Superconducting Fault Current LimitersProf. Dr.-Ing. Mathias Noe, Karlsruhe Institute of TechnologyInstitute for Technical PhysicsEUCAS Short Course Power Applications, , September 17th 2017, Geneva

Page 2: Superconducting Fault Current Limiters · SuperconductingFault Current Limiters Howto design a resistive fault current limiter? Nominal voltage 24 kV Nominal current 1005 A AC withstand

KIT-Zentrum Energie2 M. Noe, EUCAS Short Course, Power Applications – Fault Current Limiters

Table of Contents

MotivationBasic PrinciplesDesign ExampleState-of-the-ArtSummary

Your questions are welcome any time

Page 3: Superconducting Fault Current Limiters · SuperconductingFault Current Limiters Howto design a resistive fault current limiter? Nominal voltage 24 kV Nominal current 1005 A AC withstand

KIT-Zentrum Energie3 M. Noe, EUCAS Short Course, Power Applications – Fault Current Limiters

It is impossible to avoid short-cicuit currents

Page 4: Superconducting Fault Current Limiters · SuperconductingFault Current Limiters Howto design a resistive fault current limiter? Nominal voltage 24 kV Nominal current 1005 A AC withstand

KIT-Zentrum Energie4 M. Noe, EUCAS Short Course, Power Applications – Fault Current Limiters

Conventional Measures to limit short-circuitcurrents

• Splitting into sub grids

• Introducing ahigher voltage range

• Splitting of bus bars

• (Sequential tripping)

• High impedancetransformers

• Current limitingair core reactors

Novel Concepts

• Superconductors

• Semiconductorse.g. FACTS

• Hybrid systems

Topologicalmeasures

Apparatusmeasures

PassiveIncrease of impedance at

nominal and fault conditions

ActiveSmall impedance at nominal loadfast increase of impedance at fault

• High voltage fuses(< 1 kA, < 36 kV)

• IS-limiter, CLiP(< 4 kA, < 36 kV)

• FCL circuit breakers

Page 5: Superconducting Fault Current Limiters · SuperconductingFault Current Limiters Howto design a resistive fault current limiter? Nominal voltage 24 kV Nominal current 1005 A AC withstand

KIT-Zentrum Energie5 M. Noe, EUCAS Short Course, Power Applications – Fault Current Limiters

Short-Circuit Currents

Grid Transformer Transfer Line Load

Peak short-circuit current Kp Ii 22

j XQ j XT j XL

Stationary Electrical Circuit (Three phase short-circuit)

3nUc

RLRTRQ

LTQK ZZZZ

kI

k

b

n

K

n

nb

k

nk Z

ZcIIgetwe

IUZwith

ZUcI

33

c=1.1 for high SC currents

c=1 for low SC currents

Page 6: Superconducting Fault Current Limiters · SuperconductingFault Current Limiters Howto design a resistive fault current limiter? Nominal voltage 24 kV Nominal current 1005 A AC withstand

KIT-Zentrum Energie6 M. Noe, EUCAS Short Course, Power Applications – Fault Current Limiters

Table of Contents

MotivationBasic PrinciplesDesign ExampleState-of-the-ArtSummary

Your questions are welcome any time

Page 7: Superconducting Fault Current Limiters · SuperconductingFault Current Limiters Howto design a resistive fault current limiter? Nominal voltage 24 kV Nominal current 1005 A AC withstand

KIT-Zentrum Energie11 M. Noe, EUCAS Short Course, Power Applications – Fault Current Limiters

Ideal Fault Current Limiter Fast short-circuit limitation No or small impedance at normal operation Fast and automatic recovery Fail safe Applicable at high voltages Cost effective

Recovery

limited

SCFCL

Normal Operation Short-Circuit

Time

unlimited

Cur

rent

Page 8: Superconducting Fault Current Limiters · SuperconductingFault Current Limiters Howto design a resistive fault current limiter? Nominal voltage 24 kV Nominal current 1005 A AC withstand

KIT-Zentrum Energie12 M. Noe, EUCAS Short Course, Power Applications – Fault Current Limiters

Superconducting Fault Current LimitersDifferent types

and many more…

Page 9: Superconducting Fault Current Limiters · SuperconductingFault Current Limiters Howto design a resistive fault current limiter? Nominal voltage 24 kV Nominal current 1005 A AC withstand

KIT-Zentrum Energie13 M. Noe, EUCAS Short Course, Power Applications – Fault Current Limiters

Table of Contents

MotivationBasic PrinciplesDesign ExampleState-of-the-ArtSummary

Your questions are welcome any time

Page 10: Superconducting Fault Current Limiters · SuperconductingFault Current Limiters Howto design a resistive fault current limiter? Nominal voltage 24 kV Nominal current 1005 A AC withstand

KIT-Zentrum Energie14 M. Noe, EUCAS Short Course, Power Applications – Fault Current Limiters

Superconducting Fault Current LimitersHow to design a resistive fault current limiter?

1.4 Ohm

Page 11: Superconducting Fault Current Limiters · SuperconductingFault Current Limiters Howto design a resistive fault current limiter? Nominal voltage 24 kV Nominal current 1005 A AC withstand

KIT-Zentrum Energie15 M. Noe, EUCAS Short Course, Power Applications – Fault Current Limiters

Superconducting Fault Current LimitersHow to design a resistive fault current limiter?

Nominal voltage 24 kVNominal current 1005 AAC withstand voltage 50 kVLightning impulse 125 kVMax. prospective current (peak) 10.8 kALimitation time  120 msMax. short‐circuit current cont. (RMS) 4 kARecovery time < 30 s

1.4 Ohm

Page 12: Superconducting Fault Current Limiters · SuperconductingFault Current Limiters Howto design a resistive fault current limiter? Nominal voltage 24 kV Nominal current 1005 A AC withstand

KIT-Zentrum Energie17 M. Noe, EUCAS Short Course, Power Applications – Fault Current Limiters

Superconducting fault current limitersHow much superconducting wire is needed?

16.5275

1005414.12

AA

IIn

c

rp

How many tapes in parallel?

Assumption 2011 for 10mm wide YBCO tape at 77K, sf

What is the total tape length?1) What is the total voltage along the tape during limiation?

kVkAkVU RMS 25.84.143

24lim,

2) Do not overheat the tape during limitation?

For a electrical field of 0,43 V/cm the temperature during limitation time of 120 ms can bekept below 360 K.

mmlSC 342036190

Page 13: Superconducting Fault Current Limiters · SuperconductingFault Current Limiters Howto design a resistive fault current limiter? Nominal voltage 24 kV Nominal current 1005 A AC withstand

KIT-Zentrum Energie18 M. Noe, EUCAS Short Course, Power Applications – Fault Current Limiters

Superconducting fault current limitersWhich configuration for the HTS?

BBifilar straight

AStraight line

DBifilar coil

CMonofilar coil

Page 14: Superconducting Fault Current Limiters · SuperconductingFault Current Limiters Howto design a resistive fault current limiter? Nominal voltage 24 kV Nominal current 1005 A AC withstand

KIT-Zentrum Energie20 M. Noe, EUCAS Short Course, Power Applications – Fault Current Limiters

Superconducting fault current limitersHow to calculate the total loss?

Current lead loss?

45 W/kA for uncooled and optimized copper current lead from 300 K to 77 K

45 W/kA * 1 kA *6=270 W at nominal current

Page 15: Superconducting Fault Current Limiters · SuperconductingFault Current Limiters Howto design a resistive fault current limiter? Nominal voltage 24 kV Nominal current 1005 A AC withstand

KIT-Zentrum Energie21 M. Noe, EUCAS Short Course, Power Applications – Fault Current Limiters

Superconducting fault current limitersHow to calculate the total loss?

Loss of the cyrostat?

P=120 W

Three LN2 vessels in onevacuum vessel.

Page 16: Superconducting Fault Current Limiters · SuperconductingFault Current Limiters Howto design a resistive fault current limiter? Nominal voltage 24 kV Nominal current 1005 A AC withstand

KIT-Zentrum Energie22 M. Noe, EUCAS Short Course, Power Applications – Fault Current Limiters

Superconducting fault current limitersHow to calculate the total loss?

AC loss of the superconductor?

Clem 2008 PRB 77 134506

P f0I c2 2a2 a x

c

a

tanh1sinh2 x

D sinh2 c

Dsinh2 a

D sinh2 c

D

dx d12a

1 ca 8 3a

tan1sinh2 a

D sinh2 c

Dsinh2 c

D sinh2 x

D

0

c

dx

2a

D

Page 17: Superconducting Fault Current Limiters · SuperconductingFault Current Limiters Howto design a resistive fault current limiter? Nominal voltage 24 kV Nominal current 1005 A AC withstand

KIT-Zentrum Energie23 M. Noe, EUCAS Short Course, Power Applications – Fault Current Limiters

Superconducting fault current limitersHow to calculate the total loss?

Summary of total loss

Page 18: Superconducting Fault Current Limiters · SuperconductingFault Current Limiters Howto design a resistive fault current limiter? Nominal voltage 24 kV Nominal current 1005 A AC withstand

KIT-Zentrum Energie24 M. Noe, EUCAS Short Course, Power Applications – Fault Current Limiters

Superconducting fault current limitersWhich cooling option?

A B C D

Page 19: Superconducting Fault Current Limiters · SuperconductingFault Current Limiters Howto design a resistive fault current limiter? Nominal voltage 24 kV Nominal current 1005 A AC withstand

KIT-Zentrum Energie25 M. Noe, EUCAS Short Course, Power Applications – Fault Current Limiters

Table of Contents

MotivationBasic PrinciplesDesign ExampleState-of-the-ArtSummary

Your questions are welcome any time

Page 20: Superconducting Fault Current Limiters · SuperconductingFault Current Limiters Howto design a resistive fault current limiter? Nominal voltage 24 kV Nominal current 1005 A AC withstand

KIT-Zentrum Energie26 M. Noe, EUCAS Short Course, Power Applications – Fault Current Limiters

Superconducting fault current limitersMajor projects on resistive type SFCL

Lead Company Year/Country 1) Data 2) Phase SuperconductorACCEL/NexansSC D / ´04 12 kV, 600 A 3‐ph. Bi 2212 bulkCESI RICERCA Italy / ´05 3.2 kV, 220 A 3‐ph. Bi 2223 tapeSiemens / AMSC D / USA / ´07 7.5 kV, 300 A 1‐ph. YBCO tapeLSIS Korea /’07 24 kV, 630A 3‐ph. YBCO tapeHyundai / AMSC Korea / ´07 13.2 kV, 630 A 1‐ph. YBCO tapeKEPRI Korea / ´07 22.9 kV, 630 A 3‐ph. Bi 2212 bulkToshiba J / 2008 6.6 kV, 72 A 3‐ph. YBCO tapeNexans SC D / 2009 12 kV, 100 A 3‐ph. Bi 2212 bulkNexans SC D / 2009 12 kV, 800 A 3‐ph. Bi 2212 bulkRSE I / 2011 9 kV, 250 A 3‐ph. Bi 2223 tapeRSE I / 2012 9 kV, 1 kA 3‐ph. YBCO tapeKEPRI Korea / 2011 22.9 kV, 3 kA 3‐ph. YBCO tapeNexans SC D / 2011 12 kV, 800 A 3‐ph. YBCO tapeAMSC / Siemens USA / D / 2012  115 kV, 1.2 kA 3‐ph. YBCO tapeRolls Royce UK / ‐ 11.5 kV, 400 A 3‐ph. MgB2  wireNexans SC D/2013 10 kV, 2.4 kA 3‐ph. YBCO tapeNexans SC EU 2013 24 kV, 1 kA 3‐ph. YBCO tapeApplied Materiaks US /2013 15 kV / 1kA 3‐ph. YBCO tapeNexans SC UK/2015 12 kV/1.6 kA 3‐ph. YBCO tapeApplied Materials US / 2016 115 kV 3‐ph. YBCO tapePlus more Projects in Russia, China, India

Page 21: Superconducting Fault Current Limiters · SuperconductingFault Current Limiters Howto design a resistive fault current limiter? Nominal voltage 24 kV Nominal current 1005 A AC withstand

KIT-Zentrum Energie27 M. Noe, EUCAS Short Course, Power Applications – Fault Current Limiters

Superconducting Fault Current LimitersState‐of‐the‐Art

Page 22: Superconducting Fault Current Limiters · SuperconductingFault Current Limiters Howto design a resistive fault current limiter? Nominal voltage 24 kV Nominal current 1005 A AC withstand

KIT-Zentrum Energie28 M. Noe, EUCAS Short Course, Power Applications – Fault Current Limiters

Superconducting fault current limitersRecent installation12 kV, 1600 A resistive FCL installed in busbar at  Western Power Distribution, Chester Street, Birmingham, since End 2015

Page 23: Superconducting Fault Current Limiters · SuperconductingFault Current Limiters Howto design a resistive fault current limiter? Nominal voltage 24 kV Nominal current 1005 A AC withstand

KIT-Zentrum Energie29 M. Noe, EUCAS Short Course, Power Applications – Fault Current Limiters

Superconducting fault current limitersRecent developmentChina

Page 24: Superconducting Fault Current Limiters · SuperconductingFault Current Limiters Howto design a resistive fault current limiter? Nominal voltage 24 kV Nominal current 1005 A AC withstand

KIT-Zentrum Energie30 M. Noe, EUCAS Short Course, Power Applications – Fault Current Limiters

Superconducting fault current limitersApplications

Page 25: Superconducting Fault Current Limiters · SuperconductingFault Current Limiters Howto design a resistive fault current limiter? Nominal voltage 24 kV Nominal current 1005 A AC withstand

KIT-Zentrum Energie31 M. Noe, EUCAS Short Course, Power Applications – Fault Current Limiters

Superconducting Air Core Fault Current LimitersR&D Example

Page 26: Superconducting Fault Current Limiters · SuperconductingFault Current Limiters Howto design a resistive fault current limiter? Nominal voltage 24 kV Nominal current 1005 A AC withstand

KIT-Zentrum Energie32 M. Noe, EUCAS Short Course, Power Applications – Fault Current Limiters

Superconducting Air Core Fault Current LimitersR&D ExampleElectrical Equivalent Circuit

Page 27: Superconducting Fault Current Limiters · SuperconductingFault Current Limiters Howto design a resistive fault current limiter? Nominal voltage 24 kV Nominal current 1005 A AC withstand

KIT-Zentrum Energie33 M. Noe, EUCAS Short Course, Power Applications – Fault Current Limiters

Superconducting Air Core Fault Current LimitersR&D ExampleMagnetic field distribution in case of (A) the air core reactor and (B) the AC‐SFCL during normal operation

Page 28: Superconducting Fault Current Limiters · SuperconductingFault Current Limiters Howto design a resistive fault current limiter? Nominal voltage 24 kV Nominal current 1005 A AC withstand

KIT-Zentrum Energie34 M. Noe, EUCAS Short Course, Power Applications – Fault Current Limiters

Superconducting Air Core Fault Current LimitersR&D Example60 kVA Laboratory Demonstrator

Page 29: Superconducting Fault Current Limiters · SuperconductingFault Current Limiters Howto design a resistive fault current limiter? Nominal voltage 24 kV Nominal current 1005 A AC withstand

KIT-Zentrum Energie35 M. Noe, EUCAS Short Course, Power Applications – Fault Current Limiters

Superconducting Air Core Fault Current LimitersR&D ExampleSimulation of expected progression of peak limited short‐circuit current |Îlim| with peak prospective current |Ip|

Page 30: Superconducting Fault Current Limiters · SuperconductingFault Current Limiters Howto design a resistive fault current limiter? Nominal voltage 24 kV Nominal current 1005 A AC withstand

KIT-Zentrum Energie36 M. Noe, EUCAS Short Course, Power Applications – Fault Current Limiters

Superconducting Air Core Fault Current LimitersR&D ExampleMeasurement of expected progression of peak limited short‐circuit current |Îlim| with peak prospective current |Ip|

Page 31: Superconducting Fault Current Limiters · SuperconductingFault Current Limiters Howto design a resistive fault current limiter? Nominal voltage 24 kV Nominal current 1005 A AC withstand

KIT-Zentrum Energie37 M. Noe, EUCAS Short Course, Power Applications – Fault Current Limiters

Superconducting Air Core Fault Current LimitersR&D Example

ObjectivesBuilt and test a single phase 10 kV, 600 A air coil SFCLProject partnersSiemens, KIT

Page 32: Superconducting Fault Current Limiters · SuperconductingFault Current Limiters Howto design a resistive fault current limiter? Nominal voltage 24 kV Nominal current 1005 A AC withstand

KIT-Zentrum Energie38 M. Noe, EUCAS Short Course, Power Applications – Fault Current Limiters

Table of Contents

MotivationBasic PrinciplesDesign ExampleState-of-the-ArtSummary

Your questions are welcome any time

Page 33: Superconducting Fault Current Limiters · SuperconductingFault Current Limiters Howto design a resistive fault current limiter? Nominal voltage 24 kV Nominal current 1005 A AC withstand

KIT-Zentrum Energie39 M. Noe, EUCAS Short Course, Power Applications – Fault Current Limiters

Superconducting Fault Current LimitersResearch Directions Develop compact and inexpensive medium voltage SCFCLs Develop high voltage SCFCL prototypes and first field installations Demonstrate and improve reliability with long term tests Develop tests standards

IEEE test guide for FCLs available Show value proposition and „educate costumer“

Some manufacturers offer commercial applications.

Page 34: Superconducting Fault Current Limiters · SuperconductingFault Current Limiters Howto design a resistive fault current limiter? Nominal voltage 24 kV Nominal current 1005 A AC withstand

KIT-Zentrum Energie40 M. Noe, EUCAS Short Course, Power Applications – Fault Current Limiters

o Successful field installations up to 220 kV for different types.

o A few companies started to offer first products.

o An IEEE test guide has been published.

Status of Superconducting Fault Current Limiters