Summary Test Report
SC and LC Fiber Optic Mating Adapter Testing
Product Name: SC and LC Fiber Optic Mating Adapters
Prepared For: Leviton Mfg. Company Inc.
Prepared By: Experior Laboratories
Service Project Number: 11768
Report Issued: May 21, 2012
Revision: SR-2
Prepared By: Reviewed By: Reviewed By:
Christopher Escobar John Kim Deepak George
Technical Writer Technical Director QA Manager
Leviton Mfg. Company Inc.SPN 11768
Table of Contents • Rev SR-2
This document shall not be reproduced except in full, without the written approval of Experior Laboratories, Inc. The results of the testing reported herein related only to the actual items tested.
Table of Contents
1 Abstract . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2 General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62.1 References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62.2 Test Samples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3 Testing Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103.1 Tests and Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103.2 Test Result Summary. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
4 Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 174.1 Initial Insertion Loss and Return Loss. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
4.1.1 References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 174.1.2 Test Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
4.1.2.1 Test Method and Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 184.1.3 Test Requirement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 204.1.4 Test Results . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 214.1.5 Test Sample Failures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 234.1.6 Test Anomalies. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 234.1.7 Photographs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
5 Appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 265.1 Test Data Sheets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 265.2 Outsourced Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Leviton Mfg. Company Inc.SPN 11768
List of Figures • Rev SR-2
Summary Test Report: SC and LC Fiber Optic Mating Adapters Page 3 of 26
List of FiguresFigure 1: Test Sample Configuration: 6-Pack SC Sample (12 Ports). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7Figure 2: Test Sample Configuration: 6-Pack LC Sample (12 Ports) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8Figure 3: Test Sample: 6-Quad LC Sample (24 Ports) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8Figure 4: Test Sample from Leviton Mfg. Company Inc.: Singlemode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9Figure 5: Test Sample from Leviton Mfg. Company Inc.: Multimode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9Figure 6: Test Program for SPN 11768 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10Figure 7: Test Setup Diagram for Device Under Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18Figure 8: Test Setup Diagram for Initial Insertion Loss (Singlemode): Reference . . . . . . . . . . . . . . . . . . . . 18Figure 9: Test Setup Diagram for Initial Return Loss (Singlemode): Reference . . . . . . . . . . . . . . . . . . . . . . 18Figure 10: Test Setup Diagram for Initial Insertion Loss (Singlemode): Measurement . . . . . . . . . . . . . . . . . 18Figure 11: Test Setup Diagram for Initial Return Loss (Singlemode): Measurement . . . . . . . . . . . . . . . . . . . 18Figure 12: Test Setup Diagram for Initial Insertion Loss (Multimode): Reference . . . . . . . . . . . . . . . . . . . . . 19Figure 13: Test Setup Diagram for Initial Return Loss (Multimode): Reference . . . . . . . . . . . . . . . . . . . . . . 19Figure 14: Test Setup Diagram for Initial Insertion Loss (Multimode): Measurement . . . . . . . . . . . . . . . . . . 19Figure 15: Test Setup Diagram for Initial Return Loss (Multimode): Measurement. . . . . . . . . . . . . . . . . . . . 19Figure 16: Test Setup for Initial Insertion Loss and Return Loss: SC Singlemode . . . . . . . . . . . . . . . . . . . . . 24Figure 17: Test Setup for Initial Insertion Loss and Return Loss: SC Multimode. . . . . . . . . . . . . . . . . . . . . . 24Figure 18: Test Setup for Initial Insertion Loss and Return Loss: LC Singlemode . . . . . . . . . . . . . . . . . . . . . 25Figure 19: Test Setup for Initial Insertion Loss and Return Loss: LC Multimode. . . . . . . . . . . . . . . . . . . . . . 25
List of TablesTable 1: Test Group Description: SC Samples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7Table 2: Test Group Description: LC Samples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7Table 3: Test Program Result Summary: SC Samples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11Table 4: Test Program Result Summary: LC Samples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14Table 5: Test Equipment for Initial Insertion Loss and Return Loss . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17Table 6: Optical Measurement Result Summary for Initial Insertion Loss and Return Loss . . . . . . . . . . . . 21
Leviton Mfg. Company Inc.SPN 11768
List of Acronyms • Rev SR-2
Summary Test Report: SC and LC Fiber Optic Mating Adapters Page 4 of 26
List of Acronyms
• IL: Insertion Loss• RL: Return Loss• SM: Singlemode• MM: Multimode• DUT: Device Under Test
Revision History and Test Deviations
Declaration of Compliance
Experior Laboratories hereby declares that Leviton Mfg. Company Inc. SC and LC samples to be compliant to the test requirements within this test program.
Date Revision Notes
April 24, 2012 SR-1 Initial Release
May 21, 2012 SR-2 • Updated Section 2.2 Test Samples on page 7. • Created new IL/RL test setup diagrams.
Test Deviation Description
--- ---
Leviton Mfg. Company Inc.SPN 11768
Abstract • 1 Rev SR-2
Summary Test Report: SC and LC Fiber Optic Mating Adapters Page 5 of 26
1 ABSTRACT
Client: Leviton Mfg. Company Inc.
Client Contact: Tom Sauter
Client Address: 201 North Service Rd. Melville, NY 11747 USA
This summary test report describes the testing of Leviton Mfg. Company Inc.’s SC and LC Fiber Optic Mating Adapters. This report is a summary of Experior Laboratories’ Test Report SPN 11768 Rev B. Information in this summary test report is organized into five sections.
Section 1, Abstract, on page 1: Overview of this summary test report.Section 2, General Information, on page 2: References of industry standards and other documents used in this summary test report. Description and configuration of device under test.Section 3, Testing Overview, on page 3: Overview of this test program. Includes test sequence and result summary (if applicable) of all tests performed at Experior Laboratories. Section 4, Testing, on page 4: Description of test procedure(s) conducted at Experior Laboratories including monitoring requirements, environmental requirements, mechanical requirements, and test equipment (if applicable).Section 5, Appendix, on page 5: Test data sheets. Information on tests out sourced to another laboratory (if applicable). Failure analysis and test problem reports (if applicable).
An electronic copy of this summary test report is submitted to the customer.
Leviton Mfg. Company Inc.SPN 11768
General Information • 2 Rev SR-2
Summary Test Report: SC and LC Fiber Optic Mating Adapters Page 6 of 26
2 GENERAL INFORMATION
2.1 References
• Quote Number: EXLQ1548-B• PO Number: 458406• Experior Laboratories: Test Report SPN 11768 Rev B• TIA/EIA-455-1B Cable Flexing for Fiber Optic Interconnecting Devices• TIA/EIA-455-2C Impact Test Measurements for Fiber Optic Devices• TIA/EIA-455-4C Fiber Optic Component Temperature Life Test• TIA/EIA-455-5C Humidity Test Procedure for Fiber Optic Components• TIA/EIA-455-6B Cable Retention Test Procedure for Fiber Optic Cable Interconnecting Devices• TIA/EIA-455-13A Visual and Mechanical Inspection of Fiber Optic Components, Devices, and Assemblies• TIA/EIA-455-21A Mating Durability of Fiber Optic Interconnecting Devices• TIA/EIA-455-34A Interconnection Device Insertion Loss Test• TIA/EIA-455-36A Twist Test for Fiber Optic Connecting Devices• TIA/EIA-455-107A Determination of Component Reflectance or Link/System Return Loss Using a Loss Test
Set• TIA/EIA-455-158 Measurement of Breakaway Frictional Force in Fiber Optic Connector Alignment Sleeves• TIA/EIA-455-188 Low Temperature Testing of Fiber Optic Components• TIA-568-C.3 Optical Fiber Cabling Components Standard• TIA/EIA-604-3-B Fiber Optic Connector Intermateability Standard, Type SC and SC-APC• TIA/EIA-604-10A Fiber Optic Connector Intermateability Standard – Type LC• TIA/EIA-604-10B Fiber Optic Connector Intermateability Standard – Type LC
Leviton Mfg. Company Inc.SPN 11768
Test Samples • 2.2 Rev SR-2
Summary Test Report: SC and LC Fiber Optic Mating Adapters Page 7 of 26
2.2 Test Samples
See Table 1, Leviton Mfg. Company Inc. submitted fiber optic mating adapters as shown in Table 1 and Table 2. Ports tested for Samples A, B, and C, are 1-4, 5-8, and 9-12 respectively. Ports tested for Samples D, E, and F, are 1-4, 5-8, and 9-12 respectively.
Table 1: Test Group Description: SC Samples
Table 2: Test Group Description: LC Samples
Figure 1: Test Sample Configuration: 6-Pack SC Sample (12 Ports)
Sample Description Sample Quantity Test Group
6-Pack SC duplex fiber optic mating adapters
6 (samples labeled as A,B,C,D,E and F);Samples A, B and C will have SM cables populated in the
adapters and Samples D, E, F will have MM cables populated in the adapters.
Groups 1, 2, 3, 4
6-Pack SC duplex 1 Group 5
Sample Description Sample Quantity Test Group
6-Pack LC duplex fiber optic mating adapters
6 (samples labeled as A, B, C, D, E and F);Samples A, B and C will have SM cables populated in the
adapters and Samples D, E, F will have MM cables populated in the adapters.
Groups 1, 2, 3, 4
6-Pack LC duplex 1 Group 5
6-Pack Quad LC 1 Group 5
Sample A: Ports 1-4 populated with singlemode cables
Sample B: Ports 5-8 populated with singlemode cables
Sample C: Ports 9-12 populated with singlemode cables
Sample D: Ports 1-4 populated with multimode cables
Sample E: Ports 5-8 populated with multimode cables
Sample F: Ports 9-12 populated with multimode cables
Leviton Mfg. Company Inc.SPN 11768
Test Samples • 2.2 Rev SR-2
Summary Test Report: SC and LC Fiber Optic Mating Adapters Page 8 of 26
Figure 2: Test Sample Configuration: 6-Pack LC Sample (12 Ports)
Figure 3: Test Sample: 6-Quad LC Sample (24 Ports)
Sample A: Ports 1-4 populated with singlemode cables
Sample B: Ports 5-8 populated with singlemode cables
Sample C: Ports 9-12 populated with singlemode cables
Sample D: Ports 1-4 populated with multimode cables
Sample E: Ports 5-8 populated with multimode cables
Sample F: Ports 9-12 populated with multimode cables
Leviton Mfg. Company Inc.SPN 11768
Test Samples • 2.2 Rev SR-2
Summary Test Report: SC and LC Fiber Optic Mating Adapters Page 9 of 26
Figure 4: Test Sample from Leviton Mfg. Company Inc.: Singlemode
Figure 5: Test Sample from Leviton Mfg. Company Inc.: Multimode
Single Mode Samples
Multi Mode Samples
Leviton Mfg. Company Inc.SPN 11768
Testing Overview • 3 Rev SR-2
Summary Test Report: SC and LC Fiber Optic Mating Adapters Page 10 of 26
3 TESTING OVERVIEW
3.1 Tests and Sequence
The test identification numbers in the format of Gx-y are labels given in Experior Laboratories datasheets, where x is the group number, and y is the test number within the group.
Figure 6: Test Program for SPN 11768
Leviton Mfg. Company Inc.SPN 11768
Test Result Summary • 3.2 Rev SR-2
Summary Test Report: SC and LC Fiber Optic Mating Adapters Page 11 of 26
3.2 Test Result Summary
A result matrices are given in Table 3 on page 11 and Table 4 on page 14. All optical characterization measurements shall be conducted at 1310/1550 nm for SM samples (Samples A, B, and C) and 850/1300 nm for MM samples (Samples D, E, and F). Results are summarized by compliant sample ports out of total sample ports tested. See Experior Laboratories’ Test Report SPN 11768 Rev B for raw data and details.
Table 3: Test Program Result Summary: SC Samples
Test Requirement Comply/Total Tested
Group 1
Initial Insertion Loss and Return Loss
IL ≤ 0.75 dB 24/24
SM Samples: RL ≥ 26.0 dB 12/12
MM Samples: RL ≥ 20.0 dB 12/12
G1-2 Low Temperature
During the Test:Attenuation Increase ≤ 0.30 dB 24/24
After the Test: IL ≤ 0.75 dB 24/24
After the Test:SM Samples: RL ≥ 26.0 dB 12/12
After the Test:MM Samples: RL ≥ 20.0 dB 12/12
G1-3 Temperature Life
After the Test: IL ≤ 0.75 dB 24/24
After the Test:SM Samples: RL ≥ 26.0 dB 12/12
After the Test:MM Samples: RL ≥ 20.0 dB 12/12
G1-4 Humidity
During the Test:Attenuation Increase ≤ 0.40 dB 24/24
After the Test: IL ≤ 0.75 dB 24/24
After the Test:SM Samples: RL ≥ 26.0 dB 12/12
After the Test:MM Samples: RL ≥ 20.0 dB 12/12
Leviton Mfg. Company Inc.SPN 11768
Test Result Summary • 3.2 Rev SR-2
Summary Test Report: SC and LC Fiber Optic Mating Adapters Page 12 of 26
Group 2
Initial Insertion Loss and Return Loss
IL ≤ 0.75 dB 24/24
SM Samples: RL ≥ 26.0 dB 12/12
MM Samples: RL ≥ 20.0 dB 12/12
G2-2 Cable Flexing
After the Test: IL ≤ 0.75 dB 24/24
After the Test:SM Samples: RL ≥ 26.0 dB 12/12
After the Test:MM Samples: RL ≥ 20.0 dB 12/12
G2-3 Twist
After the Test: IL ≤ 0.75 dB 24/24
After the Test:SM Samples: RL ≥ 26.0 dB 12/12
After the Test:MM Samples: RL ≥ 20.0 dB 12/12
G2-4 Impact
After the Test: IL ≤ 0.75 dB 24/24
After the Test:SM Samples: RL ≥ 26.0 dB 12/12
After the Test:MM Samples: RL ≥ 20.0 dB 12/12
Group 3
Initial Insertion Loss and Return Loss
IL ≤ 0.75 dB 24/24
SM Samples: RL ≥ 26.0 dB 12/12
MM Samples: RL ≥ 20.0 dB 12/12
G3-2 Cable Retention
After the Test: IL ≤ 0.75 dB 24/24
After the Test:Attenuation Increase ≤ 0.50 dB 24/24
After the Test:SM Samples: RL ≥ 26.0 dB 12/12
After the Test:MM Samples: RL ≥ 20.0 dB 12/12
Test Requirement Comply/Total Tested
Leviton Mfg. Company Inc.SPN 11768
Test Result Summary • 3.2 Rev SR-2
Summary Test Report: SC and LC Fiber Optic Mating Adapters Page 13 of 26
Group 4
Initial Insertion Loss and Return Loss
IL ≤ 0.75 dB 24/24
SM Samples: RL ≥ 26.0 dB 12/12
MM Samples: RL ≥ 20.0 dB 12/12
G4-2 Mating Durability
After the Test: IL ≤ 0.75 dB 15/15
After the Test:SM Samples: RL ≥ 26.0 dB 7/7
After the Test:MM Samples: RL ≥ 20.0 dB 8/8
Group 5
G5-1 IntermateabilityDimension Measurements per
TIA/EIA-604-3-B 12/12
Removal Force ≤ 5.88 N 12/12
Test Requirement Comply/Total Tested
Leviton Mfg. Company Inc.SPN 11768
Test Result Summary • 3.2 Rev SR-2
Summary Test Report: SC and LC Fiber Optic Mating Adapters Page 14 of 26
Table 4: Test Program Result Summary: LC Samples
Test Requirement Comply/Total Tested
Group 1
Initial Insertion Loss and Return Loss
IL ≤ 0.75 dB 24/24
SM Samples: RL ≥ 26.0 dB 12/12
MM Samples: RL ≥ 20.0 dB 12/12
G1-2 Low Temperature
During the Test:Attenuation Increase ≤ 0.30 dB 24/24
After the Test: IL ≤ 0.75 dB 24/24
After the Test:SM Samples: RL ≥ 26.0 dB 12/12
After the Test:MM Samples: RL ≥ 20.0 dB 12/12
G1-3 Temperature Life
After the Test: IL ≤ 0.75 dB 24/24
After the Test:SM Samples: RL ≥ 26.0 dB 12/12
After the Test:MM Samples: RL ≥ 20.0 dB 12/12
G1-4 Humidity
During the Test:Attenuation Increase ≤ 0.40 dB 24/24
After the Test: IL ≤ 0.75 dB 24/24
After the Test:SM Samples: RL ≥ 26.0 dB 12/12
After the Test:MM Samples: RL ≥ 20.0 dB 12/12
Leviton Mfg. Company Inc.SPN 11768
Test Result Summary • 3.2 Rev SR-2
Summary Test Report: SC and LC Fiber Optic Mating Adapters Page 15 of 26
Group 2
Initial Insertion Loss and Return Loss
IL ≤ 0.75 dB 24/24
SM Samples: RL ≥ 26.0 dB 12/12
MM Samples: RL ≥ 20.0 dB 12/12
G2-2 Cable Flexing
After the Test: IL ≤ 0.75 dB 24/24
After the Test:SM Samples: RL ≥ 26.0 dB 12/12
After the Test:MM Samples: RL ≥ 20.0 dB 12/12
G2-3 Twist
After the Test: IL ≤ 0.75 dB 24/24
After the Test:SM Samples: RL ≥ 26.0 dB 12/12
After the Test:MM Samples: RL ≥ 20.0 dB 12/12
G2-4 Impact
After the Test: IL ≤ 0.75 dB 24/24
After the Test:SM Samples: RL ≥ 26.0 dB 12/12
After the Test:MM Samples: RL ≥ 20.0 dB 12/12
Group 3
Initial Insertion Loss and Return Loss
IL ≤ 0.75 dB 24/24
SM Samples: RL ≥ 26.0 dB 12/12
MM Samples: RL ≥ 20.0 dB 12/12
G3-2 Cable Retention
After the Test: IL ≤ 0.75 dB 24/24
After the Test:Attenuation Increase ≤ 0.50 dB 24/24
After the Test:SM Samples: RL ≥ 26.0 dB 12/12
After the Test:MM Samples: RL ≥ 20.0 dB 12/12
Test Requirement Comply/Total Tested
Leviton Mfg. Company Inc.SPN 11768
Test Result Summary • 3.2 Rev SR-2
Summary Test Report: SC and LC Fiber Optic Mating Adapters Page 16 of 26
Group 4
Initial Insertion Loss and Return Loss
IL ≤ 0.75 dB 16/16
SM Samples: RL ≥ 26.0 dB 8/8
MM Samples: RL ≥ 20.0 dB 8/8
G4-2 Mating Durability
After the Test: IL ≤ 0.75 dB 16/16
After the Test:SM Samples: RL ≥ 26.0 dB 8/8
After the Test:MM Samples: RL ≥ 20.0 dB 8/8
Group 5
G5-1 IntermateabilityDimension Measurements per
TIA/EIA-604-10A 12/12
Removal Force ≥ 1.0 N and ≤ 2.5 N 12/12
G5-1 Intermateability(LC Quad Sample)
Dimension Measurements perTIA/EIA-604-10A 12/12
Removal Force ≥ 1.0 N and ≤ 2.5 N 12/12
Test Requirement Comply/Total Tested
Leviton Mfg. Company Inc.SPN 11768
Testing • 4 Rev SR-2
Summary Test Report: SC and LC Fiber Optic Mating Adapters Page 17 of 26
4 TESTING
4.1 Initial Insertion Loss and Return Loss
4.1.1 References
• TIA/EIA-455-34A Interconnection Device Insertion Loss Test• TIA/EIA-455-107A Determination of Component Reflectance or Link/System Return Loss Using a Loss Test
Set
4.1.2 Test Equipment
Table 5: Test Equipment for Initial Insertion Loss and Return LossInstrum. Number Manufacturer Model Number Instrument Description
1102 Hewlett Packard 81533B Optical Head Interface
1186 Agilent 81618A Optical Head Interface Module
1198 Rifocs 715RF-24 Multimode 62.5 Optical Switch
1238 JGR BR5 Quad-Wave Backreflection Meter
1251 Rifocs 781RL-850-106 850nm Multimode RL Meter
1255 Hewlett Packard HP 81533A Optical Head Interface
1256 Hewlett Packard HP 81524A Optical Power Head
1258 Hewlett Packard HP 81524A Optical Power Head
1260 Extech 42280 Temperature Humidity Datalogger
1263 Rifocs 753R-850 Triple 850nm LED Source
1264 Rifocs 753R-1300 Triple 1300nm LED Source
1266 Rifocs 715RF-24-106 1x24 Multimode Optical Switch
1269 Rifocs 715RF-2-106 1x2 Multimode Optical Switch
1273 Rifocs 715RF-2-106 1x2 MM Optical Switch
1399 Tektronix TFP2 FiberMaster Multimode OTDR
1401 Corning OptiSplice CDS Fiber Fusion Splicer
1405 Fujikura CT-30 Fiber Cleaver
1406 Sumitomo FC-6S Fiber Cleaver
1439 Agilent 81624A Optical Power Head
1451 Rifocs 781RL-13-110 1300nm MM Return Loss Meter
Leviton Mfg. Company Inc.SPN 11768
Test Method and Setup • 4.1.2.1 Rev SR-2
Summary Test Report: SC and LC Fiber Optic Mating Adapters Page 18 of 26
4.1.2.1 Test Method and Setup
Measure initial IL and RL as shown from Figure 7 on page 18 to Figure 15 on page 19. The DUT shown in Figure 7 is simplified by populating one port only.
Figure 7: Test Setup Diagram for Device Under Test
Figure 8: Test Setup Diagram for Initial Insertion Loss (Singlemode): Reference
Figure 9: Test Setup Diagram for Initial Return Loss (Singlemode): Reference
Figure 10: Test Setup Diagram for Initial Insertion Loss (Singlemode): Measurement
Figure 11: Test Setup Diagram for Initial Return Loss (Singlemode): Measurement
JGR Power Meter
Launch Cable Connector 1
Mated Connector Pair
JGR
Launch Cable Connector 1
Mated Connector Pair
Mandrel
JGR Power Meter
Launch Cable Optical head inter face
Mated Connector
JGR
Launch Cable
MatedConnector Pair
Mandrel
Leviton Mfg. Company Inc.SPN 11768
Test Method and Setup • 4.1.2.1 Rev SR-2
Summary Test Report: SC and LC Fiber Optic Mating Adapters Page 19 of 26
Figure 12: Test Setup Diagram for Initial Insertion Loss (Multimode): Reference
Figure 13: Test Setup Diagram for Initial Return Loss (Multimode): Reference
Figure 14: Test Setup Diagram for Initial Insertion Loss (Multimode): Measurement
Figure 15: Test Setup Diagram for Initial Return Loss (Multimode): Measurement
850/1300 nmSource Power Meter
Launch CableConnector 1
Mated Connector
pair
Mode Filter
Return Loss Meter:850/1300 nm
Launch Cable Connector 1
Mated Connector
Pair
Mode Fi lter
850/1300 nmSource Power Meter
Launch Cable Optical Head Inter face
Mated Connector
pair
Mode Fi lter
Return Loss Meter:850/1300 nm Power Meter
Launch Cable Optical Head Inter face
Mated Connector
pair
Mode Fi lter
Leviton Mfg. Company Inc.SPN 11768
Test Requirement • 4.1.3 Rev SR-2
Summary Test Report: SC and LC Fiber Optic Mating Adapters Page 20 of 26
The adapter (DUT) is shown with only one port populated. The same procedure applies to all ports.
Mode Filter: Use five close-wound turns with minimal tension on smooth, round mandrels. Create fiber loop diameters. If the Fiber core diameter is 62.5 µm, it will need mode filter diameter of 20 mm. This value represents the fiber loop diameter. If cabled fiber is employed, reduce the mandrel diameter by the cable diameter. For example, 2.5 mm (0.1 inch) cables would require a 17.5 mm diameter (0.65 inch) mandrel to support the fiber loop diameter of 20 mm.
4.1.3 Test Requirement
The requirements for this test are as follows:
• Maximum IL shall be 0.75 dB.• Singlemode Samples: Minimum RL shall be 26.0 dB.• Multimode Samples: Minimum RL shall be 20.0 dB.
Leviton Mfg. Company Inc.SPN 11768
Test Results • 4.1.4 Rev SR-2
Summary Test Report: SC and LC Fiber Optic Mating Adapters Page 21 of 26
4.1.4 Test Results
Optical measurement result summary for Initial Insertion Loss and Return Loss is shown in Table 6. Test details for are available in Experior Laboratories’ Test Report SPN 11768 Rev B.
Table 6: Optical Measurement Result Summary for Initial Insertion Loss and Return LossCategory Optical Measurement Pass/Fail
Group 1 Singlemode SC Samples: A (Ports 1 to 4), B (Ports 5 to 8), and C (Ports 9 to 12)
IL [dB] at 1310 nm Insertion loss measured from 0.03 to 0.38 dB. Pass
IL [dB] at 1550 nm Insertion loss measured from 0.02 to 0.33 dB. Pass
RL [dB] at 1310 nm Return loss measured from 53.3 to 58.9 dB. Pass
RL [dB] at 1550 nm Return loss measured from 53.2 to 60.9 dB. Pass
Group 1 Multimode SC Samples: D (Ports 1 to 4), E (Ports 5 to 8), and F (Ports 9 to 12)
IL [dB] at 850 nm Insertion loss measured from 0.05 to 0.13 dB. Pass
IL [dB] at 1300 nm Insertion loss measured from 0.04 to 0.18 dB. Pass
RL [dB] at 850 nm Return loss measurements were > 40 dB. Pass
RL [dB] at 1300 nm Return loss measurements were > 40 dB. Pass
Group 1 Singlemode LC Samples: A (Ports 1 to 4), B (Ports 5 to 8), and C (Ports 9 to 12)
IL [dB] at 1310 nm Insertion loss measured from -0.02 to 0.35 dB. Pass
IL [dB] at 1550 nm Insertion loss measured from -0.05 to 0.26 dB. Pass
RL [dB] at 1310 nm Return loss measured from 53.9 to 58.1 dB. Pass
RL [dB] at 1550 nm Return loss measured from 55.2 to 58.6 dB. Pass
Group 1 Multimode LC Samples: D (Ports 1 to 4), E (Ports 5 to 8), and F (Ports 9 to 12)
IL [dB] at 850 nm Insertion loss measured from 0.03 to 0.12 dB. Pass
IL [dB] at 1300 nm Insertion loss measured from 0.02 to 0.08 dB. Pass
RL [dB] at 850 nm Return loss measurements were > 40 dB. Pass
RL [dB] at 1300 nm Return loss measurements were > 40 dB. Pass
Group 2 Singlemode SC Samples: A (Ports 1 to 4), B (Ports 5 to 8), and C (Ports 9 to 12)
IL [dB] at 1310 nm Insertion loss measured from 0.04 to 0.33 dB. Pass
IL [dB] at 1550 nm Insertion loss measured from 0.02 to 0.25 dB. Pass
RL [dB] at 1310 nm Return loss measured from 54.9 to 64.4 dB. Pass
RL [dB] at 1550 nm Return loss measured from 55.4 to 64.4 dB. Pass
Group 2 Multimode SC Samples: D (Ports 1 to 4), E (Ports 5 to 8), and F (Ports 9 to 12)
IL [dB] at 850 nm Insertion loss measured from 0.04 to 0.02 dB. Pass
IL [dB] at 1300 nm Insertion loss measured from 0.02 to 0.15 dB. Pass
RL [dB] at 850 nm Return loss measurements were > 40 dB. Pass
RL [dB] at 1300 nm Return loss measurements were > 40 dB. Pass
Leviton Mfg. Company Inc.SPN 11768
Test Results • 4.1.4 Rev SR-2
Summary Test Report: SC and LC Fiber Optic Mating Adapters Page 22 of 26
Group 2 Singlemode LC Samples: A (Ports 1 to 4), B (Ports 5 to 8), and C (Ports 9 to 12)
IL [dB] at 1310 nm Insertion loss measured from -0.04 to 0.27 dB. Pass
IL [dB] at 1550 nm Insertion loss measured from -0.05 to 0.20 dB. Pass
RL [dB] at 1310 nm Return loss measured from 53.4 to 57.5 dB. Pass
RL [dB] at 1550 nm Return loss measured from 54.5 to 57.6 dB. Pass
Group 2 Multimode LC Samples: D (Ports 1 to 4), E (Ports 5 to 8), and F (Ports 9 to 12)
IL [dB] at 850 nm Insertion loss measured from 0.06 to 0.04 dB. Pass
IL [dB] at 1300 nm Insertion loss measured from 0.04 to 0.10 dB. Pass
RL [dB] at 850 nm Return loss measurements were > 40 dB. Pass
RL [dB] at 1300 nm Return loss measurements were > 40 dB. Pass
Group 3 Singlemode SC Samples: A (Ports 1 to 4), B (Ports 5 to 8), and C (Ports 9 to 12)
IL [dB] at 1310 nm Insertion loss measured from 0.02 to 0.39 dB. Pass
IL [dB] at 1550 nm Insertion loss measured from 0.02 to 0.30 dB. Pass
RL [dB] at 1310 nm Return loss measured from 50.9 to 60.8 dB. Pass
RL [dB] at 1550 nm Return loss measured from 52.4 to 61.7 dB. Pass
Group 3 Multimode SC Samples: D (Ports 1 to 4), E (Ports 5 to 8), and F (Ports 9 to 12)
IL [dB] at 850 nm Insertion loss measured from 0.04 to 0.28 dB. Pass
IL [dB] at 1300 nm Insertion loss measured from 0.02 to 0.27 dB. Pass
RL [dB] at 850 nm Return loss measurements were > 40 dB. Pass
RL [dB] at 1300 nm Return loss measurements were > 40 dB. Pass
Group 3 Singlemode LC Samples: A (Ports 1 to 4), B (Ports 5 to 8), and C (Ports 9 to 12)
IL [dB] at 1310 nm Insertion loss measured from -0.03 to 0.27 dB. Pass
IL [dB] at 1550 nm Insertion loss measured from -0.03 to 0.26 dB. Pass
RL [dB] at 1310 nm Return loss measured from 54.0 to 60.0 dB. Pass
RL [dB] at 1550 nm Return loss measured from 54.7 to 60.0 dB. Pass
Group 3 Multimode LC Samples: D (Ports 1 to 4), E (Ports 5 to 8), and F (Ports 9 to 12)
IL [dB] at 850 nm Insertion loss measured from 0.00 to 0.13 dB. Pass
IL [dB] at 1300 nm Insertion loss measured from -0.01 to 0.10 dB. Pass
RL [dB] at 850 nm Return loss measurements were > 40 dB. Pass
RL [dB] at 1300 nm Return loss measurements were > 40 dB. Pass
Group 4 Singlemode SC Samples: A (Ports 1 to 4), B (Ports 5 to 8), and C (Ports 9 to 12)
IL [dB] at 1310 nm Insertion loss measured from 0.03 to 0.35 dB. Pass
IL [dB] at 1550 nm Insertion loss measured from 0.03 to 0.29 dB. Pass
RL [dB] at 1310 nm Return loss measured from 54.1 to 59.4 dB. Pass
RL [dB] at 1550 nm Return loss measured from 55.0 to 60.7 dB. Pass
Category Optical Measurement Pass/Fail
Leviton Mfg. Company Inc.SPN 11768
Test Sample Failures • 4.1.5 Rev SR-2
Summary Test Report: SC and LC Fiber Optic Mating Adapters Page 23 of 26
4.1.5 Test Sample Failures
No test sample failures exist for this test.
4.1.6 Test Anomalies
No test anomalies exist for this test.
Group 4 Multimode SC Samples: D (Ports 1 to 4), E (Ports 5 to 8), and F (Ports 9 to 12)
IL [dB] at 850 nm Insertion loss measured from 0.04 to 0.15 dB. Pass
IL [dB] at 1300 nm Insertion loss measured from 0.02 to 0.18 dB. Pass
RL [dB] at 850 nm Return loss measurements were > 40 dB. Pass
RL [dB] at 1300 nm Return loss measurements were > 40 dB. Pass
Group 4 Singlemode LC Samples: A (Ports 1 to 2), B (Ports 5 to 7), and C (Ports 9 to 11)
IL [dB] at 1310 nm Insertion loss measured from -0.01 to 0.31 dB. Pass
IL [dB] at 1550 nm Insertion loss measured from -0.01 to 0.26 dB. Pass
RL [dB] at 1310 nm Return loss measured from 53.6 to 57.3 dB. Pass
RL [dB] at 1550 nm Return loss measured from 55.2 to 57.6 dB. Pass
Group 4 Multimode LC Samples: D (Ports 1, 3, 4), E (Ports 7 to 8), and F (Ports 9 to 11)
IL [dB] at 850 nm Insertion loss measured from 0.05 to 0.12 dB. Pass
IL [dB] at 1300 nm Insertion loss measured from 0.04 to 0.09 dB. Pass
RL [dB] at 850 nm Return loss measurements were > 40 dB. Pass
RL [dB] at 1300 nm Return loss measurements were > 40 dB. Pass
Category Optical Measurement Pass/Fail
Leviton Mfg. Company Inc.SPN 11768
Photographs • 4.1.7 Rev SR-2
Summary Test Report: SC and LC Fiber Optic Mating Adapters Page 24 of 26
4.1.7 Photographs
Figure 16: Test Setup for Initial Insertion Loss and Return Loss: SC Singlemode
Figure 17: Test Setup for Initial Insertion Loss and Return Loss: SC Multimode
IL-RL measurements in progress on SM samples.
IL-RL measurements in progress on MM samples
Leviton Mfg. Company Inc.SPN 11768
Photographs • 4.1.7 Rev SR-2
Summary Test Report: SC and LC Fiber Optic Mating Adapters Page 25 of 26
Figure 18: Test Setup for Initial Insertion Loss and Return Loss: LC Singlemode
Figure 19: Test Setup for Initial Insertion Loss and Return Loss: LC Multimode
IL-RL measurements in progress on SM samples
IL-RL measurements in progress on MM samples
Leviton Mfg. Company Inc.SPN 11768
Appendix • 5 Rev SR-2
Summary Test Report: SC and LC Fiber Optic Mating Adapters Page 26 of 26
5 APPENDIX
5.1 Test Data Sheets
See Experior Laboratories’ Test Report SPN 11768 Rev B for raw data and details.
5.2 Outsourced Tests
All testing was conducted by Experior Laboratories.