2 3

MEMO

Caution

To use this product safely please read the following

instructions

The power must be off whenever you are in contact with the product.

Read and understand the following technical information about the

product.

For your safety only a qualied electrician should work on this product.

1.

2.

3.

Page 3: SP04EAO Modulo Analogo CIMON

8/16/2019 SP04EAO Modulo Analogo CIMON

http://slidepdf.com/reader/full/sp04eao-modulo-analogo-cimon 3/17

4 5

General Specifications

Items Specication Standards

 Ambient Temp. -10°C~70°C -

Storage Temp. -25°C~80°C -

 Ambient Humidity 5~95%RH, (Non-condensing) -

Storage Humidity 5~95%RH, (Non-condensing) -

Vibration

For discontinuous vibration

IEC 61131-2

Frequency Acceleration Amplitude Times10≤f<57Hz - 0.075mm

X,Y,Z

Each direction,

10 times

57≤f≤150Hz 9.8m/s2{1G} -

Contionuous vibration

Frequency Acceleration Amplitude

10≤f<57Hz - 0.035mm

57≤f≤150Hz 4.9m/s2{1G} -

Shocks

 · Max. impact acceleration: 147m/S2(15G)

 · Authorized time : 11ms

 · Pulse wave : Sign half-wave pulse (3 times each in X, Y, Z)

IEC 61131-2

Noise

Square waveimpulse noise

± 2,000V CIMON standard

Electrostaticdischarge

Voltage : 4kV (contact discharging)IEC 61131-2

IEC 1000-2

Radiatedelectromagnetic

eld noise27~500 MHz,10V/m

IEC 61131-2

IEC 1000-4-3

Fast TransientBurst noise

Power module

Digital I/O(24V or more)

Digital I/O(lessthan 24V)

 Analog I/OComm. interface IEC 61131-2

IEC 1000-4-4

2 kV 2 kV 0.25 kV

Voltage 2 kV/1min 0.5 kV/1min

 Ambientconditions

No corrosive gas or dust

Cooling type Natural air cooling

PLC-S Analog Output (Specications)

Items SP04EAA SP04EOAV SP04EOAI

 Analog Output point 2 points 4 points

 Analog Output

Voltage: 0V~+5V, 1V~+5V,0V~+10V, -10V~+10V

Current : 0~20mA,4~20mA

0V ~ +10V.-10V ~ 10V

(switch mode)4~20mA

Output setting method Setting by CICONSwitch OFF : 0V~10VSwitch ON :-10~10V

CICON settingNot possible

Digital Input

14bit, 0~16000

16bit, 0~64000Setting by CICON

14bit, 0~16000

 Accuracy ± 0.1% (Full Scale)

Conversion velocity 10ms

 Absolute Max. Output± 12V24mA

± 12V ± 24mA

Insulation method Photo Coupler between Input terminal and PLC

Power supply External DC 24V

I/O occupation 16 points

I/O Terminal 12points Terminal 8points Terminal

Consump-tion

current(mA)

Internal @DC3.3V, 15mA @DC3.3V, 15mA @DC3.3V, 15mA

External @DC24V, 70mA @DC24V, 60mA @DC24V, 70mA

Page 4: SP04EAO Modulo Analogo CIMON

8/16/2019 SP04EAO Modulo Analogo CIMON

http://slidepdf.com/reader/full/sp04eao-modulo-analogo-cimon 4/17

6 7

PLC-S Analog Input (Specifications)

Analog Mux Specifications (SP04EAM)

Items CM3-SP04EAO CM3-SP04EAA

 Analog Input point 4 points 2 points

 Analog InputVoltage: 0V~+5V, 1V~+5V, 0V~+10V, -10V~+10V

Current : 0~20mA, 4~20mA

Resolution 14bit, 0~1600014bit, 0~1600016bit, 0~64000

Setting by CICON

 Accuracy ± 0.1%(Full Scale)

Conversion speed 2.1ms / 1ch

 Absolute Max. input Voltage: ±12VCurrent: ±25mA

±12V±25mA

InsulationPhoto-coupler insulation between input terminal and PLC

(No insulation between channels)

I/O points occupied 16 points

Power Supply External DC 24V

Connection Terminal 12 points Terminal Block

Consumptioncurrent (mA)

Inner @DC3.3V, 15mA @DC3.3V, 15mA

External @DC24V, 60mA @DC24V, 70mA

Items Standard

 Analog Input 4 Channels / 1 Module

 Analog Input Voltage, RTD sensor, TC sensor 

Relay

Max/Min ON TIMEMin. 0.1 sec / Max. 1000.0 sec

Insulation Method Relay

I/O points occupied 16 points

Number of Ports Input 12ports / Output 3ports

Relay Life Expectancy Number of Operation of 108

Features of Analog Module

CM3-SP04EAO is Analog Input module which has 4CH voltage/current Input.CM3-SP04EOAV is Analog Output module which has 4CH voltage output (-10~10V, 0~10V).CM3-SP04EOAI is Analog Output module which has 4CH current output (4~20mA).CM3-SP04EAA is Analog Input and Output mixed module which has 2CH voltage/current input and 2CH voltage/current output.

DA conversion module converts digital value, 16bit binary data (data: 14bit) from PLCCPU, into analog signal (voltage or current output). It converts digital value 0~16000(-8000~8000) / 0~64000(-32000~32000) to analog value 0~20mA, 4~20mA,-10~10V, 0~5V, 0V~10V, 1~5V.

 AD conversion module converts input Max. and Min value into 0~16000(-8000~8000).If input value gets out of the range, it converts into -192~16191(8192~8191). If valuegets out of this, -192~16191(-8192~8191) is xed.

There are two AD conversion methods :1. Average processing 2. Sampling processing

Through “Hold Clear” function, DA module can output offset value (4mA, -10V) whenRUN mode changes to STOP mode or maintain output value being with RUN mode.

Channel that converting is prohibited will output the minimum value of each output mode.(0mA, 4mA, -10V, 0V, 1V)

User can set up Offset/Gain value through CICON Ladder Program.

Maximum 11 analog modules can be installed in one slot.

Normal status: LED On, Error status: LED blinking by 0.5sec interval.

1)

2)

3)

4)

5)

6)

7)

8)

9)

Page 5: SP04EAO Modulo Analogo CIMON

8/16/2019 SP04EAO Modulo Analogo CIMON

http://slidepdf.com/reader/full/sp04eao-modulo-analogo-cimon 5/17

8 9

Input / Output Signal

Direction of Signal

(CPU ← Module)

Direction of Signal

(CPU → Module)

Input Name of Signal Output Name of Signal

X00 Module ready Y10

X01 Y11

X02Flag indicating the

operation condition set upY12

Requesting to set up

operation condition

X03

Refer to “HELP” menu

in CICON

Y13

Refer to “HELP” menu

in CICON

X04 Y14

X05 Y15

X06 Y16

X07 Y17

X08 Y18

X09 Y19

X0A Y1A

X0B Y1B

X0C Y1C

X0D Y1D

X0E Y1E

X0FFlag indicating error in

moduleY1F Requesting to clear error 

SP04EAO USER MEMORY

 AddressDescription Default R/W

Hexa Deci

0H 0 CH.1 Digital converted value - R

1H 1 CH.2 Digital converted value - R

2H 2 CH.3 Digital converted value - R

3H 3 CH.4 Digital converted value - R

4H 4 CH.1 Input signal value - R

5H 5 CH.2 Input signal value - R

6H 6 CH.3 Input signal value - R

7H 7 CH.4 Input signal value - R

8H 8 CH.1 Percentage value - R

9H 9 CH.2 Percentage value - R

 AH 10 CH.3 Percentage value - R

BH 11 CH.4 Percentage value - R

CH 12 CH.1 Input range setting 0 R/W

DH 13 CH.2 Input range setting 0 R/W

EH 14 CH.3 Input range setting 0 R/W

FH 15 CH.4 Input range setting 0 R/W

10H 16 Raw Value Digital Output set 0 R/W

11H 17 Reserved - -

12H 18 CH.1 Average processing setting value 2000h R/W

13H 19 CH.2 Average processing setting value 2000h R/W

14H 20 CH.3 Average processing setting value 2000h R/W

15H 21 CH.4 Average processing setting value 2000h R/W

16H 22 CH.1 Max. alarm set value 0 R/W

17H 23 CH.2 Max. alarm set value 0 R/W

18H 24 CH.3 Max. alarm set value 0 R/W

19H 25 CH.4 Max. alarm set value 0 R/W

1AH 26 CH.1 Min. alarm set value 0 R/W1BH 27 CH.2 Min. alarm set value 0 R/W

1CH 28 CH.3 Min. alarm set value 0 R/W

1DH 29 CH.4 Min. alarm set value 0 R/W

1EH 30  Alarm in Max status - R

1FH 31  Alarm in Min. status - R

20H 32 CH.1 Digital Filter Constant 30 R/W

21H 33 CH.2 Digital Filter Constant 30 R/W

22H 34 CH.3 Digital Filter Constant 30 R/W

23H 35 CH.4 Digital Filter Constant 30 R/W

24H 36 Calibration Code - R/W

25H 37 Error Code - R

26H 38 OS Version - R

Page 6: SP04EAO Modulo Analogo CIMON

8/16/2019 SP04EAO Modulo Analogo CIMON

http://slidepdf.com/reader/full/sp04eao-modulo-analogo-cimon 6/17

10 11

SP04EAA USER MEMORY

Hexa

0H

1H

2H

3H

4H

5H

6H

7H

8H

9H

 AH

BH

CH

DH

EH

FH

10H

11H

12H

13H

14H

15H

16H

17H

18H

19H

1AH1BH

1CH

1DH

1EH

Deci

0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

2627

28

29

30

-

-

-

-

-

-

-

-

0

0

0

2000h

2000h

0

0

0

0

30

30

0

0

0

0

0

0

0

00

0

-

-

R

R

R

R

R

R

R

R

R/W

R/W

R/W

R/W

R/W

R/W

R/W

R/W

R/W

R/W

R/W

R/W

R/W

R/W

R/W

R/W

R/W

R/W

R/WR/W

R/W

R

R

CH.1 Digital converted value (AD)

CH.2 Digital converted value (AD)

CH.1 Input signal value (AD)

CH.2 Input signal value (AD)

CH.1 Percentage value (AD)

CH.2 Percentage value (AD)

 Alarm in Max status (AD)

 Alarm in M in. status (AD)

CH.1 Input range setting (AD)

CH.2 Input range setting (AD)

Raw Value Digital output set (AD)

CH.1 Average processing setting value(AD)

CH.2 Average processing setting value (AD)

CH.1 Max. alarm set value (AD)

CH.2 Max. alarm set value (AD)

CH.1 Min. alarm set value (AD)

CH.2 Min. alarm set value (AD)

CH.1 Digital Filter Constant (AD)

CH.2 Digital Filter Constant (AD)

Enable / Disable to D/A convert setup

CH.1 DA Output type (current 2, voltage 4)

CH.2 DA Output type (current 2, voltage 4)

CH.1 DA range of Digital value

CH.2 DA range of Digital value

CH.1 DA Channel Hold / Clear 

CH.2 DA Channel Hold / Clear 

CH.1 Digital Output value (DA)CH.2 Digital Output value (DA)

 AD / DA Resolu tion Set

Error Code

OS Version

 AddressDescription R/WDefault

SP04EOAV / SP04EOAI USER MEMORY

Hexa

00H

01H

02H

03H

04H

05H

06H

07H

08H

09H

0AH

0BH

0CH

0DH

0EH

0FH

10H

11H

12H

13H

14H

15H

16H

17H

Deci

0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

-

0

R/W

R/W

R/W

R/W

R/W

R/W

R/W

R/W

R/W

R/W

R/W

R/W

R/W

R/W

R/W

R/W

R/W

R

R

R

R

R

R

R/W

Enable/Disable to D/A convert setup

CH.1 Digital Output value

CH.2 Digital Output value

CH.3 Digital Output value

CH.4 Digital Output value

CH.1 Range of Digital value

CH.2 Range of Digital value

CH.3 Range of Digital value

CH.4 Range of Digital value

CH.1 Channel Hold / Clear 

CH.2 Channel Hold / Clear 

CH.3 Channel Hold / Clear 

CH.4 Channel Hold / Clear 

CH.1 Range of Voltage output setup

CH.2 Range of Voltage output setup

CH.3 Range of Voltage output setup

CH.4 Range of Voltage output setup

CH.1 Status

CH.2 Status

CH.3 Status

CH.4 Status

Error Code

OS Version

DA Output Enable

(Same Function to I/O Y Signal)

 AddressDescription R/WDefault

Page 7: SP04EAO Modulo Analogo CIMON

8/16/2019 SP04EAO Modulo Analogo CIMON

http://slidepdf.com/reader/full/sp04eao-modulo-analogo-cimon 7/17

12 13

Features of SP04EAM

 Analog Mux module receives analog values from 4 channels and outputs the samevalues to one port at a time.

Desired channels can be selected to be enabled or disabled and get operationstatus.

Different relay ON time can be set by each channel from 0.1 to 1000.0 secondsrange.

Relay count values can be checked for life expectancy for the relay.

Easy control with Auto/Manual mode.

Power LED blinks by 0.5 second interval when there’s an error with CPU

communication.

It is not suitable for current signal use since this module switches analog signalsrepeatedly.

1)

2)

3)

4)

5)

6)

Input / Output Signal of SP04EAM

** Note that I/O ags shown above are applied when the MUX module is installed in the rst slot

Flag Direction (CPU ← MUX Module) Flag Direction (CPU → MUX Module)

Input Flag Output Flag

X20 MUX Channel Change Completed Y20

X21 Settings Save Completed Y21 Mux Channel Change Request

X22 1CH Relay Open Predict Y22 Settings Save Request

X23 2CH Relay Open Predict Y23 1CH stoppage Request

X24 3CH Relay Open Predict Y24 2CH stoppage Request

X25 4CH Relay Open Predict Y25 3CH stoppage Request

X26 1CH Relay Activate Y26 4CH stoppage Request

X27 2CH Relay Activate Y27

X28 3CH Relay Activate Y28

X29 4CH Relay Activate Y29

X2A 1CH Relay Count Reset Completed Y2A

X2B 2CH Relay Count Reset Completed Y2B 1CH Relay Count Reset Request

X2C 3CH Relay Count Reset Completed Y2C 2CH Relay Count Reset Request

X2D 4CH Relay Count Reset Completed Y2D 3CH Relay Count Reset Request

X2E Module Error Y2E 4CH Relay Count Reset Request

X2F MUX Channel Change Completed Y2F Error Clear Request

Page 8: SP04EAO Modulo Analogo CIMON

8/16/2019 SP04EAO Modulo Analogo CIMON

http://slidepdf.com/reader/full/sp04eao-modulo-analogo-cimon 8/17

14 15

SP04EAM USER MEMORY

 AddressContents R/W

Hex. Dec.

0H 0 MUX Channel Enable / Disable R/W

1H 1 CH.1 Relay Count High R

2H 2 CH.1 Relay Count Low R

3H 3 CH.2 Relay Count High R

4H 4 CH.2 Relay Count Low R

5H 5 CH.3 Relay Count High R

6H 6 CH.3 Relay Count Low R

7H 7 CH.4 Relay Count High R

8H 8 CH.4 Relay Count Low R

9H 9  Auto/Manual Mode R/W

 AH 10 Operation Status R

BH 11 CH.1 ON time setting value R/W

CH 12 CH.2 ON time setting value R/W

DH 13 CH.3 ON time setting value R/W

EH 14 CH.4 ON time setting value R/W

FH 15 Error Code R

10H 16

11H 17

12H 18

13H 19

14H 20 OS Version R

Wiring Method

► CM3-SP04EAO

► CM3-SP04EAA

Voltage Input

Voltage Input / Output

Current Input

Current Input / Output

CH 1

CH 2

CH 3

CH 4

 AD Ch 1

 AD Ch 2

DA Ch 1

DA Ch 2

CH 1

CH 2

CH 3

CH 4

 AD Ch 1

 AD Ch 2

DA Ch 1

DA Ch 2

Terminal 1

Terminal 4

Terminal 7

Terminal 10

Terminal 1

Terminal 4

Terminal 7

Terminal 10

Terminal 1

Terminal 4

Terminal 7

Terminal 10

Terminal 1

Terminal 4

Terminal 8

Terminal 11

Terminal 3

Terminal 6

Terminal 9

Terminal 12

Terminal 3

Terminal 6

Terminal 9

Terminal 12

Connect 1-2

Connect 4-5

Connect 7-8

Connect 10-11

Connect 1-2

Connect 4-5

Terminal 3

Terminal 6

Terminal 9

Terminal 12

Terminal 3

Terminal 6

Terminal 9

Terminal 12

Channel

Channel

Channel

Channel

+ Terminal

+ Terminal

+ Terminal

+ Terminal

- Terminal

- Terminal

Connection

Connection

- Terminal

- Terminal

24V Extenrnal

24V Extenrnal

24V Extenrnal

24V Extenrnal

Connection : bottom of module

Connection : bottom of module

Connection : bottom of module

Connection : bottom of module

Page 9: SP04EAO Modulo Analogo CIMON

8/16/2019 SP04EAO Modulo Analogo CIMON

http://slidepdf.com/reader/full/sp04eao-modulo-analogo-cimon 9/17

16 17

Wiring Method

► CM3-SP04EOAV, CM3-SP04EOAI

► Prior to wiring Analog Input to Terminal, double check terminal (+) and (–)

CH 1

CH 2

CH 3

CH 4

Terminal 1

Terminal 3

Terminal 5

Terminal 7

Terminal 2

Terminal 4

Terminal 6

Terminal 8

Channel + Terminal - Terminal

24V Extenrnal Connection : bottom of module

► CM3-SP04EAM

CH 1

CH 2

CH 3

CH 4

Terminal 1

Terminal 4

Terminal 7

Terminal 10

Terminal 3

Terminal 6

Terminal 9

Terminal 12

Channel + Terminal - Terminal

Input Wiring

► SP04EAO Voltage Input ► SP04EAO Current Input

Page 10: SP04EAO Modulo Analogo CIMON

8/16/2019 SP04EAO Modulo Analogo CIMON

http://slidepdf.com/reader/full/sp04eao-modulo-analogo-cimon 10/17

18 19

Input Wiring

► SP04EAA Voltage Input ► SP04EAA Current Input

Output Wiring

► SP04EOAI Voltage Output ► SP04EOAI Current Output

Page 11: SP04EAO Modulo Analogo CIMON

8/16/2019 SP04EAO Modulo Analogo CIMON

http://slidepdf.com/reader/full/sp04eao-modulo-analogo-cimon 11/17

20 21

Output Wiring

► SP04EAA Voltage Output ► SP04EAA Current Output

SP04EAM Wiring

A1+

A1-

COM1

A2+

A2-

COM2   A1+

A1-

COM

CH1

CH2

CH3

CH4

A3+

A3-

COM3

A4+

A4-

COM4

► MUXING

► Bottom Terminal

► Analog Output

► Analog Input

Page 12: SP04EAO Modulo Analogo CIMON

8/16/2019 SP04EAO Modulo Analogo CIMON

http://slidepdf.com/reader/full/sp04eao-modulo-analogo-cimon 12/17

22 23

SP04EAM Wiring Example Dimension

Unit : mm

► All analog modules are the same size.

TC sensor

► Analog Output ► Analog Input

A1+

A1-

COM

Page 13: SP04EAO Modulo Analogo CIMON

8/16/2019 SP04EAO Modulo Analogo CIMON

http://slidepdf.com/reader/full/sp04eao-modulo-analogo-cimon 13/17

24 25

Dimension Revision History

Version Date Content Page

V1.0 2014-02-25 New Revision

V1.1 2015-01-26 SP04EAM added

V1.2 2015-05-27 SP04EAM Wiring /  SP04EAM Wiring Example

V1.3 2015-10-27 Wiring Method

 

-

1 - 28

21 - 22

15

Page 14: SP04EAO Modulo Analogo CIMON

8/16/2019 SP04EAO Modulo Analogo CIMON

http://slidepdf.com/reader/full/sp04eao-modulo-analogo-cimon 14/17

26 27

Product Warranty

January 2014

 All Cimon products including hardware, software, and rmware (collectively called

“Products”) carry a one-year warranty against defects in materials and workmanship

beginning from the date of product receipt from seller or its appointed distributor. If a

product proves defective in materials and workmanship within one year from the date

of purchase, we will replace or repair it. Products returned under warranty after

30 days may be replaced with refurbished or remanufactured goods at Cimon’s

discretion.  Cimon makes no representation or warranty, express or implied,

that the operation of the Products will be uninterrupted or error free, or that the

functions contained therein will meet or satisfy buyer’s intended use or requirements.Repaired or replaced Products provided as a result of this warranty are

warranted for a period of six (6) months from the shipment to buyer or the

remainder of the original warranty term for that particular product, whichever

is longer.  Cimon’s standard policy is that all customers are responsible for freight

charges to Cimon when returning products under the warranty return policy.

This warranty will be void if Products date codes or serial numbers are removed or

defaced. Warranties do not apply to products that have been subjected to abnormal

use, abnormal conditions, improper storage, exposure to moisture or dampness,

unauthorized modications, unauthorized repair, misuse, neglect, accident, alteration,

improper installation or other acts which are not the fault of Cimon, including damage

caused in shipping. Our warranty also does not apply to any product that has

been damaged by external causes such as re, ood, sand, dirt, lightning, acts of

God, battery leakage, theft, blown fuses, improper use of any electrical source or

connection to product not recommended in writing for interconnection by Cimon.

In no event will Cimon be liable, whether in contract, tort or under any other legal

theory, for lost profits or revenues, loss of use or similar economic loss, for any

indirect, special, incidental, consequential, punitive or similar damages arising out

of or in connection with any products including non-conforming products, or for any

third party claims against you relating to the products, even if we have been advised of

the possibility of such claim. In no event will our monetary liability in respect of any

product exceed the purchase price that you paid for it.

Product Warranty

To minimize the risk of potential safety problems, you should follow all applicable

local and national codes that regulate the installation and operation of your

equipment. These codes vary from area to are and usually change with time. It is your

responsibility to determine which codes should be followed, and to verify that the

equipment, installation and operation is in compliance with the latest revision of these

codes.

CIMON SOFTWARE AND HARDWARE (COLLECTIVELY REFFERED TO AS,

“PRODUCTS”) LICENSE DISCLAIMER AND LIMITATION OF WARRANTIES

YOUR USE OF ANY CIMON PRODUCTS AND CONTENT ACCESSIBLE THROUGH

THE PRODUCTS IS ENTIRELY AT YOUR OWN RISK. EXCEPT AS DESCRIBED IN THIS

 AGREEMENT, THE PRODUCTS ARE PROVIDED "AS IS." TO THE MAXIMUM EXTENT

PERMITTED BY APPLICABLE LAW, CIMON, ITS AFFILIATES, AND ITS THIRD PARTY

SERVICE OR DATA PROVIDERS, LICENSORS, DISTRIBUTORS OR SUPPLIERS

(COLLECTIVELY REFERRED TO AS, "SUPPLIERS") DISCLAIM ALL WARRANTIES,

EXPRESS OR IMPLIED, INCLUDING ANY WARRANTY THAT THE PRODUCTS ARE

FIT FOR A PARTICULAR PURPOSE, TITLE, MERCHANTABILITY, DATA LOSS, NON-

INTERFERENCE WITH OR NON-INFRINGEMENT OF ANY INTELLECTUAL PROPERTY

RIGHTS, OR THE ACCURACY, RELIABILITY, QUALITY OR CONTENT IN OR LINKED TO

THE PRODUCTS.

CIMON AND ITS AFFILIATES AND SUPPLIERS DO NOT WARRANT THAT THE

PRODUCTS ARE SECURE, FREE FROM BUGS, VIRUSES, INTERRUPTION, ERRORS,

THEFT OR DESTRUCTION. FURTHER, CIMON DOES NOT WARRANT ACCESS TO

THE INTERNET OR TO ANY OTHER SERVICE, CONTENT OR DATA TRANSMITTED

THROUGH THE PRODUCTS. IF THE EXCLUSIONS FOR IMPLIED WARRANTIES DO

NOT APPLY TO YOU, ANY IMPLIED WARRANTIES ARE LIMITED TO 60 DAYS FROM

THE DATE OF PURCHASE OR DELIVERY OF THE PRODUCTS, WHICHEVER IS

SOONER.

EQUIPMENT DAMAGE OR SERIOUS INJURY TO PERSONNEL INCLUDING DEATH

CAN RESULT FROM THE FAILURE TO FOLLOW ALL APPLICABLE CODES AND

STANDARDS INCLUDING ENGINEERING STANDARDS. CIMON DOES NOT

 ASSUME ANY RESPONSIBILITY FOR YOUR PRODUCT DESIGN, INSTALLATION OR

OPERATION.

Page 15: SP04EAO Modulo Analogo CIMON

8/16/2019 SP04EAO Modulo Analogo CIMON

http://slidepdf.com/reader/full/sp04eao-modulo-analogo-cimon 15/17

28 29

Product Warranty

CIMON LTD AND ITS AFFILIATES AND SUPPLIERS DISCLAIM ANY REP-

RESENTATIONS OR WARRANTIES THAT YOUR USE OF THE PRODUCTS WILL

SATISFY OR ENSURE COMPLIANCE WITH ANY LEGAL OBLIGATIONS OR LAWS OR

REGULATIONS.

LIMITATION OF LIABILITY AND INDEMNITY. TO THE MAXIMUM EXTENT PERMITTED

BY APPLICABLE LAW, THE ENTIRE LIABILITY OF CIMON, AND ITS AFFILIATES

 AND SUPPLIERS FOR ALL MATTERS OR CLAIMS RELATING TO THIS AGREEMENT

SHALL BE LIMITED TO THE AMOUNT YOU PAID FOR THE PRODUCTS DURING THE

TWELVE (12) MONTHS PRIOR TO SUCH CLAIM.

THE STATUTE OF LIMITATIONS FOR FILING A CLAIM SHALL BE LIMITED TO THE

SHORTER OF TWELVE MONTHS, OR THE SHORTEST PERIOD ALLOWED UNDER

 APPLICABLE LAW.

SUBJECT TO APPLICABLE LAW, CIMON AND ITS AFFILIATES AND SUPPLIERS ARE

NOT LIABLE FOR ANY OF THE FOLLOWING: (A) INDIRECT, SPECIAL, INCIDENTAL,

PUNITIVE OR CONSEQUENTIAL DAMAGES; (B) DAMAGES RELATING TO FAILURES

OF TELECOMMUNICATIONS, THE INTERNET, ELECTRONIC COMMUNICATIONS,

CORRUPTION, SECURITY, LOSS OR THEFT OF DATA, VIRUSES, SPYWARE, LOSS

OF BUSINESS, REVENUE, PROFITS OR INVESTMENT, OR USE OF SOFTWARE

OR HARDWARE THAT DOES NOT MEET CIMON SYSTEM REQUIREMENTS. THE

 ABOVE LIMITATIONS APPLY EVEN IF CIMON AND ITS AFFILIATES AND SUPPLIERS

HAVE BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES AND/OR THE

POSSIBILITY OF DAMAGES GREATER THAN THE LIMITATION ABOVE. THIS

 AGREEMENT SETS FORTH THE ENTIRE LIABILITY OF CIMON, ITS AFFILIATES ANDYOUR EXCLUSIVE REMEDY WITH RESPECT TO THE SOFTWARE AND ITS USE.

THE PARTIES FURTHER AGREE THAT THE APPLICABLE LAW AND VENUE FOR

 ANY DISPUTED ARE THE LAWS OF CALIFORNIA. TO THE EXTENT ALLOWED BY

 APPLICABLE LAW, ANY CLAIMS SHALL BE BROUGHT IN LOS ANGELES CALIFORNIA

 AND CALIFORNIA LAW SHALL APPLY. THE CALIFORNIA VERSION OF THE UCC IS

THE PREFERRED LAW TO BE APPLIED TO ANY WARRANT AND RELATED CLAIMS.

MEMO

Page 16: SP04EAO Modulo Analogo CIMON

8/16/2019 SP04EAO Modulo Analogo CIMON

http://slidepdf.com/reader/full/sp04eao-modulo-analogo-cimon 16/17

30 31

MEMO MEMO

Page 17: SP04EAO Modulo Analogo CIMON

8/16/2019 SP04EAO Modulo Analogo CIMON

http://slidepdf.com/reader/full/sp04eao-modulo-analogo-cimon 17/17

Version:1.3

Revision Date : Oct, 2015

Printed : May, 2015

BCP18044

H.Q Address : 5F KDT B/D, #48, Beolmal-ro, Bundang-gu,Seongnam-si, GyeongGi-do, Korea

  463-836

Tel : +82-31-778-3071

Homepage : www.cimon.com

USA : 3699 Wilshire Blvd suite 1250 Los Angeles CA90010

Tel : 213 384-8703

Homepage : www.cimon.com

CIMON CO.,LTD.