SSM1Instruction Manual
Measures •Pressurefrom0~500psia •Temperaturefrom-40˚~400˚F
Calculates •Superheatforlowside •Subcoolforhighside (TVX)Systems
Refrigerants: •R22 •R134a •R404a •R410a
1.800.547.5740www.ueitest.com
Supe
r Hea
t / Su
b Coo
l Mete
r
SSM1: Super Heat / Sub Cool Meter
ThankyouforpurchasingtheUEiSSM1Superheat/SubcoolMeter.UsetheSSM1tomeasuresuperheatandsubcoolbydirectconnec-tionsfortemperatureandpressure.TheSSM1isprogrammedwiththemostcommonfourrefrigerants,withdatafromtheNIST-Prorefrigerationdatabasefortemperature-pressurevalues.
Technical NoteSuperheatandsubcoolarethemosteffectivemeasurestodetermineifasystemisproperlychargedandoperatingwithinmanufacture
guidelines.
1.
What is Super Heat / Sub Cool? Refrigerantsuperheatreferstotheriseintemperatureofvaporaftertherefrigeranthascom-pletelychangedfromaliquidtoagas.Thedewpoint(temperatureatmeasuredpressurewherealloftheliquidevaporates)isdeterminedbypropertiesoftherefrigerantandmeasuringthepressure.Whencom-paringthistothemeasuredpipetemperatureofthereturnlinewilldeterminesuperheat.TheSSM1willcalculatethisvaluedirectlyandupdateinrealtime.Usesuperheatonfixedorificeorcapillarysystems.
Refrigerantsubcoolingreferstothedropintemperatureofliquidrefrigerantafterithascom-pletelychangedfromagastoaliquid.Theboilingpoint(temperatureatmeasuredpressurewheretheliquidstopsboilingandstartstofurthercool)isdeter-minedbypropertiesoftherefrigerantandmeasuringpressure.Whencomparingthistothemeasuredpipetemperatureattheexitofthecondenserdeterminessubcooling.TheSSM1willcalculatethisvaluedirectly,andupdateinrealtime.UseSubcoolingonTXVsystems,astheyaredesignedtomaintainaconstantsuperheat.
2.
OPERATION
1. Presstopowerthemeteron
2. ZeroPressure:Whiledisplayingpressureholdthe “Pressure/TEMP”buttonfor3seconds.
3. Pressthe“Pressure/TEMP”buttontoselectthe pressureortemperaturemode. 4. RefrigerantType:Pressthe“RefrigType”buttonto scrollthroughtheavailablerefrigeranttypes (R22,R134a,R404A,R40A).
5. Press“”buttontoswitchthebacklightonoroff.
6. Press“TempSH/SC”whiledisplayingtemperatureto scrollthrougheithertheprobetemperature,calculated superheatorcalculatedsubcool.
7. Press“Scale”toselectdesiredunitsforpressureor temperature.Theavailableunitsforpressureinclude PSI,BAR,KPA,Kg/cm2,InHgandcmHg.Theavailable unitsfortemperatureinclude°Fand°C.
3.
4.
CONNECTIONS
1. Connectastandardrefrigeranthosetothe¼”flare connectorontopoftheSSM1.(Fig.1)-OR-Connectthe SSM1in-linetoarefrigerantsourceusingthetee fitting(Fig.2)
2. Connecttheincludedpipeclampprobetothek-type inputjackontopoftheSSM1.(Fig.1)
Fig.2Fig.1
MEASuRINg SuPERHEAT
1.Connectthepressuretothesuctionline serviceport
2.Attachthepipeclamptemperatureprobetothe suctionline(mustbeatleast6”fromthe compressor)
1.
2.
5.
5.Add/removerefrigerantbyconnectingtheSSM1 in-linetoarefrigerantsourceandmonitorpressure whileaddingorremovingrefrigerant.
NOTE: Refer to manufacturers specification and procedures when adding / removing refrigerant.
6.
3.Press“RefrigType”to selecttheproper refrigerant.Theselected refrigeranttypewillshow onthedisplay.*
4.Press“TEMPSH/SC”to selectthedesired parametertoview.
*
MEASuRINg SuBCOOL
1.Connectpressuretotheliquidlineserviceport
2.Attachthepipeclamptemperatureprobeonthe condenserexitline
7.
1.
2.
3.Press“RefrigType”to selecttheproper refrigerant.Theselected refrigeranttypewillshow onthedisplay.*
4.Press“TEMPSH/SC”to selectthedesired parametertoview.
8.
*
5.Add/removerefrigerantbyconnectingtheSSM1 in-linetoarefrigerantsourceandmonitorpressure whileaddingorremovingrefrigerant.
NOTE: Refer to manufacturers specification and procedures when adding / removing refrigerant.
TEMPERATuRE CALIBRATION
Aprocesstosettemperaturecalibrationtoanicepointisincludedtocompensatefordifferencesintemperaturesensors,ortoresettheunittoproperoperation.Pleasefollowthesestepstoperformatemperatureset; 1. Connecttemperatureprobe 2. Press“PressureTEMP”todisplayprobe temperature(verifythat“TEMP”isshownon theLCD. 3. Placethetemperatureprobesensingareaina mixtureofcrushediceandwater.(Distilled waterwillprovidethemostaccuratesource) 4. Stirtheicewatermixturewiththetemperature probeandallowthereadingtostabilize 5. Pressandhold“TempSH/SC”buttonforfour seconds
Thiswillsettheicepointto32°F.Themeterwill compensateforchangesupto10°F.
9.
10.
SPECIFICATIONS
• OperatingEnvironment:32~122°F• StorageEnvironment:0~140°F• Over-rangeindication:OL• Autopoweroff:After30minutesidle NOTE: Turn OFF when not in use to extend battery life.• Battery:Standard9Vbattery,NEDA1604, IEC6F22
Function Resolution Accuracy0~500psia 0.1psi ±0.5%FS+1 (2kPa,0.02bars) digit
-40~400°F 0.1° ±1°F(-40~200°F)(-40~204°C) or±0.5°C(-40~93°C) ±2°F(201~400°F) or±1°C(94~204°C)
WARRANTyTheSSM1iswarrantedtobefreefromdefectsinmaterialsandworkmanshipforaperiodofthreeyearsfromthedateofpurchase.Ifwithinthewarrantyperiodyourinstrumentshouldbecomeinoperativefromsuchdefects,theunitwillberepairedorreplacedatUEi’soption.Thiswarrantycoversnormaluseanddoesnotcoverdamagewhichoccursinshipmentorfailurewhichresultsfromalteration,tampering,accident,misuse,abuse,neglectorimpropermaintenance.Batteriesandconsequentialdamageresultingfromfailedbatteriesarenotcoveredbywarranty. Anyimpliedwarranties,includingbutnotlimitedtoimpliedwarrantiesofmerchantabilityandfitnessforaparticularpurpose,arelimitedtotheexpresswarranty.UEishallnotbeliableforlossofuseoftheinstrumentorotherincidentalorconsequentialdam-ages,expenses,oreconomicloss,orforanyclaimorclaimsforsuchdamage,expensesoreconomicloss.Apurchasereceiptorotherproofoforiginalpurchasedatewillberequiredbeforewar-rantyrepairswillberendered.Instrumentsoutofwarrantywillberepaired(whenrepairable)foraservicecharge.Returntheunitpostagepaidandinsuredto: