ID Type Drawing Location Description
HIGH PRIORITY ITEMS
2302
AA - Placeholder for unknowns General view Building - General/Building - General address-Level 3 East : ii. Level 3 East Concourse l. Water pools away from floalong Grid N7
2739
Ext - Substan tial - San itary Sewer Si te Serv ices Drawing S ite Services/Si te Services Not to speci ficat ion/drawings-sag in san itary l ine from San MH4A to San MH
2817 Arch - Substantial - Door Hardware A 00104 A3 Corridor 3 4W-AC3/4W-AC3 Not to specification/drawings-Astragal missing
5876 Arch - Substantial - Masonry Units A 00103 B3 PC 9 10 3W-BAD/3W-BAD Not to specification/drawings-Diagonal crack
MEDIUM PRIORITY ITEMS
491 AA - Placeholder for unknowns A 00101 B3 Main Electrical
Room1W-703/1W-703 address-Concrete finish has dips and divots
509 AA - Placeholder for unknowns A 00103 C3 lift 3E-CL/3E-CL address-Significant wear slab cracking parallel to installed saw cuts was obse
the area of SE elevator 5.
540 Arch - Substantial - Grandstands PedestrianCoating System
A 00103 C3 gradin 2 3E-CG2/3E-CG2 Not to specification/drawings-Surface defects.
542 Arch - Substantial - Grandstands PedestrianCoating System
A 00103 C3 gradin 1 3E-CG1/3E-CG1 Not to specification/drawings-Surface defects. Row 13, seat 5 south of 1st VOsouth end
561 Arch - Substantial - Grandstands PedestrianCoating System
A 00103 C3 gradin 4 3E-CG4/3E-CG4 Not to specification/drawings-Footprints in coating
562 Arch - Substantial - Grandstands PedestrianCoating System
A 00103 C3 gradin 4 3E-CG4/3E-CG4 Not to specification/drawings-Bubbles in coating
563 Arch - Substantial - Grandstands PedestrianCoating System
A 00103 C3 gradin 4 3E-CG4/3E-CG4 Not to specification/drawings-Footprints in coating
587
AA - Placeholder for unknowns A 00103 A3 Stairs A address-Cracks observed at landings and in treads, along long axis of stair. Calso generating at lowest landing at joint between structural steel support and foundation support. (Cannon SVR 022)
588
AA - Placeholder for unknowns A 00103 B3 Stair F 3W-106/3W-106 address-Cracks observed at landings and in treads, along long axis of stair. Calso generating at lowest landing at joint between structural steel support and foundation support. (Cannon SVR 022)
591
AA - Placeholder for unknowns A 00103 D3 stairs 3E-104/3E-104 address-Significant cracks in inner curbs noted at landing between L2-L3. (Ca
SVR 022)677
AA - Placeholder for unknowns A 00102 B3 Mechanical serviceroom
2W -707/2W -707 address-Slope in mechanical room . 2W -707 between north exterior.
682 Arch - Substantial - Fixed Audience Seating A 00104 A3 gradin 3 4W-AG3/4W-AG3 Not to specification/drawings-Concern regarding clearance between accessib
and glazing facade.
694 Arch - Substantial - Acoustic Tile Ceilings A 00105 A3 corridor 2 5W-201/5W-201 Ceiling not installed to correct level-Ceiling height to be confirmed or a varianc
submitted.
711 AA - Placeholder for unknowns A 00101 A3 Exercise
STORAGE1W-303/1W-303 address-Fill and finish hole.
PAG HSS SNAGR REPORT
8/20/2019 Stadium deficiencies list
2/15
ID Type Drawing Location Description
PAG HSS SNAGR REPORT
712 Arch - Substantial - Door Hardware A 00101 A3 Exercise
STORAGENot to specification/drawings-Latch plate missing - non-rated door
790 Arch - Substantial - Design issues A 00103 A3 gradin 1 3W-G1/3W-G1 Design Issue-Seat alignment due to bowl curve to be confirmed.794 AA - Placeholder for unknowns A 00103 B3 Mech 3W-409/3W-409 address-Hole in concrete block upper wall requires fill.817 AA - Placeholder for unknowns A 00103 B3 Prepa area 3W-407/3W-407 address-Paint required on plywood.
819 AA - Placeholder for unknowns A 00103 A3 First aid 3W-405/3W-405 address-Fill holes.820 AA - Placeholder for unknowns A 00103 B3 Prepa area 3W-407/3W-407 address-SS Countertop not sized properly for the slanted bottle coolers
823 Arch - Occupancy - Gypsum Board A 00103 B3 Prepa area 3W-407/3W-407 Not to specification/drawings-Typical all concessions - Seal all openings in ce
825 Arch - Substantial - Painting A 00103 A3 Hawkers Room 3W-404/3W-404 Make good damage-Finish door frame826 Mech - Substantial - Sheet Metal A 00103 A3 Hawkers Room 3W-404/3W-404 Not to specification/drawings-Sleeve masonry for ductwork
827Elec - Substantial - Building AutomationSystem
A 00103 A3 Hawkers Room 3W-404/3W-404 Not to specification/drawings-Incomplete work
829Elec - Substantial - Audio Visual & SoundSystems
A 00103 A3 Queue Area Not to specification/drawings-Conduit left proud of wall. To be cut flush
831 Arch - Substantial - Painting A 00103 A3 TR 3W-302/3W-302 Make good damage-Paint touch up
833 AA - Placeholder for unknowns A 00103 A3 Prepa area 3W-403/3W-403 address-caulk between brace and wall. Is this to be caulking? Who is doing th
835 A A - Placeholder for unknowns A 00103 A3 Prepa area 3W-403/3W-403 address-Fire-rated paint patch needed on plywood.
836 AA - Placeholder for unknowns A 00103 A3 Prepa area 3W-403/3W-403 address-Seal openings in ceiling. Install access doors.850 Arch - Substantial - Masonry Units A 00103 A3 Merchandise 3W-401/3W-401 Not to specification/drawings-Hole needs filled.853 G eneral - Substantial - Final Clean A 00103 A3 PCX 3W-PCX1/3W-PCX1 Not to standards-Lots of concrete staining.
919 Arch - Substantial - Design issues A 00101 B3 Media truck 1W-602/1W-602 Design Issue-Typical all columns - column protection in loading dock to be rev
922 AA - Placeholder for unknowns General view FOP/FOP address-Date for installation of soccer equipment sleeves requested972 AA - Placeholder for unknowns A 00102 C3 Stairs 2E-20X/2E-20X address-Cracked wear slab
1349 AA - Placeholder for unknowns A 00103 C3 spectator
concourse3E-CQA/3E-CQA address-Wear slab cracked
1379 Elec - Substantial - AV System A 00103 C3 Food prep Not to specification/drawings-Data cover missing
1453
Arch - Substantial - Architectural Woodwork General view Not to specification/drawings-14) 7) Millwork as to be MDF but does not look Msite. Specifications do not say MDF. Use MDF instead of particle board. Pleasconfirm MDF was not used.
1454
Arch - Substantial - Design issues General view Building - General/Building - General Design Issue-14) 8) Group sales MDF to be mobile but are fixed on site. Drawhave always shown fixed millwork as millwork cannot move with a sink in it .
1460
Arch - Substantial - Design issues General view Building - General/Building - General Design Issue-13) 1) bottom stair on exterior club stairs is extremely short. PleCannon and PDC verify. Concrete was cast to raise the railing, S and N stairs
1461
Arch - Substantial - Design issues General view Building - General/Building - General Design Issue-13) 8) the information/email re: glazing requires a response. Labthe glazing are inside or outside? To be reviewed by Cannon, inside SVR of CLevel 7 stickers inside of glazing.
8/20/2019 Stadium deficiencies list
3/15
ID Type Drawing Location Description
PAG HSS SNAGR REPORT
1469 AA - Placeholder for unknowns General view Building - General/Building - General address-12.) 11) wiring mesh for the speaker to be submitted
1470
AA - Placeholder for unknowns Level 6.1 6.1W/Level 6.1 address-11.) 1) Guard rails Level 6.1 : CoH requests a review of safety standacleaning purposes ONSS to provide mesh to prevent people climbing.
1471 Arch - Substantial - Design issues General view Building - General/Building - General Design Issue-11.) 8) List of obstructed view seats to be sent to the CoH 24 on
lower East.
1474 AA - Placeholder for unknowns General view Building - General/Building - General address-2.)7) Column Level 3 West issue with the vertical pipe to be closed?
Fastening to be reviewed
1480 Arch - Substantial - Design issues General view Building - General/Building - General Design Issue-17.) 5) visiting coaches change room, not as per drawing: Millwo
reviewed.
1481
Elec - Substantial - Other General view Building - General/Building - General Not to specif ication/drawings-17. ) 6) Electrical/ smart boards in TC Offices.. .wfixed as per layout provided by TiCats? Quote for plug modification to be sent
1482
Arch - Substantial - Design issues General view Building - General/Building - General Design Issue-17.) 8) Seat count/ obstructed views- currently, TiCats have sat seat and counted more than 700 obstructed seats (count continues). Cannon review.
1483
AA - Placeholder for unknowns General view Building - General/Building - General address-17.) 14) n/s power- understanding the variation was not submitted hounderstand that there are power and data capabilities in the existing light stanplease confirm. No power/ data provision. VD required.
1494 AA - Placeholder for unknowns General view Building - General/Building - General address-General Notes of Sept 30/14 , 2) Letter from AHU Factory to confirm
warranty to AHU after smoke fire.
1498 AA - Placeholder for unknowns General view Building - General/Building - General address-16.3 Upper East VOM area- stair depth (safety issue?)
1499 AA - Placeholder for unknowns General view Building - General/Building - General address-16.7 Suites -glass slider/ transition to be flush? Code/PSOS complian
1507 AA - Placeholder for unknowns General view Building - General/Building - General address-16.17) Washroom accessories (including hand dryer) - shop drawing
forwarded / reviewed (by sponsors) / approved- noted.
1510 AA - Placeholder for unknowns General view Building - General/Building - General address-16.23) west storage doors are not compliant with variation.
1520 AA - Placeholder for unknowns General view Building - General/Building - General address-15.2) TV level 7 position to be clarified
1527FF&E - Substantial - Kitchen Equipment A 00102 C3 Concessions prepa
area2E-404/2E-404 Not to specification/drawings-Cup dispensers are missing
1531FF&E - Substantial - Kitchen Equipment A 00102 C3 Concessions prepa
area2E-404/2E-404 Not to specif ication/drawings-Pop and ice machine not operational at time of
inspection
1535FF&E - Substant ia l - Ki tchen Equ ipment A 00102 D3 Concessions areas 2E-405/2E-405 Not to spec if icat ion/drawings-Pop and ice machine no t operat iona l a t t ime o f
inspection
1536FF&E - Substant ia l - Ki tchen Equ ipment A 00102 D3 Concessions areas 2E-405/2E-405 Not to spec if icat ion/drawings-Pop and ice machine no t operat iona l a t t ime o f
inspection
1537FF&E - Substant ia l - Ki tchen Equ ipment A 00102 D3 Concessions areas 2E-405/2E-405 Not to spec if icat ion/drawings-Pop and ice machine no t operat iona l a t t ime o f
inspection
8/20/2019 Stadium deficiencies list
4/15
ID Type Drawing Location Description
PAG HSS SNAGR REPORT
1538FF&E - Substant ia l - Ki tchen Equ ipment A 00102 D3 Concessions areas 2E-406/2E-406 Not to spec if icat ion/drawings-Pop and ice machine no t operat iona l a t t ime o f
inspection
1543FF&E - Substantial - Kitchen Equipment A 00102 D3 Concessions areas 2E-406/2E-406 Not to specification/drawings-Stainless steel trims missing on concession side
lines
1544
FF&E - Substant ia l - Ki tchen Equ ipment A 00102 D3 Concessions areas 2E-406/2E-406 Not to spec if icat ion/drawings-S ta in less stee l chase for pop l ines missing
1551 AA - Placeholder for unknowns A 00102 D3 Hawkers room 2E-403/2E-403 address-Hot heated drawers to be commissioned
1556FF&E - Substantial - Kitchen Equipment A 00102 C3 Concession prepa
area2E-400/2E-400 Not to specif ication/drawings-Pop and ice machine not operational at time of
inspection
1559FF&E - Substantial - Kitchen Equipment A 00102 C3 Concession prepa
area2E-400/2E-400 Not to specif ication/drawings-Stainless steel chase for pop lines miss ing
1568FF&E - Substantial - Kitchen Equipment A 00103 C3 Food prep 3E-400/3E-400 Not to specif ication/drawings-Pop and ice machine not operational at time of
inspection
1569FF&E - Substantial - Kitchen Equipment A 00103 C3 Food prep 3E-400/3E-400 Not to specif ication/drawings-Stainless steel trims miss ing on concession side
lines1570 FF&E - Substantial - Kitchen Equipment A 00103 C3 Food prep 3E-400/3E-400 Not to specif ication/drawings-Stainless steel chase for pop lines miss ing
1579FF&E - Substantial - Kitchen Equipment A 00103 D3 prep area 3E-405/3E-405 Not to specif ication/drawings-Pop and ice machine not operational at time of
inspection1581 FF&E - Substantial - Kitchen Equipment A 00103 D3 prep area 3E-405/3E-405 Not to specification/drawings-One (1) popcorn holder broken
1582FF&E - Substantial - Kitchen Equipment A 00103 D3 prep area 3E-405/3E-405 Not to specif ication/drawings-Stainless steel trims m iss ing on concession side
lines1583 FF&E - Substantial - Kitchen Equipment A 00103 D3 prep area 3E-405/3E-405 Not to specification/drawings-Stainless steel chase for pop lines missing1584 FF&E - Substantial - Kitchen Equipment A 00103 D3 prep area 3E-405/3E-405 Not to specification/drawings-Stainless steel chase for pop lines missing1586 FF&E - Substantial - Kitchen Equipment A 00103 D3 prep area 3E-405/3E-405 Not to specification/drawings-W armer 708 is not set in place as per drawing1605 FF&E - Substantial - Kitchen Equipment A 00103 B3 Prepa area 3W-407/3W -407 Not to specification/drawings-Cup dispensers are missing
1645 AA - Placeholder for unknowns A 00101 A3 Stairs Building - General/Building - General review-Level one East: 1.1 SE Stair J North concrete guard has through-wall
several locations. Pin and take a picture
1684
AA - Placeholder for unknowns General view Building - General/Building - General review-Level One East: 3. SE Stair J crack across first landing, aligned with tfrom steel to concrete support structure below no relief cut or movement joint NW Stair J and NE Stair M radiates. Pin and take a picture
1845 AA - Placeholder for unknowns A 00104 A3 stairs H 4W-105/4W-105 address-Cracking of concrete seams in stairwell. Wearing slab affected only -
waterproofing or structural issueC
1847
AA - Placeholder for unknowns A 00104 A3 stairs H 4W-105/4W-105 address-Lots of cracking and chipping of concrete on stair edges. Wearing sla
affected only - not a waterproofing or structural issue
1848 AA - Placeholder for unknowns A 00104 A3 stairs H 4W-105/4W-105 address-Lots of cracking and chipping of stair treads. Wearing slab affected o
a waterproofing or structural issue
1862 AA - Placeholder for unknowns A 00104 A3 Stairs G 4W-102/4W-102 address-Rough seam between concrete pads, lots of chipping and nearby cra
Wearing slab affected only - not a waterproofing or structural issue
1863 AA - Placeholder for unknowns A 00104 A3 Stairs G 4W-102/4W-102 address-Stair pan infill concrete cracking between club and suite level, south
Wearing slab affected only - not a waterproofing or structural issue
8/20/2019 Stadium deficiencies list
5/15
ID Type Drawing Location Description
PAG HSS SNAGR REPORT
1864 AA - Placeholder for unknowns A 00105 A3 Stairs G 5W-102/5W-102 address-Hole in corner of pad, cracking and rough finish. Wearing slab affecte
not a waterproofing or structural issue
1962 Arch - Substantial - Washroom Accessories A 00105 A3 private suite WC
female5W-332/5W -332 Not to specification/drawings-Replace scratched stall door.
2110 AA - Placeholder for unknowns A 00105 A3 B stairs H 5W-105/5W-105 address-Rough patches around column
2111 AA - Placeholder for unknowns A 00105 A3 B stairs H 5W-105/5W-105 address-Pad seams rough and cracked. Wearing slab affected only - not a
waterproofing or structural issue
2156General - Substant ia l - Final Clean General view Bui lding - Genera l/Bu ild ing - General Not to standards-Bldg General : 2 .1 xiv: remove rust stains, o il , weld scorches
other foreign material stains on finished concrete floors
2159 AA - Placeholder for unknowns General view Building - General/Building - General address-Bldg General: 2.1 xvii: install backer rod and sealant at joints betwee
CMU walls and concrete /precast slabs
2249 AA - Placeholder for unknowns General view Building - General/Building - General address-2. Level 2 East ii : South East Accessible Seating Platform: f. At front
edge metal panels, seal all edges typical
2251
AA - Placeholder for unknowns General view Building - General/Building - General address-Level 2 East: South East Accessible Seating Platform h. Crack in conwear slab from bottom of Stair R7 to infill wall below Stair J. W earing slab affe- not a waterproofing or structural issue
2252
Arch - Substantial - Aluminum Grandstands General view Building - General/Building - General Not to specification/drawings-2. Level 2 East ii : South East Accessible SeatinPlatform I. Install sealant at tops and sides of refinished metal infill panels thro
2265
AA - Placeholder for unknowns General view Building - General/Building - General address-2. Level 2 East iv. a. Remove oversized sealant infill between door fr
concrete curb, infill with concrete and seal to door frame. confirm work is com
2292 AA - Placeholder for unknowns General view Building - General/Building - General address-Level 3 East : I. General: a. Fill all CMU wall inside corners and move
joints flush with sealant c/w backer rod as required by width/depth
2295 AA - Placeholder for unknowns General view Building - General/Building - General address-Level 3 East : ii. Level 3 East Concourse e. Repair cracks in wear sla
radiating from Elevator 6 shaft
2301
AA - Placeholder for unknowns General view Building - General/Building - General address-Level 3 East : ii. Level 3 East Concourse k. Repair cracks in wear slaincluding at heads of seating access aisles adjacent to Grid N1, Grid N7, GridStair N2 three cracks at North corner and door of Elevator 5. Lobby
2304 AA - Placeholder for unknowns General view Building - General/Building - General address-Level 3 East : ii. Level 3 East Concourse n. At Stair N1, JM has left h
initials in the concrete repair
2330 Arch - Substantial - Acoustic Tile Ceilings General view Building - General/Building - General Not to specification/drawings-2.3 West Building 1 Level 1 West xvi. 1W-325 V
b. Seal the t-bar along the East corridor
2331
Arch - Substantial - Masonry Units General view Building - General/Building - General Not to specification/drawings-2.3 West Building 1 Level 1 West xvi. 1W-325 Vc. Fill the concrete block wall where it meets the floor. Confirm required work icomplete.
2344 AA - Placeholder for unknowns General view Building - General/Building - General address-2.4 East Building 1. Level 1 East: Stair J: a. At least one crack in con
running up the bottom flight
2345 AA - Placeholder for unknowns General view Building - General/Building - General address-2.4 East Building 1. Level 1 East: Stair J: b. Crack across lower landi
concrete aligned with concrete support wall below
2349 AA - Placeholder for unknowns General view Building - General/Building - General address-2.4 East Building 1. Level 1 East: Stair J: h. Seal joint flush at transit
stair concrete to wear slab concrete
8/20/2019 Stadium deficiencies list
6/15
ID Type Drawing Location Description
PAG HSS SNAGR REPORT
2352 AA - Placeholder for unknowns General view Building - General/Building - General address-2.4 East Building 1. Level 1 East: Stair M : d. Seal joints in concrete c
mid- landing repair cracks in curbs
2353 AA - Placeholder for unknowns General view Building - General/Building - General address-2.4 East Building 1. Level 1 East: Stair M : e. Patch concrete around
base L2 head of lower flight
2354
AA - Placeholder for unknowns General view Building - General/Building - General address-2.4 East Building 1. Level 1 East: Stair M : f. Repair cracks in L2 con
wear slab at floor drain adjacent to head of lower flight
2355
Arch - Substantial - TPO Roofing General view Building - General/Building - General Not to specification/drawings-2.4 East Building 1. Level 1 East: Stair M : h. Insflashing against side wall of Elevator 6 shaft, at upper flight concrete block wa
2357Struc - Substantial - Metal Stairs andBalustrades
General view Bui ld ing - General/Building - General Not to specification/drawings-2.4 East Building 1. Level 1 East: Stair M : j. Reguard pickets at North side of upper mid- landing
2358 AA - Placeholder for unknowns A 00106 A3 stair G 6W-102/6W-102 address-36.2. 6 Level 6 West ii. Stair G : a. Stair no sings , guards, and hand
rusting: grind, clean, and recoat. Confirm work is complete
2360 AA - Placeholder for unknowns A 00106 A3 corridor 2 6W-AC2/6W-AC2 address-36.2 6 Level 6 West: iii Level 6 West Concourse : a. Cracks in wear s
outside Mens Washroom6W-302 at head of Stair G2490 AA - Placeholder for unknowns A 00102 C3 Guest service 2E-201A/2E-201A address-Concrete slab incomplete behind column. Typical of columns on Lev2497 AA - Placeholder for unknowns A 00102 C3 Queue areas 2E-205/2E-205 address-Concrete slab behind column incomplete
2508Elec - Substantial - AV System A 00102 C3 parking 2E-QA/2E-QA Not to specification/drawings-Conflict between sign and TV. TV to be moved t
of wall.
2516
Arch - Substantial - Signage and Graphics A 00102 D3 Queue area 2E-208/2E-208 Not to specification/drawings-Conflict between sign and TV. Move sign to adja
(north).2541 AA - Placeholder for unknowns A 00103 A3 PCX 3W-PCX1/3W-PCX1 address- crack in pad.2560 AA - Placeholder for unknowns A 00106 A3 corridor 2 6W-AC2/6W-AC2 address-Concrete staining and rust marks, typical 6 west.
2667 AA - Placeholder for unknowns A 00106 A3 B elevator vestibule 6W-202/6W-202 address-Crumbling seal between curb and concrete pad
2669 AA - Placeholder for unknowns A 00106 A3 B elevator vestibule 6W-202/6W-202 address-Large crack in pad between concession and column
2733 AA - Placeholder for unknowns Site Services Drawing Site Services/Site Services address-OSG-1 change 1 lid that has no holes to holes. Confirm work has be
complete2828 FF&E - Substantial - Kitchen Equipment A 00104 A3 Bar 4W-309/4W-309 Not to specification/drawings-Pop lines incomplete
2842 Arch - Substantial - Design issues A 00104 A3 Group sales suite B 4W-315/4W-315 Design Issue-Sound attenuation - confirm with BKL if this is a concern.
2869Mech - Substantial - Air Handling Units A 00101 B3 Uniform laundry
storage1W-401/1W-401 Not to speci ficat ion/drawings-West s ide L1 Security Opera tions 1W-401: coor
location of rad heater with system furniture
2876 AA - Placeholder for unknowns A 00103 C3 spectator WR 3E-304/3E-304 address-Unfinished around structural brace. Confirm work is complete2888
Elec - Substantial - Other A 00106 A3 hawkers room Exterior of W est Stands Not to specif ication/drawings-Hard wiring being changed to plug in to be conswith other combi ovens
3021 AA - Placeholder for unknowns A 00102 D3 Stairs 2E-104/2E-104 address-Masonry cap required.
3039 Arch - Substantial - Gypsum Board A 00102 D3 Spectator WR
male2E-307/2E-307 Not to specification/drawings-Mud/sand trim. Both ends of washroom.
3042 Arch - Substantial - Gypsum Board A 00102 D3 Spectator WR
female2E-306/2E-306 Not to specification/drawings-Mud/sand trim. Both ends of washroom.
8/20/2019 Stadium deficiencies list
7/15
ID Type Drawing Location Description
PAG HSS SNAGR REPORT
3049 Arch - Substantial - Gypsum Board A 00102 C3 Spectators WR
female2E-302/2E-302 Not to specification/drawings-Mud trim. Both sides of washroom.
3073
Mech - Substant ia l - Gas F ired Uni ts A 00102 D3 Concessions a reas 2E-406/2E-406 Not to speci ficat ion/drawings-L 2 NE Concess ion- gas regulator needs to be m1m away from electrical equipment, currently it is about 850mm from future ligfixture.
3105 AA - Placeholder for unknowns A 00105 A3 Premium guestservices5W-30X/5W-30X address-Door hardware complete per code. Addi tional hardware requested th
Change Order.
3111 Arch - Substantial - Tiling A 00105 A3 private suite WC
female5W-332/5W-332 grout missing / inadequate-Grouting required
3146Fire - Substantial - Sprinkler System General view Bui ld ing - General/Bui ld ing - General Not to specification/drawings-East Side: spr inkler exi t from East side to West
labelling still required.
3167
Mech - Substantial - Piping A 00101 A3 Suite 1 washroom 1W-323/1W -323 Not to specification/drawings-W est SIde: TMV-1 for showers for visitors 1W -31W-332 will need temperature gauge provided for discharge supply (for visuatemperature delivery)*
3168
Mech - Substantial - Piping A 00101 B3 Suite 3 washroom 1W-375/1W -375 Not to specification/drawings-W est SIde: TMV-1 for shower rms 1W -375, 1W-391, 1W-395 will need temperature gauge provided for discharge supply (for vtemperature delivery)*
3176 AA - Placeholder for unknowns General view Exterior of West Stands address-West Building: 1. Building Exterior: I. Stair A and South facade: a. Pr
metal flashing over masonry veneer not installed slab edge.
3203
AA - Placeholder for unknowns A 00106 A3 B elevator vestibule
2
6W -206/6W -206 address-Level 6 W es t: ii. Concrete exterior floor cracks adjacent to Elevator 4
3215Mech - Substantial - Piping A 00101 C3 Vestibule 1E-201/1E-201 Brackets loose/missing-2.4 East Building: III. Elevator 5 and vestibule 1E-201
Attach standpipe plate to wall
3222
AA - Placeholder for unknowns General view Exterior East Stands/Exterior EastStands
address-2.4 East Building: iv. West wall of East parking: a. Veneer block not ito underside of slab deck above, c/w exposed spray insulation detail f or closurequired
3227 Arch - Substantial - Sheet Metal Flashing andTrim
A 00101 D3 elevators 1E-205/1E-205 Not to specification/drawings-2.4 East Building 1. Building Exterior V. D. Seal underside of slab edge at Stair M install prefinished metal f lashing.
3228
AA - Placeholder for unknowns A 00101 D3 elevators 1E-205/1E-205 address-2.4 East Building 1. Building Exterior v. e. Above door E1E-205, the tbarrier continuity appears incomplete , with veneer block as cold bridge. Jog ineast of door not as per drawings.
3229 AA - Placeholder for unknowns General view Exterior East Stands/Exterior East
Standsaddress-2.4 East Building 1. Building Exterior vi. North facade: a. Resolve stablock air space at east end
3230 AA - Placeholder for unknowns General view Exterior East Stands/Exterior East
Standsaddress-2.4 East Building 1. Building Exterior vi. North facade: b. Overhead d200 requires soffit, and vapor/thermal/air barrier continuity.
3232 AA - Placeholder for unknowns A 00106 A3 B elevator vestibule
26W-206/6W-206 address-L6W Elevator 4 lobby , slab crack
3236 AA - Placeholder for unknowns General view Exterior East Stands/Exterior East
Standsaddress-East Bldg Exterior L1E exposed interior block partition
3239 Arch - Substantial - Masonry Units General view Exterior of West Stands Not to specification/drawings-West Bldg Exterior: Door 1W-202 repair block w
Confirm required work is complete.3240 AA - Placeholder for unknowns General view Exterior of West Stands address-West Bldg Exterior: Door 1W-202 requires soffit, insulation continuity
8/20/2019 Stadium deficiencies list
8/15
ID Type Drawing Location Description
PAG HSS SNAGR REPORT
3246 AA - Placeholder for unknowns General view Exterior East Stands/Exterior East
Standsaddress-19. 7 Gas Valve at North East to be protected: issue of code for acceclarified.
3291Mech - Substantial - Diffusers, Registers,Grilles, Louvers, Vents
A 00101 B3 BIN cleaning RM Not to specification/drawings-West Side L1 : Compactor Bay 1W-513 : Dampactuator not installed. Remove cover on transfer grille on opposite wall.
3307
Arch - Substantial - Glass and Glazing A 00101 A3 Laundry 1W-306/1W-306 Not to specification/drawings-East Level 1: Players Equipment Storage windo
transaction type as scheduled. Installed window to be changed out for transacwindow.
3312
AA - Placeholder for unknowns General view FOP/FOP address-General : East head wall cracks to be monitored and repaired. Dirt anequipment marks to be cleaned. East head wall repairs required at mis- alignefasteners and other locations
3313 AA - Placeholder for unknowns General view Exterior of West Stands address-West Stands : level 4 head wall, precast repairs required due to dam
during construction activities, four locations. Coordinate repair
3342
AA - Placeholder for unknowns General view Exterior East Stands/Exterior EastStands
address-Grandstand coating at east stands between N6 and N7 (Stair R6 aislirregular surface texture and coverage, footprints, and other deformations in thcoating. Area shall be resurfaced.
3343 AA - Placeholder for unknowns General view Exterior of West Stands address-2West finish trim and window closures required atLevel 2 offices , Ar
Confirm work is complete
3344
Fire - Substantial - Standpipe and HoseSystem
A 00102 D3 FIRST AID 2E-309/2E-309 Not to specification/drawings-2E-309 Fire hose cabinet outside of 309 , contrareview and correct angle of fire hose connection for proper operation and clea
3346
AA - Placeholder for unknowns General view FOP/FOP address-FOP : manhole covers have domed tops, covers should be replaced tops that are flush with players walking surface. Confirm work is complete
3442 AA - Placeholder for unknowns A 00103 A3 Merchandise 3W-400/3W-400 address-3West 3W-400 Merch Outlet: steel deck dents.3469 Arch - Substantial - Painting A 00103 A3 PCX 3W-PCX1/3W-PCX1 Not to specification/drawings-3West Exterior: repainting, IMP markings3477 A A - Placeholder for unknowns A 00103 B3 PC 9 10 3W-BAD/3W-BAD address-3West , Concourse: anchor bolts rusted
3479 AA - Placeholder for unknowns A 00103 B3 PC 9 10 3W-BAD/3W-BAD address-3West , Concourse: spray on water proofing -finished product/workm
3481 AA - Placeholder for unknowns A 00103 B3 PC 9 10 3W-BAD/3W-BAD address-3West , Concourse: speakers too low.
3490Elec - Substantial - Other General view North Plaza Not to specification/drawings-SVR 013 : Level 1 West: North hosting patio rec
not yet relocated to wall
3529
Arch - Substantial - Fixed Audience Seating General view Exterior East Stands/Exterior EastStands
Not to specification/drawings-A-SVR # 29: 2.4.6.East Upper Seating Bowl: I. 2Seating installed: some seating showing rust at hinges some seats don't returvertical.
3532
Struc - Substantial - Metal Stairs andBalustrades
General view Bui ld ing - General/Building - General Not to specif ication/drawings-Cannon Design Field architects Report # 31:Observations of Work in Progress:2.1 General: As per previous ASVRs the guinstalled at the lowest tiers of seating, east and west buildings, has a gap betwbottom bar of the guard and the edg
3537
AA - Placeholder for unknowns A 00102 D3 Stairs 2E-104/2E-104 address-Cannon Design Architects Field Report #31: 2.4 East Building 4 LeveConcourse: ii. Correct poor saw cuts at Stair M middle column, Grids E15z/N1
8/20/2019 Stadium deficiencies list
9/15
ID Type Drawing Location Description
PAG HSS SNAGR REPORT
3547
Ext - Substantial - Security Fences General view Exterior East Stands/Exterior EastStands
Not to specification/drawings-Cannon Design Architects Field Report #32:Observations of work in progress 2.1 General: East Side: I. Perimeter securitypost at North parking entrance is damaged and bent.
3631 AA - Placeholder for unknowns General view South Plaza/South Plaza address-the City rejected the green- stained concrete paving at the south end
plaza
3674
AA - Placeholder for unknowns A 00101 D3 elevators 1E-205/1E-205 address-Cannon Design Architects Report # 34: 35.2. East Building: General 2 Elevator 5 Lobby : a remove oversized sealant infill between door frame andconcrete curb infill with concrete and seal to door f rame. Confirm work is com
3708
Arch - Substantial - Signage and Graphics A 00103 B3 Prepa area 3W-407/3W-407 Not to specification/drawings-Cannon Design Architects Field Report # 37 LevWest: ii. Prep 3W -407: a. As installed, room identification signage is hidden wis open
3741Plumb - Substantial - Fixtures A 00106 A3 spectator WR
female6W-301/6W -301 Not to specification/drawings-access panel in wrong place.
3789 AA - Placeholder for unknowns A 00105 A3 Stairs G 5W-102/5W-102 address-Cannon Design Architects Field Report # 37: 4. Level 5 West III. Stai
H: a. Repair cracks in many treads at 1/3 points3829 AA - Placeholder for unknowns A 00101 C3 Janitors 1E-509/1E-509 address-Fill gap between wall and access cover. who is doing this work?
3864 AA - Placeholder for unknowns A 00101 C3 FOP Storage
Community1E-502 review-Repair broken slabs at base of column. Confirm repair is complete.
3871
AA - Placeholder for unknowns A 00101 D3 For Equip Storage
Events
G1E-500/G1E-500 address-Sea l condu it return above/ near 1E-604 doors. Who is to do this work
3899 Arch - Substantial - Painting A 00101 D3 End zone 1E-305/1E-305 Make good damage-Paint return filler
3900Mech - Substant ia l - Hydron ic Piping Systems A 00103 C3 specta to r WR 3E-400/3E-400 Not to spec if icat ion/drawings-Trim around open ing a round heat ing water l ines
3956 Arch - Substantial - Architectural Woodwork A 00104 A3 Group sales suite 4W-300/4W-300 Not to specification/drawings-G&P to provide a price to replace scratched cou
3960 Arch - Substantial - Tiling A 00107 A3 Media WG unisex 7W-301/7W-301 grout missing / inadequate-
3969 Arch - Substantial - Door Hardware A 00107 A3 broadcast 7W-602/7W -602 Not to specification/drawings-Latch plate missing on non-rated door
4053 AA - Placeholder for unknowns A 00101 B3 Suite 3 washroom 1W-374/1W-374 address-caulk corner between walls, fill mortar seam and remove writing abov
Who is doing the masonry caulking on the west side?4214 Arch - Substantial - Painting 3W-303 3W-303/3W-303 Lack of filling-fill and paint holes above toilet4218 A rch - Substantial - Tiling A 00103 A3 First aid 3W-405A/3W-405A Tile cracked / damaged-broken missing tile in corner behind toilet4237 Elec - Substantial - Other A 00103 A3 Prepa area 3W-403/3W-403 Not to specification/drawings-Access hatch missing
4523 Arch - Substantial - Architectural Woodwork A 00107 A3 Security spotters
booth7W-500/7W-500 Not to specification/drawings-millwork is chipped
4566 AA - Placeholder for unknowns A 00103 C3 spectator WR 3E-304/3E-304 address-repair damage to wall adjacent to access panel below sink.4581 AA - Placeholder for unknowns A 00103 C3 Food prep 3E-402/3E-402 address-repair hole in masonry, and paint.4599 AA - Placeholder for unknowns A 00103 C3 lift 3E-CL/3E-CL address-Is this pipe to be insulated4600 A A - Placeholder for unknowns A 00103 C3 lift 3E-CL/3E-CL address-fill floor gap behind column. Determine what work is required here.4601 AA - Placeholder for unknowns A 00103 C3 lift 3E-CL/3E-CL address-transome frame not installed. Confirm work is complete.
8/20/2019 Stadium deficiencies list
10/15
ID Type Drawing Location Description
PAG HSS SNAGR REPORT
4627 AA - Placeholder for unknowns A 00102 D3 Concessions areas 2E-405/2E-405 address-Trim temporary conduit flush to wall and patch.
4628 AA - Placeholder for unknowns A 00102 D3 Concessions areas 2E-405/2E-405 address-seal pipe cuts at wall. Confirm what work, if any, is required here.
4630
Arch - Substantial - Painting A 00102 D3 Concessions areas 2E-405/2E-405 Make good damage-repaint door and frame
4713 AA - Placeholder for unknowns A 00101 A3 Players lounge address-wall finish around device Plan pic # 10360
5244 Arch - Substantial - Signage and Graphics General view Building Signage Not to specification/drawings-Banner-G-C-F_FR-CA EXT 8.0-G2 Change 'Po
'Portes'
5245 Arch - Substantial - Signage and Graphics General view Building Signage Not to specification/drawings-EXT-8.1_FR-CA to add Tribunes (for East and O
5246 Arch - Substantial - Signage and Graphics General view Building Signage Not to specification/drawings-EXT-8.1_FR-CA Change 'Media' to 'Medias'5247 Arch - Substantial - Signage and Graphics General view Building Signage Not to specification/drawings-EXT-14.1_FR-CA Change the accent
5248 Arch - Substantial - Signage and Graphics General view Building Signage Not to specification/drawings-EXT-15.1_FR-CA debarcadaire/embarcadaire in
quai de chargement/dechargement
5249 Arch - Substantial - Signage and Graphics General view Building Signage Not to specification/drawings-EXT-16.0 G1_FR-CA EQUIPEMENT instead of
EQUIPMENT
5250 Arch - Substantial - Signage and Graphics General view Building Signage Not to specification/drawings-INT-1.2 G-C2 Type 01_FR-CA Change 'add
HYDROTHRAPIE' to 'add HYDROTHÉRAPIE'
5251
Arch - Substantial - Signage and Graphics General view Building Signage Not to specification/drawings-INT-1.2 G-C2 Type 01_FR-CA Change '1W-33'
332'
5254 Arch - Substantial - Signage and Graphics General view Building Signage Not to specification/drawings-INT-1.2 G-C2 Type 02_FR-CA STAGING AREA
DE TRANSIT5256 Arch - Substantial - Signage and Graphics General view Building Signage Not to specification/drawings-INT-1.4 G1_FR-CA Trainer is Entraîneur""5257 Arch - Substantial - Signage and Graphics General view Building Signage Not to specification/drawings-INT-1.5 G2 Type 03_FR-CA TRASH = ORDURE
5258 Arch - Substantial - Signage and Graphics General view Building Signage Not to specification/drawings-INT-1.5 G2-C1 Type 02-FR-CA 'Salle d'audiovis
instead of 'salle de conference'
5260 Arch - Substantial - Signage and Graphics General view Building Signage Not to specification/drawings-INT-1.5 G2-C2 Type 01_FR-CA Stockage de
poussettes/fauteuils roulants
5261 Arch - Substantial - Signage and Graphics General view Building Signage Not to specification/drawings-INT-1.5 G2-C2 TYPE 01_FR-CA Placard de l'as
instead of Acsenceur WC
5263
Arch - Substantial - Signage and Graphics General view Building Signage Not to specification/drawings-INT-1.5 G2-C2 TYPE 01_FR-CA Stockage pourcommunautaire instead of Stockage d'equipement de sport de communaute
5264
Arch - Substantial - Signage and Graphics General view Building Signage Not to specification/drawings-INT-1.5 G2-C2 TYPE 01_FR-CA Stockage pourcommunautaire instead of Stockage d'equipement de sport de communaute
5266 Arch - Substantial - Signage and Graphics General view Building Signage Not to specification/drawings-INT-1.5 G2-C2 TYPE 01_FR-CA Stockage de la
club instead of loge du club stockage5267 Arch - Substantial - Signage and Graphics General view Building Signage Not to specification/drawings-INT-3.2 G3_FR-CA SI GES
5268 Arch - Substantial - Signage and Graphics General view Building Signage Not to specification/drawings-INT-4.0 G2_FR-CA change all SIEGES" into "SI
8/20/2019 Stadium deficiencies list
11/15
ID Type Drawing Location Description
PAG HSS SNAGR REPORT
5269 Arch - Substantial - Signage and Graphics General view Building Signage Not to specification/drawings-INT-6.0 G1_FR-CA Change Service Client to Se
clients
5270 Arch - Substantial - Signage and Graphics General view Building Signage Not to specification/drawings-INT-6.2 G3_FR-CA promenade supérieure inste
Promanade5271 Arch - Substantial - Signage and Graphics General view Building Signage Not to specification/drawings-INT-7.0 G1_FR-CA Ascenseur
5273 Arch - Substantial - Signage and Graphics General view Building Signage Not to specification/drawings-INT-7.1 G1_FR-CA Ascenseur 5274 Arch - Substantial - Signage and Graphics General view Building Signage Not to specification/drawings-INT-7.1 G1_FR-CA Salon des joueurs5276 Arch - Substantial - Signage and Graphics General view Building Signage Not to specification/drawings-INT-7.1 G1_FR-CA Stockage de vélos5277 Arch - Substantial - Signage and Graphics General view Building Signage Not to specification/drawings-INT-9.0 G2_FR-CA SORTIE instead of sortie5278 Arch - Substantial - Signage and Graphics General view Building Signage Not to specification/drawings-INT-9.0 G2_FR-CA Vestiaires5279 Arch - Substantial - Signage and Graphics General view Building Signage Not to specification/drawings-INT-10.0 G2_FR-CA Tribune de la presse5281 Arch - Substantial - Signage and Graphics General view Building Signage Not to specification/drawings-INT-10.0 G2_FR-CA promenade5282 Arch - Substantial - Signage and Graphics General view Building Signage Not to specification/drawings-INT-10.0 G2_FR-CA Niveau suite5284 Arch - Substantial - Signage and Graphics General view Building Signage Not to specification/drawings-INT-10.0 G2_FR-CA Niveau suite5285 Arch - Substantial - Signage and Graphics General view Building Signage Not to specification/drawings-INT-10.0 G2_FR-CA Salle du club5286 Arch - Substantial - Signage and Graphics General view Building Signage Not to specification/drawings-INT-10.0 G2_FR-CA Promenade inférieure5287 Arch - Substantial - Signage and Graphics General view Building Signage Not to specification/drawings-INT-10.0 G2_FR-CA salle de presse5288 Arch - Substantial - Signage and Graphics General view Building Signage Not to specification/drawings-INT-10.0 G2_FR-CA Vestiaires d'équipe
5289
Arch - Substantial - Signage and Graphics General view Building Signage Not to specification/drawings-INT-10.0 G2_FR-CA PROMENADE SUPÉRIEU
5292 Arch - Substantial - Signage and Graphics General view Building Signage Not to specification/drawings-INT-12.1 G1_FR-CA Promenade supérieure5293 Arch - Substantial - Signage and Graphics General view Building Signage Not to specification/drawings-INT-12.1 G1_FR-CA Terrain5294 Arch - Substantial - Signage and Graphics General view Building Signage Not to specification/drawings-INT-12.1 G1_FR-CA Quai de chargement5295 Arch - Substantial - Signage and Graphics General view Building Signage Not to specification/drawings-INT 3.0 G2 SIÈGES5296 Arch - Substantial - Signage and Graphics General view Building Signage Not to specification/drawings-INT 12.0 PROMENADE SUP RIEURE5297 Arch - Substantial - Signage and Graphics General view Building Signage Not to specification/drawings-INT 5.0 G1 SI GES5298 Arch - Substantial - Signage and Graphics General view Building Signage Not to specification/drawings-INT 5.1 SI GES
5301 AA - Placeholder for unknowns Site Services Drawing Site Services/Site Services address-PDC report Nov 2014 - Provide consultant Test Certificate for each m
passing the test.
5303 AA - Placeholder for unknowns Site Services Drawing Site Services/Site Services address-PDC Report Nov 2014 - reports of the Television and Photographic
inspections
5306 AA - Placeholder for unknowns A 00101 A3 Athletic trainers
private1W-310/1W-310 address-PDC Report Nov 2014 - Pr ivacy cur ta in between o ff ice and examinat
to be installed
5313
Elec - Substantial - Other A 00107 A3 Broadcast booth
camera
7W -303/7W -303 Not to specif ication/drawings-PDC Report Nov 2014 - Cue lights not observed
5877 Arch - Substantial - Design issues A 00101 B3 Suite 3 washroom 1W-375/1W-375 Design Issue-Area deficiency - Locker numbers
6223 Arch - Substantial - Preformed Metal WallSystem
General view Bui ld ing - General/Building - General Not to specification/drawings-Suspected thermal br idge at Local jo ints on LevEast Elevation
6224 Arch - Substantial - Preformed Metal WallSystem
General view Bui ld ing - General/Bui ld ing - General Not to specif ication/drawings-Suspected thermal bridge at local joints on LeveElevator, North End
8/20/2019 Stadium deficiencies list
12/15
ID Type Drawing Location Description
PAG HSS SNAGR REPORT
6225 Arch - Substantial - Preformed Metal WallSystem
General view Bui ld ing - General/Bui ld ing - General Not to specif ication/drawings-Suspected thermal bridge at local joints on LeveElevation, South end
6226 Arch - Substantial - Preformed Metal WallSystem
General view Bui ld ing - General/Bui ld ing - General Not to specif ication/drawings-Suspected thermal bridge at east Stands, north Tower (north elevation shown)
6227
Arch - Substantial - Preformed Metal Wall
System
General view Bui ld ing - General/Bui ld ing - General Not to specif ication/drawings-Suspected thermal bridge at local joints on Leve
Elevation, North End
6228 Arch - Substantial - Preformed Metal WallSystem
General view Bui ld ing - General/Building - General Not to specif ication/drawings-Suspected thermal bridge at southeast corner osouthwest elevator tower
6234Elec - Substantial - Communications A 00102 A3 Director US
scouting office2W-324/2W-324 Not to speci ficat ion/drawings-P lacement o f data out le ts is unacceptable to ten
6240 AA - Placeholder for unknowns A 00106 A3 spectator
concourse6W-201/6W -201 address-Signage is overlapping. Determine new location/layout
6250Elec - Substantial - Other A 00105 A3 B private suite 12 5W-327/5W-327 Not to specification/drawings-Pot Light (2 relamp)
6255 AA - Placeholder for unknowns A 00107 A3 Broadcast booth
camera7W-303/7W-303 address-Green Screens required in both TV Camera booths
6258 Arch - Substantial - Design issues A 00105 A3 B VIP lobbies 5W-202/5W-202 Design Issue-Head room issue with brace on south wall of elevator lobby. Lev
& 6?
6262 AA - Placeholder for unknowns A 00102 B3 Studio 2W 601 2W-601/2W-601 address-Studio rooms 2W-601, 2W-602, 2W-603 per room data sheet to hav
multilevel and dimmer light switching. Switching requires programming.
6263 AA - Placeholder for unknowns A 00101 A3 Security OperationCenter 1W-207/1W-207 address-Door to exte rio r i s not accessible - threshold too high , width insuf fi cie
6264 AA - Placeholder for unknowns General view Exterior of West Stands address-Grade at entrance approximately 8% from sidewalk. Does this meet
accessibility/OBC?
6265 AA - Placeholder for unknowns General view Building - General/Building - General address-Showers (all Accessible showers): Pressure equalizing / thermostatic
valve lever required (currently it is a spring loaded shower head)
6266 AA - Placeholder for unknowns General view Building - General/Building - General address-Washrooms: Sink pipes should be insulated (even with temp controll
faucet).
6272 AA - Placeholder for unknowns A 00102 C3 Portable
concession2E-204/2E-204 address-concourse, repair concrete curb fracture at one guard post near Grid
/E15 ensure guard still meets structural requirements.
6274 AA - Placeholder for unknowns A 00102 D3 empty 2 2E-20E/2E-20E address-concourse, water pooling away from drains at North accessible platfo
6279 AA - Placeholder for unknowns A 00102 C3 Spectators WR
male2E-301/2E-301 address-2E 301 washroom, install concrete grout between curbs and door f ra
6280
AA - Placeholder for unknowns A 00102 C3 Concessions prepa
area
2E-407/2E-407 address-2E 407/404 Concession and Prep, seal CMU knee joints.
6281 Arch - Substantial - Design issues A 00107 A3 stairs D 7W-400/7W-400 Design Issue-Glazing to be installed between CFL Statistician and Written Pre
6282 AA - Placeholder for unknowns A 00103 C3 PC X 3E-PCX/3E-PCX address-3E Concourse, remove rust stains including along field side curb
6286 AA - Placeholder for unknowns A 00103 D3 stairs 3E-104/3E-104 address-Level 1E stair M remove staining of concrete, including mid landings
apparent paint at movement joint at lowest mid landing
6290 AA - Placeholder for unknowns A 00101 A3 Exercise
STORAGE1W-303/1W -303 address-Level 1W Stair A and south facade, holes in masonry joints
8/20/2019 Stadium deficiencies list
13/15
ID Type Drawing Location Description
PAG HSS SNAGR REPORT
6291 AA - Placeholder for unknowns A 00107 A3 broadcast 7W-602/7W-602 address-PDC Report - Level 6 W, broadcast room, work counter supports are
casework panels6292 A A - Placeholder for unknowns A 00103 A3 PCX 2 3W-PCX2/3W-PCX2 address-Level 3 W exterior, repainting, IMP marks.
6297Elec - Substantial - Other A 00101 B3 Main Electrical
Room1W-703/1W-703 Not to spec if icat ion/drawings-Any miss ing a rc flash hazard labe ls sha ll be inst
indicated in final arc flash study. SVR 017
6300 Elec - Substantial - Other General view Building - General/Building - General Not to specif ication/drawings-SVR 017-Cont ractor to ensure panel schedulestyped.
6301Elec - Substantial - Other A 00105 A3 Private suite 2 5W-303/5W-303 Not to specification/drawings-SVR 017-Circuit labelling is not in the correct for
Suite S3.6311 Elec - Substantial - Other A 00101 D3 LV elec room 1E-604/1E-604 Not to specification/drawings-Lighting control panel wiring ongoing in 1E-604
6368 AA - Placeholder for unknowns A 00106 A3 B universal WC 6W-304/6W-304 address-Accessibility Report 2.13 - 6W-304 Universal Toilet Room is provided
vending machine that is mounted too high and is not cane detectable.
6370 AA - Placeholder for unknowns A 00103 A3 Queue Area 3W-QA/3W-QA address-Accessibility Report 2.17 - Concession stands have protrusions on e
that extend into the path of travel
6373Elec - Substantial - Other A 00107 A3 Broadcast booth
camera7W-303/7W-303 Not to speci ficat ion/drawings-SVR-15 Booths in general: Pot L igh ts have no t b
installed in a straight line
6375Elec - Substantial - Other A 00104 A3 TR 4W-501 Not to specification/drawings-SVR-15 Some panel directories are hand-written
directory shall be neat and type-written
6417Elec - Substantial - Communicat ions A 00101 B3 Telecom area 1W -706/1W -706 Not to specif ication/drawings-SVR-001 1W -706 BIX IDC blocks shall be clear
labelled per specification
6420
Elec - Substantia l - Communications A 00101 B3 Internal MediaProduction
1W-601/1W-601 Not to speci ficat ion/drawings-SVR-001 (1W-601) Empty patch panel pos it ionsclosed. Contractor shall place blank plates where connectors have not been in
6421Elec - Occupancy - Communications A 00101 B3 Internal Media
Production1W -601/1W -601 Not to specif ication/drawings-SVR-001 (1W -601) Cont ractor shall bond groun
common lead on audio cables to patch panel.
6424Elec - Substantia l - Communications A 00101 B3 Internal Media
Production1W-601/1W-601 Not to speci ficat ion/drawings-SVR-001 (1W-601) Cable d rop bends (water fal ls
cable tray shall be provided as per specification.
6425Elec - Substantial - Communicat ions A 00101 B3 Telecom area 1W -707/1W -707 Not to specif ication/drawings-SVR-001 (1W -707) BIX IDC blocks shall be loca
per specification.
6430Elec - Substantia l - Communications A 00101 B3 Uniform laundry
storage1W-702/1W-702 Not to speci ficat ion/drawings-SVR-001 1W 702: Al l opt ical f ib re pa tch pane ls
labeled and unused ports shall be capped.
6431Elec - Substantia l - Communications A 00101 B3 Uniform laundry
storage1W-702/1W-702 Not to speci ficat ion/drawings-SVR-001 1W-702 ; Every copper B IX patch pan
be lablled as per specification
6432
Elec - Substantia l - Communications A 00101 B3 Uniform laundrystorage
1W-702/1W-702 Not to speci ficat ion/drawings-SVR-011 1W-702 : Mul tipa ir cabl ing f rom MER slevel 1, room 1W-700 before travelling to above floors. Contractor shall install
continuously from MER to each TR.
6433
Elec - Substantia l - Communications A 00101 B3 Uniform laundrystorage
1W-702/1W-702 Not to speci ficat ion/drawings-SVR-001 1W-702 ; Mul tipa ir cabl ing f rom MER slevel 1 room 1W702 before travelling to above floors. Contractor shall install ccontinuously from MER to each TR.
6434
Elec - Substantia l - Communications A 00101 B3 Uniform laundrystorage
1W-702/1W-702 Not to speci ficat ion/drawings-SVR-001 1W-702: mul tipa ir cabl ing s tops on levroom &02 before travelling to above floors. Contractor shall install cabling confrom MER to each TR.
8/20/2019 Stadium deficiencies list
14/15
ID Type Drawing Location Description
PAG HSS SNAGR REPORT
6439Elec - Substantial - Communicat ions A 00101 A3 Warm up area 1W -360/1W -360 Not to specif ication/drawings-SVR-001 1W -700; All optical fibre patch panels
labelled and unused ports shall be capped
6441Elec - Substantial - Communicat ions A 00101 A3 Warm up area 1W -361/1W -361 Not to specif ication/drawings-SVR-001 1W -700 : Every copper BIX patch pan
be labelled as per specification
6442
Elec - Substantial - Communicat ions A 00101 A3 W arm up area 1W -360/1W -360 Not to specif ication/drawings-SVR-001 1W -700: Mult ipair cabling f rom MER to
700 and 1W-702 is not OSP. Cabling shall be removed and replaced.
6443
Elec - Substantial - Communicat ions A 00101 A3 Warm up area 1W -360/1W -360 Not to specif ication/drawings-SVR-001 1W -700: Mult ipair cabling from MER slevel one room 1W-700 before travelling to above floors. Contractor shall instacabling continuously from MER to each TR
6444
Elec - Substantial - Communicat ions A 00101 A3 Warm up area 1W -360/1W -360 Not to specif ication/drawings-SVR-001 1W 700: Multipair cabling f rom MER stlevel one room 702 before travelling to above floors. Contractor shall install cacontinuously from MER to each TR.
6451Elec - Substantial - Communications A 00102 B3 TR 2W-705/2W-705 Not to specification/drawings-SVR-001 2W-705 : Every copper BIX patch pan
be labelled per specification
6456Elec - Substantial - Communications A 00102 A3 2W 701 2W-701/2W -701 Not to specification/drawings-SVR-001 2W -701: Every copper BIX patch pane
be labelled per specification
6465Elec - Substantial - Communicat ions A 00103 A3 Spectators WC 3W -300/3W -300 Not to specif ication/drawings-SVR-001 3W -600 : Every copper BIX patch pan
be labelled per specification.
6469Elec - Substantial - Communications A 00104 A3 EL 4W-502/4W-502 Not to specification/drawings-SVR-001 4W-503: Every copper BIX patch pane
be labelled per specification.
6474 Elec - Substantial - Communications A 00104 A3 TR 4W-500 Not to specification/drawings-SVR-001 4W-500: Every copper BIX patch panebe labelled as per specification
6479Elec - Substantial - Communications A 00105 A3 TR 5W-500/5W-500 Not to specification/drawings-SVR-001 5W-500: Every copper BIX patch pane
be labelled as per specification
6482Elec - Substant ia l - Communicat ions A 00105 A3 B cor ridor TR EL 5W-502/5W-502 Not to speci ficat ion/drawings-SVR-001 5W-502: Every copper BIX patch pane
be labelled as per specifications
6486Elec - Substantial - Communications A 00107 A3 TR 7W-603/7W-603 Not to specification/drawings-SVR-003 7W-603: all optical fibre patch panels
labelled and unused ports shall be capped
6488Elec - Substantial - Communications A 00107 A3 TR 7W-603/7W-603 Not to specification/drawings-SVR-003 7W-603: every copper BIX patch pane
labelled as per specifications
6489Elec - Substant ia l - Communicat ions A 00101 C3 Mechan ical room 1E-603/1E-603 Not to speci ficat ion/drawings-SVR-001 1E-602: a ll opt ical f ibre patch panels s
labelled and unused ports shall be capped.
6490
Elec - Substant ia l - Communicat ions A 00101 C3 Mechan ical room 1E-603/1E-603 Not to speci ficat ion/drawings-SVR-001 1E-602: 25th pai r on copper vo ice baccable has not been terminated as per specifications. Terminate 24th and 25th24 of patch panel.
6493Elec - Substantial - Communications A 00101 D3 elevators 1E-606/1E-606 Not to specification/drawings-SVR-001 1E 606: all optical fibre patch panels s
labelled per specification
6494Elec - Substantial - Communications A 00101 D3 elevators 1E-606/1E-606 Not to specification/drawings-SVR-001 1E-606: every copper BIX patch panel
labelled per specifications
6497
Plumb - Substantial - Plumbing Specialties A 00101 B3 Green RMchanging
1W-391/1W-391 Not to speci ficat ion/drawings-M-SVR 21 i tem 28 TMV-1 ( thermostat ic mixing vfor visitors changing/shower rooms 1-W 322 and 323 need to be reviewed fortemperature discharge of 35C/95F .
8/20/2019 Stadium deficiencies list
15/15
ID Type Drawing Location Description
PAG HSS SNAGR REPORT
6501
Fire - Substantial - Sprinkler System A 00105 A3 TR 5W-501/5W-501 Not to specification/drawings-M-SVR 23 Item 71 5W-501 : single upright; SpriEngineer to confirm coverage on either side of beam and distance of head fro
6502
Fire - Substantial - Sprinkler System A 00105 A3 TR 5W-501/5W-501 Not to specification/drawings-M-SVR 23 item 74 5W-501: single upright ; SpriEngineer to confirm coverage on either side of beam and distance of of head
ceiling6503
Plumb - Substantial - Fixtures A 00101 B3 Uniform laundrystorage
1W -503/1W -503 Not to specif ication/drawings-M-SVR 24 Item 75 Uniform Laundry 1W -503 ; pdome strainer at bottom of trench
6506Fire - Substantial - Standpipe and HoseSystem
A 00106 A3 B TR 6W-502/6W-502 Not to specification/drawings-M-SVR 24 item 91 Hang FE unit on wall
6542Mech - Substantial - HVAC Air Filtration A 00101 B3 Main Electrical
Room1W-703/1W-703 Not to speci ficat ion/drawings-M-SVR24 i tem 242 L1 Main E lec. Rooms; AC u
not ductedLOW PRIORITY ITEMS
3509
Ext - Substantial - Landscaping General view Not to specification/drawings-Morrison Hershfield Report #2 Behind the Hostina scissor lift has been driven through the planting bed, all of the disturbed planbe replanted.
5426Ext - Substan tial - Concre te Paving Si te Serv ices Drawing S ite Services/Si te Services Not to spec if icat ion/drawings-Replace 1 pane l o f s idewalk at Gate 3 Spring wo