30
Total Price 1 Custom Duty Taxes and Duties Foreign Currency CIF Foreign Currency Local Currency Local Currency 1 2 3 5 6 7=4X6 8 9 (I) SWITCHYARD PART A Supply and Erection of 220kV Switch Yard Equipments (as per respective Technical Specifications and relevant special conditions ) suitable for 2 Bus system 1 220 KV Indoor GIS Equipment (Separate Enclosure for Each Phase shall be considered) 1.1 3- Ø 220 kV, 2000 A, 40 kA-3 sec, metal enclosed SF6 Gas Insulated Switchgear - Line bay Module comprising Sets 6 Circuit breaker Current transformer 1500-1200-600/1A ( no. of cores as per TS) -1 no for each phase Line side Disconnector with one maintenance earthing switch High speed/Fast Acting Line Earthing switch Bus Disconnector with Earthing switch (Bus side common earthing switch for two bus) Bus Disconnector without Earthing switch SF6 Gas Insulated Bus Duct (GIB) from respective GIS bay module up to SF6 to Air insulated polymer housed bushings including required support structures and other accessories LCC Panel All other items as per technical specification 1.2 3- Ø 220 kV, 4000 A, 40 kA-3 sec, metal enclosed SF6 Gas Insulated Switchgear - Bus bar Module comprising Sets 2 3 X Single phase Voltage transformer 220KV/ SQRT 3//110V/ SQRT 3 -( no. of cores as per TS) sagrigated from bus bar unit High speed/Fast Acting Earthing switch Bus Disconnector with Earthing switch All other items as per technical specification 1.3 3- Ø 220 kV, 2000 A, 40 kA-3 sec, metal enclosed SF6 Gas Insulated Switchgear - Bus Coupler bay Module comprising Set 1 Circuit breaker Current transformer 1500-1200-600/1A ( no. of cores as per TS) -1 no for each phase Bus Disconnector with one Earthing switch -2 nos. LCC Panel All other items as per technical specification 1.4 3- Ø 220 kV, 2000 A, 40 kA-3 sec, metal enclosed SF6 Gas Insulated Switchgear - 220/132 KV Transformer bay Module comprising Sets 2 SWITCHYARD BOQ FOR 220/132/66kV Wankaner GIS Schedule No. 1 Plant and Mandatory Spare Parts Supplied from Abroad Country of Origin Sr. No. 4 Unit of Measurement Quantity Unit Price 1 Particulars of Item

SWITCHYARD BOQ FOR 220/132/66kV Wankaner GIS Office/0-2016/3… · Supply and Erection of 132kV Switch Yard Material as per respective Technical Specifications and relevant special

  • Upload
    others

  • View
    98

  • Download
    4

Embed Size (px)

Citation preview

Total Price1 Custom Duty

Taxes and Duties

Foreign Currency CIF Foreign

CurrencyLocal

CurrencyLocal

Currency1 2 3 5 6 7=4X6 8 9(I) SWITCHYARD PART

A

Supply and Erection of 220kV Switch Yard Equipments (as per respective Technical Specifications and relevant special conditions ) suitable for 2 Bus system

1220 KV Indoor GIS Equipment (Separate Enclosure for Each Phase shall be considered)

1.1 3- Ø 220 kV, 2000 A, 40 kA-3 sec, metal enclosed SF6 Gas Insulated Switchgear - Line bay Module comprising Sets 6Circuit breakerCurrent transformer 1500-1200-600/1A ( no. of cores as per TS) -1 no for each phase Line side Disconnector with one maintenance earthing switchHigh speed/Fast Acting Line Earthing switch Bus Disconnector with Earthing switch (Bus side common earthing switch for two bus)Bus Disconnector without Earthing switchSF6 Gas Insulated Bus Duct (GIB) from respective GIS bay module up to SF6 to Air insulated polymer housed bushings including required support structures and other accessoriesLCC Panel All other items as per technical specification

1.2 3- Ø 220 kV, 4000 A, 40 kA-3 sec, metal enclosed SF6 Gas Insulated Switchgear - Bus bar Module comprising Sets 23 X Single phase Voltage transformer 220KV/ SQRT 3//110V/ SQRT 3 -( no. of cores as per TS) sagrigated from bus bar unit High speed/Fast Acting Earthing switch

Bus Disconnector with Earthing switch All other items as per technical specification

1.3 3- Ø 220 kV, 2000 A, 40 kA-3 sec, metal enclosed SF6 Gas Insulated Switchgear - Bus Coupler bay Module comprising Set 1Circuit breakerCurrent transformer 1500-1200-600/1A ( no. of cores as per TS) -1 no for each phase Bus Disconnector with one Earthing switch -2 nos.LCC Panel All other items as per technical specification

1.4 3- Ø 220 kV, 2000 A, 40 kA-3 sec, metal enclosed SF6 Gas Insulated Switchgear - 220/132 KV Transformer bay Module comprising Sets 2

SWITCHYARD BOQ FOR 220/132/66kV Wankaner GIS Schedule No. 1 Plant and Mandatory Spare Parts Supplied from Abroad

Country of Origin

Sr. No.

4

Unit of Measurement Quantity

Unit Price1

Particulars of Item

Total Price1 Custom Duty

Taxes and Duties

SWITCHYARD BOQ FOR 220/132/66kV Wankaner GIS Schedule No. 1 Plant and Mandatory Spare Parts Supplied from Abroad

Country of Origin

Sr. No.

Unit of Measurement Quantity

Unit Price1

Particulars of ItemCircuit breaker Current transformer 1500-1200-600/1A ( no. of cores as per TS)-1 no for each phase Transformer side Disconnector with one maintenance earthing switch Bus Disconnector with Earthing switch (Bus side common earthing switch for two bus)Bus Disconnector without Earthing switchSF6 Gas Insulated Bus Duct (GIB) from respective GIS bay module up to SF6 to Air insulated polymer housed bushings including required support structures and other accessoriesLCC Panel All other items as per technical specification

1.5 3- Ø 220 kV, 2000 A, 40 kA-3 sec, metal enclosed SF6 Gas Insulated Switchgear - 220/66 KV Transformer bay Module comprising Sets 3Circuit breaker Current transformer 1500-1200-600/1A ( no. of cores as per TS)-1 no for each phase Transformer side Disconnector with one maintenance earthing switch Bus Disconnector with Earthing switch (Bus side common earthing switch for two bus)Bus Disconnector without Earthing switchSF6 Gas Insulated Bus Duct (GIB) from respective GIS bay module up to SF6 to Air insulated polymer housed bushings including required support structures and other accessoriesLCC Panel All other items as per technical specification

2 220KV Outdoor Equipment

2.1 Polymer housed Surge Arrester 198kV, 10kA, Cl-3 with structure and clamp connectors Nos. 33

2.2 220kV Bus Post polymer housed Insulator with structure and clamp connectors Nos. 12

2.3 220kV High Bus Post polymer housed Insulator with structure and clamp connectors Nos. 15

2.4 220kV SF6 to Air insulated polymer housed bushing 1- Phase with structure and clamp connectors Nos. 33

BSupply and Erection of Material for 220kV Switch Yard (as per respective Technical Specifications and relevant special conditions ) suitable for 2 Bus scheme.

1 Gantry structures GI as per BOM, Steel & A/B part MT 462 Gantry structures GI as per BOM, Bolt nut part MT 2.6

Total Price1 Custom Duty

Taxes and Duties

SWITCHYARD BOQ FOR 220/132/66kV Wankaner GIS Schedule No. 1 Plant and Mandatory Spare Parts Supplied from Abroad

Country of Origin

Sr. No.

Unit of Measurement Quantity

Unit Price1

Particulars of ItemNote: The weight of structure may vary as per actual weight of double tier ganty.

3 Lighting Mast structure - Steel & A/B part MT 13.53Lighting Mast structure - Bolt nut part MT 0.54Note: The weight of LM structure may vary as per actual requirement of LMs.

4

Stringing of Flyover bus with Following Conductor for all the three phases with required Silicon Rubber Insulators, hardwares & accessories, spacers provided at every 5.0 mtr. interval (Suitable for 350mm spacing)etc. complete as per relevant standards and approved drawings with Jumpers for continuous Bus Arrangement.

4.1-B Break Up of Supply Items for Erection of above workAL59(61/3.50) Conductor Rmtr. 360Silicon Rubber Insulator string-120KN No. 48Double Tension H/W & Acc with Turn Buckle suitable for Twin AL59(61/3.50) cond. & 120kN SRI No. 12

Double Tension H/W & Acc without Turn Buckle suitable for Twin AL59(61/3.50) cond. & 120kN SRI No. 12

Spacers suitable for Twin AL59(61/3.50) Cond. (350mm Spacing) No. 36

5

Droppers (including required suspension string with hardware & accessories, if any) & Jumpers (including Equipment to Equipment) with Following conductor as per standards and approved drawings with provision of required spacers (Suitable for 350mm spacing) at every 5.0 mtr. interval.

5.1-B Break Up of Supply Items for Erection of above workAL59(61/3.50) Conductor RMtr 1080Silicon Rubber Insulator string-120KN No. 27Single Suspension H/W & Acc. Twin AL59(61/3.50) Cond. No. 27Spacers suitable for Twin AL59(61/3.50) Cond.(350mm Spacing) No. 108Fire Wedge Connectors suitable for AL59(61/3.50) Conductor to AL59(61/3.50) conductor No. 36

5.2-B Break Up of Supply Items for Erection of above workAL59(61/3.50) Conductor RMtr 540Fire Wedge Connectors suitable for AL59(61/3.50) Conductor to Line conductor No. 30

C

Supply and Erection of 132kV Switch Yard Equipments as per respective Technical Specifications and relevant special conditions suitable for Single Main bus Scheme with Twin AL59(61/3.50) and relevant flyover bus with Twin AL59(61/3.50) conductor

1Surge Arrester 120kV, 10kA, Class 3 with str and clamp connectors as per Technical spec No. 9

2 PT 132kV/v3-/110V/v3-3C with structure and clamp connectors No. 03 BPI 6kN with str and clamp connectors as per Technical spec No. 144 HBPI 6kN with str and clamp connectors as per Technical spec No. 6

Total Price1 Custom Duty

Taxes and Duties

SWITCHYARD BOQ FOR 220/132/66kV Wankaner GIS Schedule No. 1 Plant and Mandatory Spare Parts Supplied from Abroad

Country of Origin

Sr. No.

Unit of Measurement Quantity

Unit Price1

Particulars of Item5 HDB Isolator with ES 1600A 40kA 3S with str and clamp connectors as

per Technical spec Set 1

6 HDB Isolator without ES 1600A 40kA 3S with str and clamp connectors as per Technical spec Set 5

7 CT 600-300-150/1A, 5C 40kA 3S with str and clamp connectors as per Technical spec No. 3

8 CT 1200-600-300-150/1A, 5C 40kA 3S with str and clamp connectors as per Technical spec No. 6

9 CB 1600A 40kA 3S with str and clamp connectors as per Technical specSet 3

D

Supply and Erection of 132kV Switch Yard Material as per respective Technical Specifications and relevant special conditions suitable for Single Main bus Scheme with Twin AL59(61/3.50) and relevant flyover bus with Twin AL59(61/3.50) conductor

1 Gantry structures GI as per BOM, Steel & A/B part. MT 3.12 Gantry structures GI as per BOM, Bolt nut part. MT 0.2

3

Stringing of Main bus with Following Conductor for all the three phases with required Silicon Rubber Insulators, hardwares & accessories, spacers provided at every 4.0 mtr. interval (Suitable for 350mm spacing)etc. complete as per relevant standards and approved drawings with Jumpers for continuous Bus Arrangement.

3.1-B Break Up of Supply Items for Erection of above workAL59(61/3.50) Conductor Rmtr. 327Silicon Rubber Insulator string-120KN No. 12Double Tension H/W & Acc with Turn Buckle suitable for Twin AL59(61/3.50) cond. & 120kN SRI No. 3

Double Tension H/W & Acc without Turn Buckle suitable for Twin AL59(61/3.50) cond. & 120kN SRI No. 3

Spacers suitable for Twin AL59(61/3.50) Cond. (350mm Spacing) No. 41.00

4

Stringing of Flyover bus with Following Conductor for all the three phases with required Silicon Rubber Insulators, hardwares & accessories, spacers provided at every 4.0 mtr. interval (Suitable for 350mm spacing)etc. complete as per relevant standards and approved drawings with Jumpers for continuous Bus Arrangement.

4.1-B Break Up of Supply Items for Erection of above workAL59(61/3.50) Conductor Rmtr. 189Silicon Rubber Insulator string-120KN No. 12Double Tension H/W & Acc with Turn Buckle suitable for Twin AL59(61/3.50) cond. & 120kN SRI No. 3

Double Tension H/W & Acc without Turn Buckle suitable for Twin AL59(61/3.50) cond. & 120kN SRI No. 3

Spacers suitable for Twin AL59(61/3.50) Cond. (350mm Spacing) No. 24

Total Price1 Custom Duty

Taxes and Duties

SWITCHYARD BOQ FOR 220/132/66kV Wankaner GIS Schedule No. 1 Plant and Mandatory Spare Parts Supplied from Abroad

Country of Origin

Sr. No.

Unit of Measurement Quantity

Unit Price1

Particulars of Item

5

Droppers (including required suspension string with hardware & accessories, if any) & Jumpers (including Equipment to Equipment) with Following conductor as per standards and approved drawings with provision of required spacers (Suitable for 350mm spacing) at every 4.0 mtr. interval.

5.1-B Break Up of Supply Items for Erection of above workAL59(61/3.50) Conductor RMtr 540Silicon Rubber Insulator string-120KN No. 9Single Suspension H/W & Acc. Twin AL59(61/3.50) Cond. No. 9Spacers suitable for Twin AL59(61/3.50) Cond.(350mm Spacing) No. 68Fire Wedge Connectors suitable for AL59(61/3.50) Conductor to AL59(61/3.50) conductor No. 30

5.2-B Break Up of Supply Items for Erection of above workAL59(61/3.50) Conductor RMtr 120Fire Wedge Connectors suitable for AL59(61/3.50) Conductor to Line conductor No. 18

E

Supply and Erection of 66 kV Switch Yard Equipments (as per respective Technical Specifications and relevant special conditions ) suitable for 2 Bus system

1 66 KV GIS Indoor Equipment

1.1 3- Ø 66 kV, 1600 A, 25 kA-3 sec, metal enclosed SF6 Gas Insulated Switchgear - Line bay Module comprising Sets 5Surge Arrester 60kV, 10kA, Class 3 suitable for connection of 66kV Power Cable-1 no for each phase Circuit breakerCurrent transformer 600-300/1A ( no. of cores as per TS)Line side Disconnector with one maintenance earthing switch High speed/Fast Acting Line Earthing switch Voltage Transformer, 66KV/√3//110V/√3, 3 CBus Disconnector with Earthing switch (Bus side common earthing switch for two bus)Bus Disconnector without Earthing SwitchLCC Panel All other items as per technical specification

1.2 3- Ø 66 kV, 2000 A, 25 kA-3 sec, metal enclosed SF6 Gas Insulated Switchgear - Bus bar Module comprising Sets 23 X Single phase Voltage transformer 66KV/ SQRT 3//110V/ SQRT 3 -sagrigated from bus bar unit High speed/Fast Acting Earthing switch

Bus Disconnector with Earthing switch All other items as per technical specification

1.3 3- Ø 66 kV, 1600 A, 25 kA-3 sec, metal enclosed SF6 Gas Insulated Switchgear - Bus Coupler bay Module comprising Set 1

Total Price1 Custom Duty

Taxes and Duties

SWITCHYARD BOQ FOR 220/132/66kV Wankaner GIS Schedule No. 1 Plant and Mandatory Spare Parts Supplied from Abroad

Country of Origin

Sr. No.

Unit of Measurement Quantity

Unit Price1

Particulars of ItemCircuit breaker Current transformer 1500-1200/1 ( no. of cores as per TS)Bus Disconnector with one Earthing switch -2 nos.LCC Panel All other items as per technical specification

1.4 3- Ø 66 kV, 1600 A, 25 kA-3 sec, metal enclosed SF6 Gas Insulated Switchgear - 220/66 KV Transformer bay Module comprising Sets 3Surge Arrester 60kV, 10KA, Class 3 suitable for connection of 66kV Power Cable -1 no for each phase Circuit breakerCurrent transformer 1500-1200/1A ( no. of cores as per TS) Transformer side Disconnector with one maintenance earthing switch Bus Disconnector with Earthing switch (Bus side common earthing switch for two bus)Bus Disconnector without Earthing SwitchLCC Panel All other items as per technical specification

1.5 3- Ø 66 kV, 1600 A, 25 kA-3 sec, metal enclosed SF6 Gas Insulated Switchgear - Interconnecting Line bay Module comprising Sets 2Surge Arrester 60kV, 10kA, Class 3 suitable for connection of 66kV Power Cable-1 no for each phase Circuit breakerCurrent transformer 1500-1200/1A ( no. of cores as per TS)Line side Disconnector with one maintenance earthing switch High speed/Fast Acting Line Earthing switch Voltage Transformer, 66KV/√3//110V/√3, 3 CBus Disconnector with Earthing switch (Bus side common earthing switch for two bus)Bus Disconnector without Earthing SwitchLCC Panel All other items as per technical specification

266kV High Bus Post Insulator with structure and clamp connectors suitable for connection of 66kV Power Cable and Single/Twin AL59(61/3.50) Cond. Nos. 9

FSupply and Erection of 66kV Switch Yard Equipments as per respective technical specifications and relevant special conditions suitable for One Main Bus with Twin AL59(61/3.50) conductor scheme

Total Price1 Custom Duty

Taxes and Duties

SWITCHYARD BOQ FOR 220/132/66kV Wankaner GIS Schedule No. 1 Plant and Mandatory Spare Parts Supplied from Abroad

Country of Origin

Sr. No.

Unit of Measurement Quantity

Unit Price1

Particulars of Item1 Surge Arrester 60kV, 10KA, Class 3 with structure and clamp connectors

suitable for Twin AL59(61/3.50) Cond. No. 6

2 BPI 4kN with structure and clamp connectors suitable for Twin AL59(61/3.50) Cond. No. 6

3 HDB Isolator with ES 2000 A 25kA 3s with structure and clamp connectors suitable for Twin AL59(61/3.50) Cond. Set. 2

4 HDB Isolator without ES 2000 A 25kA 3s with structure and clamp connectors suitable for Twin AL59(61/3.50) Cond. Set. 2

5 CT 1600-1200-600 /1 3C 31.5KA 3S with structure and clamp connectors suitable for Twin AL59(61/3.50) Cond. No. 6

6 CB 1600A 25kA 3S with structure and clamp connectors suitable for Twin AL59(61/3.50) Cond. Set. 2

GSupply and Erection of 66kV Switch Yard Materials as per respective technical specifications and relevant special conditions suitable for One Main Bus with Twin AL59(61/3.50) conductor scheme

1

Stringing of Flyover bus with Following Conductor for all the three phases with required Silicon Rubber Insulators, hardwares & accessories, spacers provided at every 4.0 mtr. interval (Suitable for 350mm spacing)etc. complete as per relevant standards and approved drawings with Jumpers for continuous Bus Arrangement.

1.1-B Break Up of Supply Items for Erection of above workAL59(61/3.50) Conductor Rmtr. 203.4Silicon Rubber Insulator string-120KN No. 12Double Tension H/W & Acc with Turn Buckle suitable for Twin AL59(61/3.50) cond. & 120kN SRI No. 3

Double Tension H/W & Acc without Turn Buckle suitable for Twin AL59(61/3.50) cond. & 120kN SRI No. 3

Spacers suitable for Twin AL59(61/3.50) Cond. (350mm Spacing) No. 25Fire Wedge Connectors suitable for AL59(61/3.50) Conductor to Existing Bus conductor No. 12

2

Droppers (including required suspension string with hardware & accessories, if any) & Jumpers (including Equipment to Equipment) with Following conductor as per standards and approved drawings with provision of required spacers (Suitable for 350mm spacing) at every 5.0 mtr. interval.

2.1-B Break Up of Supply Items for Erection of above workAL59(61/3.50) Conductor RMtr 360Spacers suitable for Twin AL59(61/3.50) Cond.(350mm Spacing) No. 30Fire Wedge Connectors suitable for AL59(61/3.50) Conductor to AL59(61/3.50) conductor No. 30

Total Price1 Custom Duty

Taxes and Duties

SWITCHYARD BOQ FOR 220/132/66kV Wankaner GIS Schedule No. 1 Plant and Mandatory Spare Parts Supplied from Abroad

Country of Origin

Sr. No.

Unit of Measurement Quantity

Unit Price1

Particulars of Item

H

Supply and Laying of (6+1) X 630sq.mm 66kv Aluminium XLPE power cable with end termination kit and three phase earth link without SVL in ground as per approved drawings with providing and fixing of brick and sand layer covering the cable in any type of soil & Terminal connection, clamp & connectors, support structure arrangement for satisfactory functioning Including required terminations. Job includes excavation of all type of soils, Backfilling and necessary civil work. Rmtr. 0

ITesting & Maintenance Equipment shall be provided as per Annexure-B as below Testing & Maintenance Equipment for GIS

1Gas filling and Evacuating Plant for GIS as per - DILO make (Model 3-001-4-R002)

set 1

2

Gas Recovery unit, DILO make (Model B057R17) with required accessories namely Pressure tank storage capacity 70Kg, Rubber Hose and packing with heat treatment

set 1

3 Dew point measurement meter- DILO Make (Model 3-035-R020) set 14 SF6 gas leakage detector - DILO Make (Model 3-033-R002) set 1

5Computer set with UPS dust cover etc as per technical specifications ( for officer in charge)

set 1

6 A-4 size mono laser printer as per technical specifications.( for officer In charge)

set 1

7 Earth Resistance Tester Digital GE-OHM C make Model no EN 61557/VDE 0413 or updated version with better features.

No 1

8Insulation Resistance Tester (Test volt upto 5kV, Range 100kohm to 10 Tohm), Megger Make, Model-S1568

No 1

9LCM Kit (Range :Total leakage current- 200µA to 9mA, Resistive leakage current- 1µA to 9mA) Make : Doble- LCM 500(Wireless)

No 1

10 Insulation Diagnostic Analyzer, Model: IDAX300 Megger make No 1

11

Measurement system for testing overhead lines and high voltage cables to determine parameters of voltage class upto 400KV namely, Impedence(Z), line angle(Φ), k-factor (k0) and mutual coupling complete with supply cord, accessories like Laptop, software etc.Make: Omicron 1] CPC Line impedance test system with CPC 100, CP CU1,CP GB1 with cables. 2] CP Sequence test card with different states.

No 1

12 Clip on meter AC/DC V/I/OHM -0-1000V, 0-25A Meco/Rishabh/ Motwane Make

No 1

13

Motor and manual Operated Oil BDV testing Kit –Megger(OTS 100AF)/BAUR (DTA100C) make with 0-100kV range, auto cut off feature, with standard ball -cup and measuring gauge as per IS.

No 1

14

Hydraulic Platform with Loading Capcity of 350kg. and height of 10m (Firefly Energy Ltd Make,Model-A.N.I.L)/(VANJAX Make, Model-VXLTM-350/11000)

No. 1

Total Price1 Custom Duty

Taxes and Duties

SWITCHYARD BOQ FOR 220/132/66kV Wankaner GIS Schedule No. 1 Plant and Mandatory Spare Parts Supplied from Abroad

Country of Origin

Sr. No.

Unit of Measurement Quantity

Unit Price1

Particulars of Item

15Emergency Power Supply Unit (Make- Aux Power- Wavelength system & solution,Output voltage-220V DC)

No. 1

16Portable hand-held PD measurement kit with all required accessories suitable for GIS- Doble make (Model DFA100)

No. 1

17CB Analyzer with 6-Channel DCRM kit with all required accessories suitable for GIS Model: HiSAC-Ultima –SCOPE make with suitable Laptop

No. 1

18 Tan Delta Kit- Doble Make (Model-M4100)/ Megger (Delta-4000) No. 119 GPS Instrument (Trimble JUNO SA handheld GPS) No. 120 Hydraulic Pallet Truck (Wont Ind Equip.-Type: W-HOPT 25) No. 1

J

EOT Crane of suitable capacity (minimum 5T safe working load) with single hook and double girder arrangement. Contractor shall submit the capacity calculation of the crane. There shall be provision for lifting arrangement of EOT crane for maintenance purpose. However, Contractor shall submit the capacity calculation of the crane considering erection and maintenance of largest GIS component / assembly.

Nos. 1

K Visual Monitoring System (VMS) as per technical specification. (Alongwith local PC monitoring set up, remote end PC monitoring set up shall be in the scope of supply) Lump sum LS

L Online Transformer Intelligent condition monitoring system (OTICM) as per Technical Specification Lump sum LS

M

Ventilation system (for maintaining positive pressure) shall be provided for following building as per Technical Specifications

a) 220 & 66KV GIS Hall Lump sum LS

N Fire Detection and Alarm System as per Technical Specification Lump sum LS

O Dismantling of following items:1) Equipments,Cables,MKs,Panels etc. of 132kV Dhrol Line bay 2) 132kV Bus Span.1 no.3) 66kV Bus Spans. 1 no.4) Transformers, Equipments,Cables,MKs,Panels etc. of 03 Nos. of 132/66kV Transformer bays5) DPs,Gantry Structures,Cables,Earthmat,Fencing or any obstacle creating hurdles in proposed scope of work. 0 0

P Supply and installation of Portable and wheel/trolley mounted fire extinguishers for Control room, 220kV GIS Hall, Relay panel room of GIS Hall,Transformers,Reactors and other Strategic locations as per Technical Specification.1) Dry chemical powder type of 9 Kg. capacity. No. 62) Dry chemical powder type of 25 Kg. capacity. No. 4

Total Price1 Custom Duty

Taxes and Duties

SWITCHYARD BOQ FOR 220/132/66kV Wankaner GIS Schedule No. 1 Plant and Mandatory Spare Parts Supplied from Abroad

Country of Origin

Sr. No.

Unit of Measurement Quantity

Unit Price1

Particulars of Item3) Dry chemical powder type of 50 Kg. capacity. No. 44) Carbon dioxide ( CO2) gas type of capacity 6.5 Kg. capacity No. 95) Carbon dioxide (CO2) gas type of capacity 22.5 Kg. capacity No. 66) Mechanical Foam type of capacity 9 LT. No. 47) Mechanical Foam type of capacity 50 LT. No. 4

Q Supply and installation of Tower/Split Air Conditioner Machine at following Locations.

A) 3 Ton Capacity Split AC (5 star rating and reputed make)1) LCC Room of 220kV GIS Nos. 5

B) 1.5 Ton Capacity Split AC (5 star rating and reputed make)1) Testing Lab Nos. 22) Admin. Offices Nos. 73) Reception cum Waiting Room Nos. 3

C) 3 Ton Capacity Tower AC (3 star rating and reputed make)1) SCADA Control Room Nos. 22) Conference Room Nos. 2

R

Supply and Erection of General purpose equipments and materials as per respective technical specifications and relevant special conditions.

1

Suitable arrangement of 11kv connections(A) from 11 KV Control room of existing Wankaner SS to one no. of 11kV/415V, 500 kVA distribution transformer and (B) from separate 11 KV express feeder to another 11kV/415V, 500 kVA distribution transformer Which comprises of:1) 22 kV outdoor Isolator, 630A, STC: 25 kA – 3 sec.2) 9 KV LAwith support structure, insulated conductor and DP structure with DO fuse, 22kV BPIs arrangement including Dist box suitable to dist transformer. (11KV Power Cable shall be supplied by GETCO, however Laying of cable is in the scope of bidder) Package LS

Total Price1 Custom Duty

Taxes and Duties

SWITCHYARD BOQ FOR 220/132/66kV Wankaner GIS Schedule No. 1 Plant and Mandatory Spare Parts Supplied from Abroad

Country of Origin

Sr. No.

Unit of Measurement Quantity

Unit Price1

Particulars of Item

2

Distribution Transformer 11kV/415V,500 kVA with suitable Dist. Box and its fixing -mounting arrangement as per drg. No. GETCO/E/2S-STD/P-031/LTD R0,Dtd. 11-03-15. Required LT Distribution boxes with LT cable and changeover switch supply is in the scope of bidder. Set 2

3DG set 250 KVA suitable for Outdoor plinth mounting with required panels and accessories as per Technical Specification. Set 1

4Providing major spares and Tools & Tackles as per 'Annexure-A' asbelowNote: Bidder has to quote against the following spares as applicable. Quantities against the spares shall be finalized during detailed Engineering and bidder has to supply the same. If any item not quoted against spares, but required during detailed engineering shall be supplied by the successful bidder at no extra cost to GETCO.

(A) 220 kV Gas Insulated Switchgear Nos. 31 General Nos. 3

1.1 SF6 gas Pressure Relief Devices, 3 Nos. - One each used in Bay Module,CB Module and Bus Bar Module

Set 1

1.2 SF6 Pressure gauge cum switch or density monitors and pressure switch 3 Nos. - One each used in Bay Module,CB Module and Bus Bar Module

Set 1

1.3 “O” Rings or Seals of original material & Size used in Single Phase GIS Module of each type (Bay Module,CB Module and Bus Bar Module)

Nos. 3

1.4 Molecular sieve in tamper,moisture & leak proof packing. Weight of each packing shall be equal to that to be used in GIS Module consists of 3 phase 1 bay

Set 1

1.5 All types of Control Valves for SF6 gas with coupler, 3 Nos. - One each used in Bay Module,CB Module and Bus Bar Module

Set 1

1.6 Covers/Shields with all accessories necessary to close a compartment in case of dismantling of any part of the Enclosure so that system can be pressurised and dielectrically tested for all 3 Phase. ( 3 phase required , one complete bay)

Set 1

1.7 Locking device to keep the Dis-connectors (Isolators) and Earthing switches in close or open position in case of removal of the driving Mechanism for one complete bay.(3 Phase)

Nos. 3

1.8 Each type of Insulator cones which support bus bar used in single bay for line , Transformer & Bus bar module

Set 1

1.9 SF6 to air bushing Set 11.10 Motor of Each type and rating used in CB,Disconnector,HSE and Earth

switch used in 1-phase module1.11 Limit switches and Aux. Switches of each type used in

CB,Disconnector,HSE and Earth switch used in 1-phase module 2.0 For GIS 220 kV Circuit Breaker No. 1

Total Price1 Custom Duty

Taxes and Duties

SWITCHYARD BOQ FOR 220/132/66kV Wankaner GIS Schedule No. 1 Plant and Mandatory Spare Parts Supplied from Abroad

Country of Origin

Sr. No.

Unit of Measurement Quantity

Unit Price1

Particulars of Item 2.1 Complete Circuit Breaker pole with interrupter, main circuit, enclosure

and operating mechanism Nos. 6

2.2 Trip coil assembly used in CB Module (3 Phase) Nos. 32.3 Closing coil assembly used in CB Module (3 Phase) Set 12.4 Relays, Power contactors, push buttons, timers & MCBs etc of each

type & rating provided in LCC of one bay module3 For GIS 220 kV ISOLATORS Nos. 3

3.1 Complete set of single phase dis-connector including main circuit, enclosure, driving mechanism etc.

No. 1

3.2 High speed/Fast acting fault making grounding switch (3 nos of single phase) including main circuit , enclosure and driving mechanism etc.

No. 1

3.3 Single phase Earthing switch including main circuit, enclosure, driving mechanism etc.

4.0 For GIS 220 KV CURRENT TRANSFORMER Set 1 4.1 CTs used in one module - complete for Transformer Bay and Line

Bay/Bus Coupler Bay with enclosure (Single phase requirement) 5.0 For GIS 220kV Potential Transformer No. 1 5.1 Gas Insulated Complete 1-Ph PT (Single phase requirement)6 Spares for E O T crane

6.1 Hoist Motor No. 16.2 C.T. Motor No. 16.3 L.T.Motor No. 16.4 All type of Limit switches used in EOT crane Set 16.5 All type of brakes used in EOT crane Set 1 (B) 66 kV Gas Insulated Switchgear

1 General 1.1 SF6 gas Pressure Relief Devices, 3 Nos. - One each used in Bay

Module,CB Module and Bus Bar ModuleNos. 3

1.2 SF6 Pressure gauge cum switch or density monitors and pressure switch 3 Nos. - One each used in Bay Module,CB Module and Bus Bar Module

Nos. 3

1.3 “O” Rings or Seals of original material & Size used in GIS Module of one bay (Bay Module,CB Module and Bus Bar Module)

Set 1

Total Price1 Custom Duty

Taxes and Duties

SWITCHYARD BOQ FOR 220/132/66kV Wankaner GIS Schedule No. 1 Plant and Mandatory Spare Parts Supplied from Abroad

Country of Origin

Sr. No.

Unit of Measurement Quantity

Unit Price1

Particulars of Item 1.4 Molecular sieve in tamper,moisture & leak proof packing. Weight of each

packing shall be equal to that to be used in GIS Module for 1 baySet 1

1.5 All types of Control Valves for SF6 gas with coupler, 3 Nos. - One each used in Bay Module,CB Module and Bus Bar Module

Nos. 3

1.6 Covers/Shields with all accessories necessary to close a compartment in case of dismantling of any part of the Enclosure so that system can be pressurised and dielectrically tested for one complete bay

Set 1

1.7 Locking device to keep the Dis-connectors (Isolators) and Earthing switches in close or open position in case of removal of the driving Mechanism for one complete bay.

Set 1

1.8 Each type of Insulator cones which support bus bar used for line , Transformer & Bus bar module

Set 1

1.9 Motor of Each type and rating used in CB,Disconnector,HSE and Earth switch used in one complete bay

Set 1

1.10 Limit switches and Aux. Switches of each type used in CB,Disconnector,HSE and Earth switch used in one complete bay

Set 1

2.0 For GIS 66 kV Circuit Breaker 2.1 Complete Circuit Breaker pole with interrupter, main circuit, enclosure

and operating mechanism No. 1

2.2 Trip coil assembly used in CB Module Nos. 22.3 Closing coil assembly used in CB Module Nos. 12.4 Relays, Power contactors, push buttons, timers & MCBs etc of each

type & rating provided in LCC of one bay moduleSet 1

3 For GIS 66 kV ISOLATORS Nos. 1 3.1 Complete set of 3 phase dis-connector including main circuit, enclosure,

driving mechanism etc.for one bayNo. 1

3.2 High speed/Fast acting fault making grounding switch including main circuit , enclosure and driving mechanism etc. for one complete bay.

No. 1

3.3 Three phase Earthing switch including main circuit, enclosure, driving mechanism etc.

4.0 For GIS 66 KV CURRENT TRANSFORMER 4.1 CTs used in one module - complete for Transformer Bay and Line

Bay/Bus Coupler Bay with enclosure Set 1

5.0 For GIS 66kV Potential Transformer 5.1 Gas Insulated Complete 1-Ph PT No. 1 (C) DG set ( portable three phase 415V 10 KVA Honda / Kirlosakar

make) set 1

(D) Welding M/C: Input volt.230-440V(single/two phase), 50Hz, Insulation class A, 200 Amp. With 30 m welding cable

set 1

(E) Tools & Tackles (General) 1 Earthing Rod (Highly insulated FRP telescopic Earthing/ Discharge Rod.

with cable suitable for 400 & 220kV Switchyard- National MakeNos 18

Total Price1 Custom Duty

Taxes and Duties

SWITCHYARD BOQ FOR 220/132/66kV Wankaner GIS Schedule No. 1 Plant and Mandatory Spare Parts Supplied from Abroad

Country of Origin

Sr. No.

Unit of Measurement Quantity

Unit Price1

Particulars of Item 2 Spanner [Ring, Fixed, Box]

Fix=10x11,12x13,14x15,,16x17Ring=10x11,12x13,14x15,16x17 Tubular=12x13,14x15,16x17,18x19 Screw driver=827I,927 Nut driver= 7mm - Taparia/Gedore/Zalani Make

Set 3

3 Steel Roller -Size 1" Nos 10 4 Aluminium Roller -Size 4" Nos 5 5 One/two/three Wheel pulley -Size 1" (Gadore) Nos 2 6 Winch Machine with Handle -05 Ton Capacity Nos 2 7 Hydraulic Press Machine with Dog, panther, zebra & moose dye sets--

100 Ton Capacity ( Hydraulic force ent. / Techno spent )Nos 2

8 Hand drill Wolf Make 240 V Capacity :-Hole up to 31 mm , Single Phase Nos 1

9 Drill Machine -5/8" Dia Wolf Make Standing Drill machine having 3 Feet Pillar & suitable for making Holes up to ¾”. Motor

Nos 2

10 Chain pulley block -5 tonne capacity (Morries) Nos 2 11 Wire rope pulley block -02 Tonne (Morries) Set 1 12 Tent-Standard quality water proof Tent made from H.D.P.E. Materials

with 5 Nos of bamboos Rods and having capacity of 8 to 10 Person to stay & size 10 Ft x 10Ft Multipurpose

Set 1

13 Water pump (Crompton Make) Set -5 HP with hose pipe of 30 m Crompton Make

Nos 2

15 Crowbar -1.5 Mtr Nos 5 16 Crowbar -1.0 Mtr Nos 5 17 Hammer with wooden handle -10Kg Nos 1 18 Pickaxe ( Trikam) -2 '' width with handle Nos 5 19 Pawda[shovel] -12 '' width with handle Nos 5 20 Axe (Kuhadi) with handle Nos 5 21 Sythe (Dharia) with handle Nos 10 22 Tar Poline (Tad Patri) 5X5 m (HDPE), 200 GSM Nos 5 23 Nylon Rope -0.5" Dia -100 mtrs (Garware Make) Bundle 1 24 Nylon Rope 0.75" Dia -100 mtrs (Garware Make) Bundle 1 25 Nylon Rope -1" Dia -100 mtrs (Garware Make) Bundle 1 26 Aluminium Ladder -15 ft. Aluminium folding factory ladder (Heavy duty)

made from high tensile aluminium alloy design no 152 AFFL 15 Ft height (4.56 mtrs) specification section= 15/8” X 1.1/4” Steps= 15/8 X 1.1/4 12”Center to Center

Set 1

27 Telescopic aluminium ladder(3 sections) with platform -25 ft Nos 1 28 Hot air blower (Wolf Make)

Total Price1 Custom Duty

Taxes and Duties

SWITCHYARD BOQ FOR 220/132/66kV Wankaner GIS Schedule No. 1 Plant and Mandatory Spare Parts Supplied from Abroad

Country of Origin

Sr. No.

Unit of Measurement Quantity

Unit Price1

Particulars of Item Small Capacity =1.5m3/min, Nos 1 Big Capacity =2.0m3/min Nos 1

29 Vaccum cleaner -Eureka Forbes Make (Industrial) Nos 1 Safety Tools1 Full body Harness as per technical specification Nos 152 Halmet with ISI mark of reputed make Nos 103 Hand Gloves Hand gloves of quality as per IS certification 4770 & test

potential 7500Volt Pair 6

4 Gum boot (Pair) -Size 8,9,10. -Standard make Pair for each size

3

Display Boards and others 1 Single line diagram drawn with radium paint on a board of approx size of

1200x900 mm with fixing arrangement on control room wall. Set 1

2 Gas Single line diagram drawn with radium paint on a board of approx size of 1200x900 mm with fixing arrangement on wall of 220kV GIS Hall.

Set 1

3 Key board with hook for different keys of each equipments/panels/cubicles with SLD drawn with color approx size 2'x2'

Set 1

5Supply of Furniture, RO Water Filter System, Water Cooler Etc. as per 'Annexure-C' as below Set 1Supply of Furniture, RO Water Filter System, Water Cooler Etc.

1 Furniture for 400/220/66KV S/S a) Cushioned chair of Godrej make no. Ch-1018D NO 15

b) Steel rack of size 30"X36"X15" with three partitions, prepared 20 gauges

NO 2

c) Providing Control Room Table modular 5X5 Panta work surface with pedestal CPU Trolley & Key Board tray of Godrej or equivalent

NO 1

d) Office table with SDU & pedestal 5026 Godrej make NO 4 e) Modular workstations of Godrej make or equivalent 4X2 Panta work surface with pedestal CPU trolley & keyboard Tray or equivalent

NO 2

Total Price1 Custom Duty

Taxes and Duties

SWITCHYARD BOQ FOR 220/132/66kV Wankaner GIS Schedule No. 1 Plant and Mandatory Spare Parts Supplied from Abroad

Country of Origin

Sr. No.

Unit of Measurement Quantity

Unit Price1

Particulars of Item f) Revolving chair PCH -5D02-STAR R-MID BACK NO 40g) Wooden sofa set- 3 seated as per drawing. NO 2g) Wooden sofa set- 2 seated as per drawing. NO 2 h) Conference table of 'Godrej' make of "Encarta conference table' of approved design and make. FOR 25 SEAT.

NO 1

i) providing and fixing laminated table as per design with laminated post formed top, drawers/shutters with facility of lock, key , board tray, wire manger, t.w. foot rest. The same shall be made with 12mm thick ply wood. All exposed edges shall be finished with 1mm thick laminated as approved. Providing and fixing t.w beading upto 25mm size. All t.w surface shall be polished with matching colour malemine polished of 3 coats. all exposed area shall be finished with laminate as per drawing

Sq.meter 40

j) T.W. partition 75mm thick with vinyl polished , soft board , electrical rack way etc complete as per drawing.

Sq.meter 10

k)Providing and fixing laminated reception table with premium black granite top as per detail drg. All edges shall be mirror polished.( 5 feet x 3.5 feet)

Sq.meter 1.75

m) Providing t.w corner/central tepoy as per design with laminated top with 9mm thick bronze glass etc with malemine polish etc complete.(size 2.5 feet x 2.5 feet)

no 2

2 RO water filter system 25Ltr. Capacity Reputed make No. 13 Water Cooler Providing & installing SHRIRAM USHA or equivalent make

water cooler of 40Ltr./hr. capacity suitable to operate on 230V+10% , 50Hz. Single phase AC supply with hermetically sealed type suction cooled compressor with overload protection confirming to IS 106

No. 1

4 42" , Sony or equivalent make flat LCD TV No. 1

6Supply and Erection of Fire stand with 4 buckets including concreting asper our drawing & Instruction of E. I. C. Set 2

7Providing of Insulating Mat (Size2000x1000x2mm) as per Technical Specification No. 200

S

Supply and installation of materials for Illumination system in allrespect as per respective specifications and special conditions(Important Note: Concealed wiring shall be considered for IndoorIllumination)

Total Price1 Custom Duty

Taxes and Duties

SWITCHYARD BOQ FOR 220/132/66kV Wankaner GIS Schedule No. 1 Plant and Mandatory Spare Parts Supplied from Abroad

Country of Origin

Sr. No.

Unit of Measurement Quantity

Unit Price1

Particulars of ItemIndoor Illumination

1

Providing & Fixing of Energy Efficient LED type (Techhnical spec Cl No. 2.10.4.8-I LED 3 type) Indoor decorative luminaries as per design calculation, with respect to required lux level & relevant tender drgs.as per technical spec. Scope also includes providing and fixing of 15/5 A plug, Portable Emergency Light, Bell, Fan, Ex- Fan, DC Point,Occupancy & Light Level Sensor with requisite MCBs and DC 100W lamp , DC Plug etc all items as per Ann-4 in following rooms (with safety device ELCB)

i SCADA Control Room Package LSii Lab Package LSiii Reception Package LSiv Conference Room Package LSv Admin Offices Package LSvi LCC Room Package LSvii Security Officer Cabin Package LS

2

Providing & Fixing of Energy Efficient LED Type (Techhnical spec Cl No. 2.10.4.8-I LED 1 or I LED 2 type) Indoor decorative luminaries as per design calculation, with respect to required lux level & relevant tender drgs.as per technical spec. Scope also includes providing and fixing of 15/5 A plug, Portable Emergency Light, Bell, Fan, Ex- Fan, DC Point, Occupancy & Light Level Sensor with requisite MCBs and DC 100W lamp , DC Plug etc all items as per Ann-4 in following rooms (with safety device ELCB)

i LV Room Package LSii Store Room Package LSiii Ramp Slope Package LSiv Pantry Package LSv Passage (Corridor) Package LSvi Ramp Slopes Package LSvii Veranda Package LSviii WCs Package LSix Toilets Package LS

Total Price1 Custom Duty

Taxes and Duties

SWITCHYARD BOQ FOR 220/132/66kV Wankaner GIS Schedule No. 1 Plant and Mandatory Spare Parts Supplied from Abroad

Country of Origin

Sr. No.

Unit of Measurement Quantity

Unit Price1

Particulars of Itemx AHU Rooms Package LSxi Security Cabin Package LSxii Battery Room Package LS

3

Providing & Fixing of Energy Efficient LED type (Techhnical spec Cl No. 2.10.4.8-I LED4 Type) Indoor decorative luminaries as per design calculation, with respect to required lux level & relevant tender drgs., and required industrial grade point wiring as per technical spec. Scope also includes providing and fixing of 15/5 A plug, Portable Emergency Light, Bell, Fan, Ex- Fan, DC Point,Occupancy & Light Level Sensor with requisite MCBs and DC 100W lamp , DC Plug etc all items as per Ann-4 in following rooms (with safety device ELCB)

i GIS Room Package LS

4

Providing & Fixing of Energy Efficient LED Type (Techhnical spec Cl No. 2.10.4.8-I LED 1 or I LED 2 type) Indoor decorative luminaries as per design calculation, with respect to required lux level & relevant tender drgs.as per technical spec. Scope also includes providing and fixing of 15/5 A plug, Portable Emergency Light, Bell, Fan, Ex- Fan, DC Point, Occupancy & Light Level Sensor with requisite MCBs and DC 100W lamp , DC Plug etc all items as per Ann-4 in following room.

i Store building Package LS

Outdoor Illumination

5

Providing and fixing of flood light luminaries as per design for whole switch yard area (Tender Scope only) with Energy Efficient LED type (Techhnical spec Cl No. 2.10.4.8-I LED 5 Type) Outdoor luminaries as per design calculation, with respect to required lux level & relevant tender drgs., and required industrial grade point wiring as per technical spec.& ancillaries and suitable for mounting on structure at appropriate height as per specifications TS illuminations cl. no 2.10.4.8 with necessary GI fabrication & GI bolt nuts to fix control gear box at the structure with complete internal and external wiring to J. box ,Dist panel/section feeder pillar etc with supply of required 3 c x 2.5 mm2 copper armoured cable (as per spec ) .The scope includes supply and erection of all the materials required for satisfactory functioning of above work. Package LS

Total Price1 Custom Duty

Taxes and Duties

SWITCHYARD BOQ FOR 220/132/66kV Wankaner GIS Schedule No. 1 Plant and Mandatory Spare Parts Supplied from Abroad

Country of Origin

Sr. No.

Unit of Measurement Quantity

Unit Price1

Particulars of Item

6

Providing and installation of Energy efficient LED type post top lantern for main gate and road from main gate to switchyard via control room as per design with Philips/CGL/Bajaj/GE/Oshram make & ancillaries suitable for mounting on Gate pillars and 4.5 mtr poles with necessary GI fabrication & GI bolt nuts to fix control gear box with complete internal and external wiring to J.box,Dist panel/section feeder pillar, fixing terminal etc. with supply of required 3 c x 2.5 mm2 copper armoured cable as per spec .This also includes the supply and erection of required 4.5 mtr poles and its foundation work as per spec and earthing with main mesh. The scope includes supply and erection of all the materials required for satisfactory functioning of above work. Package LS

7

Providing and fixing of street light luminaries for reamaining area (like road, near whole compound wall/fencing area etc.) of switch yard complete as per design with Philips/CGL/Bajaj/GE/Oshram or Similar make LED lamp & ancillaries suitable for mounting on 7.0 mtr swaged poles as per spec.TS illuminations cl. no 2.10.4.8 (S-LED) at appropriate height with necessary GI fabrication & GI bolt nuts to fix control gear box with complete internal and external wiring to J. box ,dist panel/section feeder pillar, fixing terminal etc with supply of required 3 c x 2.5 mm2 copper armoured cable (as per spec). This also includes the supply and erection of 7.0 mtr swaged pole and foundation work as per spec. and panting with two coats of primer and two priming of zinc chromate as well as earthing with main mesh. The scope includes supply and erection of all the materials required for satisfactory functioning of above work.

Package LS

8

Supply and Erection of main lighting Panel ACP-1 as per Specifications. Set comprises minimum 2 nos.of such panels qty may be more if required as per design. Scope also includes the providing and erection of cable (size as per design requirement) and 25x6 GI strip for earthing with main mesh Set 1

Total Price1 Custom Duty

Taxes and Duties

SWITCHYARD BOQ FOR 220/132/66kV Wankaner GIS Schedule No. 1 Plant and Mandatory Spare Parts Supplied from Abroad

Country of Origin

Sr. No.

Unit of Measurement Quantity

Unit Price1

Particulars of Item

9

Supply and Erection of main lighting Panel ACP-2 as per Specifications Set comprises minimum 4 nos.of such panels qty may be more if required as per design. Scope also includes the providing and erection of cable (size as per design requirement) and 25x6 GI strip for earthing with main mesh Set 1

10

Supply and Erection of main lighting Panel ACP-3 as per Specifications Set comprises minimum 4 nos.of such panels qty may be more if required as per design. Scope also includes the providing and erection of cable (size as per design requirement) and 25x6 GI strip for earthing with main mesh Set 1

11

Supply and Erection of main lighting Panel ACP-4 as per Specifications Set comprises minimum 2 nos.of such panels qty may be more if required as per design.Scope also includes the providing and erection of cable (size as per design requirement) and 25x6 GI strip for earthing with main mesh Set 1

12

Supply and Erection of main Yard light Dist. Board as per designed capacity ratings.Scope also includes providing and erection of cable (size as per design requirement) and 50x6 GI strip for earthing with main mesh

Nos 2

13

Supply and Erection of Lighting Transformers as per designed capacity.Scope also includes the providing and erection of 50x6 GI strip for earthing with main mesh. Please refer the drawing "General Schematic for Illumination" in the TS Illumination. Set 1

14

Providing of concreting in 1:2:4 mix including muffing for erection of pole & Dist boxes panels including excavation of HR/SR as per approved drawing. Package LS

Total Price1 Custom Duty

Taxes and Duties

SWITCHYARD BOQ FOR 220/132/66kV Wankaner GIS Schedule No. 1 Plant and Mandatory Spare Parts Supplied from Abroad

Country of Origin

Sr. No.

Unit of Measurement Quantity

Unit Price1

Particulars of Item

15

Providing & fixing of ' B ' Class ISI marked GI pipe of 25 mm inner diameter for cable looping, road crossing with necessary elbow / band to J. Box etc. Package LS

16

Providing and fixing of GI clamp (25mm wide GI strip with 6 mm GI nut bolts) on structure at approx. 1 or 2 Mtr. Interval for clamping of cable. Clamp should be fix in such a way that cable can be easily mount inside it & sustain standing on structure. This also includes required other materials,accessories etc.required for complete functioning of Illumination system of whole project. Please refer the drawing "General Schematic for Illumination" in the TS Illumination. Package LS

T

Supply and installation of materials for Earthing system in allrespect as per respective specifications and special conditions(Successful bidder has to submit the complete design and BOQ forapproval)

1

Supply and Installation of earthing strips/round bars as shown below including digging of 600 mm depth and 450 mm wide trench fixing on structure as per std equipment earthing philosophy including fixing arrangement with two bolt arrangement, jointing, welding etc. complete.a) 75 x 10 mm GI strip. RMt. 7500b) 50 x 6 mm GI strip. RMt. 2000c) 40 mm dia steel rod RMt. 7500d) 40mm dia 3mtr long steel rod Nos. 110

2Providing and installing Check pit as per drawing and instruction of Engineer In charge with provision of earth chamber. Nos. 6

3

Supply, Installation, Testing and Commissioning of maintenance free treated earth electrodes, as per attached drawing no. GETCO/E/P-021 (2 OF 2) R2 dated 04-06-15 and Technical specifications GETCO/E/TS-Maintenance free earth pits /R1 dated 04-06-15. Nos. 100

Note: The quantities of the ACP's mentioned in the schedule of requirement are based on std. requirement, which shall be finalized during detail engineering. The bidder has to assess the qty. of ACP's at the time of quoting the bid. The qty of ACP's finalized during detail engineering is binding to the bidder & no any extra payment shall be made. In all the case the decision of GETCO will be final.

Total Price1 Custom Duty

Taxes and Duties

SWITCHYARD BOQ FOR 220/132/66kV Wankaner GIS Schedule No. 1 Plant and Mandatory Spare Parts Supplied from Abroad

Country of Origin

Sr. No.

Unit of Measurement Quantity

Unit Price1

Particulars of Item

4Providing BB masonry inspection chamber (man hole) incl.light type CI cover as per GETCO drawing no P021 Nos. 100

5 Design of earthgrid for switchyard using computer algorithmsfor modeling grounding systems as per Cl. 16.8 of IEEE-80. Package LS

6Earthing Adequacy study for whole switchyard after commisioning earthmat in all respect (Scope as per annexure-E) Package LS

U

Supply and Erection of Ladder Type Cable Trays and Accessories as per respective Technical Specifications and relevant special conditions.  

Width of tray450mm Rmtr. 150350mm Rmtr. 150

1

2

3

4

5

6

7

Sr No

Description Unit of Measurement Quantity

Note: Cross, Tees, Elbows, Coupler plates, Bends, Reducer etc. required for complete installation of Ladder Type Tray are included in the Scope.Length: Standard length of tray is 2500mm, Height is 75mm, Thickness is 2mm (min.)

Note: Extra earth should be removed away from the site s/s premises or refilling earthing pits if required. All required materials for this job such as Copper Bonded Earthing Steel Rods, CI cover with frame,cement,sand, Ground Enhancement Material, gravel, bricks etc. to be supplied by the contractor.

(II) PLCC PART

Stringing of Earth Wire with 7/3.15 GS wire with required hardwares accessories etc. complete as per standards and approved drawings shall be provided free of cost, if required.

SPECIAL NOTES:

Submission of study report of Very Fast Transient Over Voltage (VFTO) shall be in the scope of bidder.

Successful bidder has to depute his expert to visit site annually for the period of five years from the date of commissioning to inspect GIS for carrying out status evaluation of GIS performance.This is intended to share the operational challenges and confirming the maintenances followed by GETCO.

LCC of 220kV and 66kV GIS shall be front openable. LCC shall be installed in such a way that facing of front side of LCC and GIS module is same. Opposite to LCC panel, C&R panels shall be arranged exactly in line with GIS module. Sufficient maintenance space shall be kept between LCC & C&R panel.

Mounting channels to be grouted in flooring for GIS support shall be designed and verified by GIS OEM only. No local fabrication is allowed for such fixing arrangement.

Supply & Erection of any 220/132kV & 220/66kV Transformers are not in the scope of bidder, but bidder will erect the items other than the scope of transformer manufacturer and witness during the erection and testing of the same and provide all the result in as built drawings/documents.

Lightning cum Lighting Masts shall be provided for GIS Buildings, Switchyard area ,Control room area etc. as per DSLP Calculation. These LMs shall be utilized for Illuminaton of Switchyard also.

Total Price1 Custom Duty

Taxes and Duties

SWITCHYARD BOQ FOR 220/132/66kV Wankaner GIS Schedule No. 1 Plant and Mandatory Spare Parts Supplied from Abroad

Country of Origin

Sr. No.

Unit of Measurement Quantity

Unit Price1

Particulars of Item1 220kV CHI CVT with CC=4400PF (with two windings having VA burden

50 & 50 and having accuracy of 0.2 & 3P class for metering & protection core respectively. The simultaneous burden shall be 100VA at both 0.2/3P accuracy class.The terminal for metering core shall be brought out in separate sealable compartment/box. with HF terminal for PLCC purpose along with supporting structure, Clamps/Connectors. ( For providing connection from CVT HF terminal to MCD-80 the stranded (non flexible strands) PVC insulated copper cable of size 16 sq. mm shall be used.)

No. 6

3 FSK Data Modem Make: ABB & Type: NSK 5 with stand alone 19" rack with power supply module with 220V DC to 48V DC converter , Programmable for both Baud Rate (50 to 2400 Baud) and VFT Channel Centre Frequency

No. 1

4 FSK Data Modem ,Make: ABB & Type: NSK 5, Programmable for both Baud Rate (50 to 2400 Baud) and VFT Channel Centre Frequency No. 0

5 PLCC Exchange of Make: MATRIX, Type Eternity 10S suitable for both PLCC Dialling and Express Communication connectivity with Universal slot architecture and Hot stand by Power supply with 220V DC to 48V DC converter, switch and CPU card having configuration for 16 Nos. of Trunks & 16 Nos. of Subscribers along with Digital Key phones- 2 Nos. & 2 Wire telephone instruments- 8 Nos. of reputed make.

No. 1

DAS Meters network wiring complete up to RS 485 to RS 232 Convertor of DAS PC usinga) 3 core communication cable Mtr. 100b) RS 485 to RS 232 Converter No. 1

7 PC for DAS as per specification No. 1(III) Protection Part

Sr No

Description Unit of Measurement Quantity

V

Supply, Erection, Testing and Commissioning of Protectionequipments and materials as per respective technical specificationsand relevant special conditions and suitable for Single Main Bussystem on 132kV side

1Control & Relay Panels for 132KV Bays ( Control Voltage - 110V DC ) as per tech specifications with following break up1) Control & Relay panel for line Set 13) Control & Relay panel for Transformer without Differential Set 2

2 Integration of new bays (i.e. 3 Nos.) with existing numerical busbar protection scheme Alstom make MiCOM P741/2 in all respect Set 1

PROTECTION BOQ of 220kV Wankaner Sub Station (132kV & 66kV Existing System)

6

Total Price1 Custom Duty

Taxes and Duties

SWITCHYARD BOQ FOR 220/132/66kV Wankaner GIS Schedule No. 1 Plant and Mandatory Spare Parts Supplied from Abroad

Country of Origin

Sr. No.

Unit of Measurement Quantity

Unit Price1

Particulars of Item

W

Supply, Erection, Testing and Commissioning of Protectionequipments and materials as per respective technical specificationsand relevant special conditions and suitable for Single Main Bussystem on 66kV side

1Control & Relay Panels for 66kV bays ( Control Voltage - 110V DC ) as per tech specifications with following break up.2) Control & Relay Panel for Interconnecting bay Set 2

X Supply and installation of materials/item for Power Cable andcontrol Cable wiring including preparation of wiring schedule.

1

Supply and Laying of 1.1 kV PVC armoured copper/Aluminum control/LTpower cable in trench including binding/clamping of cable with PVC locable wire tie as per requirement including supply and fixing ofidentification tags on both ends and at distance of every 100mtr.(Note :- Aluminium cables of size 185 mm2 & above shall be XLPE type) 1) 2c x 2.5 mm2, armoured copper control cable Mtr. 4003) 4cx2.5 mm2, armoured copper control cable Mtr. 5004) 4c x 4 mm2 , armoured copper control cable Mtr. 38005) 7c x 2.5 mm2, armoured copper control cable Mtr. 3006) 12c x 2.5 mm2, armoured copper control cable Mtr. 22507) 12c x 4 mm2, armoured copper control cable Mtr. 2008) 19c x 2.5 mm2 , armoured copper control cable Mtr. 26009) 27c x 2.5 mm2 , armoured copper control cable Mtr. 85011) 4 x 10 mm2 , Al. armoured LT cable Mtr. 10013) 3.5 x 50 mm2 , Al. armoured LT cable Mtr. 300Termination of the control cable at panel / MK box/equipment includingPVC binding dressing/shaping drilling of holes in panels for glands nutsfor following size. The work also includes Looping in panel and MK boxwith using crimping type of lugs of suitable size with ferruling with propersize of copper cable wire. The loops should be bunched with using buttontape and proper shaping etc.1) cables from 2 core to 7 core of 2.5 & 4.0 Sq.mm size No. 1302) cables above 7 core No. 140Laying of 1.1kv PVC/XLPE armored Al. LT power cable in ground bydigging trench of suitable width and 450 mm depth with providing andfixing of brick and sand layer covering the cable in any type of soil andLaying of 1.1kv PVC armored copper control cable in heavy duty PVCpipe of suitable size buried in ground by digging trench of suitable widthand 450 mm depth in any type of soil including supply and fixing of Pipeand identification tags at distance of every 100 Mtrs for following size

1) Control Cables upto 7 core Mtr. 1702) Control Cables above 7 core and all LT cables Mtr. 230

2

3

Total Price1 Custom Duty

Taxes and Duties

SWITCHYARD BOQ FOR 220/132/66kV Wankaner GIS Schedule No. 1 Plant and Mandatory Spare Parts Supplied from Abroad

Country of Origin

Sr. No.

Unit of Measurement Quantity

Unit Price1

Particulars of ItemProviding and fixing of 50mm dia 'B' class GI pipes with necessary size ofband and couplings for control cable protection of CT, PT/CVTetc.equipments including fixing with structures as per instruction ofEngineer-in-charge. 1) 132 kV switch yard Mtr. 502) 66 kV switch yard Mtr. 25Providing and fixing of 100mm dia 'B' class GI pipes with necessary sizeof band and couplings for control cable protection of CB, Isolatoretc.equipments including fixing with structures as per instruction ofEngineer-in-charge. 1) 132 kV switch yard Mtr. 502) 66 kV switch yard Mtr. 25

5 Providing and fixing bay MK as per tech spec No. 3

7 Providing and fixing Yard LT ACDB as per tech spec -with 12 OG feeders No. 1

8

Providing and fixing of all weather proof, cold rolled sheet steel junctionbox for CVT & PT, CT terminations with 30 Nos. of disconnecting type,'Elmex' make CATDM 4 or equivalent type connectors and required no offuses, links etc.as per instruction of Engineer-in-charge.

No. 2

Sr No

Description Unit of Measurement Quantity

2 GPS based Time Syncronising Unit (IEC 61850 compatible) Set 1

Y

Supply, Erection, Testing and Commissioning of Protectionequipments and materials as per respective technical specificationsand relevant special conditions and suitable for Two Main Bussystem on 220kV side

1Control & Protection panels for 220KV Bays ( Control Voltage - 220V DC ) as per tech specifications & suitable for GIS switchgear modules with following break up1) Control & Protection panel for Line Set 63) Control & Protection panel for Transformer with Differential (220/132kV TRF) Set 2

4) Control & Protection panel for Transformer with Differential (220/66kV TRF) Set 3

5) Control & Protection panel for BC Set 16) Busbar Protection - (Central Unit - 24 bays, Peripheral Units - 12 Bays) [CU shall be mounted in one of the bay control & protection panel while PUs shall be mounted in respective bay control and protection panels as shown in panel GA drawing]

Set 1

4

4a

PROTECTION BOQ of 220kV Wankaner Sub Station (220kV & 66kV)

Total Price1 Custom Duty

Taxes and Duties

SWITCHYARD BOQ FOR 220/132/66kV Wankaner GIS Schedule No. 1 Plant and Mandatory Spare Parts Supplied from Abroad

Country of Origin

Sr. No.

Unit of Measurement Quantity

Unit Price1

Particulars of Item

Z

Supply, Erection, Testing and Commissioning of Protectionequipments and materials as per respective technical specificationsand relevant special conditions and suitable for Two Main Bussystem on 66kV side

1Control & Protection panels for 66KV Bays ( Control Voltage - 220V DC ) as per tech specifications & suitable for GIS switchgear modules with following break up1) Control & Protection Panel for Line Set 52) Control & Protection Panel for Buscoupler Set 13) Control & Protection Panel for Transformer W/O Differential Relay (for 220/66KV TRF) Set 3

5) Control & Protection Panel for Interconnecting bay Set 26) Under Frequency Panel Set 1

AA

Supply, Erection, Testing & Commissioning of General purposeequipments and materials as per respective technical specificationsand relevant special conditions and suitable for Two Main Bussystem on 220kV and 66kV side

1

Battery set - 220 V, 250Ah at ECV -1.14, C5 Duly cycle {1.2 V, 180 cells, (174 For Battery set and 6 Spare) } Ni-CAD Battery Set (Equivalent to 266 Ah as per C5 duty cycle at ECV - 1.0) with Two Step Two Tier FRP stand of adequate size (Rating is tentative for estimation purpose please refer Remarks)

No. 2

2

Battery Charger - 220 V (Float - 30A / Boost - 60A) - (SCADA compatible)Suitable to Ni-Cd Battery set and shall be able to charge Battery set as per requirement during float / boost mode as well as it shall supply to load as per rated voltage of load components. (Rating is tentative for estimation purpose please refer Remarks)

No. 2

4 DCDB-220 V with 20 Feeder No. 45 DCDB-220 V with 20 Feeder (For PLCC Panels) No. 2

6 SCADA compatible LTPB suitable for GIS switchgear module and related accessories as per specifications. No. 2

AB

Supply, Installation, Testing and Commissioning of materials/itemfor Power Cable and Control Cable including preparation of wiringschedule on the basis of GIS/HYBRID and LCC requirement andreferring to typical philosophy. However, final Cable philosophyshall be derived during detailed engineering and got approved.(Please refer Remarks)

1

Supply and Laying of 1.1 kV FRLSH PVC armoured copper/Aluminumcontrol/LT power cable in trench including binding/clamping of cable withPVC locable wire tie as per requirement including supply and fixing ofidentification tags at both ends and at distance of every 100mtr.(Note :- Aluminium cables of size 185 mm2 & above shall be XLPE type)

Total Price1 Custom Duty

Taxes and Duties

SWITCHYARD BOQ FOR 220/132/66kV Wankaner GIS Schedule No. 1 Plant and Mandatory Spare Parts Supplied from Abroad

Country of Origin

Sr. No.

Unit of Measurement Quantity

Unit Price1

Particulars of Item1) 2c x 2.5 mm2, armoured copper control cable Mtr.2) 2c x 4 mm2 , armoured copper control cable Mtr.3) 4cx2.5 mm2, armoured copper control cable Mtr.4) 4c x 4 mm2 , armoured copper control cable Mtr.5) 7c x 2.5 mm2, armoured copper control cable Mtr.6) 12c x 2.5 mm2, armoured copper control cable Mtr.7) 12c x 4 mm2, armoured copper control cable Mtr.8) 19c x 2.5 mm2 , armoured copper control cable Mtr.9) 27c x 2.5 mm2, armoured copper control cable Mtr.10A) 1 x 50 mm2 , armoured copper cable Mtr.10B) 4C x 10 mm2 , armoured copper control cable Mtr.11) 4 x 10 mm2 , Al. armoured LT cable Mtr.12) 3.5 x 25 mm2 , Al. armoured LT cable Mtr.13) 3.5 x 50 mm2 , Al. armoured LT cable Mtr.14) 3.5 x 120 mm2 , Al. armoured LT cable Mtr.15) 1C x 150 mm2 , Al. armoured LT cable Mtr.16) 1C x 240 mm2 , Al. armoured LT cable Mtr.17) 1C x 300 mm2 , Al. armoured LT cable Mtr.18) 3.5 x 300 mm2 , Al. armoured LT cable Mtr.

Termination of the Control and Power cable at panel / MK box/equipmentincluding PVC binding, dressing, shaping, drilling of holes in panels forglands nuts, providing of glands for following size. The work also includeslooping in Panel and MK box by using crimping type lugs of suitable sizewith ferruling (machine printed) with proper size of copper cable wire. Theloops should be bunched by using button tape and proper shaping etc.

1) cables from 2 core to 7 core of 2.5 & 4.0 Sq.mm size No. LS$2) cables above 7 core No. LS$Laying of 1.1kv FRLSH PVC/XLPE armored Al. LT power cable inground by digging trench of suitable width and 450 mm depth withproviding and fixing of brick and sand layer covering the cable in any typeof soil and Laying of 1.1kv PVC armored copper control cable in heavyduty PVC pipe of suitable size buried in ground by digging trench ofsuitable width and 450 mm depth in any type of soil including supply andfixing of Pipe and identification tags at distance of every 100 Mtrs forfollowing size1) Control Cables upto 7 core Mtr. LS$2) Control Cables above 7 core and all LT cables Mtr. LS$

3a

Supply, Erection, Testing and Commissioning of Modular Multi-diameter Cable sealing system as per respective technicalspecification and relevant special conditions wherever the electrical/ instrumentation / communication / LT Power cable undergroundand over-ground enter or leave bay kiosks / control room ofsubstations / cable trench / basement.

LS LS

2

3

LS$

Total Price1 Custom Duty

Taxes and Duties

SWITCHYARD BOQ FOR 220/132/66kV Wankaner GIS Schedule No. 1 Plant and Mandatory Spare Parts Supplied from Abroad

Country of Origin

Sr. No.

Unit of Measurement Quantity

Unit Price1

Particulars of ItemProviding and fixing of suitable BOX type GI perforated tray with necessary clamps and couplings for control cable of PT/CVT etc. equipments including fixing with structures up to plinth level as per instruction of Engineer-in-charge. 2) 220 kV Switch Yard Mtr. 50

4a

Providing and fixing of suitable BOX type GI perforated tray with necessary clamps and couplings for control cable of CB, Isolator, Earth Switch etc. equipments including fixing with structures up to plinth level as per instruction of Engineer-in-charge.

Note:

(IV) SCADA Part

Sr No

Description Unit of Measurement Quantity

AC

Supply, Erection, Testing and Commissioning of SCADA equipments and materials as per respective technical specifications and relevant special conditions and suitable for Two Main Bus system on 220kV and 66kV side

1 Bay Control Unit / RTU for Substation Auxiliaries # Nos 12 Bay Control Unit for Protection Coupler of PLCC / FOTE ** Nos 03 HMI Server computer with required softwares Nos 24 DR workstation PC No. 15 Gateway for remote control with software No 16 Gateway for SLDC Data with software No 17 SCADA software (For local and Remote control centre) No 18 Ethernet Fiber Switches* Nos 13

4

# Battery and Charger sizings are tentative as they are derived on the basis of available data of trip coil, LCC, DC Drives, GIS Module etc. Bidder has to derive Battery and Charger sizing based on their GIS component rating & design and accordingly it shall be quoted (Size not less than shown in BOQ). Battery and charger sizing shall be got approved during detailed engineering before finalization. Accordingly dimensions of LV Room, Battery room etc. shall be finalized.

$ Quantity and size of cables shall be derived by bidder based on GIS & LCC requirement. Typical philosophies are for reference only. However basic requirements like, 4 Sq.mm cable for CT, PT and 2.5 Sq.mm for Control wiring is to be followed as per philosophy. Also, 1CX150 size cables for incoming AC supply are to be considered as per rating of LT Panel board. Other than GIS-LCC - Panel cables, typical philosophies may be referred.

Total Price1 Custom Duty

Taxes and Duties

SWITCHYARD BOQ FOR 220/132/66kV Wankaner GIS Schedule No. 1 Plant and Mandatory Spare Parts Supplied from Abroad

Country of Origin

Sr. No.

Unit of Measurement Quantity

Unit Price1

Particulars of Item9 Line Interface unit - 2 Cable entry, 12 ports Nos 1910 Line Interface unit - 8 Cable entry, 32 ports Nos 114 Laser Jet colour Printer Nos 115 Laser Jet Printer Nos 1

16

3 KVA UPS with Battery having Auto changeover scheme for seamless changeover (Battery - 12V SMF Battery set, Ah rating and Nos.shall be suitable for 2 hours back-up as per UPS DC Voltage rating)

Nos 2

19 Armoured Fibre Optic Cable with HDPE duct (Mutli mode) MTR. 165024 Panel for mounting SCADA equipments Nos 125 Panel for mounting PLCC / FOTE BCU Nos 126 Panel for mounting Station Auxiliaries BCU/RTU Nos 128 Furniture for SCADA equipments Set 129 Panel for Mounting Spares Nos 1

Spares for SCADA and Protection 1 Bay Control Unit Nos 12 Bay Control and Protection Unit Nos 13 Line Interface Unit - 8 Cable entry, 32 ports Nos 14 Ethernet fiber switch Nos 15 Busbar Protection Peripheral Unit Nos 1

Note:

5) Contractor shall be responsible for necessary co-ordination with FOTE and OPGW supplier & erection agency to establish remote connectivity and over all operation from Master Control Centre through SCADA system.SCADA BOQ for 132kV Wankaner Substation(To Control 220kV Wankaner Substation)

Sr No

Description Unit of Measurement Quantity

ADSupply, Erection, Testing and Commissioning of SCADA equipments and materials as per respective technical specifications and relevant special conditions.

1 HMI Server computer with required softwares Nos 22 DR workstation PC Nos 15 Ethernet Fiber Switch* Nos 26 Line Interface unit - 2 Cable entry, 12 ports Nos 18 Laser Jet colour Printer Nos 19 Laser Jet Printer Nos 1

1) Any material/equipment accessories which are not listed in BOQ or scope of supply but required to complete the job shall be included and shown in technical bid.2)*Ethernet switches shall have as many spare ports as utilized ports. 3) ** PLCC / FOTE BCU shall have sufficient I/Os as per given list considering future lines also. 4) # BCU for station Auxiliary shall have sufficient I/Os as per list or otherwise suitable RTU shall be provided.

Total Price1 Custom Duty

Taxes and Duties

SWITCHYARD BOQ FOR 220/132/66kV Wankaner GIS Schedule No. 1 Plant and Mandatory Spare Parts Supplied from Abroad

Country of Origin

Sr. No.

Unit of Measurement Quantity

Unit Price1

Particulars of Item

10

3 KVA UPS with Battery having Auto changeover scheme for seamless changeover (Battery - 12V SMF Battery set, Ah rating and Nos.shall be suitable for 2 hours back-up as per UPS DC Voltage rating)

Nos 2

16 Panel for mounting SCADA equipments Nos 119 Furniture for SCADA equipments Set 1

Note:

3) Contractor shall be responsible for necessary co-ordination with FOTE and OPGW supplier & erection agency to establish remote connectivity and over all operation from Master Control Centre through SCADA system.

Grand Summary

Name of Bidder

Signature of Bidder

1 Specify currencies in accordance with ITB 19.Create additional columns for foreign currencies up to a maximum number of 3 foreign currencies if so required.

Country of Origin Declaration Form

ItemDescription Country

NOTE:

(3)   Bidder shall quote for all the items as per BoQ

The source of exchange rate shall be: Telegraphic Transfer Selling Rate of State Bank of India in India.

The date for the exchange rate shall be: Opening date of Technical Bid

complete the job shall be included and shown in technical bid.1) Any material/equipment accessories which are not listed in BOQ or scope of supply but required to

(4)   The currency that shall be used for bid evaluation and comparison purposes to convert all bid prices expressed in various currencies into a single currency is: Indian

2)*Ethernet switches shall have as many spare ports as utilized ports.

TOTAL of Column 7 , Column 8 and Column 9 to be carried forward to Schedule No. 5.

(1) the taxes & duties for bought out items shall be included in EXW price for Indian Bidder and in CIF price for Foreign Bidder for which bidder shall provide break up of

(2)   The bidder shall specify the applicable local taxes description and rates.