Symmetra LXTechnical Training
© 2003 APC corporation.
Agenda
Mechanical DesignSystem ArchitectureTheory of OperationSystem User InterfaceInformation SourcesQuestions and Answers
The target audience of this presentation is expected to have completed Symmetra LX Family Overview and Symmetra LX Configuration trainings.
Technical Training
© 2003 APC corporation.
SystemsTower 230V
8kVA N+1 (5.6kW)•Ships (1) Power Modules, (1) Battery Modules installed, rest ship on pallet
•Up to (2) Battery Modules•50A hard-wire input
•230V L-N-G•400V L-L-L-N-G
•No receptacles
16kVA N+1 4-batts (11.2kW)•Ships (2) Power Modules, (2) Battery Modules installed, rest ship on pallet
•Up to (4) Battery Modules•100A hard-wire input
•230V L-N-G•400V L-L-L-N-G
•No receptacles
16kVA N+1 13-batts (11.2kW)•Ships with (2) Power Modules, (9) Battery Modules installed, rest ship on pallet
•Up to (13 Battery Modules)•100A hard-wire input
•230V L-N-G•400V L-L-L-N-G
•No receptaclesSymmetra LX
© 2003 APC corporation.
SystemsRack-mount 230/480V
8kVA N+1 13U (6.4kW)
•Ships as empty frame w/ modules on pallet•50A hard-wire input
•230V L-N-G•400V L-L-L-N-G
•(6) IEC320C19; (8)IEC320C13
16kVA N+1 19U (12.8kW)
•Ships as empty frame w/ modules on pallet•100A hard-wire input
•230V L-N-G•400V L-L-L-N-G
•(10) IEC320C19; (8)IEC320C13
Symmetra LX
© 2003 APC corporation.
Extended Run Frames
Symmetra LX
Stackable 3 and 9-battery rack-mount XR frames•Available Q4.
•Today use current black SYRMXR4I 4-battery frame.
Stackable 9-battery tower XR frame•18 battery modules in same space as 12 today.
•Available Q4.
•Today use current black Symmetra XR12 12-battery frame.
Battery cabinet extension cables•Enables connection from LX tower to current Symmetra XR12
•SYAOPT3- 208V 4-foot•SYAOPT3I- 230V 4-foot •SYOPT3- 208V 15-foot•SYOPT3I- 230V 15-foot
© 2003 APC corporation.
16kVA XR frame
Mechanical design
5U
N/A
N/A
57.0 inches1446.5 mm
19U
34.2 inches869.0 mm
13U
23.7 inches602.0 mm
13U
23.7 inches 602.0 mm
RM
TWR
XR3 frame
XR9 frame 8kVA frame
16kVA frame
120/208 and 230 VAC
Footprint: 19.0 x 29.1 inches482.5 mm x 738.5 mm
© 2003 APC corporation.
Mechanical design
Rack mount Tower
All systems
© 2003 APC corporation.
Mechanical design
Symmetra
UPS Network Management Card with Environmental MonitoringProvides remote user interface, Manage via Web Browser, SNMP, and Telnet. Includes PowerChute Network Shutdown.
Removable Input/Output Wiring Tray (LX only)Allows easy hard-wiring at install and fast maintenance.
Field-replaceable Power Distribution Panels •Enable quick in-field modification of output receptacles to fit changing needs.
•Tower models ship with no receptacles, rack-mount models ship with receptacles appropriate for different voltage needs.
Extended Run Communication CardAllows Intelligence Modules to monitor the health of external batteries
Extended Run Connector
Allows hot-install of up to seven Extended Run Frames for quick, easy response to changing runtime needs
1:1 & 3:1 option in single product (230V LX only)Same product can be wired for either 3 or 1-phase input. (Rack/Tower 9 and 19 slot frames)
230V 200/208V
© 2003 APC corporation.
Mechanical designAll systems
Rack mount Tower
© 2003 APC corporation.Symmetra LX
All systemsFrame Electronic ModuleField-replaceable, Not Hot-swappable
PowerView DisplayHot-swappable
Flash upgradeable
Power Modules Hot-swappable
Battery ModulesHot-swappable
Intelligence ModulesHot-swappable
only one at a time!
Single Front DoorField-replaceable
Mechanical design
© 2003 APC corporation.
All systems
Power sharing and redundancy N+1
Theory of operation
© 2003 APC corporation.
Mechanical designAll systems
Power Module Battery Module
Intelligence ModuleFrame Electronic Module
© 2003 APC corporation.
Mechanical design
Network Management Card
Symmetra LX communications card
EPO and Enable Switch
External battery connector
All systems
PDU
I/O wiring tray
© 2003 APC corporation.
System architecture230 VAC
© 2003 APC corporation.
Symmetra LX Theory of Operation
Rectifier &PFC +/- DC Bus
BatteryCharger
InverterOutputSection
155 -276VAC Input
120 VDCBattery
240 VACOutput
Power Module Diagram
A/C out (typical)
120/208V or 120/240V 60hz
220/230/240V 50hz
© 2003 APC corporation.
Theory of operation
PFC(Power Factor
Correction)INVERTER
Battery Charger
DC Bus+/-400VDC
Symmetra LX Power Module
AC
MID
AC-OUTAC-1
MID
+BATT
Double conversion on-line UPS
230 VAC
© 2003 APC corporation.
Utility power
PFC(Power Factor
Correction)INVERTER
Battery Charger
DC Bus+/-400VDC
Symmetra LX Power Module
AC
MID
AC-OUTAC-1
MID
+BATT
Theory of operation230 VAC
© 2003 APC corporation.
Battery power
PFC(Power Factor
Correction)INVERTER
Battery Charger
DC Bus+/-400VDC
Symmetra LX Power Module
AC
MID
AC-OUTAC-1
MID
+BATT
Theory of operation230 VAC
© 2003 APC corporation.
Theory of operation: Power module
Phase to Phase Per Phase Phase to Neutral200 208 240 100 120 220 230 240
Part number:Max Output Power (kVA) 3740 3890 4000 1870 2244 4000 4000 4000Max Output Power (Watts) 2800 3200 3200 1400 1600 2800 2800 2800Max Output Current (from Inverters) 18.7 18.7 16.7 18.7 18.7 18.2 17.4 16.7Output Power Factor (Watt/VA) 0.75 0.82 0.80 0.75 0.71 0.70 0.70 0.70Input Power Factor (Watt/VA) 0.90 0.90 0.98 0.90 0.90 0.98/0.90
100/200 and 120/208 VAC models 230 VAC models
SYPM4KISYPM4KP
All systems
© 2003 APC corporation.
Theory of operation: OverloadAll systemsLess than 105%: indefinitely
More than 105%: 4 seconds. Then “Overload” fault is indicated.
© 2003 APC corporation.
Theory of operation: Battery Module:
SYBT5 for 120/208 and 230VAC modelsSYBT5FR for 100/200 VAC model
120VDC: 10 X 12VDC 7.2AH
Maximum 7 extended run (XR) frames
4 Power Modules charge 4 Battery Modules in appx. 3 hours.Each Power Module contains a 300W charger.
All systems
XR3 frame
XR9 frame
© 2003 APC corporation.
Theory of operation: Intelligence module
Diagnostics serial port
LEDs
Cold BootSwitch
UPS_ONBypassNormal operation
Module Fault
This IM in Control
All systems
© 2003 APC corporation.
System user interface
Input circuit breaker Maintenance bypass switch
PowerView display
All systems
© 2003 APC corporation.
System user interface
Network interface card (standard)
SmartSlot Cards
All systems
Simple signalling interface
ENABLE switch
© 2003 APC corporation.
Left-hand barQuick link other
functions
Left-hand barQuick link other
functions
Main Status Screen:Overview of key
functions; UPS and card
Main Status Screen:Overview of key
functions; UPS and card
Browser AccessibleSaves installing software on the network management console.
Browser AccessibleSaves installing software on the network management console.
InfraStruXure Management Design BenefitsNetwork Management Card Screen Shot
InfraStruXure Management Design BenefitsNetwork Management Card Screen Shot
© 2003 APC corporation.
All systems
System user interface
System enable switch
EPO switch connector(dry contact or external 24VDC)
XR battery module
External PowerView display (up to 15 feet / 5 meters away)
© 2003 APC corporation.
DisplayHigh visibility and backlit
Status LightsIndicates current system status, alarms, warnings independent of LCD display
NavigationMenu, status, mode change and set point adjustment
HelpDetailed instruction on operation
EnterSelect current menu item, confirm change
EscapeEasy to return to previous menu item
User Interface Design Benefits
Consistent User InterfaceSame user interface across all APC UPS, cooling, and environmental monitoring products
SecurityPassword protected
© 2003 APC corporation.Symmetra LX
208/120VSYAPD1
- (1) L14-30R, (2) L5-20R
SYPD3- (1) L6-30R, (2) L6-20R
SYPD7- (3) L6-20R
SYPD11- (2) L6-30R
230VSYPD4
- (2) IEC320C19, (8) IEC320C13
SYPD8- (4) IEC320C19
SYPD9- (1) 32A hard-wire connection
SYPD10- (1) IEC309, (2) IEC320C19
Replacement internal back-plates
Retaining Screws
Accessories
© 2003 APC corporation.
Accessories
Symmetra LX
•Wall-mount or rack-mount•Online, test, and bypass modes•Different options for SYLX
•World-wide•SBP16KP- All hardwire connections
•208/120V•SBP16KRMP4U- (6) L14-30R•SBP16KRMP4U-HW
•(1) L14-30R, (3) L5-20R, (1) HW 100A
•230V •SBP16KRMI4U- (3) HW 32A
1Phase Service Bypass Panels
© 2003 APC corporation.
Accessories
Symmetra LX
Power Distribution Units (PDU)
Expansion PDU•Used to enable extra Rack PDU•L14-30P input plug w/ 28 ft cord•Output receptacles:
•120V•AP7580- (4) L5-20R•AP7582- (12) 5-20R•AP7583- (4) L5-30R
•208V•AP7581- (4) L6-20R•AP7584- (4) L6-30R
•230V (require SYPD9)•AP7585- (4) IEC320C19 16A•AP7586- (4) IEC309 32A
© 2003 APC corporation.
Rack PDU: Basic, Metered, Switched
Input SelectorPress to invert displayPress to monitor the next phase
Serial PortProvides local access to the control console
Reset ButtonResets Rack PDU without affecting outlet state
Current MonitorDisplays current draw for the phase indicated
Load Indicator LEDIdentifies overload and warning conditions
Network ConnectionAccess, configure, and manage via Web, SNMP, Telnet, or InfraStruXure Manager
Vertical & Tool less MountZero U mounting
Snap into a NetShelter VX rear channel
Single inputOne branch whip connection
Multi-branch input provides 5.7kW of AC power
Multiple OutletsConnect multiple pieces of equipment
Provides 120V/208V on one strip
© 2003 APC corporation.
Questions