Switch-disconnectors-fuse (SASIL) BS bolted fuse system
Product family
The SASIL systemincludes switch-discon-nector-fuses in accordancewith IEC/EN 60947-3.Here, British Standardfuses are used as fuse-links. Their strip-type,push-in and modulardesign ensures a rapidengineering and easyinstallation in low voltageassemblies (TTA/PTTA).
An operator-independentsnap-action mechanismund double-break feature(upstream and down-stream of the fuse) pro-vide increased personnelprotection during thefunctional switching andexchange of the fuse.
The horizontal mountingmethod of SASIL stripswith outgoing on rightside allows a high packingdensity in switch gearcabinets. Naturally allSASIL strips can also bemounted vertically withcable termination on bot-tom side.
SASIL combines fuseswitch-disconnection andposition indication in onecompact device.
• High personnelprotection
• Modular design• Easy installation• High operational safety• High protection against
contact• High breaking capacity• High short-circuit
strength• Push-in design• Cold-swapping of fuses• Integrated device
accessories• High rated diversity
factor
2-1
Switch-dis-
connector-fuses
(SASIL) LV HRCsystem
Switch-
disconnector
fuses (SASIL)
BS system
Switch-
disconnector(SALIT)
LV
HRC strip-
fuseways
LV HRC
strip-type
fuse switch-
disconnectors
LV HRCfuse-
bases
LV HRC
fuse switch-
disconnectors
C|O|S|M|O®-
60mm Busbar
System
Current
transformers
Consumer
supply technology
Distribution
and instrument
cabinets
Powerlizer
system electronics
Switch-disconnec-
tor-fuses (SASIT)
DIN and BS
systems
Terminals
Appendix
Product group Product type
3-pole, 185 mm Strip, sizes A1-B6, w. manually op. mech., w/o current msrmntbusbar system Strip, sizes A1-B6, w. manually op. mech., w. 1 transformer
Strip, sizes A1-B6, w. manually op. mech., w. 3 transformers
2-pole, 185 mm Strip, sizes A1-B6, w. manually op. mech., w/o current msrmntbusbar system
SASIL accessories SASIL system accessoriesSASIL device mounting system, 185mm
Page02-04
02-06
02-12
02-18
02-20
02-24
Type key 02-28
Wiring diagram 02-30
Drawings 02-31
Technical data 02-44
2-2
Mounting dimensions of field distributor busbar system
225200 25
50
500525
10
90185 2
2
min. 30
344
550 1
23025
Busbar support SST-185/…
Switchingcabinet profilekit SSP
Fixing plate kitBP1/SST
Busbar coverSSA-185
Closing lock-outESS/SASIL…
Bus disconnectingelement kitSTE…/SST
Cable compartmentcoverKA/SSA-185
Cable separatorKSH/SASIL
Socket connector, 16-pole BL/SASIL00-3
Strip guideLF01/SASIL
Drawing toolAW/SASIL00-3
Separator sheet for plugging cable compartment cover(not supplied)
Fuse combination rail (SASIL)
Screw fixing of stripguide possible;Drill hole – Ø 5.3 (for M6)
Fastening railBS1/SST
SASIL mounting system
2-3
Switch-dis-
connector-fuses
(SASIL) LV HRCsystem
Switch-
disconnector
fuses (SASIL)
BS system
Switch-
disconnector(SALIT)
LV
HRC strip-
fuseways
LV HRC
strip-type
fuse switch-
disconnectors
LV HRCfuse-
bases
LV HRC
fuse switch-
disconnectors
C|O|S|M|O®-
60mm Busbar
System
Current
transformers
Consumer
supply technology
Distribution
and instrument
cabinets
Powerlizer
system electronics
Switch-disconnec-
tor-fuses (SASIT)
DIN and BS
systems
Terminals
Appendix
Type SASIL
Plug-incontact
1 or 3 transformers
Fuse monitor/Measuring module EE05
Auxiliary switches: 1 make and 1 break
PlungerClosing lock-out
Double-breakfeature
Manually op. mech., can be lockedwith up to 3 padlocks
Operator-independentsnap-action mechanism
LED, fuse failure
Customerconnection
Measuring deviceMoving iron / bimetallic
Transparent Terminal compartment cover
3mmtwo-way keybit lock
Fuse pick-up contacts
Layout of connector-strips
PIN SASIL without EE-Module 1 CT L1 (S2)2 CT L1 (S1)
3 CT L2 (S2)
4 CT L2 (S1)
5 CT L3 (S2)
6 CT L3 (S1)
7 ESOO-norm. open contact8 ESOO-norm. open contact9 ESOO-norm. closed contact
10 ESOO-norm. closed contact11 Switch position indicator
normally closed contact12 Switch position indicator
normally closed contact13 Switch position indicator
normally open contact14 Switch position indicator
normally open contact15 free16 free
SASIL with EE-Module GND-BUS connectionSwitch position indicator normally open contactBUS-Connection-Data A
BUS-Connection-Data B
BUS-Connection shieding
Switch position indicator normally open contactEE-Module/Relay - norm. closed contactEE-Module/Relay - norm. open contactEE-Module/Relay - common contactPE-arrangementN-arrangement
free
Switch position indicator normally closed contactSwitch position indicator normally closed contactDC 24V (+)DC 24V (-)
SASIL-MOT without EE-Module CT L1 (S2)CT L1 (S1)
Switch position indicator normally closed contactSwitch position indicator normally closed contactSwitch position indicator normally open contactSwitch position indicator normally open contactES05 - normally closed contact ES05 - normally open contactES05 - commonPE-arrangementN-arrangement
Motor drive - ON (DC 24V)
Motor drive - GND
Motor drive - OFF (DC 24V)
DC 24V (+)DC 24V (-)
SASIL-MOT with EE-Module GND-BUS connectionSwitch position indicator normally open contactBUS-Connection-Data A
BUS-Connection-Data B
BUS-Connection shieding
Switch position indicator normally open contactEE-Module/Relay - norm. closed cont.EE-Module/Relay - norm. open cont.EE-Module/Relay - common contactPE-arrangementN-arrangement
Motor drive - ON (DC 24V)
Motor drive - GND
Motor drive - OFF (DC 24V)
DC 24V (+)DC 24V (-)
16-pole push-on terminal strip
Current distributioncomponents
Switch-disconnec-tor-fuses (SASIL),BS system
3-pole, 185mm busbarsystem
Strip, sizes A1 to B6,w. manually-op.mech., w/o currentmsrmnt
2-4
Product definition
SASIL outgoing strips are3-pole pluggable strip-typeswitch-disconnector-fuses.The strips are equippedwith an operator-independ-ent snap-action mechanismand manually-operatedmechanism for clear posi-tion indication andaccomodate 3 BS fuse-linksin accordance with BS88-2,sizes A1/63A to B6/630A.All SASIL strips have plug-incontacts and can be se-curely plugged in an uprightfield distributor busbar sys-tem of 10mm thickness and185mm distance betweenbusbar centres using thecorresponding strip guides.A screw terminal for cablelug connection is availableat the output side.The interlocking mecha-nism in the handle pre-vents the strip cover from
opening in the connectedstate. A double-break fea-ture (upstream and down-stream of the fuse) allows asafe exchange of the fuse.
Applications
SASIL strips are mainlyused for system, cable andmotor protection inthree-phase systems up to690V in main andsubdistribution boards oflow voltage assemblies inaccordance with IEC/EN60439-1 (TTA/PTTA), for in-dustrial, power station andbuilding services applica-tions. Their horizontal fit-ting and compact dimen-sions allow a large numberof cable outlets to be fittedin a limited space.A uniform width, depth andgrid dimension of 25mm ofthe strip height (75mm,150mm) enable a rapid en-
gineering and mounting ofthe strips with differentcomponent sizes used inthe switchgear cabinet.The control line and auxil-iary circuit systems are con-tacted automatically via theterminal strip / socket con-nector system when theSASIL strip is plugged in.
Product construction
The device accessories arefactory-fitted in the SASILstrip.
POSITION INDICATOR1 make contact and 1 breakcontact, wired up on apush-on terminal strip, forexternal indication.
PUSH-ON TERMINAL STRIPfor wiring of the externalauxiliary circuits.
Size Position indicator, 1M+1B Std.P Type Article No.
SASIL...
A1/63A Without 1 A1 A6200026
A1/63A With 1 A1/SKL/SÖ A6204005
BX/125A Without 1 BX A6200027
BX/125A With 1 BX/SKL/SÖ A6204006
B1/100A Without 1 B1 A5200074
B1/100A With 1 B1/SKL/SÖ A5204005
B2/200A Without 1 B2 A1200005
B2/200A With 1 B2/SKL/SÖ A1204002
B4/400A Without 1 B4 A2200008
B4/400A With 1 B4/SKL/SÖ A2204002
B6/630A Without 1 B6 A3200007
B6/630A With 1 B6/SKL/SÖ A3204003
2-5
Switch-dis-
connector-fuses
(SASIL) LV HRCsystem
Switch-
disconnector
fuses (SASIL)
BS system
Switch-
disconnector(SALIT)
LV
HRC strip-
fuseways
LV HRC
strip-type
fuse switch-
disconnectors
LV HRCfuse-
bases
LV HRC
fuse switch-
disconnectors
C|O|S|M|O®-
60mm Busbar
System
Current
transformers
Consumer
supply technology
Distribution
and instrument
cabinets
Powerlizer
system electronics
Switch-disconnec-
tor-fuses (SASIT)
DIN and BS
systems
Terminals
Appendix
Current distributioncomponents
Switch-disconnec-tor-fuses (SASIL),BS system
3-pole, 185mm busbarsystem
Strip, sizes A1 to B6,w. manually-op.mech., w. 1transformer
2-6
Product definition
SASIL strips are 3-polepluggable strip-typeswitch-disconnector-fuses.The strips are equippedwith an operator-independ-ent snap-action mechanismand manually-operatedmechanism for clear posi-tion indication andaccomodate 3 BS fuse-linksin accordance with BS88-2,sizes A1/63A to B6/630A,and 1 current transformer.All SASIL strips have plug-incontacts and can be se-curely plugged in an uprightfield distributor busbar sys-tem of 10mm thickness and185mm distance betweenbusbar centres using thecorresponding strip guides.A screw terminal for cablelug connection is availableat the output side.The interlocking mecha-nism in the handle pre-vents the strip cover fromopening in the connectedstate. A double-break fea-ture (upstream and down-stream of the fuse) allows asafe exchange of the fuse.
Applications
SASIL strips with EE moni-toring module are mainly
used for system, cable andmotor protection inthree-phase systems up to690V in main andsubdistribution boards oflow voltage assemblies inaccordance with IEC/EN60439-1 (TTA/PTTA), for in-dustrial, power station andbuilding services applica-tions. Their horizontal fit-ting compact dimensionsallow a large number of ca-ble outlets to be fitted in alimited space. A uniformwidth, depth and grid di-mension of 25mm of thestrip height (75mm,150mm) enable a rapid en-gineering and mounting ofthe strips with differentcomponent sizes used inthe switchgear cabinet.The control line and auxil-iary circuit systems are con-tacted automatically via theterminal strip / socket con-nector system when theSASIL strip is plugged in.
Product construction
The device accessories arefactory-fitted in the SASILstrip.
CURRENT MEASUREMENT1-phase current measure-ment by N/1A or N/5A
transformers, class 1, in ac-cordance with VDE 0414, fit-ted in phase L1. The follow-ing transformer ratios areavailable:50A/75A/100A/150A/200A/250A/400A. The trans-formers can be wired up ei-ther internally on a measur-ing device or externally on apush-on terminal strip. Alltransformers can be oper-ated open for an unlimitedperiod of time.In the case of a cable infeed(Z version), the transform-ers are installed „back tofront“ (turned through180°).
MEASURING DEVICESIt is possible to use 48mm x48mm measuring devicesas class 1.5 moving iron cur-rent meters. They have adial with 2-fold overloadarea.
POSITION INDICATOR1 make contact and 1 breakcontact, wired up on apush-on terminal strip, forexternal indication.
PUSH-ON TERMINAL STRIPfor wiring of the externalauxiliary circuits.
To order strips with othertransformer ratios or measu-ring devices, use type key onpage 2-28
Size Transformerratio, class 1
Transformerwiring(M: measu-ring deviceS: terminalstrip)
Measuringdevice
Position indi-cator, 1M+1B
Utilizationcategory,AC500V/690V
Std.P Type Article No.
SASIL...
A1/63A 75A-1A M Moving iron Without AC23 1 A1/1W75-1M/MD A6206009
A1/63A 75A-1A M Moving iron With AC23 1 A1/1W75-1M/SKL/MD/SÖ A6221022
A1/63A 75A-1A MS Moving iron Without AC23 1 A1/1W75-1MS/SKL/MD A6212014
A1/63A 75A-1A MS Moving iron With AC23 1 A1/1W75-1MS/SKL/MD/SÖ A6221023
A1/63A 75A-1A S Without Without AC23 1 A1/1W75-1S/SKL A6207015
A1/63A 75A-1A S Without With AC23 1 A1/1W75-1S/SKL/SÖ A6218013
A1/63A 75A-5A M Moving iron Without AC23 1 A1/1W75-5M/MD A6201028
A1/63A 75A-5A M Moving iron With AC23 1 A1/1W75-5M/SKL/MD/SÖ A6209018
A1/63A 75A-5A MS Moving iron Without AC23 1 A1/1W75-5MS/SKL/MD A6203013
A1/63A 75A-5A MS Moving iron With AC23 1 A1/1W75-5MS/SKL/MD/SÖ A6209019
A1/63A 75A-5A S Without Without AC23 1 A1/1W75-5S/SKL A6202016
A1/63A 75A-5A S Without With AC23 1 A1/1W75-5S/SKL/SÖ A6211012
A1/63A 50A-1A M Moving iron Without AC23 1 A1/1W50-1M/MD A6206011
A1/63A 50A-1A M Moving iron With AC23 1 A1/1W50-1M/SKL/MD/SÖ A6221024
A1/63A 50A-1A MS Moving iron Without AC23 1 A1/1W50-1MS/SKL/MD A6212015
A1/63A 50A-1A MS Moving iron With AC23 1 A1/1W50-1MS/SKL/MD/SÖ A6221025
A1/63A 50A-1A S Without Without AC23 1 A1/1W50-1S/SKL A6207016
A1/63A 50A-1A S Without With AC23 1 A1/1W50-1S/SKL/SÖ A6218014
A1/63A 50A-5A M Moving iron Without AC23 1 A1/1W50-5M/MD A6201029
A1/63A 50A-5A M Moving iron With AC23 1 A1/1W50-5M/SKL/MD/SÖ A6209022
A1/63A 50A-5A MS Moving iron Without AC23 1 A1/1W50-5MS/SKL/MD A6203014
A1/63A 50A-5A MS Moving iron With AC23 1 A1/1W50-5MS/SKL/MD/SÖ A6209023
A1/63A 50A-5A S Without Without AC23 1 A1/1W50-5S/SKL A6202017
A1/63A 50A-5A S Without With AC23 1 A1/1W50-5S/SKL/SÖ A6211013
BX/125A 125A-1A M Moving iron Without AC23 1 BX/1W125-1M/MD A6206012
BX/125A 125A-1A M Moving iron With AC23 1 BX/1W125-1M/SKL/MD/SÖ A6221026
BX/125A 125A-1A MS Moving iron Without AC23 1 BX/1W125-1MS/SKL/MD A6212016
BX/125A 125A-1A MS Moving iron With AC23 1 BX/1W125-1MS/SKL/MD/SÖ A6221027
BX/125A 125A-1A S Without Without AC23 1 BX/1W125-1S/SKL A6207017
BX/125A 125A-1A S Without With AC23 1 BX/1W125-1S/SKL/SÖ A6218015
BX/125A 125A-5A M Moving iron Without AC23 1 BX/1W125-5M/MD A6201033
BX/125A 125A-5A M Moving iron With AC23 1 BX/1W125-5M/SKL/MD/SÖ A6209024
BX/125A 125A-5A MS Moving iron Without AC23 1 BX/1W125-5MS/SKL/MD A6203016
BX/125A 125A-5A MS Moving iron With AC23 1 BX/1W125-5MS/SKL/MD/SÖ A6209025
BX/125A 125A-5A S Without Without AC23 1 BX/1W125-5S/SKL A6202018
BX/125A 125A-5A S Without With AC23 1 BX/1W125-5S/SKL/SÖ A6211014
BX/125A 50A-1A M Moving iron Without AC23 1 BX/1W50-1M/MD A6206013
BX/125A 50A-1A M Moving iron With AC23 1 BX/1W50-1M/SKL/MD/SÖ A6221028
BX/125A 50A-1A MS Moving iron Without AC23 1 BX/1W50-1MS/SKL/MD A6212017
BX/125A 50A-1A MS Moving iron With AC23 1 BX/1W50-1MS/SKL/MD/SÖ A6221029
BX/125A 50A-1A S Without Without AC23 1 BX/1W50-1S/SKL A6207018
BX/125A 50A-1A S Without With AC23 1 BX/1W50-1S/SKL/SÖ A6218016
BX/125A 50A-5A M Moving iron Without AC23 1 BX/1W50-5M/MD A6201037
BX/125A 50A-5A M Moving iron With AC23 1 BX/1W50-5M/SKL/MD/SÖ A6209026
BX/125A 50A-5A MS Moving iron Without AC23 1 BX/1W50-5MS/SKL/MD A6203017
BX/125A 50A-5A MS Moving iron With AC23 1 BX/1W50-5MS/SKL/MD/SÖ A6209027
BX/125A 50A-5A S Without Without AC23 1 BX/1W50-5S/SKL A6202015
BX/125A 50A-5A S Without With AC23 1 BX/1W50-5S/SKL/SÖ A6211015
BX/125A 75A-1A M Moving iron Without AC23 1 BX/1W75-1M/MD A6206014
BX/125A 75A-1A M Moving iron With AC23 1 BX/1W75-1M/SKL/MD/SÖ A6221030
2-7
Switch-dis-
connector-fuses
(SASIL) LV HRCsystem
Switch-
disconnector
fuses (SASIL)
BS system
Switch-
disconnector(SALIT)
LV
HRC strip-
fuseways
LV HRC
strip-type
fuse switch-
disconnectors
LV HRCfuse-
bases
LV HRC
fuse switch-
disconnectors
C|O|S|M|O®-
60mm Busbar
System
Current
transformers
Consumer
supply technology
Distribution
and instrument
cabinets
Powerlizer
system electronics
Switch-disconnec-
tor-fuses (SASIT)
DIN and BS
systems
Terminals
Appendix
Size Transformerratio, class 1
Transformerwiring(M: measu-ring deviceS: terminalstrip)
Measuringdevice
Position indi-cator, 1M+1B
Utilizationcategory,AC500V/690V
Std.P Type Article No.
SASIL...
BX/125A 75A-1A MS Moving iron Without AC23 1 BX/1W75-1MS/SKL/MD A6212018
BX/125A 75A-1A MS Moving iron With AC23 1 BX/1W75-1MS/SKL/MD/SÖ A6221031
BX/125A 75A-1A S Without Without AC23 1 BX/1W75-1S/SKL A6207019
BX/125A 75A-1A S Without With AC23 1 BX/1W75-1S/SKL/SÖ A6218017
BX/125A 75A-5A M Moving iron Without AC23 1 BX/1W75-5M/MD A6201044
BX/125A 75A-5A M Moving iron With AC23 1 BX/1W75-5M/SKL/MD/SÖ A6209028
BX/125A 75A-5A MS Moving iron Without AC23 1 BX/1W75-5MS/SKL/MD A6203018
BX/125A 75A-5A MS Moving iron With AC23 1 BX/1W75-5MS/SKL/MD/SÖ A6209029
BX/125A 75A-5A S Without Without AC23 1 BX/1W75-5S/SKL A6202019
BX/125A 75A-5A S Without With AC23 1 BX/1W75-5S/SKL/SÖ A6211016
BX/125A 100A-1A M Moving iron Without AC23 1 BX/1W100-1M/MD A6206015
BX/125A 100A-1A M Moving iron With AC23 1 BX/1W100-1M/SKL/MD/SÖ A6221032
BX/125A 100A-1A MS Moving iron Without AC23 1 BX/1W100-1MS/SKL/MD A6212019
BX/125A 100A-1A MS Moving iron With AC23 1 BX/1W100-1MS/SKL/MD/SÖ A6221033
BX/125A 100A-1A S Without Without AC23 1 BX/1W100-1S/SKL A6207020
BX/125A 100A-1A S Without With AC23 1 BX/1W100-1S/SKL/SÖ A6218018
BX/125A 100A-5A M Moving iron Without AC23 1 BX/1W100-5M/MD A6201047
BX/125A 100A-5A M Moving iron With AC23 1 BX/1W100-5M/SKL/MD/SÖ A6209030
BX/125A 100A-5A MS Moving iron Without AC23 1 BX/1W100-5MS/SKL/MD A6203019
BX/125A 100A-5A MS Moving iron With AC23 1 BX/1W100-5MS/SKL/MD/SÖ A6209031
BX/125A 100A-5A S Without Without AC23 1 BX/1W100-5S/SKL A6202020
BX/125A 100A-5A S Without With AC23 1 BX/1W100-5S/SKL/SÖ A6211017
B1/100A 100A-1A M Moving iron Without AC23 1 B1/1W100-1M/MD A5206007
B1/100A 100A-1A M Moving iron With AC23 1 B1/1W100-1M/SKL/MD/SÖ A5221005
B1/100A 100A-1A MS Moving iron Without AC23 1 B1/1W100-1MS/SKL/MD A5212003
B1/100A 100A-1A MS Moving iron With AC23 1 B1/1W100-1MS/SKL/MD/SÖ A5221008
B1/100A 100A-1A S Without Without AC23 1 B1/1W100-1S/SKL A5207004
B1/100A 100A-1A S Without With AC23 1 B1/1W100-1S/SKL/SÖ A5218003
B1/100A 100A-5A M Moving iron Without AC23 1 B1/1W100-5M/MD A5201004
B1/100A 100A-5A M Moving iron With AC23 1 B1/1W100-5M/SKL/MD/SÖ A5209005
B1/100A 100A-5A MS Moving iron Without AC23 1 B1/1W100-5MS/SKL/MD A5203005
B1/100A 100A-5A MS Moving iron With AC23 1 B1/1W100-5MS/SKL/MD/SÖ A5209008
B1/100A 100A-5A S Without Without AC23 1 B1/1W100-5S/SKL A5202003
B1/100A 100A-5A S Without With AC23 1 B1/1W100-5S/SKL/SÖ A5211004
B1/100A 50A-1A M Moving iron Without AC23 1 B1/1W50-1M/MD A5206005
B1/100A 50A-1A M Moving iron With AC23 1 B1/1W50-1M/SKL/MD/SÖ A5221003
B1/100A 50A-1A MS Moving iron Without AC23 1 B1/1W50-1MS/SKL/MD A5212001
B1/100A 50A-1A MS Moving iron With AC23 1 B1/1W50-1MS/SKL/MD/SÖ A5221006
B1/100A 50A-1A S Without Without AC23 1 B1/1W50-1S/SKL A5207002
B1/100A 50A-1A S Without With AC23 1 B1/1W50-1S/SKL/SÖ A5218001
B1/100A 50A-5A M Moving iron Without AC23 1 B1/1W50-5M/MD A5201002
B1/100A 50A-5A M Moving iron With AC23 1 B1/1W50-5M/SKL/MD/SÖ A5209003
B1/100A 50A-5A MS Moving iron Without AC23 1 B1/1W50-5MS/SKL/MD A5203003
B1/100A 50A-5A MS Moving iron With AC23 1 B1/1W50-5MS/SKL/MD/SÖ A5209006
B1/100A 50A-5A S Without Without AC23 1 B1/1W50-5S/SKL A5202001
B1/100A 50A-5A S Without With AC23 1 B1/1W50-5S/SKL/SÖ A5211002
B1/100A 75A-1A M Moving iron Without AC23 1 B1/1W75-1M/MD A5206006
B1/100A 75A-1A M Moving iron With AC23 1 B1/1W75-1M/SKL/MD/SÖ A5221004
B1/100A 75A-1A MS Moving iron Without AC23 1 B1/1W75-1MS/SKL/MD A5212002
B1/100A 75A-1A MS Moving iron With AC23 1 B1/1W75-1MS/SKL/MD/SÖ A5221007
2-8
Size Transformerratio, class 1
Transformerwiring(M: measu-ring deviceS: terminalstrip)
Measuringdevice
Position indi-cator, 1M+1B
Utilizationcategory,AC500V/690V
Std.P Type Article No.
SASIL...
B1/100A 75A-1A S Without Without AC23 1 B1/1W75-1S/SKL A5207003
B1/100A 75A-1A S Without With AC23 1 B1/1W75-1S/SKL/SÖ A5218002
B1/100A 75A-5A M Moving iron Without AC23 1 B1/1W75-5M/MD A5201003
B1/100A 75A-5A M Moving iron With AC23 1 B1/1W75-5M/SKL/MD/SÖ A5209004
B1/100A 75A-5A MS Moving iron Without AC23 1 B1/1W75-5MS/SKL/MD A5203004
B1/100A 75A-5A MS Moving iron With AC23 1 B1/1W75-5MS/SKL/MD/SÖ A5209007
B1/100A 75A-5A S Without Without AC23 1 B1/1W75-5S/SKL A5202002
B1/100A 75A-5A S Without With AC23 1 B1/1W75-5S/SKL/SÖ A5211003
B2/200A 100A-1A M Moving iron Without AC23 1 B2/1W100-1M/MD A1206007
B2/200A 100A-1A M Moving iron With AC23 1 B2/1W100-1M/SKL/MD/SÖ A1221011
B2/200A 100A-1A MS Moving iron Without AC23 1 B2/1W100-1MS/SKL/MD A1212003
B2/200A 100A-1A MS Moving iron With AC23 1 B2/1W100-1MS/SKL/MD/SÖ A1221014
B2/200A 100A-1A S Without Without AC23 1 B2/1W100-1S/SKL A1207012
B2/200A 100A-1A S Without With AC23 1 B2/1W100-1S/SKL/SÖ A1218010
B2/200A 100A-5A M Moving iron Without AC23 1 B2/1W100-5M/MD A1201008
B2/200A 100A-5A M Moving iron With AC23 1 B2/1W100-5M/SKL/MD/SÖ A1209011
B2/200A 100A-5A MS Moving iron Without AC23 1 B2/1W100-5MS/SKL/MD A1203006
B2/200A 100A-5A MS Moving iron With AC23 1 B2/1W100-5MS/SKL/MD/SÖ A1209014
B2/200A 100A-5A S Without Without AC23 1 B2/1W100-5S/SKL A1202011
B2/200A 100A-5A S Without With AC23 1 B2/1W100-5S/SKL/SÖ A1211006
B2/200A 150A-1A M Moving iron Without AC23 1 B2/1W150-1M/MD A1206008
B2/200A 150A-1A M Moving iron With AC23 1 B2/1W150-1M/SKL/MD/SÖ A1221012
B2/200A 150A-1A MS Moving iron Without AC23 1 B2/1W150-1MS/SKL/MD A1212004
B2/200A 150A-1A MS Moving iron With AC23 1 B2/1W150-1MS/SKL/MD/SÖ A1221015
B2/200A 150A-1A S Without Without AC23 1 B2/1W150-1S/SKL A1207013
B2/200A 150A-1A S Without With AC23 1 B2/1W150-1S/SKL/SÖ A1218011
B2/200A 150A-5A M Moving iron Without AC23 1 B2/1W150-5M/MD A1201009
B2/200A 150A-5A M Moving iron With AC23 1 B2/1W150-5M/SKL/MD/SÖ A1209012
B2/200A 150A-5A MS Moving iron Without AC23 1 B2/1W150-5MS/SKL/MD A1203007
B2/200A 150A-5A MS Moving iron With AC23 1 B2/1W150-5MS/SKL/MD/SÖ A1209015
B2/200A 150A-5A S Without Without AC23 1 B2/1W150-5S/SKL A1202012
B2/200A 150A-5A S Without With AC23 1 B2/1W150-5S/SKL/SÖ A1211007
B2/200A 200A-1A M Moving iron Without AC23 1 B2/1W200-1M/MD A1206009
B2/200A 200A-1A M Moving iron With AC23 1 B2/1W200-1M/SKL/MD/SÖ A1221013
B2/200A 200A-1A MS Moving iron Without AC23 1 B2/1W200-1MS/SKL/MD A1212005
B2/200A 200A-1A MS Moving iron With AC23 1 B2/1W200-1MS/SKL/MD/SÖ A1221016
B2/200A 200A-1A S Without Without AC23 1 B2/1W200-1S/SKL A1207014
B2/200A 200A-1A S Without With AC23 1 B2/1W200-1S/SKL/SÖ A1218012
B2/200A 200A-5A M Moving iron Without AC23 1 B2/1W200-5M/MD A1201010
B2/200A 200A-5A M Moving iron With AC23 1 B2/1W200-5M/SKL/MD/SÖ A1209013
B2/200A 200A-5A MS Moving iron Without AC23 1 B2/1W200-5MS/SKL/MD A1203008
B2/200A 200A-5A MS Moving iron With AC23 1 B2/1W200-5MS/SKL/MD/SÖ A1209016
B2/200A 200A-5A S Without Without AC23 1 B2/1W200-5S/SKL A1202013
B2/200A 200A-5A S Without With AC23 1 B2/1W200-5S/SKL/SÖ A1211008
B4/400A 150A-1A M Moving iron Without AC23 1 B4/1W150-1M/MD A2206009
B4/400A 150A-1A M Moving iron With AC23 1 B4/1W150-1M/SKL/MD/SÖ A2221015
B4/400A 150A-1A MS Moving iron Without AC23 1 B4/1W150-1MS/SKL/MD A2212007
B4/400A 150A-1A MS Moving iron With AC23 1 B4/1W150-1MS/SKL/MD/SÖ A2221016
B4/400A 150A-1A S Without Without AC23 1 B4/1W150-1S/SKL A2207010
B4/400A 150A-1A S Without With AC23 1 B4/1W150-1S/SKL/SÖ A2218010
2-9
Switch-dis-
connector-fuses
(SASIL) LV HRCsystem
Switch-
disconnector
fuses (SASIL)
BS system
Switch-
disconnector(SALIT)
LV
HRC strip-
fuseways
LV HRC
strip-type
fuse switch-
disconnectors
LV HRCfuse-
bases
LV HRC
fuse switch-
disconnectors
C|O|S|M|O®-
60mm Busbar
System
Current
transformers
Consumer
supply technology
Distribution
and instrument
cabinets
Powerlizer
system electronics
Switch-disconnec-
tor-fuses (SASIT)
DIN and BS
systems
Terminals
Appendix
Size Transformerratio, class 1
Transformerwiring(M: measu-ring deviceS: terminalstrip)
Measuringdevice
Position indi-cator, 1M+1B
Utilizationcategory,AC500V/690V
Std.P Type Article No.
SASIL...
B4/400A 150A-5A M Moving iron Without AC23 1 B4/1W150-5M/MD A2201011
B4/400A 150A-5A M Moving iron With AC23 1 B4/1W150-5M/SKL/MD/SÖ A2209011
B4/400A 150A-5A MS Moving iron Without AC23 1 B4/1W150-5MS/SKL/MD A2203009
B4/400A 150A-5A MS Moving iron With AC23 1 B4/1W150-5MS/SKL/MD/SÖ A2209010
B4/400A 150A-5A S Without Without AC23 1 B4/1W150-5S/SKL A2202020
B4/400A 150A-5A S Without With AC23 1 B4/1W150-5S/SKL/SÖ A2211008
B4/400A 200A-1A M Moving iron Without AC23 1 B4/1W200-1M/MD A2206006
B4/400A 200A-1A M Moving iron With AC23 1 B4/1W200-1M/SKL/MD/SÖ A2221007
B4/400A 200A-1A MS Moving iron Without AC23 1 B4/1W200-1MS/SKL/MD A2212004
B4/400A 200A-1A MS Moving iron With AC23 1 B4/1W200-1MS/SKL/MD/SÖ A2221008
B4/400A 200A-1A S Without Without AC23 1 B4/1W200-1S/SKL A2207007
B4/400A 200A-1A S Without With AC23 1 B4/1W200-1S/SKL/SÖ A2218007
B4/400A 200A-5A M Moving iron Without AC23 1 B4/1W200-5M/MD A2201008
B4/400A 200A-5A M Moving iron With AC23 1 B4/1W200-5M/SKL/MD/SÖ A2209013
B4/400A 200A-5A MS Moving iron Without AC23 1 B4/1W200-5MS/SKL/MD A2203006
B4/400A 200A-5A MS Moving iron With AC23 1 B4/1W200-5MS/SKL/MD/SÖ A2209012
B4/400A 200A-5A S Without Without AC23 1 B4/1W200-5S/SKL A2202016
B4/400A 200A-5A S Without With AC23 1 B4/1W200-5S/SKL/SÖ A2211005
B4/400A 250A-1A M Moving iron Without AC23 1 B4/1W250-1M/MD A2206007
B4/400A 250A-1A M Moving iron With AC23 1 B4/1W250-1M/SKL/MD/SÖ A2221009
B4/400A 250A-1A MS Moving iron Without AC23 1 B4/1W250-1MS/SKL/MD A2212005
B4/400A 250A-1A MS Moving iron With AC23 1 B4/1W250-1MS/SKL/MD/SÖ A2221010
B4/400A 250A-1A S Without Without AC23 1 B4/1W250-1S/SKL A2207008
B4/400A 250A-1A S Without With AC23 1 B4/1W250-1S/SKL/SÖ A2218008
B4/400A 250A-5A M Moving iron Without AC23 1 B4/1W250-5M/MD A2201009
B4/400A 250A-5A M Moving iron With AC23 1 B4/1W250-5M/SKL/MD/SÖ A2209019
B4/400A 250A-5A MS Moving iron Without AC23 1 B4/1W250-5MS/SKL/MD A2203007
B4/400A 250A-5A MS Moving iron With AC23 1 B4/1W250-5MS/SKL/MD/SÖ A2209020
B4/400A 250A-5A S Without Without AC23 1 B4/1W250-5S/SKL A2202017
B4/400A 250A-5A S Without With AC23 1 B4/1W250-5S/SKL/SÖ A2211006
B4/400A 400A-1A M Moving iron Without AC23 1 B4/1W400-1M/MD A2206008
B4/400A 400A-1A M Moving iron With AC23 1 B4/1W400-1M/SKL/MD/SÖ A2221011
B4/400A 400A-1A MS Moving iron Without AC23 1 B4/1W400-1MS/SKL/MD A2212006
B4/400A 400A-1A MS Moving iron With AC23 1 B4/1W400-1MS/SKL/MD/SÖ A2221012
B4/400A 400A-1A S Without Without AC23 1 B4/1W400-1S/SKL A2207009
B4/400A 400A-1A S Without With AC23 1 B4/1W400-1S/SKL/SÖ A2218009
B4/400A 400A-5A M Moving iron Without AC23 1 B4/1W400-5M/MD A2201010
B4/400A 400A-5A M Moving iron With AC23 1 B4/1W400-5M/SKL/MD/SÖ A2209021
B4/400A 400A-5A MS Moving iron Without AC23 1 B4/1W400-5MS/SKL/MD A2203008
B4/400A 400A-5A MS Moving iron With AC23 1 B4/1W400-5MS/SKL/MD/SÖ A2209022
B4/400A 400A-5A S Without Without AC23 1 B4/1W400-5S/SKL A2202018
B4/400A 400A-5A S Without With AC23 1 B4/1W400-5S/SKL/SÖ A2211007
B6/630A 250A-1A M Moving iron Without AC23 1 B6/1W250-1M/MD A3206007
B6/630A 250A-1A M Moving iron With AC23 1 B6/1W250-1M/SKL/MD/SÖ A3221009
B6/630A 250A-1A MS Moving iron Without AC23 1 B6/1W250-1MS/SKL/MD A3212004
B6/630A 250A-1A MS Moving iron With AC23 1 B6/1W250-1MS/SKL/MD/SÖ A3221012
B6/630A 250A-1A S Without Without AC23 1 B6/1W250-1S/SKL A3207011
B6/630A 250A-1A S Without With AC23 1 B6/1W250-1S/SKL/SÖ A3218005
B6/630A 250A-5A M Moving iron Without AC23 1 B6/1W250-5M/MD A3201010
B6/630A 250A-5A M Moving iron With AC23 1 B6/1W250-5M/SKL/MD/SÖ A3209007
2-10
Size Transformerratio, class 1
Transformerwiring(M: measu-ring deviceS: terminalstrip)
Measuringdevice
Position indi-cator, 1M+1B
Utilizationcategory,AC500V/690V
Std.P Type Article No.
SASIL...
B6/630A 250A-5A MS Moving iron Without AC23 1 B6/1W250-5MS/SKL/MD A3203006
B6/630A 250A-5A MS Moving iron With AC23 1 B6/1W250-5MS/SKL/MD/SÖ A3209010
B6/630A 250A-5A S Without Without AC23 1 B6/1W250-5S/SKL A3202007
B6/630A 250A-5A S Without With AC23 1 B6/1W250-5S/SKL/SÖ A3211005
B6/630A 400A-1A M Moving iron Without AC23 1 B6/1W400-1M/MD A3206008
B6/630A 400A-1A M Moving iron With AC23 1 B6/1W400-1M/SKL/MD/SÖ A3221010
B6/630A 400A-1A MS Moving iron Without AC23 1 B6/1W400-1MS/SKL/MD A3212005
B6/630A 400A-1A MS Moving iron With AC23 1 B6/1W400-1MS/SKL/MD/SÖ A3221013
B6/630A 400A-1A S Without Without AC23 1 B6/1W400-1S/SKL A3207009
B6/630A 400A-1A S Without With AC23 1 B6/1W400-1S/SKL/SÖ A3218006
B6/630A 400A-5A M Moving iron Without AC23 1 B6/1W400-5M/MD A3201011
B6/630A 400A-5A M Moving iron With AC23 1 B6/1W400-5M/SKL/MD/SÖ A3209008
B6/630A 400A-5A MS Moving iron Without AC23 1 B6/1W400-5MS/SKL/MD A3203007
B6/630A 400A-5A MS Moving iron With AC23 1 B6/1W400-5MS/SKL/MD/SÖ A3209011
B6/630A 400A-5A S Without Without AC23 1 B6/1W400-5S/SKL A3202008
B6/630A 400A-5A S Without With AC23 1 B6/1W400-5S/SKL/SÖ A3211006
B6/630A 600A-1A M Moving iron Without AC23 1 B6/1W600-1M/MD A3206009
B6/630A 600A-1A M Moving iron With AC23 1 B6/1W600-1M/SKL/MD/SÖ A3221011
B6/630A 600A-1A MS Moving iron Without AC23 1 B6/1W600-1MS/SKL/MD A3212006
B6/630A 600A-1A MS Moving iron With AC23 1 B6/1W600-1MS/SKL/MD/SÖ A3221014
B6/630A 600A-1A S Without Without AC23 1 B6/1W600-1S/SKL A3207010
B6/630A 600A-1A S Without With AC23 1 B6/1W600-1S/SKL/SÖ A3218007
B6/630A 600A-5A M Moving iron Without AC23 1 B6/1W600-5M/MD A3201012
B6/630A 600A-5A M Moving iron With AC23 1 B6/1W600-5M/SKL/MD/SÖ A3209009
B6/630A 600A-5A MS Moving iron Without AC23 1 B6/1W600-5MS/SKL/MD A3203008
B6/630A 600A-5A MS Moving iron With AC23 1 B6/1W600-5MS/SKL/MD/SÖ A3209012
B6/630A 600A-5A S Without Without AC23 1 B6/1W600-5S/SKL A3202009
B6/630A 600A-5A S Without With AC23 1 B6/1W600-5S/SKL/SÖ A3211007
2-11
Switch-dis-
connector-fuses
(SASIL) LV HRCsystem
Switch-
disconnector
fuses (SASIL)
BS system
Switch-
disconnector(SALIT)
LV
HRC strip-
fuseways
LV HRC
strip-type
fuse switch-
disconnectors
LV HRCfuse-
bases
LV HRC
fuse switch-
disconnectors
C|O|S|M|O®-
60mm Busbar
System
Current
transformers
Consumer
supply technology
Distribution
and instrument
cabinets
Powerlizer
system electronics
Switch-disconnec-
tor-fuses (SASIT)
DIN and BS
systems
Terminals
Appendix
Current distributioncomponents
Switch-disconnec-tor-fuses (SASIL),BS system
3-pole, 185mm busbarsystem
Strip, sizes A1 to B6,w. manually-op.mech., w. 3transformers
2-12
Product definition
SASIL strips are 3-polepluggable strip-typeswitch-disconnector-fuses.The strips are equippedwith an operator-independ-ent snap-action mechanismand manually-operatedmechanism for clear posi-tion indication andaccomodate 3 BS fuse-linksin accordance with BS88-2,sizes A1/63A to B6/630A,and 3 current transformers.All SASIL strips have plug-incontacts and can be se-curely plugged in an uprightfield distributor busbar sys-tem of 10mm thickness and185mm distance betweenbusbar centres using thecorresponding strip guides.A screw terminal for cablelug connection is availableat the output side.The interlocking mecha-nism in the handle pre-vents the strip cover fromopening in the connectedstate. A double-break fea-ture (upstream and down-stream of the fuse) allows asafe exchange of the fuse.
Applications
SASIL strips are mainlyused for system, cable and
motor protection inthree-phase systems up to690V in main andsubdistribution boards oflow voltage assemblies inaccordance with IEC/EN60439-1 (TTA/PTTA), for in-dustrial, power station andbuilding services applica-tions. Their horizontal fit-ting and compact dimen-sions allow a large numberof cable outlets to be fittedin a limited space.A uniform width, depth andgrid dimension of 25mm ofthe strip height (75mm,150mm) enable a rapid en-gineering and mounting ofthe strips with differentcomponent sizes used inthe switchgear cabinet.The control line and auxil-iary circuit systems are con-tacted automatically via theterminal strip / socket con-nector system when theSASIL strip is plugged in.
Product construction
The device accessories arefactory-fitted in the SASILstrip.
CURRENT MEASUREMENT3-phase current measure-ment by N/1A or N/5Atransformers, class 1, in ac-
cordance with VDE 0414.The following transformerratios are available:50A/75A/100A/150A/200A/250A/400A. The trans-formers can be wired up ei-ther internally on a measur-ing device or externally on apush-on terminal strip. Alltransformers can be oper-ated open for an unlimitedperiod of time.In the case of a cable infeed(Z version), the transform-ers are installed „back tofront“ (turned through180°).
MEASURING DEVICESIt is possible to use 48mm x48mm measuring devicesas class 1.5 moving iron cur-rent meters. They have adial with 2-fold overloadarea.
POSITION INDICATOR1 make contact and 1 breakcontact, wired up on apush-on terminal strip, forexternal indication.
PUSH-ON TERMINAL STRIPfor wiring of the externalauxiliary circuits.
To order strips with othertransformer ratios or measu-ring devices, use type key onpage 2-28
Size Transformerratio
Transformerwiring(M: measu-ring deviceS: terminalstrip)
Measuringdevice
Position indi-cator, 1M+1B
Utilizationcategory,AC500V/690V
Std.P Type Article No.
SASIL...
A1/63A 75A-1A MS Moving iron Without AC23 1 A1/3W75-1MS/SKL/MD A6215023
A1/63A 75A-1A MS Moving iron With AC23 1 A1/3W75-1MS/SKL/MD/SÖ A6223016
A1/63A 75A-1A S Without Without AC23 1 A1/3W75-1S/SKL A6214021
A1/63A 75A-1A S Without With AC23 1 A1/3W75-1S/SKL/SÖ A6220015
A1/63A 75A-5A MS Moving iron Without AC23 1 A1/3W75-5MS/SKL/MD A6213022
A1/63A 75A-5A MS Moving iron With AC23 1 A1/3W75-5MS/SKL/MD/SÖ A6222014
A1/63A 75A-5A S Without Without AC23 1 A1/3W75-5S/SKL A6208029
A1/63A 75A-5A S Without With AC23 1 A1/3W75-5S/SKL/SÖ A6219012
A1/63A 50A-1A MS Moving iron Without AC23 1 A1/3W50-1MS/SKL/MD A6215024
A1/63A 50A-1A MS Moving iron With AC23 1 A1/3W50-1MS/SKL/MD/SÖ A6223017
A1/63A 50A-1A S Without Without AC23 1 A1/3W50-1S/SKL A6214022
A1/63A 50A-1A S Without With AC23 1 A1/3W50-1S/SKL/SÖ A6220016
A1/63A 50A-5A MS Moving iron Without AC23 1 A1/3W50-5MS/SKL/MD A6213023
A1/63A 50A-5A MS Moving iron With AC23 1 A1/3W50-5MS/SKL/MD/SÖ A6222015
A1/63A 50A-5A S Without Without AC23 1 A1/3W50-5S/SKL A6208030
A1/63A 50A-5A S Without With AC23 1 A1/3W50-5S/SKL/SÖ A6219013
BX/125A 125A-1A MS Moving iron Without AC23 1 BX/3W125-1MS/SKL/MD A6215025
BX/125A 125A-1A MS Moving iron With AC23 1 BX/3W125-1MS/SKL/MD/SÖ A6223018
BX/125A 125A-1A S Without Without AC23 1 BX/3W125-1S/SKL A6214023
BX/125A 125A-1A S Without With AC23 1 BX/3W125-1S/SKL/SÖ A6220017
BX/125A 125A-5A MS Moving iron Without AC23 1 BX/3W125-5MS/SKL/MD A6213024
BX/125A 125A-5A MS Moving iron With AC23 1 BX/3W125-5MS/SKL/MD/SÖ A6222016
BX/125A 125A-5A S Without Without AC23 1 BX/3W125-5S/SKL A6208031
BX/125A 125A-5A S Without With AC23 1 BX/3W125-5S/SKL/SÖ A6219014
BX/125A 50A-1A MS Moving iron Without AC23 1 BX/3W50-1MS/SKL/MD A6215026
BX/125A 50A-1A MS Moving iron With AC23 1 BX/3W50-1MS/SKL/MD/SÖ A6223019
BX/125A 50A-1A S Without Without AC23 1 BX/3W50-1S/SKL A6214024
BX/125A 50A-1A S Without With AC23 1 BX/3W50-1S/SKL/SÖ A6220018
BX/125A 50A-5A MS Moving iron Without AC23 1 BX/3W50-5MS/SKL/MD A6213025
BX/125A 50A-5A MS Moving iron With AC23 1 BX/3W50-5MS/SKL/MD/SÖ A6222017
BX/125A 50A-5A S Without Without AC23 1 BX/3W50-5S/SKL A6208032
BX/125A 50A-5A S Without With AC23 1 BX/3W50-5S/SKL/SÖ A6219015
BX/125A 75A-1A MS Moving iron Without AC23 1 BX/3W75-1MS/SKL/MD A6215027
BX/125A 75A-1A MS Moving iron With AC23 1 BX/3W75-1MS/SKL/MD/SÖ A6223020
BX/125A 75A-1A S Without Without AC23 1 BX/3W75-1S/SKL A6214025
BX/125A 75A-1A S Without With AC23 1 BX/3W75-1S/SKL/SÖ A6220019
BX/125A 75A-5A MS Moving iron Without AC23 1 BX/3W75-5MS/SKL/MD A6213026
BX/125A 75A-5A MS Moving iron With AC23 1 BX/3W75-5MS/SKL/MD/SÖ A6222018
BX/125A 75A-5A S Without Without AC23 1 BX/3W75-5S/SKL A6208033
BX/125A 75A-5A S Without With AC23 1 BX/3W75-5S/SKL/SÖ A6219016
BX/125A 100A-1A MS Moving iron Without AC23 1 BX/3W100-1MS/SKL/MD A6215028
BX/125A 100A-1A MS Moving iron With AC23 1 BX/3W100-1MS/SKL/MD/SÖ A6223021
BX/125A 100A-1A S Without Without AC23 1 BX/3W100-1S/SKL A6214026
BX/125A 100A-1A S Without With AC23 1 BX/3W100-1S/SKL/SÖ A6220020
BX/125A 100A-5A MS Moving iron Without AC23 1 BX/3W100-5MS/SKL/MD A6213027
BX/125A 100A-5A MS Moving iron With AC23 1 BX/3W100-5MS/SKL/MD/SÖ A6222019
BX/125A 100A-5A S Without Without AC23 1 BX/3W100-5S/SKL A6208035
BX/125A 100A-5A S Without With AC23 1 BX/3W100-5S/SKL/SÖ A6219017
B1/100A 100A-1A MS Moving iron Without AC23 1 B1/3W100-1MS/SKL/MD A5215005
B1/100A 100A-1A MS Moving iron With AC23 1 B1/3W100-1MS/SKL/MD/SÖ A5223003
2-13
Switch-dis-
connector-fuses
(SASIL) LV HRCsystem
Switch-
disconnector
fuses (SASIL)
BS system
Switch-
disconnector(SALIT)
LV
HRC strip-
fuseways
LV HRC
strip-type
fuse switch-
disconnectors
LV HRCfuse-
bases
LV HRC
fuse switch-
disconnectors
C|O|S|M|O®-
60mm Busbar
System
Current
transformers
Consumer
supply technology
Distribution
and instrument
cabinets
Powerlizer
system electronics
Switch-disconnec-
tor-fuses (SASIT)
DIN and BS
systems
Terminals
Appendix
Size Transformerratio
Transformerwiring(M: measu-ring deviceS: terminalstrip)
Measuringdevice
Position indi-cator, 1M+1B
Utilizationcategory,AC500V/690V
Std.P Type Article No.
SASIL...
B1/100A 100A-1A S Without Without AC23 1 B1/3W100-1S/SKL A5214003
B1/100A 100A-1A S Without With AC23 1 B1/3W100-1S/SKL/SÖ A5220003
B1/100A 100A-5A MS Moving iron Without AC23 1 B1/3W100-5MS/SKL/MD A5213005
B1/100A 100A-5A MS Moving iron With AC23 1 B1/3W100-5MS/SKL/MD/SÖ A5222003
B1/100A 100A-5A S Without Without AC23 1 B1/3W100-5S/SKL A5208004
B1/100A 100A-5A S Without With AC23 1 B1/3W100-5S/SKL/SÖ A5219004
B1/100A 50A-1A MS Moving iron Without AC23 1 B1/3W50-1MS/SKL/MD A5215003
B1/100A 50A-1A MS Moving iron With AC23 1 B1/3W50-1MS/SKL/MD/SÖ A5223001
B1/100A 50A-1A S Without Without AC23 1 B1/3W50-1S/SKL A5214001
B1/100A 50A-1A S Without With AC23 1 B1/3W50-1S/SKL/SÖ A5220001
B1/100A 50A-5A MS Moving iron Without AC23 1 B1/3W50-5MS/SKL/MD A5213003
B1/100A 50A-5A MS Moving iron With AC23 1 B1/3W50-5MS/SKL/MD/SÖ A5222001
B1/100A 50A-5A S Without Without AC23 1 B1/3W50-5S/SKL A5208002
B1/100A 50A-5A S Without With AC23 1 B1/3W50-5S/SKL/SÖ A5219002
B1/100A 75A-1A MS Moving iron Without AC23 1 B1/3W75-1MS/SKL/MD A5215004
B1/100A 75A-1A MS Moving iron With AC23 1 B1/3W75-1MS/SKL/MD/SÖ A5223002
B1/100A 75A-1A S Without Without AC23 1 B1/3W75-1S/SKL A5214002
B1/100A 75A-1A S Without With AC23 1 B1/3W75-1S/SKL/SÖ A5220002
B1/100A 75A-5A MS Moving iron Without AC23 1 B1/3W75-5MS/SKL/MD A5213004
B1/100A 75A-5A MS Moving iron With AC23 1 B1/3W75-5MS/SKL/MD/SÖ A5222002
B1/100A 75A-5A S Without Without AC23 1 B1/3W75-5S/SKL A5208003
B1/100A 75A-5A S Without With AC23 1 B1/3W75-5S/SKL/SÖ A5219003
B2/200A 100A-5A S Without Without AC23 1 B2/3W100-5S/SKL A1208018
B2/200A 150A-5A S Without Without AC23 1 B2/3W150-5S/SKL A1208019
B2/200A 200A-5A S Without Without AC23 1 B2/3W200-5S/SKL A1208020
B2/200A 100A-5A MS Moving iron Without AC23 1 B2/3W100-5MS/SKL/MD A1213017
B2/200A 150A-5A MS Moving iron Without AC23 1 B2/3W150-5MS/SKL/MD A1213018
B2/200A 200A-5A MS Moving iron Without AC23 1 B2/3W200-5MS/SKL/MD A1213019
B2/200A 150A-1A S Without Without AC23 1 B2/3W150-1S/SKL A1214013
B2/200A 200A-1A S Without Without AC23 1 B2/3W200-1S/SKL A1214014
B2/200A 100A-1A S Without Without AC23 1 B2/3W100-1S/SKL A1214015
B2/200A 100A-1A MS Moving iron Without AC23 1 B2/3W100-1MS/SKL/MD A1215019
B2/200A 150A-1A MS Moving iron Without AC23 1 B2/3W150-1MS/SKL/MD A1215020
B2/200A 200A-1A MS Moving iron Without AC23 1 B2/3W200-1MS/SKL/MD A1215021
B2/200A 100A-5A S Without With AC23 1 B2/3W100-5S/SKL/SÖ A1219012
B2/200A 150A-5A S Without With AC23 1 B2/3W150-5S/SKL/SÖ A1219013
B2/200A 200A-5A S Without With AC23 1 B2/3W200-5S/SKL/SÖ A1219014
B2/200A 100A-1A S Without With AC23 1 B2/3W100-1S/SKL/SÖ A1220012
B2/200A 150A-1A S Without With AC23 1 B2/3W150-1S/SKL/SÖ A1220013
B2/200A 200A-1A S Without With AC23 1 B2/3W200-1S/SKL/SÖ A1220014
B2/200A 100A-5A MS Moving iron With AC23 1 B2/3W100-5MS/SKL/MD/SÖ A1222011
B2/200A 150A-5A MS Moving iron With AC23 1 B2/3W150-5MS/SKL/MD/SÖ A1222012
B2/200A 200A-5A MS Moving iron With AC23 1 B2/3W200-5MS/SKL/MD/SÖ A1222013
B2/200A 100A-1A MS Moving iron With AC23 1 B2/3W100-1MS/SKL/MD/SÖ A1223012
B2/200A 150A-1A MS Moving iron With AC23 1 B2/3W150-1MS/SKL/MD/SÖ A1223013
B2/200A 200A-1A MS Moving iron With AC23 1 B2/3W200-1MS/SKL/MD/SÖ A1223014
B4/400A 200A-5A S Without Without AC23 1 B4/3W200-5S/SKL A2208019
B4/400A 250A-5A S Without Without AC23 1 B4/3W250-5S/SKL A2208020
B4/400A 400A-5A S Without Without AC23 1 B4/3W400-5S/SKL A2208021
B4/400A 150A-5A S Without Without AC23 1 B4/3W150-5S/SKL A2208022
2-14
Size Transformerratio
Transformerwiring(M: measu-ring deviceS: terminalstrip)
Measuringdevice
Position indi-cator, 1M+1B
Utilizationcategory,AC500V/690V
Std.P Type Article No.
SASIL...
B4/400A 200A-5A MS Moving iron Without AC23 1 B4/3W200-5MS/SKL/MD A2213020
B4/400A 250A-5A MS Moving iron Without AC23 1 B4/3W250-5MS/SKL/MD A2213021
B4/400A 400A-5A MS Moving iron Without AC23 1 B4/3W400-5MS/SKL/MD A2213022
B4/400A 150A-5A MS Moving iron Without AC23 1 B4/3W150-5MS/SKL/MD A2213023
B4/400A 200A-1A S Without Without AC23 1 B4/3W200-1S/SKL A2214016
B4/400A 250A-1A S Without Without AC23 1 B4/3W250-1S/SKL A2214017
B4/400A 400A-1A S Without Without AC23 1 B4/3W400-1S/SKL A2214018
B4/400A 150A-1A S Without Without AC23 1 B4/3W150-1S/SKL A2214019
B4/400A 200A-1A MS Moving iron Without AC23 1 B4/3W200-1MS/SKL/MD A2215021
B4/400A 250A-1A MS Moving iron Without AC23 1 B4/3W250-1MS/SKL/MD A2215022
B4/400A 400A-1A MS Moving iron Without AC23 1 B4/3W400-1MS/SKL/MD A2215023
B4/400A 150A-1A MS Moving iron Without AC23 1 B4/3W150-1MS/SKL/MD A2215024
B4/400A 200A-5A S Without With AC23 1 B4/3W200-5S/SKL/SÖ A2219014
B4/400A 250A-5A S Without With AC23 1 B4/3W250-5S/SKL/SÖ A2219015
B4/400A 400A-5A S Without With AC23 1 B4/3W400-5S/SKL/SÖ A2219016
B4/400A 150A-5A S Without With AC23 1 B4/3W150-5S/SKL/SÖ A2219017
B4/400A 200A-1A S Without With AC23 1 B4/3W200-1S/SKL/SÖ A2220014
B4/400A 250A-1A S Without With AC23 1 B4/3W250-1S/SKL/SÖ A2220015
B4/400A 400A-1A S Without With AC23 1 B4/3W400-1S/SKL/SÖ A2220016
B4/400A 150A-1A S Without With AC23 1 B4/3W150-1S/SKL/SÖ A2220017
B4/400A 200A-5A MS Moving iron With AC23 1 B4/3W200-5MS/SKL/MD/SÖ A2222013
B4/400A 250A-5A MS Moving iron With AC23 1 B4/3W250-5MS/SKL/MD/SÖ A2222014
B4/400A 400A-5A MS Moving iron With AC23 1 B4/3W400-5MS/SKL/MD/SÖ A2222015
B4/400A 150A-5A MS Moving iron With AC23 1 B4/3W150-5MS/SKL/MD/SÖ A2222016
B4/400A 200A-1A MS Moving iron With AC23 1 B4/3W200-1MS/SKL/MD/SÖ A2223014
B4/400A 250A-1A MS Moving iron With AC23 1 B4/3W250-1MS/SKL/MD/SÖ A2223015
B4/400A 400A-1A MS Moving iron With AC23 1 B4/3W400-1MS/SKL/MD/SÖ A2223016
B4/400A 150A-1A MS Moving iron With AC23 1 B4/3W150-1MS/SKL/MD/SÖ A2223017
B6/630A 250A-1A MS Moving iron Without AC23 1 B6/3W250-1MS/SKL/MD A3215012
B6/630A 250A-1A MS Moving iron With AC23 1 B6/3W250-1MS/SKL/MD/SÖ A3223013
B6/630A 250A-1A S Without Without AC23 1 B6/3W250-1S/SKL A3214016
B6/630A 250A-1A S Without With AC23 1 B6/3W250-1S/SKL/SÖ A3220011
B6/630A 250A-5A MS Moving iron Without AC23 1 B6/3W250-5MS/SKL/MD A3213016
B6/630A 250A-5A MS Moving iron With AC23 1 B6/3W250-5MS/SKL/MD/SÖ A3222010
B6/630A 250A-5A S Without Without AC23 1 B6/3W250-5S/SKL A3208023
B6/630A 250A-5A S Without With AC23 1 B6/3W250-5S/SKL/SÖ A3219011
B6/630A 400A-1A MS Moving iron Without AC23 1 B6/3W400-1MS/SKL/MD A3215013
B6/630A 400A-1A MS Moving iron With AC23 1 B6/3W400-1MS/SKL/MD/SÖ A3223014
B6/630A 400A-1A S Without Without AC23 1 B6/3W400-1S/SKL A3214017
B6/630A 400A-1A S Without With AC23 1 B6/3W400-1S/SKL/SÖ A3220012
B6/630A 400A-5A MS Moving iron Without AC23 1 B6/3W400-5MS/SKL/MD A3213017
B6/630A 400A-5A MS Moving iron With AC23 1 B6/3W400-5MS/SKL/MD/SÖ A3222011
B6/630A 400A-5A S Without Without AC23 1 B6/3W400-5S/SKL A3208024
B6/630A 400A-5A S Without With AC23 1 B6/3W400-5S/SKL/SÖ A3219012
B6/630A 600A-1A MS Moving iron Without AC23 1 B6/3W400-1MS/SKL/MD A3215014
B6/630A 600A-1A MS Moving iron With AC23 1 B6/3W600-1MS/SKL/MD/SÖ A3223015
B6/630A 600A-1A S Without Without AC23 1 B6/3W600-1S/SKL A3214018
B6/630A 600A-1A S Without With AC23 1 B6/3W600-1S/SKL/SÖ A3220013
B6/630A 600A-5A MS Moving iron Without AC23 1 B6/3W600-5MS/SKL/MD A3213018
B6/630A 600A-5A MS Moving iron With AC23 1 B6/3W600-5MS/SKL/MD/SÖ A3222012
2-15
Switch-dis-
connector-fuses
(SASIL) LV HRCsystem
Switch-
disconnector
fuses (SASIL)
BS system
Switch-
disconnector(SALIT)
LV
HRC strip-
fuseways
LV HRC
strip-type
fuse switch-
disconnectors
LV HRCfuse-
bases
LV HRC
fuse switch-
disconnectors
C|O|S|M|O®-
60mm Busbar
System
Current
transformers
Consumer
supply technology
Distribution
and instrument
cabinets
Powerlizer
system electronics
Switch-disconnec-
tor-fuses (SASIT)
DIN and BS
systems
Terminals
Appendix
Size Transformerratio
Transformerwiring(M: measu-ring deviceS: terminalstrip)
Measuringdevice
Position indi-cator, 1M+1B
Utilizationcategory,AC500V/690V
Std.P Type Article No.
SASIL...
B6/630A 600A-5A S Without Without AC23 1 B6/3W600-5S/SKL A3208025
B6/630A 600A-5A S Without With AC23 1 B6/3W600-5S/SKL/SÖ A3219013
2-16
2-17
Switch-dis-
connector-fuses
(SASIL) LV HRCsystem
Switch-
disconnector
fuses (SASIL)
BS system
Switch-
disconnector(SALIT)
LV
HRC strip-
fuseways
LV HRC
strip-type
fuse switch-
disconnectors
LV HRCfuse-
bases
LV HRC
fuse switch-
disconnectors
C|O|S|M|O®-
60mm Busbar
System
Current
transformers
Consumer
supply technology
Distribution
and instrument
cabinets
Powerlizer
system electronics
Switch-disconnec-
tor-fuses (SASIT)
DIN and BS
systems
Terminals
Appendix
Current distributioncomponents
Switch-disconnec-tor-fuses (SASIL),BS system
2-pole, 185mm busbarsystem
Strip, sizes A1 to B6,w. manually-op.mech., w/o currentmsrmnt
2-18
Product definition
SASIL strips are 2-polepluggable strip-typeswitch-disconnector-fuses.The strips are equippedwith an operator-independ-ent snap-action mechanismand manually-operatedmechanism for clear posi-tion indication andaccomodate 2 BS fuse-linksin accordance with BS-88,sizes A1/63A to B6/630A.All SASIL strips have plug-incontacts and can be se-curely plugged in an uprightfield distributor busbar sys-tem of 10mm thickness and370mm distance betweenbusbar centres using thecorresponding strip guides.A screw terminal for cablelug connection is availableat the output side.The interlocking mecha-nism in the handle pre-vents the strip cover from
opening in the connectedstate. A double-break fea-ture (upstream and down-stream of the fuse) allows asafe exchange of the fuse.
Applications
SASIL strips are mainlyused for system, cable andmotor protection in directcurrent systems up toDC440V in main andsubdistribution boards oflow voltage assemblies inaccordance with IEC/EN60439-1 (TTA/PTTA), for in-dustrial, power station andbuilding services applica-tions. Their horizontal fit-ting and compact dimen-sions allow a large numberof cable outlets to be fittedin a limited space.
A uniform width, depth andgrid dimension of 25mm ofthe strip height (75mm,
150mm) enable a rapid en-gineering and mounting ofthe strips with differentcomponent sizes used inthe switchgear cabinet.The control line and auxil-iary circuit systems are con-tacted automatically via theterminal strip / socket con-nector system when theSASIL strip is plugged in.
Product construction
The device accessories arefactory-fitted in the SASILstrip.
POSITION INDICATOR1 make contact and 1 breakcontact, wired up on apush-on terminal strip, forexternal indication.
PUSH-ON TERMINAL STRIPfor wiring of the externalauxiliary circuits.
Size Position indicator, 1M+1B Utilization category,DC220V/440V
Std.P Type Article No.
SASIL...
A1/63A Without DC22/21 1 A1-2 A6200028
A1/63A With DC22/21 1 A1-2/SKL/SÖ A6204008
BX/125A Without DC22/21 1 BX-2 A6200029
BX/125A With DC22/21 1 BX-2/SKL/SÖ A6204009
B1/100A Without DC22/21 1 B1-2 A5200003
B1/100A With DC22/21 1 B1-2/SKL/SÖ A5204006
B2/200A Without DC22/21 1 B2-2 A1200006
B2/200A With DC22/21 1 B2-2/SKL/SÖ A1204001
B4/400A Without DC22/21 1 B4-2 A2200003
B4/400A With DC22/21 1 B4-2/SKL/SÖ A2204003
B6/630A Without DC22/21 1 B6-2 A3200009
B6/630A With DC22/21 1 B6-2/SKL/SÖ A3204002
2-19
Switch-dis-
connector-fuses
(SASIL) LV HRCsystem
Switch-
disconnector
fuses (SASIL)
BS system
Switch-
disconnector(SALIT)
LV
HRC strip-
fuseways
LV HRC
strip-type
fuse switch-
disconnectors
LV HRCfuse-
bases
LV HRC
fuse switch-
disconnectors
C|O|S|M|O®-
60mm Busbar
System
Current
transformers
Consumer
supply technology
Distribution
and instrument
cabinets
Powerlizer
system electronics
Switch-disconnec-
tor-fuses (SASIT)
DIN and BS
systems
Terminals
Appendix
Current distributioncomponents
Switch-disconnec-tor-fuses (SASIL),BS system
SASIL accessories
SASIL systemaccessories
2-20
Product definition
The SASIL system accesso-ries allow a wide range ofswitchgear cabinets to beprepared for easy fitting ofSASIL switch-disconnector-fuses.Simple profiles and coversdivide the cabinets into de-vice, busbar and cablecompartments.
Applications
Fitting of components inswitchgear cabinets for lowvoltage assemblies(TTA/PTTA in accordancewith IEC/EN 60439-1) incompliance with system en-gineering specifications.
Product construction
SWITCHING CABINET PRO-FILE KITThis kit is required for theexpansion of switchgearcabinet systems whichhave not been prepared forthe fitting of SASIL compo-nents during manufacture.It consists of four sectionsand serves as a base sup-port for all built-in compo-nents of the system acces-sories.
BUSBAR SUPPORTThe 3-pole type-testedbusbar support is used to
accomodate the field dis-tributor busbar system. It issuitable for flat copperbusbars with cross-sectionsof 40mm x 10mm to100mm x 10mm. The sup-port is fixed at theswitchgear cabinet usingfixing plates or fixing brack-ets. A special version withclosing plate for the bottombusbar support is alsoavailable.
BUSBAR COVERThe 150mm high busbarcover or cable compartmentcover is used for probe-safeIP20 separation of the cabi-net busbar compartmentfrom the device compart-ment and cable compart-ment. Thiscompartmentalization pro-vides increased personneland operational safety ofthe switching station andallows working while thesystem is energized.
BUSBAR DISCONNECTIONKITThe kit is used with lowvoltage assemblies, forsectionalizing the field dis-tributor busbars. It is in-serted in the busbar sup-ports SST-185/10010.
STRIP GUIDEStrip guides allow easymounting of the SASIL
strips in the switchgear cab-inet using their push-in de-sign. They enable the SASILstrips to be mounted whilethe system is energized.Each SASIL strip is securedwith four M5x20 screws(not included).The strip guide alsoaccomodates the socketconnector, cable separatorand closing lock-out.
CABLE SEPARATORThe cable separator kit isused for IP20 separation ofthe cabinet cable compart-ment from the device com-partment.
SOCKET CONNECTORThe 16-pole socket connec-tor is the customer terminalof the SASIL strips for con-trol and auxiliary circuit wir-ing. The independentmounting of the socket con-nector at the strip guidealso allows unequipped re-serve spaces to beprewired.
CLOSING LOCK-OUTThe closing lock-out pre-vents incorrectly mountedSASIL strips from beingconnected. All closinglock-outs are clipped intothe respective strip guides.
Switching cabinet profile kit, for non-prepared system cabi-nets
Std.P Type Article No.
Kit, 4 individual profiles of 2023mm length 1 SSP/SASIL A8017256
Busbar support, 3-pole, 185mm busbar system Std.P Type Article No.
Busbar support, 100mm x 10mm 1 SST-185/10010 A8017276
Busbar support, 40mm x 10mm 1 SST-185/4010 A8017272
Busbar support, 50mm x 10mm 1 SST-185/5010 A8017273
Busbar support, 60mm x 10mm 1 SST-185/6010 A8017274
Busbar support, 80mm x 10mm 1 SST-185/8010 A8017275
Busbar support, 3-pole, 185mm busbar system Std.P Type Article No.
Busbar support, 100mm x 10mm, with seal plate 1 SST-185/A2/10010 A8017282
Busbar support, 40mm x 10mm, with seal plate 1 SST-185/A1/4010 A8017278
Busbar support, 50mm x 10mm, with seal plate 1 SST-185/A1/5010 A8017279
Busbar support, 60mm x 10mm, with seal plate 1 SST-185/A1/6010 A8017280
Busbar support, 80mm x 10mm, with seal plate 1 SST-185/A2/8010 A8017281
Busbar support fixing kit Std.P Type Article No.
Fixing plate kit (2 pcs) 1 BP1/SST A8017286
Fixing bracket for RITTAL cabinet PS4015 1 BW1/SST A8017315
Busbar cover, type of protection IP20 Std.P Type Article No.
Fastening rail kit (2x1850mm) 1 BS1/SST A8017285
Cable compartment cover, height of module 150mm 1 KA/SSA-185 A8017284
Busbar cover, height of module 150mm 1 SSA-185 A8017283
Busbar disconnection kit, for inserting in SST185/10010 Std.P Type Article No.
Bus disconnecting element, 100mm x 10mm 1 STE100/SST A8017311
Bus disconnecting element, 60mm x 10mm 1 STE60/SST A8017309
Bus disconnecting element, 80mm x 10mm 1 STE80/SST A8017310
Strip guide, kit for fitting a SASIL strip Std.P Type Article No.
Sizes 00-50 / height of module 50mm (2 pieces) 1 LF01/SASIL00-50 A8500300
Size 1 / height of module 75mm (2 pieces) 1 LF01/SASIL1 A8600066
Sizes 2-3 / height of module 150mm (2 pieces) 1 LF01/SASIL2-3 A8700074
Cable separator, kit for separating cable compartment of cabi-net
Std.P Type Article No.
Sizes 00-50 (3 pieces) 1 KSH/SASIL00-50 A8500308
Size 1 (3 pieces) 1 KSH/SASIL1 A8600139
Sizes 2-3 with mounting frame (3 pieces) 1 KSH/SASIL2-3 A8700140
2-21
Switch-dis-
connector-fuses
(SASIL) LV HRCsystem
Switch-
disconnector
fuses (SASIL)
BS system
Switch-
disconnector(SALIT)
LV
HRC strip-
fuseways
LV HRC
strip-type
fuse switch-
disconnectors
LV HRCfuse-
bases
LV HRC
fuse switch-
disconnectors
C|O|S|M|O®-
60mm Busbar
System
Current
transformers
Consumer
supply technology
Distribution
and instrument
cabinets
Powerlizer
system electronics
Switch-disconnec-
tor-fuses (SASIT)
DIN and BS
systems
Terminals
Appendix
Socket connector, customer control circuit terminal Std.P Type Article No.
Socket connector, 16-pole 1 BL/SASIL00-3 A8016141
Closing lock-out, retrofittable in strip guide Std.P Type Article No.
Sizes 00-50 / height of module 50mm 1 ESS/SASIL00-50 A8517305
Size 1 / height of module 75mm 1 ESS/SASIL1 A8617306
Sizes 2-3 / height of module 150mm 1 ESS/SASIL2-3 A8717307
Drawing tool, for drawing out SASIL strips Std.P Type Article No.
Drawing tool 1 AW/SASIL00-3 A8000005
Reserve panel cover, transparent Std.P Type Article No.
Sizes 00-50 / height of module 50mm 1 LFA-D3/SASIL00-50 A8500313
Size 1 / height of module 75mm 1 LFA-D3/SASIL1 A8600142
Sizes 2-3 / height of module 150mm 1 LFA-D3/SASIL2-3 A8700143
Reserve panel covers, transparent, w. ventilation elmnts, IP30 Std.P Type Article No.
Size 1 / height of module 75mm, horizontal fitting 1 LFALH/SASIL1 A8600258
Sizes 2-3 / height of module 150mm, horizontal fitting 1 LFALH/SASIL2-3 A8700260
Size 1 / height of module 75mm, vertical fitting 1 LFALV/SASIL1 A8600259
Sizes 2-3 / height of module 150mm, vertical fitting 1 LFALV/SASIL2-3 A8700261
Reserve panel cover, sheet steel Std.P Type Article No.
Height of module 50mm, RAL7035 1 LFA050/25 A8500003
Height of module 75mm, RAL7035 1 LFA075/25 A8600005
Height of module 150mm, RAL7035 1 LFA150/25 A8700001
Height of module 300mm, RAL7035 1 LFA300/25 A8900002
Height of module 50mm, RAL7032 1 LFA050/25/7032 A8500030
Height of module 75mm, RAL7032 1 LFA075/25/7032 A8600032
Height of module 150mm, RAL7032 1 LFA150/25/7032 A8700037
Height of module 300mm, RAL7032 1 LFA300/25/7032 A8900036
Reserve panel cover, sheet steel, ventilation slots, IP30 Std.P Type Article No.
Height of module 50mm, RAL7035 1 LFA050L/25 A8500004
Height of module 75mm, RAL7035 1 LFA075L/25 A8600006
Height of module 150mm, RAL7035 1 LFA150L/25 A8700005
Height of module 300mm, RAL7035 1 LFA300L/25 A8900003
Height of module 50mm, RAL7032 1 LFA050L/25/7032 A8500031
Height of module 75mm, RAL7032 1 LFA075L/25/7032 A8600033
Height of module 150mm, RAL7032 1 LFA150L/25/7032 A8700035
Height of module 300mm, RAL7032 1 LFA300L/25/7032 A8900037
2-22
Strip cover with operating handle Std.P Type Article No.
Sizes 00-50 / height of module 50mm 1 LD/SASIL00-50/D3 A8500148
Size 1 / height of module 75mm 1 LD/SASIL1/D3 A8100270
Size 2 / height of module 150mm 1 LD/SASIL2/D3 A8200149
Size 3 / height of module 150mm 1 LD/SASIL3/D3 A8300271
Fastener for strip cover, kit Std.P Type Article No.
7mm square, for fitting in SASIL00-3 5 V7/SASIL00-3 A8008008
8mm square, for fitting in SASIL00-3 5 V8/SASIL00-3 A8008004
2-23
Switch-dis-
connector-fuses
(SASIL) LV HRCsystem
Switch-
disconnector
fuses (SASIL)
BS system
Switch-
disconnector(SALIT)
LV
HRC strip-
fuseways
LV HRC
strip-type
fuse switch-
disconnectors
LV HRCfuse-
bases
LV HRC
fuse switch-
disconnectors
C|O|S|M|O®-
60mm Busbar
System
Current
transformers
Consumer
supply technology
Distribution
and instrument
cabinets
Powerlizer
system electronics
Switch-disconnec-
tor-fuses (SASIT)
DIN and BS
systems
Terminals
Appendix
Current distributioncomponents
Switch-disconnec-tor-fuses (SASIL),BS system
SASIL accessories
SASIL device moun-ting system, 185mm
2-24
Product definition
The SASIL device mountingsystem extends the fusecombination system by an-other module. Mountingplates and device mountingmodules, available with orwithout voltage tap andwith various moduleheights ranging from100mm to 600mm, enablelow voltage assemblies tobe expanded as required.
Thus other devices such ascircuit-breakers, motorstarter combinations, mod-ular installation devices etc.can be positioned in thesame switchgear cabinet inwhich SASIL strips are fit-ted, which saves consider-able space in the cabinet.
Applications
The SASIL device mountingsystem is mounted in allcommercially availableswitchgear cabinets inwhich SASIL strips can bemounted. It allows SASILstrips, mounting plates, de-vice mounting modules andsupply modules to bemounted in the sameswitchgear cabinet andwith a common field dis-tributor busbar system. Thisenables a state-of-the-artmodular construction of
low voltage assemblies inaccordance with IEC/EN60439-1.
Product construction
MOUNTING PLATESMounting plates arescrew-fixed at the two rearswitching cabinet profiles.There are closed versionswith aperture for the volt-age tap kit and versionswith system holes (5.3mmdrill holes and 12.5mmspacing).
SUPPLY MODULEThe supply module allowsthe field distributor busbarsystem to be supplied. Theplug-in contacts are de-signed for rated currents upto 630A. Higher supply cur-rents require two or moremodules.
DEVICE MOUNTING MOD-ULEDevice mounting moduleswith integrated mountingplate are available for dif-ferent expansion versions.From a module height of200mm, they can be pro-vided with a voltage tap tothe field distributor busbar.The supplied guides alloweasy contacting of the fielddistributor busbar. Themodules are fixed at thetwo frontal cabinet profiles.
Prepared modules for mod-ular installation devicesand bus-mounting fuse-ele-ments are also available.
DEVICE DOORDoors for mounting platesand device mounting mod-ules are available withmodule heights of 100mmto 600mm. Versions withinspection window are alsoavailable. The doors arefixed at the frontal left cabi-net profile using the sup-plied hinges and are lockedusing a 3mm two-way keybit.
TERMINAL COMPARTMENTSEPARATORTerminal compartment sep-arators and flange platesprovide IP20 separation ofthe cabinet device compart-ment from the cable com-partment. Separators mustbe ordered separately withmounting plates, but aresupplied with devicemounting modules. Theyare fixed at the two rightcabinet profiles.
VOLTAGE TAP KITTwo kits for 100A and 630Aare available. The 100A ver-sion can only be mountedwith device mounting mod-ules, while the 630A ver-sion is also available formounting plates.
Mounting plate without hole grid Std.P Type Article No.
Height of module 100mm 1 MP100/SASIL A8030000
Height of module 150mm 1 MP150/SASIL A8030001
Height of module 200mm 1 MP200/SASIL A8030002
Height of module 300mm 1 MP300/SASIL A8030003
Height of module 450mm 1 MP450/SASIL A8030004
Height of module 600mm 1 MP600/SASIL A8030005
Mounting plate with hole grid Std.P Type Article No.
Height of module 100mm 1 MPL100/SASIL A8030006
Height of module 150mm 1 MPL150/SASIL A8030007
Height of module 200mm 1 MPL200/SASIL A8030008
Height of module 300mm 1 MPL300/SASIL A8030009
Height of module 450mm 1 MPL450/SASIL A8030010
Height of module 600mm 1 MPL600/SASIL A8030011
Mounting plate prepared for voltage tap, without hole grid Std.P Type Article No.
Height of module 200mm 1 MP200/E/SASIL A8030100
Height of module 300mm 1 MP300/E/SASIL A8030101
Mounting plate prepared for voltage tap, with hole grid Std.P Type Article No.
Height of module 200mm 1 MPL200/E/SASIL A8030102
Height of module 300mm 1 MPL300/E/SASIL A8030103
Supply module, 630A Std.P Type Article No.
Height of module 100mm 1 EM100/E/SASIL A8030300
Terminal compartment separator w / w/o flange opening Std.P Type Article No.
Height of module 100mm 1 ASG100/SASIL A8030501
Height of module 150mm (1xFP1.. required) 1 ASG150/SASIL A8030502
Height of module 200mm (1xFP2.. required) 1 ASG200/SASIL A8030503
Height of module 300mm (2xFP1.. required) 1 ASG300/SASIL A8030504
Height of module 450mm (3xFP1.. required) 1 ASG450/SASIL A8030505
Height of module 600mm (4xFP1.. required) 1 ASG600/SASIL A8030506
Height of module 100mm, without flange opening 1 ASGG100/SASIL A8030500
Device mounting module without voltage tap Std.P Type Article No.
Height of module 150mm 1 GEM150/SASIL A8030200
2-25
Switch-dis-
connector-fuses
(SASIL) LV HRCsystem
Switch-
disconnector
fuses (SASIL)
BS system
Switch-
disconnector(SALIT)
LV
HRC strip-
fuseways
LV HRC
strip-type
fuse switch-
disconnectors
LV HRCfuse-
bases
LV HRC
fuse switch-
disconnectors
C|O|S|M|O®-
60mm Busbar
System
Current
transformers
Consumer
supply technology
Distribution
and instrument
cabinets
Powerlizer
system electronics
Switch-disconnec-
tor-fuses (SASIT)
DIN and BS
systems
Terminals
Appendix
Device mounting module prepared for voltage tap Std.P Type Article No.
Height of module 200mm 1 GEM200/SASIL A8030201
Height of module 300mm 1 GEM300/SASIL A8030202
Height of module 450mm 1 GEM450/SASIL A8030203
Height of module 600mm 1 GEM600/SASIL A8030204
Device mounting module for modular installation, withoutvoltage tap
Std.P Type Article No.
Height of module 150mm, 1x18 TE 1 GEM150/RE/SASIL A8030205
Device mounting module for modular installation, withoutvoltage tap, tier spacing 125mm
Std.P Type Article No.
Height of module 200mm, 1x18 TE 1 GEM200/RE/SASIL A8030206
Height of module 300mm, 2x18 TE 1 GEM300/RE/SASIL A8030207
Height of module 450mm, 3x18 TE 1 GEM450/RE/SASIL A8030208
Height of module 600mm, 4x18 TE 1 GEM600/RE/SASIL A8030209
For bus-mounting fuse-bases, with voltage tap, 60mm busbarsystem
Std.P Type Article No.
Height of module 450mm, incl. 60mm busbar system 1 GEM450/RS/SASIL A8030210
Cover plate for modular installation devices, tier spacing150mm
Std.P Type Article No.
Height of module 300mm, 2x18 TE 1 BSAP/300/RE2X150/SASIL A8030810
Height of module 450mm, 3x18 TE 1 BSAP/450/RE-3X150/SASIL A8030811
Height of module 600mm, 4x18 TE 1 BSAP/600/RE-4X150/SASIL A8030812
Door without inspection window, D3 fastener Std.P Type Article No.
Height of module 100mm, RAL7035 1 T100/D3/SASIL A8030400
Height of module 150mm, RAL7035 1 T150/D3/SASIL A8030401
Height of module 200mm, RAL7035 1 T200/D3/SASIL A8030402
Height of module 300mm, RAL7035 1 T300/D3/SASIL A8030403
Height of module 450mm, RAL7035 1 T450/D3/SASIL A8030404
Height of module 600mm, RAL7035 1 T600/D3/SASIL A8030405
Height of module 100mm, RAL7032 1 T100/D3/SASIL/7032 A8030411
Height of module 150mm, RAL7032 1 T150/D3/SASIL/7032 A8030412
Height of module 200mm, RAL7032 1 T200/D3/SASIL/7032 A8030413
Height of module 300mm, RAL7032 1 T300/D3/SASIL/7032 A8030414
Height of module 450mm, RAL7032 1 T450/D3/SASIL/7032 A8030415
Height of module 600mm, RAL7032 1 T600/D3/SASIL/7032 A8030416
2-26
Door with inspection window, D3 fastener Std.P Type Article No.
Height of module 150mm, RAL7035 1 TS150/D3/SASIL A8030406
Height of module 200mm, RAL7035 1 TS200D3/SASIL A8030407
Height of module 300mm, RAL7035 1 TS300/D3/SASIL A8030408
Height of module 450mm, RAL7035 1 TS450/D3/SASIL A8030409
Height of module 600mm, RAL7035 1 TS600/D3/SASIL A8030410
Height of module 150mm, RAL7032 1 TS150/D3/SASIL/7032 A8030417
Height of module 200mm, RAL7032 1 TS200/D3/SASIL/7032 A8030418
Height of module 300mm, RAL7032 1 TS300/D3/SASIL/7032 A8030419
Height of module 450mm, RAL7032 1 TS450/D3/SASIL/7032 A8030420
Height of module 600mm, RAL7032 1 TS600/D3/SASIL/7032 A8030421
Flange plate, closed Std.P Type Article No.
Height of module 150mm 1 FP1/SASIL A8030600
Height of module 200mm (for ASG200) 1 FP2/SASIL A8030601
Flange plate for cable covers KSH/SASIL1 Std.P Type Article No.
Height of module 150mm 1 FP1/KSH/SASIL A8030602
Height of module 200mm (for ASG200) 1 FP2/KSH/SASIL A8030603
Voltage tap kit, 100A Std.P Type Article No.
For device mounting module (25mm² cable), M6 1 BSE/100A/SASIL A8030701
Voltage tap kit, 630A Std.P Type Article No.
For mounting plates and device mounting module, M10 1 BSE/630A/SASIL A8030700
2-27
Switch-dis-
connector-fuses
(SASIL) LV HRCsystem
Switch-
disconnector
fuses (SASIL)
BS system
Switch-
disconnector(SALIT)
LV
HRC strip-
fuseways
LV HRC
strip-type
fuse switch-
disconnectors
LV HRCfuse-
bases
LV HRC
fuse switch-
disconnectors
C|O|S|M|O®-
60mm Busbar
System
Current
transformers
Consumer
supply technology
Distribution
and instrument
cabinets
Powerlizer
system electronics
Switch-disconnec-
tor-fuses (SASIT)
DIN and BS
systems
Terminals
Appendix
2-28
Type SASIL 185mmType key for SASIL strips
Type of operation
Size
Design
Number of poles
CTs
Accuracy class rating of the CTs to VDE 0414
Order exampleSASIL strip, size 2
1
2
3
4
5
6
➤
*MOT
00-5012
2N3
3NA1BXB1B2B4B6
*DK
*-2
*1W3W6W
1WZ3WZ6WZ
*V
VB
Manual operationMotor operation, DC24V
DIN LV HRC size 00 Utilization category: 400V/AC23 500V/AC23 690V/AC23DIN LV HRC size 1 Utilization category: 400V/AC23 500V/AC23 690V/AC23DIN LV HRC size 2 Utilization category: 400V/AC23 500V/AC23 690V/AC23DIN LV HRC size 2 Utilization category: 400V/AC23 500V/AC22 690V/AC22DIN LV HRC size 3 Utilization category: 400V/AC23 500V/AC23 690V/AC23DIN LV HRC size 3 Utilization category: 400V/AC23 500V/AC22 690V/AC22BS88, size A1/63A, module height 50 mmBS88, size non-standard/125A, module height 50 mmBS88, size B1/100A, module height 75 mmBS88, size B2/200A, module height 75 mmBS88, size B4/400A, module height 150 mmBS88, size non-standard/630A, module height 150 mm
StripDouble strip, 2 strips w. a common manually-op. mech.Coupling strip for coupling of two field distributor busbar systems (for DIN LV HRC size 3)
3-pole2-pole
Without transformers fitted in the strip1 transformer, fitted in strip to phase L1, feeding through field distribution busbars3 transformers, fitted in strip, feeding through field distribution busbars6 transformers, fitted in double strip, feeding through field distribution busbars1 current transformer, built-in strip on phase L1, feeding through cable terminal3 current transformers, built-in strip, feeding through cable terminal6 current transformers, built-in strip, feeding through cable terminal
Class 1Class 0.5, with certification mark (for transformers from 150A)Class 0.5, with certification mark, individuallycertified (for transformers from 150A)
➤ Strip, manually op., 3-pole➤ Utilization category, AC23V / 690V➤ 3 current-transformers (CT), 250A-1A, class 0.5, with certification mark, individually certified,
wired up on measuring device and push-on terminal strip➤ Ammeter, bimetallic, max. demand indicator / setting time 8 min. ➤ Position indicator, 1 make and 1 break contact➤ Electronic fuse monitor
➤ Please adhere to the order given here
Order example SASIL 2 / 3W VB 250 - 1 MS / SKL / MB8 / SÖ / ES001 2 3 4 5 6 7 8 9 10 11 12 13
2-29
Switch-dis-
connector-fuses
(SASIL) LV HRCsystem
Switch-
disconnector
fuses (SASIL)
BS system
Switch-
disconnector(SALIT)
LV
HRC strip-
fuseways
LV HRC
strip-type
fuse switch-
disconnectors
LV HRCfuse-
bases
LV HRC
fuse switch-
disconnectors
C|O|S|M|O®-
60mm Busbar
System
Current
transformers
Consumer
supply technology
Distribution
and instrument
cabinets
Powerlizer
system electronics
Switch-disconnec-
tor-fuses (SASIT)
DIN and BS
systems
Terminals
Appendix
Type SASIL 185mmType key for SASIL strips
➤
Order example SASIL 2 / 3W VB 250 - 1 MS / SKL / MB8 / SÖ / ES001 2 3 4 5 6 7 8 9 10 11 12 13
5075
100125150200250300400500600
15
SM
MS
*SKL
*MD
MB8MB15
*SÖ1S
*ES00
CT primary current
CT secondary current
CT wiring
Push-on terminal stripfor auxiliary circuits
Measuring device
Auxiliary switch for position indication
Electronic modules
7
8
9
10
11
12
13
50A75A100A125A150A200A250A300A400A500A600A
1A5A
On push-on terminal strip, for external connectionOn measuring device (1 transformer)On measuring device and push-on terminal strip
For strips without device accessories and for internal current measurement and indicationPush-on terminal strip required for 3-pole current measurement, auxiliary switches and electronic modules,and for 1-pole current measurement with external terminal connection
Without measuring deviceMoving iron current meterBimetallic, with slave pointer, setting time 8min. (for transformers from 125A)Bimetallic, with slave pointer, setting time 15min. (for transformers from 125A)
Without position indicator1 make and 1 break1 make (in conjunction with electronic module ES05)
Without electronic modulesElectronic fuse monitor
* No type ID must be stated for these versions.
2-30
SASIL...1W...M/SKL/M.../SÖ/ES00
Ordering details see pages 2-7; 2-11
Q1 Lastrennschalter mit Sicherung / NH vertical switch-disconnector-fuseQ1-S1 Hilfsschalter Schaltstellungsanzeige / Auxillary switchF1, F2, F3 Sicherungen / FusesF4 Sicherungsüberwachung ES00 / Electronic fuse monitor ES00V1-V3 Störmeldungsanzeige F1-F3 Sicherungsüberwachung / Phase-related LED fault indicator F1-F3V4 Bereitschaftsanzeige Sicherungsüberwachung / Ready signal-fuse monitoringX1 Steckerleiste / Connection stripT1 Stromwandler / Current transformerP1 Strommesser / Ammeter
3/N/PE 50Hz AC380-690VL1L2L3(N)PE(N)
Darstellung im ausgeschalteten Zustand /Off-state view
Einspeisung /Incoming unit
AP1T1
Q1
F1 F2 F3
L1 L2 L3Abgang / Outgoing unit
V4 V1 V2 V3
Q1-S1
F4
X1
2
1
4
3
6
5
1615
97
810
1311
1214
Sicherungsüberwachung ES00(Arbeitsstromprinzip) /Electronic fuse monitor ES00(in working current concept)
Schaltstellunganzeige /Indicator for switchoperating position
Schließer /Normallyopencontact
Öffner(bei StörungKontaktgeöffnet) /Contact breakes(on operationfault)
Öffner /Normallyclosedcontact
Schließer(bei StörungKontaktgeschlossen) /Contact makes (on operation fault)
Q1 Lastrennschalter mit Sicherung / NH vertical switch-disconnector-fuseQ1-S1 Hilfsschalter Schaltstellungsanzeige / Auxillary switchF1, F2, F3 Sicherungen / FusesF4 Sicherungsüberwachung ES00 / Electronic fuse monitor ES00V1-V3 Störmeldungsanzeige F1-F3 Sicherungsüberwachung / Phase-related LED fault indicator F1-F3V4 Bereitschaftsanzeige Sicherungsüberwachung / Ready signal-fuse monitoringX1 Steckerleiste / Connection stripT1, T2, T3 Stromwandler / Current transformerP1 Strommesser / Ammeter
3/N/PE 50Hz AC380-690VL1L2L3(N)PE(N)
Darstellung im ausgeschalteten Zustand /Off-state view
Einspeisung /Incoming unit
AP1T1
Q1
F1 F2 F3
L1 L2 L3Abgang / Outgoing unit
V4 V1 V2 V3
Q1-S1
F4
X1
2
1
4
3
6
5
1516
97
810
1311
1214
Sicherungsüberwachung ES00(Arbeitsstromprinzip) /Electronic fuse monitor ES00(in working current concept)
Schaltstellunganzeige /Indicator for switchoperating position
Schließer /Normallyopencontact
Öffner(bei StörungKontaktgeöffnet) /Contact breakes(on operationfault)
Öffner /Normallyclosedcontact
Schließer(bei StörungKontaktgeschlossen) /Contact makes (on operation fault)
T2
T3 Option
S1
S1
S1
S2
S2
S2
SASIL...3W...MS/SKL/M.../SÖ/ES00
Ordering details see pages 2-13; 2-16
2-31
Switch-dis-
connector-fuses
(SASIL) LV HRCsystem
Switch-
disconnector
fuses (SASIL)
BS system
Switch-
disconnector(SALIT)
LV
HRC strip-
fuseways
LV HRC
strip-type
fuse switch-
disconnectors
LV HRCfuse-
bases
LV HRC
fuse switch-
disconnectors
C|O|S|M|O®-
60mm Busbar
System
Current
transformers
Consumer
supply technology
Distribution
and instrument
cabinets
Powerlizer
system electronics
Switch-disconnec-
tor-fuses (SASIT)
DIN and BS
systems
Terminals
Appendix
SASILA1/...
Ordering details see page 2-5
155
81
10
542
3mm DB
11,5
M8 72
185 ± 1,5 185 ± 1,5
230
25
260
X50
590
44,5 M4
108
145
155
81
10
542
3mm DB
11,5
M8 72
185 ± 1,5 185 ± 1,5
230
25
260
X
50
590
58 M8
108
145
SASILBX/...
Ordering details see page 2-5
2-32
SASILB1/...
Ordering details see page 2-5
590
X
260
155
230
25
81
185 1.5
10
X
180 136
75
3mm DB
111
185 1.5
M8
M10
96
SASILB2/...
Ordering details see page 2-5
2-33
Switch-dis-
connector-fuses
(SASIL) LV HRCsystem
Switch-
disconnector
fuses (SASIL)
BS system
Switch-
disconnector(SALIT)
LV
HRC strip-
fuseways
LV HRC
strip-type
fuse switch-
disconnectors
LV HRCfuse-
bases
LV HRC
fuse switch-
disconnectors
C|O|S|M|O®-
60mm Busbar
System
Current
transformers
Consumer
supply technology
Distribution
and instrument
cabinets
Powerlizer
system electronics
Switch-disconnec-
tor-fuses (SASIT)
DIN and BS
systems
Terminals
Appendix
SASILB4/...
Ordering details see page 2-5
25
X
X
590
10
260
155
96
150
542
185 1.5
37.5
3mm DB
M12
230
81
111 M8
145
185 1.5
25
X
X
590
10
260
155
96
150
542
185 1.5
37.5
3mm DB
M12
230
81
111 M8
145
185 1.5
SASILB6/...
Ordering details see page 2-5
25
X
X
590
10
260
155
96
150
542
185 1.5
37.5
3mm DB
M12
230
81
111 M8
145
185 1.5
2-34
SASILA1-2/...
Ordering details see page 2-19
155
260 23
081
25
10
370 ± 1,5
542
590
44,5 M4
50
3mm DB
11,5
M8 72
145
X
X
155
260 23
081
25
10
370 ± 1,5
542
590
58 M8
50
3mm DB
11,5
M8 72
145
X
X
SASILBX-2/...
Ordering details see page 2-19
2-35
Switch-dis-
connector-fuses
(SASIL) LV HRCsystem
Switch-
disconnector
fuses (SASIL)
BS system
Switch-
disconnector(SALIT)
LV
HRC strip-
fuseways
LV HRC
strip-type
fuse switch-
disconnectors
LV HRCfuse-
bases
LV HRC
fuse switch-
disconnectors
C|O|S|M|O®-
60mm Busbar
System
Current
transformers
Consumer
supply technology
Distribution
and instrument
cabinets
Powerlizer
system electronics
Switch-disconnec-
tor-fuses (SASIT)
DIN and BS
systems
Terminals
Appendix
SASILB1-2/...
Ordering details see page 2-19
25
X
X
590
10
260 2
30
155
96
180
81
75
544
370 1.5
M10
3mm DB
111 M8
260
155
230
25
81
590
75
370 1.5
10
X
X96
180
M10
111
3mm DB
M8
SASILB2-2/...
Ordering details see page 2-19
2-36
SASILB4-2/...
Ordering details see page 2-19
25
X
X
590
10
260
155
96
145
150
542
370 1.537.5
3mm DB
M12
230
81
111 M8
25
X
X
590
10
260
155
96
145
150
542
370 1.537.5
3mm DB
M12
230
81
111 M8
SASILB6-2/...
Bestellangaben siehe Seite 2-19
2-37
Switch-dis-
connector-fuses
(SASIL) LV HRCsystem
Switch-
disconnector
fuses (SASIL)
BS system
Switch-
disconnector(SALIT)
LV
HRC strip-
fuseways
LV HRC
strip-type
fuse switch-
disconnectors
LV HRCfuse-
bases
LV HRC
fuse switch-
disconnectors
C|O|S|M|O®-
60mm Busbar
System
Current
transformers
Consumer
supply technology
Distribution
and instrument
cabinets
Powerlizer
system electronics
Switch-disconnec-
tor-fuses (SASIT)
DIN and BS
systems
Terminals
Appendix
SSP/SASIL
Ordering details see page 2-5
SST-185/...
Ordering details see page 2-5
2023
11.5
25 24.8
O 5.3 12.5
4x
24.8
25
50
25
12.5
Typ A SST-185/4010 40SST-185/5010 50SST-185/6010 60SST-185/8010 80SST-185/10010 100
A24
185
495
10
185
O6.
5
SW6
10
A 15
185
406
495
185
450
2932
12.5 Typ Ma A
SST-185/A1/4010 40SST-185/A1/5010 50SST-185/A1/6010 60SST-185/A1/8010 80SST-185/A1/10010 100
Ordering details see page 2-5 Ordering details see page 2-5
SST-185/A2/10010 BP1/SST
4
M6
46.5
12.5
40
39
25
36.5
90
6.5
24
19.5
1.51850
12.5 104.3
BW1/SST BS1/SST
Ordering details see page 2-5 Ordering details see page 2-5
48
48
152.7
149.
5
25.2
2.2
5050
64.4
456,5
185
149,5
185
KA/SSA-185 SSA-185
Ordering details see page 2-5 Ordering details see page 2-5
2-38
STE.../SST
Ordering details see page 2-5
LF01/SASIL00-50
Ordering details see page 2-5
141
58.5
2548
50
75
125149.5
40 4.8
25
12.5
234.5
175
4.8
M5
50
125
Ordering details see page 2-5 Ordering details see page 2-5
LF01/SASIL1 LF01/SASIL2-3
200
43
35.5
48
6.5
200
6,5
70
63
39
KSH/SASIL00-50 KSH/SASIL1
Ordering details see page 2-5 Ordering details see page 2-5
54.5
205
68
32
6.5
12
KSH/SASIL2-3 BL/SASIL00-3
Ordering details see page 2-5 Ordering details see page 2-5
2-39
Switch-dis-
connector-fuses
(SASIL) LV HRCsystem
Switch-
disconnector
fuses (SASIL)
BS system
Switch-
disconnector(SALIT)
LV
HRC strip-
fuseways
LV HRC
strip-type
fuse switch-
disconnectors
LV HRCfuse-
bases
LV HRC
fuse switch-
disconnectors
C|O|S|M|O®-
60mm Busbar
System
Current
transformers
Consumer
supply technology
Distribution
and instrument
cabinets
Powerlizer
system electronics
Switch-disconnec-
tor-fuses (SASIT)
DIN and BS
systems
Terminals
Appendix
ESS/SASIL00-50
Ordering details see page 2-5
ESS/SASIL1
Ordering details see page 2-5
B
20
62.5
122.5
21.5
113
AA-B
Ordering details see page 2-5 Ordering details see page 2-5
ESS/SASIL2-3 AW/SASIL00-3
3mm DB
25
590
A
Typ ASASIL 00-50 49SASIL 1 74.5SASIL 2-3 149.5
LFA-D3/SASIL... LFALH/SASIL1, LFALH/SASIL2-3
Ordering details see page 2-5 Ordering details see page 2-5
35.7
3mm DB
A
590
25
Typ ASASIL 1 74.5SASIL 2-3 149.5
590
A
536
Typ Ma A
LFA50/15 50LFA75/25 75LFA150/25 150LFA300/25 300
O7
23
LFALV/SASIL1, LFALV/SASIL2-3 LFA.../25/...
Ordering details see page 2-5 Ordering details see page 2-5
2-40
LFA...L/25/...
Ordering details see page 2-5
LD/SASIL00-50/D3
Ordering details see page 2-5
590A
536
Typ Ma A
LFA50/15 50LFA75/25 75LFA150/25 150LFA300/25 300
26.7
23
50
590
56
3mm DB
75
590
56
150
590
56
Ordering details see page 2-5 Ordering details see page 2-5
LD/SASIL1/D3 LD/SASIL2/D3, LD/SASIL3/D3
V7/SASIL00-3 V8/SASIL00-3
Ordering details see page 2-5 Ordering details see page 2-5
MP.../SASIL MPL.../SASIL
Ordering details see page 2-5 Ordering details see page 2-5
2-41
Switch-dis-
connector-fuses
(SASIL) LV HRCsystem
Switch-
disconnector
fuses (SASIL)
BS system
Switch-
disconnector(SALIT)
LV
HRC strip-
fuseways
LV HRC
strip-type
fuse switch-
disconnectors
LV HRCfuse-
bases
LV HRC
fuse switch-
disconnectors
C|O|S|M|O®-
60mm Busbar
System
Current
transformers
Consumer
supply technology
Distribution
and instrument
cabinets
Powerlizer
system electronics
Switch-disconnec-
tor-fuses (SASIT)
DIN and BS
systems
Terminals
Appendix
MP.../E/SASIL
Ordering details see page 2-5
MPL.../E/SASIL
Ordering details see page 2-5
185
53
75
540
98
185
525
Ordering details see page 2-5 Ordering details see page 2-5
EM100/E/SASIL ASG(G).../SASIL,
Typ A GEM150 148 GEM200 198GEM300 298GEM450 448 GEM600 598
190
A
553
Typ A GEM150 148 1xZGEM200 198 1xZGEM300 298 2xZGEM450 448 3xZGEM600 598 4xZ
553
190
A
Z
18TE=324mm
GEM.../SASIL GEM.../RE/SASIL
Ordering details see page 2-5 Ordering details see page 2-5
553
285
230
448
195
GEM450/RS/SASIL T(S).../D3/SASIL...
Ordering details see page 2-5 Ordering details see page 2-5
2-42
FP1/SASIL, FP2/SASIL
Ordering details see page 2-5
FP.../KSH/SASIL
Ordering details see page 2-5
Typ A B
FP1 119 110
FP2 169 160
110
119
A B
GEM...
MIN
.50
185 185
10
MIN
.50
MPL...GEM...
54.4
185
m.50
m.50
185
10M10
Ordering details see page 2-5 Ordering details see page 2-5
BSE/100A/SASIL BSE/630A/SASIL
2-43
Switch-dis-
connector-fuses
(SASIL) LV HRCsystem
Switch-
disconnector
fuses (SASIL)
BS system
Switch-
disconnector(SALIT)
LV
HRC strip-
fuseways
LV HRC
strip-type
fuse switch-
disconnectors
LV HRCfuse-
bases
LV HRC
fuse switch-
disconnectors
C|O|S|M|O®-
60mm Busbar
System
Current
transformers
Consumer
supply technology
Distribution
and instrument
cabinets
Powerlizer
system electronics
Switch-disconnec-
tor-fuses (SASIT)
DIN and BS
systems
Terminals
Appendix
2-44
Type SASIL A1-2 SASIL BX-2Technical data for switch-disconnector-fuse (SASIL), BS bolted fuse system (in accordance with IEC/EN 60947-3)
Electricalcharacteristics
Fuse-links
Mechanicalcharacteristics
Cableconnection
Type ofprotection
Operatingconditions
1)Without packaging2)35°C normal temperature, at 55°C with reduced operating current3)Upright busbar4)Cable connection right5)Cable connection bottom
Rated operational voltage Ue VRated operational current Ie AConventional free air thermal current with fuses Ith AConventional free air thermal current with solid links Ith ARated frequency - HzRated insulation voltage Ui VRated conditional short-circuit current - kAeff
Rated short-time withstand current (1sec) Icw kAeff
Utilization category - -Rated making capacity - ARated breaking capacity - ARated impulse withstand voltage Uimp kVOperating cycles with current - -Total power loss at Ith (without fuse) Pv W
Size to BS88-1 - -Max. rated current IN AMax. permis. power loss per fuse-link Pv W
Operating cycles without current - -Weight 1) - kgBusbar distance - mmBusbar thickness3) - mm
Flat terminal Bolt diameter - - Cable lug (DIN 46 235) - mm2
Flat bar - mmTightening torque Ma Nm
Terminal Clamping cross-section - mm2
Tightening torque Ma NmTerminal Clamping cross-section - mm2
Tightening torque Ma NmTerminal Clamping cross-section - mm2
Tightening torque Ma NmTerminal Clamping cross-section - mm2
Tightening torque Ma Nm
Front side Operational state - -Device fitted Front cover open - -
Ambient temperature 2) Tu °CRated operating mode - - Actuation - -Mounting position - -Altitude - mPollution degree - -Overvoltage category - -
DC440 DC44063A 10063A 100
- -- -
AC 1000 AC 100025 25- -
DC-21B DC-21B150 150150 150
8 8300 30013 13
A1 Bx563A 12512 12
1700 17004.6 4.6370 37010 10
M8 M81 x 10 - 95 1 x 10 - 95
24 x 5 24 x 510 10- -
- -
- -
- -
IP40 IP40IP20 IP20
-25 to +55 -25 to +55Continuous operation Continuous operation
Independent manual operation Independent manual operationHorizontal4), vertical5) Horizontal4), vertical5)
Up to 2000 Up to 20003 3III III
2-45
Switch-dis-
connector-fuses
(SASIL) LV HRCsystem
Switch-
disconnector
fuses (SASIL)
BS system
Switch-
disconnector(SALIT)
LV
HRC strip-
fuseways
LV HRC
strip-type
fuse switch-
disconnectors
LV HRCfuse-
bases
LV HRC
fuse switch-
disconnectors
C|O|S|M|O®-
60mm Busbar
System
Current
transformers
Consumer
supply technology
Distribution
and instrument
cabinets
Powerlizer
system electronics
Switch-disconnec-
tor-fuses (SASIT)
DIN and BS
systems
Terminals
Appendix
Type SASIL B1-2 SASIL B2-2Technical data for switch-disconnector-fuse (SASIL), BS bolted fuse system (in accordance with IEC/EN 60947-3)
Electricalcharacteristics
Fuse-links
Mechanicalcharacteristics
Cableconnection
Type ofprotection
Operatingconditions
1)Without packaging2)35°C normal temperature, at 55°C with reduced operating current3)Upright busbar4)Cable connection right5)Cable connection bottom
Rated operational voltage Ue VRated operational current Ie AConventional free air thermal current with fuses Ith AConventional free air thermal current with solid links Ith ARated frequency - HzRated insulation voltage Ui VRated conditional short-circuit current - kAeff
Rated short-time withstand current (1sec) Icw kAeff
Utilization category - -Rated making capacity - ARated breaking capacity - ARated impulse withstand voltage Uimp kVOperating cycles with current - -Total power loss at Ith (without fuse) Pv W
Size to BS88-1 - -Max. rated current IN AMax. permis. power loss per fuse-link Pv W
Operating cycles without current - -Weight 1) - kgBusbar distance - mmBusbar thickness3) - mm
Flat terminal Bolt diameter - - Cable lug (DIN 46 235) - mm2
Flat bar - mmTightening torque Ma Nm
Terminal Clamping cross-section - mm2
Tightening torque Ma NmTerminal Clamping cross-section - mm2
Tightening torque Ma NmTerminal Clamping cross-section - mm2
Tightening torque Ma NmTerminal Clamping cross-section - mm2
Tightening torque Ma Nm
Front side Operational state - -Device fitted Front cover open - -
Ambient temperature 2) Tu °CRated operating mode - - Actuation - -Mounting position - -Altitude - mPollution degree - -Overvoltage category - -
DC440 DC440100 200100 200
- -- -
AC 1000 AC 100025 25- -
DC-21B DC-21B150 375150 375
8 8300 15019 45
B1 B2100 20010 23
1700 10004.5 6.75370 37010 10
M8 M101 x 10 - 95 1 x 25 - 150; 2 x 25 - 70
24 x 5 30 x 1010 15- -
- -
- -
- -
IP40 IP40IP20 IP20
-25 to +55 -25 to +55Continuous operation Continuous operation
Independent manual operation Independent manual operationHorizontal4), vertical5) Horizontal4), vertical5)
Up to 2000 Up to 20003 3III III
2-46
Typ Sasil B1-2 Typ Sasil B2-2Type SASIL B4-2 SASIL B6-2Technical data for switch-disconnector-fuse (SASIL), BS bolted fuse system (in accordance with IEC/EN 60947-3)
Electricalcharacteristics
Fuse-links
Mechanicalcharacteristics
Cableconnection
Type ofprotection
Operatingconditions
Rated operational voltage Ue VRated operational current Ie AConventional free air thermal current with fuses Ith AConventional free air thermal current with solid links Ith ARated frequency - HzRated insulation voltage Ui VRated conditional short-circuit current - kAeff
Rated short-time withstand current (1sec) Icw kAeff
Utilization category - -Rated making capacity - ARated breaking capacity - ARated impulse withstand voltage Uimp kVOperating cycles with current - -Total power loss at Ith (without fuse) Pv W
Size to BS88-1 - -Max. rated current IN AMax. permis. power loss per fuse-link Pv W
Operating cycles without current - -Weight 1) - kgBusbar distance - mmBusbar thickness3) - mm
Flat terminal Bolt diameter - - Cable lug (DIN 46 235) - mm2
Flat bar - mmTightening torque Ma Nm
Terminal Clamping cross-section - mm2
Tightening torque Ma NmTerminal Clamping cross-section - mm2
Tightening torque Ma NmTerminal Clamping cross-section - mm2
Tightening torque Ma NmTerminal Clamping cross-section - mm2
Tightening torque Ma Nm
Front side Operational state - -Device fitted Front cover open - -
Ambient temperature 2) Tu °CRated operating mode - - Actuation - -Mounting position - -Altitude - mPollution degree - -Overvoltage category - -
DC440 DC440400 630400 630
- -- -
AC 1000 AC 100025 25- -
DC-21B DC-21B600 945600 945
8 8200 20084 180
B4 B6400 60034 48
1000 100012.4 12.9370 37010 10
M12 M121 x 35 - 300; 2 x 35 - 240 1 x 35 - 300; 2 x 35 - 240
40 x 10 40 x 1030 30- -
- -
- -
- -
IP40 IP40IP20 IP20
-25 to +55 -25 to +55Continuous operation Continuous operation
Independent manual operation Independent manual operationHorizontal4), vertical5) Horizontal4), vertical5)
Up to 2000 Up to 20003 3III III
1)Without packaging2)35°C normal temperature, at 55°C with reduced operating current3)Upright busbar4)Cable connection right5)Cable connection bottom
2-47
Switch-dis-
connector-fuses
(SASIL) LV HRCsystem
Switch-
disconnector
fuses (SASIL)
BS system
Switch-
disconnector(SALIT)
LV
HRC strip-
fuseways
LV HRC
strip-type
fuse switch-
disconnectors
LV HRCfuse-
bases
LV HRC
fuse switch-
disconnectors
C|O|S|M|O®-
60mm Busbar
System
Current
transformers
Consumer
supply technology
Distribution
and instrument
cabinets
Powerlizer
system electronics
Switch-disconnec-
tor-fuses (SASIT)
DIN and BS
systems
Terminals
Appendix
Type SASIL A1 SASIL BX
Technical data for fuse switch-disconnector-fuse (SASIL), BS bolted fuse system (in accordance with IEC/EN 60947-3)
1)Without packaging2)35°C normal temperature, at 55°C with reduced operating current3)Upright busbar4)Cable connection right5)Cable connection bottom
Electricalcharacteristics
Fuse-links
Mechanicalcharacteristics
Cableconnection
Type ofprotection
Operatingconditions
Rated operational voltage Ue VRated operational current Ie AConventional free air thermal current with fuses Ith AConventional free air thermal current with solid links Ith ARated frequency - HzRated insulation voltage Ui VRated conditional short-circuit current - kAeff
Rated short-time withstand current (1sec) Icw kAeff
Utilization category - -Rated making capacity - ARated breaking capacity - ARated impulse withstand voltage Uimp kVOperating cycles with current - -Total power loss at Ith (without fuse) Pv W
Size to BS88-1 - -Max. rated current IN AMax. permis. power loss per fuse-link Pv W
Operating cycles without current - -Weight 1) - kgBusbar distance - mmBusbar thickness3) - mm
Flat terminal Bolt diameter - - Cable lug (DIN 46 235) - mm2
Flat bar - mmTightening torque Ma Nm
Terminal Clamping cross-section - mm2
Tightening torque Ma NmTerminal Clamping cross-section - mm2
Tightening torque Ma NmTerminal Clamping cross-section - mm2
Tightening torque Ma NmTerminal Clamping cross-section - mm2
Tightening torque Ma Nm
Front side Operational state - -Device fitted Front cover open - -
Ambient temperature 2) Tu °CRated operating mode - - Actuation - -Mounting position - -Altitude - mPollution degree - -Overvoltage category - -
AC500 AC690 AC500 AC69063 63 125 10063 63 125 100- - - -
40 - 60 40 - 60 40 - 60 40 - 60AC 1000 AC 1000
50 80 50 80- - - -
AC-23B AC-23B AC-23B AC-23B1600 1000 1600 10001280 800 1280 800
8 8 8 8300 300 300 30048 19 48 19
A1 Bx563A 125A12 12
1700 17004.85 4.85185 18510 10
M8 M81x10 - 95 1x10 - 95
24x5 24x510 10- -
- -
- -
- -
IP40 IP40IP20 IP20
- 25 bis + 55 - 25 bis + 55Continuous operation Continuous operation
Independent manual operation Independent manual operationHorizontal4), vertical5) Horizontal4), vertical5)
Up to 2000 Up to 20003 3III III
2-48
Type SASIL B1 SASIL B2
Technical data for fuse switch-disconnector-fuse (SASIL), BS bolted fuse system (in accordance with IEC/EN 60947-3)
1)Without packaging2)35°C normal temperature, at 55°C with reduced operating current3)Upright busbar4)Cable connection right5)Cable connection bottom
Electricalcharacteristics
Fuse-links
Mechanicalcharacteristics
Cableconnection
Type ofprotection
Operatingconditions
Rated operational voltage Ue VRated operational current Ie AConventional free air thermal current with fuses Ith AConventional free air thermal current with solid links Ith ARated frequency - HzRated insulation voltage Ui VRated conditional short-circuit current - kAeff
Rated short-time withstand current (1sec) Icw kAeff
Utilization category - -Rated making capacity - ARated breaking capacity - ARated impulse withstand voltage Uimp kVOperating cycles with current - -Total power loss at Ith (without fuse) Pv W
Size to BS88-1 - -Max. rated current IN AMax. permis. power loss per fuse-link Pv W
Operating cycles without current - -Weight 1) - kgBusbar distance - mmBusbar thickness3) - mm
Flat terminal Bolt diameter - - Cable lug (DIN 46 235) - mm2
Flat bar - mmTightening torque Ma Nm
Terminal Clamping cross-section - mm2
Tightening torque Ma NmTerminal Clamping cross-section - mm2
Tightening torque Ma NmTerminal Clamping cross-section - mm2
Tightening torque Ma NmTerminal Clamping cross-section - mm2
Tightening torque Ma Nm
Front side Operational state - -Device fitted Front cover open - -
Ambient temperature 2) Tu °CRated operating mode - - Actuation - -Mounting position - -Altitude - mPollution degree - -Overvoltage category - -
AC690 AC690100 200100 200
- -40 -60 40 -60
AC 1000 AC 100080 50- -
AC-23B AC-23B1000 1600800 1200
8 8300 15019 45
B1 B2100 20010 23
1700 10004.75 8.1185 18510 10
M8 M101 x 10 - 95 1 x 25 - 150; 2 x 25 - 70
24 x 5 30 x 1010 15- -
- -
- -
- -
IP40 IP40IP20 IP20
-25 to +55 -25 to +55Continuous operation Continuous operation
Independent manual operation Independent manual operationHorizontal4), vertical5) Horizontal4), vertical5)
Up to 2000 Up to 20003 3III III
2-49
Switch-dis-
connector-fuses
(SASIL) LV HRCsystem
Switch-
disconnector
fuses (SASIL)
BS system
Switch-
disconnector(SALIT)
LV
HRC strip-
fuseways
LV HRC
strip-type
fuse switch-
disconnectors
LV HRCfuse-
bases
LV HRC
fuse switch-
disconnectors
C|O|S|M|O®-
60mm Busbar
System
Current
transformers
Consumer
supply technology
Distribution
and instrument
cabinets
Powerlizer
system electronics
Switch-disconnec-
tor-fuses (SASIT)
DIN and BS
systems
Terminals
Appendix
Type SASIL B4 SASIL B6
Technical data for switch-disconnector-fuse (SASIL), BS bolted fuse system (in accordance with IEC/EN 60947-3)
Electricalcharacteristics
Fuse-links
Mechanicalcharacteristics
Cableconnection
Type ofprotection
Operatingconditions
Rated operational voltage Ue VRated operational current Ie AConventional free air thermal current with fuses Ith AConventional free air thermal current with solid links Ith ARated frequency - HzRated insulation voltage Ui VRated conditional short-circuit current - kAeff
Rated short-time withstand current (1sec) Icw kAeff
Utilization category - -Rated making capacity - ARated breaking capacity - ARated impulse withstand voltage Uimp kVOperating cycles with current - -Total power loss at Ith (without fuse) Pv W
Size to BS88-1 - -Max. rated current IN AMax. permis. power loss per fuse-link Pv W
Operating cycles without current - -Weight 1) - kgBusbar distance - mmBusbar thickness3) - mm
Flat terminal Bolt diameter - - Cable lug (DIN 46 235) - mm2
Flat bar - mmTightening torque Ma Nm
Terminal Clamping cross-section - mm2
Tightening torque Ma NmTerminal Clamping cross-section - mm2
Tightening torque Ma NmTerminal Clamping cross-section - mm2
Tightening torque Ma NmTerminal Clamping cross-section - mm2
Tightening torque Ma Nm
Front side Operational state - -Device fitted Front cover open - -
Ambient temperature 2) Tu °CRated operating mode - - Actuation - -Mounting position - -Altitude - mPollution degree - -Overvoltage category - -
Rated operational voltage Ue VRated operational current Ie AConventional free air thermal current with fuses Ith AConventional free air thermal current with solid links Ith ARated frequency - HzRated insulation voltage Ui VRated conditional short-circuit current - kAeff
Rated short-time withstand current (1sec) Icw kAeff
Utilization category - -Rated making capacity - ARated breaking capacity - ARated impulse withstand voltage Uimp kVOperating cycles with current - -Total power loss at Ith (without fuse) Pv W
Size to BS88-1 - -Max. rated current IN AMax. permis. power loss per fuse-link Pv W
Operating cycles without current - -Weight 1) - kgBusbar distance - mmBusbar thickness3) - mm
Flat terminal Bolt diameter - - Cable lug (DIN 46 235) - mm2
Flat bar - mmTightening torque Ma Nm
Terminal Clamping cross-section - mm2
Tightening torque Ma NmTerminal Clamping cross-section - mm2
Tightening torque Ma NmTerminal Clamping cross-section - mm2
Tightening torque Ma NmTerminal Clamping cross-section - mm2
Tightening torque Ma Nm
Front side Operational state - -Device fitted Front cover open - -
Ambient temperature 2) Tu °CRated operating mode - - Actuation - -Mounting position - -Altitude - mPollution degree - -Overvoltage category - -
Rated operational voltage Ue VRated operational current Ie AConventional free air thermal current with fuses Ith AConventional free air thermal current with solid links Ith ARated frequency - HzRated insulation voltage Ui VRated conditional short-circuit current - kAeff
Rated short-time withstand current (1sec) Icw kAeff
Utilization category - -Rated making capacity - ARated breaking capacity - ARated impulse withstand voltage Uimp kVOperating cycles with current - -Total power loss at Ith (without fuse) Pv W
Size to BS88-1 - -Max. rated current IN AMax. permis. power loss per fuse-link Pv W
Operating cycles without current - -Weight 1) - kgBusbar distance - mmBusbar thickness3) - mm
Flat terminal Bolt diameter - - Cable lug (DIN 46 235) - mm2
Flat bar - mmTightening torque Ma Nm
Terminal Clamping cross-section - mm2
Tightening torque Ma NmTerminal Clamping cross-section - mm2
Tightening torque Ma NmTerminal Clamping cross-section - mm2
Tightening torque Ma NmTerminal Clamping cross-section - mm2
Tightening torque Ma Nm
Front side Operational state - -Device fitted Front cover open - -
Ambient temperature 2) Tu °CRated operating mode - - Actuation - -Mounting position - -Altitude - mPollution degree - -Overvoltage category - -
AC690 AC690400 630400 630
- -40 -60 40 -60
AC 1000 AC 100080 80- -
AC-23B AC-23B2520 40001890 3000
8 8200 200126 270
B4 B6400 63034 48
1000 100015.5 16.5185 18510 10
M12 M121 x 35 - 300; 2 x 35 - 240 1 x 35 - 300; 2 x 35 - 240
40 x 10 40 x 1030 30- -
- -
- -
- -
IP40 IP40IP20 IP20
-25 to +55 -25 to +55Continuous operation Continuous operation
Independent manual operation Independent manual operationHorizontal4), vertical5) Horizontal4), vertical5)
Up to 2000 Up to 20003 3III III
1)Without packaging2)35°C normal temperature, at 55°C with reduced operating current3)Upright busbar4)Cable connection right5)Cable connection bottom