STABILITY OF A SIX STOREY STEEL FRAME STRUCTURE

SHAMSHINAR BINTI SALEHUDDIN

A dissertation submitted in partial fulfilment of the

requirements for the award of the degree of

Master of Engineering ( Civil - Structure )

Faculty of Civil Engineering

Universiti Teknologi Malaysia

MAY, 2011

Page 2: Stability of a six storey steel frame structure June 2011eprints.utm.my/id/eprint/26383/1/ShamshinarSalehuddinMFKA2011.p… · accurate. On top of this, several designers did not

iii

To my beloved husband, family, lecturers and friends

Page 3: Stability of a six storey steel frame structure June 2011eprints.utm.my/id/eprint/26383/1/ShamshinarSalehuddinMFKA2011.p… · accurate. On top of this, several designers did not

iv

ACKNOWLEDGEMENT

In the process of preparing and completing this report, I was in contact either

directly or indirectly with many people, academicians and wholesaler. They have

contributed towards my understanding and thought.

In particular, I wish to express my greatest appreciation to my supervisor, Assoc.

Prof. Dr. Suhaimi Abu Bakar for his encouragement, guidance, critics, and motivations.

Without his continued support and interest, this report would have been the same as

presented here.

At the same moment, I am grateful to all my family members for their support

and encouragement. My sincere appreciations also to my beloved husband, Mohd Faisal

bin Mohd Azlan and my father in law, Dr. Mohd Azlan bin Yahya who have provided

assistance and useful tips indeed. Finally, special thank dedicated to Universiti Malaysia

Perlis and Ministry of Higher Education for giving opportunity to sponsor my master

and those who directly or indirectly involve in the process of producing this study.

I hope my findings in this study will expand the knowledge in this field and

contribute to all of us in future.

Page 4: Stability of a six storey steel frame structure June 2011eprints.utm.my/id/eprint/26383/1/ShamshinarSalehuddinMFKA2011.p… · accurate. On top of this, several designers did not

v

ABSTRACT

The world nowadays requires more tall buildings to overcome limited land

space and creating high esthetic value. However, these high rise buildings require high

frame structure stability for safety and design purposes. This research focused on non

linear geometric analysis to be compared to previous studies on linear analysis. The

linear analysis did not consider deformed configuration which can be considered as least

accurate. On top of this, several designers did not incorporate the wind load which could

lead to sway effect to tall buildings. In this study, a six storey 2-D steel frame structure

with twenty four meter height has been selected to be idealized as tall building model.

The model was analyzed by using SAP2000 structural analysis software with the

consideration of geometric non linear effect. At the same time, several factors including

the use of bracing, varying distributed loads on beam’s element and an increased in

column size at bottom part of the building were also applied to study the sway and

stability of the building. In addition, several cases including placing a fully bracing,

bracing at half height of the building and alternate bracing were also studied. This study

showed that a steel frame with the consideration of wind load produce greater sway

value as compared to the steel frame without wind load. The sway prediction by using

linear analysis was found to be less than 4% compared to the sway prediction from non

linear analysis. This indicates that the non linear analysis is vital and significant element

to be adopted for the analysis of tall building. The study also found that the use of

bracing system results in small sway values compared to the frame without bracing

system. As for consideration to costing aspect, the use of alternate bracing provide

better option compared to half bracing in terms of stability of the building. The analysis

results also showed that the adjustment of distributed load at upper part of steel frame

structure able to provide different sway values, creating higher stiffness at lower part of

the building which reduces the sway values and increases the stability of the building.

SAP2000 software is found as reliable tool in evaluating structural analysis especially

when involving non linear analysis.

Page 5: Stability of a six storey steel frame structure June 2011eprints.utm.my/id/eprint/26383/1/ShamshinarSalehuddinMFKA2011.p… · accurate. On top of this, several designers did not

vi

ABSTRAK

Pada masa sekarang, dunia memerlukan lebih bangunan tinggi untuk mengatasi

masalah kekurangan ruang tanah dan untuk mencipta nilai estetika yang tinggi.

Walaubagaimanapun, bangunan tinggi ini memerlukan lebih kestabilan dalam struktur

kerangka untuk tujuan keselamatan dan rekabentuk. Kajian ini menumpu lebih kepada

analisis geometrik tak linear kerana kajian sebelumnya lebih kepada analisis linear.

Analisis linear tidak mengambil kira perubahan bentuk yang boleh di anggap kurang

tepat. Selain daripada itu, ramai jurutera kadang kala tidak mengendahkan beban angin

yang juga boleh menyumbang kesan huyung kepada bangunan tinggi. Dalam kajian

ini,enam tingkat struktur kerangka keluli 2-D setinggi dua puluh empat meter dipilih

sebagai bahan kajian untuk bangunan tinggi. Model ini telah dianalisis menggunakan

perisian SAP2000 dengan mengambil kira analisis geometrik tak linear. Pada masa yang

sama, beberapa pendekatan dilakukan seperti meletak perembat, mempelbagai beban

teragih seragam di atas rasuk dan menambah saiz tiang di bahagian bawah di aplikasi

untuk mengkaji huyung atau kestabilan bangunan. Tambahan lagi, beberapa kes seperti

meletak keseluruhan kerangka dengan perembat, hanya separuh di bahagian atas dan

berselang seli juga dikaji. Jelas menunjukkan bahawa kerangka keluli dengan beban

angin memberi lebih tinggi nilai huyung dari kerangka keluli tanpa beban angin.

Ramalan huyung menggunakan analisis linear didapati kurang melebihi 4% dari ramalan

huyung oleh analisis tak linear. Ini menunjukkan analisis tak linear adalah keperluan

dan penting digunakan untuk menganalisis bangunan tinggi. Sistem kerangka

berperembat memberi nilai huyung yang lebih kecil berbanding sistem kerangka tanpa

berperembat. Dari aspek kos pembinaan, pilihan antara hanya separuh perembat di

bahagian atas dan berselang seli menunjukkan kerangka berselang seli adalah lebih baik

untuk meningkatkan kestabilan bangunan. Keputusan analisis jelas menunjukkan

ubahsuai beban teragih seragam di atas rasuk di bahagian atas bangunan boleh memberi

nilai huyung yang sedikit. Tambahan lagi, meningkatkan kekukuhan bangunan pada

bahagian bawah juga boleh mengurangkan nilai huyung dan meningkatkan kestabilan

bangunan. Perisian SAP2000 didapati adalah alat yang boleh digunakan untuk

menganalisis struktur terutama yang melibatkan analisis non linear.

Page 6: Stability of a six storey steel frame structure June 2011eprints.utm.my/id/eprint/26383/1/ShamshinarSalehuddinMFKA2011.p… · accurate. On top of this, several designers did not

vii

TABLE OF CONTENTS

CHAPTER TITLE PAGE

THESIS TITLE i

DECLARATION ii

DEDICATION iii

ACKNOWLEDGMENT iv

ABSTRACT v

ABSTRAK vi

TABLE OF CONTENTS vii

LIST OF TABLES xi

LIST OF FIGURES xiii

NOTATIONS xvi

CHAPTER 1 INTRODUCTION 1

1.0 Introduction 1

1.1 Statement of Problems 2

1.2 Objectives of the Research 3

1.3 Scope of the Research 3

1.4 Significance of the Research 4

CHAPTER 2 LITERATURE REVIEW 5

2.0 Introduction 5

2.1 Structural Stability 7

2.2 Linear and Non Linear Analysis 8

Page 7: Stability of a six storey steel frame structure June 2011eprints.utm.my/id/eprint/26383/1/ShamshinarSalehuddinMFKA2011.p… · accurate. On top of this, several designers did not

viii

2.3 Theoretical Formula of Non Linear Analysis 9

2.4 Linear and Non Linear Analysis of Frame

Structure

12

2.5 Brace System 14

2.6 Wind Loading 15

CHAPTER 3 VERIFICATION OF STRUCTURAL

ANALYSIS SOFTWARE SAP2000

18

3.0 Introduction 18

3.1 Manual Calculation Using Mathcad 20

3.2 Analysis of Frame Structure Using

SAP2000

33

CHAPTER 4 LINEAR AND GEOMETRIC NON

LINEAR ANALYSIS OF STEEL

FRAME STRUCTURE

35

3.0 Introduction 35

4.1 The Distributed Load on Beam 35

4.2 Wind calculation using CP3, Chapter V

( Part 2)

39

4.3 Linear and Geometric Non Linear Analysis

Using SAP2000

44

4.4 Cases to be Analyzed Using SAP2000 48

CHAPTER 5 ANALYSIS RESULTS AND

DISCUSSIONS

56

5.0 Introduction 56

5.1 Results for Linear and Geometric Non

Linear Analysis of Steel Frame

56

Page 8: Stability of a six storey steel frame structure June 2011eprints.utm.my/id/eprint/26383/1/ShamshinarSalehuddinMFKA2011.p… · accurate. On top of this, several designers did not

ix

5.1.1

Case 1 - Linear and Non Linear Analysis of

Steel Frame without Wind Load

57

5.1.2 Case 2 – Linear and Non Linear Analysis of

Steel Frame with Wind Load Consideration

61

5.1.3 Case 2(a) – Non Linear Analysis of Steel

Frame with Maximum Wind Load

Consideration

64

5.1.4 Case 3 – Linear and Non Linear Analysis of

Steel Frame with Fully Bracing

66

5.1.5 Case 4 – Linear and Non Linear Analysis of

Steel Frame with Bracing Placed at Half

Top Side of Building

69

5.1.6 Case 5 – Linear and Non Linear Analysis of

Steel Frame with Alternate Bracing

72

5.1.7 Case 6 – Linear and Non Linear Analysis of

Steel Frame with Increasing of Distributed

Load at Upper Half Portion of the Building

75

5.1.8 Case 7 – Linear and Non Linear Analysis of

Steel Frame with Decreasing of Distributed

Load at Upper Half Portion of the Building

78

5.1.9 Case 8 - Linear and Non Linear Analysis of

Steel Frame with Increasing of Column Size

at Lower Portion of the Building

81

5.2 Discussion of the Results 84

5.2.1 Analysis 1 – Comparison of Wind Effect for

Linear and Non Linear Analysis

84

5.2.2 Analysis 2 – Comparison of Sway

Prediction from Linear and Geometric Non

Linear Analysis

86

Page 9: Stability of a six storey steel frame structure June 2011eprints.utm.my/id/eprint/26383/1/ShamshinarSalehuddinMFKA2011.p… · accurate. On top of this, several designers did not

x

5.2.3 Analysis 3 - Approach Applied to Study

Sway Effect

87

5.2.4 Analysis 4 - The SAP2000 Software

Checking

92

CHAPTER 6 CONCLUSIONS AND

RECOMMENDATIONS

93

6.0 Introduction 93

6.1 Conclusions 93

6.2 Recommendations 94

REFERENCES 95

Page 10: Stability of a six storey steel frame structure June 2011eprints.utm.my/id/eprint/26383/1/ShamshinarSalehuddinMFKA2011.p… · accurate. On top of this, several designers did not

xi

LIST OF TABLES

TABLE NO. TITLE PAGE

4.1 Topography factor, S1 39

4.2 Ground roughness, building size and height above ground,

factor S2

40

4.3 Force coefficients Cf for rectangular clad buildings with flat

roofs (acting in the direction of the wind)

42

4.4 Wind calculation result using CP3, Chapter V ( Part 2 ) 44

5.1 Sway for linear and non linear analysis of steel frame

without wind load - Case 1

58

5.2 Sway for linear and non linear analysis of steel frame with

the consideration of wind load - Case 2

61

5.3 Sway for non linear analysis of steel frame with the

maximum consideration of wind load - Case 2(a)

64

5.4 Sway for linear and non linear analysis of steel frame with

fully bracing - Case 3

66

5.5 Sway for linear and non linear analysis of steel frame with

bracing system placed at half of building ( top side ) - Case 4

69

5.6 Sway for linear and non linear analysis of steel frame with

alternate bracing - Case 5

72

5.7 Sway for linear and non linear analysis of steel frame with

increase distributed load at half building ( top side ) - Case 6

75

5.8 Sway for linear and non linear analysis of steel frame with

Page 11: Stability of a six storey steel frame structure June 2011eprints.utm.my/id/eprint/26383/1/ShamshinarSalehuddinMFKA2011.p… · accurate. On top of this, several designers did not

xii

decrease distributed load at half building ( top side ) - Case 7 78

5.9 Sway for linear and non linear analysis of steel frame by

increasing of column size at lower half portion of the

building - Case 8

81

5.10 Sway value due to wind and no wind effect predicted from

linear analysis

85

5.11 Sway value due to wind and no wind effect predicted from

linear analysis

85

5.12 Sway result of steel frame structure from linear and

geometric non linear analysis prediction ( Case 2 )

86

5.13 Comparison of sway for several methods of bracing system 88

5.14 Higher and lower distributed load on a beam 89

5.15 Comparison of sway due to standard and higher column size 91

Page 12: Stability of a six storey steel frame structure June 2011eprints.utm.my/id/eprint/26383/1/ShamshinarSalehuddinMFKA2011.p… · accurate. On top of this, several designers did not

xiii

LIST OF FIGURES

FIGURE NO. TITLE PAGE

2.1 Instability of frame structure under horizontal loads 7

2.2 Pictorial representation of bar with second order effect 8

2.3 Load deformation curves of one storey frame 13

2.4 Deformation of a brace 14

2.5 A wind load assume to hit the building 16

3.1 Arrangement of number for calculation at a trial steel frame

structure

19

3.2 A trial steel frame structure illustrate in SAP2000 33

3.3 Result of displacement, U1 at top joint at left hand in unit

millimeter

34

4.1 The plan view of building to be calculated for distributed

load

36

4.2 The frame model to be analyzed 38

4.3 The plan shape of the steel frame structure that hit by the

wind

43

4.4 New model form 45

4.5 Joint restraint 46

4.6 Load Case Data form 47

4.7 Analytical model for Case 1 48

4.8 Analytical model for Case 2 49

Page 13: Stability of a six storey steel frame structure June 2011eprints.utm.my/id/eprint/26383/1/ShamshinarSalehuddinMFKA2011.p… · accurate. On top of this, several designers did not

xiv

4.9 Analytical model for Case 3 : Steel frame structure with fully

braced

50

4.10 Analytical model for Case 4 : Partially braced steel frame

structure

51

4.11 Analytical model for Case 5 : Steel frame structure with

alternate bracing system

52

4.12 Analytical model for Case 6 : Higher value of distributed

load

53

4.13 Analytical model for Case 7 : Lower value of distributed

load

54

4.14 Analytical model for Case 8 : Higher stiffness of the column

base

55

5.1(a) Sway at different level of steel frame structure without wind

load ( linear analysis )

59

5.1(b) Sway at different level of steel frame structure without wind

load ( non linear analysis )

60

5.2(a) Sway at different level of steel frame structure with wind

load consideration ( linear analysis )

62

5.2(b) Sway at different level of steel frame structure with wind

load consideration ( non linear analysis )

63

5.2(c) Sway at different level of steel frame structure with

maximum wind load consideration ( non linear analysis )

65

5.3(a) Sway at different level of steel frame structure with fully

bracing ( linear analysis )

67

5.3(b) Sway at different level of steel frame structure with fully

bracing ( non linear analysis )

68

5.4(a) Sway at different level of steel frame with half of top side of

the building be placed with bracing system ( linear analysis )

70

5.4(b) Sway at different level of steel frame with half of top side of

the building be placed with bracing system ( non linear

Page 14: Stability of a six storey steel frame structure June 2011eprints.utm.my/id/eprint/26383/1/ShamshinarSalehuddinMFKA2011.p… · accurate. On top of this, several designers did not

xv

analysis ) 71

5.5(a) Sway at different level of steel frame with alternate bracing

( linear analysis )

73

5.5(b) Sway at different level of steel frame with alternate bracing

( non linear analysis )

74

5.6(a) Sway at different level of steel frame structure with

increasing of applied distributed load acted at upper of the

building ( linear analysis )

76

5.6(b) Sway at different level of steel frame structure with

increasing of applied distributed load acted at upper of the

building ( non linear analysis )

77

5.7(a) Sway at different level of steel frame structure with

decreasing of applied distributed load acted at upper of the

building ( linear analysis )

79

5.7(b) Sway at different level of steel frame structure with

decreasing of applied distributed load acted at upper of the

building ( non linear analysis )

80

5.8(a) Sway at different level of steel frame structure by increasing

the stiffness of the column at lower portion ( linear analysis )

82

5.8(b) Sway at different level of steel frame structure by increasing

the stiffness of the column at lower portion ( non linear

analysis )

83

5.9 Comparison between the Results from Linear and Geometric

Non Linear Analysis

87

5.10 Comparison of Sway Prediction ( Geometric Non Linear

Analysis ) due to Different Type of Bracing System

88

5.11 Comparison of Sway due to Different Distributed Load from

Geometric Non Linear Analysis

90

5.12 Comparison of Sway for Standard Column Size and Higher

Column Size ( Non Linear Analysis Prediction )

91

Page 15: Stability of a six storey steel frame structure June 2011eprints.utm.my/id/eprint/26383/1/ShamshinarSalehuddinMFKA2011.p… · accurate. On top of this, several designers did not

xvi

NOTATIONS

P - Axial load

P – delta - Non linear effect

A - Area

I - Moment of inertia

Φ - Angle

2D - Two dimensional

BS - British Standard

V - Wind speed

Vs - Design wind speed

S1 - Topography factor

S2 - Ground roughness, building size and height above ground

S3 - Exposure to wind

q - Dynamic pressure of wind

k - Wind coefficient

Wk - Wind load

Cf - Force coefficient

ke - Linear elastic stiffness matrix

kg - Geometric stiffness matrix

Γ - Diagonal matrix

Page 16: Stability of a six storey steel frame structure June 2011eprints.utm.my/id/eprint/26383/1/ShamshinarSalehuddinMFKA2011.p… · accurate. On top of this, several designers did not

xvii

Ke - Global linear elastic stiffness matrix

T - Transform

u - Member displacement for local

v - Member displacement for global

Q - Member force

E - Modulus of elasticity

W - Distributed load

L - Length

U1 - Displacement value in X direction

U2 - Displacement value in Y direction

U3 - Displacement value in Z direction

R1 - Rotation value in X direction

R2 - Rotation value in Y direction

R3 - Rotation value in Z direction

Page 17: Stability of a six storey steel frame structure June 2011eprints.utm.my/id/eprint/26383/1/ShamshinarSalehuddinMFKA2011.p… · accurate. On top of this, several designers did not

CHAPTER 1

INTRODUCTION

There are several types of structure in this modern world. Most of the

structures behaves like linear elastic under a service loads. Slender structures such as

suspension systems, arches and tall buildings can be considered as non linear elastic. In

general, buildings having 30 to 50 stories can be classified as tall buildings. While, for

buildings with 50 stories or more can be considered as super tall buildings.

Tall building is the most structure that requires stability because it consist a lot of

frame structure with different width and height. Building will be unstable if inadequate

of lateral support and may resulted to collapse. Buildings and structures are considered

stable with lateral supports by using either bracing system or shear system or both such

as wall to ensure the stability of the building. Moreover, the important thing to consider

are the software to be used to analysis the tall building structure and a wind speed at

construction area to avoid any problem in future.

Page 18: Stability of a six storey steel frame structure June 2011eprints.utm.my/id/eprint/26383/1/ShamshinarSalehuddinMFKA2011.p… · accurate. On top of this, several designers did not

2

1.1 Statement of Problems

There are several problems that require scientific explanation in this study:

1. A linear analysis is more prefer as compare to non linear analysis in

structural design. This is because it can be simplify by design, time and

cost saving, and at the same time it does not require the use of computer

software for non linear case. Furthermore, a non linear analysis is more

complicated than linear analysis in structural problem solving. Therefore it

is important to understand the difference between both non linear and linear

analysis and able to justify the application of these approach. At the same

time the verification of the software is necessary to identify the reliability

of the tool.

2. The wind speed in Malaysia is less than 35 km/h at 10 m height refer to

Malaysia Standard. Eventhough the wind speed is small, it can still give

adverse effect to the tall building. Therefore, the identification of suitable

wind speed is important to ensure the stability of the steel frame.

3. Client or project initiator always focuses on capital cost and not the quality

of the building construction. Intergration of additional structure such as

bracing may increase the operation cost but at the same time it will improve

the sway and crack and therefore increase the life time of the building.

Hence, it is important to identify the requirement and the positioning of the

braces in steel frame structure.

Page 19: Stability of a six storey steel frame structure June 2011eprints.utm.my/id/eprint/26383/1/ShamshinarSalehuddinMFKA2011.p… · accurate. On top of this, several designers did not

3

1.2 Objectives of Study

The objectives of this study are:

1. To analyze the steel frame structure subjected to wind and without wind

load by using linear and geometric non linear analysis and to observe the

effect.

2. To compare the difference of lateral displacement or sway values between

linear and geometric non linear analysis prediction.

3. To observe if there is an alternative approach to decrease sway for steel

frame that being idealized as tall building.

4. To verify whether SAP2000 software is reliable tool for the evaluation of

tall building structure.

1.3 Scope of the Study

The scope of works in this research includes:

1. A six storey building which made up of steel material and was analyzed by

using SAP2000 software for linear and geometric non linear analysis.

2. The atmospheric wind speeds which will be use to study the wind behavior.

The evaluation will be based on data from Malaysia Standard and wind

calculation by using CP3, Chapter V ( Part 2 ).

Page 20: Stability of a six storey steel frame structure June 2011eprints.utm.my/id/eprint/26383/1/ShamshinarSalehuddinMFKA2011.p… · accurate. On top of this, several designers did not

4

1.4 Significance of the Study

This study can be used as a reference to other researchers and designers to

explore the stability in frame structure and design application. It can also provide a good

design, more stable and longer last tall building which able to provide better service to

consumers.

Page 21: Stability of a six storey steel frame structure June 2011eprints.utm.my/id/eprint/26383/1/ShamshinarSalehuddinMFKA2011.p… · accurate. On top of this, several designers did not

95

REFERENCES

[1] Daniel L. Schodek ( 2004 ). Structures, Fifth Edition, Pearson Prentice Hall, page

15 -21.

[2] Mc Guire, W., Gallagher, R.H. and Ziemian, R.D. (2000). Matrix Structural

Analysis Second Edition, John Wiley & Sons Publication, page 217-218.

[3] Robert D. Cook, David S. Malkus, Michael E. Plesha and Robert J. Witt (2002).

Concepts and Applications of Finite Element Analysis, John Wiley & Sons

Publication.

[4] E.S. Kameshki, M.P. Saka (2003). Genetic Algorithm based Optimum Design of

Nonlinear Planar Steel Frames with Various Semi – Rigid Connections, Journal of

Construction Steel Research, Volume 59.

[5] El Zanaty, M. H and Murray, D.W (1983). Nonlinear Finite Element Analysis of

Steel Frames, Journal of Structural Engineering, Volume 109, No. 1 - 4.

[6] Hingginbotham , A.B. and Hanson (1976). Axial Behaviour of Steel Members,

Journal of the Structural Engineering Division, ASCE, Volume 106.

[7] Emil Simiu and Robert H. Scanlan (1996). Wind Effects on Structures, 1996, John

Wiley & Sons Publication.

[8] Seshasayee Ankireddi and Henry T. Y. Yang (1996). Simple ATMD Control

Methodology for Tall Buildings Subject to Wind Load, Journal of Structural

Engineering, Volume 122, No. 1 - 3.

[9] British Standard (1972), CP3 Chapter V ( Part 2 ). Wind Loads, London.

[10] Yi Kwei Wen (1983). Wind Direction and Structural Reliability, Journal of

Structural Engineering, Volume 109, No. 1 - 4.

Page 22: Stability of a six storey steel frame structure June 2011eprints.utm.my/id/eprint/26383/1/ShamshinarSalehuddinMFKA2011.p… · accurate. On top of this, several designers did not

96

[11] K. C. Mehta, J. E. Minor and T. A. Reinhold (1983). Wind Speed Damage

Correlation in Hurricane Frederic, Journal of Structural Engineering, Volume

109, No. 1 - 4.

[12] W F Chen (1999). Practical Analysis for Semi-Rigid Frame Design, World

Scientific Publishing Co. Pte. Ltd. Singapore, page 2.

[13] M. Farshad (1994). Stability of Structures, Elsevier Science B.V, page 2.

[14] Malaysia Standard (2002). Code of Practice on Wind Loading for Building

Structure, Malaysia.