    Summary and conclusions(RET 670)

    The IED can be used for differential protection of three-phase power transformers with main CTs either

    star or delta connected. However the IED has been designed with the assumption that all main CTS arestar connected. The IED can be used in applications where the main CTs are delta connected. For such

    applications the following shall be kept in mind:

    1. The ratio for delta connected CTs shall be set (3) =1.732 times smaller than the actual individual

    phase CT ratio.

    2. The power transformer vector group shall typically be set as Yy0 because the compensation for power

    transformer the actual phase shift is provided by the external delta CT connection.

    3. The zero sequence current is eliminated by the main CT delta connections. Thus on sides where CTs

    are connected in delta the zero sequence current elimination shall be set to Off in the IED.

    (For detailed study pls ref attached engineer manual pageno.59----->)