    The main applications for the sonar interface transmitter for these tanks are

    (1) Maintain a bed level in the tank, by controlling the RAS pump (return activatedsludge.

    (2) Provide alarms or monitor fluff/pinfloc levels rising in the tank. (Fluff/Pinfloc is

    caused by an out of balance biological affect and results in an increase of suspended

    solids in the clarifier)

    The advantages are:

    (A) To optimise the density of the sludge being pumped back to the aeration tanks

    (RAS) and to optimise the sludge being pumped to the thickener, "DAF" tanks (wasteactivated sludge

    (B) To reduce wear of the sludge pump.

    (C) To reduce "loading" of the aeration and thickener "DAF" tank areas.

    (D) To reduce electricity and running costs.

    (E) To reduce manpower requirements by autmation.

    (F) To provide alarms over a GSM/page system, especially at unmanned treatment

    plants, if the clarifier becomes unsettled and high levels of solids flow into the clarifier

    launder.

    RETURN TO CONTENTS

  • 8/8/2019 Sonar Interface Level

    8/85

    PRESENTATION

    SONAR INTERFACE LEVEL

    8

    (C) Thickener Tank

    The main application of the sonar interface transmitter for these tanks are

    (A) To optimise the density of the bed level being pumped to the digester, by

    controlling the underflow pump.

    (C) To provide alarm status, with high levels of suspended solids above the bed

    (D) Used with an underflow density gauge, can provide feedback for control of floc

    to the thickener to reduce floc useage.

    (E) To reduce electricity and running costs.

    (F) To reduce manpower requirements.

    (G) Improve the performance of digestors by optimising the density pumped to

    the digestor.

    (H) Provides alarm status on a continuous basis, especially on unmanned sites.

    RETURN TO CONTENTS

  • 8/8/2019 Sonar Interface Level

    9/85

    PRESENTATION

    SONAR INTERFACE LEVEL

    9

    Application Note Controlling Sludge level in PrimarySedimentation Tanks

    Instrument: Hawk SAR-D-BS Transmitter ST002 sonar transducer

    Client: Melbourne WaterSite: Eastern Treatment PlantApplication Primary sedimentation-Sludge interface control

    Eastern treatment plant, is one of Australias largest sewerage treatment plants processing over450ML perday. There are 8 primary clarifers, all of which run 24 hours a day. Melbourne Waterrequired automaticcontrol of the primary sludge pump catering for peak and off peak loads, tooptimize the density of the sludgepumped to the DAF tanks. As well as reducing the load imposedon the sludge scraper blades to reduce wearand maintenance downtime. To do this they requireaccurate measurement of the interface blanket with asonar interface transmitter that had anautomatic cleaning mechanism. The interface transmitter neededto operate without operatorassistance, especially after hours.The system had many advantages over timedrelated solutions. Melbourne Water uses this systemin a controlled loop configuration, rather than just monitoringpurposes

    The unit is mounted to the side

    of the clarifier.The transducer

    is mounted just under the

    surface of the water. The

    transmitter is locatedin the control

    cabinet aprox 10 metres away.

    The actuator strokes the transducer

    in and out ofthe water with a

    definite action causing any

    buildup to be removed. This unit has

    been in thesewerage for over 2

    years without requiringmanualcleaning.

    The profile of the tank shows a very defined interface. This

    means that there is excellent settling of the solids with minimal

    light interface. You can see from the above screen save that the

    echo off the interface is over 2.5 volts. Melbourne Water have

    used the analogue signal from this instrument to control the

    speed of the pump which sends the sludge to the DAF area. Our

    unit can monitor the level so they can ensure that they optomise

    the sludge density while at the same time not let the level get tohigh which will put more wear on the mechanical scrapers

    Bottomof tank

    Sludgeinterface

    Transmitpulse

    1.7 metres

    RETURN TO CONTENTS

  • 8/8/2019 Sonar Interface Level

    10/85

    PRESENTATION

    SONAR INTERFACE LEVEL

    10

    Application Note Primary Sedimentation TankBeenyup STP

    Hawk SAR-D-BS, ST002 Sonar Transducer and Impact Plate

    RETURN TO CONTENTS

  • 8/8/2019 Sonar Interface Level

    11/85

    PRESENTATION

    SONAR INTERFACE LEVEL

    11

    SONAR INTERFACE TRANSMITTER WITH IMAPACT PLATE

    Typical mounting of

    the "SAR" transmitter

    with sun hood on walkway

    Sonar transducerwith impact plate

    cleaner mechanism

    Counter

    weight

    Sonar

    Transduce

    Typical installation of a sonar

    interface transmitter on a "clarifier",

    "thickener", "primary sedimentation

    tank", that has a surface scum

    collector, showing sonar sensor and

    impact plate

    Impact plate

    Part No.

    ST002-4X2P

    SAR-D-SH

    Sonar Transducer

    with impact plate

    Sonar Transmitter

    RETURN TO CONTENTS

  • 8/8/2019 Sonar Interface Level

    12/85

    APPLICATION

    HAWKMEASUREMENTSYSTEMS

    SONAR-SCUMC

    LE

    ANING

    ELECTRICACTUATORASSEMBLY

    Mounting:Thescumcleaningmechanismi

    sgenerally

    mountedfr

    omt

    hebridgeonaclarifier,thick

    enerorfrom

    thesideof

    the

    tanknearthemoveablelaunderona

    IDAL/Sequ

    entialbatchtank.

    Sonarsensormounted

    belowwate

    rlevel.

    Sonarscumc

    leaning

    m

    echanismi

    ninitial

    position

    Electr

    icActuator

    >

    Sonars

    cumc

    leaning

    mechan

    ismf

    ull/extended.

    Note:le

    ngthofstrokeis

    adjustable.

    Electric Actuator

    >

    Sonar scum cleaning mechanism,

    in its initial position mounted to

    bridge on a clarifier or thickener

    using angle iron bracketsonar

    ansducer

    Sonar

    Transducer

    Application Note Sonar Scum Cleaning Mechanism

    Full/extended length of stroke is adjustable

    RETURN TO CONTENTS

  • 8/8/2019 Sonar Interface Level

    38/85

  • 8/8/2019 Sonar Interface Level

    39/85

  • 8/8/2019 Sonar Interface Level

    40/85

    PRESENTATION

    SONAR INTERFACE LEVEL

    RETURN TO CONTENTS

    Impact Plate

  • 8/8/2019 Sonar Interface Level

    41/85

    PRESENTATION

    SONAR INTERFACE LEVEL

    RETURN TO CONTENTS

    ITEM NO.QTY. DRAWING NO. DESCRIPTION

    1 1 HAW_A_SA-SS-SBA

    2 1 HAW_A_SA-SS-EPA

    1 HAW_A_SA-0 Sonar Sensor

    2

    1

    3

    Sonar Sludge Swing Bracket

  • 8/8/2019 Sonar Interface Level

    42/85

    Diagram

    NON CONTACT LEVEL MEASUREMENT

    SONAR TRANSDUCER + SCUM BRUSHDiagram

    Mounting: Flange or External Bracket

    Sealing : Sonar Transducer IP68

    Scum Brush IP68 (weited area)

    9

    >

    Scum Brush Motor / Electrics24 VDCSupply from SAR-D Transmitter

    10 >

    316 SS Protection tubefor rotating shaft

    8

    >

    Nylon Brush

    7

    >

    Replaceable Brush

    6

    >

    Sealed Bearing

    4

    >

    Sonar SensorST002

    2> 1.0" BSP nipple 316SS

    5>

    3> 316SS

    Mounting pole

    5>Bracket to supportScum Brush motor

    11

    >

    Wiring to SAR-DTransmitter

    >>

  • 8/8/2019 Sonar Interface Level

    43/85

    FUNCTION

    The portable (PIA) weatherproof analyzer, allows for an early

    determination of where the interface is. When the interface is

    detected, an audible signal, as well as either a Bar Graph indicating

    percentage or a 0 - 100% digital display, provides the operator

    with all the necessary information to accurately gauge the interface

    depth.

    Because the analyzer uses sonar technology, it is not affected

    by colour change, (eg. use of ferric chloride). A single sensor

    works on all density levels, including applications with heavy

    solids, such as the Daf area in a sewage treatment plant.

    TYPICAL APPLICATIONS

    s WASTE WATER TREATMENT PLANT: Primary andSecondary Clarifier Interface or bed level. Daf Plant.

    s MINING: Clarifiers, thickeners, settlers, settling ponds.

    s FOOD: Carbon columns.

    s WATER: Clarifiers, potable and raw water plants.

    KEY FEATURES

    s Single sonar transducer, handles all density ranges.

    s Rugged stainless (316SS) sonar transducer plus

    metal carrying case and battery charger.s Audible alarm when interface detected, as well as digital

    display.

    s Not affected by colour change.

    INTERFACE LEVEL MONITORING

    Portable InterfaceAnalyzerPIA Series

    Portable Sludge and Interface Level Analyzer

    Range: 0 - 20,000 mg/1Not affected by colour change

    PATENTS PENDING

    AUS

    TRALIAN

    MANUFACTU

    RE

    D

    DESIGNED

    & Approved

    PORTABL

    EINTRFAC

    EANALYZ

    ER

    ONOFF

    ENT

    1

    DATA SHEETAUGUST 2001

    ENT

    ONOFF

    PORTABLEINTRFACEANALYZER

  • 8/8/2019 Sonar Interface Level

    44/85

    I N T E R F A C E L E V E L M O N I T O R I N G

    Portable Interface AnalyzerPIA Series

    2

    Principal of Operation

    The PIA Series Sonar Interface/Density Analyzer

    consists of a Hand Calibrater and the appropriateSSA-1-2-10 sonar transducer.

    The transducer may be used on a wide range of

    densities. The Interface/Density Analyzer, detects

    a density change and provides an autible alarm as

    well as a Bar Graph Display.

    Example:

    High density sludge with suspended solids can use

    the same sensor as used for lower density

    sludge/interfaces.

    The PIA Sonar Interface/Density Analyzer transmits

    a sound pulse towards the reflector plate. The pulse

    signal is reflected off the plate, back to the sonar

    transducer, then the PIA Analyzer interprets the

    signal, compensates for temperature and provides,

    an audible output and display of the sludge/interface.

    Echo processing software monitors the operating

    efficiency of the sonar transducer. When the density

    of the monitored liquid increases or decreases thischange is displayed on the PIA Hand Calibrator in

    % terms or simple bar graph representation. The

    auto zero can be set in clean water or an area in

    the tank where a lower density is known to be. This

    will become the zero point and will show a

    corresponding change on the Display (0%) of the

    Hand Analyzer.

    Using the Portable Interface Analyzer

    As the PIA can be used in very light densities eg:

    (water clarifier, measuring floculent) to heavy

    densities (thickeners), an auto-calibrate is required

    to set the zero (0%). The transducer (SSA-1) is

    immersed below the surface of the liquid. A simple

    push button function, will auto calibrate the

    instrument to zero. Lowering the transducer into

    the vessel, will see the display change in percentage,

    as the density changes. An audible alarm, can be

    set for a desired density level. Changing liquid

    colours has no effect on the interface reading.

    Features

    s Full range of Echo processing software to cover

    the heavy and light density interfaces.

    s Audjble buzzer for blanket level detection,programmable to operate at a required density.

    s NEMA 4X (IP67) enclosure for PIA Analyzer.

    s NEMA 4X (IP68) enclosure for Sonar Transducer.

    s Full operational diagnosics display on theoperation of the PIA Analyzer.

    s Simple Auto Calibrate function.

    s Re-chargable batteries, with battery charger.

    s 4 hours continuous operation.

    s One Sonar Sensor does all Densities.

    DATA SHEETAUGUST 2001

  • 8/8/2019 Sonar Interface Level

    45/85

    DIMENSIONS

    3

    I N T E R F A C E L E V E L M O N I T O R I N G

    Portable Interface AnalyzerPIA Series

    PIA Remote Sonar Density AnalyzerP/N: (PIA-1-D)

    PIA Remote Sonar TransducerP/N: (SSA-1-2-10)

    50mm

    243mm

    90mm

    130mm

    42mm

    60mm

    1" BSPNipple

    25mm

    180mm

    60mm

    PORTABLE INTRFACE ANA LYZER

    ENT

    ONOFF

    DATA SHEETAUGUST 2001

  • 8/8/2019 Sonar Interface Level

    46/85

    4

    DATA SHEETAUGUST 2001

    I N T E R F A C E L E V E L M O N I T O R I N G

    Portable Interface AnalyzerPIA Series

    SPECIFICATIONS

    PART NUMBERING

    Range

    0 20,000mg/1

    Operating Voltage

    4 x 1.5V batteries

    Display

    % change

    Bar graph

    Alarm

    Audible alarm

    Electronic Accuracy + 0.25% of maximum range

    Operating Temperature

    Remote electronics

    -20C (-4F) to 60C (140F)

    Remote transducer

    -20C (-4F) to 100C (212F)

    Transducer/Amplifier Separation

    10m (33ft) supplied (longer cable on request)

    Display

    2 x 8 digit alphanumeric LCD with Diagnostics

    Memory

    Non-Volatile (No backup battery required)

    >10 years data retention

    Enclosure Sealing

    Remote Analyzer IP67

    Remote Transducer IP68

    Typical Weight

    Remote Analyzer 1kg (2.2lb)

    Remote Transducer 2kg (4.4lb)

    Transducer

    316 Stainless Steel (Other Materials option)

    SSA-1

    HOUSING MATERIAL0 = UPVC2 = Stainless Steel4 = Polypropylene5 = PVDF Kynar6 = Teflon

    10 = Cable lenth 10 metres (Standard)

    SSA-1 - 2 - 10

    PIA Series Transducer

    Hawk Measurement Systems

    15-17 Maurice CourtNunawading 3131 Victoria Australia

    Telephone: 61 3 9873 4750

    Facsimile: 61 3 9873 4538

    E-mail Address: [email protected] Site: http://www.hawklevel.com

    ADDITIONAL PRODUCT WARRANTY AND APPLICATION GUARANTEES UPON REQUEST.

    TECHNICAL DATA SUBJECT TO CHANGE WITHOUT NOTICE.

    Represented by:

    8/01

    Measurement Systems

    PIA Remote Sonar Interface Analyzer

    MODEL

    PIA-1 = Sonar Interface Analyser (PORTABLE)

    (Complete with metal carrying

    case and battery charger)

    Charging KitD = 220 to 240Vac

    E = 110 to 120Vac

    PIA-1 - D

  • 8/8/2019 Sonar Interface Level

    47/85

    Installation and Operating Instructions

    Portable InterfaceAnalyzerSonar - PIA Series

    Interface level monitoring

    Measurement Systems

    AUS

    TRALIAN

    MANUFACTU

    RE

    D

    DESIGNED

    &

    Approved

  • 8/8/2019 Sonar Interface Level

    48/85

    1

    INTRODUCTION

    PROPRIETARY NOTICE

    The information contained in this publication is

    derived in part from proprietary and patent data.

    This information has been prepared for the express

    purpose of assisting operating and maintenance

    personnel in the efficient use of the instrument

    described herein.

    Publication of this information does not convey

    any rights to use or reproduce it, or to use for any

    purpose other than in connection with the

    installation, operation and maintenance of the

    equipment described herein.

    Copyright 1995

    Printed by Graphic Zone, Australia

    All Rights Reserved.

    WARNING

    This instrument contains electronic components

    that are susceptible to damage by static electricity.

    Proper handling* procedures must be observed

    during the removal, installation, or handling or

    internal circuit boards or devices.

    * Handling Procedure1. Power to unit must be removed.

    2. Personnel must be grounded, via wrist strap or

    other safe, suitable means, before any printed

    circuit board or other internal device is installed,

    removed or adjusted.

    3. Printed circuit boards must be transported in

    a conductive bag or other conductive container.

    Boards must not be removed from protective

    enclosure until the immediate time of

    installation. Removed boards must be placed

    immediately in a protective container fortransport, storage, or return to factory.

    Comments:

    This instrument is not unique in its content of ESD

    (electrostatic discharge) sensitive components.

    Most modern electronic designs contain

    components that utilize metal oxide technology

    (NMOS, CMOS, etc.) Experience has proven that

    even small amounts of static electricity can damage

    or destroy these devices. Damaged components,

    even though they appear to function properly,

    exhibit early failure.

    CONTENTS

    PRINCIPLE OF OPERATION 2

    ST SELECTION GUIDELINES 2

    SPECIFICATIONS 3

    DIMENSIONS 5

    MOUNTING 7

    FACIA 8

    WIRING 9

    PARAMETER and FLOW CHARTS 13

    FLOW CHARTS 14

    TRACKING 16

    WARRANTY/PART NUMBERING 18

    Edition: No. 1

    SONAR - PIA Series

  • 8/8/2019 Sonar Interface Level

    49/85

    2

    PRINCIPALE OF OPERATION

    The PIA Series Sonar sends a series of high

    frequency pulses to thr reflecting plate andmonitors the return sigal. Whn an interfacewith a higher density than the calibrateddensity is reached, the calibration density isreached, the return signal size changes. Thischange in signal size is reflected in the displaychanging according to the difference detected.

    Differing densities may be zeroed out bycalibration. Always chooseto calibrate in thelowest density position within the liquid tobe tested. The lowest density will be set as a

    SONAR - PIA Series

    SPECIFICATIONS

    zero point. Densities higher than this will

    cause the display to increase its displayedvalve. The gain valve and the sensitivitysetting for the auto cal operation can beobserved by pressing the up and downbutton. The top line of the display will showthese settings.

    A manual adjustment for fine tuning or forsmall density changes can be best adjustedwithin the manual adjustment under the trimheading.

    Range

    0 20,000mg/1

    Operating Voltage 4 x 1.5V batteries

    Display

    % change

    Bar graph

    Alarm

    Audible alarm

    Electronic Accuracy

    + 0.25% of maximum range

    Operating Temperature

    Remote electronics

    -20C (-4F) to 60C (140F) Remote transducer

    -20C (-4F) to 100C (212F)

    Transducer/Amplifier Separation

    10m (33ft) supplied (longer cable on request)

    Display

    2 x 8 digit alphanumeric LCD with Diagnostics

    Memory

    Non-Volatile (No backup battery required) >10 years data retention

    Enclosure Sealing

    Remote Analyzer IP67

    Remote Transducer IP68

    Typical Weight

    Remote Analyzer 1kg (2.2lb)

    Remote Transducer 2kg (4.4lb)Transducer

    316 Stainless Steel (Other Materials option)

  • 8/8/2019 Sonar Interface Level

    50/85

    3

    SONAR - PIA Series

    DIMENSIONS

    PIA Remote Sonar Density AnalyzerP/N: (PIA-1-D)

    243mm

    90mm

    130mm

    PORTABLE INTRFACE ANALYZER

    ENT

    ONOFF

    42mm

    60mm

    Sludge %35.6%

  • 8/8/2019 Sonar Interface Level

    51/85

    4

    SONAR - PIA Series

    PIA Remote Sonar TransducerP/N: (SSA-1-2-10)

    DIMENSIONS contd

    50mm

    1" BSPNipple

    25mm

    180mm

    60mm

  • 8/8/2019 Sonar Interface Level

    52/85

    5

    SONAR - PIA Series

    PIA Remote Sonar Case

    DIMENSIONS contd

    PORTAB

    LEINTRFACEAN

    ALYZER

    ENTO

    NOFF

    Sludge%

    35.6%

    PIA Handheld Analyzer

    SSA Sensor

    Battery Charger

    Charging /Battery Replacement

    Whn the A.C. power supply is connected to the PIA no charging of the batteries occur.

    To re-charge the battery it is necessary to use the battery charger supplied. Batteries

    may be removed by carefully gripping the base of the PIA where the indentations are

    located. Push these two (2) places and remove the bottom seal.

    A tongue is attached to allow the battery pack to be removed. It is necessary to push

    down on the tongue to release this pack. Pull out the pack. There are five (5) batteries

    (1.2 V Nickl Metal Hydride). If you replace these batteries with new batteries they MUST

    be the same type.

  • 8/8/2019 Sonar Interface Level

    53/85

    CAL

    6

    CALIBRATION PROCEDURE

    SONAR - PIA Series

    Sludge %

    35.50%

    Unlock:0

    Disp Mode

    Sludge %

    CAL

    CalibrateNo

    Damping10

    SW Point30%

    Alarm SetNo

    CodeNo

    Set UpTrim

    Set Up

    Press RUN for 1 sec to start unit operating.

    Press RUN for 1 sec to stop unit operating.

    The sensor must be lowered into the liquid where the density (% Solids) is the lowest. The sensormust be lowered to where the reflecting bracket is beneath the liquid surface by a minimum ofat least 20mm.It would be best to lower the sensor until the black sealing cap is at the liquid level.Once this is done follow the Normal Calibration procedure under SET UP heading (for large %solids change in the liquid) or the Fine Calibration under TRIM heading which is better for liquidswhere there is a smaller % solids change.

    Sludge %

    Gn 80% (operating gain diagnostic)Sens 9 (sensitivity setting diagnostic)

    Allows or coded entry 0-200

    Enter code if coded entry is used. adjustments can be accelerated byholding the up or down button and then push the CAL button.

    No

    Sludge %

    Bar Graph

    Yes

    NoCalibrate

    Wait

    CalibrateDone

    Sledge %0.0%

    CAL

    CAL

    CAL

    CAL

    CAL

    CAL

    RUN * When the sensor is lowered this will increase Sludge % displayed value.

    If no change is shown when the sensor is lowered you should go to Trim

    heading and manually adjust the gain to read 0.5% at the point you knowto be the lowwest % solids, then press RUN and repeat the loweringproceedure of the transducer into the liquid to be monitored.

    Normal Calibration

    No

    Yes

    No

    Yes

    Audible Alarm % Set Point

    Allows audible alarm to actuateat SW Point % selected

    Access Code Adjustment

    Trim

    0-239 Allows damping of the display

    *

  • 8/8/2019 Sonar Interface Level

    54/85

    CAL

    CALIBRATION PROCEDURE

    Sludge %35.50%

    Unlock:0

    CalibrateNo

    Sens 535.50%

    Set UpTrim

    Set Up

    Trim

    CAL

    CAL

    Fine Calibration

    7

    SONAR - PIA Series

    Trim

    Sludge35.5%

    RUN

    Yes

    No CAL

    Gn:50%35.50%

    CAL

    RUNCalibrate

    No

    RUN

    Sludge %0.5%

    When the sensor is lowered this %value will increase with increasingSludge %.

    Adjust Sensitivity1-91 = low sensitivity9 = high sensitivity

    Manual gainadjustment forselected sensitivitynumber. Adjust toread 0 to 0.5% ondisplay

    Resume normaloperation

    Sludge %

    Gn 80% (operating gain diagnostic)

    Sens 9 (sensitivity setting diagnostic)

    Set UpTrim

  • 8/8/2019 Sonar Interface Level

    55/85

  • 8/8/2019 Sonar Interface Level

    56/85

  • 8/8/2019 Sonar Interface Level

    57/85

    Hawk Measurement Systems Pty. Ltd.ACN 006 782 449

    15-17 Maurice CourtNunawading 3131 Victoria Australia

    Telephone: 61 3 9873 4750Facsimile: 61 3 9873 4538

    INTERNET: http://www.hawklevel.com.au

    E-mail Address: hawks ale s@h awk .co m.a u

    Measurement Systems

  • 8/8/2019 Sonar Interface Level

    58/85

    INTERFACE LEVEL MONITORING

    Sonar Level TransmitterSA Series

    DATA SHEETJANUARY 2004

    1

    FUNCTION

    Bed/Interface/Sludge Blanket, continuous levelmeasurement using HAWKs comprehensive range ofSonar Transducers and proven Sonar echo processingalgorithms.

    TYPICAL APPLICATIONS

    WASTE WATER TREATMENT PLANT: Primaryand Secondary Clarifier interface level,

    Sequential batch reactors, Idal plants, Thickeners.

    MINING: Clarifiers, thickeners, settlers, settlingponds. (Coal, Zinc, Nickel, Lead, Iron,

    Magnesium, Copper, Aluminium)

    FOOD: Carbon columns, Thickeners, Clarifiers.

    WATER: Clarifiers, Thickeners, and raw waterplants.

    KEY FEATURES

    Widest range of Sonar Transducers to improveinterface measurements, especially light andvery heavy densities.

    Automatic cleaning mechanism removes build-up on the Sonar sensor, especially where scalingand suspended solids are present.

    Surface skimmers in primary clarifiers can beaccomadated with the addition of the skimmerimpact plate.

    INTERFACE LEVEL MONITORING

    Sonar LevelTransmitterSA Series

    Sludge, Interface / Bed Level, Water Clarity.

    Sonar frequency range from 1mHz to 10kHzdepending on Interface Density.

    SPECIAL SONAR TRANSDUCERVersion with 150mm Blanking Range.

    GSM Modem for remote technical anddiagnostic support.

    ApprovedAUS

    TRALIAN

    M

    ANUFA CTU

    RED

    DESIGNED

    &

    SAA. Class 1 Zone 1 pendingSAA. Class 1 Zone 0 pending

    SONAR with GSM capabilit y

  • 8/8/2019 Sonar Interface Level

    59/85

    INTERFACE LEVEL MONITORING

    Sonar Level TransmitterSA Series

    DATA SHEETJANUARY 2004

    2

    PRINCIPAL OF OPERATION

    The SA Series Sonar Level System consists of an SAtransmitter and the appropriate ST001, ST002, ST003,

    ST004, ST005, ST006, ST007, ST008, ST009, ST010,

    sonar transducer.

    The transducer selection will vary dependent upon

    the density of the interface to be detected. Performance

    is very frequency (sonar transducer) dependent.

    Example:

    High density sludge with suspended solids

    will use a lower frequency transmitter, to defract

    the signal around the particles in suspension.

    Lower density sludge/interfaces require higher

    frequency transducers in order to maximize the return

    signal.

    The SA Sonar level transmitter emits a sound pulse

    towards the interface/sludge which is at the bottom

    of the clarifier/tank, etc. The pulse signal is reflected

    off the interface, back to the sonar transducer, then

    the level transmitter interprets the signal, compensates

    for temperature and provides a distance reading, and

    an analog output proportional to the sludge/interface

    height. Modbus Communications is also available.

    Echo processing software monitors the operating

    efficiency of the sonar transducer. As the efficiency

    of the transducer drops off due to build-up on the

    sensing face (generally caused by fats settling out, or

    suspended solids attaching to the transducer), the

    sonar transmitter will increase the level of ultrasonic

    cleaning of the face or where fitted will activate the

    automatic Scum Cleaner which will remove all heavy

    build-up on the sonar transducer.

    As a rule, the lower the frequency, the greater the

    pressure wave with each pulse, the greater the

    cleaning.

    Application Example:

    Mining Thickener. (Dense mud layer)

    For this application we must use a low

    frequency sonar transducer to measure the

    bed level and not see the floc interface level.

    We select the ST009 (15kHz) sonar transducer

    and appropriate housing material for chemical

    compatibility. Also select the auto-scum

    cleaner because of suspended solids that will

    attach to the sensor, as well as minimizing

    scale build-up. High temperature service to

    150C (302F).

    FEATURES

    Full range of sonar transducers to optimisedetection of heavy and light density interfaces.

    The SA Sonar transmitter handles all Hawksonar transducers.

    Standard range to 15 metres. Option: 30 metres.

    Ultrasonic cleaning (light build-up) of the sonartransducer face and automatic control of theheavy build-up Scum Cleaner (option).

    4-20mA (Isolated) analog output for blanket/bedlevel or distance to blanket/bed (interface).

    200m sonar transducer/sonar transmitterseparation distance.

    NEMA 4X (IP67) enclosure for SA transmitter. 4 relays, field programmable for control purposes.

    Modbus Communications, RS485.

    Windows based Sonar Hawk diagnostic andcommunication software.

    Full operational diagnostics display on the SAtransmitter.

    Special Short Blanking Range.

    GSM Modem for remote technical and diagnosticsupport.

    Bed Level monitoring / Floc Control

    Using a specially chosen low frequency transducer guaranteesthat the bed level will always be the largest echo. This is veryimportant for floc control. (See Hawk application sheet onthickener interface measuring.)

    DATA BLOCK

    Name = Input A

    Date = 19/01/95

    Time = 10:35:32 PM

    Y scal e = 500 mV/ Div

    Y at 50% = 1.54 V

    X scal e = 500 us /Di v

    X at 0% = -0.50 ms

    X size = 250 (254)

    Maximum = 2.66 V

    Minimum = -0.03 V

    Input B

    19/01/95

    10:35:32 PM

    1 V/Div

    -2.68 V

    500 us/Div

    -0.50 ms

    250 (254)

    Overload

    -0.16 V

    CURSOR VALUESX1 : 0 .74ms

    X2 : 3 .26 ms

    dX : 2 .52 ms

    Y1 : -0.20 -0.16 V

    Y2 : 0.94 1.12 V

    dY : 1.14 1.28 V

    Thickener application for Sonar Interface

    Bottomof Tank

    Bed Level

    Floc Interface

    Transmit Pulse

    500 us/Div 1.4m per mill isecond

    * Consult Factory

  • 8/8/2019 Sonar Interface Level

    60/85

    INTERFACE LEVEL MONITORING

    Sonar Level TransmitterSA Series

    DATA SHEETJANUARY 2004

    WIRING DIAGRAM

    3

    SA Remote Transducer Wiring

    DIMENSIONS

    ST001 - ST010

    Black, Brown & Shieldto be joined together.

    DC-IN RS485ModbusTestInput

    IsolatedOutput

    RemoteControl Switch

    GREEN

    YELLOW

    TEST-IN

    +DC

    ACTIVE

    NEUTRAL

    TRANSDUCER

    BLACK

    RED

    BLUE

    WHITE

    A BICOM I- I+

    GND

    GND

    1ND

    1C

    1NC

    2ND

    2C

    2NC

    3ND

    3C

    3NC

    Pull

    Com

    Push

    GND

    GND

    GND

    BROWN

    RemCirt

    F303Sensor500mA, T

    F302Actuator10A, T

    AC Fuse1A, T

    301

    4 . . .20mA

    GND

    AC Power Relay 1 Relay 2 Relay 3Actuator

    Power

    N/C

    RED

    Yellow

    GREEN

    YELLOW

    TEST-IN

    +DC

    ACTIVE

    NEUTRAL

    TRANSDUCER

    BLACK

    RED

    BLUE

    WHITE

    A BICOM I - I +

    GND

    GND

    1ND

    1C 1NC

    2ND

    2C 2NC

    3ND

    3C 3NC

    Pull

    Com

    Push

    GND

    GND

    GND

    GND

    RemCirt

    F302Sensor500mA,T

    F302Actuator10mA,T

    ACFuse1A,T

    301

    4 ...20mA

    GND

    A C P o wer Relay 1 Relay 2 Relay 3Actuator

    Power

    N/C

    RED

    Yellow

    CAL

    RUN

    RELAY 1

    RELAY 2

    RELAY 3

    SLUDGE

    MASTER

    ECHO

    TX

    ST TransducerST001 - ST010

    1" BSPNipple

    75mm

    A or B

    SA Remote Transmitter

    175mm(6.9")

    186mm(7.3")

    302mm(

    11.9

    ")

    A ST001 - ST006 135mm

    B ST007 - ST010 250mm

  • 8/8/2019 Sonar Interface Level

    61/85

    INTERFACE LEVEL MONITORING

    Sonar Level TransmitterSA Series

    DATA SHEETJANUARY 2004

    4

    DIMENSIONS

    ST Auto Scum Cleaner (Option)

    1.3m

    400mm

    510mm

    2

    2

    400mm

    56

    3

    4

    Base mounting plate to bemounted on brackets or onclarifier structure.

    71 Base mounting plate (Stainless steel)

    2 Mounting holes (10mm)

    3 ST Transducer mounting pipe

    4 ST Transducer

    5 Electro-actuator

    6 ST Transducer termination enclosure7 Special ST Short Blanking Range

  • 8/8/2019 Sonar Interface Level

    62/85

    INTERFACE LEVEL MONITORING

    Sonar Level TransmitterSA Series

    DATA SHEETJANUARY 2004

    5

    FLOATING SONAR SENSOR

    SONAR INTERFACE TRANSMITTER WITH IMPACT PLATE

    SONAR - SCUM CLEANING ELECTRIC ACTUATOR ASSEMBLY

    Tank level variation can be from50mm (2) to 5.0m (advisedecant range)

    Float rises and fallsdepending on tank levels

    Cleaning mechanismwith electrical actuator

    Measuring positionfloat/sensor perpendicularto water surface

    APPLICATIONS:Monitoring interface bed level and settlingsolids on SBR/Idea Tanks. Ideal for all sonarinterface applications where the upper liquidtank varies and requires continous monitoringof settling interface and blanket.

    Cleaning actuatorextended duringcleaning cycle Pipe guide

    Polystyrene Float

    Sonar Sensormaximum range 30 metres Stainless Steel BaseFriction Grips (2)

    MOUNTING: The scum cleaning mechanism isgenerally mounted from the bridge on a clarifier,thickener or from the side of the tank near themoveable launder on a IDAL/ Sequential batch tank.Sonar senor mounted below water level.

    Sonar scun cleaningmechanism mountingpossibilities.(See manual for dimensions)

    Sonar scun cleaningmechanism in initialposition

    Sonar scun cleaningmechanism in fullyextended position.Note:length of

    stroke is adjustable.Sonar Transducer

    Cleaning mechanism

    with electrical actuator

    Typical installation of a sonarinterface transmitter on aclarifier, Thickener, primarysedimentation tank, that hasa surface scum collector,showing sonar sensor andimpact plate.

    Typical mounting of the SARtransmitter with Sun Hood on walkway

    Impact Plate

    Sonar Transducer

    Counterweight

    Sonar transducer with

    impact plate cleanermechanism

  • 8/8/2019 Sonar Interface Level

    63/85

    INTERFACE LEVEL MONITORING

    Sonar Level TransmitterSA Series

    DATA SHEETJANUARY 2004

    6

    Laptop or PC Communications

    or PLC / DCS with

    MODBUS RTU Port

    Goshawk Software for

    Inventory monitoring on P.C.

    GSM Network

    or

    CDMA Network

    Communication Network Overview Modbus, Profibus

    Multidrop connection of Sultan "AW" Ultrasonics, Variable "AS" Admittance Probes, Sonar "SA" interface transmitter

    Sultan "AW"Ultrasonic Transmitter

    Floatation Cells

    Sultan "AW"Ultrasonic Transmitter

    Slurries

    Variable AS

    Admittance

    Switch

    Sultan "AW" Ultrasonic TransmitterSilo, bin levels, coal, plastic powder,

    woodchip, sawdust, cement,clinker, iron ore, lime etc.

    Sonar "SA" Interface.

    Thickener, CCD

    GSM or CDMA Network Typically up to 32 transmitters or switches per string.

    Maximum 256 transmitters or switches.

    Using GSM/CDMA network, transmitters and switches can be

    monitored, calibrated remotely.

    Alarm status, diagnostics can be monitored.

    Support from factory engineering for customer application problems.

    Specifications for all other communication systems, eg HART, Profibus,

    Modbus etc check instruction manual.

    Sultan "AW"Ultrasonic SwitchBlocked Chute Detection

    Sonar "SA" Inteface Clarifier

    SULTAN 234

    SULTAN 234

    Sultan AW TransmitterStockpiles, Stackers,

    Reclaimers

    SONAR "SA" with GSM or CDMA NetworkUsing the GSM or CDMA modem with the Sonar

    Interface allows for technical assistance from our

    factory trained experts and design engineers.

    The SA Sonar can be Commissioned,Re-Programmed, Monitored and supported

    anywhere in the world where GSM or CDMA

    networks are found, by factory specialists.

    This provides Customers in remote locations the

    highest possible level of support.

    Up to

    32 sonar

    transmitters

    off one GSM

    modem

    Sultan "AWSTA" Smart TransducerFarm Tanks, Grain Terminals

  • 8/8/2019 Sonar Interface Level

    64/85

    DATA SHEETJANUARY 2004

    INTERFACE LEVEL MONITORING

    Sonar Level TransmitterSA Series

    7

    SPECIFICATIONS

    SA TransmitterMEASUREMENT RANGE

    0.4/0.8 to 15.0 metres - Transducer dependentOption: 30.0 metres

    Sonar tranducer frequency - All frequency versions

    MINIMUM DENSITY

    0.2% (For lower density consult the factory.)

    ACCURACY

    0.5% of span

    RESOLUTION

    Better than 10mm

    TEMPERATURE

    -20 Degrees C. to 60 Degrees C.

    DISPLAY

    1 x 16 digit alpha/numeric display.

    ECHO PROCESSING

    Advanced Sonar Hawk algorithms.

    OUTPUTS

    Analog 4-20mA (Isolated) max. 700 ohms

    Relays: 4 x S.P.D.T. 10A/240Vac non-inductive

    Driver for Auto scum cleaner

    Modbus Communications RS485

    DIAGNOSTICS

    Full operational diagnostics display.

    ENCLOSURE

    NEMA 4x (IP67) polycarbonate - wall mount.OPTION

    Automatic scum cleaner

    Sun hood

    WEIGHT

    3kgs (6.6 lbs)

    ST TransducerTRANSDUCER SELECTION

    See sonar transducer selection guidslines.ST001, ST002, ST003, ST004, ST005, ST006,ST007, ST008, ST009, ST010.

    HOUSING

    Polypropylene, PVDF (Kynar), Teflon and PVC.

    SEALING

    IP68 (Fully encapsulated)

    SPECIAL BLANKING

    150mm minimum

    TEMPERATURE SENSOR

    Internal (max. 60C Standard) high Temperature150C with external pre-amp.

    MOUNTING 1.00 inch BSP/NPT nipple

    CABLE

    Belden 83659/Tycab DMC 71402

    WEIGHT

    3.5kg

    APPROVALS

    SAA. Class 1 Zone 1 pending

    SAA. Class 1 Zone 0 pending

    Auto Scum Cleaner (Option)CONSTRUCTION

    Stainless Steel

    MOUNTING

    Base mount x 4 holes. (see drawing)

    ACTUATOR

    Electric 24VdcPneumatic Contact factory

    WEIGHT

    15Kg

    Typically, the most difficult task when wanting to determine the level

    of an interface, lies in the correct selection of the transducer frequency.

    There are many other variables to consider. They include particle size,

    flow, velocity, material, air bubble retention . . .

    IN GENERAL, THE FOLLOWINGSHOULD BE UNDERTAKEN:

    (1) Identify a position away from direct inflow, where turbulence is

    minimised.

    (2) If air bubbles are present within heavy suspended solids, use the

    scum cleaner option.

    (3) The transducer selection should be:

    ST TRANSDUCER SELECTION GUIDELINES

    % SOLIDS TRANSDUCER BLANKING

    >8% ST001 400mm

    5-8% ST002 400mm

    2% - 5% ST003 400mm

    1% - 2% ST004 400mm

  • 8/8/2019 Sonar Interface Level

    65/85

    DATA SHEETJANUARY 2004

    INTERFACE LEVEL MONITORING

    Sonar Level TransmitterSA Series

    ST Series Transducer

    * Note: Floating Sonar Sensor used for

    Sequential Batch Reactors,

    Idal Plants, etc.

    ST001ST002ST003ST004ST005ST006 See Table

    ST007ST008 HOUSING MATERIALST009 0 = UPVCST010 4 = Polypropylene

    5 = PVDF Kynar6 = Teflon44 = Full Polypropylene

    AUTO SCUM CLEANERA = Electric Actuator 24VdcB = Pneumatic Actuator

    C = Motorised Scum BrushX = Not required

    MOUNTING EXTENSION PIPE (Metres)X = Not required

    IMPACT PLATE (for Surface Skimmer)P = Impact Plate

    X = Not required

    HIGH TEMPERATUREH = High Temp

    X = Not required

    BLANKINGX = NormalS = Special Short Blanking

    FLOATING SONAR SENSOR*X = Not requiredF = Float

    SENSOR Ex RATINGEx = Class 1 Zone 1Exin = Class 1 Zone 0

    ST001 - 4 A 2 P H X X

    }TRANSDUCER % SOLIDS BLANKING

    ST001 >8% 400mm

    ST002 5-8% 400mm

    ST003 2% - 5% 400mm

    ST004 1% - 2% 400mm

    ST005

  • 8/8/2019 Sonar Interface Level

    66/85

    Installation and Operating Instructions

    SLUDGE MASTER

    Sonar Level Transmitter

    SA Series

    Interface level monitoring

    Measurement Systems

    AUS

    TRALIAN

    MANUFACTU

    RE

    D

    DESIGNED

    &

    Approved

  • 8/8/2019 Sonar Interface Level

    67/85

    1

    INTRODUCTION

    PROPRIETARY NOTICE

    The information contained in this publication is

    derived in part from proprietary and patent data.

    This information has been prepared for the express

    purpose of assisting operating and maintenance

    personnel in the efficient use of the instrument

    described herein.

    Publication of this information does not convey

    any rights to use or reproduce it, or to use for any

    purpose other than in connection with the

    installation, operation and maintenance of the

    equipment described herein.Copyright 1995

    Printed by Graphic Zone, Australia

    All Rights Reserved.

    WARNING

    This instrument contains electronic components

    that are susceptible to damage by static electricity.

    Proper handling* procedures must be observed

    during the removal, installation, or handling or

    internal circuit boards or devices.

    * Handling Procedure1. Power to unit must be removed.

    2. Personnel must be grounded, via wrist strap or

    other safe, suitable means, before any printed

    circuit board or other internal device is installed,

    removed or adjusted.

    3. Printed circuit boards must be transported in

    a conductive bag or other conductive container.

    Boards must not be removed from protective

    enclosure until the immediate time of

    installation. Removed boards must be placed

    immediately in a protective container for

    transport, storage, or return to factory.

    Comments:

    This instrument is not unique in its content of ESD

    (electrostatic discharge) sensitive components.

    Most modern electronic designs contain

    components that utilize metal oxide technology

    (NMOS, CMOS, etc.) Experience has proven that

    even small amounts of static electricity can damage

    or destroy these devices. Damaged components,

    even though they appear to function properly,

    exhibit early failure.

    CONTENTS

    PRINCIPLE OF OPERATION 2

    ST SELECTION GUIDELINES 2

    SPECIFICATIONS 3

    DIMENSIONS 5

    MOUNTING 7

    FACIA 8

    WIRING 9

    PARAMETER and FLOW CHARTS 13

    FLOW CHARTS 14

    TRACKING 16

    WARRANTY/PART NUMBERING 18

    Edition: No. 1

    SONAR - SA Series

  • 8/8/2019 Sonar Interface Level

    68/85

    2

    PRINCIPALE OF OPERATION

    The SA Series Sonar Level System consists ofan SA transmitter and the appropriate ST001,ST002, ST003, ST004 or ST005 sonartransducer.

    The transducer selection will vary dependentupon the density of the interface to bedetected.

    Example:High density sludge with suspendedsolids will use a lower frequencytransmitter - ST001 or ST002.

    Lower density sludge/interfaces require higherfrequency transducers in order to maximisethe return signal - ST003, ST004 or ST005.

    Note:

    See guideline selection chart for sonartransducers.

    The SA Sonar level transmitter emits a soundpulse towards the interface/sludge which isat the bottom of the clarifier/tank, etc. Thepulse signal is reflected off the interface, backto the sonar transducer, then the leveltransmitter interprets the signal,compensates for temperature and providesa distance reading, and an analog outputproportional to the sludge/interface height.

    Echo processing software monitors theoperating efficiency of the sonar transducer.As the efficiency of the transducer drops offdue to build-up on the sensing face (generallycaused by fats settling out, or suspended

    solids attaching to the transducer), the sonartransmitter will increase the level ofultrasonic cleaning of the face or where fittedwill activate the automatic Scum Cleanerwhich will remove all heavy build-up on thesonar transducer.

    SONAR - SA Series

    ST TRANSDUCER SELECTION

    GUIDELINES

    % Solids Transducer Blanking

    >5% ST001 800mm

    2-5% ST002 600mm

    0.5% - 2% ST003 500mm

    0.2% - 0.5% ST004 400mm

  • 8/8/2019 Sonar Interface Level

    69/85

    3

    SPECIFICATIONS

    SONAR - SA Series

    % Solids Detection>5% ST-001

    2-5% ST-002

    0.5-2.0% ST-003

    100m (334ft)

    Cable

    TYCAB DMC 71402 or BELDEN 83659

    Maximum Operating Pressure

    30 P.S.I. (2 Bar)

    Beam Angle

    10 years data retention

    Enclosure Sealing

    Integral System IP67

    Remote Electronics IP67

    Remote Transducer IP68

    Cable Entries

    IP68 cable glands Integral: 2 x 16mm

    Remote: 3 x 16mm

    Mounting

    ANSI, JIS or DIN Flange

    4 in/100mm or 10 in/250mm

    BSP Thread / NPT Thread 2in or 3in

    Typical Weight

    Remote Amplifier 2kg (4.4lb)

    Remote Transducer 2kg (4.4lb)

    Actuator 15kg (33lb)

    SA Transmitter

    Measurement Range

    0.4/0.8 to 10.0 metres - Transducerdependent

    Option: 30.0 metres

    Minimum Density

    0.2% (For lower density consult thefactory.)

    Accuracy

    0.5% of span

    Resolution

    Better than 10mm

    Temperature

    -20 Degrees C. to 60 Degrees C.

    Display

    2 x 8 digit alpha/numeric display.

    Echo Processing

    Advanced Sonar Hawk algorithms.

    Outputs

    Analog 4-20mA (Isolated) max. 700 ohms

    Relays: 4 x S.P.D.T. 10A/240Vacnon-inductive

    Driver for Auto scum cleaner

  • 8/8/2019 Sonar Interface Level

    70/85

    Diagnostics Full operational diagnostics display.

    Enclosure

    NEMA 4x (IP67) polycarbonate - wall

    mount.

    Option

    Automatic scum cleaner

    Weight

    3kgs (6.6 lbs)

    ST Transducer

    Transducer Selection

    See sonar transducer selection

    guidslines. ST001, ST002, ST003,

    ST004 and ST005.

    Housing

    Polypropylene, PVDF (Kynar), Teflon and

    PVC.

    Sealing

    IP68 (Fully encapsulated)

    4

    SPECIFICATIONS

    SONAR - SA Series

    Temperature Sensor Internal (max. 60C Standard) high

    Temperature 90C

    Mounting

    1.00 inch BSP/NPT nipple

    Cable

    Belden 83659/Tycab DMC 71402

    Weight

    3.5kg

    Approvals

    Auto Scum Cleaner (Option)

    Construction

    Stainless Steel

    Mounting

    Base mount x 4 holes. (see drawing)

    Actuator

    Electric 24Vdc

    Pneumatic

    Weight

    15Kg

    Approved

  • 8/8/2019 Sonar Interface Level

    71/85

    5

    DIMENSIONS contd

    ST Auto Scum Cleaner (Option)

    1.3m

    400mm

    510mm

    2

    2

    400mm

    56

    3

    4Base mounting plate to bemounted on brackets or onclarifier structure.

    1 Base mounting plate (Stainless steel)

    2 Mounting holes (10mm)

    3 ST Transducer mounting pipe

    4 ST Transducer

    5 Electro-actuator

    6 ST Transducer termination enclosure

    SONAR - SA Series

  • 8/8/2019 Sonar Interface Level

    72/85

    6

    DIMENSIONS contd

    ST Transducer ST001 - ST005

    1" BSPNipple

    75mm

    135mm

    SA Remote Transmitter

    SONAR - SA Series

    175mm(6.9")

    186mm

    (7.3")

    302mm(11.9

    ")

  • 8/8/2019 Sonar Interface Level

    73/85

    7

    MOUNTING

    SONAR - SA Series

    Transmitter Enclosed

    Sun Shield

    The RangeMaster Amplifier should be mounted out of direct sunlight. If mounted outside, the

    RangeMaster should face away from the sun and have a sunshield fitted.

    300mm (11.8")

    400mm(15.75")

    450mm (17.7")

    281mm (11.06")

    Mounting holes - 5mm/0.197" dia. 4 places

    166mm(6.5")

  • 8/8/2019 Sonar Interface Level

    74/85

    8

    FACIA

    SONAR - SA Series

    SLUDGE

    MASTER

    ECHO

    TX

    CAL

    RUN

    RELAY 1

    RELAY 2

    RELAY 3

    Transmit PulseIndicator

    Return Signal

    SwitchingRelays

    ActuatorPositionIndicator

  • 8/8/2019 Sonar Interface Level

    75/85

    9

    WIRING

    SA Remote Transducer Wiring

    ST001 - ST005

    Black, Brown & Shieldto be joined together.

    Extending Transducer Cable

    Use TYCAB DMC 71402 or BELDEN 9538

    WHITE

    BLUE

    GREEN

    YELLOW

    DRAIN/SHIELD

    BROWN

    BLACK

    RED

    JUNCTION BOX

    SONAR - SA Series

    DC-IN RS485TestInput

    IsolatedOutput

    Remote ACTControl Switch

    GREEN

    YELLOW

    TEST-IN

    +DC

    ACTIVE

    NEUTRAL

    TRANSDUCER

    BLACK

    RED

    BLUE

    WHITEA BICOM I- I+

    GND

    GND

    1ND

    1C

    1NC

    2ND

    2C

    2NC

    3ND

    3C

    3NC

    Pull

    Com

    Push

    GND

    GND

    GND

    GND

    RemCirt

    F303Sensor500mA, T

    F302Actuator10A, T

    AC Fuse1A, T

    301

    4 . . .20mA

    GND

    AC Power Relay 1 Relay 2 Relay 3Actuator

    Power

    N/C

    RED

    Yellow

    GREEN

    YELLOW

    TEST-IN

    +DC

    ACTIVE

    NEUTRAL

    TRANSDUCER

    BLACK

    RED

    BLUE

    WHITE

    A BICOM I - I +

    GND

    GND

    1ND

    1C

    1NC

    2ND

    2C

    2NC

    3ND

    3C

    3NC

    Pull

    Com

    Push

    GND

    GND

    GND

    GND

    RemCirt

    F302Sensor500mA,T

    F302Actuator10mA,T

    ACFuse1A,T

    301

    4 . . .20mA

    GND

    A C Po wer Rel ay 1 Relay 2 Relay 3Actuator

    Power

    N/C

    RED

    Yellow

    CAL

    RUN

    RELAY 1

    RELAY 2

    RELAY 3

    SLUDGE

    MASTER

    GREEN

    YELLOW

    TEST-IN

    +DC

    ACTIVE

    NEUTRAL

    TRANSDUCER

    BLACK

    RED

    BLUE

    WHITE

    A BICOM I - I +

    GND

    GND

    1ND

    1C

    1NC

    2ND

    2C

    2NC

    3ND

    3C

    3NC

    Pull

    Com

    Push

    GND

    GND

    GND

    GND

    RemCirt

    F302Sensor500mA,T

    F302Actuator10mA,T

    ACFuse1A,T

    301

    4 . . .20mA

    GND

    A C Po wer Relay 1 Relay 2 Rel ay 3Actuator

    Power

    N/C

    RED

    Yellow

    CAL

    RUN

    RELAY 1

    RELAY 2

    RELAY 3

    SLUDGE

    MASTER

    ECHO

    TX

  • 8/8/2019 Sonar Interface Level

    76/85

    WIRING contd

    10

    SONAR - SA Series

    BRKT

    1,3,5,....

    2,4,6,....

    AMP

    BLACK

    RED

    WHITE

    BLUE

    GREEN

    YELLOW

    SHLD

    PULL

    COM

    PUSH

    D-PULL

    D-PUSH

    BLACK

    P-WIPR

    REM-Ct.

    RED

    WHITE

    BLUE

    GREEN

    YELLOW

    SHLD

    PULL

    COM

    PUSH

    ActuatorLED

    GREEN

    YELLOW

    TEST-IN

    +DC

    ACTIVE

    NEUTRAL

    SHIELD/BLACK

    RED

    BLUE

    WHITE

    A BICOM I- I+

    GND

    GND

    1ND

    1C

    1NC

    2ND

    2C

    2NC

    3ND

    3C

    3NC

    Pull

    Com

    Push

    GND

    GND

    GND

    GND

    RemCirt

    F303Sensor500mA, T

    F302Actuator10A, T

    AC Fuse1A, T

    301

    4 . . .20mA

    GND

    AC Power Relay 1 Relay 2 Relay 3

    RemoteActuatorPushButtonRS485

    TESTINPUT

    DC In

    4-20MA

    OUTPUT

    ToJunction Box

    3 CoreExtension Cable

    6 Coreplus Shield

    Extension Cable

    Green

    Black

    Blue

    White

    Red

    JUNCTIONBOX

    ACTUATORS MECHANISM

    Enlargementof

    JUNCTIONBOX

    TRANSDUCEREXTENSION CABLE

    ACTUATOR

    Switch

    SONAR TRANSMITTER

    ActuatorPower

    ACTUATOR

    Black and Brownto be joined together

    TRANSDUCERCABLE

    TRANSDUCEREXTENSION CABLE

    The cable on this sidemust be connected tothe Sonar Transmitter

    The cable on this sidemust be connected tothe Transducer andActuator mechanism

    Transducer

  • 8/8/2019 Sonar Interface Level

    77/85

    11

    WIRING contd

    I+ Current loop isolated supply (Driving only. Norm. +18Vdc).

    I- Current loop return.

    ICOM Current loop common (Modulating user supply only).

    RELAY 1 N.O. Relay 1 Normally Open contact.

    RELAY 1 C Relay 1 Common contact.

    RELAY 1 N.C. Relay 1 Normally Closed contact.

    RELAY 2 N.O. Relay 2 Normally Open contact.RELAY 2 C Relay 2 Common contact.

    RELAY 2 N.C. Relay 2 Normally Closed contact.

    RELAY 3 Similar (Remote unit only).

    RELAY 4 Similar (Remote unit only).

    TEST-IN Test Input: Unit is forced into Standby Mode.

    Relays switch to pre-programmed 00.0m state, current loop goes

    to 4mA, and unit stops pulsing.

    +DC DC Supply input: Nominal 12Vdc or 24Vdc depending on model.

    GND DC Supply input Common/Ground terminal.EARTH AC Supply Earth terminal.

    NEUTRAL AC Supply Neutral terminal.

    ACTIVE AC Supply Active terminal. Nom 110Vac or 220Vac or 240Vac

    depending on model.

    RS485-A Do Not Use.

    RS485-B Do Not Use.

    TEST (pad) Used to test loop current refer to diagrams below.

    TestI-

    I+

    ICOM

    mA

    +

    RL

    Test

    I-

    I+

    ICOM

    mA

    +

    RL connected RL not connected

    Terminal Connections

    SONAR - SA Series

  • 8/8/2019 Sonar Interface Level

    78/85

    12

    WIRING contd

    SONAR - SA Series

    Terminal Connections for DC Supply Model dependant

    b) 3 Wire DC Modulating from Common User Supply (RL to +DC)

    UserDC Supply

    +

    +

    PLCDCSIND

    RL Max 700

    4-20mA

    I+ (Not used)

    ICOM

    I

    +DC

    GND

    Note:RL max = 700 if user DC Supply 18V

    Useshielded

    cable

    c) 3 Wire DC Modulating from Common User Supply (RL to GND)

    Note:RL max = 700 if user DC Supply 18V

    UserDC Supply

    +

    +

    PLCDCSIND

    RL Max 700

    4-20mA

    I+ (Not used)

    ICOM

    I

    +DC

    GND

    Useshielded

    cable

    Note: Isolated current output can be made common with +DC or GND if required.(e.g. RL connected to GND)

    a) 4 Wire DC Driving from Internal Isolated Supply (I+)

    UserDC Supply

    +

    +

    PLCDCSIND

    RL Max 700

    4-20mA Useshielded

    cable

    I+

    ICOM (Not used)

    I

    +DC

    GND

  • 8/8/2019 Sonar Interface Level

    79/85

    WIRING contd

    13

    SONAR - SA Series

    Terminal Connections for AC Supply Model dependant

    110/220/240VacSupply

    e) Modulating from Users External DC Supply (RL to Pos.)

    PLCDCSIND

    RL Max 700

    4-20mA

    I+ (Not used)

    ICOM

    I

    Active

    Neutral

    Note:RL max = 700 if user DC Supply 18V

    {Earth

    +

    +

    UserDC Supply

    Useshielded

    cable

    110/220/240VacSupply

    f) Modulating from Users External DC Supply (RL to Neg.)

    PLCDCSIND

    RL Max 700

    4-20mA

    I+ (Not used)

    ICOM

    I

    Active

    Neutral

    Note:RL max = 700 if user DC Supply 18V

    {Earth

    +

    +

    UserDC Supply

    Useshielded

    cable

    110/220/240VacSupply

    PLCDCSIND

    RL Max 700

    4-20mAI+

    ICOM (Not used)

    I

    Active

    Neutral{Earth

    +

    d) 4 Wire DC Driving from Internal Isolated Supply (I+)

    Note: Isolated current output can be made common with external DC Supply Pos.or Neg. if required.(e.g. RL connected to GND)

    Useshielded

    cable

  • 8/8/2019 Sonar Interface Level

    80/85

    PARAMETER and FLOW CHARTS

    SetupTo gain access to the parameter menu, press

    and hold the CAL button until "Unlock 0" is

    displayed on the LCD. Then use the buttons

    to select the access code. The factory default

    is 0.

    Units

    Allows the user to select the units for display

    of measured distances and relay set point

    programming. The choices are metres or feet.

    Display

    Allows the user to select the prefered displayon the LCD, options Space, Material, % Material.

    Application Type

    Allows the user to select the type ofapplication Liquids, Slurries, Solids. Theresponse of the system is automaticallychanged to allow for application requirments.

    Speed

    Allows the user to select the approximatespeed of the level change. This automaticallysets various parameters to allow a faster or

    slower response.Damping

    Allows the user to define how quickly the switch

    responds to changes in the measured level

    within the vessel being monitored. A low

    damping value gives a fast response and a high

    damping gives a slow response. The damping

    limits are from 0 to 239. Eg. If you set the

    damping to a value of 60, the displayed distance

    will be the average of the last 60 pulses.

    Low Level - HA Series Only

    Sets the distance from the face of the transducer

    that corresponds to the low level in the vesselbeing monitored - 4mA analog output level.

    High level - HA Series Only

    Sets the distance from the face of the transducer

    that corresponds to the High level in the vessel

    being monitored - 20mA analog output level.

    Note:When setting the High and Low levels aminimum span of 100mm MUST be maintained.

    Blanking

    Allows the user to blank out unwanted nearthe senor echoes. Any echoes within thisentered distance will be ignored.

    Fail OptAllows the user to select their preferredFailsafe condition. There are 5 possible mAoutput failure values. They are: 20mA, 4mA,Last Known, 20.00mA.

    Failsafe TimeAllows the user to enter the number of pulseswhen a last echo condition occurs prior tofailing. It is recommended to enter a minimumof 50 pulses.

    RelaysAllows the user to set the relays for switching.The relays are programmed in a distance

    from the transducer face to the position whereswitching is required.

    Relays work in the following manner:

    OFF The relays will remain de-energisedregardless of the measured distanceor vessel contents.

    The relays can be programmed to energiseor de-energise depending on the product levelin the vessel being monitored.

    FS If FS is selected, the relay will operateas a failsafe relay. The relay will beenergised at all times and willde-energise if the ultrasonic switchgoes in to failsafe condition.

    EN The relay is normally energised andwill de -energise when the product risesabove the level determined by L1 andremain de -energised until the productfalls below the level determined by L2.

    DEN The relay is normally de -energised andwill energise when the product risesabove the level determined by L1 andremain energised until the product fallsbelow the level determined by L2.

    L1 L1 determines the first switch pointfor relay switching.

    L2 L2 determines the second switch pointfor relay switching.

    Note:L1 and L2 are set in the chosen displayunits relative to the face of the transducer.

    BlankingAllows the user to set the blanking distancebeyond the minimum specified distance toignore unwanted echoes between the targetproduct and the transducer. Use thebuttons to set required blanking.

    CodeAllows the user to set an access code otherthan 0 to avoid unauthorised changes to theprogramming. Use the buttons to select

    the desired access code.

    14

    SONAR - SA Series

  • 8/8/2019 Sonar Interface Level

    81/85

    SET-UP FLOW CHART

    15

    SONAR - SA Series

    Note: To increment and decrement digital numbers

    faster, press and hold either or then press and

    hold CAL button. This will scroll the numbers faster.

    CAL

    Search

    CAL

    Setup

    CAL

    Set up

    CAL

    Code 0

    CAL

    Rly 3 L20.853m

    CAL

    Rly 3 L10.851m

    CAL

    CAL

    CAL

    Rly: No:3En

    Rly: No:2En

    Rly: No:1En

    DenFSOff

    DenFSOff

    DenFSOff

    CAL

    CAL

    Display

    Level %

    CAL

    Speed0.2.0m/m

    CAL

    Speed AdjYes / No

    CAL

    Damping229

    CAL

    High Level0.250

    CAL

    Blanketing0.307m

    CAL

    Fail Opt4.0mA

    Rly No: 2En

    DenFSOff

    Low Level4m

    Last20.00mA20.00mA

    Display

    Level

    Display

    Distance

    UnitsMetres

    MetresFeet

  • 8/8/2019 Sonar Interface Level

    82/85

  • 8/8/2019 Sonar Interface Level

    83/85

    TRACKING

    Standard Entry

    Note: To increment and decrement digital numbers

    faster, press and hold either or then

    press and holdCAL button.

    This will scroll the numbers faster.

    17

    SONAR - SA Series

    CAL

    CAL

    CAL

    Stable0.000m

    Hold235

    Confirm2

    Window2.336m

    Slope 81.023m

    Gain StepGS : 12.5%

    1.023m

    Set up

    Space1.623m

    Unlock:0

    Unlock:195

    195Combined withCAL willincrease speed of display.

    Set upTrackingTrim

    GN 14.5%1.022m

    Distance StepDS : 0.91.023m

    Comm Adds1

    End Distance4.62m

    CAL

    CAL

    CAL

    CAL

    CAL

    CAL

    CAL

    CAL

    CAL

    Recover0.0%

    CAL

    Gain increase startingfrom Gain Step Value

    Initial Gain valuestarting value

    Distance for initial gainvalue

    Angle of gain increase

    Acceptable returnechoes before outputupdate

    The amount of pulsesbefore reaction if echomoves out of window

    Gain increase when noecho is present

    Distance echo mustmove to move output

    Communicationaddress

    THLD

    Tracking

    CAL

    CAL

    Maximum distance theecho is expected

    Voltage above which anacceptable echo canbe identified

  • 8/8/2019 Sonar Interface Level

    84/85

    WARRANTY

    SA SONAR - Manual

    18

    SA Remote Transmitter

    Hawk control products will be replaced, putin good operating condition, or the purchaseprice refunded, at the option of Hawk, free

    of charges except transportation, if defectivein their manufacture, labeling, packaging, or

    shipping, and if notice of said defect isreceived by Hawk within one year from the

    date of shipment. The cost of suchreplacement, repair or refund or purchaseprice shall be the exclusive remedy for any

    breach of warranty, and Hawk shall not beliable to any person for consequential

    damages for injury or commercial lossresulting from any breach of any warranty.Hawk makes no warranty of fitness for a

    particular purpose, and makes no otherwarranty, express or implied, including

    implied warranty arising from course ofdealing or usage of trade.

    PART NUMBERING

    Transducer % Solids Blanking

    ST001 >8% 1000mm

    ST002 5-8% 800mm

    ST003 2% - 5% 600mm

    ST004 1% - 2% 600mmST005

  • 8/8/2019 Sonar Interface Level

    85/85

    Measurement Systems