Space Input Data UNITED MOTORS 12/31/2012 TECHNOZONE 04:19PM
Hourly Analysis Program v4.51 Page 1 of 31
CHANGING & LOCKERS ROOM 1. General Details: Floor Area ............................................................. 14.1 m² Avg. Ceiling Height .................................................. 3.0 m Building Weight ................................................... 341.8 kg/m² 1.1. OA Ventilation Requirements: Space Usage .......................................... User-Defined OA Requirement 1 .................................................. 0.0 L/s OA Requirement 2 .................................................. 0.0 L/s Space Usage Defaults ........................... User-Defined 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 20.00 W/m² Ballast Multiplier .................................................... 1.00 Schedule .................................... Fractional Schedule
2.4. People: Occupancy ............................................................... 1.0 Person Activity Level ......................................... Medium Work Sensible ................................................................. 86.5 W/person Latent ................................................................... 133.3 W/person Schedule ..................................... Fractional Schedule
2.2. Task Lighting: Wattage ................................................................. 0.00 W/m² Schedule ............................................................. None
2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None
2.3. Electrical Equipment: Wattage ................................................................. 0.00 W/m² Schedule .................................... Fractional Schedule 3. Walls, Windows, Doors:
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SE 20.1 0 0 0 3.1. Construction Types for Exposure SE Wall Type ........................................ Default Wall Assembly 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0.00 L/s Design Heating ...................................................... 0.00 L/s Energy Analysis .................................................... 0.00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type .......................................... Slab Floor On Grade Floor Area ............................................................. 14.1 m² Total Floor U-Value ............................................. 1.000 W/(m²-°K) Exposed Perimeter .................................................. 3.5 m Edge Insulation R-Value ....................................... 1.00 (m²-°K)/W 7. Partitions: (No partition data).
Space Input Data UNITED MOTORS 12/31/2012 TECHNOZONE 04:19PM
Hourly Analysis Program v4.51 Page 2 of 31
CORRIDOR 1. General Details: Floor Area ............................................................. 26.1 m² Avg. Ceiling Height .................................................. 3.0 m Building Weight ................................................... 341.8 kg/m² 1.1. OA Ventilation Requirements: Space Usage .......................................... User-Defined OA Requirement 1 .................................................. 0.0 L/s OA Requirement 2 .................................................. 0.0 L/s Space Usage Defaults ........................... User-Defined 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 20.00 W/m² Ballast Multiplier .................................................... 1.00 Schedule .................................... Fractional Schedule
2.4. People: Occupancy ............................................................... 1.0 Person Activity Level ......................................... Medium Work Sensible ................................................................. 86.5 W/person Latent ................................................................... 133.3 W/person Schedule ..................................... Fractional Schedule
2.2. Task Lighting: Wattage ................................................................. 0.00 W/m² Schedule ............................................................. None
2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None
2.3. Electrical Equipment: Wattage ................................................................. 0.00 W/m² Schedule .................................... Fractional Schedule 3. Walls, Windows, Doors:
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SE 14.6 1 0 0 3.1. Construction Types for Exposure SE Wall Type ........................................ Default Wall Assembly 1st Window Type ............................... CORRIDOR WINDOW 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0.00 L/s Design Heating ...................................................... 0.00 L/s Energy Analysis .................................................... 0.00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type .......................................... Slab Floor On Grade Floor Area ............................................................. 26.1 m² Total Floor U-Value ............................................. 1.000 W/(m²-°K) Exposed Perimeter .................................................. 2.6 m Edge Insulation R-Value ....................................... 1.00 (m²-°K)/W 7. Partitions: 7.1. 1st Partition Details: Partition Type ........................................ Wall Partition Area ....................................................................... 33.0 m² U-Value ............................................................... 2.800 W/(m²-°K) Uncondit. Space Max Temp .................................. 40.0 °C Ambient at Space Max Temp ................................ 40.0 °C Uncondit. Space Min Temp ................................... 23.9 °C Ambient at Space Min Temp ................................. 12.8 °C
7.2. 2nd Partition Details: (No partition data).
Space Input Data UNITED MOTORS 12/31/2012 TECHNOZONE 04:19PM
Hourly Analysis Program v4.51 Page 3 of 31
DINNING HALL 1. General Details: Floor Area ............................................................. 27.1 m² Avg. Ceiling Height .................................................. 3.0 m Building Weight ................................................... 341.8 kg/m² 1.1. OA Ventilation Requirements: Space Usage .......................................... User-Defined OA Requirement 1 .................................................. 0.0 L/s OA Requirement 2 .................................................. 0.0 L/s Space Usage Defaults ........................... User-Defined 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 20.00 W/m² Ballast Multiplier .................................................... 1.00 Schedule .................................... Fractional Schedule
2.4. People: Occupancy ............................................................. 12.0 People Activity Level ......................................... Medium Work Sensible ................................................................. 86.5 W/person Latent ................................................................... 133.3 W/person Schedule ..................................... Fractional Schedule
2.2. Task Lighting: Wattage ................................................................. 0.00 W/m² Schedule ............................................................. None
2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None
2.3. Electrical Equipment: Wattage ................................................................. 0.00 W/m² Schedule .................................... Fractional Schedule 3. Walls, Windows, Doors: (No Wall, Window, Door data). 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0.00 L/s Design Heating ...................................................... 0.00 L/s Energy Analysis .................................................... 0.00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type .......................................... Slab Floor On Grade Floor Area ............................................................. 27.1 m² Total Floor U-Value ............................................. 1.000 W/(m²-°K) Exposed Perimeter .................................................. 0.0 m Edge Insulation R-Value ....................................... 1.00 (m²-°K)/W 7. Partitions: 7.1. 1st Partition Details: Partition Type ........................................ Wall Partition Area ....................................................................... 62.1 m² U-Value ............................................................... 2.800 W/(m²-°K) Uncondit. Space Max Temp .................................. 40.0 °C Ambient at Space Max Temp ................................ 40.0 °C Uncondit. Space Min Temp ................................... 23.9 °C Ambient at Space Min Temp ................................. 12.8 °C
7.2. 2nd Partition Details: (No partition data).
Space Input Data UNITED MOTORS 12/31/2012 TECHNOZONE 04:19PM
Hourly Analysis Program v4.51 Page 4 of 31
ELECTRICAL & REPAIR ROOM 1. General Details: Floor Area ............................................................. 16.7 m² Avg. Ceiling Height .................................................. 3.0 m Building Weight ................................................... 341.8 kg/m² 1.1. OA Ventilation Requirements: Space Usage .......................................... User-Defined OA Requirement 1 .................................................. 3.5 L/s/person OA Requirement 2 .................................................. 0.0 L/s Space Usage Defaults ........................... User-Defined 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 20.00 W/m² Ballast Multiplier .................................................... 1.00 Schedule .................................... Fractional Schedule
2.4. People: Occupancy ............................................................... 2.0 People Activity Level ......................................... Medium Work Sensible ................................................................. 86.5 W/person Latent ................................................................... 133.3 W/person Schedule ..................................... Fractional Schedule
2.2. Task Lighting: Wattage ................................................................. 0.00 W/m² Schedule ............................................................. None
2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None
2.3. Electrical Equipment: Wattage ............................................................... 800.0 Watts Schedule .................................... Fractional Schedule 3. Walls, Windows, Doors:
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NW 17.9 0 0 0
W 11.9 0 0 0 3.1. Construction Types for Exposure NW Wall Type ........................................ Default Wall Assembly 3.2. Construction Types for Exposure W Wall Type ........................................ Default Wall Assembly 4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 16.7 0 0 4.1. Construction Types for Exposure H Roof Type ....................................... Default Roof Assembly 5. Infiltration: Design Cooling ...................................................... 0.00 L/s Design Heating ...................................................... 0.00 L/s Energy Analysis .................................................... 0.00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type .......................................... Slab Floor On Grade Floor Area ............................................................. 16.7 m² Total Floor U-Value ............................................. 1.000 W/(m²-°K) Exposed Perimeter .................................................. 5.2 m Edge Insulation R-Value ....................................... 1.00 (m²-°K)/W 7. Partitions: 7.1. 1st Partition Details: Partition Type ........................................ Wall Partition Area ....................................................................... 37.5 m² U-Value ............................................................... 2.800 W/(m²-°K) Uncondit. Space Max Temp .................................. 40.0 °C Ambient at Space Max Temp ................................ 40.0 °C Uncondit. Space Min Temp ................................... 23.9 °C
Ambient at Space Min Temp ................................. 12.8 °C
Space Input Data UNITED MOTORS 12/31/2012 TECHNOZONE 04:19PM
Hourly Analysis Program v4.51 Page 5 of 31
7.2. 2nd Partition Details: (No partition data).
Space Input Data UNITED MOTORS 12/31/2012 TECHNOZONE 04:19PM
Hourly Analysis Program v4.51 Page 6 of 31
ENGINE OVER HAUL 1. General Details: Floor Area ............................................................. 37.6 m² Avg. Ceiling Height .................................................. 3.0 m Building Weight ................................................... 341.8 kg/m² 1.1. OA Ventilation Requirements: Space Usage .......................................... User-Defined OA Requirement 1 .................................................. 3.5 L/s/person OA Requirement 2 .................................................. 0.0 L/s Space Usage Defaults ........................... User-Defined 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 20.00 W/m² Ballast Multiplier .................................................... 1.00 Schedule .................................... Fractional Schedule
2.4. People: Occupancy ............................................................... 4.0 People Activity Level ......................................... Medium Work Sensible ................................................................. 86.5 W/person Latent ................................................................... 133.3 W/person Schedule ..................................... Fractional Schedule
2.2. Task Lighting: Wattage ................................................................. 0.00 W/m² Schedule ............................................................. None
2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None
2.3. Electrical Equipment: Wattage ............................................................. 1500.0 Watts Schedule .................................... Fractional Schedule 3. Walls, Windows, Doors:
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NW 24.0 0 0 0 3.1. Construction Types for Exposure NW Wall Type ........................................ Default Wall Assembly 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0.00 L/s Design Heating ...................................................... 0.00 L/s Energy Analysis .................................................... 0.00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type .......................................... Slab Floor On Grade Floor Area ............................................................. 37.6 m² Total Floor U-Value ............................................. 1.000 W/(m²-°K) Exposed Perimeter .................................................. 4.2 m Edge Insulation R-Value ....................................... 1.00 (m²-°K)/W 7. Partitions: 7.1. 1st Partition Details: Partition Type ........................................ Wall Partition Area ..................................................................... 129.8 m² U-Value ............................................................... 2.800 W/(m²-°K) Uncondit. Space Max Temp .................................. 40.0 °C Ambient at Space Max Temp ................................ 40.0 °C Uncondit. Space Min Temp ................................... 23.9 °C Ambient at Space Min Temp ................................. 12.8 °C
7.2. 2nd Partition Details: Partition Type ................................... Ceiling Partition Area ....................................................................... 37.6 m² U-Value ................................................................ 2.800 W/(m²-°K) Uncondit. Space Max Temp .................................. 40.0 °C Ambient at Space Max Temp ................................ 40.0 °C Uncondit. Space Min Temp ................................... 23.9 °C Ambient at Space Min Temp ................................. 12.8 °C
Space Input Data UNITED MOTORS 12/31/2012 TECHNOZONE 04:19PM
Hourly Analysis Program v4.51 Page 7 of 31
FILING AREA M 1. General Details: Floor Area ............................................................. 34.7 m² Avg. Ceiling Height .................................................. 3.0 m Building Weight ................................................... 341.8 kg/m² 1.1. OA Ventilation Requirements: Space Usage .......................................... User-Defined OA Requirement 1 .................................................. 0.0 L/s OA Requirement 2 .................................................. 0.0 L/s Space Usage Defaults ........................... User-Defined 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 20.00 W/m² Ballast Multiplier .................................................... 1.00 Schedule .................................... Fractional Schedule
2.4. People: Occupancy ............................................................... 2.0 People Activity Level ......................................... Medium Work Sensible ................................................................. 86.5 W/person Latent ................................................................... 133.3 W/person Schedule ..................................... Fractional Schedule
2.2. Task Lighting: Wattage ................................................................. 0.00 W/m² Schedule ............................................................. None
2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None
2.3. Electrical Equipment: Wattage ................................................................. 0.00 W/m² Schedule .................................... Fractional Schedule 3. Walls, Windows, Doors:
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 15.6 1 0 0 3.1. Construction Types for Exposure NE Wall Type ........................................ Default Wall Assembly 1st Window Type ................................. PRAYER WINDOW-1 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0.00 L/s Design Heating ...................................................... 0.00 L/s Energy Analysis .................................................... 0.00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: (No partition data).
Space Input Data UNITED MOTORS 12/31/2012 TECHNOZONE 04:19PM
Hourly Analysis Program v4.51 Page 8 of 31
HRW 1. General Details: Floor Area ............................................................... 1.0 m² Avg. Ceiling Height .................................................. 3.0 m Building Weight ................................................... 341.8 kg/m² 1.1. OA Ventilation Requirements: Space Usage .......................................... User-Defined OA Requirement 1 .............................................. 350.0 L/s OA Requirement 2 .................................................. 0.0 L/s Space Usage Defaults ........................... User-Defined 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ................................................................. 0.00 W/m² Ballast Multiplier .................................................... 1.00 Schedule ............................................................. None
2.4. People: Occupancy ............................................................... 0.0 Person Activity Level ......................................... Medium Work Sensible ................................................................. 86.5 W/person Latent ................................................................... 133.3 W/person Schedule .............................................................. None
2.2. Task Lighting: Wattage ................................................................. 0.00 W/m² Schedule ............................................................. None
2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None
2.3. Electrical Equipment: Wattage ................................................................. 0.00 W/m² Schedule ............................................................. None 3. Walls, Windows, Doors: (No Wall, Window, Door data). 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0.00 L/s Design Heating ...................................................... 0.00 L/s Energy Analysis .................................................... 0.00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: (No partition data).
Space Input Data UNITED MOTORS 12/31/2012 TECHNOZONE 04:19PM
Hourly Analysis Program v4.51 Page 9 of 31
LOBBY 1. General Details: Floor Area ............................................................. 31.3 m² Avg. Ceiling Height .................................................. 3.0 m Building Weight ................................................... 341.8 kg/m² 1.1. OA Ventilation Requirements: Space Usage .......................................... User-Defined OA Requirement 1 .................................................. 0.0 L/s OA Requirement 2 .................................................. 0.0 L/s Space Usage Defaults ........................... User-Defined 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 20.00 W/m² Ballast Multiplier .................................................... 1.00 Schedule .................................... Fractional Schedule
2.4. People: Occupancy ............................................................... 1.0 Person Activity Level ......................................... Medium Work Sensible ................................................................. 86.5 W/person Latent ................................................................... 133.3 W/person Schedule ..................................... Fractional Schedule
2.2. Task Lighting: Wattage ................................................................. 0.00 W/m² Schedule ............................................................. None
2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None
2.3. Electrical Equipment: Wattage ................................................................. 0.00 W/m² Schedule .................................... Fractional Schedule 3. Walls, Windows, Doors:
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 30.0 0 0 0
SE 17.4 0 0 0 3.1. Construction Types for Exposure NE Wall Type ........................................ Default Wall Assembly 3.2. Construction Types for Exposure SE Wall Type ........................................ Default Wall Assembly 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0.00 L/s Design Heating ...................................................... 0.00 L/s Energy Analysis .................................................... 0.00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type .......................................... Slab Floor On Grade Floor Area ............................................................. 31.3 m² Total Floor U-Value ............................................. 1.000 W/(m²-°K) Exposed Perimeter .................................................. 8.3 m Edge Insulation R-Value ....................................... 1.00 (m²-°K)/W 7. Partitions: (No partition data).
Space Input Data UNITED MOTORS 12/31/2012 TECHNOZONE 04:19PM
Hourly Analysis Program v4.51 Page 10 of 31
LOBBY M 1. General Details: Floor Area ............................................................. 72.2 m² Avg. Ceiling Height .................................................. 3.0 m Building Weight ................................................... 341.8 kg/m² 1.1. OA Ventilation Requirements: Space Usage .......................................... User-Defined OA Requirement 1 .................................................. 0.0 L/s OA Requirement 2 .................................................. 0.0 L/s Space Usage Defaults ........................... User-Defined 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 20.00 W/m² Ballast Multiplier .................................................... 1.00 Schedule .................................... Fractional Schedule
2.4. People: Occupancy ............................................................... 1.0 Person Activity Level ......................................... Medium Work Sensible ................................................................. 86.5 W/person Latent ................................................................... 133.3 W/person Schedule ..................................... Fractional Schedule
2.2. Task Lighting: Wattage ................................................................. 0.00 W/m² Schedule ............................................................. None
2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None
2.3. Electrical Equipment: Wattage ................................................................. 0.00 W/m² Schedule .................................... Fractional Schedule 3. Walls, Windows, Doors:
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 19.6 2 0 0 3.1. Construction Types for Exposure NE Wall Type ........................................ Default Wall Assembly 1st Window Type ............................... M LOBBY WINDOW-1 4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 72.2 0 0 4.1. Construction Types for Exposure H Roof Type ....................................... Default Roof Assembly 5. Infiltration: Design Cooling ...................................................... 0.00 L/s Design Heating ...................................................... 0.00 L/s Energy Analysis .................................................... 0.00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: 7.1. 1st Partition Details: Partition Type ........................................ Wall Partition Area ....................................................................... 73.1 m² U-Value ............................................................... 2.800 W/(m²-°K) Uncondit. Space Max Temp .................................. 40.0 °C Ambient at Space Max Temp ................................ 40.0 °C Uncondit. Space Min Temp ................................... 23.9 °C Ambient at Space Min Temp ................................. 12.8 °C
7.2. 2nd Partition Details: (No partition data).
Space Input Data UNITED MOTORS 12/31/2012 TECHNOZONE 04:19PM
Hourly Analysis Program v4.51 Page 11 of 31
LV ROOM 1. General Details: Floor Area ............................................................. 18.4 m² Avg. Ceiling Height .................................................. 3.0 m Building Weight ................................................... 341.8 kg/m² 1.1. OA Ventilation Requirements: Space Usage .......................................... User-Defined OA Requirement 1 .................................................. 3.5 L/s/person OA Requirement 2 .................................................. 0.0 L/s Space Usage Defaults ........................... User-Defined 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 20.00 W/m² Ballast Multiplier .................................................... 1.00 Schedule .................................... Fractional Schedule
2.4. People: Occupancy ............................................................... 2.0 People Activity Level ......................................... Medium Work Sensible ................................................................. 86.5 W/person Latent ................................................................... 133.3 W/person Schedule ..................................... Fractional Schedule
2.2. Task Lighting: Wattage ................................................................. 0.00 W/m² Schedule ............................................................. None
2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None
2.3. Electrical Equipment: Wattage ............................................................. 100.00 W/m² Schedule .................................... Fractional Schedule 3. Walls, Windows, Doors:
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SE 15.4 0 0 0
SW 17.5 0 0 0
NE 17.5 0 0 0 3.1. Construction Types for Exposure SE Wall Type ........................................ Default Wall Assembly 3.2. Construction Types for Exposure SW Wall Type ........................................ Default Wall Assembly 3.3. Construction Types for Exposure NE Wall Type ........................................ Default Wall Assembly 4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 18.4 0 0 4.1. Construction Types for Exposure H Roof Type ....................................... Default Roof Assembly 5. Infiltration: Design Cooling ...................................................... 0.00 L/s Design Heating ...................................................... 0.00 L/s Energy Analysis .................................................... 0.00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type .......................................... Slab Floor On Grade Floor Area ............................................................. 18.4 m² Total Floor U-Value ............................................. 1.000 W/(m²-°K) Exposed Perimeter .................................................. 4.4 m Edge Insulation R-Value ....................................... 1.00 (m²-°K)/W 7. Partitions: 7.1. 1st Partition Details: Partition Type ........................................ Wall Partition
Area ....................................................................... 15.4 m² U-Value ................................................................ 2.800 W/(m²-°K)
Space Input Data UNITED MOTORS 12/31/2012 TECHNOZONE 04:19PM
Hourly Analysis Program v4.51 Page 12 of 31
Uncondit. Space Max Temp .................................. 40.0 °C Ambient at Space Max Temp ................................ 40.0 °C Uncondit. Space Min Temp ................................... 23.9 °C Ambient at Space Min Temp ................................. 12.8 °C
7.2. 2nd Partition Details: (No partition data).
Space Input Data UNITED MOTORS 12/31/2012 TECHNOZONE 04:19PM
Hourly Analysis Program v4.51 Page 13 of 31
OFFICE M 1. General Details: Floor Area ........................................................... 342.5 m² Avg. Ceiling Height .................................................. 3.0 m Building Weight ................................................... 341.8 kg/m² 1.1. OA Ventilation Requirements: Space Usage .......................................... User-Defined OA Requirement 1 .................................................. 0.0 L/s OA Requirement 2 .................................................. 0.0 L/s Space Usage Defaults ........................... User-Defined 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 20.00 W/m² Ballast Multiplier .................................................... 1.00 Schedule .................................... Fractional Schedule
2.4. People: Occupancy ............................................................. 36.0 People Activity Level ............................................. Office Work Sensible ................................................................. 71.8 W/person Latent ..................................................................... 60.1 W/person Schedule ..................................... Fractional Schedule
2.2. Task Lighting: Wattage ................................................................. 0.00 W/m² Schedule ............................................................. None
2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None
2.3. Electrical Equipment: Wattage ............................................................... 30.00 W/m² Schedule .................................... Fractional Schedule 3. Walls, Windows, Doors:
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 101.4 2 2 0
SE 38.5 1 0 0 3.1. Construction Types for Exposure NE Wall Type ........................................ Default Wall Assembly 1st Window Type ............................... M OFFICE WINDOW-1 2nd Window Type ............................ M OFFICE WINDOW -2 3.2. Construction Types for Exposure SE Wall Type ........................................ Default Wall Assembly 1st Window Type ................................. PRAYER WINDOW-1 4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 342.5 0 0 4.1. Construction Types for Exposure H Roof Type ....................................... Default Roof Assembly 5. Infiltration: Design Cooling ...................................................... 0.00 L/s Design Heating ...................................................... 0.00 L/s Energy Analysis .................................................... 0.00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: 7.1. 1st Partition Details: Partition Type ........................................ Wall Partition Area ....................................................................... 64.3 m² U-Value ............................................................... 2.800 W/(m²-°K) Uncondit. Space Max Temp .................................. 40.0 °C Ambient at Space Max Temp ................................ 40.0 °C Uncondit. Space Min Temp ................................... 23.9 °C
Ambient at Space Min Temp ................................. 12.8 °C
Space Input Data UNITED MOTORS 12/31/2012 TECHNOZONE 04:19PM
Hourly Analysis Program v4.51 Page 14 of 31
7.2. 2nd Partition Details: (No partition data).
Space Input Data UNITED MOTORS 12/31/2012 TECHNOZONE 04:19PM
Hourly Analysis Program v4.51 Page 15 of 31
PANTRY M 1. General Details: Floor Area ............................................................... 8.8 m² Avg. Ceiling Height .................................................. 3.0 m Building Weight ................................................... 341.8 kg/m² 1.1. OA Ventilation Requirements: Space Usage .......................................... User-Defined OA Requirement 1 .................................................. 0.0 L/s OA Requirement 2 .................................................. 0.0 L/s Space Usage Defaults ........................... User-Defined 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 20.00 W/m² Ballast Multiplier .................................................... 1.00 Schedule .................................... Fractional Schedule
2.4. People: Occupancy ............................................................... 1.0 Person Activity Level ......................................... Medium Work Sensible ................................................................. 86.5 W/person Latent ................................................................... 133.3 W/person Schedule ..................................... Fractional Schedule
2.2. Task Lighting: Wattage ................................................................. 0.00 W/m² Schedule ............................................................. None
2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None
2.3. Electrical Equipment: Wattage ................................................................. 0.00 W/m² Schedule .................................... Fractional Schedule 3. Walls, Windows, Doors:
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SE 8.1 0 0 0 3.1. Construction Types for Exposure SE Wall Type ........................................ Default Wall Assembly 4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 8.8 0 0 4.1. Construction Types for Exposure H Roof Type ....................................... Default Roof Assembly 5. Infiltration: Design Cooling ...................................................... 0.00 L/s Design Heating ...................................................... 0.00 L/s Energy Analysis .................................................... 0.00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: (No partition data).
Space Input Data UNITED MOTORS 12/31/2012 TECHNOZONE 04:19PM
Hourly Analysis Program v4.51 Page 16 of 31
PRAYER ROOM 1. General Details: Floor Area ............................................................. 24.4 m² Avg. Ceiling Height .................................................. 3.0 m Building Weight ................................................... 341.8 kg/m² 1.1. OA Ventilation Requirements: Space Usage .......................................... User-Defined OA Requirement 1 .................................................. 0.0 L/s OA Requirement 2 .................................................. 0.0 L/s Space Usage Defaults ........................... User-Defined 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 20.00 W/m² Ballast Multiplier .................................................... 1.00 Schedule .................................... Fractional Schedule
2.4. People: Occupancy ............................................................... 8.0 People Activity Level ......................................... Medium Work Sensible ................................................................. 86.5 W/person Latent ................................................................... 133.3 W/person Schedule ..................................... Fractional Schedule
2.2. Task Lighting: Wattage ................................................................. 0.00 W/m² Schedule ............................................................. None
2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None
2.3. Electrical Equipment: Wattage ................................................................. 0.00 W/m² Schedule .................................... Fractional Schedule 3. Walls, Windows, Doors:
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 25.3 1 1 0
SE 35.8 2 1 0 3.1. Construction Types for Exposure NE Wall Type ........................................ Default Wall Assembly 1st Window Type ........................... RECEPTION WINDOW-2 2nd Window Type ......................... RECEPTION WINDOW-3 3.2. Construction Types for Exposure SE Wall Type ........................................ Default Wall Assembly 1st Window Type ................................. PRAYER WINDOW-1 2nd Window Type ............................... PRAYER WINDOW-1 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0.00 L/s Design Heating ...................................................... 0.00 L/s Energy Analysis .................................................... 0.00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type .......................................... Slab Floor On Grade Floor Area ............................................................. 24.4 m² Total Floor U-Value ............................................. 1.000 W/(m²-°K) Exposed Perimeter ................................................ 10.8 m Edge Insulation R-Value ....................................... 1.00 (m²-°K)/W 7. Partitions: (No partition data).
Space Input Data UNITED MOTORS 12/31/2012 TECHNOZONE 04:19PM
Hourly Analysis Program v4.51 Page 17 of 31
RECEP/JOB CARD CLERKS 1. General Details: Floor Area ............................................................. 39.9 m² Avg. Ceiling Height .................................................. 3.0 m Building Weight ................................................... 341.8 kg/m² 1.1. OA Ventilation Requirements: Space Usage .......................................... User-Defined OA Requirement 1 .................................................. 3.5 L/s/person OA Requirement 2 .................................................. 0.0 L/s Space Usage Defaults ........................... User-Defined 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 20.00 W/m² Ballast Multiplier .................................................... 1.00 Schedule .................................... Fractional Schedule
2.4. People: Occupancy ............................................................. 10.0 People Activity Level ......................................... Medium Work Sensible ................................................................. 86.5 W/person Latent ................................................................... 133.3 W/person Schedule ..................................... Fractional Schedule
2.2. Task Lighting: Wattage ................................................................. 0.00 W/m² Schedule ............................................................. None
2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None
2.3. Electrical Equipment: Wattage ............................................................... 600.0 Watts Schedule .................................... Fractional Schedule 3. Walls, Windows, Doors:
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SW 18.9 0 0 0
NW 13.6 0 0 0 3.1. Construction Types for Exposure SW Wall Type ........................................ Default Wall Assembly 3.2. Construction Types for Exposure NW Wall Type ........................................ Default Wall Assembly 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0.00 L/s Design Heating ...................................................... 0.00 L/s Energy Analysis .................................................... 0.00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type .......................................... Slab Floor On Grade Floor Area ............................................................. 39.9 m² Total Floor U-Value ............................................. 1.000 W/(m²-°K) Exposed Perimeter .................................................. 3.3 m Edge Insulation R-Value ....................................... 1.00 (m²-°K)/W 7. Partitions: 7.1. 1st Partition Details: Partition Type ........................................ Wall Partition Area ....................................................................... 51.1 m² U-Value ............................................................... 2.800 W/(m²-°K) Uncondit. Space Max Temp .................................. 40.0 °C Ambient at Space Max Temp ................................ 40.0 °C Uncondit. Space Min Temp ................................... 23.9 °C Ambient at Space Min Temp ................................. 12.8 °C
7.2. 2nd Partition Details: (No partition data).
Space Input Data UNITED MOTORS 12/31/2012 TECHNOZONE 04:19PM
Hourly Analysis Program v4.51 Page 18 of 31
RECEPTION LOUNGE & STORE 1. General Details: Floor Area ........................................................... 160.1 m² Avg. Ceiling Height .................................................. 3.0 m Building Weight ................................................... 341.8 kg/m² 1.1. OA Ventilation Requirements: Space Usage .......................................... User-Defined OA Requirement 1 .................................................. 0.0 L/s OA Requirement 2 .................................................. 0.0 L/s Space Usage Defaults ........................... User-Defined 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 20.00 W/m² Ballast Multiplier .................................................... 1.00 Schedule .................................... Fractional Schedule
2.4. People: Occupancy ............................................................... 8.0 People Activity Level ......................................... Medium Work Sensible ................................................................. 86.5 W/person Latent ................................................................... 133.3 W/person Schedule ..................................... Fractional Schedule
2.2. Task Lighting: Wattage ................................................................. 0.00 W/m² Schedule ............................................................. None
2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None
2.3. Electrical Equipment: Wattage ............................................................. 1000.0 Watts Schedule .................................... Fractional Schedule 3. Walls, Windows, Doors:
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 98.1 1 0 0
NW 17.4 0 0 0
NE 32.3 1 1 0 3.1. Construction Types for Exposure NE Wall Type ........................................ Default Wall Assembly 1st Window Type ........................... RECEPTION WINDOW-1 3.2. Construction Types for Exposure NW Wall Type ........................................ Default Wall Assembly 3.3. Construction Types for Exposure NE Wall Type ........................................ Default Wall Assembly 1st Window Type ........................... RECEPTION WINDOW-2 2nd Window Type ......................... RECEPTION WINDOW-3 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0.00 L/s Design Heating ...................................................... 0.00 L/s Energy Analysis .................................................... 0.00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type .......................................... Slab Floor On Grade Floor Area ........................................................... 160.1 m² Total Floor U-Value ............................................. 1.000 W/(m²-°K) Exposed Perimeter ................................................ 26.3 m Edge Insulation R-Value ....................................... 1.00 (m²-°K)/W 7. Partitions: 7.1. 1st Partition Details: Partition Type ........................................ Wall Partition Area ..................................................................... 119.2 m² U-Value ............................................................... 2.800 W/(m²-°K) Uncondit. Space Max Temp .................................. 40.0 °C Ambient at Space Max Temp ................................ 40.0 °C
Uncondit. Space Min Temp ................................... 23.9 °C Ambient at Space Min Temp ................................. 12.8 °C
Space Input Data UNITED MOTORS 12/31/2012 TECHNOZONE 04:19PM
Hourly Analysis Program v4.51 Page 19 of 31
7.2. 2nd Partition Details: (No partition data).
Space Input Data UNITED MOTORS 12/31/2012 TECHNOZONE 04:19PM
Hourly Analysis Program v4.51 Page 20 of 31
SECURITY ROOM 1. General Details: Floor Area ............................................................... 4.9 m² Avg. Ceiling Height .................................................. 3.0 m Building Weight ................................................... 341.8 kg/m² 1.1. OA Ventilation Requirements: Space Usage .......................................... User-Defined OA Requirement 1 .................................................. 3.5 L/s/person OA Requirement 2 .................................................. 0.0 L/s Space Usage Defaults ........................... User-Defined 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 20.00 W/m² Ballast Multiplier .................................................... 1.00 Schedule .................................... Fractional Schedule
2.4. People: Occupancy ............................................................... 2.0 People Activity Level ......................................... Medium Work Sensible ................................................................. 86.5 W/person Latent ................................................................... 133.3 W/person Schedule ..................................... Fractional Schedule
2.2. Task Lighting: Wattage ................................................................. 0.00 W/m² Schedule ............................................................. None
2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None
2.3. Electrical Equipment: Wattage ............................................................... 250.0 Watts Schedule .................................... Fractional Schedule 3. Walls, Windows, Doors:
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SW 10.2 0 0 0
NW 7.7 0 0 0 3.1. Construction Types for Exposure SW Wall Type ........................................ Default Wall Assembly 3.2. Construction Types for Exposure NW Wall Type ........................................ Default Wall Assembly 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0.00 L/s Design Heating ...................................................... 0.00 L/s Energy Analysis .................................................... 0.00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type .......................................... Slab Floor On Grade Floor Area ............................................................... 4.9 m² Total Floor U-Value ............................................. 1.000 W/(m²-°K) Exposed Perimeter .................................................. 1.8 m Edge Insulation R-Value ....................................... 1.00 (m²-°K)/W 7. Partitions: (No partition data).
Space Input Data UNITED MOTORS 12/31/2012 TECHNOZONE 04:19PM
Hourly Analysis Program v4.51 Page 21 of 31
SERVER & UPS ROOM M 1. General Details: Floor Area ............................................................. 10.5 m² Avg. Ceiling Height .................................................. 3.0 m Building Weight ................................................... 341.8 kg/m² 1.1. OA Ventilation Requirements: Space Usage .......................................... User-Defined OA Requirement 1 .................................................. 0.0 L/s OA Requirement 2 .................................................. 0.0 L/s Space Usage Defaults ........................... User-Defined 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 20.00 W/m² Ballast Multiplier .................................................... 1.00 Schedule .................................... Fractional Schedule
2.4. People: Occupancy ............................................................... 1.0 Person Activity Level ......................................... Medium Work Sensible ................................................................. 86.5 W/person Latent ................................................................... 133.3 W/person Schedule ..................................... Fractional Schedule
2.2. Task Lighting: Wattage ................................................................. 0.00 W/m² Schedule ............................................................. None
2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None
2.3. Electrical Equipment: Wattage ............................................................. 100.00 W/m² Schedule .................................... Fractional Schedule 3. Walls, Windows, Doors: (No Wall, Window, Door data). 4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 10.5 0 0 4.1. Construction Types for Exposure H Roof Type ....................................... Default Roof Assembly 5. Infiltration: Design Cooling ...................................................... 0.00 L/s Design Heating ...................................................... 0.00 L/s Energy Analysis .................................................... 0.00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: 7.1. 1st Partition Details: Partition Type ........................................ Wall Partition Area ......................................................................... 8.1 m² U-Value ............................................................... 2.800 W/(m²-°K) Uncondit. Space Max Temp .................................. 40.0 °C Ambient at Space Max Temp ................................ 40.0 °C Uncondit. Space Min Temp ................................... 23.9 °C Ambient at Space Min Temp ................................. 12.8 °C
7.2. 2nd Partition Details: (No partition data).
Space Input Data UNITED MOTORS 12/31/2012 TECHNOZONE 04:19PM
Hourly Analysis Program v4.51 Page 22 of 31
STAIRS & LOBBY M 1. General Details: Floor Area ............................................................. 13.3 m² Avg. Ceiling Height .................................................. 3.0 m Building Weight ................................................... 341.8 kg/m² 1.1. OA Ventilation Requirements: Space Usage .......................................... User-Defined OA Requirement 1 .................................................. 0.0 L/s OA Requirement 2 .................................................. 0.0 L/s Space Usage Defaults ........................... User-Defined 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 20.00 W/m² Ballast Multiplier .................................................... 1.00 Schedule .................................... Fractional Schedule
2.4. People: Occupancy ............................................................... 0.0 Person Activity Level ......................................... Medium Work Sensible ................................................................. 86.5 W/person Latent ................................................................... 133.3 W/person Schedule ..................................... Fractional Schedule
2.2. Task Lighting: Wattage ................................................................. 0.00 W/m² Schedule ............................................................. None
2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None
2.3. Electrical Equipment: Wattage ................................................................. 0.00 W/m² Schedule .................................... Fractional Schedule 3. Walls, Windows, Doors:
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SE 9.9 1 0 0 3.1. Construction Types for Exposure SE Wall Type ........................................ Default Wall Assembly 1st Window Type ............................... CORRIDOR WINDOW 4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 13.3 0 0 4.1. Construction Types for Exposure H Roof Type ....................................... Default Roof Assembly 5. Infiltration: Design Cooling ...................................................... 0.00 L/s Design Heating ...................................................... 0.00 L/s Energy Analysis .................................................... 0.00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: 7.1. 1st Partition Details: Partition Type ........................................ Wall Partition Area ....................................................................... 22.2 m² U-Value ............................................................... 2.800 W/(m²-°K) Uncondit. Space Max Temp .................................. 40.0 °C Ambient at Space Max Temp ................................ 40.0 °C Uncondit. Space Min Temp ................................... 23.9 °C Ambient at Space Min Temp ................................. 12.8 °C
7.2. 2nd Partition Details: (No partition data).
Space Input Data UNITED MOTORS 12/31/2012 TECHNOZONE 04:19PM
Hourly Analysis Program v4.51 Page 23 of 31
TEL ROOM 1. General Details: Floor Area ............................................................... 5.4 m² Avg. Ceiling Height .................................................. 3.0 m Building Weight ................................................... 341.8 kg/m² 1.1. OA Ventilation Requirements: Space Usage .......................................... User-Defined OA Requirement 1 .................................................. 0.0 L/s OA Requirement 2 .................................................. 0.0 L/s Space Usage Defaults ........................... User-Defined 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 20.00 W/m² Ballast Multiplier .................................................... 1.00 Schedule .................................... Fractional Schedule
2.4. People: Occupancy ............................................................... 1.0 Person Activity Level ......................................... Medium Work Sensible ................................................................. 86.5 W/person Latent ................................................................... 133.3 W/person Schedule ..................................... Fractional Schedule
2.2. Task Lighting: Wattage ................................................................. 0.00 W/m² Schedule ............................................................. None
2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None
2.3. Electrical Equipment: Wattage ............................................................... 50.00 W/m² Schedule .................................... Fractional Schedule 3. Walls, Windows, Doors: (No Wall, Window, Door data). 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0.00 L/s Design Heating ...................................................... 0.00 L/s Energy Analysis .................................................... 0.00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type .......................................... Slab Floor On Grade Floor Area ............................................................... 5.4 m² Total Floor U-Value ............................................. 1.000 W/(m²-°K) Exposed Perimeter .................................................. 0.0 m Edge Insulation R-Value ....................................... 1.00 (m²-°K)/W 7. Partitions: 7.1. 1st Partition Details: Partition Type ........................................ Wall Partition Area ....................................................................... 15.7 m² U-Value ............................................................... 2.800 W/(m²-°K) Uncondit. Space Max Temp .................................. 40.0 °C Ambient at Space Max Temp ................................ 40.0 °C Uncondit. Space Min Temp ................................... 23.9 °C Ambient at Space Min Temp ................................. 12.8 °C
7.2. 2nd Partition Details: (No partition data).
Space Input Data UNITED MOTORS 12/31/2012 TECHNOZONE 04:19PM
Hourly Analysis Program v4.51 Page 24 of 31
TEL ROOM M 1. General Details: Floor Area ............................................................... 4.7 m² Avg. Ceiling Height .................................................. 3.0 m Building Weight ................................................... 341.8 kg/m² 1.1. OA Ventilation Requirements: Space Usage .......................................... User-Defined OA Requirement 1 .................................................. 0.0 L/s OA Requirement 2 .................................................. 0.0 L/s Space Usage Defaults ........................... User-Defined 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 20.00 W/m² Ballast Multiplier .................................................... 1.00 Schedule .................................... Fractional Schedule
2.4. People: Occupancy ............................................................... 1.0 Person Activity Level ......................................... Medium Work Sensible ................................................................. 86.5 W/person Latent ................................................................... 133.3 W/person Schedule ..................................... Fractional Schedule
2.2. Task Lighting: Wattage ................................................................. 0.00 W/m² Schedule ............................................................. None
2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None
2.3. Electrical Equipment: Wattage ............................................................... 50.00 W/m² Schedule .................................... Fractional Schedule 3. Walls, Windows, Doors: (No Wall, Window, Door data). 4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 4.7 0 0 4.1. Construction Types for Exposure H Roof Type ....................................... Default Roof Assembly 5. Infiltration: Design Cooling ...................................................... 0.00 L/s Design Heating ...................................................... 0.00 L/s Energy Analysis .................................................... 0.00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: (No partition data).
Space Input Data UNITED MOTORS 12/31/2012 TECHNOZONE 04:19PM
Hourly Analysis Program v4.51 Page 25 of 31
TOILET A 1. General Details: Floor Area ............................................................... 2.6 m² Avg. Ceiling Height .................................................. 3.0 m Building Weight ................................................... 341.8 kg/m² 1.1. OA Ventilation Requirements: Space Usage .......................................... User-Defined OA Requirement 1 .................................................. 0.0 L/s OA Requirement 2 .................................................. 0.0 L/s Space Usage Defaults ........................... User-Defined 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 20.00 W/m² Ballast Multiplier .................................................... 1.00 Schedule .................................... Fractional Schedule
2.4. People: Occupancy ............................................................... 1.0 Person Activity Level ......................................... Medium Work Sensible ................................................................. 86.5 W/person Latent ................................................................... 133.3 W/person Schedule ..................................... Fractional Schedule
2.2. Task Lighting: Wattage ................................................................. 0.00 W/m² Schedule ............................................................. None
2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None
2.3. Electrical Equipment: Wattage ................................................................. 0.00 W/m² Schedule .................................... Fractional Schedule 3. Walls, Windows, Doors: (No Wall, Window, Door data). 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0.00 L/s Design Heating ...................................................... 0.00 L/s Energy Analysis .................................................... 0.00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type .......................................... Slab Floor On Grade Floor Area ............................................................... 2.6 m² Total Floor U-Value ............................................. 1.000 W/(m²-°K) Exposed Perimeter .................................................. 0.0 m Edge Insulation R-Value ....................................... 1.00 (m²-°K)/W 7. Partitions: (No partition data).
Space Input Data UNITED MOTORS 12/31/2012 TECHNOZONE 04:19PM
Hourly Analysis Program v4.51 Page 26 of 31
TOILET F 1. General Details: Floor Area ............................................................... 2.5 m² Avg. Ceiling Height .................................................. 3.0 m Building Weight ................................................... 341.8 kg/m² 1.1. OA Ventilation Requirements: Space Usage .......................................... User-Defined OA Requirement 1 .................................................. 0.0 L/s OA Requirement 2 .................................................. 0.0 L/s Space Usage Defaults ........................... User-Defined 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 20.00 W/m² Ballast Multiplier .................................................... 1.00 Schedule .................................... Fractional Schedule
2.4. People: Occupancy ............................................................... 1.0 Person Activity Level ......................................... Medium Work Sensible ................................................................. 86.5 W/person Latent ................................................................... 133.3 W/person Schedule ..................................... Fractional Schedule
2.2. Task Lighting: Wattage ................................................................. 0.00 W/m² Schedule ............................................................. None
2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None
2.3. Electrical Equipment: Wattage ................................................................. 0.00 W/m² Schedule .................................... Fractional Schedule 3. Walls, Windows, Doors: (No Wall, Window, Door data). 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0.00 L/s Design Heating ...................................................... 0.00 L/s Energy Analysis .................................................... 0.00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type .......................................... Slab Floor On Grade Floor Area ............................................................... 2.5 m² Total Floor U-Value ............................................. 1.000 W/(m²-°K) Exposed Perimeter .................................................. 0.0 m Edge Insulation R-Value ....................................... 1.00 (m²-°K)/W 7. Partitions: (No partition data).
Space Input Data UNITED MOTORS 12/31/2012 TECHNOZONE 04:19PM
Hourly Analysis Program v4.51 Page 27 of 31
TOILET M 1. General Details: Floor Area ............................................................... 2.5 m² Avg. Ceiling Height .................................................. 3.0 m Building Weight ................................................... 341.8 kg/m² 1.1. OA Ventilation Requirements: Space Usage .......................................... User-Defined OA Requirement 1 .................................................. 0.0 L/s OA Requirement 2 .................................................. 0.0 L/s Space Usage Defaults ........................... User-Defined 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 20.00 W/m² Ballast Multiplier .................................................... 1.00 Schedule .................................... Fractional Schedule
2.4. People: Occupancy ............................................................... 1.0 Person Activity Level ......................................... Medium Work Sensible ................................................................. 86.5 W/person Latent ................................................................... 133.3 W/person Schedule ..................................... Fractional Schedule
2.2. Task Lighting: Wattage ................................................................. 0.00 W/m² Schedule ............................................................. None
2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None
2.3. Electrical Equipment: Wattage ................................................................. 0.00 W/m² Schedule .................................... Fractional Schedule 3. Walls, Windows, Doors: (No Wall, Window, Door data). 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0.00 L/s Design Heating ...................................................... 0.00 L/s Energy Analysis .................................................... 0.00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type .......................................... Slab Floor On Grade Floor Area ............................................................... 2.5 m² Total Floor U-Value ............................................. 1.000 W/(m²-°K) Exposed Perimeter .................................................. 0.0 m Edge Insulation R-Value ....................................... 1.00 (m²-°K)/W 7. Partitions: (No partition data).
Space Input Data UNITED MOTORS 12/31/2012 TECHNOZONE 04:19PM
Hourly Analysis Program v4.51 Page 28 of 31
TOILETS GF 1. General Details: Floor Area ............................................................. 19.5 m² Avg. Ceiling Height .................................................. 3.0 m Building Weight ................................................... 341.8 kg/m² 1.1. OA Ventilation Requirements: Space Usage .......................................... User-Defined OA Requirement 1 .................................................. 0.0 L/s OA Requirement 2 .................................................. 0.0 L/s Space Usage Defaults ........................... User-Defined 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 20.00 W/m² Ballast Multiplier .................................................... 1.00 Schedule .................................... Fractional Schedule
2.4. People: Occupancy ............................................................... 1.0 Person Activity Level ......................................... Medium Work Sensible ................................................................. 86.5 W/person Latent ................................................................... 133.3 W/person Schedule ..................................... Fractional Schedule
2.2. Task Lighting: Wattage ................................................................. 0.00 W/m² Schedule ............................................................. None
2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None
2.3. Electrical Equipment: Wattage ................................................................. 0.00 W/m² Schedule .................................... Fractional Schedule 3. Walls, Windows, Doors:
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SE 29.7 0 0 0 3.1. Construction Types for Exposure SE Wall Type ........................................ Default Wall Assembly 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ...................................................... 0.00 L/s Design Heating ...................................................... 0.00 L/s Energy Analysis .................................................... 0.00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type .......................................... Slab Floor On Grade Floor Area ............................................................. 19.5 m² Total Floor U-Value ............................................. 1.000 W/(m²-°K) Exposed Perimeter .................................................. 5.3 m Edge Insulation R-Value ....................................... 1.00 (m²-°K)/W 7. Partitions: (No partition data).
Space Input Data UNITED MOTORS 12/31/2012 TECHNOZONE 04:19PM
Hourly Analysis Program v4.51 Page 29 of 31
TOILETS M 1. General Details: Floor Area ............................................................... 9.2 m² Avg. Ceiling Height .................................................. 3.0 m Building Weight ................................................... 341.8 kg/m² 1.1. OA Ventilation Requirements: Space Usage .......................................... User-Defined OA Requirement 1 .................................................. 0.0 L/s OA Requirement 2 .................................................. 0.0 L/s Space Usage Defaults ........................... User-Defined 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 20.00 W/m² Ballast Multiplier .................................................... 1.00 Schedule .................................... Fractional Schedule
2.4. People: Occupancy ............................................................... 1.0 Person Activity Level ......................................... Medium Work Sensible ................................................................. 86.5 W/person Latent ................................................................... 133.3 W/person Schedule ..................................... Fractional Schedule
2.2. Task Lighting: Wattage ................................................................. 0.00 W/m² Schedule ............................................................. None
2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None
2.3. Electrical Equipment: Wattage ................................................................. 0.00 W/m² Schedule .................................... Fractional Schedule 3. Walls, Windows, Doors: (No Wall, Window, Door data). 4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 9.2 0 0 4.1. Construction Types for Exposure H Roof Type ....................................... Default Roof Assembly 5. Infiltration: Design Cooling ...................................................... 0.00 L/s Design Heating ...................................................... 0.00 L/s Energy Analysis .................................................... 0.00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: 7.1. 1st Partition Details: Partition Type ........................................ Wall Partition Area ....................................................................... 26.2 m² U-Value ............................................................... 2.800 W/(m²-°K) Uncondit. Space Max Temp .................................. 40.0 °C Ambient at Space Max Temp ................................ 40.0 °C Uncondit. Space Min Temp ................................... 23.9 °C Ambient at Space Min Temp ................................. 12.8 °C
7.2. 2nd Partition Details: (No partition data).
Space Input Data UNITED MOTORS 12/31/2012 TECHNOZONE 04:19PM
Hourly Analysis Program v4.51 Page 30 of 31
WATCHMANS ROOM M 1. General Details: Floor Area ............................................................. 12.6 m² Avg. Ceiling Height .................................................. 3.0 m Building Weight ................................................... 341.8 kg/m² 1.1. OA Ventilation Requirements: Space Usage .......................................... User-Defined OA Requirement 1 .................................................. 3.5 L/s/person OA Requirement 2 .................................................. 0.0 L/s Space Usage Defaults ........................... User-Defined 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 20.00 W/m² Ballast Multiplier .................................................... 1.00 Schedule .................................... Fractional Schedule
2.4. People: Occupancy ............................................................... 1.0 Person Activity Level ......................................... Medium Work Sensible ................................................................. 86.5 W/person Latent ................................................................... 133.3 W/person Schedule ..................................... Fractional Schedule
2.2. Task Lighting: Wattage ................................................................. 0.00 W/m² Schedule ............................................................. None
2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None
2.3. Electrical Equipment: Wattage ............................................................... 300.0 Watts Schedule .................................... Fractional Schedule 3. Walls, Windows, Doors:
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SW 11.6 0 0 0
SE 16.1 0 0 0 3.1. Construction Types for Exposure SW Wall Type ........................................ Default Wall Assembly 3.2. Construction Types for Exposure SE Wall Type ........................................ Default Wall Assembly 4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 12.6 0 0 4.1. Construction Types for Exposure H Roof Type ....................................... Default Roof Assembly 5. Infiltration: Design Cooling ...................................................... 0.00 L/s Design Heating ...................................................... 0.00 L/s Energy Analysis .................................................... 0.00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: 7.1. 1st Partition Details: Partition Type .................................... Ceiling Partition Area ....................................................................... 12.2 m² U-Value ............................................................... 2.800 W/(m²-°K) Uncondit. Space Max Temp .................................. 40.0 °C Ambient at Space Max Temp ................................ 40.0 °C Uncondit. Space Min Temp ................................... 23.9 °C Ambient at Space Min Temp ................................. 12.8 °C
7.2. 2nd Partition Details: (No partition data).
Space Input Data UNITED MOTORS 12/31/2012 TECHNOZONE 04:19PM
Hourly Analysis Program v4.51 Page 31 of 31
WORKERS REST ROOM M 1. General Details: Floor Area ............................................................. 24.4 m² Avg. Ceiling Height .................................................. 3.0 m Building Weight ................................................... 341.8 kg/m² 1.1. OA Ventilation Requirements: Space Usage .......................................... User-Defined OA Requirement 1 .................................................. 3.5 L/s/person OA Requirement 2 .................................................. 0.0 L/s Space Usage Defaults ........................... User-Defined 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................. Recessed (Unvented) Wattage ............................................................... 20.00 W/m² Ballast Multiplier .................................................... 1.00 Schedule .................................... Fractional Schedule
2.4. People: Occupancy ............................................................... 4.0 People Activity Level ......................................... Medium Work Sensible ................................................................. 86.5 W/person Latent ................................................................... 133.3 W/person Schedule ..................................... Fractional Schedule
2.2. Task Lighting: Wattage ................................................................. 0.00 W/m² Schedule ............................................................. None
2.5. Miscellaneous Loads: Sensible ...................................................................... 0 W Schedule .............................................................. None Latent .......................................................................... 0 W Schedule .............................................................. None
2.3. Electrical Equipment: Wattage ............................................................... 300.0 Watts Schedule .................................... Fractional Schedule 3. Walls, Windows, Doors:
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SW 16.5 0 0 0
NW 21.4 0 0 0 3.1. Construction Types for Exposure SW Wall Type ........................................ Default Wall Assembly 3.2. Construction Types for Exposure NW Wall Type ........................................ Default Wall Assembly 4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 24.4 0 0 4.1. Construction Types for Exposure H Roof Type ....................................... Default Roof Assembly 5. Infiltration: Design Cooling ...................................................... 0.00 L/s Design Heating ...................................................... 0.00 L/s Energy Analysis .................................................... 0.00 L/s Infiltration occurs only when the fan is off. 6. Floors: Type ....................... Floor Above Conditioned Space (No additional input required for this floor type). 7. Partitions: 7.1. 1st Partition Details: Partition Type ........................................ Wall Partition Area ....................................................................... 16.8 m² U-Value ............................................................... 2.800 W/(m²-°K) Uncondit. Space Max Temp .................................. 40.0 °C Ambient at Space Max Temp ................................ 40.0 °C Uncondit. Space Min Temp ................................... 23.9 °C Ambient at Space Min Temp ................................. 12.8 °C
7.2. 2nd Partition Details: (No partition data).