Upload
others
View
7
Download
0
Embed Size (px)
Citation preview
INVESTITOR:
Elektrotehnička i prometna škola Osijek,
Osijek, Istarska ulica 3
OIB: 34175550062
GRAĐEVINA:
Rekonstrukcija i dogradnja Elektrotehničke i
prometne škole Osijek
LOKACIJA:
Osijek, k.č.br. 5989/2 i 5989/9 k.o. Osijek
IZVEDBENI PROJEKT
STROJARSKI PROJEKT
GRIJANJE, HLAĐENJE I VENTILACIJA
BROJ PROJEKTA:
SP/66-19/IZ
ZOP:
BP-IZV 01/2019
MAPA:
3
GLAVNI PROJEKTANT:
Bogdan Paulik, dipl.ing.arh.
PROJEKTANT:
IVAN TOMIČIĆ, mag.ing.mech.
U Tenji, Listopad 2019. ČLAN UPRAVE:
IVAN TOMIČIĆ, mag.ing.mech.
CALFACTIO j.d.o.o. za projektiranje i inženjering
GRAĐEVINA: Rekonstrukcija i dogradnja Elektrotehničke i prometne škole Osijek
LOKACIJA: Osijek, Istarska ulica 3, k.č.br. 5989/2 i 5989/9 k.o. Osijek
BROJ PROJEKTA: DATUM:
SP/66-19/IZ Listopad 2019.g
2
POPIS MAPA IZVEDBENOG PROJEKTA ZOP: BP-IZV 01/2019
MAPA 1: ARHITEKTONSKI PROJEKT
BP CONSULTING d.o.o. Osijek
PROJEKTANT: Bogdan Paulik, dipl.ing.arh.
MAPA 2: GRAĐEVINSKI PROJEKT – PROJEKT KONSTRUKCIJE
i-KONST j.d.o.o. Višnjevac
PROJEKTANT: Marija Bartolić, mag.ing.aedif.
MAPA 3: STROJARSKI PROJEKT – STROJARSKE INSTALACIJE – GRIJANJE, HLAĐENJE I
VENTILACIJA
CALFACTIO j.d.o.o. Tenja
PROJEKTANT: IVAN TOMIČIĆ, mag.ing.mech.
BROJ UPISA: S1901
CALFACTIO j.d.o.o. za projektiranje i inženjering
GRAĐEVINA: Rekonstrukcija i dogradnja Elektrotehničke i prometne škole Osijek
LOKACIJA: Osijek, Istarska ulica 3, k.č.br. 5989/2 i 5989/9 k.o. Osijek
BROJ PROJEKTA: DATUM:
SP/66-19/IZ Listopad 2019.g
3
SADRŽAJ MAPE
Popis mapa izvedbenog projekta
1. OPĆA DOKUMENTACIJA
1.1 Izvadak iz sudskog registra za tvrtku CALFACTIO j.d.o.o.
1.2 Ugovor o poslovno-tehničkoj suradnji
1.3 Rješenje o imenovanju projektanta
1.4 Rješenje o upisu projektanta u imenik ovlaštenih inženjera
1.5 Izjava projektanta o usklađenosti projekta
1.6 Posebni uvjeti građenja
2. PRIKAZ MJERA ZAŠTITE NA RADU I ZAŠTITE OD POŽARA
3. TEHNIČKI OPIS
4. PRORAČUNI
5. PROGRAM KONTROLE I OSIGURANJA KVALITETE
6. POSEBNI TEHNIČKI UVIJETI GRADNJE I NAČIN ZBRINJAVANJA GRAĐEVNOG OTPADA
7. NACRTI
CALFACTIO j.d.o.o. za projektiranje i inženjering
GRAĐEVINA: Rekonstrukcija i dogradnja Elektrotehničke i prometne škole Osijek
LOKACIJA: Osijek, Istarska ulica 3, k.č.br. 5989/2 i 5989/9 k.o. Osijek
BROJ PROJEKTA: DATUM:
SP/66-19/IZ Listopad 2019.g
4
1. OPĆA DOKUMENTACIJA
GLAVNI PROJEKT: STROJARSKI PROJEKT
INVESTITOR: Elektrotehnička i prometna škola Osijek, Osijek, Istarska ulica 3
GRAĐEVINA: Rekonstrukcija i dogradnja Elektrotehničke i prometne škole Osijek
ADRESA: Osijek, k.č.br. 5989/2 i 5989/9 k.o. Osijek
VRSTA PROJEKTA: STROJARSKI PROJEKTGRIJANJE, HLAĐENJE I VENTILACIJA
PROJEKTANT: Ivan Tomičić, mag.ing.mech.
U Tenji, Listopad 2019.g.
CALFACTIO j.d.o.o. za projektiranje i inženjering
GRAĐEVINA: Rekonstrukcija i dogradnja Elektrotehničke i prometne škole Osijek
LOKACIJA: Osijek, Istarska ulica 3, k.č.br. 5989/2 i 5989/9 k.o. Osijek
BROJ PROJEKTA: DATUM:
SP/66-19/IZ Listopad 2019.g
5
CALFACTIO j.d.o.o. za projektiranje i inženjering
GRAĐEVINA: Rekonstrukcija i dogradnja Elektrotehničke i prometne škole Osijek
LOKACIJA: Osijek, Istarska ulica 3, k.č.br. 5989/2 i 5989/9 k.o. Osijek
BROJ PROJEKTA: DATUM:
SP/66-19/IZ Listopad 2019.g
6
Temeljem Zakona o gradnji Republike Hrvatske (NN RH br. 153/13, 20/17, 39/19) donosim slijedeće
R J E Š E N J E br. SP/66-19/IZ-1
kojim se imenuje IVAN TOMIČIĆ, mag.ing.mech. za
PROJEKTANTA NA IZRADI PROJEKTA
INVESTITOR: Elektrotehnička i prometna škola Osijek, Osijek, Istarska ulica 3
GRAĐEVINA: Rekonstrukcija i dogradnja Elektrotehničke i prometne škole Osijek
ADRESA: Osijek, k.č.br. 5989/2 i 5989/9 k.o. Osijek
VRSTA
PROJEKTA:
IZVEDBENI PROJEKT - STROJARSKI PROJEKT - GRIJANJE, HLAĐENJE I
VENTILACIJA
ZOP: BP-IZV
01/2019 BR- PROJ.: SP/66-19/IZ
Imenovani će izradu kompletne projektne dokumentacije vršiti i voditi prema važećim propisima
za ovu vrstu projekta, vodeći računa o zahtjevima Investitora i nadležnih tijela.
Imenovani ima 13 godina radnog iskustva na poslovima projektiranja, građenja i nadzora nad
izgradnjom građevina, te položen stručni ispit.
Uvjerenje o položenom stručnom ispitu, broj 531-06-2-16-4 od 07.srpnja 2016. godine izdane od
Republika Hrvatska, Ministarstvo graditeljstva i prostornog uređenja i Rješenje o upisu u imenik
ovlaštenih inženjera strojarstva pod red. brojem 1901.
U Tenji, Listopad 2019.g. Član uprave:
Ivan Tomičić, mag.ing.mech.
CALFACTIO j.d.o.o. za projektiranje i inženjering
GRAĐEVINA: Rekonstrukcija i dogradnja Elektrotehničke i prometne škole Osijek
LOKACIJA: Osijek, Istarska ulica 3, k.č.br. 5989/2 i 5989/9 k.o. Osijek
BROJ PROJEKTA: DATUM:
SP/66-19/IZ Listopad 2019.g
7
CALFACTIO j.d.o.o. za projektiranje i inženjering
GRAĐEVINA: Rekonstrukcija i dogradnja Elektrotehničke i prometne škole Osijek
LOKACIJA: Osijek, Istarska ulica 3, k.č.br. 5989/2 i 5989/9 k.o. Osijek
BROJ PROJEKTA: DATUM:
SP/66-19/IZ Listopad 2019.g
8
Na temelju Zakona o gradnji (NN RH br. 153/13, 20/17, 39/19) ) i Pravilnika o obveznom sadržaju i
opremanju projekata građevina (NN 64/14, 41/15, 105/15, 61/16, 20/17) izdaje se:
IZJAVA br. SP/66-19/IZ-2
projektanta o usklađenosti glavnog projekta s prostornim planom, odredbama posebnih zakona i drugih
propisa
INVESTITOR: Elektrotehnička i prometna škola Osijek, Osijek, Istarska ulica 3
GRAĐEVINA: Rekonstrukcija i dogradnja Elektrotehničke i prometne škole Osijek
ADRESA: Osijek, Istarska ulica 3, k.č.br. 5989/2 i 5989/9 k.o. Osijek
VRSTA
PROJEKTA: IZVEDBENI PROJEKT - STROJARSKI PROJEKT
PROJEKTANT: IVAN TOMIČIĆ, mag.ing.mech., Rješenje o upisu u imenik ovlaštenih inženjera
rednim brojem 1901. sa datumom upisa 10. kolovoza 2016. godine
Ovaj GLAVNI projekt usklađen je sa prostornim planovima:
- Prostornim planom Grada Osijeka ("Službeni glasnik" Grada Osijeka broj: 8/05, 5/09, 17A/09-
ispr, 12/10, 12/12 i 20A/18)
- Generalnim urbanističkim planom grada Osijeka ("Službeni glasnik" Grada Osijeka broj: 5/06,
12/06-ispr, 1/07-ispr, 12/10, 12/11, 12/12, 2/13.-ispravak, 4/13. –ispravak, 7/14, 11/15, 5/16-
ispravak, 2/17 i 6A/18-pročišćeni tekst)
te posebnim zakonima, propisima, odnosno posebnim uvjetima:
- Zakon o gradnji (NN 153/13, 20/17, 39/19)
- Zakon o prostornom uređenju (NN RH br. 153/13, 65/17, 39/19)
- Zakon o zaštiti na radu (NN RH br. 71/14, 118/14, 154/14, 94/18, 96/18)
- Zakon o zaštiti od požara RH (NN br. 92/10)
- Zakon o zaštiti od buke (NN 30/09, 55/13, 153/13, 41/16, 114/18)
- Zakon o mjernim jedinicama (NN 145/12)
- Zakon o vodama (NN 153/09, 63/11, 56/13, 14/14) - Zakon o komunalnom gospodarstvu (NN 68/18, 110/18)
- Zakon o održivom gospodarenju otpadom (NN 94/13, 73/17, 14/19)
- Zakon o zaštiti pučanstva od zaraznih bolesti (NN 79/07, 113/08, 43/09, 130/17)
- Zakon o vodi za ljudsku potrošnju (NN 56/13, 64/15, 104/17, 115/18)
- Pravilnik o zaštiti na radu za mjesta rada (NN 29/13)
- Pravilnik o sigurnosnim znakovima (NN 91/15)
- Pravilnik o gospodarenju građevnim otpadom (NN 38/08) - Pravilnik o obveznom sadržaju i opremanju projekata građevina (NN 64/14, 41/15, 105/15, 61/16,
20/17)
- Pravilnik hidrantskoj mreži za gašenje požara (NN 8/06)
- Pravilnik o vatrogasnim aparatima (NN 101/11, 74/13)
- Pravilnik o najviše dopuštenim razinama buke u sredini u kojoj rade i borave ljudi ( NN 145/04)
- Tehnički propis o racionalnoj uporabi energije i toplinskoj zaštiti u zgradama (NN 128/15, 70/18, 13/18, 86/18)
- Pravilnik o kontroli projekta (NN br. 32/14)
- Pravilnik o zaštiti na radu za mjesta rada (NN br. 29/13)
- Pravilnik o tehničkim normativima za zaštitu od statičkog elektriciteta (Sl. 62/73)
- Pravilnik o graničnim vrijednostima emisija otpadnih voda (NN 80/13, 43/14)
CALFACTIO j.d.o.o. za projektiranje i inženjering
GRAĐEVINA: Rekonstrukcija i dogradnja Elektrotehničke i prometne škole Osijek
LOKACIJA: Osijek, Istarska ulica 3, k.č.br. 5989/2 i 5989/9 k.o. Osijek
BROJ PROJEKTA: DATUM:
SP/66-19/IZ Listopad 2019.g
9
- Pravilnik o graničnim vrijednostima izloženosti opasnim tvarima pri radu i o biološkim graničnim vrijednostima (NN 13/09, 75/13)
- Uredba o tvarima koje oštećuju ozonski sloj i fluoriranim stakleničkim plinovima (NN 92/12)
- Tehnički propis o sustavima ventilacije, djelomične klimatizacije i klimatizacije zgrada (NN 3/07)
- Tehnički propis za dimnjake u građevinama (NN 3/07)
- Tehnički propis o sustavima grijanja i hlađenja zgrada (NN 110/08)
- HRN EN 12170:2004 – Sustavi grijanja u građevinama – Postupak pripreme dokumenata za rad, održavanje i uporabu – Sustavi grijanja koji zahtijevaju obučenog rukovatelja
- HRN EN 12171:2004 – Sustavi grijanja u građevinama – Postupak pripreme dokumenata za rad, održavanje i uporabu – Sustavi grijanja koji zahtijevaju obučenog rukovatelja
- HRN EN 14336:2005 – Sustavi grijanja u građevinama – Ugradnja i preuzimanje sustava toplovodnog grijanja
- HRN EN 378-2:2012 – Rashladni sustavi i dizalice topline – Sigurnosni i ekološki zahtjevi – 2. dio: Projektiranje, izvedba, ispitivanje, označivanje i dokumentacija
- HRN EN 378-3:2012 – Rashladni sustavi i dizalice topline – Sigurnosni i ekološki zahtjevi – 3. dio: Mjesto instalacije i osobna zaštita
- HRN EN 378-4:2012 – Rashladni sustavi i dizalice topline – Sigurnosni i ekološki zahtjevi – 4. dio: Postupanje, održavanje, popravak i oporaba
- EN 15316-1 Sustavi grijanja u zgradama – Metoda proračuna energijskih zahtjeva i učinkovitosti sustava – 1. dio: Općenito
- EN 15316-2-1 Sustavi grijanja u građevinama – Metoda proračuna energijskih zahtjeva i učinkovitosti sustava – 2-1. dio: Sustavi za grijanje prostora zračenjem topline
- EN 15316-2-3 Sustavi grijanja u zgradama – Metoda proračuna energijskih zahtjeva i učinkovitosti sustava – 2-3. dio: Razvodi sustava grijanja prostora
- EN 15316-4-1 Sustavi grijanja u zgradama – Metoda proračuna energijskih zahtjeva i učinkovitosti sustava – 4-1. dio: Sustavi za proizvodnju topline izgaranjem (kotlovi)
- EN 15316-4-5 Sustavi grijanja u zgradama – Metoda proračuna energijskih zahtjeva i učinkovitosti sustava – 4-5. dio: Sustavi za proizvodnju topline za grijanje prostora, pokazatelji i kvaliteta daljinskog grijanja i sustava velikih volumena
- EN 15316-3-1 Sustavi grijanja u zgradama – Metoda proračuna energijskih zahtjeva i učinkovitosti sustava – 3-1. dio: Sustavi za pripremu potrošne tople vode, pokazatelji potreba prema izljevnome mjestu
- EN 15316-3-2 Sustavi grijanja u zgradama – Metoda proračuna energijskih zahtjeva i učinkovitosti sustava – 3-2. dio: Sustavi za pripremu potrošne tople vode, razvod
- EN 15316-3-3 Sustavi grijanja u zgradama – Metoda proračuna energijskih zahtjeva i učinkovitosti sustava – 3-3. dio: Sustavi za pripremu potrošne tople vode, zagrijavanje
- HRN EN 15241 Ventilacija u zgradama -- Metode proračuna energijskih gubitaka zbog ventilacije i infiltracije u poslovnim zgradama
- HRN EN 12831 Sustavi grijanja u građevinama – Postupak proračuna normiranoga toplinskog opterećenja
- HRN EN 13790:2008 – Energijska svojstva zgrada – Proračun potrebne energije za grijanje i hlađenje prostora
- HRN EN ISO 13789 Toplinske značajke zgrada – Koeficijent transmisijskih prijenosnih toplinskih gubitaka – Metoda proračuna
- HRN EN 12828:2013 – Sustavi grijanja u zgradama – Izvedba sustava toplovodnog grijanja
- HRN EN 12098-1 Regulacija sustava grijanja – 1 dio: Uređaji za kontrolu sustava toplovodnog grijanja s kompenzacijom prema vanjskoj temperaturi
- HRN EN 12098- 2 Regulacija sustava grijanja – 1 dio: Uređaji za optimalnu kontrolu uključivanja toplovodnog grijanja
- HRN EN ISO 16484-1 Sustavi kontrole zgrade – 1 dio: Pregled i definicije
- HRN EN ISO 16484 -2 Sustavi kontrole i automatizacije zgrade (GVK)– 2 dio: Oprema za kontrolni sustav
- HRN EN 1297 Ventilacija zgrada – zračni kanali – zahtjevi za sustav zračnih kanala i sastavnih dijelova da bi se osiguralo održavanje kanalskog sustava
- HRN EN 13456 Ventilacija zgrada – postupci proračuna za određivanje provjetravanja u stambenim zgradama
- HRN EN 13779 Ventilacija u nestambenim zgradama- zahtjevi za sustave ventilacije i klimatizacije
- HRN EN 12599 Ventilacija u zgradama- ispitni postupci i mjerne metode za primopredaju izvedenih sustava ventilacije i klimatizacije
- HRN EN 14134 Ventilacija u zgradama- ispitivanje značajki i provjera instalacije za stambene ventilacijske sustave
CALFACTIO j.d.o.o. za projektiranje i inženjering
GRAĐEVINA: Rekonstrukcija i dogradnja Elektrotehničke i prometne škole Osijek
LOKACIJA: Osijek, Istarska ulica 3, k.č.br. 5989/2 i 5989/9 k.o. Osijek
BROJ PROJEKTA: DATUM:
SP/66-19/IZ Listopad 2019.g
10
- Pravilnik o kontroli projekta (NN br. 32/14)
- Pravilnik o zaštiti na radu za mjesta rada (NN br. 29/13)
- Pravilnik o tehničkim normativima za zaštitu od statičkog elektriciteta (Sl. 62/73)
- Pravilnik o graničnim vrijednostima emisija otpadnih voda (NN 80/13, 43/14)
- Pravilnik o tehničkim zahtjevima za građevine odvodnje otpadnih voda, kao i rokovima obvezne kontrole ispravnosti građevina odvodnje i pročišćavanja otpadnih voda (NN 3/11)
- Norma HRN EN 806-2 Specifikacija za instalacije u zgradama za dovod vode za ljudsku uporabu – 2. Dio: Projektiranje (EN 806-2:2005)
- Norma HRN EN 806-3 Specifikacija za instalacije unutar zgrada za dovod vode za ljudsku uporabu – 3. Dio: Određivanje veličine cijevi – Pojednostavljena metoda (EN 806-3:2006)
- Posebni uvjeti građenja broj: G000032/6617/19TG – HEP-Toplinarstvo – Pogon Osijek, 12.08.2019.
U Tenji, Listopad 2019.g.
Projektant:
Ivan Tomičić, mag.ing.mech.
Član uprave:
Ivan Tomičić, mag.ing.mech.
CALFACTIO j.d.o.o. za projektiranje i inženjering
GRAĐEVINA: Rekonstrukcija i dogradnja Elektrotehničke i prometne škole Osijek
LOKACIJA: Osijek, Istarska ulica 3, k.č.br. 5989/2 i 5989/9 k.o. Osijek
BROJ PROJEKTA: DATUM:
SP/66-19/IZ Listopad 2019.g
11
CALFACTIO j.d.o.o. za projektiranje i inženjering
GRAĐEVINA: Rekonstrukcija i dogradnja Elektrotehničke i prometne škole Osijek
LOKACIJA: Osijek, Istarska ulica 3, k.č.br. 5989/2 i 5989/9 k.o. Osijek
BROJ PROJEKTA: DATUM:
SP/66-19/IZ Listopad 2019.g
12
Temeljem članka Zakona o zaštiti na radu RH (N.N. br. 71/14, 118/14, 154/14, 94/18, 96/18), a
nakon pregleda tehničke dokumentacije izdaje se
IZJAVA br. SP/66-19/IZ-ZNR
GLAVNI PROJEKT: STROJARSKI PROJEKT - GRIJANJE, HLAĐENJE I VENTILACIJA
INVESTITOR: Elektrotehnička i prometna škola Osijek, Osijek, Istarska ulica 3
GRAĐEVINA: Rekonstrukcija i dogradnja Elektrotehničke i prometne škole Osijek
ADRESA: Osijek, Istarska ulica 3, k.č.br. 5989/2 i 5989/9 k.o. Osijek
Potvrđuje se da je ovaj projekt sadrži sva tehnička rješenja za primjenu propisanih i priznatih
pravila zaštite na radu kojima projektirano sredstvo rada odnosno građevina mora udovoljavati za sve
vrijeme svoje upotrebe u skladu sa Zakonom o zaštiti na radu (NN RH br. 71/14, 118/14, 154/14, 94/18,
96/18).
U Tenji, Listopad 2019.g.
Projektant:
Ivan Tomičić, mag.ing.mech.
Član uprave:
Ivan Tomičić, mag.ing.mech.
CALFACTIO j.d.o.o. za projektiranje i inženjering
GRAĐEVINA: Rekonstrukcija i dogradnja Elektrotehničke i prometne škole Osijek
LOKACIJA: Osijek, Istarska ulica 3, k.č.br. 5989/2 i 5989/9 k.o. Osijek
BROJ PROJEKTA: DATUM:
SP/66-19/IZ Listopad 2019.g
13
Temeljem članka 14. stavak 3. Zakona o zaštiti od požara RH (N.N. br. 92/10), a nakon pregleda
tehničke dokumentacije izdaje se
ISPRAVA br. SP/66-19/IZ-ZP
GLAVNI PROJEKT: STROJARSKI PROJEKT
INVESTITOR: Elektrotehnička i prometna škola Osijek, Osijek, Istarska ulica 3
GRAĐEVINA: Rekonstrukcija i dogradnja Elektrotehničke i prometne škole Osijek
ADRESA: Osijek, Istarska ulica 3, k.č.br. 5989/2 i 5989/9 k.o. Osijek
Potvrđuje se da je ovaj projekt sadrži sva tehnička rješenja za primjenu mjera zaštite od požara,
primijenjena u glavnom projektu sukladno Zakonu o zaštiti od požara (NN RH br. 92/10).
U Tenji, Listopad 2019.g.
Projektant:
Ivan Tomičić, mag.ing.mech.
Član uprave:
Ivan Tomičić, mag.ing.mech.
CALFACTIO j.d.o.o. za projektiranje i inženjering
GRAĐEVINA: Rekonstrukcija i dogradnja Elektrotehničke i prometne škole Osijek
LOKACIJA: Osijek, Istarska ulica 3, k.č.br. 5989/2 i 5989/9 k.o. Osijek
BROJ PROJEKTA: DATUM:
SP/66-19/IZ Listopad 2019.g
14
2. PRIKAZ MJERA ZAŠTITE NA RADU I ZAŠTITE OD POŽARA
3.1. PRIKAZ TEHNIČKIH RJEŠENJA ZA PRIMJENU PRAVILA ZAŠTITE NA RADU
PRIMJENJENI PROPISI I STANDARDI
• Zakon o gradnji (NN 153/13, 20/17, 39/19)
• Zakon o zaštiti na radu (NN 74/14, 118/14, 154/14, 94/18, 96/18),
• Zakon o zaštiti od požara ( NN 92/10),
• Zakon o zaštiti od buke ( NN 30/09, 55/13, 153/13, 41/16, 114/18),
• Zakon o normizaciji ( NN 80/13),
• Zakon o mjeriteljstvu (NN 74/14),
• Zakon o hrani ( NN 81/13, 14/14),
• Zakon o vodi za ljudsku potrošnju (NN 56/13).
• Zakon o vodama (NN 63/11, 130/11,56/13, 14/14)
• Zakon o zaštiti okoliša ( NN 80/13, 153/13, 78/15, 12/18, 118/18)
• Pravilnik o zaštiti na radu za mjesta rada (NN 23/13)
• Pravilnik o najviše dopuštenim razinama buke u sredini u kojoj ljudi rade i borave ( NN 145/04),
• Pravilnik o graničnim vrijednostima emisija otpadnih voda (NN 80/13, 43/14, 27/15, 3/16)
• Pravilnik o sigurnosnim znakovima (NN 91/15, 102/15, 61/16)
• Norma HRN EN 806-2 Specifikacija za instalacije u zgradama za dovod vode za ljudsku uporabu – 2. Dio: Projektiranje (EN 806-2:2005)
• Norma HRN EN 806-3 Specifikacija za instalacije unutar zgrada za dovod vode za ljudsku uporabu – 3. Dio: Određivanje veličine cijevi – Pojednostavljena metoda (EN 806-3:2006)
• Norma HRN EN 752 Odvodni i kanalizacijski sustavi izvan zgrada (EN 752:2008)
• Norma HRN EN 1610:1997 Ispitivanje i polaganje kanalizacijskih cjevovoda i kanala
• Norma HRN/DIN 18910/74
• Norma HRN/DIN 8061; DIN 8062; DIN 8063
• Norma HRN/ISO 7/1
3.1.1. TEHNIČKI OPIS INSTALACIJE
Instalacija grijanja, hlađenja i ventilacije:
a) Grijanje Grijanje objekta predviđeno je centralno putem ventilokonvektora i radijatora (u kupaonicama i toaletima). Ventilokonvektori su namijenjeni za rad s optočni zrakom. Građevina se priključuje na sustav daljinskog grijanja TE-TO Osijek ugradnjom Indirektne toplinske podstanice tipa KOMPAKT K-250. Dvocijevni razvod grijanja se vodi u zidovima, podovima i spuštenim stropovima. Razvod se izvodi iz kompozitnih polipropilenskih cijevi ojačanih staklenim vlaknima.
b) Hlađenje Za potrebe hlađenja u zelenoj površini na predmetnoj parceli ugradit će se reverzibilna visokoučinkovita zrak-voda dizalica topline (niskotemperaturna). Rashladna tijela su isti ventilokonvektori koji služe i za grijanje u zimskom periodu.
c) Ventilacija Za potrebe ventiliranja prostora učionica u svaku učionicu se ugrađuje ventilacijska jedinica sa povratom topline (rekuperacijom). Ventilacijske jedinice se ugrađuju u prostoru spuštenog stropa, isto tako i kanalski razvod do stropnih vrtložnih distributera. Svježi zrak se dovodi kanalom sa usisa na fasadi, i istrošeni zrak otpadni zrak se odvodi kanalom sa ispustom na fasadi. U kupaonicama i
CALFACTIO j.d.o.o. za projektiranje i inženjering
GRAĐEVINA: Rekonstrukcija i dogradnja Elektrotehničke i prometne škole Osijek
LOKACIJA: Osijek, Istarska ulica 3, k.č.br. 5989/2 i 5989/9 k.o. Osijek
BROJ PROJEKTA: DATUM:
SP/66-19/IZ Listopad 2019.g
15
toaletima se ugrađuju odsisni ventilatori kapaciteta da se zadovolji potreban broj izmjena zraka prema posebnim propisima.
Ostale prostorije se ventiliraju prirodnim putem otvaranjem prozora i vrata.
3.1.2. OPIS OPASNOSTI
3.1.2.1. Mehaničke opasnosti
Opasnosti koje nastaju pri polaganju cjevovoda su:
- padovi radnika u dubinu, - zatrpavanja,
- pad predmeta na radnika,
- udar radnika,
Zaštita na radu od ovih opasnosti provodi primjenom osnovnih pravila zaštite na radu kojima se uklanja ili smanjuje opasnost na sredstvima rada (čl. 9, stavak 2. Zakona zaštite na radu).
3.1.2.2. Opasnost od statički elektriciteta i groma Gromobranska instalacija mora biti vezana na zajednički sustav uzemljenja i izvedena sukladno propisima o gromobranima.
- Radi sprječavanja skupljanja statičkog elektriciteta prilikom rada, svi stabilni i pokretni dijelovi strojeva i uređaja moraju biti vezani u galvansku cjelinu, koja je propisno uzemljena.
- Zaštitu od strujnog udara potrebno je izvesti uzemljenjem opreme i premošćenjem svih spojeva na cijevnoj mreži s kojima se dolazi u kontakt.
OPASNO PO ŽIVOT je gasiti elektro opremu vodom i na to treba posebno upoznati zaposlene. U slučaju požara potrebno je isključiti predmetnu građevinu iz napona električne mreže, a požar na elektro opremi gasiti aparatima za početno gašenje vatre sa CO2.
3.1.2.3. Opasnost od požara i eksplozije (mogućnost nastajanja zapaljive i eksplozivne smjese) Za objekt srednje škole izrađen je sustav za vatrodojavu požara, a osigurano je dovoljno aparata za gašenje požara suhim prahom. Objekt ima svoju unutarnju hidrantsku mrežu, a priključak je na sustav javne vodoopskrbe Grada Osijeka. Ukupno je instalirano osam unutarnjih hidrantskih ormarića.
Ukupan broj i raspored vatrogasnih aparata tip S-9 ili drugog odgovarajućeg tipa, je prikazano u planu gašenja požara.
3.1.2.4. Opasnost od buke U objektu srednje škole buka nema opasnosti od prekomjerne buke od strane instalacije grijanja, hlađenja i ventilacije. Sav unutarnji razvod razvoda grijanja/hlađenja i kanalski razvod ventilacije je projektiran tako da brzina u cijevima ne prelazi 2 m/s čime su šumovi u cijevnom razvodu smanjeni na najmanju moguću mjeru. Sav razvod se vodi u zidu, podu, spuštenom stropu ili instalacijskim kanalima, toplinski i zvučno izolirani.
Vanjska jedinica dizalica topline je smještena na dovoljnoj udaljenosti od predmetnog i postojećih objekata, te na taj način nema prekomjerne vanjske buke.
Odabrane ventilacijske jedinice s povratom topline, imaju nisku razinu buke.
3.1.2.5. Toplinske opasnosti Predviđeni cijevni razvod se propisno izolira paroneprospusnom toplinskom izolacijom.
3.1.2.6. Nestručno rukovanje opremom
CALFACTIO j.d.o.o. za projektiranje i inženjering
GRAĐEVINA: Rekonstrukcija i dogradnja Elektrotehničke i prometne škole Osijek
LOKACIJA: Osijek, Istarska ulica 3, k.č.br. 5989/2 i 5989/9 k.o. Osijek
BROJ PROJEKTA: DATUM:
SP/66-19/IZ Listopad 2019.g
16
U objektu srednje škole u strojarnici u kojoj je smještena oprema instalacija vodovoda, kanalizacije te grijanja i hlađenja mogu ući samo ovlaštene obučene osobe. Na zidovima moraju biti upute za rukovanje opremom i uređajima.
3.1.3. NATPISI NA MJESTU RADA Na mjestu rada se moraju nalaziti ovi dobro čitljivi i lako uočljivi znakovi opasnosti, obveza, zabrana i uputa za siguran. Sve instalacije se moraju biti propisno obilježiti. Na ulazu u radne prostorije i u radnim prostorima obvezno je postaviti oznake zabrana a koji se postavljaju:
Na dvorištu i objektu hladnjače postaviti će se uočljivi natpisi i znakovi zabrane pušenja i korištenja otvorene vatre, te uočljivi prometni znakovi prema projektom utvrđenoj organizaciji prometa.
Na vanjskim vratima dijela objekta tehničke sobe će se postaviti uočljivi natpisi i znakovi opasnosti.
Na svim cjevovodima za identifikaciju grupe tvari (medija) koji prolaze kroz cjevovod postaviti će se uočljivi znakovi strelice.
Plin voda vruća voda (para)
Na dvorištu postaviti će se i druga projektirana oprema za gašenje požara kao:
- unutarnji hidrantski oramrići,
- aparati za gašenje požara za klasu požara A, B i C I dr.
Oznake koje se postavljaju uz evakuacijske putove i na elementima izlaza biti će u skladu sa smjernicama EU (EEZ 58/92), Pravilnikom o sigurnosnim znakovima te uz njega vezanu normu HNR 7010 (grafički simboli-sigurnosne boje i znakovi sigurnosti) i HRN Z.SO.005 (obavijesni znakovi koji se odnose na zaštitu i spašavanje).
CALFACTIO j.d.o.o. za projektiranje i inženjering
GRAĐEVINA: Rekonstrukcija i dogradnja Elektrotehničke i prometne škole Osijek
LOKACIJA: Osijek, Istarska ulica 3, k.č.br. 5989/2 i 5989/9 k.o. Osijek
BROJ PROJEKTA: DATUM:
SP/66-19/IZ Listopad 2019.g
17
3.1.4. MJERE SIGURNOSTI KOD GRADNJE
Tijekom gradnje treba se pridržavati slijedećih mjera:
1. Gradilište mora biti osigurano od pristupa osoba koje nisu tamo zaposlene.
2. Gradilište mora biti vidljivo označeno. Opasna mjesta moraju biti posebno označena i osigurana.
3. Svi prelazi viši od 1.0 m moraju imati ogradu.
4. Potrebno je provesti osiguranje od udara električnom energijom. Svi alati i strojevi moraju imati zakonom propisanu zaštitu.
5. U toku gradnje potrebno je osigurati redovan stručni nadzor nad izvođačem te osigurati primjenu svih propisa u građevinarstvu.
6. Za ispravnu izvedbu instalacije grijanja, hlađenja i ventilacije treba tijekom gradnje obavezno kontrolirati kvalitetu ugrađenih materijala i atestima dokazati njihovu valjanost i kvalitetu prema HRN za dotičan materijal koji je ugrađen. Nužno je paziti da se cijevi prilikom montaže ne oštete.
7. Na gradilištu je potrebno osigurati uvjete osobne higijene, osobnih zaštitnih sredstava, te smještaj, prehranu i prijevoz radnika.
8. Na gradilištu moraju biti osigurana sredstva za pružanje neposredne prve pomoći.
9. Za provedbu ovih zaštitnih mjera nadležna je i odgovorna uprava gradilišta.
Provjeru provedbe ovih zaštitnih mjera provodi rukovoditelj gradilišta, nadzorni inženjer, te ovlašteno tijelo Grada.
3.2. PRIKAZ TEHNIČKIH RJEŠENJA ZA PRIMJENU PRAVILA ZAŠTITE OD POŽARA
PRIMIJENJENI PROPISI I STANDARDI
• Zakon o gradnji (NN 153/13, 20/17, 39/19)
• Zakon o zaštiti od požara ( NN 92/10)
• Pravilnik o sigurnosnim znakovima (NN 91/15, 102/15, 61/16)
• Pravilnik o hidrantskoj mreži za gašenje požara (NN 8/06)
• Pravilnik o vatrogasnim aparatima ( NN 101/11, 74/13)
• Tehnički propis za niskonaponske električne instalacije (NN 5/10),
• HRN 7010 – Grafički simboli- sigurnosni znakovi za mjesta rada i javne prostore - PEHD vodovodne cijevi HRN EN 12201-1:2003 - PVC-cijevi za kanalizaciju HRN EN 1401 Zakon o zaštiti od požara Pravilnik o razvrstavanju građevina u skupine po zahtjevnosti mjera zaštite od požara (NN 56/12) Pravilnik o otpornosti na požar i drugim zahtjevima koje građevine moraju zadovoljiti u slučaju požara (NN 29/13, 87/15) Pravilnik o sustavima za dojavu požara (NN 56/99) Pravilnik o uvjetima za vatrogasne pristupe (NN 35/94, 55/94, 142/03) Pravilnik o zaštiti od požara u skladištima (NN 93/08) Pravilnik o mjerama zaštite od požara kod građenja (NN 141/11)
CALFACTIO j.d.o.o. za projektiranje i inženjering
GRAĐEVINA: Rekonstrukcija i dogradnja Elektrotehničke i prometne škole Osijek
LOKACIJA: Osijek, Istarska ulica 3, k.č.br. 5989/2 i 5989/9 k.o. Osijek
BROJ PROJEKTA: DATUM:
SP/66-19/IZ Listopad 2019.g
18
3.2.2. TEHNIČKI OPIS INSTALACIJE
Isto kao u prethodnom poglavlju
3.2.3. OPASNOST OD POŽARA Kao izvori opasnosti od požara mogu biti:
- prateća električna instalacija, - elektromotorni uređaji, - visoke temperatura i prijenos vatre,
3.2.4. PRIKAZ OPASNOSTI I MJERE ZAŠTITE
3.2.4.1. Opće odredbe
• Osposobljavanje djelatnika za rad na siguran način i upoznavanje s mjerama za sprečavanje nastanka i širenja požara i eksplozije, te postupcima za gašenje na njihovim radnim mjestima obavlja se prije zaposlenja prema uputama za siguran rad i postupke u slučaju požara.
• Teorijsko i praktično osposobljavanje djelatnika, kao i obveznu godišnju provjeru osposobljenosti mogu obavljati osobe koje imaju posebne ovlasti i odgovornosti u stručnim službama korisnika ili tvrtke za to ovlaštene,
• O osposobljenosti i godišnjoj provjeri osposobljenosti vodi se dokumentacija iz koje je vidljivo tko je, kada, i kako i prema kojim uputama za rad na siguran rad i postupanje u slučaju požara obavio osposobljavanje i godišnju provjeru osposobljenosti.
• Održavanje i nadziranje ispravnosti strojeva i uređaja obavlja se na način i u vremenskim razmacima određenim propisom, odnosno uputom proizvođača, o čemu mora postojati dokumentacija.
• Održavanje i nadziranje ispravnosti postrojenja mogu obavljati samo osposobljene osobe.
3.2.4.2. Mjere zaštite od požara i eksplozije
U školskim prostorijama i prostorima opasnosti zabranjeno je:
1. pušenje i korištenje otvorene vatre u bilo kom obliku,
2. držanje oksidirajućih, reaktivnih i samozapaljivih tvari,
3. odlaganje zapaljivih i drugih tvari koje nisu namijenjene tehnološkom procesu,
4. pristup vozilima koja pri radu svog pogonskog uređaja mogu iskriti,
5. uporaba električnih uređaja koji nemaju protueksplozijsku zaštitu,
6. nošenje odjeće i obuće koja se može nabiti statičkim elektricitetom i uporaba uređaja i opreme koji nisu propisno zaštićeni od statičkog elektriciteta.
7. zabranjeno je skladištenje zapaljivih tekućina u dijelovima građevine koja nisu namijenjena za skladištenje zapaljivih tekućina.
3.2.4.3. Opasnost od statičkog elektriciteta i groma
- Gromobranska instalacija mora biti vezana na zajednički sustav uzemljenja i izvedena sukladno propisima o gromobranima.
- Radi sprječavanja skupljanja statičkog elektriciteta prilikom rada, svi stabilni i pokretni dijelovi strojeva moraju biti vezani u galvansku cjelinu, koja je propisno uzemljena.
CALFACTIO j.d.o.o. za projektiranje i inženjering
GRAĐEVINA: Rekonstrukcija i dogradnja Elektrotehničke i prometne škole Osijek
LOKACIJA: Osijek, Istarska ulica 3, k.č.br. 5989/2 i 5989/9 k.o. Osijek
BROJ PROJEKTA: DATUM:
SP/66-19/IZ Listopad 2019.g
19
3.2.4.4. Opasnost od požara i eksplozije (mogućnost nastajanja zapaljive i eksplozivne smjese)
Za cijeli objekt izrađen je sustav za zaštitu od požara. Za navedeno osigurano je dovoljno aparata za gašenje požara suhim prahom.
Objekt ima aparate za gašenje požara, sustav za dojavu požara, a koristiti će sustav unutarnje hidrantske mreže objekta te sustav ulične hidrantske mreže.
Ukupan broj i raspored vatrogasnih aparata tip S-9 ili drugog odgovarajućeg tipa, je prikazano u planu gašenja požara.
Pored obavljanja pregleda vatrogasne opreme u propisanim rokovima, vatrogasna oprema mora se svakodnevno i vizualno nadzirati.
3.2.4.5. Natpisi na mjestu rada Na mjestu rada se moraju nalaziti ovi dobro čitljivi i lako uočljivi znakovi opasnosti, obveza, zabrana i uputa za siguran, a koji se postavljaju na ulazu u radne prostorije strojarnice i u radnim prostorima strojarnice.
Na vanjskim vratima strojarnice će se postaviti uočljivi natpisi i znakovi opasnosti.
3.2.5. PRIKAZ TEHNIČKIH RJEŠENJA ZA PRIMJENU PRAVILA ZAŠTITE OD POŽARA
Dio instalacije koji je goriv ( plastične cijevi, brtvila i izolacija ) ukopan je u zemlju ili se vodi u podu i zidu i kao takav ne može biti uzročnikom niti prijenosnikom požara.
- Elektromotorni uređaji izvedeni su u propisanoj zaštiti za tu vrstu instalacije, kao i prateća električna
instalacija.
- Kao protupožarna mjera predviđeno je postavljanje protupožarnih aparata za cjelokupni objekt:
S-9, 9 kg, ……..16 kom
CO2 , 5 kg ……… 1 kom
- Isto tako se ugrađuje unutarnja hidrantska mreža sa zidnim hidrantima sukladno normi HRN EN 671-1 ili HRN EN 671-2. Zidni hidranti su obojeni crvenom bojom na kojoj se nalazi oznaka iz koje je jasno vidljivo da se u ormariću nalazi oprema hidrantske mreže za gašenje požara. Smatrat će se da je ovom zahtjevu udovoljeno ako se ormarić označi simbolom prema normi HRN ISO 6309. Najniži tlak na mlaznici kod minimalne protočne količine od 25 L/min ne smije biti manji od 2,5 bara.
CALFACTIO j.d.o.o. za projektiranje i inženjering
GRAĐEVINA: Rekonstrukcija i dogradnja Elektrotehničke i prometne škole Osijek
LOKACIJA: Osijek, Istarska ulica 3, k.č.br. 5989/2 i 5989/9 k.o. Osijek
BROJ PROJEKTA: DATUM:
SP/66-19/IZ Listopad 2019.g
20
Hidrantska mreža je izvedena na takav način da se ostvari potpuno prekrivanje prostora koji se štiti najmanje s jednim mlazom vode s tim da se na dužinu cijevi od 15 m s mlaznicom dodaje dužina mlaza od najviše 5 m. Unutarnja hidrantska mreža za gašenje požara projektirana je na način da je pokriven prostor koji se štiti jednim mlazom vode. Minimalna dužina crijeva za gašenje za unutarnje hidrante ne smije biti manja od 15,0 m.
- Ukupan broj unutarnjih zidnih hidranata je 8 kom.
- Osigurana je efikasna prirodna i prisilna ventilacija
- Pod je armirani beton sa završnom oblogom iz keramike, a zidovi od blok opeke, ožbukani.
- U objektu na vidnim mjestima istaknuti znak « ZABRANJENO PUŠENJE «
- Zaposleno osoblje mora poznavati osnovne propise i mjere zaštite od požara i savjesno ih provoditi.
- Obvezna je redovita kontrola opreme i instalacija prema uputstvu za održavanje.
3.3. MJERE SIGURNOSTI KOD GRADNJE
U fazi izvođenja radova na izgradnji predmetne građevine svi izvođači dužni su se pridržavati odredbi
Pravilnika o mjerama zaštite od požara kod građenja (NN 141/11). Ovim Pravilnikom definirane su mjere
zaštite od požara koje treba poduze ti na gradilištu tijekom građenja, kako bi se požarni rizik ograničio na
prihvatljivu mjeru, te omogućila učinkovita intervencija vatrogasaca uz njihovu zaštitu.
Osim dokumentacije propisane posebnim propisom iz područja gradnje, izvođač na gradilištu mora imati i
Elaborat zaštite od požara koji je poslužio kao podloga za izradu glavnog projekta građevine, a sukladno
odredbama čl.1. citiranog Pravilnika.
Mjere zaštite od požara na gradilištu moraju se provoditi kontinuirano dok god gradilište postoji , a sukladno
odredbama čl. 3. citiranog Pravilnika.
Odgovorna osoba za provođenje mjera zaštite od požara na gradilištu je izvođač radova, a ukoliko kod
građenja sudjeluje više izvođača, odgovorna osoba za provođenje mjera zaštite od požara je glavni izvođač
radova, a sukladno odredbama čl. 7. citiranog Pravilnika.
Ukoliko se na gradilištu predmetne građevine tijekom gradnje budu koristile tehnologije visokog požarnog
rizika, ili će biti otežani uvjeti gašenja i spašavanja, potrebno je provesti dodatne mjere zaštite od požara, a
sukladno prethodno izrađenoj prosudbi privremeno povećanog požarnog rizika, a sukladno odredbama čl. 8.
citiranog Pravilnika.
Ovisno o vrsti radova koji se u pojedinim fazama građenja izvode na gradilištu, na odgovarajući način je
potrebno primijeniti propise koji uređuju pojedina područja, a sukladno odredbama čl. 9. citiranog
Pravilnika.
Najčešća mjesta i radnje potencijalno opasne za nastanak i širenje požara na gradilištima su:
• mjesta držanja odnosno skladištenja zapaljivih i/ili eksplozivnih tvari,
• skladišta plinskih boca,
• prostor za uporabu sredstava za čišćenje i raznih otapala,
• deponij građevinskog otpada,
• ambalažni materijali,
• uređaji, oprema i instalacije koje mogu prouzročiti nastajanje i širenje požara (peći za grijanje, plinski i
električni uređaji, privremena instalacija rasvjete i dr.)
• uporaba ljepila i obrada,
• uporaba otvorenog plamena ili žara pri radu (vrenje ljepenke, skidanje uljnog naliča, pušenje i slično),
• uporaba uređaja i alata koji iskre,
• spaljivanje raznog materijala,
• rušenja i demontaže,
• puštanje u rad pojedinih instalacija (plina, struje).
CALFACTIO j.d.o.o. za projektiranje i inženjering
GRAĐEVINA: Rekonstrukcija i dogradnja Elektrotehničke i prometne škole Osijek
LOKACIJA: Osijek, Istarska ulica 3, k.č.br. 5989/2 i 5989/9 k.o. Osijek
BROJ PROJEKTA: DATUM:
SP/66-19/IZ Listopad 2019.g
21
Kako bi se spriječilo nastajanje i širenje požara na gradilištu i osiguralo njegovo učinkovito gašenje potrebno
je planirati i provoditi odgovarajuće organizacijske i tehničke mjere na gradilištu, za vrijeme i izvan radnog
vremena, a koje uključuju:
• mjere praćenja i kontrole ulazaka i izlazaka (ograđivanje gradilišta, čuvarska službe i drugo),
• mjere zabrane ili ograničenja kretanja vozila i osoba,
• mjere zabrane ili ograničenja unošenja opasnih tvari koje nisu namijenjene za potrebe građenja
(pirotehnika i slično) i obavljanja opasnih radnji (pušenje i slično),
• mjere označavanja, upozoravanja, obavješćivanja i informiranja o opasnostima i provođenju potrebnih
mjera zaštite od požara,
• osposobljenost osoba za provedbu preventivnih mjera zaštite od požara, gašenje početnih požara i
spašavanje ljudi i imovine ugroženih požarom,
• odabir mjesta i uvjete smještaja osoba na gradilištu (stambene barake, kontejneri i drugo) koji se odnose
na sigurnosne udaljenosti (minimalno 5 metara u svim smjerovima od ostalih objekata gradilišta), požarna
svojstva konstrukcijskih elemenata (minimalno razreda reakcije na požar A2), grijanje i hlađenje prostorija
(zatvoreni sustavi) i drugo,
• odabir mjesta i uvjete držanja i skladištenja zapaljivih i eksplozivnih tvari (sigurnosne udaljenosti,
ograđivanje, znakovi opasnosti, priručni uređaji i oprema za gašenje požara i drugo),
• mjere zaštite od požara kod obavljanja radova koji mogu izazvati požar (zavarivanje – elektrolučno ili
autogeno, rezanje reznom pločom, brušenje, lemljenje, rad uporabom otvorenog plamena kao što je varenje
ljepenke kod hidroizolaterskih radova, skidanje boja plamenikom i slično),
• mjere osiguranja dostatne količine i odgovarajuće vrste sredstava za gašenje početnih požara (vode,
pijeska i drugo),
• mjere osiguranja dostatne količine i odgovarajuće vrste opreme za gašenje početnih požara (vatrogasnih
aparata, posuda za vodu, hidranata i drugo),
• mjere osiguranja pristupa za potrebe vatrogasne intervencije i održavanja,
• mjere zbrinjavanja i redovitog uklanjanja prašine i otpada (osobito ambalažnog otpada, krpa natopljenih
otapalima i sli čno),
• odabir odgovarajuće izvedbe (Ex-izvedba) i mjere održavanja u ispravnom stanju uređaja, opreme i alata te
njihova pohrana i stavljanje van pogona nakon uporabe,
• mjere zaštite od atmosferskog pražnjenja,
• mjere provjere provođenja mjera zaštite od požara,
• način postupanja i uzbunjivanja u slučaju požara (pozivanje brojeva telefona: zaštita i spašavanje 112,
vatrogasci 193, policija 192, hitna pomoć 194).
Provjeru provedbe ovih zaštitnih mjera provodi rukovoditelj gradilišta, nadzorni inženjer, te ovlašteno tijelo
Grada.
U Tenji, Listopad 2019.g.
Projektant:
Ivan Tomičić, mag.ing.mech.
CALFACTIO j.d.o.o. za projektiranje i inženjering
GRAĐEVINA: Rekonstrukcija i dogradnja Elektrotehničke i prometne škole Osijek
LOKACIJA: Osijek, Istarska ulica 3, k.č.br. 5989/2 i 5989/9 k.o. Osijek
BROJ PROJEKTA: DATUM:
SP/66-19/IZ Listopad 2019.g
22
3. TEHNIČKI OPIS
4.1 OPĆENITO:
Predmet Izvedbenog projekta je zahvat u prostoru Rekonstrukcija i dogradnja Elektrotehničke i
prometne škole Osijek, na lokaciji Osijek, Istarska ulica 3, na k.č.br. 5989/2 i 5989/9 k.o. Osijek.
Na građevinskoj čestici nema je već postojeća zgrada Elektrotehničke i prometne škole Osijek, a sve
prikazano na Izvodu iz katastarskog plana Područnog ureda za katastar Osijek.
Za Investitora Elektrotehnička i prometna škola Osijek, izrađen je Izvedbeni strojarski projekt u kome
su obrađene slijedeće instalacije: GRIJANJE, HLAĐENJE I VENTILACIJA na zahvatu u prostoru
Rekonstrukcija i dogradnja Elektrotehničke i prometne škole Osijek.
Na predmetnoj lokaciji postoje vodovi komunalne infrastrukture: vodovod, kanalizacija, plin, daljinsko
grijanje i NN elektro mreža.
Na području predmetnog zahvata nalaze se instalacije vrelovodnog raspleta sustava daljinskog grijanja
koje je potrebno izmjestiti. Investitor je dužan podnijeti zahtjev distributeru HEP-Toplinarstvo d.o.o.
Pogon Osijek zahtjev za izmještanjem istoga. Sve troškove izmještanja snosi investitor, a projektnu
dokumentaciju i radove izvodi HEP-Toplinarstvo d.o.o. – Pogon Osijek.
OPĆI PODACI
Za predmetnu građevinu treba riješiti slijedeće instalacije:
➢ Indirektna toplinska podstanica ➢ Dizalica topline ➢ Ventilokonvektorsko grijanje/hlađenje ➢ Radijatorsko grijanje kupaonica i toaleta ➢ Ventilacija
4.1 OPIS RADA SUSTAVA
Za predmetnu građevinu je predviđena ugradnja sustava grijanja/hlađenja putem kazetnih i parapetnih
ventilokonvektora, te radijatorskog grijanja u kupaonicama i toaletima. Kao izvor toplinske energije u
sezoni grijanja će se do vanjskih temperatura iznad 0°C koristiti visokoučinkovita reverzibilna dizalica
topline snage 180 kW na grijanju, dok će se kod vanjskih temperatura ispod 0°C sustava
ventilokonvektorskog i radijatorskog grijanja opskrbljivati toplinskom energijom iz indirektne toplinske
podstanice tipa KOMPAKT-250.
U sezoni hlađenja će se kao izvor rashladne vode za sustav ventilokonvektorskog hlađenja koristiti
visokoučinkovita reverzibilna dizalica topline snage 171 kW na hlađenju.
Regulacija i upravljanje sustava grijanja/hlađenja obavljat će se pomoću programibilnog logičkog
kontrolera Siemens S7-1200, koji je zajednički za dizalicu topline, ventilokonvektore i toplinsku
podstanicu.
U učionicama je predviđena ugradnja sustava prisilne rekuperacije s povratom topline pomoću
pojedinačnih lokalnih rekuperacijskih jedinica ugrađenih u spušteni strop same prostorije.
U toaletima i WC-ima je predviđena ugradnja pojedinačnih odsisnih ventilatora sa odsisom istrošenog
zraka direktno kroz vanjski zid u okolinu.
CALFACTIO j.d.o.o. za projektiranje i inženjering
GRAĐEVINA: Rekonstrukcija i dogradnja Elektrotehničke i prometne škole Osijek
LOKACIJA: Osijek, Istarska ulica 3, k.č.br. 5989/2 i 5989/9 k.o. Osijek
BROJ PROJEKTA: DATUM:
SP/66-19/IZ Listopad 2019.g
23
4.2 INDIREKTNA TOPLINSKA PODSTANICA
Na osnovu izračunatih gubitaka topline i izabranih ogrjevnih tijela izabrana je indirektna toplinska
stanica KOMPAKT STANICA 250, dimenzija NO 50 i toplinske snage 250 kW, proizvod MontMontaža Oprema
d.o.o.. Predviđena indirektna toplinska stanice je energetski učinkovita s elektronski reguliranom
cirkulacijskom crpkom, regulatorom diferencijalnog tlaka i elektronskim regulatorom s pripadajućom
opremom i osjetnicima za vođenje temperature grijanja (sustav 60/40 °C) u zavisnosti od vanjskih uvjeta.
Oprema toplinske stanice smještena je na zajednički okvirni čelični nosač zavarene izvedbe.
Primarni krug toplinske podstanice pripremljen je za spoj na vrelovod distributera, a sekundarni na
toplovodnu mrežu potrošača.
U komplet toplinske stanice uključen je spojni cjevovod primara i sekundara i pripadajuća oprema s
armaturom (pločasti izmjenjivač topline, ultrazvučni mjerač topline, elektronski regulirana cirkulacijska
pumpa u sekundaru, termoregulacijski ventil s aktuatorom, regulator diferencijalnog tlaka, ekspanzijski
uređaj sa sigurnosnim ventilom, elektronski regulator daljinskog grijanja s pripadajućom opremom i
osjetnicima za vođenje temperature grijanja u zavisnosti o vanjskim uvjetima i upravljačkim elektro
ormarićem, hvatači nečistoće, zaporni ventili i kuglaste slavine.
Za ekspanziju vode i održavanje tlaka u sustavu izabran je sustav s otvorenom ekspanzijskom posudom
u kojoj se održava tlak pomoću tlačne crpke, tlačne sklopke, prestrujnog elektromagnetskog ventila i
elektrokomandnog ormara. Odabran je ekspanzijski uređaj s jednom crpkom tip EU 200-A-I "Pireko"
Oroslavlje.
Indirektna toplinska stanica će opskrbljivati ogrjevnom vodom krug ventilokonvektorskog grijanja
hodnika, učionica, kabineta i soba, i krug radijatorskog grijanja kupaonica i toaleta, i to pri vanjskoj
temperaturi ispod 0°C.
4.2.1 UVJETI I UPUTE ZA MONTAŽU
Indirektna toplinska stanica će se ugraditi u strojarnici u prizemlju predmetnog objekta. Montažu
opreme i predmetnih instalacija smiju i mogu izvoditi samo ovlašteni izvoditelji za tu vrstu radova i koji
posjeduju stručnu radnu snagu, potrebnu opremu, alat, pribor i ostala oruđa za rad.
Izvoditelj radove izvodi točno po projektnoj dokumentaciji i pod stručnom kontrolom nadzornog
inženjera.
Vrelovodni priključak nije dio ovog projekta. Za izradu projekta i radova na vrelovodnom priključku
Investitor mora podnijeti zahtjev u HEP-Toplinarstvo d.o.o. – Pogon Osijek.
4.3 DIZALICA TOPLINE
Dizalica topline (DT) je uređaj koji omogućava prijenos (toplinske) energije iz sustava (toplinskog
spremnika) niže temperaturne razine u sustav (toplinski spremnik) više temperaturne razine korištenjem
dodatne energije (rada) pomoću lijevo kretnog kružnog procesa prikladnog radnog medija.
Predviđa se ugradnja visokoučinkovite reverzibilne dizalice topline zrak-voda koja kao toplinski izvor
koristi okolni zrak. Dizalica će raditi u polivalentnom načinu rada. Dizalica topline za vanjsku montažu sa
šest Inverter kompresora. Svi inverter kompresori daju odlične performanse pri djelomičnom opterećenju.
Horizontalna dobava zraka dozvoljava montažu blizu zidova sa formiranjem ispušnih struja poprečno na
pravac ispuhivanja. Dizajniran je tako da zahtjeva jako malu potrebnu površinu za ugradnju.
Izmjenjivač topline je zaštićen posebnim premazom pa je uređaj pogodan za rad i u iznimno
korozivnim sredinama.Crni premaz pruža mu snažnu zaštitu od različitih agresivnih vanjskih utjecaja, a
hidrofilni film sprječava nakupljanje vode na rebrima izmjenjivača topline, čime smanjuje stvaranje
vlage. Ovaj iznimni napredak u izdržljivosti produljuje životni vijek proizvoda te značajno smanjuje
operativne troškove i troškove održavanja.
Uz uređaj se isporučuje kontroler sa 5" kolor displejem, sa mogućnošću povezivanja do 5
uređaja.Kontroler je montiran unutar elektro kutije unutar samog uređaja ili ga je moguće montirati
dislocirano na željenu lokaciju.
Inverterska dizalica topline koja ima mogućnost rada kao dizalica topline za grijanje/hlađenje.
CALFACTIO j.d.o.o. za projektiranje i inženjering
GRAĐEVINA: Rekonstrukcija i dogradnja Elektrotehničke i prometne škole Osijek
LOKACIJA: Osijek, Istarska ulica 3, k.č.br. 5989/2 i 5989/9 k.o. Osijek
BROJ PROJEKTA: DATUM:
SP/66-19/IZ Listopad 2019.g
24
Predviđena instalacija će se koristiti za sustav niskotemperaturnog ventilokonvektorskog
grijanja/hlađenja, niskotemperaturnog radijatorskog grijanja kupaonica i toaleta.
Preko regulacije ugrađene u DT regulira se temperatura vode polaznog voda na 7°C ili 50°C, a time i
krug grijanja /hlađenja. Crpka doprema ogrjevnu / rashladnu vodu preko 3‐putnog preklopnog do
pločastog izmjenjivača tipa ALFALAVAL TL6-BFM, pomoću cirkulacisjke crpke primara. Ogrijevni/rashladni
medij primara je 35% etile-glikol. u strojarnici ventila u PUFFER (međuspremnik ogrjevne/rashladne
vode) ili i višefunkcionalni međuspremnik ogrjevne vode. U ljetnom periodu DT1 ima primarnu funkciju
hlađenja sustava.
Ekspanzija ogrjevnog i rashladnog medija osigurana je ugradnjom membranske zatvorene ekspanzijske
posude zajedno sa sigurnosnim ventilima.
Ogrjevni i rashladni medij odvode se u strojarnicu u prizemlju zgrade gdje se ugrađuju:
- rastavljivi pločasti toplinski izmjenjivač
- inercijski akumulacijski spremnik – hidraulička skretnica
- razdjelnik i sabirnik hladne/tople vode
- na razdjelnicima/sabirnicama se ugrađuju ogranci rashladnog/ogrjevnog medija
Predviđeno je izvođenje ogranaka hladne/tople vode na kojima se ugrađuju cirkulacijske crpke,
elektronski regulirane:
- krug ventilokonvektorskog grijanja/hlađenja
- krug radijatorskog grijanja
Regulacija rada dizalica topline vrši se sa komandnih ormarića jedinice.
Na predmetnu građevinu se planira ugraditi visokoučinkovita reverzibilna zrak-voda dizalica topline kao
LG ACHH050LBAB. Jedinica je sastavljena iz jednog modula sljedećih tehničkih karakterika:
Rashladni medij kao radna tvar:R410A
Broj kompresora:6
Područje rada:
Temperatura rashladnog medija: 5-20°C
Temperatura ogrijevnog medija: 30-55°C
radno područje: grijanje: od -30° do +35°C
radno područje: hlađenje: od -15° do +48°C
Grijanje (vanjska temp.7°C/voda 40/45°C)
Qg=180kW
N ukupno = 52.9kW / 380-415 V, 3F, 50 Hz
COP=3.4
SCOP=3,3
Hlađenje (vanjska temp.35°C/voda 7/12°C)
Qh=171kW
N ukupno = 55.2kW / 380-415 V, 3F, 50 Hz
EER=3.10
SEER=4,5
Nivo zvučnog tlaka: 68 dB(A) na udaljenosti 1 m od jedinice
dimenzije ukupno: 2291x2154 mm; h = 2293 mm
težina ukupno: 1430 kg
NAPOMENA:
Uređaj se isporučuje bez hidro bloka i pumpe
CALFACTIO j.d.o.o. za projektiranje i inženjering
GRAĐEVINA: Rekonstrukcija i dogradnja Elektrotehničke i prometne škole Osijek
LOKACIJA: Osijek, Istarska ulica 3, k.č.br. 5989/2 i 5989/9 k.o. Osijek
BROJ PROJEKTA: DATUM:
SP/66-19/IZ Listopad 2019.g
25
Dizalica topline za grijanje i hlađenje. Uređaj je optimiziran za niskoenergetske objekte sa širokim
rasponom modulacije inverterskih kompresora.
Dizalica topline se ugrađuje na betonsku temeljnu ploču s postoljem visine minimalno 30cm od okolnog
terena. Ugradnja dizalica topline prema uputama proizvođača.
Puštanje dizalice topline u pogon podrazumijeva njezino prvo uključivanje nakon postavljanja na
mjestu na kojem će se koristiti i primopredaju krajnjem korisniku.
Postupak prvog uključivanja dizalice topline obuhvaća provođenje više provjera i ispitivanja
neposredno prije, tijekom i neposredno nakon samog uključivanja:
• provjeru usklađenosti izvedbe s projektom
• provjeru spojeva svih priključaka
• provjeru cijevnih vodova i ventila kruga posrednog medija
• provjeru i ispitivanje sigurnosne opreme sustava grijanja i kruga posrednog medija
• provjeru električne instalacije
• provjeru sustava regulacije
• odzračivanje svih cijevnih vodova i ogrjevnih tijela sustava grijanja
• namještanje prestrujnih ventila
• provjeru protoka ogrjevnog i posrednog medija
• provjeru rada displeja na dizalici topline i regulacijskoj jedinici
• ispitivanje razine buke pri radu.
Za puštanje dizalice topline u pogon, uključujući sve potrebne provjere i ispitivanja, treba predvidjeti
do nekoliko dana, dok svi pogonski parametri ne dosegnu stabilnu i ekonomičnu razinu. Nakon tih nekoliko
dana probnog rada ponovno treba provesti provjeru svih dijelova sustava i ukloniti smetnje, ako su bile
uočene. Nakon toga može uslijediti primopredaja krajnjem korisniku pri čemu se provodi:
- vizualni pregled cijelog sustava
- predaja cjelokupne tehničke dokumentacije
- provjera sigurnosnih elemenata i zadovoljavanje sigurnosnih mjera.
4.4 EKSPANZIJSKE POSUDE
Povećanje volumena vode u instalaciji primara dizalice topline i sekundara koje nastaje uslijed
zagrijavanja vode od 10º na 60°C (∆t=50°C) kompenzirat će se membranskom ekspanzijskom posudom
pod tlakom.
Sukladno proračunu, za sustav grijanja pomoću dizalica topline odabiru se tlačne membranske
ekspanzijske posude radnog volumena:
- 24 l (primar dizalica topline)
- 100 l ( sekundar – krug ventilokonvektorskog grijanja/hlađenja i radijatorskog grijanja)
Predviđena je ekspanzijskih posuda radnog tlaka do 3.0 bar, koje se nalaze u Strojarnici.
CALFACTIO j.d.o.o. za projektiranje i inženjering
GRAĐEVINA: Rekonstrukcija i dogradnja Elektrotehničke i prometne škole Osijek
LOKACIJA: Osijek, Istarska ulica 3, k.č.br. 5989/2 i 5989/9 k.o. Osijek
BROJ PROJEKTA: DATUM:
SP/66-19/IZ Listopad 2019.g
26
4.5 CIJEVNI RAZVOD
Primarni cjevovodi se po izlasku iz dizalica topline vodi iz predizoliranih savitljivih PE-Xa cijevi sa PE-
Hd zaštitnom cijevi za opskrbu ogrjevnom i rashladnom vodom, proizvod kao Uponor Ecoflex Thermo
Single ø110x15,1mm PN10 u skladu s normom EN 15632. Polaganje se vrši u jednom dijelu od dizalice
topline do strojarnice.
Toplinska izolacija je od pjena od umreženog polietilena.
Odzračivanje instalacije se vrši odzračnim lončićima u kompletu sa odzračnom cijevi i odzračnim ventilom
– ručno odzračivanje.
Svi priključci kao i sama zaporna armatura na razdjelniku/sabirniku je nazivnog pritiska NP6. Na
razdjelniku se nalazi i priključak s manometrom i manometarskom slavinom za kontrolu strujanja.
Razdjelnici su postavljeni na oslonce montirane na visini koja omogućuje posluživanje armature s poda.
Isti su izolirani termoizolacijom od izolacijskog materijala zatvorenih ćelija s parnom branom, baziran na
ekstrudiranoj elastomernoj pjeni, crne boje (koeficijent otpora difuzije vodene pare m 10000, toplinska
vodljivost 0.033 W/mK pri 0°C). Debljina stijenke izolacije je 20 mm.
Na svim cjevovodima, polaznim i povratnim, predviđeni su termometri i manometri, a smješteni su tako
da ih moguće nesmetano očitavati.
Sva oprema unutar instalacije povezana je cjevovodima odgovarajućeg promjera u ovisnosti od količine
protoka medija i preporučljive brzine protoka istog.
Cjevovodi u građevini se vode nevidljivo, u spuštenom stropu, instalacijskim kanalima, zidu ili podu, osim
u strojarnici gdje se vode vidljivo, po zidu strojarnice.
Vođenje cjevovoda mora osigurati samokompenzirajući, što je omogućeno pravilnom geometrijom
pojednih krakova cjevovoda.
Cjevovodi su ovješeni na stropnu konstrukciju ili zidove građevine. Razmak oslonaca i ovješenja određen
je u ovisnosti o dozvoljenoj samonosivoj dužini izoliranog cjevovoda, a u ovisnosti o promjeru istog.
Cijevne razvode koji se vode u prostoru građevine potrebno je voditi oslonjene na oslonce – klizne točke
sa vođenjem i čvrste točke – na određenim razmacima i to za čelične cijevi:
- za cijevi do NO25 – razmak oslonaca je 1,9m
- za cijevi od NO32 do NO40 – razmak oslonaca je 2,5m
- za cijevi NO50 – razmak oslonaca je 2,9m
- za cijevi od NO65 i više – razmak oslonaca je 3,9m
Dok za kompozitne polipropilenske cijevi ojačane staklenim vlaknima razmaci oslonaca za horizontalni
razvod se izvode prema slijedećoj tablici:
Kod vertikalnog razvoda navedeni razmaci se mogu povećati za 20%.
CALFACTIO j.d.o.o. za projektiranje i inženjering
GRAĐEVINA: Rekonstrukcija i dogradnja Elektrotehničke i prometne škole Osijek
LOKACIJA: Osijek, Istarska ulica 3, k.č.br. 5989/2 i 5989/9 k.o. Osijek
BROJ PROJEKTA: DATUM:
SP/66-19/IZ Listopad 2019.g
27
Na najvišim točkama toplovodnih cjevovoda ugrađuju se odzračni lonci, s mogućnošću odzračivanja s poda
– ručni odzračni ventili.
Liče se svi metalni dijelovi koji nisu tvornički oličeni. Prije ličenja potrebno je mehaničkim putem
odstraniti hrđu i sve nečistoće. Nakon čišćenja do metalnog sjaja nanose se dva sloja temeljne boje u
dvije nijanse. Neizolirane dijelove instalacije potrebno je oličiti i sa dva sloja zaštitnog laka otpornog na
povišenu temperaturu.
Svi cjevovodi u objektu su izolirani termoizolacijom od izolacijskog materijala zatvorenih ćelija s
parnom branom, baziran na ekstrudiranoj elastomernoj pjeni, crne boje (koeficijent otpora difuzije
vodene pare m 10000, toplinska vodljivost 0.033 W/mK pri 0°C). Debljina stijenke izolacije je 13 mm.
Debljina stjenke izolacije cjevovoda u strojarnici je 20mm. Stavkom obuhvatiti i predpripremljene
dijelove za izoliranje pripadajućih fazonskih komada, koljena, ogranaka, cijevne armature, završnih
manžeta i slično, te specijalno ljepilo i originalnu samoljepljivu traku za brtvljenje šavova. Sve spojeve
pažljivo difuzijski zabrtviti.
Prije izvršenja hladne tlačne probe ne smiju se ličiti mjesta zavara niti izolirati cjevovod.
Čelične cijevi su međusobno spojene zavarivanjem, a oprema i armatura prirubničkim spojevima ili
cijevnim navojem.
Kompozitne PPR cijevi su međusobno spojene polifuzijskim zavarivanjem, a oprema i armatura cijevnim
navojem upotrebom prijelaznih komada.
Za odvod vode prilikom gravitacijskog pražnjenja razdjelnika predviđen je otvoren odvod. Sav ostali
odvod voda s poda vrši se preko podnih rešetki.
Nakon izvršene montaže potrebno je izvršiti ispitivanje sustava – tlačna i topla proba, puštanje u pogon,
probni rad – te izvršiti balansiranje instalacije.
Potrebno je izvršiti ispitivanje instalacije te priložiti odgovarajuće rezultate ispitivanja (po ovlaštenoj
organizaciji).
Sve dostupne cjevovode označiti sa obojenim prstenovima za označavanje ili strelicama s oznakom
smjera strujanja medija.
4.6 GRIJANJE I HLAĐENJE
4.6.1 VENTILOKONVEKTORI
Za sve radne prostorije predmetne zgrade predviđena je ugradnja ventilokonvektorskih jedinica – 2
cijevni uređaji. Ogrjevni medij - topla voda 50/40°C, rashladni medij – hladna voda 7/12°C.
U radne prostore predviđena je ugradnja ventilokonvektora, za rad s optočnim zrakom, s maskom,
dvocijevne izvedbe, s trobrzinskim ventilatorom, izoliranom okapnicom za skupljanje kondenzata, setom
priključnih cijevi 1/2“, troputnim ON/OFF ventilom, zapornim i balansirajućim ventilom 1/2“, senzorom
minimalne temperature polaza TC.
Uglavnom je predviđena ugradnja kazetnih ventilokonvektora, osim u sobama, kabinetima, stubištu i
foaeju gdje je predviđena ugradnja paapetnih ventilokonvektora.
Zimi se na izmjenjivač ventilokonvektora dovodi ogrjevni medij – topla voda 50/40°C iz dizalica topline –
zagrijavanje prostora (do vanjskih temperatura iznad 0°C). Kada vanjska temperatura padne ispod 0°C
onda se u sustav dovodi ogrjevni medij iz kompaktne toplinske stanice daljinskog grijanja – topla voda
60/40°C.
Ljeti se na izmjenjivač ventiloknvektora dovodi rashladni medij iz dizalica topline – rashladna voda 7/12°
- hlađenje prostora.
CALFACTIO j.d.o.o. za projektiranje i inženjering
GRAĐEVINA: Rekonstrukcija i dogradnja Elektrotehničke i prometne škole Osijek
LOKACIJA: Osijek, Istarska ulica 3, k.č.br. 5989/2 i 5989/9 k.o. Osijek
BROJ PROJEKTA: DATUM:
SP/66-19/IZ Listopad 2019.g
28
Nivo grijanja odnosno hlađenja određuje se postavljanjem željene vrijednosti temperature na zidnom
sobnom termostatu.
Odabrani ventilokonvektori pokrivaju potrebe za grijanjem i hlađenjem prostorija u kojima su ugrađeni,
na brzini vrtnje ventilatora prema tablici u poglavlju 7.PRORAČUNI.
Sa svakog ventilokonvektora predviđeno je izvođenje ispusta kondenzata. Predviđena je ugradnja PPR
cijevi za odvod kondenzata sa odvodom preko vertikala u zelenu površinu, upojne bunare ili spojem na
najbliže odvode umivaonika unutar građevine, a dijelom (parapetni uređaji prizemlja) sa ispustom na
teren.
Razvod ogrjevnog/rashladnog medija od strojarnice do ventilokonvekora izvodi se iz kompozitnih PPR
cijevi ojačanih staklenim vlaknima. Razvod unutar instalacijskih kanala i spuštenog stropa.
Odzračivanje instalacije vrši se automatskim odzračnim lončićima u kompletu sa odzračnim ručnim
ventilom i slavinom.
Svu cijevnu instalaciju potrebno je izolirati toplinskom izolacijom sa parnom pranom.
Nakon montaže instalacije potrebno je izvršiti hladnu tlačnu probu i funkcionalnu probu.
Tijekom probnog pogona potrebno je izvršiti regulaciju i balansiranje sustava.
Nakon završene montaže instalacije sustava grijanja/hlađenja izvršiti će se hladno ispitavanje probnim
tlakom od 4,5 bara u trajanju od osam sati. Rezultati o uspješno obavljenoj tlačnoj probi zapisnički će se
evidentirati od strane nadzornog inženjera.
Po obavljenoj tlačnoj probi potrebno je izvršiti probni rad sistema grijanja uz grubu i finu
regulaciju instalacije grijanja/hlađenja sve dok se ne postignu projektirani parametri.
Automatska regulacija
Sustav automatske regulacije napaja sve ventilokonvektore i na operatorskom panelu (na vratima ormara)
prikazuju se osnovni set podataka sa svakog sobnog termostata.
Komunikacija svakog sobnog termostata sa sustavom automatske regulacije je MODBUS RTU (RS485)
protokolom. Srce sustava automatske regulacije je programibilni logički kontroler Siemens S7-1200 i
zajednički je za dizalice topline i ventilokonvektore.
Podacima na operatorskom panelu moguće je pristupiti putem TCP/IP protokola putem VNC preglednika.
Logika upravljanja
1. Potpuno automatski rad – na sobnim termostatima se podesi vrijema rada radnim danima od 6 do 16
sati, u strojarnici se jednako tako podese i crpke i dizalice topline.
2. Ručni rad – ukoliko je potreban rad sustava van radnog vremena, na upravljačkom panelu se prebaci
dizalicu topline, željeni krug grijanja/hlađenja i željeni sobni termostat na „RUČNI“ mod upravljanja,
te ih se uključi. Po prestanku potrebe za radom izvan radnog vremena sustav se prebaci na
automatski mod rada.
4.6.2 RADIJATORSKO GRIJANJE
U kupaonicama i toaletima predmetne zgrade ogrjevna tijela su kompaktni pločasti čelični ventilski
radijatori tip kao VaiRAD 22 KV proizvođača Vaillant ili nekog drugog jednakovrijednih karakteristika,
kupaonski cijevni radijatori, te pločasti čelični vetikalni radijatori. Radijatori su opremljeni odzračnim
pipcima, termostatskim ventilima s termostatskom glavom i H-ventilima za spoj radijator iz poda.
Radijatori se instaliraju na zid standardnim ovjesnim priborom. Razvod radijatorskog grijanja od
strojarnice do etažnih razdjelnika radijatorskog grijanja vršit će se iz kompozitnih PPR cijevi.
CALFACTIO j.d.o.o. za projektiranje i inženjering
GRAĐEVINA: Rekonstrukcija i dogradnja Elektrotehničke i prometne škole Osijek
LOKACIJA: Osijek, Istarska ulica 3, k.č.br. 5989/2 i 5989/9 k.o. Osijek
BROJ PROJEKTA: DATUM:
SP/66-19/IZ Listopad 2019.g
29
Razvod radijatorskog grijanja od etažnih razdjelnika se izvodi višeslojnim cijevima REHAU Rautitan flex
PE-Xa promjera 16x2mm. Cijevi se polažu na podnu ploču prije polaganja estriha. Cijevi koje se polažu na
pod prema tlu toplinski izolirati izolacijom najmanje debljine 1/3 promjera cijevi, minimalno 6mm
najviše do 50mm. Cijevi koje se polažu u površinskom sloju poda u međukatnoj konstrukciji izolirati
toplinskom izolacijom minimalne debljine 6mm.
Sva oprema radijatorskog grijanja povezana je cjevovodima odgovarajućeg promjera u ovisnosti količine
protoka medija i preporučljive brzine protoka istog.
Cijevi grijanja, spojnice kao i ostala oprema spajaju se pomoću specijalnih alata i spojnica i to ovisno o
proizvođaču. Pri prolasku kroz zidove moraju se postaviti zaštitne cijevi. Cjevovod je potrebno položiti u
estrih. Po završetku montaže potrebno je izvršiti ispitivanje instalacije na nepropusnost prema
odredbama DIN 18380. Tlačna proba izvodi se tlakom 1,3 puta većim od radnog tlaka odnosno za minimum
1,00 bar višim od radnog. Instalacija se natlači na potreban tlak i ostavi 24 sata, u tom vremenu tlak ne
bi smio pasti za više od 0,2 bara i ne smije biti propuštanja vode.
Montažni elementi (spojnice, držači i sl.) moraju biti isključivo originalni za cijevi od peroksidom
umreženog polietilena (PE-Xa).
4.7 VENTILACIJA
Učionice i ulazni hol
Ventilacija prostora učionica i ulaznog hola će se vršiti pomoću lokalnog pojedinačnog sustva ventilacije
sa ventilacijskom jedinicom s povratom topline (rekuperatorom) tip kao LG LZ-H050GBA5, LZ-H080GBA5
i LZ-H100GBA5, maksimalnog kapaciteta 500m3/h, 800m3/h i 1000m3/h. Minimalni stupanj učinkovitosti
povrata topline (entalpija – grijanje) iznosi 70%. Rekuperatori su spojeni na ventilacijske horizontalne
kanale koji vode zrak na fasadu predmetnog objekta. Rekuperator je predviđen za ugradnju u spušteni
strop pojedine prostorije, i potrebno je predvidjeti prostor za servis rekuperatora (izmjenu filtera).
Ugradnjom rekuperatorske jedinice osigurava se minimalno 2 izmjene zraka po satu za pojedinu učionicu i
ulazni hodnik.
Na strani usisa svježeg vanjskog zraka ugrađuju se okrugli kanalski električni grijači snage 2 kW, odnosno
2,4 kW, koji služe za predgrijavanje svježeg zraka u slučajevima niskih vanjskih temperatura u zimskom
periodu.
Na kanalskom razvodu sustava ventilacije iza rekuperatorske ventilacijske jedinice se ugrađuju prigušivači
zvuka promjera u skladu s ventilacijskim kanalom i duljine 500mm.
Kupaonice i toaleti
Ventilacija kupaonica i toaleta predviđena je kao odsisna s pomoću jednocijevnog ventilacijskog sustava s
odsisnim ventilatorom ugrađenim u samu kupaonicu ili toalet, a koji odsisava zrak iz prostorije. Zrak iz
prostorije se odvodi pomoću horizontalne korugirane cijevi u spuštenom stropu koja odvodi zrak u vanjski
prostor kroz vanjski zid.
Kupaonice je opremljena s odsisnim ventilatorom kapaciteta 60, 90 ili 200 m3/h što je dovoljan kapacitet
za volumen predmetnih kupaonica i toaletate omogućuje standardnih 4 izmjene zraka po satu.
Ventilatori su vezani na prekidač za paljenje svjetla i imaju opciju produljenog rada pomoću timera.
Predviđa se produljenje rada ca. 5 minuta nakon gašenja svjetla. Predviđeni ventilatori emitiraju buku od
samo 35 dB(A) što može biti bitno za komfor. Ventilatori se ugrađuju podžbukno.
Spoj kućišta ventilatora na horizontalnu cijev je Ø100mm i izvodi se iz limenih ventilacijskih kanala
(spiralno namotani) za odvod zraka izvedenih od pocinčanog lima debljine 0,6mm do proboja kroz vanjski
zid zgrade, te se na kraju se montira ukrasna fiksna protukišna žaluzija.
CALFACTIO j.d.o.o. za projektiranje i inženjering
GRAĐEVINA: Rekonstrukcija i dogradnja Elektrotehničke i prometne škole Osijek
LOKACIJA: Osijek, Istarska ulica 3, k.č.br. 5989/2 i 5989/9 k.o. Osijek
BROJ PROJEKTA: DATUM:
SP/66-19/IZ Listopad 2019.g
30
Ventilacijski kanali
Limeni ventilacijski kanali (spiralno namotani) za dovod - odvod zraka izvedeni od pocinčanog lima
debljine 0,6mm, s prirubnicama, vijcima, maticama i zavješenjima. Kompletan cjevovodni sustav se
izrađuje iz spiro cijevi izrađenih iz pocinčane beskonačne trake, normalnim N falcanjem, tako da je
glatka s unutrašnje strane. Cijevi se isporučuju u dužinama od 6m. U isporuku je uključena odgovarajuća
količina spojnica za spajanje ravnih dionica međusobno, kao i fazonskih komada, ovjesi, konzole, oslonci i
sl. Komplet s potrebnim cijevnim i fazonskim komadima (Q-komadi, redukcije itd.), obujmicama i ostalom
potrebnom opremom. Dimenzije cijevi: Ø100 - 250 mm.
U dijelu prolaza kanala ispod AB grede, gdje je to potrebno, vrši se prijelaz na pravokutni ventilacijski
kanal. Pravokutni ventilacijski kanali se izrađuju iz pocinčanog lima debljine 0,6mm. Svi elementi moraju
biti pripremljeni za montažu sa ugrađenim spojnim materijalom – prirubnica ili SB profil.
Ventilacijski kanali se izoliraju fleksibilnom toplinskom izolacijom debljine 10mm, tip kao ARMAFLEX.
Distribucija zraka u prostoru se vrši pomoću stropnih vrtložnih distributera ugrađenih u spušteni strop s
priključnom kutijom. Priključna kutija se na kanal spaja fleksibilnim zrakotijesnim spojem.
Radi sprečavanja prijenosa buke i vibracija od ventilacijskog uređaja na kanalni razvod isti se spajaju sa
kanalom zrakotijesnim fleksibilnim spojem kao FLC-Si kod kojeg je platno sa obje strane spojeno
pocinčanim limom i materijal je silikon, te je namijenjen za maksimalnu temperaturu 280°C.
Kanalni razvod se vješa na strop standardnim ovjesnim priborom i ovjesnicama sa antivibracijskom
gumom.
Rekuperacijska jedinica se vješa o strop pomoću nosača iz pocinčanog čeličnog lima sa antivibracijskom
gumenom podloškom.
Ventilacija ostalih prostorija se vrši prirodnim putem.
U Tenji, Listopad 2019.g.
Projektant:
Ivan Tomičić, mag.ing.mech.
CALFACTIO j.d.o.o. za projektiranje i inženjering
GRAĐEVINA: Rekonstrukcija i dogradnja Elektrotehničke i prometne škole Osijek
LOKACIJA: Osijek, Istarska ulica 3, k.č.br. 5989/2 i 5989/9 k.o. Osijek
BROJ PROJEKTA: DATUM:
SP/66-19/IZ Listopad 2019.g
31
4. PRORAČUNI
7.1. GRIJANJE
Proračun toplinskih gubitaka rađen računalnim programom TechCON 8.2. na osnovi arhitektonskih
podloga, prema HRN U.J5.600 po postupku EN12831 i dat je tabelarno u nastavku.
Zbog opširnosti proračuna toplinskih gubitaka isti se neće prikazivati. U nastavku se daje ukupna toplinska
bilanca objekta.
CALFACTIO j.d.o.o. za projektiranje i inženjering
GRAĐEVINA: Rekonstrukcija i dogradnja Elektrotehničke i prometne škole Osijek
LOKACIJA: Osijek, Istarska ulica 3, k.č.br. 5989/2 i 5989/9 k.o. Osijek
BROJ PROJEKTA: DATUM:
SP/66-19/IZ Listopad 2019.g
32
7.1.1. OGRJEVNA TIJELA
RADIJATORI
Prizemlje
Br. Prostorija tp Toplinski
gubitci Qg
Temp. režim
Oznaka radijatora
(°C) (W) (W)
PRIZEMLJE
1.13 Sanitarije 2 15 111 205 50/40 VaiRAD 11 V 600/400
1.14 Sanitarije 3 15 767 935 50/40 KORATHERM VERTIKAL K20VM 1200/884
UKUPNO: 1140
1. KAT
2.05 Sanitarije 1 24 397 465 50/40 Kupaonski radijator 1810/750
2.10 Sanitarije 2 15 696 935 50/40 KORATHERM VERTIKAL K20M 1200/844
2.11 Sanitarije 3 15 91 205 50/40 VaiRAD 11 V 600/400
2.14 Sanitarije 5 24 573 465 50/40 Kupaonski radijator 1810/750
2.16 Sanitarije 6 24 452 465 50/40 Kupaonski radijator 1810/750
2.18 Sanitarije 7 24 721 465 50/40 Kupaonski radijator 1810/750
UKUPNO: 3000
2.KAT
3.09 Sanitarije 1 15 696 935 50/40 KORATHERM VERTIKAL K20VM 1200/884
3.10 Sanitarije 2 15 81 205 50/40 VaiRAD 11 V 600/400
3.13 Sanitarije 4 24 501 465 50/40 Kupaonski radijator 1810/750
3.15 Sanitarije 5 24 524 465 50/40 Kupaonski radijator 1810/750
3.17 Sanitarije 6 24 476 465 50/40 Kupaonski radijator 1810/750
UKUPNO: 2535
3.KAT
4.03 Sanitarije 1 15 65 205 50/40 VaiRAD 11 V 600/400
4.04 Sanitarije 2 15 779 935 50/40 KORATHERM VERTIKAL K20VM 1200/884
4.05 Sanitarije 3 15 451 509 50/40 VaiRAD 22 V 600/600
UKUPNO: 1649
SVEUKUPNO: 8324
CALFACTIO j.d.o.o. za projektiranje i inženjering
GRAĐEVINA: Rekonstrukcija i dogradnja Elektrotehničke i prometne škole Osijek
LOKACIJA: Osijek, Istarska ulica 3, k.č.br. 5989/2 i 5989/9 k.o. Osijek
BROJ PROJEKTA: DATUM:
SP/66-19/IZ Listopad 2019.g
33
VENTILOKONVEKTORI
PRIZEMLJE
Br. Prostorija tp -
zima Toplinski
gubitci tp -
ljeto Toplinski dobitci
Qgi Qhi Oznaka
ventilokonvektora
Brzina na
grijanju
(°C) (W) (°C) (W) (W) (W)
1.01 Pneumatika i hidraulika
20 4716 26 5766 2510 4247 LIGHT-ECM 63 RC 1.brzina
2510 4247 LIGHT-ECM 63 RC 1.brzina
1.02 Automatika i robotika
20 4203 26 5548 2510 4247 LIGHT-ECM 63 RC 1.brzina
2510 4247 LIGHT-ECM 63 RC 1.brzina
1.03 Pogonska tehnika
20 4053 26 5186 2510 4247 LIGHT-ECM 63 RC 1.brzina
2510 4247 LIGHT-ECM 63 RC 1.brzina
1.04 Ulaz, hodnik, stubište
20 7281 26 6469 4910 4247 LIGHT-ECM 63 RC 3.brzina
4910 4247 LIGHT-ECM 63 RC 3.brzina
1.05 Kabinet 1 20 2005 26 1931 2330 2599 VCE38 3.brzina
1.06 Obnovljivi izvori energije
20 4832 26 5614 2510 4247 LIGHT-ECM 63 RC 1.brzina
2510 4247 LIGHT-ECM 63 RC 1.brzina
1.07 Kabinet 2 20 1519 26 1039 1650 1685 VCE28 3.brzina
1.08 Server soba 20 - 26 3000 2510 4247 LIGHT-ECM 63 RC 1.brzina
1.09 Vratarnica 20 678 26 519 810 893 VCE 18 1.brzina
1.10 Vjetrobran 20 1464 26 2195 2300 2667 LIGHT-ECM 62 RC 1.brzina
1.11 Stubište i dizalo
20 1546 26 1468 1900 2223 LIGHT-ECM 61 RC 1.brzina
UKUPNO: 41400 56784
1.KAT
2.01 Radionica 20 5577 26 7178 3522 4247 LIGHT-ECM 63 RC 2.brzina
3522 4247 LIGHT-ECM 63 RC 2.brzina
2.02 Maker space 20 3739 26 4714 4150 4975 LIGHT-ECM 64 RC 2.brzina
2.03 Dnevni prostor 20 2100 26 2499 2300 2667 LIGHT-ECM 62 RC 1.brzina
2.04 Soba 1 20 657 26 829 810 893 VCE18 1.brzina
2.06 Kabinet 1 20 1907 26 1885 2330 2599 VCE38 3.brzina
2.07 Radionica 2 20 5654 26 6149 3522 4247 LIGHT-ECM 63 RC 2.brzina
3522 4247 LIGHT-ECM 63 RC 2.brzina
2.08 Servis za popravak malih uređaja
20 2493 26 4042 2510 4247 LIGHT-ECM 63 RC 1.brzina
2.09 Stubište i dizalo
20 2129 26 2497 2600 2769 VCE48 3.brzina
2.13 Soba 2 20 495 26 724 810 893 VCE18 1.brzina
2.15 Soba 3 20 533 26 719 810 893 VCE18 1.brzina
2.17 Soba 4 20 426 26 711 810 893 VCE18 1.brzina
2.19 Hodnik i stubište
20 1296 26 2591 2300 2667 LIGHT-ECM 62 RC 1.brzina
2.20 Hodnik 20 2201 26 895 2300 2223 LIGHT-ECM 61 RC 2.brzina
UKUPNO: 35818 42707
CALFACTIO j.d.o.o. za projektiranje i inženjering
GRAĐEVINA: Rekonstrukcija i dogradnja Elektrotehničke i prometne škole Osijek
LOKACIJA: Osijek, Istarska ulica 3, k.č.br. 5989/2 i 5989/9 k.o. Osijek
BROJ PROJEKTA: DATUM:
SP/66-19/IZ Listopad 2019.g
34
2.KAT
3.01 Računalstvo 20 6276 26 6449 3522 4247 LIGHT-ECM 63 RC 2.brzina
3522 4247 LIGHT-ECM 63 RC 2.brzina
3.02 Računalstvo 2 20 5758 26 6220 3522 4247 LIGHT-ECM 63 RC 2.brzina
3522 4247 LIGHT-ECM 63 RC 2.brzina
3.03 Tehničko crtanje i modeliranje
20 5544 26 5794 3522 4247 LIGHT-ECM 63 RC 2.brzina
3522 4247 LIGHT-ECM 63 RC 2.brzina
3.04 Kabinet 1 20 1906 26 2019 2330 2599 VCE38 3.brzina
3.05 Računalstvo 3 20 4599 26 5711 2510 4247 LIGHT-ECM 63 RC 1.brzina
2510 4247 LIGHT-ECM 63 RC 1.brzina
3.06 Studio 20 2050 26 2925 2510 4247 LIGHT-ECM 63 RC 1.brzina
3.07 Kabinet 2 20 1093 26 1053 1360 1685 VCE28 1.brzina
3.08 Stubište i dizalo
20 2160 26 2544 2600 2769 VCE48 3.brzina
3.12 Soba 1 20 835 26 806 850 893 VCE18 2.brzina
3.14 Soba 2 20 807 26 806 810 893 VCE18 1.brzina
3.16 Soba 3 20 767 26 818 810 893 VCE18 1.brzina
3.18 Hodnik i stubište
20 2761 26 3186 3522 4247 LIGHT-ECM 63 RC 2.brzina
3.19 Hodnik 20 2201 26 866 2300 2223 LIGHT-ECM 61 RC 2.brzina
UKUPNO: 43244 54425
3.KAT
4.01 Konferencijska dvorana
20 11418 26 19807
4150 4975 LIGHT-ECM 64RC 2.brzina
4150 4975 LIGHT-ECM 64RC 2.brzina
4150 4975 LIGHT-ECM 64RC 2.brzina
4150 4975 LIGHT-ECM 64RC 2.brzina
4.02 Stubište i dizalo
20 3268 26 2290 3230 2599 VCE38 6.brzina
4.06 Foaje 20 14887 26 23478
7520 8312 VCE108 1.brzina
7520 8312 VCE108 1.brzina
7520 8312 VCE108 1.brzina UKUPNO: 42390 47435
SVEUKUPNO: 162852 201351
CALFACTIO j.d.o.o. za projektiranje i inženjering
GRAĐEVINA: Rekonstrukcija i dogradnja Elektrotehničke i prometne škole Osijek
LOKACIJA: Osijek, Istarska ulica 3, k.č.br. 5989/2 i 5989/9 k.o. Osijek
BROJ PROJEKTA: DATUM:
SP/66-19/IZ Listopad 2019.g
35
7.2. HLAĐENJE
Proračun dobitaka topline izvršen je prema podlogama koje su dobivene od arhitekta uz korištenje
propisa i normi VDI 2078. Usvojena vanjska temperatura tvp=+32°C i temperatura unutarnjeg prostora
tup= +26°C. Proračun dobitaka topline izvršen je na PC računalu. Dobiveni rezultati se zbog opširnosti
ne prikazuju, nalaze se projektanta i dati će se na uvid na traženje Investitora, nadzora ili
inspekcijskih službi.
7.2.1. IZBOR DIZALICE TOPLINE
Odabire se reverzibilna zrak-voda dizalica topline kao LG ACHH050LBAB. Jedinica je sastavljena iz jednog
modula sljedećih tehničkih karakterika:
Rashladni medij kao radna tvar:R410A
Broj kompresora:6
Područje rada:
Temperatura rashladnog medija: 5-20°C
Temperatura ogrijevnog medija: 30-55°C
radno područje: grijanje: od -30° do +35°C
radno područje: hlađenje: od -15° do +48°C
Grijanje (vanjska temp.7°C/voda 40/45°C)
Qg=180kW
N ukupno = 52.9kW / 380-415 V, 3F, 50 Hz
COP=3.4
SCOP=3,3
Hlađenje (vanjska temp.35°C/voda 7/12°C)
Qh=171kW
N ukupno = 55.2kW / 380-415 V, 3F, 50 Hz
EER=3.10
SEER=4,5
Nivo zvučnog tlaka: 68 dB(A) na udaljenosti 1 m od jedinice
dimenzije ukupno: 2291x2154 mm; h = 2293 mm
težina ukupno: 1430 kg
NAPOMENA:
Uređaj se isporučuje bez hidro bloka i pumpe
CALFACTIO j.d.o.o. za projektiranje i inženjering
GRAĐEVINA: Rekonstrukcija i dogradnja Elektrotehničke i prometne škole Osijek
LOKACIJA: Osijek, Istarska ulica 3, k.č.br. 5989/2 i 5989/9 k.o. Osijek
BROJ PROJEKTA: DATUM:
SP/66-19/IZ Listopad 2019.g
36
7.3. IZBOR OPREME
7.3.1. PRORAČUN EKPANZIJSKE POSUDE
PRIMAR – DIZALICA TOPLINE
SEKUNDAR
Količina vode u sustavu (L)
Cjevovod Kotao Ogrijevna
tijela
200 50 0
Ukupno VA= 250,00
Postotak širenja n(60°)= 1,71
Ve= 4,28 L -volumen širenja vode
VV= 1,25 L -volumen zalihe vode (min. 3 lit)
p0= 1 bar -primarni tlak ekspanzijske posude
pV= 3 bar -tlak sigurnosnog ventila
pe= 2,5 bar -projektni krajnji tlak
Vn,min= 16,98 L -volumen ekpanzijske posude
Odabrana je ekpanzijska posuda volumena 24 litre kao ELBI ERCE 24.
Količina vode u sustavu (L)
Cjevovod Kotao Ogrijevna
tijela
1065 500 130
Ukupno VA= 1695,00
Postotak širenja n(60°)= 1,71
Ve= 28,98 L -volumen širenja vode
VV= 8,48 L -volumen zalihe vode (min. 3 lit)
p0= 1 bar -primarni tlak ekspanzijske posude
pV= 3 bar -tlak sigurnosnog ventila
pe= 2,5 bar -projektni krajnji tlak
Vn,min= 87,41 L -volumen ekpanzijske posude
Odabrana je ekpanzijska posuda volumena 100 litara kao ELBI ERCE 100.
CALFACTIO j.d.o.o. za projektiranje i inženjering
GRAĐEVINA: Rekonstrukcija i dogradnja Elektrotehničke i prometne škole Osijek
LOKACIJA: Osijek, Istarska ulica 3, k.č.br. 5989/2 i 5989/9 k.o. Osijek
BROJ PROJEKTA: DATUM:
SP/66-19/IZ Listopad 2019.g
37
7.3.2. CIRKULACIJSKE CRPKE
7.3.2.1. PRIMAR – DIZALICA TOPLINE
Izabrana je cirkulaciona crpka kao Grundfos MAGNA 3 65-150 F ili jednakovrijedna, sa frekventnom
regulacijom.
7.3.2.2. SEKUNDAR – HLAĐENJE
Izabrana je cirkulaciona crpka kao Grundfos MAGNA 3 65-150 F ili jednakovrijedna, sa frekventnom
regulacijom.
Dio
nic
a
Duljina
Lζ Q Δϑ mkr NO w R L*R Z L*R+Z
sum(L*
R+Z)
(m) - (W) (°C) (kg/h) (m/s) (Pa/m) (Pa) (Pa) (Pa) (Pa)
1 28,00 14 147129 5 25343 100 110,0 / 15 1,41 302 8456 13882 22338 22338
22,3 kPa
18,7 kPa
51,7 kPa
Htot = 97,4 kPa
G = 25,65 m3/h
Cjevovod =
Chiller =
Izmjenjivač =
DEFINIRAJ PUMPU
Dionica PRIMAR (hlađenje)
Dv/S
(mm)
Dio
nic
a
Duljina
Lζ Q Δϑ mkr NO w R L*R Z L*R+Z
sum(L*
R+Z)
(m) - (W) (°C) (kg/h) (m/s) (Pa/m) (Pa) (Pa) (Pa) (Pa)
1 10,00 14 147129 5 25343 80 88,9 / 3,2 1,32 220 2200 12152 14352 14352
14,4 kPa
0 kPa
34,5 kPa
Htot = 51,3 kPa
G = 25,65 m3/h
(mm)
Cjevovod =
Chiller =
Izmjenjivač =
DEFINIRAJ PUMPU
Dionica SEKUNDAR (hlađenje)
Dv/S
CALFACTIO j.d.o.o. za projektiranje i inženjering
GRAĐEVINA: Rekonstrukcija i dogradnja Elektrotehničke i prometne škole Osijek
LOKACIJA: Osijek, Istarska ulica 3, k.č.br. 5989/2 i 5989/9 k.o. Osijek
BROJ PROJEKTA: DATUM:
SP/66-19/IZ Listopad 2019.g
38
7.3.2.3. SEKUNDAR – KRUG VENTILOKONVEKTORA
Izabrana je cirkulaciona crpka kao Grundfos MAGNA 3 65-120 F ili jednakovrijedna, sa frekventnom
regulacijom.
7.3.2.4. SEKUNDAR – KRUG RADIJATORA
Izabrana je cirkulaciona crpka kao Grundfos ALPHA2 25-40 130 ili jednakovrijedna, sa frekventnom
regulacijom.
Dio
nic
a
Duljina
Lζ Q Δϑ mkr NO w R L*R Z L*R+Z
sum(L*
R+Z)
(m) - (W) (°C) (kg/h) (m/s) (Pa/m) (Pa) (Pa) (Pa) (Pa)
1 15,00 10 4975 5 857 25 32,0 / 4,4 0,56 180 2700 1571 4271 4271
2 9,60 3 9950 5 1793 32 40,0 / 5,5 0,75 220 2112 854 2966 7237
3 9,30 3 14925 5 2689 40 50,0 / 6,9 0,73 155 1442 791 2232 9469
4 40,00 5 19900 5 3586 50 63,0 / 8,6 0,60 80 3200 915 4115 13584
5 8,00 3 72837 5 13124 80 90,0 / 12 1,09 210 1680 1768 3448 17032
6 8,00 3 105987 5 19097 100 110,0 / 15 1,06 208 1664 1689 3353 20385
7 18,00 5 147129 5 26510 100 110,0 / 15 1,47 320 5760 5425 11185 31570
31,6 kPa
19,8 kPa
5 kPa
Htot = 59,2 kPa
G = 27,05 m3/h
Sekundar - Ventilokonvektori
Dv/S
(mm)
Cjevovod =
Ogrijevno tiljelo =
Filter =
DEFINIRAJ PUMPU
Dio
nic
a
Duljina
Lζ Q Δϑ mkr NO w R L*R Z L*R+Z
sum(L*
R+Z)
(m) - (W) (°C) (kg/h) (m/s) (Pa/m) (Pa) (Pa) (Pa) (Pa)
1 17,50 12 1032 10 89 12 15,0 / 1 0,19 45 788 208 995 995
2 9,60 8 2062 10 178 12 15,0 / 1 0,37 150 1440 553 1993 2988
3 6,00 0 2492 10 215 15 18,0 / 1 0,30 85 510 0 510 3498
4 6,80 0 3180 10 274 15 18,0 / 1 0,38 120 816 0 816 4314
5 6,80 6 4298 10 370 20 22,0 / 1 0,33 75 510 321 831 5145
6 50,00 12 8200 10 706 25 32,0 / 4,4 0,46 200 10000 1292 11292 16437
16,4 kPa
7 kPa
0 kPa
Htot = 24,6 kPa
G = 0,72 m3/h
Izmjenjivač =
DEFINIRAJ PUMPU
Dv/S
(mm)
Cjevovod =
Ogrijevno tiljelo =
CALFACTIO j.d.o.o. za projektiranje i inženjering
GRAĐEVINA: Rekonstrukcija i dogradnja Elektrotehničke i prometne škole Osijek
LOKACIJA: Osijek, Istarska ulica 3, k.č.br. 5989/2 i 5989/9 k.o. Osijek
BROJ PROJEKTA: DATUM:
SP/66-19/IZ Listopad 2019.g
39
7.4. VENTILACIJA
U tablici se prikazuju odabrane ventilacijske jedinice za prisilno provjetravane prostorije i projektirani broj
izmjena zraka pojedine prostorije.
VENTILACIJA
Prizemlje
Br. Prostorija Način provjetravanja
Volumen
prostorije
Volumni
protok ventil. Jedinic
e
Broj izmjen
a zraka
Oznaka ventilacijske jedinice
(m3) (m3/h) h-1
1.01
Pneumatika i hidraulika
Prisilno s povratom topline
216,70 1000 4,61 LZ-H100GBA5
1.02
Automatika i robotika
Prisilno s povratom topline
224,50 1000 4,45 LZ-H100GBA5
1.03
Pogonska tehnika Prisilno s povratom
topline 218,40 1000 4,58 LZ-H100GBA5
1.04
Ulaz, hodnik, stubište Prisilno s povratom
topline 477,60 1000 2,09 LZ-H100GBA5
1.05
Kabinet 1 Prirodno 62,20 - 1,00 -
1.06
Obnovljivi izvori energije
Prisilno s povratom topline
215,50 1000 4,64 LZ-H100GBA5
1.07
Kabinet 2 Prirodno 62,20 - 1,00 -
1.08
Server soba Prirodno 51,90 - 0,50 -
1.09
Vratarnica Prirodno 17,40 - 0,50 -
1.10
Vjetrobran Prirodno 54,00 - 0,50 -
1.11
Stubište i dizalo Prirodno 95,80 - 0,50 -
1.12
Sanitarije 1 Prisilno 10,70 90 8,41 HELIOS MINIVENT
M1/100
1.13
Sanitarije 2 Prisilno 15,60 90 5,77 HELIOS MINIVENT
M1/100
1.14
Sanitarije 3 Prisilno 46,70 200 4,28 HELIOS MINIVENT
M1/150
1769,20 5380
CALFACTIO j.d.o.o. za projektiranje i inženjering
GRAĐEVINA: Rekonstrukcija i dogradnja Elektrotehničke i prometne škole Osijek
LOKACIJA: Osijek, Istarska ulica 3, k.č.br. 5989/2 i 5989/9 k.o. Osijek
BROJ PROJEKTA: DATUM:
SP/66-19/IZ Listopad 2019.g
40
1.kat
Br. Prostorija Način provjetravanja Volumen prostorij
e
Volumni protok ventil.
Jedinice
Broj izmjena zraka
Oznaka ventilacijske jedinice
2.01
Radionica Prisilno s povratom
topline 269,00 1000 3,72 LZ-H100GBA5
2.02
Maker space Prisilno s povratom
topline 172,00 800 4,65 LZ-H080GBA5
2.03
Dnevni prostor Prisilno s povratom
topline 149,90 500 3,34 LZ-H050GBA5
2.04
Soba 1 Prirodno 52,20 0,50 -
2.05
Sanitarije 1 Prisilno 8,80 60 6,82 EVOLUTION 10/4
2.06
Kabinet 1 Prirodno 62,80 - 1,00 -
2.07
Radionica 2 Prisilno s povratom
topline 269,00 1000 3,72 LZ-H100GBA5
2.08
Servis za popravak malih uređaja
Prisilno s povratom topline
140,40 500 3,56 LZ-H050GBA5
2.09
Stubište i dizalo Prirodno 130,80 - 0,50 -
2.10
Sanitarije 2 Prisilno 46,70 200 4,28 HELIOS MINIVENT
M1/150
2.11
Sanitarije 3 Prisilno 15,60 90 5,77 HELIOS MINIVENT
M1/100
2.12
Sanitarije 4 Prisilno 10,70 90 8,41 HELIOS MINIVENT
M1/100
2.13
Soba 2 Prirodno 43,30 - 0,50 -
2.14
Sanitarije 5 Prisilno 9,10 60 6,59 EVOLUTION 10/4
2.15
Soba 3 Prirodno 49,70 - 0,50 -
2.16
Sanitarije 6 Prisilno 8,80 60 6,82 EVOLUTION 10/4
2.17
Soba 4 Prirodno 43,30 - 0,50 -
2.18
Sanitarije 7 Prisilno 9,10 60 6,59 EVOLUTION 10/4
2.19
Hodnik i stubište
Prirodno 94,20 - 0,50 -
2.20
Hodnik Prirodno 196,70 - 0,50 -
1782,10 4420
CALFACTIO j.d.o.o. za projektiranje i inženjering
GRAĐEVINA: Rekonstrukcija i dogradnja Elektrotehničke i prometne škole Osijek
LOKACIJA: Osijek, Istarska ulica 3, k.č.br. 5989/2 i 5989/9 k.o. Osijek
BROJ PROJEKTA: DATUM:
SP/66-19/IZ Listopad 2019.g
41
2.kat
Br. Prostorija Način provjetravanja Volumen prostorij
e
Volumni protok ventil.
Jedinice
Broj izmjena zraka
Oznaka ventilacijske jedinice
3.01
Računalstvo Prisilno s povratom
topline 227,00 1000 4,41 LZ-H100GBA5
3.02
Računalstvo 2 Prisilno s povratom
topline 235,20 1000 4,25 LZ-H100GBA5
3.03
Tehničko crtanje i modeliranje
Prisilno s povratom topline
228,70 1000 4,37 LZ-H100GBA5
3.04
Kabinet 1 Prirodno 62,80 - 1,00 -
3.05
Računalstvo 3 Prisilno s povratom
topline 215,50 1000 4,64 LZ-H100GBA5
3.06
Studio Prisilno s povratom
topline 118,00 500 4,24 LZ-H050GBA5
3.07
Kabinet 2 Prirodno 64,10 - 1,00 -
3.08
Stubište i dizalo Prirodno 133,90 - 0,50 -
3.09
Sanitarije 1 Prisilno 46,70 200 4,28 HELIOS MINIVENT
M1/150
3.10
Sanitarije 2 Prisilno 15,60 90 5,77 HELIOS MINIVENT
M1/100
3.11
Sanitarije 3 Prisilno 10,70 90 8,41 HELIOS MINIVENT
M1/100
3.12
Soba 1 Prirodno 43,30 - 0,50 -
3.13
Sanitarije 4 Prisilno 8,80 60 6,82 EVOLUTION 10/4
3.14
Soba 2 Prirodno 43,30 - 0,50 -
3.15
Sanitarije 5 Prisilno 8,80 60 6,82 EVOLUTION 10/4
3.16
Soba 3 Prirodno 43,30 - 0,50 -
3.17
Sanitarije 6 Prisilno 8,80 60 6,82 EVOLUTION 10/4
3.18
Hodnik i stubište
Prirodno 130,80 - 0,50 -
3.19
Hodnik Prirodno 196,70 - 0,50 -
1842 5060
CALFACTIO j.d.o.o. za projektiranje i inženjering
GRAĐEVINA: Rekonstrukcija i dogradnja Elektrotehničke i prometne škole Osijek
LOKACIJA: Osijek, Istarska ulica 3, k.č.br. 5989/2 i 5989/9 k.o. Osijek
BROJ PROJEKTA: DATUM:
SP/66-19/IZ Listopad 2019.g
42
3.kat
Br. Prostorija Način provjetravanja
Volumen
prostorije
Volumni
protok ventil. Jedinic
e
Broj izmjen
a zraka
Oznaka ventilacijske jedinice
4.01 Konferencijska dvorana
Prisilno s povratom topline
445,10 1000
4,49 LZ-H100GBA5
1000 LZ-H100GBA5
4.02 Stubište i dizalo Prirodno 158,10 - 0,5 -
4.03 Sanitarije 1 Prisilno 11,20 90 8,04 HELIOS MINIVENT
M1/100
4.04 Sanitarije 2 Prisilno 31,40 130 4,14 AP3102 fi120
4.05 Sanitarije 3 Prisilno 25,00 130 5,20 AP3102 fi120
4.06 Foaje Prirodno 317,10 - 0,5 -
987,9 2320
Za prisilnu ventilaciju učionica odabrane ventilacijska jedinice horizontalne izvedbe sa pločastim unakrsnim
rekuperatorom sa ugrađenim bypassom, filterima na tlaku i odsisu, tlačnim i odsisnim ventilatorima,te svim
potrebnim elementima za zaštitu, kontrolu i regulaciju uređaja i temperature slijedečih karakteristika:
Proizvod LG LZ-H050GBA4
Tv = 34.5°C, 75 % RH
Tp = 26.5°C , 64.5 % RH
Tv= 7°C ST
Tp = 20°C ST
VZ = 500 m3/h
ESP = 150 / 100 / 50 Pa
Stupanj učink. (temp.): 78% /78% / 79%
Stupanj učink. (ental.- grijanje): 73% / 73% / 73%
Dimenzije: 988 x 1014 mm ; h = 273 mm
Težina: 44 kg
N = 240/220/90 W - 230 V - 50 Hz
Nivo zvučnog tlaka: 35/33/25 dB(A)
Priključak zraka: Ø200
Proizvod LG LZ-H080GBA4
Tv = 34.5°C, 75 % RH
Tp = 26.5°C , 64.5 % RH
Tv= 7°C ST
Tp = 20°C ST
VZ = 800 m3/h
ESP = 200 / 110 / 60 Pa
Stupanj učink. (temp.): 79% /79% / 82%
Stupanj učink. (ental.- grijanje): 72% / 72% / 74%
Dimenzije: 1062 x 1014 mm ; h = 365 mm
Težina: 62 kg
N = 390/280/187 W - 230 V - 50 Hz
Nivo zvučnog tlaka: 41/38/32 dB(A)
Priključak zraka: Ø250
CALFACTIO j.d.o.o. za projektiranje i inženjering
GRAĐEVINA: Rekonstrukcija i dogradnja Elektrotehničke i prometne škole Osijek
LOKACIJA: Osijek, Istarska ulica 3, k.č.br. 5989/2 i 5989/9 k.o. Osijek
BROJ PROJEKTA: DATUM:
SP/66-19/IZ Listopad 2019.g
43
Proizvod LG LZ-H100GBA4
Tv = 34.5°C, 75 % RH
Tp = 26.5°C , 64.5 % RH
Tv= 7°C ST
Tp = 20°C ST
VZ = 1000 m3/h
ESP = 160 / 90 / 50 Pa
Stupanj učink. (temp.): 77% /77% / 78%
Stupanj učink. (ental.- grijanje): 70% / 70% / 72%
Dimenzije: 1062 x 1014 mm ; h = 365 mm
Težina: 62 kg
N = 480/385/210 W - 230 V - 50 Hz
Nivo zvučnog tlaka: 41/38/32 dB(A)
Priključak zraka: Ø250
U Tenji, Listopad 2019.g.
Projektant:
Ivan Tomičić, mag.ing.mech.
CALFACTIO j.d.o.o. za projektiranje i inženjering
GRAĐEVINA: Rekonstrukcija i dogradnja Elektrotehničke i prometne škole Osijek
LOKACIJA: Osijek, Istarska ulica 3, k.č.br. 5989/2 i 5989/9 k.o. Osijek
BROJ PROJEKTA: DATUM:
SP/66-19/IZ Listopad 2019.g
44
5. PROGRAM KONTROLE I OSIGURANJA KVALITETE
Prema Zakonu o gradnji (NN RH br. 153/13, 20/17, 39/19) izrađen je program kontrole i osiguranja kvalitete.
a) Opći naputak
Sve projektirane strojarske instalacije moraju se izvesti prema važećim tehničkim propisima za ovu
vrstu radova i građevina.
Prilikom izvedbe moraju se upotrijebiti sva zaštitna sredstva, oprema i pribor pri čemu se poštuju
pravila zaštite na radu.
Svi radovi trebaju se izvesti sa stručnom radnom snagom, solidno i kvalitetno.
Za izvedbu će se upotrijebiti samo onaj materijal i oprema koji odgovaraju standardima.
Izvoditelj radova će prije početka radova proučiti projekt, usporediti sa postojećim stanjem, a za
eventualne izmjene i dopune projekta, izvođač će pribaviti suglasnost projektanta i nadzornog
inženjera.
Za sve ugrađene materijale i opremu izvoditelj će dostaviti ateste o ispravnosti istih.
b) Zapisnici i izvješća o ispitivanju instalacije grijanja/hlađenja
Tijekom izvođenja radova i poslije završetka radova na instalaciji grijanja potrebno je izvršiti tlačno
ispitivanje instalacije i ugrađene opreme. Tlačno ispitivanje instalacije (cjevovoda) koja se polaže u
pod i u šliceve u zidu obvezno izvršiti prije polaganja podne obloge i zažbukavanja zidnih šliceva. Po
završetku svih radova i ugradnje opreme, treba izvršiti tlačno ispitivanje, puštanje u rad uređaja od
strane ovlaštenog servisera, pregled odvoda dimnih plinova i dovoda svježeg zraka i funkcionalnu
probu. O svim ovim radnjama sačiniti zasebne zapisnike o ispitivanju.
c) Zapisnici i izvješća o ispitivanju instalacije ventilacije Po završetku radova na instalaciji ventilacije potrebno je izvršiti ispitivanje funkcionalnosti i
učinkovitosti ventilacijske instalacije i ugrađene opreme. Ispitivanje učinkovitosti instalacije izvršiti
od strane osobe ovlaštene za ispitivanje sustava ventilacije. Poslije ispitivanja sačiniti zasebne
zapisnike o ispitivanju.
Ispitivanje učinkovitosti sustava ventilacije mora izvršiti ovlaštena osoba koja izdaje potvrdu o
sukladnosti građevine s tehničkim zahtjevima za građevinu.
U Tenji, Listopad 2019.g.
Projektant:
Ivan Tomičić, mag.ing.mech.
CALFACTIO j.d.o.o. za projektiranje i inženjering
GRAĐEVINA: Rekonstrukcija i dogradnja Elektrotehničke i prometne škole Osijek
LOKACIJA: Osijek, Istarska ulica 3, k.č.br. 5989/2 i 5989/9 k.o. Osijek
BROJ PROJEKTA: DATUM:
SP/66-19/IZ Listopad 2019.g
45
6. POSEBNI TEHNIČKI UVIJETI GRADNJE I NAČIN ZBRINJAVANJA GRAĐEVNOG OTPADA
Ovi uvjeti reguliraju i specificiraju:
- prava, dužnost i obveze investitora, izvoditelja i projektanta ovim projektom tretiranog
postrojenja
- izbor, nabavu i izradu opreme specificirane u predračunu
- montažu, ispitivanje i preuzimanje projektiranog postrojenja
- garanciju za kvalitetu i funkcionalnost postrojenja.
Stavke iz ovih uvjeta treba dosljedno primjenjivati osim:
- ako nije drugačije precizirano ugovorom između investitora i izvoditelja radova
- ako nije drugačije regulirano Zakonom.
UGOVARANJE
- U skladu s postojećim zakonskim propisima investitora može na osnovu ovog projekta, kad je isti
revidiran i odobren od nadležnog organa, zaključiti ugovor o isporuci i montaži opreme i materijala pod
uobičajenim uvjetima za ovu vrstu radova.
- Investitor može zaključiti ugovor samo sa onim izvoditeljem koji je registriran za izvođenje radova
specificiranih predračunom ovog projekta, te da ima odgovarajuće reference.
- Prije sklapanja ugovora izvoditelj je dužan proučiti projektnu dokumentaciju, provjeriti rokove i
mogućnosti nabavke opreme i materijala, mogućnost transporta, te unošenje i montažu opreme većih
gabarita.
- U slučaju potrebe za promjenama u projektnoj dokumentaciji izvoditelj je dužan za to ishoditi i
pismenu suglasnost investitora i projektanta.
GARANCIJA
- Projektant garantira za funkcionalnost i ostvarenje projektiranih parametara postrojenja pod
uvjetima da se postrojenje izvede u okviru projektne dokumentacije.
- Izvoditelj daje garanciju za period preciziran ugovorom.
- Izvoditelj daje garanciju za kvalitetu radova, trajnost postrojenja, te ugrađenu opremu i materijal
koji nije atestiran ili nije pod garancijom proizvođača.
- Garancija ne vrijedi za dijelove postrojenja kod kojih je neispravnost nastupila zbog neispravnog
rukovanja, lošeg održavanja, kao ni za dijelove koji se troše u radu.
- Izvoditelj je dužan u garantnom roku otkloniti sve nedostatke na postrojenju, odnosno njenim
dijelovima za koje daje garanciju. Ukoliko izvoditelj to ne učini, investitora može otklanjanje
nedostataka povjeriti nekoj ovlaštenoj organizaciji, a na trošak izvoditelja.
PRIPREMA RADOVA
- Prije početka radova izvoditelj je dužan proučiti i provjeriti projektnu dokumentaciju, kontrolirati
kompletnost dokumentacije, te predložiti eventualno potrebne izmjene i dopune i o tome obavijestiti
investitora i projektanta.
- Izvoditelj je dužan provjeriti da li se radovi mogu izvesti prema projektu, da li na mjestu gdje je
predviđeno postavljanje projektiranog postrojenja već postoji neko drugo postrojenje koje ne dopušta da
se radovi izvedu prema projektu.
CALFACTIO j.d.o.o. za projektiranje i inženjering
GRAĐEVINA: Rekonstrukcija i dogradnja Elektrotehničke i prometne škole Osijek
LOKACIJA: Osijek, Istarska ulica 3, k.č.br. 5989/2 i 5989/9 k.o. Osijek
BROJ PROJEKTA: DATUM:
SP/66-19/IZ Listopad 2019.g
46
- Također je izvoditelj dužan prije početka radova provjeriti stanje građevinskih i drugih radova
(stupanj izvedenosti) kao i građevinske izmjene vezane za postavljanje strojarskog postrojenja.
RADOVI
- Izvoditelj postrojenja dužan je iste izvesti tako da budu funkcionalne, trajne i kvalitetne. Radovi se
moraju izvoditi u skladu s postojećim tehničkim propisima, normativima i standardima.
- U koliko izvoditelj utvrdi da će uslijed eventualnih grešaka u projektnoj dokumentaciji ili pogrešnih
uputa od strane investitora, odnosno njegovog nadzornog organa, radovi biti izvedeni na umanjenu
trajnosti, kvalitete ili funkcionalnosti postrojenja, dužan je o tome izvijestiti investitora, da ovaj prekine
započete radove. Ako investitora to ne učini, snosi punu odgovornost za nastalu štetu.
- Ako izvoditelj odstupi od projektne dokumentacije bez suglasnosti projektanta ili nadzornog organa
investitora snosi punu odgovornost za funkcioniranje i trajnost postrojenja.
- Izvoditelj radova mora uredno voditi montažni dnevnik i montažnu knjigu, koje po završetku radova
ovjerava i obostrano potpisane predaje investitora.
- Za izvođenje naknadnih radova koji nisu obuhvaćeni ugovorom, izvoditelj je dužan investitora
podnijeti pismeni zahtjev, uz koji prilaže odgovarajuću tehničku dokumentaciju kojom se ti radovi
specificiraju.
OPREMA
- U projektirano postrojenje izvoditelj je dužan ugraditi opremu specificiranu projektnom
dokumentacijom ili neku drugu, ali karakteristike koje odgovaraju zahtjevima navedenim u istoj.
- Potrebno je strogo pridržavati se uputa za transport i rukovanje opremom, koje daje proizvođač.
- Kod zaprimanja opreme vrši se vizualna kontrola iste. O uočenim nedostacima sastavlja se zapisnik
koji potpisuje izvoditelj i prijevoznik. O tome se obavještava investitora i isporučitelj opreme.
- Nije dozvoljena ugradnja neispravne opreme, osim ako se popravak može izvršiti i onda kada je ista
već ugrađena i ako to ne ide na umanjenje održavanja roka za montažu postrojenja.
- Garanciju za trajnost i funkcionalnost opreme daje proizvođač.
IZVEDBENA I OSTALA DOKUMENTACIJA
- Izvedbenu dokumentaciju dužan je izvoditelj prilagoditi ugrađenoj opremi.
- Radioničku dokumentaciju, ukoliko je ista potrebna, daje izvoditelj radova.
- Izvoditelj je dužan u projekt unijeti sve izmjene i dopune stvarnog stanja nastale tijekom radova.
NADZOR NAD IZVEDBOM
Investitor je dužan angažirati stručnu osobu za nadgledanje radova.
PREUZIMANJE POSTROJENJA
- Nakon dovršene montaže, izvršenih ispitivanja te balansiranja i reguliranja postrojenja i probnog
pogona izvoditelj daje investitora zahtjev za primopredaju postrojenja.
- Investitor je dužan da u roku od 8 dana od dobivanja zahtjeva (sa priloženim kopijama zapisnika o
izvršenim ispitivanjima) sastavi komisiju koja će u njegovo ime od izvoditelja preuzeti postrojenje.
CALFACTIO j.d.o.o. za projektiranje i inženjering
GRAĐEVINA: Rekonstrukcija i dogradnja Elektrotehničke i prometne škole Osijek
LOKACIJA: Osijek, Istarska ulica 3, k.č.br. 5989/2 i 5989/9 k.o. Osijek
BROJ PROJEKTA: DATUM:
SP/66-19/IZ Listopad 2019.g
47
- Izvoditelj je dužan prilikom primopredaje uručiti investitora uputu za rukovanje postrojenjem, u dva
primjerka od kojih jedan treba postaviti na pogodno mjestu u prostoriji iz koje se rukuje postrojenjem.
- Na zahtjev investitora izvoditelj je dužan obučiti osoblje koje će rukovati postrojenjem kad je
investitora preuzme, a troškovi obuke padaju na teret investitora.
- Troškove pogonskog medija i energije za potrebe ispitivanja regulacije i probnog pogona snosi
investitora.
- Troškove primopredaje komisije u cijelosti snosi investitor.
TEHNIČKI UVJETI ZA IZVOĐENJE
Odabrana oprema i materijali za instalaciju moraju imati odgovarajuće ateste o kvaliteti i označenim
tehničkim podacima, te se samo tako mogu ugraditi.
Montažne radove mogu vršiti samo osobe i pravna lica sa dokumentiranom kvalifikacijom i
odgovarajućim atestima za takovu vrstu radova.
Nakon montaže kompletne instalacije i uređaja potrebno je izvršiti tlačne probe, mjerenje zadanih
veličina, probni rad i regulaciju, kako je dano u tehničkom opisu.
Kompletna instalacija i ugrađena oprema mora biti korozivno zaštićena, ovješena i omogućena
toplinska dilatacija.
Uzimajući u obzir sve navedeno, projektom predviđena instalacija i uređaji, pravilnom montažom,
ispitivanjem i regulacijom mora zadovoljavati potrebnu kvalitetu pri korištenju.
NAČIN ZBRINJAVANJA GRAĐEVINSKOG OTPADA
Na temelju “Zakona o gradnji" za ovu vrstu građevinskih radova potrebito je napraviti slijedeće:
- Nakon završetka radova sav građevinski otpad propisno zbrinuti na najbližu deponiju u skladu s
važećim propisima o zbrinjavanju građevinskog otpada.
U Tenji, Listopad 2019.g.
Projektant:
Ivan Tomičić, mag.ing.mech.
CALFACTIO j.d.o.o. za projektiranje i inženjering
GRAĐEVINA: Rekonstrukcija i dogradnja Elektrotehničke i prometne škole Osijek
LOKACIJA: Osijek, Istarska ulica 3, k.č.br. 5989/2 i 5989/9 k.o. Osijek
BROJ PROJEKTA: DATUM:
SP/66-19/IZ Listopad 2019.g
48
IZVEDBENI PROJEKT: STROJARSKI PROJEKT - GRIJANJE, HLAĐENJE I VENTILACIJA
INVESTITOR: Elektrotehnička i prometna škola Osijek, Osijek, Istarska ulica 3
GRAĐEVINA: Rekonstrukcija i dogradnja Elektrotehničke i prometne škole Osijek
ADRESA: Osijek, Istarska ulica 3 k.č.br. 5989/2 i 5989/9 k.o. Osijek
7. NACRTI
5989/4
P
r
o
la
z
J
u
lija
K
n
ife
r
a
k
o
ln
i p
ris
tu
p
5989/9
5989/2
5989/10
5989/4
± 0.00
P+3
P+2
- 0.557
,3
%
A
A
- 0.55
B
PROJEKTANT: IVAN TOMIČIĆ, mag.ing.mech.
NACRT:
PROJEKT:
LOKACIJA:
INVESTITOR:
GRAĐEVINA:
BR.PROJ:
ZOP:
DATUM:
MJERILO:1:500
LIST:
VRSTA
PROJEKTA:
C A L F A C T I Oj . d . o . o . z a p r o j e k t i r a n j e i i n ž e n j e r i n g
3 1 2 0 7 T e n j a , J a n a P a n n o n i u s a 2 4O I B : 9 5 0 3 2 6 9 4 0 1 8M o b : 0 9 9 / 3 0 1 - 8 1 9 7e - m a i l : c a l f a c t i o . o s @ g m a i l . c o m
Osijek, Istarska ulica 3, k.č.br. 5989/2 i 5989/9 k.o. Osijek
Elektrotehnička i prometna škola Osijek, OIB: 28015293209
Rekonstrukcija i dogradnja elektrotehničke i prometne škole
SP/66-19/IZ
BP-IZV 01/2019
1
SITUACIJA
STROJARSKI PROJEKT - GRIJANJE, HLAĐENJE I
VENTILACIJA
LISTOPAD 2019.G.
S
LEGENDA:
1. Dizalica topline zrak-voda, kao LG ACHH050LBAB, Qh=171 kW, Qg=180 kW,
N=55,2kW/400 V~50 Hz, T=1530 kg, na betonskom postolju visine 30cm.
2. Spojni cjevovod dizalice topline i strojarnice, predizolirana cijev kao Uponor
Ecoflex Thermo Single, 2x Ø110x15,1mm PN10
12
Povratni cjevovod grijanja/hlađenja
Polazni cjevovod grijanja/hlađenja
NAPOMENE:
- Cjevovodi grijanja/hlađenja od dizalice topline do strojarnice se izvode iz predizoliranih PE-Xa cijevi kao Uponor Ecoflex
Thermo s izolacijom iz umreženog polietilena i zaštitnom cijevi iz PE-HD
- Spojni cjevovod se izvodi od spoja s dizalicom topline do ulaska u prostor strojarnice u prizemlju zgrade, u zemlji na dubini
minimalno 80cm.
- cjevovod se polaže u rov na posteljicu od sloja pijeska min. 10cm, te se zatrpava slojem pijeska iznad tjemena cijevi debljine
min. 15cm, zatim se zatrpava zemljom od iskopa u slojevima od 30cm uz nabijanje
- Ne preporučuje se polaganje cijev pri temperaturama nižim od -15°C
- Vrelovodni priključak indirektne kompaktne toplinske podstanice K-250 nije predmet ovog projekta
SURADNIK: SLAVEN HOFER, stroj.teh.
IZVEDBENI PROJEKT
- 1.01 -
Pneumatika i hidraulika
68.8 m2 216.7 m3
20 °C 4716 W
- 1.02 -
Automatika i robotika
71.3 m2 224.5 m3
20 °C 4203 W
- 1.03 -
Pogonska tehnika
69.3 m2 218.4 m3
20 °C 4053 W
- 1.04 -
Ulaz, hodnik, stubište
156.6 m2 477.6 m3
20 °C 7281 W
- 1.05 -
Kabinet 1
20.4 m2 64.3 m3
20 °C 2005 W
- 1.06 -
Obnovljivi izvori energije
68.4 m2 215.5 m3
- 1.07 -
Kabinet 2
20.4 m2 64.4 m3
- 1.08 -
Server soba
- 1.09 -
Vratarnica
5.7 m2 17.8 m3
26 °C 519 W
- 1.10 -
Vjetrobran
17.4 m2 54.8 m3
26 °C 2195 W
- 1.11 -
Stubište i dizalo
31.4 m2 95.8 m3
26 °C 1468 W
- 1.12 -
Sanitarije 1
3.5 m2 10.7 m3
- 1.13 -
Sanitarije 2
5.1 m2 15.6 m3
- 1.14 -
Sanitarije 3
15.3 m2 46.7 m3
26 °C 6469 W 26 °C 5186 W 26 °C 5766 W26 °C 5548 W
26 °C 1931 W
20 °C 4832 W20 °C 1519 W
9.0 m2 28.4 m3
20 °C 678 W
26 °C 26 °C1039 W 5614 W
20 °C 1464 W20 °C 1546 W
15 °C -53 W 15 °C 111 W 15 °C 767 W
VCE18Qg=810 W (1.brz)Qh=893 WN=37W/220 V~50 HzT=14,1 kg
VCE28Qg=1650 W (3.brz)Qh=1685 WN=55W/220 V~50 HzT=17,2 kg
LIGHT-ECM 63 RCQg=4910 W (3.brz)Qh=4247WN=63W/220 V~50 HzT=26 kg
LIGHT-ECM 63 RCQg=4910 W (3.brz)Qh=4247WN=63W/220 V~50 HzT=26 kg
VaiR
AD
11 V
600/400
12
RZ 1 - 1. (2)
KORATHERM VERTIKAL K20VM 1200/884
16x2,2
16x2,2
16x2,2
Ø3
2x4
,4
Ø25x3,5
Ø2
0x2
,8
Ø32x4,4
Ø3
2x4
,4
Ø2
0x2
,8
Ø2
5x3
,5
Ø2
5x3
,5
LIGHT-ECM 63 RCQg=2510 W (1.brz)Qh=4247WN=63W/220 V~50 HzT=26 kg
Ø32x4,4
3000 W26 °C
VCE38Qg=2330 W (3.brz)Qh=2599 WN=61W/220 V~50 HzT=22 kg
Ø1
10
x1
5,1
Ø3
2x4
,4
DN
65
Ø5
0x6
,9
Ø6
3x8
,6
Ø6
3x8
,6
Ø6
3x8
,6
Ø6
3x8
,6
Ø75x10,3
u podu
DN
80
Vrelovod polaz
Vrelovod povratiz dizalice topline
PE-Xa Ø110x15,1
u zemlji
2x Ø110x15,1
2x Ø32x4,4
LIGHT-ECM 62 RCQg=2300 W (1.brz)Qh=2667 WN=43W/220 V~50 HzT=21 kg
LIGHT-ECM 61 RCQg=1900 W (1.brz)Qh=2223 WN=48W/220 V~50 HzT=20 kg
V2 - Ø32
Spoj odvoda kondenzata
na kanalizacijsku vertikalu
u sifonskoj izvedbi
LIGHT-ECM 63 RCQg=3522 W (2.brz)Qh=4247WN=26W/220 V~50 HzT=26 kg
LIGHT-ECM 63 RCQg=3522 W (2.brz)Qh=4247WN=26W/220 V~50 HzT=26 kg
Ø32x4,4
Ø32x4,4
Ø25 - i=0,5%
Ø25 - i=0,5%
Ø32 - i=
0,5%
V5 - Ø32
LIGHT-ECM 63 RCQg=3522 W (2.brz)Qh=4247WN=26W/220 V~50 HzT=26 kg
LIGHT-ECM 63 RCQg=3522 W (2.brz)Qh=4247WN=26W/220 V~50 HzT=26 kg
Ø32x4,4Ø32x4,4
Ø25 - i=0,5%
Ø25 - i=0,5%
Ø32 - i=
0,5%
V4 - Ø32
LIGHT-ECM 63 RCQg=3522 W (2.brz)Qh=4247WN=26W/220 V~50 HzT=26 kg
LIGHT-ECM 63 RCQg=3522 W (2.brz)Qh=4247WN=26W/220 V~50 HzT=26 kg
Ø25 - i=0,5%
Ø25 - i=0,5%
Ø32 - i=
0,5%
V3 - Ø32
Ø3
2x4
,4
Ø40x5,5
LIGHT-ECM 63 RCQg=2510 W (1.brz)Qh=4247WN=63W/220 V~50 HzT=26 kg
LIGHT-ECM 63 RCQg=2510 W (1.brz)Qh=4247WN=63W/220 V~50 HzT=26 kg
Ø40x5,5
Ø3
2x4
,4
V1 - Ø32
Ø25 - i=0,5%
Ø32 - i=
0,5%
Ø25 - i=0,5%
Ø25 - i=0,5%
u podu
Ø25 - i=
0,5%
Ø25 - i=0,5%
u podu
V6 - Ø25
Ø25x3,5
Ø25x3,5
Ø25 - i=0,5% Ø25 - i=0,5% Ø25 - i=0,5%
Ø25 - i=0,5%
Spoj odvoda kondenzata
na kanalizacijsku vertikalu
u sifonskoj izvedbi
Ø32 - i=0,5%
Ø25 - i=0,5%
Ø25 - i=
0,5%
Ø25 - i=
0,5%
Ø25 - i=
0,5%
Ø40 - i=0,5%
Ø40 - i=0,5%
Ø25 - i=
0,5%
PROJEKTANT: IVAN TOMIČIĆ, mag.ing.mech.
NACRT:
PROJEKT:
LOKACIJA:
INVESTITOR:
GRAĐEVINA:
BR.PROJ:
ZOP:
DATUM:
MJERILO:1:50
LIST:
VRSTA
PROJEKTA:
C A L F A C T I Oj . d . o . o . z a p r o j e k t i r a n j e i i n ž e n j e r i n g
3 1 2 0 7 T e n j a , J a n a P a n n o n i u s a 2 4O I B : 9 5 0 3 2 6 9 4 0 1 8M o b : 0 9 9 / 3 0 1 - 8 1 9 7e - m a i l : c a l f a c t i o . o s @ g m a i l . c o m
Osijek, Istarska ulica 3, k.č.br. 5989/2 i 5989/9 k.o. Osijek
Elektrotehnička i prometna škola Osijek, OIB: 28015293209
Rekonstrukcija i dogradnja elektrotehničke i prometne škole
SP/66-19/IZ
BP-IZV 01/2019
2
TLOCRT PRIZEMLJA - GRIJANJE I
HLAĐENJE
STROJARSKI PROJEKT - GRIJANJE, HLAĐENJE I
VENTILACIJA
LISTOPAD 2019.G.
S
Povratni cjevovod grijanja/hlađenja
Polazni cjevovod grijanja/hlađenja
LEGENDA:
1. Indirektna kompaktna toplinska podstanica, tip K-250 proizvođača MontMontaža-Oprema d.o.o.
2. Ekspanzijski uređaj s jednom crpkom tip EU 200-A-I "Pireko" Oroslavlje
3. Izolirani inercijski međuspremnik 500 lit, sa odzrakom i ispustom
4. Rastavljivi pločasti međuizmjenjivač, kao ALFA-LAVAL TL6-BFM
5. Ekspanzijska posuda, 100 lit, 3bar
6. Razdjelnik/sabirnik NO150, sa jednim priključkom DN100 na polazu i povratu, jednim priključkom
DN25 na polazu i povratu, priključak sa međuspremnika DN80.
7. Cirkulacijske crpke, prema shemi sustava grijanja/hlađenja
VCEx8 - Ventilokonvektor, za rad s optočnim zrakom, parapetni, s maskom, dvocijevne izvedbe, kao
VENTILCLIMA tip VCE x8, snaga grijanja i hlađenja iskazana na nacrtu
LIGHT-ECM 6x - Ventilokonvektor, za rad s optočnim zrakom, kazetni, za ugradnju u spušteni strop, s
maskom, dvocijevne izvedbe, kao VENTILCLIMA tip LIGHT-ECM 6x, snaga grijanja i hlađenja
iskazana na nacrtu
Oznaka prostorije
Naziv prostorije
Volumen prostorije
Gubici topline
Površina prostorije
Projektirana temperatura prostorije (zima)
Odvod kondenzata
NAPOMENE:
VENTILOKONVEKTORI
- Predviđena je montaža dvocijevnog sustava grijanja 50/40°C, odnosno hlađenja 7/12°C
- Cjevovodi grijanja/hlađenja se izvode iz kompozitnih PPR cijevi ojačanih staklenim vlaknima, za sustave grijanja/hlađenja, sa izolacijom s parnom branom debljine
13mm.
- Cjevovodi unutar strojarnice se izvode iz čeličnih cijevi za sustave grijanja/hlađenja,sa izolacijom s parnom branom debljine 20mm
- Sve dionice dvocijevnog sustava vode se u spuštenom stropu i instalacijskim nišama
- Međusobno spajanje cijevi i adekvatnih fitinga polifuzijskim zavarivanjem
- Svi prolazi cjevovoda preko razdvojenih dilatacija (fuga) zgrade moraju se položiti u zaštitnu cijev. Ova se zaština mjera provodi i kod prolaza cijevi kroz zid ili strop,
kao i kod izlaza cijevi iz poda (npr. kod priključenja ogrjevnih tijela)
- Zbog značajnih toplinskih dilatacija izvođač treba osobitu pozornost posvetiti čvrstim točkama te osigurati kompenzacijske lire na potrebnim mjestima
- Izvođač se mora u svemu strogo pridržavati uputa proizvođača opreme
- Svi prolazi kroz stropove i zidove objekta izvode se uporabom proturnih zaštitnih cijevi
- Odvod kondenzata sa ventilokonvektora izvesti u spuštenom strop do spoja na odvod umivaonika
- U spuštenom stropu pored kazetnog ventilokonvektora ugraditi revizijski otvor prema uputama proizvođača ventilokonvektora
RADIJATORSKO GRIJANJE
- Za grijanje toaleta i kupaonica izvodi se dvocijevni sustav radijatorskog grijanja iz kompozitnih PPR-cijevi (od strojarnice do etažnih razdjelnika), te iz PE-Xa cijevi
od etažnih razdjelnika do radijatora; ogrijevna tijela su čelični pločasti kompaktni ventilski radijatori tipa 11 i 22V, čelični pločasti ventilski vertikalni radijatori kao
Koratherm Vertikal K20VM, i u kupaniocama kupaonski cijevni sušači ovješeni na zid standarnim ovjesnim priborom, opremljeni termostatskim ventilom sa
termostatskom glavom na polaznom vodu i radijatorskom prigušnicom na povratnom vodu.
Predviđena je montaža dvocijevnog sustava 60/45°C iz višeslojnih PE-Xa cijevi sa centralnim etažnim razdjelnikom krugova grijanja
Sve dionice dvocijevnog sustava položene u cementnom estrihu s toplinskom izolacijom cjevovoda sukladno važećim propisima
Međusobno spajanje cijevi i adekvatnih fitinga tehnikom spajanja tzv. “pomičnom navlakom”
Svi prolazi cjevovoda preko razdvojenih dilatacija (fuga) zgrade moraju se položiti u zaštitnu cijev. Ova se zaština mjera provodi i kod prolaza cijevi kroz zid ili strop,
kao i kod izlaza cijevi iz cementne podloge (npr. kod priključenja ogrjevnih tijela)
Zbog značajnih toplinskih dilatacija izvođač treba osobitu pozornost posvetiti čvrstim točkama te osigurati kompenzacijske lire na potrebnim mjestima
Na oko 1.5 m ispred grijaćeg tijela potrebno je postaviti cijevnu liru, čime se amortiziraju sile zatezanja i pritiska
Izvođač se mora u svemu strogo pridržavati uputa proizvođača opreme
Građevinski radovi uz polaganje cijevnog razvoda (zalijevanje cementnog estriha) u svemu prema važećim standardima i tehničkoj praksi postavljanja
Svi prolazi kroz stropove i zidove objekta izvode se uporabom proturnih cijevi
- 1.06 -
Obnovljivi izvori energije
68.4 m2 215.5 m3
20 °C 4832 W
26 °C 5614 W
Projektirana temperatura prostorije (ljeto)
Dobici topline
1
2
34
5
6 7
SURADNIK: SLAVEN HOFER, stroj.teh.
IZVEDBENI PROJEKT
1000x594m
m
12
KORATHERM VERTIKAL K20VM 1200/884
Ø1
10
x1
5,1
Ø3
2x4
,4
DN
65
Ø75x10,3
DN
80
Vrelovod polaz
Vrelovod povratiz dizalice topline
PE-Xa Ø110x15,1
u zemlji
2x Ø110x15,1
2x Ø32x4,4
PROJEKTANT: IVAN TOMIČIĆ, mag.ing.mech.
NACRT:
PROJEKT:
LOKACIJA:
INVESTITOR:
GRAĐEVINA:
BR.PROJ:
ZOP:
IZVEDBENI PROJEKT
DATUM:
MJERILO:1:50
LIST:
VRSTA
PROJEKTA:
C A L F A C T I Oj . d . o . o . z a p r o j e k t i r a n j e i i n ž e n j e r i n g
3 1 2 0 7 T e n j a , J a n a P a n n o n i u s a 2 4O I B : 9 5 0 3 2 6 9 4 0 1 8M o b : 0 9 9 / 3 0 1 - 8 1 9 7e - m a i l : c a l f a c t i o . o s @ g m a i l . c o m
Osijek, Istarska ulica 3, k.č.br. 5989/2 i 5989/9 k.o. Osijek
Elektrotehnička i prometna škola Osijek, OIB: 28015293209
Rekonstrukcija i dogradnja elektrotehničke i prometne škole
SP/66-19/IZ
BP-IZV 01/2019
3
TLOCRT PRIZEMLJA - STROJARNICA
STROJARSKI PROJEKT - GRIJANJE, HLAĐENJE I
VENTILACIJA
LISTOPAD 2019.G.
S
1
3
Povratni cjevovod grijanja/hlađenja
Polazni cjevovod grijanja/hlađenja
LEGENDA:
1. Indirektna kompaktna toplinska podstanica, tip K-250 proizvođača MontMontaža-Oprema d.o.o.
2. Ekspanzijski uređaj s jednom crpkom tip EU 200-A-I "Pireko" Oroslavlje (sekundar - toplinska stanica)
3. Izolirani inercijski međuspremnik 500 lit, sa odzrakom i ispustom
4. Rastavljivi pločasti međuizmjenjivač, kao ALFA-LAVAL TL6-BFM
5. Ekspanzijska posuda, 100 lit, 3bar - sekundar (grijanje/hlađenje)
6. Ekspanzijska posuda, 24 lit, 3bar - primar (dizalica topline)
7. Razdjelnik/sabirnik NO150, sa jednim priključkom DN100 na polazu i povratu, jednim priključkom
DN25 na polazu i povratu, priključak sa međuspremnika DN80.
8. Cirkulacijske crpke, prema shemi sustava grijanja/hlađenja
9. Spremnik PTV-a, 1000 litara, sa elektrogrijačem 20kW
8
2
9
4567
SURADNIK: SLAVEN HOFER, stroj.teh.
- 2.01 -
Radionica
85.4 m2 269.0 m3
20 °C 5577 W
- 2.02 -
Maker space
54.6 m2 172.0 m3
20 °C 3739 W
- 2.03 -
Dnevni prostor
47.6 m2 149.9 m3
20 °C 2100 W
- 2.04 -
Soba 1
17.2 m2 54.3 m3
20 °C 657 W
- 2.05 -
Sanitarije 1
2.9 m2 9.1 m3
24 °C 397 W
- 2.06 -
Kabinet 1
20.6 m2 64.8 m3
26 °C 1885 W
- 2.07 -
Radionica 2
85.4 m2 269.0 m3
- 2.08 -
Servis za popravak malih uredaja
44.6 m2 140.4 m3
- 2.09 -
Stubište i dizalo
42.9 m2 135.1 m3
26 °C 2497 W
- 2.10 -
Sanitarije 2
15.3 m2 46.7 m3
15 °C 696 W
- 2.11 -
Sanitarije 3
5.1 m2 15.6 m3
15 °C 81 W
- 2.12 -
Sanitarije 4
3.5 m2 10.7 m3
- 2.13 -
Soba 2
14.2 m2 44.7 m3
- 2.14 -
Sanitarije 5
5.4 m2 16.9 m3
24 °C 571 W
- 2.15 -
Soba 3
16.3 m2 51.5 m3
- 2.16 -
Sanitarije 6
2.9 m2 9.1 m3
24 °C 452 W
- 2.17 -
Soba 4
14.2 m2 44.7 m3
26 °C 711 W
- 2.18 -
Sanitarije 7
8.6 m2 26.9 m3
24 °C 721 W
- 2.19 -
Hodnik i stubište
30.9 m2 97.2 m3
20 °C 1296 W
- 2.20 -
Hodnik
66.4 m2 209.1 m3
26 °C 2591 W
26 °C 829 W 26 °C 2499 W 26 °C 4714 W 26 °C 7178 W
20 °C 1907 W
20 °C 2175 W
26 °C 895 W
20 °C 5654 W20 °C 2493 W20 °C 2143 W
26 °C 4042 W 26 °C 6149 W
20 °C 492 W
20 °C 533 W
20 °C 426 W
26 °C 719 W
26 °C 724 W
LIGHT-ECM 62 RCQg=2300W (1.brz)Qh=2667WN=11W/220 V~50 HzT=21 kg
LIGHT-ECM 61 RCQg=2300 W (2.brz)Qh=2223 WN=48W/220 V~50 HzT=23 kg
LIGHT-ECM 63 RCQg=3522 W (2.brz)Qh=4247WN=63W/220 V~50 HzT=26 kg
LIGHT-ECM 63 RCQg=3522 W (2.brz)Qh=4247WN=63W/220 V~50 HzT=26 kg
VaiR
AD
11 V
600/400
Kupaonski radijator 1810/750
654321
RZ 2 - 2. (6)
Kupaonski radijator 1810/750Kupaonski radijator 1810/750
KORATHERM VERTIKAL K20VM 1200/884
KORALUX LINEAR MAX 1810/750
Ø32x4,4
Ø5
0x6
,9
Ø40x5,5
Ø2
5x3
,5
Ø2
0x2
,8
16x2,2
25x3,5
16x2,2
16x2,2
LIGHT-ECM 63 RCQg=3522 W (2.brz)Qh=4247WN=26W/220 V~50 HzT=26 kg
LIGHT-ECM 63 RCQg=3522 W (2.brz)Qh=4247WN=26W/220 V~50 HzT=26 kg
LIGHT-ECM 64 RCQg=4150 W (2.brz)Qh=4975WN=45W/220 V~50 HzT=26 kg
VCE18Qg=810 W (1.brz)Qh=893 WN=37W/220 V~50 HzT=14,1 kg
LIGHT-ECM 62 RCQg=2300W (1.brz)Qh=2667WN=11W/220 V~50 HzT=21 kg
LIGHT-ECM 63 RCQg=2510 W (1.brz)Qh=4247WN=63W/220 V~50 HzT=26 kg
VCE48Qg=2600 W (3.brz)Qh=2769 WN=61W/220 V~50 HzT=22 kg
VCE18Qg=810 W (1.brz)Qh=893 WN=37W/220 V~50 HzT=14,1 kg
VCE18Qg=810 W (1.brz)Qh=893 WN=37W/220 V~50 HzT=14,1 kg
VCE18Qg=810 W (1.brz)Qh=893 WN=37W/220 V~50 HzT=14,1 kg
VCE38Qg=2330 W (3.brz)Qh=2599 WN=61W/220 V~50 HzT=22 kg
2x Ø110x15,1
Ø32x4,4
Ø32x4,4
Ø32x4,4
Ø32x4,4
Ø32x4,4
Ø32x4,4
Ø2
5x3
,5
Ø25x3,5
Ø4
0x5
,5
Ø6
3x8
,6
Ø5
0x6
,9
Ø6
3x8
,6
Ø25x3,5
Ø2
5x3
,5
u podu
u podu
Ø2
5x3
,5
Ø6
3x8
,6
Ø75x10,3
2x Ø32x4,4
Ø32 - i=0,5% Ø32 - i=0,5%
Ø25 - i=0,5%
Spoj odvoda kondenzata
na kanalizacijsku vertikalu
u sifonskoj izvedbi
Ø32 - i=0,5%
V3 - Ø32 V4 - Ø32 V5 - Ø32
V1 - Ø32V2 - Ø32
Ø32 - i=
0,5%
Ø25 - i=0,5%
Ø25 - i=0,5%
Ø25 - i=
0,5%
Ø25 - i=0,5%
Ø25 - i=0,5%
Ø25 - i=0,5%
Ø25 - i=0,5%
Ø25 - i=0,5%
Ø25 - i=0,5% Ø25 - i=0,5%
Spoj odvoda kondenzata
na kanalizacijsku vertikalu
u sifonskoj izvedbi
PROJEKTANT: IVAN TOMIČIĆ, mag.ing.mech.
NACRT:
PROJEKT:
LOKACIJA:
INVESTITOR:
GRAĐEVINA:
BR.PROJ:
ZOP:
DATUM:
MJERILO:1:50
LIST:
VRSTA
PROJEKTA:
C A L F A C T I Oj . d . o . o . z a p r o j e k t i r a n j e i i n ž e n j e r i n g
3 1 2 0 7 T e n j a , J a n a P a n n o n i u s a 2 4O I B : 9 5 0 3 2 6 9 4 0 1 8M o b : 0 9 9 / 3 0 1 - 8 1 9 7e - m a i l : c a l f a c t i o . o s @ g m a i l . c o m
Osijek, Istarska ulica 3, k.č.br. 5989/2 i 5989/9 k.o. Osijek
Elektrotehnička i prometna škola Osijek, OIB: 28015293209
Rekonstrukcija i dogradnja elektrotehničke i prometne škole
SP/66-19/IZ
BP-IZV 01/2019
4
TLOCRT 1.KATA - GRIJANJE I
HLAĐENJE
STROJARSKI PROJEKT - GRIJANJE, HLAĐENJE I
VENTILACIJA
LISTOPAD 2019.G.
S
Povratni cjevovod grijanja/hlađenja
Polazni cjevovod grijanja/hlađenja
LEGENDA:
VCEx8 - Ventilokonvektor, za rad s optočnim zrakom, parapetni, s maskom, dvocijevne izvedbe, kao
VENTILCLIMA tip VCE x8, snaga grijanja i hlađenja iskazana na nacrtu
LIGHT-ECM 6x - Ventilokonvektor, za rad s optočnim zrakom, kazetni, za ugradnju u spušteni strop, s
maskom, dvocijevne izvedbe, kao VENTILCLIMA tip LIGHT-ECM 6x, snaga grijanja i hlađenja
iskazana na nacrtu
Oznaka prostorije
Naziv prostorije
Volumen prostorije
Gubici topline
Površina prostorije
Projektirana temperatura prostorije (zima)
Odvod kondenzata
NAPOMENE:
VENTILOKONVEKTORI
- Predviđena je montaža dvocijevnog sustava grijanja 50/40°C, odnosno hlađenja 7/12°C
- Cjevovodi grijanja/hlađenja se izvode iz kompozitnih PPR cijevi ojačanih staklenim vlaknima, za sustave grijanja/hlađenja, sa izolacijom
s parnom branom debljine 13mm.
- Cjevovodi unutar strojarnice se izvode iz čeličnih cijevi za sustave grijanja/hlađenja,sa izolacijom s parnom branom debljine 20mm
- Sve dionice dvocijevnog sustava vode se u spuštenom stropu i instalacijskim nišama
- Međusobno spajanje cijevi i adekvatnih fitinga polifuzijskim zavarivanjem
- Svi prolazi cjevovoda preko razdvojenih dilatacija (fuga) zgrade moraju se položiti u zaštitnu cijev. Ova se zaština mjera provodi i kod
prolaza cijevi kroz zid ili strop, kao i kod izlaza cijevi iz poda (npr. kod priključenja ogrjevnih tijela)
- Zbog značajnih toplinskih dilatacija izvođač treba osobitu pozornost posvetiti čvrstim točkama te osigurati kompenzacijske lire na
potrebnim mjestima
- Izvođač se mora u svemu strogo pridržavati uputa proizvođača opreme
- Svi prolazi kroz stropove i zidove objekta izvode se uporabom proturnih zaštitnih cijevi
- Odvod kondenzata sa ventilokonvektora izvesti u spuštenom strop do spoja na odvod umivaonika
- U spuštenom stropu pored kazetnog ventilokonvektora ugraditi revizijski otvor prema uputama proizvođača ventilokonvektora
RADIJATORSKO GRIJANJE
- Za grijanje toaleta i kupaonica izvodi se dvocijevni sustav radijatorskog grijanja iz kompozitnih PPR-cijevi (od strojarnice do etažnih
razdjelnika), te iz PE-Xa cijevi od etažnih razdjelnika do radijatora; ogrijevna tijela su čelični pločasti kompaktni ventilski radijatori tipa 11
i 22V, čelični pločasti ventilski vertikalni radijatori kao Koratherm Vertikal K20VM, i u kupaniocama kupaonski cijevni sušači ovješeni na zid
standarnim ovjesnim priborom, opremljeni termostatskim ventilom sa termostatskom glavom na polaznom vodu i radijatorskom
prigušnicom na povratnom vodu.
Predviđena je montaža dvocijevnog sustava 60/45°C iz višeslojnih PE-Xa cijevi sa centralnim etažnim razdjelnikom krugova grijanja
Sve dionice dvocijevnog sustava položene u cementnom estrihu s toplinskom izolacijom cjevovoda sukladno važećim propisima
Međusobno spajanje cijevi i adekvatnih fitinga tehnikom spajanja tzv. “pomičnom navlakom”
Svi prolazi cjevovoda preko razdvojenih dilatacija (fuga) zgrade moraju se položiti u zaštitnu cijev. Ova se zaština mjera provodi i kod
prolaza cijevi kroz zid ili strop, kao i kod izlaza cijevi iz cementne podloge (npr. kod priključenja ogrjevnih tijela)
Zbog značajnih toplinskih dilatacija izvođač treba osobitu pozornost posvetiti čvrstim točkama te osigurati kompenzacijske lire na
potrebnim mjestima
Na oko 1.5 m ispred grijaćeg tijela potrebno je postaviti cijevnu liru, čime se amortiziraju sile zatezanja i pritiska
Izvođač se mora u svemu strogo pridržavati uputa proizvođača opreme
Građevinski radovi uz polaganje cijevnog razvoda (zalijevanje cementnog estriha) u svemu prema važećim standardima i tehničkoj praksi
postavljanja
Svi prolazi kroz stropove i zidove objekta izvode se uporabom proturnih cijevi
- 1.06 -
Obnovljivi izvori energije
68.4 m2 215.5 m3
20 °C 4832 W
26 °C 5614 W
Projektirana temperatura prostorije (ljeto)
Dobici topline
SURADNIK: SLAVEN HOFER, stroj.teh.
IZVEDBENI PROJEKT
1000x594m
m
- 3.01 -
Racunalstvo
68.8 m2 227.0 m3
20 °C 6276 W
- 3.02 -
Racunalstvo 2
71.3 m2 235.2 m3
20 °C 5758 W
- 3.03 -
Tehnicko crtanje i modeliranje
69.3 m2 228.7 m3
20 °C 5544 W
- 3.04 -
Kabinet 1
20.6 m2 64.8 m3
26 °C 2019 W
- 3.05 -
Racunalstvo 3
68.4 m2 215.5 m3
26 °C 5711 W
- 3.06 -
Studio
37.5 m2 118.0 m3
- 3.07 -
Kabinet 2
21.0 m2 66.2 m3
- 3.08 -
Stubište i dizalo
27.7 m2 87.4 m3
26 °C 2544 W
- 3.09 -
Sanitarije 1
15.3 m2 46.7 m3
15 °C 696 W
- 3.10 -
Sanitarije 2
5.1 m2 15.6 m3
15 °C 81 W
- 3.11 -
Sanitarije 3
3.5 m2 10.7 m3
- 3.12 -
Soba 1
14.2 m2 46.8 m3
- 3.13 -
Sanitarije 4
2.9 m2 9.5 m3
24 °C 501 W
- 3.14 -
Soba 2
14.2 m2 46.8 m3
- 3.15 -
Sanitarije 5
2.9 m2 9.5 m3
24 °C 524 W
- 3.16 -
Soba 3
14.2 m2 46.8 m3
26 °C 818 W
- 3.17 -
Sanitarije 6
2.9 m2 9.5 m3
24 °C 476 W
- 3.18 -
Hodnik i stubište
42.9 m2 141.7 m3
20 °C 2761 W
- 3.19 -
Hodnik
64.5 m2 203.1 m3
26 °C 866 W
26 °C 3186 W 26 °C 5794 W 26 °C 6220 W 26 °C 6449 W
20 °C 1906 W
20 °C 2175 W
20 °C 4599 W20 °C 2050 W20 °C 1093 W20 °C 2174 W
26 °C 1053 W 26 °C 2925 W
20 °C 832 W
20 °C 807 W
20 °C 767 W
26 °C 806 W
26 °C 806 W
VCE48Qg=2600 W (3.brz)Qh=2769 WN=61W/220 V~50 HzT=22 kg
VCE28Qg=1360 W (1.brz)Qh=1685 WN=55W/220 V~50 HzT=17,2 kg
VCE38Qg=2330 W (3.brz)Qh=2599 WN=61W/220 V~50 HzT=22 kg
LIGHT-ECM 63 RCQg=3522 W (2.brz)Qh=4247WN=26W/220 V~50 HzT=26 kg
LIGHT-ECM 63 RCQg=3522 W (2.brz)Qh=4247WN=26W/220 V~50 HzT=26 kg
LIGHT-ECM 63 RCQg=3522 W (2.brz)Qh=4247WN=26W/220 V~50 HzT=26 kg
LIGHT-ECM 63 RCQg=3522 W (2.brz)Qh=4247WN=26W/220 V~50 HzT=26 kg
LIGHT-ECM 63 RCQg=3522 W (2.brz)Qh=4247WN=26W/220 V~50 HzT=26 kg
LIGHT-ECM 63 RCQg=3522 W (2.brz)Qh=4247WN=26W/220 V~50 HzT=26 kg
LIGHT-ECM 63 RCQg=2510 W (1.brz)Qh=4247WN=63W/220 V~50 HzT=26 kg
LIGHT-ECM 63 RCQg=2510 W (1.brz)Qh=4247WN=63W/220 V~50 HzT=26 kg
LIGHT-ECM 63 RCQg=3522 W (2.brz)Qh=4247WN=26W/220 V~50 HzT=26 kg
LIGHT-ECM 61 RCQg=2300 W (2.brz)Qh=2223 WN=12W/220 V~50 HzT=23 kg
KORATHERM VERTIKAL K20VM 1200/884
VaiR
AD
11 V
600/400
Kupaonski radijator 1810/750
54321
RZ 3 - 3. (5)
Kupaonski radijator 1810/750Kupaonski radijator 1810/750
Ø32x4,4Ø32x4,4
Ø2
5x3
,5
Ø3
2x4
,4
Ø40x5,5
Ø75x10,3
16x2,2
25x3,5
16x2,2
16x2,2
LIGHT-ECM 63 RCQg=2510 W (1.brz)Qh=4247WN=63W/220 V~50 HzT=26 kgVCE18
Qg=850 W (2.brz)Qh=893 WN=37W/220 V~50 HzT=14,1 kg
VCE18Qg=810 W (1.brz)Qh=893 WN=37W/220 V~50 HzT=14,1 kg
VCE18Qg=810 W (1.brz)Qh=893 WN=37W/220 V~50 HzT=14,1 kg
Ø32x4,4
Ø40x5,5
Ø4
0x5
,5
Ø6
3x8
,6
Ø6
3x8
,6
Ø7
5x1
0,3
Ø4
0x5
,5
Ø32x4,4
Ø32x4,4
Ø32x4,4Ø32x4,4
Ø40x5,5
Ø3
2x4
,4
Ø7
5x1
0,3
Ø7
5x1
0,3
Ø25x3,5
Ø7
5x1
0,3
2x Ø90x12,3
u podu
u podu
2x Ø32x4,4
Ø25 - i=0,5%
Ø25 - i=0,5%
Ø32 - i=
0,5%
V3 - Ø32
Ø25 - i=0,5%
Ø25 - i=0,5%
Ø32 - i=
0,5%
V4 - Ø32
Ø25 - i=0,5%
Ø25 - i=0,5%
Ø32 - i=
0,5%
V5 - Ø32
Ø25 - i=0,5%
Ø32 - i=0,5%
Ø25 - i=
0,5%
Ø32 - i=0,5% Ø25 - i=0,5%
Spoj odvoda kondenzata
na kanalizacijsku vertikalu
u sifonskoj izvedbi
V1 - Ø32V2 - Ø32
Ø25 - i=0,5%
Ø32 - i=
0,5%
Ø25 - i=0,5%
Ø32 - i=
0,5%
Ø25 - i=0,5%
Ø32 - i=0,5%
PROJEKTANT: IVAN TOMIČIĆ, mag.ing.mech.
NACRT:
PROJEKT:
LOKACIJA:
INVESTITOR:
GRAĐEVINA:
BR.PROJ:
ZOP:
DATUM:
MJERILO:1:50
LIST:
VRSTA
PROJEKTA:
C A L F A C T I Oj . d . o . o . z a p r o j e k t i r a n j e i i n ž e n j e r i n g
3 1 2 0 7 T e n j a , J a n a P a n n o n i u s a 2 4O I B : 9 5 0 3 2 6 9 4 0 1 8M o b : 0 9 9 / 3 0 1 - 8 1 9 7e - m a i l : c a l f a c t i o . o s @ g m a i l . c o m
Osijek, Istarska ulica 3, k.č.br. 5989/2 i 5989/9 k.o. Osijek
Elektrotehnička i prometna škola Osijek, OIB: 28015293209
Rekonstrukcija i dogradnja elektrotehničke i prometne škole
SP/66-19/IZ
BP-IZV 01/2019
5
TLOCRT 2.KATA - GRIJANJE I
HLAĐENJE
STROJARSKI PROJEKT - GRIJANJE, HLAĐENJE I
VENTILACIJA
LISTOPAD 2019.G.
S
Povratni cjevovod grijanja/hlađenja
Polazni cjevovod grijanja/hlađenja
LEGENDA:
VCEx8 - Ventilokonvektor, za rad s optočnim zrakom, parapetni, s maskom, dvocijevne izvedbe, kao
VENTILCLIMA tip VCE x8, snaga grijanja i hlađenja iskazana na nacrtu
LIGHT-ECM 6x - Ventilokonvektor, za rad s optočnim zrakom, kazetni, za ugradnju u spušteni strop, s
maskom, dvocijevne izvedbe, kao VENTILCLIMA tip LIGHT-ECM 6x, snaga grijanja i hlađenja
iskazana na nacrtu
Oznaka prostorije
Naziv prostorije
Volumen prostorije
Gubici topline
Površina prostorije
Projektirana temperatura prostorije (zima)
Odvod kondenzata
NAPOMENE:
VENTILOKONVEKTORI
- Predviđena je montaža dvocijevnog sustava grijanja 50/40°C, odnosno hlađenja 7/12°C
- Cjevovodi grijanja/hlađenja se izvode iz kompozitnih PPR cijevi ojačanih staklenim vlaknima, za sustave grijanja/hlađenja, sa izolacijom
s parnom branom debljine 13mm.
- Cjevovodi unutar strojarnice se izvode iz čeličnih cijevi za sustave grijanja/hlađenja,sa izolacijom s parnom branom debljine 20mm
- Sve dionice dvocijevnog sustava vode se u spuštenom stropu i instalacijskim nišama
- Međusobno spajanje cijevi i adekvatnih fitinga polifuzijskim zavarivanjem
- Svi prolazi cjevovoda preko razdvojenih dilatacija (fuga) zgrade moraju se položiti u zaštitnu cijev. Ova se zaština mjera provodi i kod
prolaza cijevi kroz zid ili strop, kao i kod izlaza cijevi iz poda (npr. kod priključenja ogrjevnih tijela)
- Zbog značajnih toplinskih dilatacija izvođač treba osobitu pozornost posvetiti čvrstim točkama te osigurati kompenzacijske lire na
potrebnim mjestima
- Izvođač se mora u svemu strogo pridržavati uputa proizvođača opreme
- Svi prolazi kroz stropove i zidove objekta izvode se uporabom proturnih zaštitnih cijevi
- Odvod kondenzata sa ventilokonvektora izvesti u spuštenom strop do spoja na odvod umivaonika
- U spuštenom stropu pored kazetnog ventilokonvektora ugraditi revizijski otvor prema uputama proizvođača ventilokonvektora
RADIJATORSKO GRIJANJE
- Za grijanje toaleta i kupaonica izvodi se dvocijevni sustav radijatorskog grijanja iz kompozitnih PPR-cijevi (od strojarnice do etažnih
razdjelnika), te iz PE-Xa cijevi od etažnih razdjelnika do radijatora; ogrijevna tijela su čelični pločasti kompaktni ventilski radijatori tipa 11
i 22V, čelični pločasti ventilski vertikalni radijatori kao Koratherm Vertikal K20VM, i u kupaniocama kupaonski cijevni sušači ovješeni na zid
standarnim ovjesnim priborom, opremljeni termostatskim ventilom sa termostatskom glavom na polaznom vodu i radijatorskom
prigušnicom na povratnom vodu.
Predviđena je montaža dvocijevnog sustava 60/45°C iz višeslojnih PE-Xa cijevi sa centralnim etažnim razdjelnikom krugova grijanja
Sve dionice dvocijevnog sustava položene u cementnom estrihu s toplinskom izolacijom cjevovoda sukladno važećim propisima
Međusobno spajanje cijevi i adekvatnih fitinga tehnikom spajanja tzv. “pomičnom navlakom”
Svi prolazi cjevovoda preko razdvojenih dilatacija (fuga) zgrade moraju se položiti u zaštitnu cijev. Ova se zaština mjera provodi i kod
prolaza cijevi kroz zid ili strop, kao i kod izlaza cijevi iz cementne podloge (npr. kod priključenja ogrjevnih tijela)
Zbog značajnih toplinskih dilatacija izvođač treba osobitu pozornost posvetiti čvrstim točkama te osigurati kompenzacijske lire na
potrebnim mjestima
Na oko 1.5 m ispred grijaćeg tijela potrebno je postaviti cijevnu liru, čime se amortiziraju sile zatezanja i pritiska
Izvođač se mora u svemu strogo pridržavati uputa proizvođača opreme
Građevinski radovi uz polaganje cijevnog razvoda (zalijevanje cementnog estriha) u svemu prema važećim standardima i tehničkoj praksi
postavljanja
Svi prolazi kroz stropove i zidove objekta izvode se uporabom proturnih cijevi
- 1.06 -
Obnovljivi izvori energije
68.4 m2 215.5 m3
20 °C 4832 W
26 °C 5614 W
Projektirana temperatura prostorije (ljeto)
Dobici topline
SURADNIK: SLAVEN HOFER, stroj.teh.
IZVEDBENI PROJEKT
1000x594m
m
- 4.01 -
Konferencijska dvorana
129.0 m2 445.1 m3
26 °C 19817 W
- 4.02 -
Stubište i dizalo
49.4 m2 170.3 m3
26 °C 2290 W
- 4.03 -
Sanitarije 1
3.5 m2 11.2 m3
15 °C 65 W
- 4.04 -
Sanitarije 2
9.8 m2 31.4 m3
15 °C 779 W
- 4.05 -
Sanitarije 3
7.8 m2 25.0 m3
15 °C 451 W
- 4.06 -
Foaje
99.1 m2 396.5 m3
26 °C 23478 W
20 °C 14887 W
20 °C 11418 W20 °C 3268 W
VCE38Qg=3230 W (6.brz)Qh=2599 WN=61W/220 V~50 HzT=21,8 kg
VCE108Qg=7520 W (1.brz)Qh=8312WN=158W/220 V~50 HzT=47,5 kg
VCE108Qg=7520 W (1.brz)Qh=8312WN=158W/220 V~50 HzT=47,5 kg
VCE108Qg=7520 W (1.brz)Qh=8312WN=158W/220 V~50 HzT=47,5 kg
VaiR
AD
11 V
600/400
KO
RA
TH
ER
M V
ER
TIK
AL K
20V
M 1200/884
VaiR
AD
22 V
600/600
12
3
RZ 4 - 4. (3)
Ø4
0x5
,5
Ø6
3x8
,6
20x2,4
16x2,2
16x2,2
16x2,2
Ø32x4,4
LIGHT-ECM 64 RCQg=4150 W (2.brz)Qh=4975WN=45W/220 V~50 HzT=26 kg
LIGHT-ECM 64 RCQg=4150 W (2.brz)Qh=4975WN=45W/220 V~50 HzT=26 kg
LIGHT-ECM 64 RCQg=4150 W (2.brz)Qh=4975WN=45W/220 V~50 HzT=26 kg
LIGHT-ECM 64 RCQg=4150 W (2.brz)Qh=4975WN=45W/220 V~50 HzT=26 kg
Ø32x4,4
Ø32x4,4
Ø5
0x6
,9
Ø32x4,4
2x Ø63x8,6
2x Ø20x2,4
Ø25 - i=0,5%
Ø32 - i=
0,5%
Ø25 - i=0,5%
Ø32 - i=
0,5%
V1 - Ø32V2 - Ø32
Ø25 - i=0,5%
Ø25 - i=0,5%
PROJEKTANT: IVAN TOMIČIĆ, mag.ing.mech.
NACRT:
PROJEKT:
LOKACIJA:
INVESTITOR:
GRAĐEVINA:
BR.PROJ:
ZOP:
DATUM:
MJERILO:1:50
LIST:
VRSTA
PROJEKTA:
C A L F A C T I Oj . d . o . o . z a p r o j e k t i r a n j e i i n ž e n j e r i n g
3 1 2 0 7 T e n j a , J a n a P a n n o n i u s a 2 4O I B : 9 5 0 3 2 6 9 4 0 1 8M o b : 0 9 9 / 3 0 1 - 8 1 9 7e - m a i l : c a l f a c t i o . o s @ g m a i l . c o m
Osijek, Istarska ulica 3, k.č.br. 5989/2 i 5989/9 k.o. Osijek
Elektrotehnička i prometna škola Osijek, OIB: 28015293209
Rekonstrukcija i dogradnja elektrotehničke i prometne škole
SP/66-19/IZ
BP-IZV 01/2019
6
TLOCRT 3.KATA - GRIJANJE I
HLAĐENJE
STROJARSKI PROJEKT - GRIJANJE, HLAĐENJE I
VENTILACIJA
LISTOPAD 2019.G.
S
Povratni cjevovod grijanja/hlađenja
Polazni cjevovod grijanja/hlađenja
LEGENDA:
VCEx8 - Ventilokonvektor, za rad s optočnim zrakom, parapetni, s maskom, dvocijevne izvedbe, kao
VENTILCLIMA tip VCE x8, snaga grijanja i hlađenja iskazana na nacrtu
LIGHT-ECM 6x - Ventilokonvektor, za rad s optočnim zrakom, kazetni, za ugradnju u spušteni strop, s
maskom, dvocijevne izvedbe, kao VENTILCLIMA tip LIGHT-ECM 6x, snaga grijanja i hlađenja
iskazana na nacrtu
Oznaka prostorije
Naziv prostorije
Volumen prostorije
Gubici topline
Površina prostorije
Projektirana temperatura prostorije (zima)
Odvod kondenzata
NAPOMENE:
VENTILOKONVEKTORI
- Predviđena je montaža dvocijevnog sustava grijanja 50/40°C, odnosno hlađenja 7/12°C
- Cjevovodi grijanja/hlađenja se izvode iz kompozitnih PPR cijevi ojačanih staklenim vlaknima, za sustave grijanja/hlađenja, sa izolacijom
s parnom branom debljine 13mm.
- Cjevovodi unutar strojarnice se izvode iz čeličnih cijevi za sustave grijanja/hlađenja,sa izolacijom s parnom branom debljine 20mm
- Sve dionice dvocijevnog sustava vode se u spuštenom stropu i instalacijskim nišama
- Međusobno spajanje cijevi i adekvatnih fitinga polifuzijskim zavarivanjem
- Svi prolazi cjevovoda preko razdvojenih dilatacija (fuga) zgrade moraju se položiti u zaštitnu cijev. Ova se zaština mjera provodi i kod
prolaza cijevi kroz zid ili strop, kao i kod izlaza cijevi iz poda (npr. kod priključenja ogrjevnih tijela)
- Zbog značajnih toplinskih dilatacija izvođač treba osobitu pozornost posvetiti čvrstim točkama te osigurati kompenzacijske lire na
potrebnim mjestima
- Izvođač se mora u svemu strogo pridržavati uputa proizvođača opreme
- Svi prolazi kroz stropove i zidove objekta izvode se uporabom proturnih zaštitnih cijevi
- Odvod kondenzata sa ventilokonvektora izvesti u spuštenom strop do spoja na odvod umivaonik
- U spuštenom stropu pored kazetnog ventilokonvektora ugraditi revizijski otvor prema uputama proizvođača ventilokonvektora
RADIJATORSKO GRIJANJE
- Za grijanje toaleta i kupaonica izvodi se dvocijevni sustav radijatorskog grijanja iz kompozitnih PPR-cijevi (od strojarnice do etažnih
razdjelnika), te iz PE-Xa cijevi od etažnih razdjelnika do radijatora; ogrijevna tijela su čelični pločasti kompaktni ventilski radijatori tipa 11
i 22V, čelični pločasti ventilski vertikalni radijatori kao Koratherm Vertikal K20VM, i u kupaniocama kupaonski cijevni sušači ovješeni na zid
standarnim ovjesnim priborom, opremljeni termostatskim ventilom sa termostatskom glavom na polaznom vodu i radijatorskom
prigušnicom na povratnom vodu.
Predviđena je montaža dvocijevnog sustava 60/45°C iz višeslojnih PE-Xa cijevi sa centralnim etažnim razdjelnikom krugova grijanja
Sve dionice dvocijevnog sustava položene u cementnom estrihu s toplinskom izolacijom cjevovoda sukladno važećim propisima
Međusobno spajanje cijevi i adekvatnih fitinga tehnikom spajanja tzv. “pomičnom navlakom”
Svi prolazi cjevovoda preko razdvojenih dilatacija (fuga) zgrade moraju se položiti u zaštitnu cijev. Ova se zaština mjera provodi i kod
prolaza cijevi kroz zid ili strop, kao i kod izlaza cijevi iz cementne podloge (npr. kod priključenja ogrjevnih tijela)
Zbog značajnih toplinskih dilatacija izvođač treba osobitu pozornost posvetiti čvrstim točkama te osigurati kompenzacijske lire na
potrebnim mjestima
Na oko 1.5 m ispred grijaćeg tijela potrebno je postaviti cijevnu liru, čime se amortiziraju sile zatezanja i pritiska
Izvođač se mora u svemu strogo pridržavati uputa proizvođača opreme
Građevinski radovi uz polaganje cijevnog razvoda (zalijevanje cementnog estriha) u svemu prema važećim standardima i tehničkoj praksi
postavljanja
Svi prolazi kroz stropove i zidove objekta izvode se uporabom proturnih cijevi
- 1.06 -
Obnovljivi izvori energije
68.4 m2 215.5 m3
20 °C 4832 W
26 °C 5614 W
Projektirana temperatura prostorije (ljeto)
Dobici topline
SURADNIK: SLAVEN HOFER, stroj.teh.
IZVEDBENI PROJEKT
1000x594m
m
LZ-H100GBA5Q=1000 m3/hN=480W/220 V~50 HzT=63 kg
Ø150
Ø100Ø100
Ø250
Ø250 Ø250
Ø250
Ø250
Ø250
Ø250
Ø250
DEV/600/48DEV/600/48DEV/600/48
DEV/600/48
DEV/600/48
PZM-250-500
EG 2,4kW
Ø250
LZ-H100GBA5Q=1000 m3/hN=480W/220 V~50 HzT=63 kg
Ø250
Ø250
Ø250
DEV/600/48
DEV/600/48
DEV/600/48
DEV/600/48
DEV/600/48
PZM-250-500
EG 2,4kW
Ø250
Ø250 300x160
Ø250
LZ-H100GBA5Q=1000 m3/hN=480W/220 V~50 HzT=63 kg
Ø250Ø250
Ø250
DEV/600/48
DEV/600/48
DEV/600/48DEV/600/48
DEV/600/48
PZM-250-500
EG 2,4kW
Ø250
300x160
Ø250Ø250
Ø250Ø250
Ø250
LZ-H100GBA5Q=1000 m3/hN=480W/220 V~50 HzT=63 kg
Ø250Ø250
Ø250
DEV/600/48
DEV/600/48DEV/600/48
DEV/600/48
PZM-250-500
EG 2,4kW
Ø250
300x160
Ø250Ø250
Ø250Ø250
Ø250
DEV/600/48
LZ-H100GBA5Q=1000 m3/hN=480W/220 V~50 HzT=63 kg
Ø250
Ø250
Ø250
Ø250Ø250
DEV/600/48
DEV/600/48
DEV/600/48
DEV/600/48
DEV/600/48
PZM-250-500PZM-250-500
EG 2,4kW
Ø250
Ø250300x160
Ø250Ø250
300x160
300x160
300x160Ø250
PROJEKTANT: IVAN TOMIČIĆ, mag.ing.mech.
NACRT:
PROJEKT:
LOKACIJA:
INVESTITOR:
GRAĐEVINA:
BR.PROJ:
ZOP:
DATUM:
MJERILO:1:50
LIST:
VRSTA
PROJEKTA:
C A L F A C T I Oj . d . o . o . z a p r o j e k t i r a n j e i i n ž e n j e r i n g
3 1 2 0 7 T e n j a , J a n a P a n n o n i u s a 2 4O I B : 9 5 0 3 2 6 9 4 0 1 8M o b : 0 9 9 / 3 0 1 - 8 1 9 7e - m a i l : c a l f a c t i o . o s @ g m a i l . c o m
Osijek, Istarska ulica 3, k.č.br. 5989/2 i 5989/9 k.o. Osijek
Elektrotehnička i prometna škola Osijek, OIB: 28015293209
Rekonstrukcija i dogradnja elektrotehničke i prometne škole
SP/66-19/IZ
BP-IZV 01/2019
7
TLOCRT PRIZEMLJA - VENTILACIJA
STROJARSKI PROJEKT - GRIJANJE, HLAĐENJE I
VENTILACIJA
LISTOPAD 2019.G.
S
LEGENDA:
1. Aksijalni odsisni ventilator, s automatskim zatvaranjem, za direktni vanjksi ispuh kroz ventilacijski kanal (cijev) + klapna, Ø100mm, opremljen
elektroničkim vremenskim programatorom, uključivanje sa prekidačem rasvjete ili preko senzora pokreta, V=90 m3/h, P=9W, U=230-240 VAC,
materijal ABS, ispuh u vanjski prostor, na ispuhu ugradnja protukišne ukrasne žaluzije
2. Aksijalni odsisni ventilator, s automatskim zatvaranjem, za direktni vanjksi ispuh kroz ventilacijski kanal (cijev) + klapna, Ø150mm, opremljen
elektroničkim vremenskim programatorom, uključivanje sa prekidačem rasvjete ili preko senzora pokreta, V=200 m3/h, P=9W, U=230-240 VAC,
materijal ABS, ispuh u vanjski prostor, na ispuhu ugradnja protukišne ukrasne žaluzije
LZ-H100GBA5 - Ventilacijska jedinica s rekuperacijom kao LG ERV LZ-H100GBA5, 1000m3/h, ugradnja u spušteni strop
LZ-H80GBA5 - Ventilacijska jedinica s rekuperacijom kao LG ERV LZ-H80GBA5, 800m3/h, ugradnja u spušteni strop
LZ-H50GBA5 - Ventilacijska jedinica s rekuperacijom kao LG ERV LZ-H50GBA5, 500m3/h, ugradnja u spušteni strop
DEV/600/xx - Stropni vrtložni distributer svježeg zraka + priključna kutija PK1, ugradnja u spušteni strop, proizvođač Klimaoprema Samobor
PZ 2xx/500 - Cijevni prigušivač zvuka, L=500mm, proizvođač Klimaoprema Samobor
EG 2 (2,4)kW - okrugli kanalski grijač zraka snage 2 (2,4)kW
NAPOMENE:
- Predviđena je izvedba ventilacijskog sustava iz okruglih ventilacijskih kanala i fazonskih elemenata
- Okrugli ventilacijski kanali kao spiralno falcana cijev iz pocinčanog lima debljine 0,6mm, promjera prema nacrtu, sa paronepropusnom izolacijom
debljine d=19mm.
- Spoj kanala i fazonskih komada vanjskom ili unutanjom spojnicom
- Spajanje priključnih kutija stropnih distributera zraka i odsisnih anemostata sa ventilacijskim kanalima izvesti pomoći fleksibilne Aluflex
dvoslojne cijevi
- Spoj rekuperatorske jedinice sa ventilacijskim kanalima izvesti kao zrakotijesan fleksibilan spoj platnom radi spriječavanja prijenosa buke i
vibracija na kanalni razvod.
- Na dovodnoj grani svježeg zraka ugrađuju se kanalski električni grijači snage 2 i 2,4kW.
- Na dovodu svježeg zraka i odvodu istrošenog zraka na fasadi montiraju se fiksne protukišne žaluzije u boji fasade
- Odvod kondenzata sa rekupretora i unutarnjih jednica hlađenja odvesti u do najbližeg odvoda umivaonika
- Rekuperacijske ventilacijske jedinice se upravljaju putem žičnih daljinski upravljača na zidu pored ulaznih vrata u prostoriju
- SERVISNI PROSTOR REKUPERATORA
- OTVOR ZA SERVIS REKUPERATORA 45 x 45 cm
21
SURADNIK: SLAVEN HOFER, stroj.teh.
IZVEDBENI PROJEKT
1000x594m
m
LZ-H050GBA5Q=500 m3/hN=240W/220 V~50 HzT=44 kg
LZ-H080GBA5Q=800 m3/hN=390W/220 V~50 HzT=63 kg
LZ-H100GBA5Q=1000 m3/hN=480W/220 V~50 HzT=63 kg
LZ-H100GBA5Q=1000 m3/hN=480W/220 V~50 HzT=63 kg
654321
LZ-H050GBA5Q=500 m3/hN=240W/220 V~50 HzT=44 kg
Ø100
Ø100
Ø100
Ø150
Ø100
EG 2kW EG 2,4kW
Ø250
Ø250
Ø250
Ø250
Ø200
Ø200
Ø200
Ø200
Ø200
Ø200Ø200
Ø200Ø200
Ø200
Ø200Ø200
Ø250
Ø250
Ø250
Ø250Ø250
Ø250
Ø250
Ø250Ø250
Ø250
Ø250Ø200Ø200
Ø250Ø250Ø200
Ø100
DEV/600/24
DEV/600/24 DEV/600/24
DEV/600/24
DEV/600/24
DEV/600/24
DEV/600/24
DEV/600/24
DEV/600/24 DEV/600/48
DEV/600/48
DEV/600/48
DEV/600/48
DEV/600/48
DEV/600/24
DEV/600/24DEV/600/24
DEV/600/24 DEV/600/48
DEV/600/48
DEV/600/48
DEV/600/48
DEV/600/48
PZM-250-500PZM-200-500
PZM-200-500
PZM-250-500PZM-250-500
EG 2,4kW
Ø250
EG 2,4kW
Ø250
Ø250
EG 2kW
Ø200
Ø200
Ø250
300x160 300x160 Ø250
300x160 Ø250
300x160Ø250
Ø250
Ø250
Ø250
PROJEKTANT: IVAN TOMIČIĆ, mag.ing.mech.
NACRT:
PROJEKT:
LOKACIJA:
INVESTITOR:
GRAĐEVINA:
BR.PROJ:
ZOP:
DATUM:
MJERILO:1:50
LIST:
VRSTA
PROJEKTA:
C A L F A C T I Oj . d . o . o . z a p r o j e k t i r a n j e i i n ž e n j e r i n g
3 1 2 0 7 T e n j a , J a n a P a n n o n i u s a 2 4O I B : 9 5 0 3 2 6 9 4 0 1 8M o b : 0 9 9 / 3 0 1 - 8 1 9 7e - m a i l : c a l f a c t i o . o s @ g m a i l . c o m
Osijek, Istarska ulica 3, k.č.br. 5989/2 i 5989/9 k.o. Osijek
Elektrotehnička i prometna škola Osijek, OIB: 28015293209
Rekonstrukcija i dogradnja elektrotehničke i prometne škole
SP/66-19/IZ
BP-IZV 01/2019
8
TLOCRT 1.KATA - VENTILACIJA
STROJARSKI PROJEKT - GRIJANJE, HLAĐENJE I
VENTILACIJA
LISTOPAD 2019.G.
S
LEGENDA:
1. Aksijalni odsisni ventilator, s automatskim zatvaranjem, za direktni vanjksi ispuh kroz ventilacijski kanal (cijev) + klapna, Ø100mm, opremljen
elektroničkim vremenskim programatorom, uključivanje sa prekidačem rasvjete ili preko senzora pokreta, V=60 m3/h, P=9W, U=230-240 VAC,
materijal ABS, ispuh u vanjski prostor, na ispuhu ugradnja protukišne ukrasne žaluzije
2. Aksijalni odsisni ventilator, s automatskim zatvaranjem, za direktni vanjksi ispuh kroz ventilacijski kanal (cijev) + klapna, Ø100mm, opremljen
elektroničkim vremenskim programatorom, uključivanje sa prekidačem rasvjete ili preko senzora pokreta, V=90 m3/h, P=9W, U=230-240 VAC,
materijal ABS, ispuh u vanjski prostor, na ispuhu ugradnja protukišne ukrasne žaluzije
3. Aksijalni odsisni ventilator, s automatskim zatvaranjem, za direktni vanjksi ispuh kroz ventilacijski kanal (cijev) + klapna, Ø150mm, opremljen
elektroničkim vremenskim programatorom, uključivanje sa prekidačem rasvjete ili preko senzora pokreta, V=200 m3/h, P=9W, U=230-240 VAC,
materijal ABS, ispuh u vanjski prostor, na ispuhu ugradnja protukišne ukrasne žaluzije
LZ-H100GBA5 - Ventilacijska jedinica s rekuperacijom kao LG ERV LZ-H100GBA5, 1000m3/h, ugradnja u spušteni strop
LZ-H80GBA5 - Ventilacijska jedinica s rekuperacijom kao LG ERV LZ-H80GBA5, 800m3/h, ugradnja u spušteni strop
LZ-H50GBA5 - Ventilacijska jedinica s rekuperacijom kao LG ERV LZ-H50GBA5, 500m3/h, ugradnja u spušteni strop
DEV/600/xx - Stropni vrtložni distributer svježeg zraka + priključna kutija PK1, ugradnja u spušteni strop, proizvođač Klimaoprema Samobor
PZ 2xx/500 - Cijevni prigušivač zvuka, L=500mm, proizvođač Klimaoprema Samobor
EG 2 (2,4)kW - okrugli kanalski grijač zraka snage 2 (2,4)kW
NAPOMENE:
- Predviđena je izvedba ventilacijskog sustava iz okruglih ventilacijskih kanala i fazonskih elemenata
- Okrugli ventilacijski kanali kao spiralno falcana cijev iz pocinčanog lima debljine 0,6mm, promjera prema nacrtu, sa paronepropusnom izolacijom
debljine d=19mm.
- Spoj kanala i fazonskih komada vanjskom ili unutanjom spojnicom
- Spajanje priključnih kutija stropnih distributera zraka i odsisnih anemostata sa ventilacijskim kanalima izvesti pomoći fleksibilne Aluflex
dvoslojne cijevi
- Spoj rekuperatorske jedinice sa ventilacijskim kanalima izvesti kao zrakotijesan fleksibilan spoj platnom radi spriječavanja prijenosa buke i
vibracija na kanalni razvod.
- Na dovodnoj grani svježeg zraka ugrađuju se kanalski električni grijači snage 2 i 2,4kW.
- Na dovodu svježeg zraka i odvodu istrošenog zraka na fasadi montiraju se fiksne protukišne žaluzije u boji fasade
- Odvod kondenzata sa rekupretora i unutarnjih jednica hlađenja odvesti u do najbližeg odvoda umivaonika
- Rekuperacijske ventilacijske jedinice se upravljaju putem žičnih daljinski upravljača na zidu pored ulaznih vrata u prostoriju
- SERVISNI PROSTOR REKUPERATORA
- OTVOR ZA SERVIS REKUPERATORA 45 x 45 cm
321
SURADNIK: SLAVEN HOFER, stroj.teh.
IZVEDBENI PROJEKT
1000x594m
m
LZ-H050GBA5Q=500 m3/hN=240W/220 V~50 HzT=44 kg
LZ-H100GBA5Q=1000 m3/hN=480W/220 V~50 HzT=63 kg
LZ-H100GBA5Q=1000 m3/hN=480W/220 V~50 HzT=63 kg
LZ-H100GBA5Q=1000 m3/hN=480W/220 V~50 HzT=63 kg
LZ-H100GBA5Q=1000 m3/hN=480W/220 V~50 HzT=63 kg
Ø100
Ø150
Ø100
Ø100
Ø100
Ø250
Ø250
Ø250
Ø250
Ø200
Ø200
Ø200Ø200
Ø200
Ø250
Ø250
Ø250Ø250
Ø250Ø250
Ø200 Ø250
Ø250Ø250Ø250
Ø100 DEV/600/48
DEV/600/48
DEV/600/48
DEV/600/48
DEV/600/24DEV/600/24
DEV/600/24DEV/600/24
DEV/600/48
DEV/600/48
DEV/600/48
DEV/600/48
DEV/600/48
DEV/600/48DEV/600/48
DEV/600/48
DEV/600/48DEV/600/48
DEV/600/48
DEV/600/48
DEV/600/48DEV/600/48
DEV/600/48
DEV/600/24PZM-250-500
PZM-250-500
PZM-250-500PZM-250-500PZM-250-500
PZM-200-500
EG 2,4kW
Ø250
EG 2,4kW
Ø250
EG 2,4kW
Ø250
EG 2,4kW
Ø250
EG 2kW
Ø200
Ø250 300x160
Ø250
300x160
Ø250Ø250
Ø250Ø250
Ø250
300x160
Ø250Ø250
Ø250Ø250
Ø250
Ø200
Ø200
Ø200
Ø250
300x160
Ø250Ø250
DEV/600/48
PROJEKTANT: IVAN TOMIČIĆ, mag.ing.mech.
NACRT:
PROJEKT:
LOKACIJA:
INVESTITOR:
GRAĐEVINA:
BR.PROJ:
ZOP:
IZVEDBENI PROJEKT
DATUM:
MJERILO:1:50
LIST:
VRSTA
PROJEKTA:
C A L F A C T I Oj . d . o . o . z a p r o j e k t i r a n j e i i n ž e n j e r i n g
3 1 2 0 7 T e n j a , J a n a P a n n o n i u s a 2 4O I B : 9 5 0 3 2 6 9 4 0 1 8M o b : 0 9 9 / 3 0 1 - 8 1 9 7e - m a i l : c a l f a c t i o . o s @ g m a i l . c o m
Osijek, Istarska ulica 3, k.č.br. 5989/2 i 5989/9 k.o. Osijek
Elektrotehnička i prometna škola Osijek, OIB: 28015293209
Rekonstrukcija i dogradnja elektrotehničke i prometne škole
SP/66-19/IZ
BP-IZV 01/2019
9
TLOCRT 2.KATA - VENTILACIJA
STROJARSKI PROJEKT - GRIJANJE, HLAĐENJE I
VENTILACIJA
LISTOPAD 2019.G.
S
LEGENDA:
1. Aksijalni odsisni ventilator, s automatskim zatvaranjem, za direktni vanjksi ispuh kroz ventilacijski kanal (cijev) + klapna, Ø100mm, opremljen
elektroničkim vremenskim programatorom, uključivanje sa prekidačem rasvjete ili preko senzora pokreta, V=60 m3/h, P=9W, U=230-240 VAC,
materijal ABS, ispuh u vanjski prostor, na ispuhu ugradnja protukišne ukrasne žaluzije
2. Aksijalni odsisni ventilator, s automatskim zatvaranjem, za direktni vanjksi ispuh kroz ventilacijski kanal (cijev) + klapna, Ø100mm, opremljen
elektroničkim vremenskim programatorom, uključivanje sa prekidačem rasvjete ili preko senzora pokreta, V=90 m3/h, P=9W, U=230-240 VAC,
materijal ABS, ispuh u vanjski prostor, na ispuhu ugradnja protukišne ukrasne žaluzije
3. Aksijalni odsisni ventilator, s automatskim zatvaranjem, za direktni vanjksi ispuh kroz ventilacijski kanal (cijev) + klapna, Ø150mm, opremljen
elektroničkim vremenskim programatorom, uključivanje sa prekidačem rasvjete ili preko senzora pokreta, V=200 m3/h, P=9W, U=230-240 VAC,
materijal ABS, ispuh u vanjski prostor, na ispuhu ugradnja protukišne ukrasne žaluzije
LZ-H100GBA5 - Ventilacijska jedinica s rekuperacijom kao LG ERV LZ-H100GBA5, 1000m3/h, ugradnja u spušteni strop
LZ-H80GBA5 - Ventilacijska jedinica s rekuperacijom kao LG ERV LZ-H80GBA5, 800m3/h, ugradnja u spušteni strop
LZ-H50GBA5 - Ventilacijska jedinica s rekuperacijom kao LG ERV LZ-H50GBA5, 500m3/h, ugradnja u spušteni strop
DEV/600/xx - Stropni vrtložni distributer svježeg zraka + priključna kutija PK1, ugradnja u spušteni strop, proizvođač Klimaoprema Samobor
PZ 2xx/500 - Cijevni prigušivač zvuka, L=500mm, proizvođač Klimaoprema Samobor
EG 2 (2,4)kW - okrugli kanalski grijač zraka snage 2 (2,4)kW
NAPOMENE:
- Predviđena je izvedba ventilacijskog sustava iz okruglih ventilacijskih kanala i fazonskih elemenata
- Okrugli ventilacijski kanali kao spiralno falcana cijev iz pocinčanog lima debljine 0,6mm, promjera prema nacrtu, sa paronepropusnom izolacijom
debljine d=19mm.
- Spoj kanala i fazonskih komada vanjskom ili unutanjom spojnicom
- Spajanje priključnih kutija stropnih distributera zraka i odsisnih anemostata sa ventilacijskim kanalima izvesti pomoći fleksibilne Aluflex
dvoslojne cijevi
- Spoj rekuperatorske jedinice sa ventilacijskim kanalima izvesti kao zrakotijesan fleksibilan spoj platnom radi spriječavanja prijenosa buke i
vibracija na kanalni razvod.
- Na dovodnoj grani svježeg zraka ugrađuju se kanalski električni grijači snage 2 i 2,4kW.
- Na dovodu svježeg zraka i odvodu istrošenog zraka na fasadi montiraju se fiksne protukišne žaluzije u boji fasade
- Odvod kondenzata sa rekupretora i unutarnjih jednica hlađenja odvesti u do najbližeg odvoda umivaonika
- Rekuperacijske ventilacijske jedinice se upravljaju putem žičnih daljinski upravljača na zidu pored ulaznih vrata u prostoriju
- SERVISNI PROSTOR REKUPERATORA
- OTVOR ZA SERVIS REKUPERATORA 45 x 45 cm
32
1
SURADNIK: SLAVEN HOFER, stroj.teh.
1000x594m
m
LZ-H100GBA5Q=1000 m3/hN=480W/220 V~50 HzT=63 kg
Ø100
Ø120
Ø100
LZ-H100GBA5Q=1000 m3/hN=480W/220 V~50 HzT=63 kg
Ø250Ø250
Ø250
Ø250Ø250
Ø250Ø250
Ø250
Ø250Ø250
Ø250
Ø250 Ø250
DEV/600/48
DEV/600/48DEV/600/48
DEV/600/48
DEV/600/48DEV/600/48
DEV/600/48DEV/600/48
DEV/600/48
DEV/600/48EG 2,4kW
Ø250
EG 2,4kW
Ø250
300x160
Ø250Ø250
Ø250Ø250
Ø250
300x160
PROJEKTANT: IVAN TOMIČIĆ, mag.ing.mech.
NACRT:
PROJEKT:
LOKACIJA:
INVESTITOR:
GRAĐEVINA:
BR.PROJ:
ZOP:
IZVEDBENI PROJEKT
DATUM:
MJERILO:1:50
LIST:
VRSTA
PROJEKTA:
C A L F A C T I Oj . d . o . o . z a p r o j e k t i r a n j e i i n ž e n j e r i n g
3 1 2 0 7 T e n j a , J a n a P a n n o n i u s a 2 4O I B : 9 5 0 3 2 6 9 4 0 1 8M o b : 0 9 9 / 3 0 1 - 8 1 9 7e - m a i l : c a l f a c t i o . o s @ g m a i l . c o m
Osijek, Istarska ulica 3, k.č.br. 5989/2 i 5989/9 k.o. Osijek
Elektrotehnička i prometna škola Osijek, OIB: 28015293209
Rekonstrukcija i dogradnja elektrotehničke i prometne škole
SP/66-19/IZ
BP-IZV 01/2019
10
TLOCRT 3.KATA - VENTILACIJA
STROJARSKI PROJEKT - GRIJANJE, HLAĐENJE I
VENTILACIJA
LISTOPAD 2019.G.
S
LEGENDA:
1. Aksijalni odsisni ventilator, s automatskim zatvaranjem, za direktni vanjksi ispuh kroz ventilacijski kanal (cijev) + klapna, Ø100mm, opremljen
elektroničkim vremenskim programatorom, uključivanje sa prekidačem rasvjete ili preko senzora pokreta, V=90 m3/h, P=9W, U=230-240 VAC,
materijal ABS, ispuh u vanjski prostor, na ispuhu ugradnja protukišne ukrasne žaluzije
2. Aksijalni odsisni ventilator, s automatskim zatvaranjem, za direktni vanjksi ispuh kroz ventilacijski kanal (cijev) + klapna, Ø120mm, opremljen
elektroničkim vremenskim programatorom, uključivanje sa prekidačem rasvjete ili preko senzora pokreta, V=130 m3/h, P=15W, U=230-240 VAC,
materijal ABS, ispuh u vanjski prostor, na ispuhu ugradnja protukišne ukrasne žaluzije
LZ-H100GBA5 - Ventilacijska jedinica s rekuperacijom kao LG ERV LZ-H100GBA5, 1000m3/h, ugradnja u spušteni strop
LZ-H80GBA5 - Ventilacijska jedinica s rekuperacijom kao LG ERV LZ-H80GBA5, 800m3/h, ugradnja u spušteni strop
LZ-H50GBA5 - Ventilacijska jedinica s rekuperacijom kao LG ERV LZ-H50GBA5, 500m3/h, ugradnja u spušteni strop
DEV/600/xx - Stropni vrtložni distributer svježeg zraka + priključna kutija PK1, ugradnja u spušteni strop, proizvođač Klimaoprema Samobor
PZ 2xx/500 - Cijevni prigušivač zvuka, L=500mm, proizvođač Klimaoprema Samobor
EG 2 (2,4)kW - okrugli kanalski grijač zraka snage 2 (2,4)kW
NAPOMENE:
- Predviđena je izvedba ventilacijskog sustava iz okruglih ventilacijskih kanala i fazonskih elemenata
- Okrugli ventilacijski kanali kao spiralno falcana cijev iz pocinčanog lima debljine 0,6mm, promjera prema nacrtu, sa paronepropusnom izolacijom
debljine d=19mm.
- Spoj kanala i fazonskih komada vanjskom ili unutanjom spojnicom
- Spajanje priključnih kutija stropnih distributera zraka i odsisnih anemostata sa ventilacijskim kanalima izvesti pomoći fleksibilne Aluflex
dvoslojne cijevi
- Spoj rekuperatorske jedinice sa ventilacijskim kanalima izvesti kao zrakotijesan fleksibilan spoj platnom radi spriječavanja prijenosa buke i
vibracija na kanalni razvod.
- Na dovodnoj grani svježeg zraka ugrađuju se kanalski električni grijači snage 2 i 2,4kW.
- Na dovodu svježeg zraka i odvodu istrošenog zraka na fasadi montiraju se fiksne protukišne žaluzije u boji fasade
- Odvod kondenzata sa rekupretora i unutarnjih jednica hlađenja odvesti u do najbližeg odvoda umivaonika
- Rekuperacijske ventilacijske jedinice se upravljaju putem žičnih daljinski upravljača na zidu pored ulaznih vrata u prostoriju
- SERVISNI PROSTOR REKUPERATORA
- OTVOR ZA SERVIS REKUPERATORA 45 x 45 cm
2
2
1
SURADNIK: SLAVEN HOFER, stroj.teh.
1000x594m
m
1
1
22
2
OTVORENI PROSTOR
STROJARNICA
IZVESTI ODZRAKE NA NAJVIŠOJ
TOČKI
VENTILOKONVEKTORI
3/4"
3/4"
50°/40°C zimi
7°/12°C ljeti
RADIJATORI50°/40°C zimi
M
1/2"
Odvod kondenzata
ChillerLG ACHH050LBABQh=171 kWQg=180 kWN=55,2kW/400 V~50 HzT=1530 kg
NO 80
NO80
400 V
B (GR)
ABA (HL)
Kompaktna indirektna toplinskapodstanica tip K-250
NO 65
NO65
80°C
60°C
8,4 kW
162kW - GRIJANJE
NO 50NO 50
NO 50NO 50
NO 25
NO 80
PE DN 100
PE DN 100
B (GR)
ABA (HL)
147kW - HLAĐENJE
NO 80
2
2 2
DN 80
DN 80
DN 100 DN 25
DN 25
3
DN 65
DN 65
17 17
2 2
2 2 2 2
2
2 2
2
4
7
6
DN 80
DN 80
5
8
9
10
11
12
13
14
15 16
18 18
19
B
AB
A
50°C
40°C
NO 65
NO 65
NO 80
NO 80
NO 80
NO 80 NO 80
NO 80
NO 80
NO 80
NO 80
NO 80NO 25
NO 25 NO 25
NO 25
NO 25
NO 80
NO 80
PROJEKTANT: IVAN TOMIČIĆ, mag.ing.mech.
NACRT:
PROJEKT:
LOKACIJA:
INVESTITOR:
GRAĐEVINA:
BR.PROJ:
ZOP:
DATUM:
MJERILO:-
LIST:
VRSTA
PROJEKTA:
C A L F A C T I Oj . d . o . o . z a p r o j e k t i r a n j e i i n ž e n j e r i n g
3 1 2 0 7 T e n j a , J a n a P a n n o n i u s a 2 4O I B : 9 5 0 3 2 6 9 4 0 1 8M o b : 0 9 9 / 3 0 1 - 8 1 9 7e - m a i l : c a l f a c t i o . o s @ g m a i l . c o m
Osijek, Istarska ulica 3, k.č.br. 5989/2 i 5989/9 k.o. Osijek
Elektrotehnička i prometna škola Osijek, OIB: 28015293209
Rekonstrukcija i dogradnja elektrotehničke i prometne škole
SP/66-19/IZ
BP-IZV 01/2019
11
STROJARSKI PROJEKT - GRIJANJE, HLAĐENJE I
VENTILACIJA
LISTOPAD 2019.G.
SHEMA SUSTAVA GRIJANJA I
HLAĐENJA
LEGENDA
1. ANTIVIBRACIJSKI PRIKLJUČCI2. KUGLASTA SLAVINA3. ODZRAČIVAČ - ODVAJAČ NEČISTOĆA KAO CALEFI DIRTCAL4. IZOLIRANI INERCIJSKI SPREMNIK 500 lit, SA ODZRAKOM I ISPUSNOM SLAVINOM5. PLOČASTI MEĐUIZMJENJIVAČ, KAO ALFA-LAVAL TL6-BFM6. EKSPANZIJSKA POSUDA SEKUNDARA, 100 l, 3bar7. ELEKTROUPRAVLJAČKI ORMAR8. KOMPAKTNA INDIREKTNA TOPLINSKA PODSTANICA - TIP K-2509. VENTIL ZA PUNJENJE I PRAŽNJENJE10. OSJETNIK VANJSKE TEMPERATURE11. VENTIL SA SIGURNOSNOM PLOMBOM KAO ZAŠTITA OD NEOVLAŠTENOG RUKOVANJA12. AUTOMATSKI ODZRAČNI VENTIL KAO CALEFI MAXCAL13. VISOKOUČINKOVITA PUMPA S MOKRIM ROTOROM KAO GRUNDFOS MAGNA 3 65-150 F, PN 10, Q=25,65m3/h, H=97,4kPa,
primar14. VISOKOUČINKOVITA PUMPA S MOKRIM ROTOROM KAO GRUNDFOS MAGNA 3 65-150 F, PN 10, Q=25,65m3/h, H=51,3kPa,
sekundar15. VISOKOUČINKOVITA PUMPA S MOKRIM ROTOROM KAO GRUNDFOS MAGNA 3 65-120 F, PN 10, Q=27,05m3/h, H=59,2kPa, krug
ventilokonvektora16. VISOKOUČINKOVITA PUMPA S MOKRIM ROTOROM KAO GRUNDFOS ALPHA2 25-40 130, PN 10, Q=0,72m3/h, H=24,35kPa, krug
radijatora17.FILTER SA OTVOROM ZA ČIŠĆENJE18. NEPOVRATNI VENTIL19.EKSPANZIJSKA POSUDA PRIMARA, 24 l, 3bar
SURADNIK: SLAVEN HOFER, stroj.teh.
IZVEDBENI PROJEKT
420x297m
m
EKSPANZIJSKI UREĐAJ
S JEDNOM CRPKOM tip
EU 200-A-I "PIREKO"
OROSLAVLJE
PROJEKTANT: IVAN TOMIČIĆ, mag.ing.mech.
NACRT:
PROJEKT:
LOKACIJA:
INVESTITOR:
GRAĐEVINA:
BR.PROJ:
ZOP:
DATUM:
MJERILO:-
LIST:
VRSTA
PROJEKTA:
C A L F A C T I Oj . d . o . o . z a p r o j e k t i r a n j e i i n ž e n j e r i n g
3 1 2 0 7 T e n j a , J a n a P a n n o n i u s a 2 4O I B : 9 5 0 3 2 6 9 4 0 1 8M o b : 0 9 9 / 3 0 1 - 8 1 9 7e - m a i l : c a l f a c t i o . o s @ g m a i l . c o m
Osijek, Istarska ulica 3, k.č.br. 5989/2 i 5989/9 k.o. Osijek
Elektrotehnička i prometna škola Osijek, OIB: 28015293209
Rekonstrukcija i dogradnja elektrotehničke i prometne škole
SP/66-19/IZ
BP-IZV 01/2019
12
STROJARSKI PROJEKT - GRIJANJE, HLAĐENJE I
VENTILACIJA
LISTOPAD 2019.G.
SHEMA TOPLINSKE STANICE
SURADNIK: SLAVEN HOFER, stroj.teh.
IZVEDBENI PROJEKT
420x297m
m
+0,00
+3,90
odvod kondenzatavoditi u padu
720NO 25
500
dimenzije ventilapolaz/povrat NO20
280
345
225
dvoputni on/off ventilAB-QM + TWA-Z (ugradnja u polaz)
visina
spuš
tenog
strop
a: 3,0
5m
PROJEKTANT: IVAN TOMIČIĆ, mag.ing.mech.
NACRT:
PROJEKT:
LOKACIJA:
INVESTITOR:
GRAĐEVINA:
BR.PROJ:
ZOP:
DATUM:
MJERILO:1:25
LIST:
VRSTA
PROJEKTA:
C A L F A C T I Oj . d . o . o . z a p r o j e k t i r a n j e i i n ž e n j e r i n g
3 1 2 0 7 T e n j a , J a n a P a n n o n i u s a 2 4O I B : 9 5 0 3 2 6 9 4 0 1 8M o b : 0 9 9 / 3 0 1 - 8 1 9 7e - m a i l : c a l f a c t i o . o s @ g m a i l . c o m
Osijek, Istarska ulica 3, k.č.br. 5989/2 i 5989/9 k.o. Osijek
Elektrotehnička i prometna škola Osijek, OIB: 28015293209
Rekonstrukcija i dogradnja elektrotehničke i prometne škole
SP/66-19/IZ
BP-IZV 01/2019
13
STROJARSKI PROJEKT - GRIJANJE, HLAĐENJE I
VENTILACIJA
LISTOPAD 2019.G.
DETALJ UGRADNJE KAZETNOG
VENTILOKONVEKTORA
SURADNIK: SLAVEN HOFER, stroj.teh.
IZVEDBENI PROJEKT
210x297m
m
cijevni razvod voditi u spuštenom stropu
spojiti fleksibilnimpriključcima min NO18
odvod kondenzata na prolazu kroz etažu izolirati
toplinska izolacija
cijevni razvod voditi u spuštenom stropu
odvod kondenzata na prolazu kroz etažu izolirati
toplinska izolacija
cijevi voditi po zidu
A
DETALJ A
odvod kondenzata voditi ufasadi i spojiti na oborinske vode
ventilokonvektor odmaknuti od zida 20-30 mm
PROJEKTANT: IVAN TOMIČIĆ, mag.ing.mech.
NACRT:
PROJEKT:
LOKACIJA:
INVESTITOR:
GRAĐEVINA:
BR.PROJ:
ZOP:
DATUM:
MJERILO:1:50
LIST:
VRSTA
PROJEKTA:
C A L F A C T I Oj . d . o . o . z a p r o j e k t i r a n j e i i n ž e n j e r i n g
3 1 2 0 7 T e n j a , J a n a P a n n o n i u s a 2 4O I B : 9 5 0 3 2 6 9 4 0 1 8M o b : 0 9 9 / 3 0 1 - 8 1 9 7e - m a i l : c a l f a c t i o . o s @ g m a i l . c o m
Osijek, Istarska ulica 3, k.č.br. 5989/2 i 5989/9 k.o. Osijek
Elektrotehnička i prometna škola Osijek, OIB: 28015293209
Rekonstrukcija i dogradnja elektrotehničke i prometne škole
SP/66-19/IZ
BP-IZV 01/2019
14
STROJARSKI PROJEKT - GRIJANJE, HLAĐENJE I
VENTILACIJA
LISTOPAD 2019.G.
DETALJ UGRADNJE PARAPETNOG
VENTILOKONVEKTORA
SURADNIK: SLAVEN HOFER, stroj.teh.
IZVEDBENI PROJEKT
210x297m
m
Pogled - A
cijevi voditi po gredi
toplinska izolacija
spojiti fleksibilnim priključcima min NO18
cijevni razvod voditiu spuštenom stropu
odvod kondenzata
300
610
DETALJ B
M 1:25
PROJEKTANT: IVAN TOMIČIĆ, mag.ing.mech.
NACRT:
PROJEKT:
LOKACIJA:
INVESTITOR:
GRAĐEVINA:
BR.PROJ:
ZOP:
DATUM:
MJERILO:1:25
LIST:
VRSTA
PROJEKTA:
C A L F A C T I Oj . d . o . o . z a p r o j e k t i r a n j e i i n ž e n j e r i n g
3 1 2 0 7 T e n j a , J a n a P a n n o n i u s a 2 4O I B : 9 5 0 3 2 6 9 4 0 1 8M o b : 0 9 9 / 3 0 1 - 8 1 9 7e - m a i l : c a l f a c t i o . o s @ g m a i l . c o m
Osijek, Istarska ulica 3, k.č.br. 5989/2 i 5989/9 k.o. Osijek
Elektrotehnička i prometna škola Osijek, OIB: 28015293209
Rekonstrukcija i dogradnja elektrotehničke i prometne škole
SP/66-19/IZ
BP-IZV 01/2019
15
STROJARSKI PROJEKT - GRIJANJE, HLAĐENJE I
VENTILACIJA
LISTOPAD 2019.G.
UGRADNJA PARAPETNOG
VENTILOKONVEKTORA - POGLED A
SURADNIK: SLAVEN HOFER, stroj.teh.
IZVEDBENI PROJEKT
210x297m
m
DETALJ AM 1:10
DETALJ BM 1:10
priključne cijevi 1/2"
priključne fleksibilnecijevi 1/2"
zaporni ventil 1/2"
troputni ON/OFF ventil 1/2"
odvod kondenzata 1/2"
balansirajući ventil 1/2"
PROJEKTANT: IVAN TOMIČIĆ, mag.ing.mech.
NACRT:
PROJEKT:
LOKACIJA:
INVESTITOR:
GRAĐEVINA:
BR.PROJ:
ZOP:
DATUM:
MJERILO:1:10
LIST:
VRSTA
PROJEKTA:
C A L F A C T I Oj . d . o . o . z a p r o j e k t i r a n j e i i n ž e n j e r i n g
3 1 2 0 7 T e n j a , J a n a P a n n o n i u s a 2 4O I B : 9 5 0 3 2 6 9 4 0 1 8M o b : 0 9 9 / 3 0 1 - 8 1 9 7e - m a i l : c a l f a c t i o . o s @ g m a i l . c o m
Osijek, Istarska ulica 3, k.č.br. 5989/2 i 5989/9 k.o. Osijek
Elektrotehnička i prometna škola Osijek, OIB: 28015293209
Rekonstrukcija i dogradnja elektrotehničke i prometne škole
SP/66-19/IZ
BP-IZV 01/2019
16
STROJARSKI PROJEKT - GRIJANJE, HLAĐENJE I
VENTILACIJA
LISTOPAD 2019.G.
UGRADNJA PARAPETNOG
VENTILOKONVEKTORA - DETALJI A I B
SURADNIK: SLAVEN HOFER, stroj.teh.
IZVEDBENI PROJEKT
210x297m
m