Click here to load reader
Upload
scribdkkk
View
101
Download
4
Embed Size (px)
Citation preview
SYNCHROTACT ® 5Synchronizing and Paralleling
Equipment and Systems
SYNCHROTACT ® 5Synchronizing and Paralleling
Equipment and Systems
Safety and Availability
SYNCHROTACT® products from ABB areused for automatic synchronization ofgenerators with power lines and forparalleling of synchronous lines.They are designed for fully-automaticparalleling or monitoring of paralleling(Synchrocheck) by means of dual-chan-nel or single-channel systems.
SYNCHROTACT 5 is the fifth generation ofsynchronizing equipment produced by ABBIndustrie AG in Switzerland. It is newlydeveloped based on decades of experienceand focus on customer’s requirement.
Optimum availability
The family range of SYNCHROTACT 5facilitates other configuration concepts suchas dual-channel bypass (redundant) synchro-nization, which connects a manual or auto-matic system in parallel to the automaticsystem. With this configuration full availabilityis achieved, in case of one channel failure,with maximum safety.
Optimizedunit design
With SYNCHROTACT 5 a family of devicesare available which can be combined easilyto realize all possible reliable concepts tosatisfy precise client’s requirements in termsof safety and availability as described above.
A redundant dual-channel system provided inone 19 inch casing eliminates interconnectionwiring.
Maximum safety
The safety of the generator and network,while synchronizing, is insured by a compactdual-channel system including two indepen-dent hardware and software. One channel isfor automatic synchronizing and the otherone is an additional independent monitoringof the first one. For the maximum operationsafety the hardware and software of eachchannel are designed by different develop-ment engineers.
AutomaticSynchronizing Synchrocheck
Synchrocheck
Dual-channel system with automatic synchronizingdevice and Synchrocheck in series
Dual-channel system with manual parallelingswitch and synchrocheck in series
AutomaticSynchronizing Synchrocheck
Synchrocheck
AutomaticSynchronizing Synchrocheck
Synchrocheck
AutomaticSynchronizing
Synchrocheck
Dual-channel system with automatic synchronizingdevice, manual paralleling switch in parallel and
Synchrocheck in series
Dual-channel main synchronizing system withbypass synchronizing system of manual paralleling
switch and a Synchrocheck
AutomaticSynchronizing
Two automatic dual-channel systems forhighest security and maximum availability
Applications and Functionality
Lowerengineering costs
♦ Fewer auxiliary relays are required, as thecontacts are designed more efficiently andinputs and outputs are separated galvani-cally one beneath the other.
♦ No separate power supply unit is required.
♦ A prefabricated unit is available for theselection of several paralleling points.Variety of applications
• For automatic synchronization andparalleling of generators
• For automatic paralleling of synchronousand asynchronous lines, transmission linesand busbars
• For monitoring of paralleling (Synchro-check) as well as monitoring of automaticand manual paralleling procedures includ-ing “dead bus”
• For the rated frequencies 50 Hz, 60 Hz and16 2/3 Hz
• For replacement of older SYNCHROTACTsystems or synchronization units by othermanufacturers.
SYNCHROTACT 5 is distinguished fromits predecessor models by additionalapplications and its fundamentallyimproved service and maintenance tool.Its well-conceived and optimized hard-ware design reduces the number ofrequired components to a minimum.
The extended casing fordual-channel parallelingsystem and dual-channelbypass system, can bemounted in a 19” frame
Fastcommissioning
♦ The convenient PC software “SynView”allows simple and fast commissioning of aSYNCHROTACT 5 system.
♦ The commissioning and parameter settingof SYNCHROTACT 5 can also be comfort-ably performed without a PC, using thecontrol elements in the front of the casing.Grouping within the parameter sets allowsfast access to the individual parameters.
♦ For setting system parameters, very simpleto use test functions are available.
♦ The SynView program indicates minimum,maximum and default values for eachparameter when a parameter is selectedand can provide a recommended value.
Special features• Up to seven sets of parameter for seven
different paralleling points can be storedin one device
• Freely-configurable digital inputs andoutputs.
ABB Industrie AGStatic Excitation Systems, Voltage Regulatorsand Synchronizing EquipmentCH-5300 Turgi / SwitzerlandTelephone: +41 56 - 299 24 86Fax: +41 56 - 299 23 33Internet: www.abb.com / unitrol 3B
HT
490
301
R00
01P
rinte
d in
Sw
itzer
land
(000
5-P
DF)
We reserve the right to change in the interest of technical development.
“SynView” PC Program
SynView is the suitable tool for thesimple and fast commissioning ofSYNCHROTACT 5 equipment.
German, English or French languagesare supported by SynView which runsunder Microsoft® Windows™ NT (95 or98 on request). Other languages arepossible but not supported as standardand are not included.
Simple parameter setting
• Selection of the parameter set• Double-click on the desired parameter
group⇒ Display of individual parameters
• Double-click on the parameter value⇒ Set new value on the parameter in
question• Transfer parameter set to SYNCHROTACT 5
by clicking on a button or using the menuoption Write.
Parameter setting of aSYNCHROTACT 5using SynView
Functions
SynView program offers the following fourmain functions:
• Setting of parameters
• Display of actual values
• Transient recorder function
• Event and error logging.
Graphic output of synchronizing events
Synchronization procedures can be recordedand evaluated later with the transient recor-der function of the SynView program. Noseparate transient recorder is required duringcommissioning.
Easy fault finding within service work
SYNCHROTACT 5 features an event anderror logger for 256 events, which are storedwith date/time-stamp and the time past sincethe start of the synchronizing process.
The values stored in the logger can bedisplayed in clear text.
User-friendly display of actual values
• Analog bar display of actual valuesU
1, U
2, f
1, f
2
• Synchroscope display• Numerical display of voltage difference
∆U, phase-angle difference α and slip s.
Auxiliary voltageNominal voltage ranges 24/48 VDC
100 to 125 VAC/DC
220 to 250 VDC
Permissible voltage range 0.75 to 1.25 × Un
Maximum power consumption 25 W / 35 VA SYN 5302
Measuring inputs U1, U2Nominal voltage range 50 to 130 VAC
Permissible voltage range 0 to 1.3 Un
Nominal frequency 16 2/3 / 50 / 60 Hz
Digital inputsNominal voltages 24/48 VDC
Current consumption 6 to 8 mA
Paralleling relaysMaximum switching voltage 250 VAC/DC
Maximum switching current, continuous 5 AAC/DC
Max. switching power DC/AC ON 1000 W/VA
Max. switching power DC/AC OFF 30 W/VA
Adjusting, command and signalling relaysMaximum switching voltage 250 VAC/DC
Maximum switching current, continuous 1.5 AAC/DC
Max. switching power DC/AC ON/OFF 100 W/VA
Serial interfacefor PC software “SynView” RS 232
Measuring rangesVoltage U1, U2 0 to 1.3 × Un
Angle matching α –179 to +180 DEG
Frequency 10 to 100 Hz
Slip s 0 to 50 %
Acceleration ds/dt 0 to 10 %/s
Paralleling time t ON 0 to 1 s
IsolationDielectric test IEC 60255-5 2 kV
Impulse voltage test IEC 60255-5 5 kV
Degrees of protection acc. to IEC 60529Front IP 54
Rear IP 50
Technical Data
Supplement to 3B HT 490 301
Temperature rangesTransport/storage –40 to +85 °CFunctionable –25 to +70 °COperation (compliance with technical data) –10 to +55 °C
Mechanical stabilityVibration IEC 60255-21-1 10 to 150 Hz
Class 2 Vibration response 1 g Endurance 2 g
Shocks and Bumps IEC 60255-21-2 Class 2 Shock response 10 g Withstand 30 g Endurance 20 g
Earthquake IEC 60255-21-3 Method A5 g in each axis
Emission / immunity (EMC)Emission IEC 55011 0.15 to 0.5 MHz: terminal disturbance 79/66 dB
0.5 to 30 MHz:73/60 dB
Emission IEC 55011 30 to 230 MHz: radiation disturbance 30 dB
230 to 1000 MHz:37 dB
Electrostatic discharges IEC 61000-4-2 Contact: 6 kVAir: 8 kV
Electromagnetic fields IEC 61000-4-6 0.15 to 80 MHz10 V, 80 % AM
IEC 61000-4-3 80 to 1000 MHz10 V/m, 80 % AM
and PM / 900 MHz
Fast transients/Bursts IEC 61000-4-4 ±1 kV / ±2 kV
Surge voltage IEC 61000-4-5 ±0.5 kV/±1 kV/±2 kV/±4 kV
Voltage dips IEC 61000-4-11 AC:30 %: 10 ms
60 %: 100 ms> 95 %: 5000 ms
1 MHz burst disturbance IEC 60255-22-1 common mode 2.5 kV differential mode 1 kV
CE conformityLV Directive 73/23/ECC EN 60950
EMC Directive 89/336/ECC EN 50081-2EN 50082-2
ABB Industrie AGStatic Excitation Systems, Voltage Regulatorsand Synchronizing EquipmentCH-5300 Turgi / SwitzerlandTelephone: +41 56 - 299 24 86Fax: +41 56 - 299 23 33Internet: www.abb.com / unitrol
We reserve the right to change in the interest of technical development.
SYN 5100Casing size (W×H×D) 190 × 127 × 90 mm
Weight 0.3 kg
Modular casing designed to snap onto top-hat rail
SYN 5200, SYN 5201, SYN 5202Plug-in type casing (Option: surface mounting)
Orientation: Horizontal
Table cutout W×H 222 × 164 mm
Device profile W×H×D 221 × 163 × 220 mm
Front frame W×H 226 × 171 mm
Weight 4.0 kg
SYNCHROTACT® 5 Device types
SYN 5302Plug-in type casing for 19" rack
Orientation: Horizontal
Table cutout W×H 443 × 155 mm
Device profile W×H×D 442 × 154 × 220 mm
Front frame W×H 447 × 171 mm
Weight 8.0 kg
SYN 5500Dimensions W×H×D 381 × 128 × 50 mm
Weight 1.4 kg
Board designed to snap onto top-hat rail
Type Function Description
SYN 5100 Synchrocheck Simple Synchrocheck
SYN 5200 Synchrocheck Synchrocheck with advanced functionality
SYN 5201 Automatic synchronizing device
Automatic single-channel synchronizing device with frequency and voltage adjustment
SYN 5202 Automatic dual-channel synchronizing system
Automatic dual-channel synchronizing system with Synchrocheck in series as second channel
SYN 5302 Automatic dual-channel synchronizing system
Redundant automatic dual-channel synchronizing system
SYN 5500 Auxiliary device for SYNCHROTACT 5
Auxiliary device for connection of several paralleling points
Construction data