POST AND BEAM ENDWALL DETAILSAB0005 - COLD FORMED ENDWALL ERECTION NOTE DETAILAB0010 - LOW EAVE - CF RAFTERAB0011 - LOW EAVE - CF RAFTER AT MASONRYAB0020 - LOW EAVE - BU RAFTERAB0025 - LOW EAVE - BU RAFTER (COL. ROTATED 90°)AB0030 - INTERIOR - CF RAFTER (SIMPLE SPAN)AB0040 - INTERIOR - CF RAFTERS (LAPPED)AB0045 - INTERIOR - CF RAFTERS (CONTINUOUS)AB0050 - INT. COL. TO RAFTER CONNECTION, W/BU & CF RAFTERS @ OPP. SIDESAB0070 - BU RAFTERS (SIMPLE SPAN)AB0080 - BU RAFTER (CONTINUOUS)AB0090 - HIGH EAVE - CF RAFTERAB0095 - HIGH EAVE - CF RAFTER (COL. ROTATED 90°)AB0098 - HIGH EAVE PARAPET - CF RAFTERAB0099 - EW CEE COLUMN TO RAFTER CONNECTIONAB0110 - EW CEE COL TO RIDGE RAFTER CONNAB0120 - RIDGE COL. TO RAF. CONNECTION, W/ BU & CF RAFTERS @ OPP. SIDESAB0150 - EW RAFTER RIDGE CONNAB0200 - ENDWALL PIGGY-BACK CEE COLUMN TO RAFTER CONNAB0210 - ENDWALL PIGGY-BACK CEE COLUMN TO RAFTER CONNAB0220 - ENDWALL PIGGY-BACK CEE COLUMN TO RAFTER CONNAB0230 - ENDWALL PIGGY-BACK CEE COLUMN TO RIDGE RAFTER CONNAB0240 - ENDWALL PIGGY-BACK CEE COLUMN TO RAFTER CONNAB0250 - ENDWALL PIGGY-BACK CEE COLUMN TO RIDGE RAFTER CONNAB0510 - EW COL TO RAFTER CONNAB0515 - EW COL TO RAFTER CONNAB0516 - LOW EAVE COL. CF RAFTER @ MASONRY WALL (COL. ROT. 90 DEG)AB0517 - LOW EAVE COL. CF RAFTER @ MASONRY WALL (COL. ROT. 90 DEG)AB0530 - CF RAFTERS (SIMPLE SPAN)AB0535 - CF RAFTER (SIMPLE SPAN-COLUMN ROTATED 90 DEG)AB0540 - CF RAFTER (LAPPED)AB0545 - COLUMN TO CF RAFTER (CONTINUOUS)AB0550 - INTERMEDIATE COL. CONN. (SIMPLE SPAN W/ BU & CF RAF. @ OPP. SIDES)
TABLE OF CONTENTS
AB0560 - BU RAFTER LEFT CF RAFTER RIGHTAB0590 - HIGH EAVE (CF RAFTER)AB0595 - EW COL TO RAFTER (COL ROTATED 90° @ HIGH EAVE)AB0598 - EW COL. TO RAF. CONNECTION (HIGH EAVE @ PARAPET BY OTHERS)AB0599 - 90° ROTATED EW COL TO RAFTER CONN @ H EAVE (WITH PARAPET)AB0610 - EW COL TO CF RAFTER CONN (@ RIDGE)AB0620 - RIDGE (BU RAFTER RIGHT, CF RAFTER LEFT)
AND PRACTICALITY OF INDIVIDUAL SITUATIONS.THIS DETAIL IS SUGGESTED IN ORDER TO MAINTAIN STRUCTURAL INTEGRITY OF ENDWALL PARTS AFTER ERECTION.
4)
BUILT-UP COLUMNS/RAFTERS MUST BE ERECTED INDIVIDUALLY WHEN USED WITH COLD FORMED ENDWALL PARTS
LC
PICK POINT
GIRTS
SPREADER BAR
(TYPICAL)
3 SPANS MAXIMUM
BRACINGWIND
A
COLD FORMED ENDWALL ERECTOR DETAIL1) GIRTS, CLIPS, RAFTERS AND COLUMNS MUST BE SECURELY AND TIGHTLY BOLTED TOGETHER PRIOR TO STANDING UP THE ENDWALL SECTION. (NOTE: THE GIRTS PROVIDE STABILITY TO THE ENDWALL SYSTEM DURING THE ERECTION PROCESS)
STRAP
LIFT
CORRECT
COLD-FORMEDRAFTER
STRAP
COLD-FORMEDRAFTER
LIFT
THIS WILL CAUSETHE RAFTER TOTWIST.
AB00
05
REGULATIONS SET FORTH BY THE OCCUPATIONAL SAFETY AND HEALTH ACT, LOCAL, STATE, AND/OR FEDERAL AGENCIES SHOULD BE ADHERED TO AT ALL TIMES. THE METAL BUILDING SUPPLIER IS NOT RESPONSIBLE FOR INJURY, DAMAGE, OR FAILURE WHICH MAY RESULT FROM FAILING TO MEET ANY OF THESE REGULATIONS.
SECTION A
2)
3)
6'-0" MINIMUM 8'-0"MAXIMUM
6'-0" MINIMUM 8'-0"MAXIMUM
INCORRECT
AB0005
1) N/A
Detail Size (W x H) :
By :: CERTIFIED ERECTION DETAILSIssued
Issued
Detailer Notes:
Download the DWG file by clicking here.
POST & BEAM ENDWALLPRIMARY FRAMING
AB0005 - COLD FORMED ENDWALL ERECTION NOTE DETAIL
08.16.19 2018.057
SAA
2 x 2
EW CEE COLUMN TO RAFTER CONN
REFERENCE ERECTOR NOTE FOR TYPICAL WASHER REQUIREMENTS
2"
COLUMN TOP CLIP FACTORY WELDED TO COLUMN
1'-4"
CEE ENDWALL COLUMN
SINGLE OR DOUBLE
A
SINGLE OR DOUBLE
CEE ENDWALL COLUMN
RAFTER
L
1/4"
S
A325 BOLTS H0603
(4) 1/2"Ø X 2"
NUTS H0300
SECTION A
RAFTER
OFCL 4"
SL
STIFFENER,IF REQUIRED
- 1 1/8" GAGE @ 4" RAFTER FLANGE
- 1 1/2" GAGE @ GREATER THAN 4" RAFTER FLANGE**
*
*
AB0020
1) N/A
Detail Size (W x H) :By :
: CERTIFIED ERECTION DETAILSIssuedIssued
Detailer Notes:
Download the DWG file by clicking here.
POST & BEAM ENDWALLPRIMARY FRAMING
AB0020 - LOW EAVE - BU RAFTER
08.16.19 2018.057SAA
1 x 1
EW CEE COLUMN TO RAFTER CONN
AB0025
SECTION A
CEE ENDWALL COLUMNSINGLE OR DOUBLE
REFERENCE ERECTOR NOTE FOR TYPICAL WASHER REQUIREMENTS
A
COLUMN TOP CLIP FACTORY WELDED TO COLUMN
8" OR 12"
CEE ENDWALL COLUMNSINGLE OR DOUBLE
1/4"
LS A325 BOLTS H0603NUTS H0300
(4) 1/2"Ø X 2"
RAFTER
OFCL
RAFTER
SL
2"
STIFFENER,IF REQUIRED
3"1"
SEE_PLAN
SEE_PLAN
- 1 1/8" GAGE @ 4" RAFTER FLANGE
- 1 1/2" GAGE @ GREATER THAN 4" RAFTER FLANGE**
*
*
SL TO FACE OF COL.
FRAME OFFSET
1) N/A
Detail Size (W x H) :By :
: CERTIFIED ERECTION DETAILSIssuedIssued
Detailer Notes:
Download the DWG file by clicking here.
POST & BEAM ENDWALLPRIMARY FRAMING
AB0025 - LOW EAVE - BU RAFTER (COL. ROTATED 90°)
08.16.19 2018.057SAA
1 x 1
EW CEE COLUMN TO RAFTER CONN
AB0030REFERENCE ERECTOR NOTE FOR TYPICAL WASHER REQUIREMENTS
1 1/2"
A325 BOLTS H0603
(8) 1/2"Ø X 2"
RAFTER
2"
COLUMN TOP CLIP FACTORY WELDED TO COLUMN
SINGLE OR DOUBLECEE ENDWALL COLUMN
A
(SIMPLE SPAN)
CEE ENDWALL COLUMNSINGLE OR DOUBLE
1/4"
1 1/2"
1'-9"
RAFTER
1'-9"
MK. EWA02CLIP
NUTS H0300
SECTION A
2"
RAFTER
OFLC 4"
SL
1) N/A
Detail Size (W x H) :By :
: CERTIFIED ERECTION DETAILSIssuedIssued
Detailer Notes:
Download the DWG file by clicking here.
POST & BEAM ENDWALLPRIMARY FRAMING
AB0030 - INTERIOR - CF RAFTER (SIMPLE SPAN)
08.16.19 2018.057SAA
1 x 1
REFERENCE ERECTOR NOTE FOR TYPICAL WASHER REQUIREMENTS
(10) 1/2"Ø X 2"
A325 BOLTS H0603
1 1/2"
NUTS H0300
RAFTER
2"
COLUMN TOP CLIP FACTORY WELDED TO COLUMN
BOLTS REQ'D ONLY AS SHOWN, NOT @ ALL HOLES
CEE ENDWALL COLUMNSINGLE OR DOUBLE
A
(LAPPED RAFTER)
CEE ENDWALL COLUMNSINGLE OR DOUBLE
1 1/2"
7'-0"
3'-2 1/2"2"
3'-2 1/2"1 1/2"
2"
SECTION A
2"
OF
RAFTERLC 4"
SL
EW CEE COLUMN TO RAFTER CONN
AB0040
1) N/A
Detail Size (W x H) :By :
: CERTIFIED ERECTION DETAILSIssuedIssued
Detailer Notes:
Download the DWG file by clicking here.
POST & BEAM ENDWALLPRIMARY FRAMING
AB0040 - INTERIOR - CF RAFTERS (LAPPED)
08.16.19 2018.057SAA
1 x 1
EW CEE COLUMN TO RAFTER CONN
AB0045REFERENCE ERECTOR NOTE FOR TYPICAL WASHER REQUIREMENTS
1 1/2"
2"
COLUMN TOP CLIP FACTORY WELDED TO COLUMN
SINGLE OR DOUBLECEE ENDWALL COLUMN
A
CEE ENDWALL COLUMNSINGLE OR DOUBLE
1 1/2"
A325 BOLTS H0603(6) 1/2"Ø X 2"
NUTS H0300
MK. EWA01CLIP
RAFTER
SECTION A
2"
OF
RAFTER
CL 4"
SL
(CONTINUOUS RAFTER)
1) N/A
Detail Size (W x H) :By :
: CERTIFIED ERECTION DETAILSIssuedIssued
Detailer Notes:
Download the DWG file by clicking here.
POST & BEAM ENDWALLPRIMARY FRAMING
AB0045 - INTERIOR - CF RAFTERS (CONTINUOUS)
08.16.19 2018.057SAA
1 x 1
EW CEE COLUMN TO RAFTER CONN
AB0050
1 1/2"
BOLT COLUMN TO RAFTER FLANGS AS SHOWN
REFERENCE ERECTOR NOTE FOR TYPICAL WASHER REQUIREMENTS
2"
COLUMN TOP CLIP FACTORY WELDED TO COLUMN
SINGLE OR DOUBLECEE ENDWALL COLUMN
A
REQUIRED @MARK GCB03
RAFTERS ONLYCOLD-FORMED
CLIP
SINGLE OR DOUBLECEE ENDWALL COLUMN
A325 BOLTS H0603
(2) 1/2"Ø X 2"
COLD-FORMED
NUTS H0300
RAFTER
1/4"
1 1/2"
RAFTERBUILT-UP
COLD-FORMED SHOWNBUILT-UP SIMILAR
SECTION A
2"
4"
RAFTER
OFCL 4"
SL
COLD FORMED RAFTER SHOWN ON LEFT SIDE
BU/HR ON RIGHT. OPPOSITE POSITIONS SIMILAR
A325 BOLTS H0603
(4) 1/2"Ø X 2"
NUTS H0300
1) N/A
Detail Size (W x H) :By :
: CERTIFIED ERECTION DETAILSIssuedIssued
Detailer Notes:
Download the DWG file by clicking here.
POST & BEAM ENDWALLPRIMARY FRAMING
AB0050 - INT. COLUMN TO RAFTER CONNECTION, W/BU & CF RAFTERS @ OPP. SIDES
08.16.19 2018.057SAA
1 x 1
EW CEE COLUMN TO RAFTER CONN
AB0080
2"
COLUMN TOP CLIP FACTORY WELDED TO COLUMN
REFERENCE ERECTOR NOTE FOR TYPICAL WASHER REQUIREMENTS
CEE ENDWALL COLUMN
SINGLE OR DOUBLE
A
(CONTINUOUS RAFTER)
SINGLE OR DOUBLE
CEE ENDWALL COLUMN
NUTS H0300
(4) 1/2"Ø X 2"
A325 BOLTS H0603
STIFFENER, RAFTER
SECTION A
RAFTER
CL OF 4"
LSIF REQUIRED
- 1 1/8" GAGE @ 4" RAFTER FLANGE
- 1 1/2" GAGE @ GREATER THAN 4" RAFTER FLANGE**
*
*
1) N/A
Detail Size (W x H) :By :
: CERTIFIED ERECTION DETAILSIssuedIssued
Detailer Notes:
Download the DWG file by clicking here.
POST & BEAM ENDWALLPRIMARY FRAMING
AB0080 - BU RAFTER (CONTINUOUS)
08.16.19 2018.057SAA
1 x 1
EW CEE COLUMN TO RAFTER CONN
AB0090
1 1/2"
CEE ENDWALL COLUMN
2"
REFERENCE ERECTOR NOTE FOR TYPICAL WASHER REQUIREMENTSCOLUMN TOP CLIP FACTORY WELDED TO COLUMN
SINGLE OR DOUBLECEE ENDWALL COLUMN
A
1'-4"
SINGLE OR DOUBLE
1/4"
1 1/2"
RAFTER
A325 BOLTS H0603
(6) 1/2"Ø X 2"
NUTS H0300
MK. EWA01CLIP
LS
SECTION A
2"
OF
RAFTER
CL 4"
SL
SEE SECONDARY DETAILSFOR HIGH EAVE SUPPORTMEMBER & CONNECTION
1) N/A
Detail Size (W x H) :By :
: CERTIFIED ERECTION DETAILSIssuedIssued
Detailer Notes:
Download the DWG file by clicking here.
POST & BEAM ENDWALLPRIMARY FRAMING
AB0090 - HIGH EAVE - CF RAFTER
08.16.19 2018.057SAA
1 x 1
EW CEE COLUMN TO RAFTER CONN
AB0095REFERENCE ERECTOR NOTE FOR TYPICAL WASHER REQUIREMENTS
SINGLE OR DOUBLECEE ENDWALL COLUMN
A
COLUMN TOP CLIP FACTORY WELDED TO COLUMN
SINGLE OR DOUBLECEE ENDWALL COLUMN
8" OR 12"
SECTION A
2"
1/4"
MK. EWA01CLIP
NUTS H0300
1 1/2"
(6) 1/2"Ø X 2"
A325 BOLTS H0603
1 1/2"
RAFTERLC OFRAFTER
LS
SL2"
3"1"
SEE_PLAN
SEE_PLAN
FACE OF COL. TO SL
SEE SECONDARY DETAILSFOR HIGH EAVE SUPPORTMEMBER & CONNECTION
FRAME OFFSET
1) N/A
Detail Size (W x H) :By :
: CERTIFIED ERECTION DETAILSIssuedIssued
Detailer Notes:
Download the DWG file by clicking here.
POST & BEAM ENDWALLPRIMARY FRAMING
AB0095 - HIGH EAVE - CF RAFTER (COL. ROTATED 90°)
08.16.19 2018.057SAA
1 x 1
EW CEE COLUMN TO RAFTER CONNECTION
AB0098
SINGLE CEE ENDWALLRAFTER
REFERENCE ERECTOR NOTE FOR TYPICAL WASHER REQUIREMENTS
PARAPET WALL BY
OTHERS
OF RAFTER
CENTERLINE
ENDWALL STEEL LINE
STEEL LINE AND
OUTSIDE FACE OF WALL
2"
USE (6) 1/2"Ø x 2" A325 BOLTS (MK. H0603) & NUTS (MK. H0300)
COLUMN TOP CLIP FACTORY WELDED TO COLUMN
CENTERLINE OF
COLUMN
SINGLE OR DOUBLE
CEE ENDWALL
COLUMN
A
2"
1'-4"
COLUMN
EWA01
CLIP
MK. EWA01
1 1/2" 1 1/2"
RAFTER
1 1/2"
SECTION A
1 1/2"
4"
1) N/A
Detail Size (W x H) :By :
: CERTIFIED ERECTION DETAILSIssuedIssued
Detailer Notes:
Download the DWG file by clicking here.
POST & BEAM ENDWALLPRIMARY FRAMING
AB0098 - HIGH EAVE PARAPET - CF RAFTER
08.16.19 2018.057SAA
1 x 1
EW CEE COLUMN TO RAFTER CONNECTION
AB0099
SINGLE CEE
ENDWALL RAFTER
PARAPET WALL
BY OTHERS
OF RAFTER
CENTERLINE
ENDWALL STEEL LINE
STEEL LINE AND
OUTSIDE FACE OF WALL
OUTSIDE FACE
OF COLUMN
SINGLE OR DOUBLE
CEE ENDWALL
COLUMN
A
COLUMN
EWA01
CLIP MK. EWA01
1 1/2"
RAFTER
1 1/2"
SECTION A
1 1/2"
3"1"
1 1/2"
COLUMN TOP CLIP FACTORY WELDED TO COLUMN
USE (6) 1/2"Ø x 2" A325 BOLTS (MK. H0603) & NUTS (MK. H0300)
REFERENCE ERECTOR NOTE FOR TYPICAL WASHER REQUIREMENTS
C
D
2"
1) N/A
Detail Size (W x H) :By :
: CERTIFIED ERECTION DETAILSIssuedIssued
Detailer Notes:
Download the DWG file by clicking here.
POST & BEAM ENDWALLPRIMARY FRAMING
AB0099 - EW CEE COLUMN TO RAFTER CONNECTION
08.16.19 (2018.057)SAA
1 x 1
EW CEE COL TO RIDGE RAFTER CONN
AB0120
LS
1 1/2"1 1/2"
OFLRAFTER
1 1/2"
2"4"
4"
SECTION A
2"
1/4"1/4"
A
AB
0120
C
BOLT COLUMN TO RAFTER FLANGES AS SHOWN
REFERENCE ERECTOR NOTE FOR TYPICAL WASHER REQUIREMENTS
SINGLE OR DOUBLE
CEE ENDWALL COLUMN
CLIP MK. GCB03
REQUIRED @
COLD-FORMED
RAFTERS ONLY
COLD-FORMEDRAFTER
A325 BOLTS H0603
NUTS H0300
(2) 1/2"Ø X 2"
BUILT-UP
RAFTER
SINGLE OR DOUBLE
CEE ENDWALL COLUMN
COLD-FORMED SHOWN
BUILT-UP SIMILAR
COLD FORMED RAFTER SHOWN ON LEFT SIDE,
BU/HR ON RIGHT. OPPOSITE POSITION SIMILAR.
A325 BOLTS H0603
NUTS H0300
(4) 1/2"Ø X 2"
1) N/A
Detail Size (W x H) :By :
: CERTIFIED ERECTION DETAILSIssuedIssued
Detailer Notes:
Download the DWG file by clicking here.
POST & BEAM ENDWALLPRIMARY FRAMING
AB0120 - RIDGE COLUMN TO RAFTER CONNECTION, W/ BU & CF RAFTERS @ OPP. SIDES
08.16.19 2018.057SAA
1 x 1
EW RAFTER RIDGE CONN
AB0150
AB
0150
1/4"
L RIDGEC
1/4"
2"4"
1 1/2"
REFERENCE ERECTOR NOTE FOR TYPICAL WASHER REQUIREMENTS
(8) 1/2"Ø X 2"
A325 BOLTS H0603
NUTS H0300
8" COLD-FORMED
RAFTER
12" COLD-FORMED
RAFTER
CLIP
MK. NCR__
1) N/A
Detail Size (W x H) :By :
: CERTIFIED ERECTION DETAILSIssuedIssued
Detailer Notes:
Download the DWG file by clicking here.
POST & BEAM ENDWALLPRIMARY FRAMING
AB0150 - EW RAFTER RIDGE CONN
08.16.19 2018.057SAA
1 x 1
AB0200
T-CLIP
MK. ECE__
1 1/
4"3
1/2"
SINGLE OR
DOUBLE ENDWALL
CEE COLUMN
CL
3"B
RA
CIN
G S
LOT
LO
CA
TIO
N
(IF
RE
QU
IRE
D)
RAFTER
SECTION A
CL OF
LS
4"
A
RAFTER SHOWN
(COLUMN SIMILAR)
3"
SINGLE OR
DOUBLE ENDWALL
CEE COLUMN
4"
- 1 1/8" GAGE @ 4" RAFTER FLANGE
- 1 1/2" GAGE @ GREATER THAN 4" RAFTER FLANGE*
ENDWALL PIGGY-BACK CEE
COLUMN TO RAFTER CONNUSE (8) 1/2" Ø X 2" A325 BOLTS H0603 / NUTS H0300
REFERENCE ERECTOR NOTE FOR TYPICAL WASHER REQUIREMENTS
STIFFENER,
IF REQUIRED
**
*
*
1) N/A
Detail Size (W x H) :By :
: CERTIFIED ERECTION DETAILSIssuedIssued
Detailer Notes:
Download the DWG file by clicking here.
POST & BEAM ENDWALLPRIMARY FRAMING
AB0200 - ENDWALL PIGGY-BACK CEE COLUMN TO RAFTER CONN
08.16.19 2018.057SAA
1 x 1
AB0210
SINGLE OR DOUBLE
ENDWALL CEE COLUMN
RAFTER
A
2" 3'-2 1/2"
1 1/4"
3'-2 1/2"1 1/2"
1 1/2"
7'-0"2"
SECTION A
1 1/2"
RAFTER
CL OF 4"LS
3"
4"
3"B
RA
CIN
G S
LOT
LO
CA
TIO
N
(IF
RE
QU
IRE
D)
T-CLIP
MK. ECE__
ENDWALL PIGGY-BACK CEE
COLUMN TO RAFTER CONNLAPPED COLD-FORM RAFTER
USE (8) 1/2" Ø X 2" A325 BOLTS H0603 / NUTS H0300
REFERENCE ERECTOR NOTE FOR TYPICAL WASHER REQUIREMENTS
BOLTS REQUIRED ONLY AS SHOWN, NOT @ ALL HOLES
3 1/2"
(6) 1/2" Ø X 2" A325
BOLTS H0603 / NUTS H0300
(AT RAFTER LAP ONLY)
1) N/A
Detail Size (W x H) :By :
: CERTIFIED ERECTION DETAILSIssuedIssued
Detailer Notes:
Download the DWG file by clicking here.
POST & BEAM ENDWALLPRIMARY FRAMING
AB0210 - ENDWALL PIGGY-BACK CEE COLUMN TO RAFTER CONN
08.16.19 2018.057SAA
1 x 1
AB0220
SINGLE OR DOUBLE
ENDWALL CEE COLUMN
A
BR
AC
ING
SLO
T L
OC
AT
ION
(IF
RE
QU
IRE
D)
1 1/2"
3"
1 1/2"
1 1/4"
3 1/2"
3"
4"
SECTION A
CLIP MK. EWA01
T-CLIP
MK. ECE__
RAFTER
1 1/2"
L OF
RAFTER
C 4"SL
2"
ENDWALL PIGGY-BACK CEE
COLUMN TO RAFTER CONNSINGLE COLD-FORM RAFTER
USE (10) 1/2" Ø X 2" A325 BOLTS H0603 / NUTS H0300
REFERENCE ERECTOR NOTE FOR TYPICAL WASHER REQUIREMENTS
1) N/A
Detail Size (W x H) :By :
: CERTIFIED ERECTION DETAILSIssuedIssued
Detailer Notes:
Download the DWG file by clicking here.
POST & BEAM ENDWALLPRIMARY FRAMING
AB0220 - ENDWALL PIGGY-BACK CEE COLUMN TO RAFTER CONN
08.16.19 2018.057SAA
1 x 1
AB0230
C 4"
2"
1 1/2"
RAFTER
L OFSL
1/4" 1/4"
1'-9"1 1/2"1 1/2" 1'-9"
A
SECTION A
3 1/2"
1 1/4"
3"
4"
CLIP MK. EWA__
RAFTER
BR
AC
ING
SLO
T L
OC
AT
ION
(IF
RE
QU
IRE
D)
3"
SINGLE OR DOUBLE
ENDWALL CEE COLUMN
T-CLIP
MK. ECF__
ENDWALL PIGGY-BACK CEE
COLUMN TO RIDGE RAFTER CONNCOLD FORM RIDGE RAFTER CONNECTION
USE (12) 1/2" Ø X 2" A325 BOLTS H0603 / NUTS H0300
REFERENCE ERECTOR NOTE FOR TYPICAL WASHER REQUIREMENTS
1) N/A
Detail Size (W x H) :By :
: CERTIFIED ERECTION DETAILSIssuedIssued
Detailer Notes:
Download the DWG file by clicking here.
POST & BEAM ENDWALLPRIMARY FRAMING
AB0230 - ENDWALL PIGGY-BACK CEE COLUMN TO RIDGE RAFTER CONN
08.16.19 2018.057SAA
1 x 1
AB0240
SINGLE OR DOUBLE
ENDWALL CEE COLUMN
RAFTER
3"A
BR
AC
ING
SLO
T L
OC
AT
ION
(IF
RE
QU
IRE
D)
3 1/2"
1 1/4"
3"
SECTION A
4"
S
RAFTER
L OFC 4"L
T-CLIP
MK. ECE__
- 1 1/8" GAGE @ 4" RAFTER FLANGE
- 1 1/2" GAGE @ GREATER THAN 4" RAFTER FLANGE*
ENDWALL PIGGY-BACK CEE
COLUMN TO RAFTER CONNCONTINUOUS BUILT-UP / HOT-ROLLED RAFTER
USE (8) 1/2" Ø X 2" A325 BOLTS H0603 / NUTS H0300
REFERENCE ERECTOR NOTE FOR TYPICAL WASHER REQUIREMENTS
*
*
STIFFENER,
IF REQUIRED
1) N/A
Detail Size (W x H) :By :
: CERTIFIED ERECTION DETAILSIssuedIssued
Detailer Notes:
Download the DWG file by clicking here.
POST & BEAM ENDWALLPRIMARY FRAMING
AB0240 - ENDWALL PIGGY-BACK CEE COLUMN TO RAFTER CONN
08.16.19 2018.057SAA
1 x 1
AB0250
A 3"
SECTION ABR
AC
ING
SLO
T L
OC
AT
ION
(IF
RE
QU
IRE
D)
SINGLE OR DOUBLE
ENDWALL CEE COLUMN 4"
3 1/2" T-CLIP
MK. ECF__
1 1/4"
3"
1/4" 1/4"RAFTER
RAFTER
CL OF 4"LS
1 1/2" 1 1/2"
ENDWALL PIGGY-BACK CEE
COLUMN TO RIDGE RAFTER CONNBUILT-UP / HOT-ROLLED RIDGE RAFTER CONNECTION
USE (8) 1/2" Ø X 2" A325 BOLTS H0603 / NUTS H0300
REFERENCE ERECTOR NOTE FOR TYPICAL WASHER REQUIREMENTS
*
**
- 1 1/8" GAGE @ 4" RAFTER FLANGE
- 1 1/2" GAGE @ GREATER THAN 4" RAFTER FLANGE
1) N/A
Detail Size (W x H) :By :
: CERTIFIED ERECTION DETAILSIssuedIssued
Detailer Notes:
Download the DWG file by clicking here.
POST & BEAM ENDWALLPRIMARY FRAMING
AB0250 - ENDWALL PIGGY-BACK CEE COLUMN TO RIDGE RAFTER CONN
08.16.19 2018.057SAA
1 x 1
EW COL TO RAFTER CONN
AB0510
ENDWALL RAFTER
1'-4"
LS
1/4"
1 1/2"
LS
4"
RAFTER
OFCL
SECTION A
A2"
1 1/2"
REFERENCE ERECTOR NOTE FOR TYPICAL WASHER REQUIREMENTS
ENDWALL
COLUMN
ENDWALL
COLUMN
CLIP MK. EWA01
(6) 1/2"Ø X 2"
A325 BOLTS H0603
NUTS H0300
1) N/A
Detail Size (W x H) :By :
: CERTIFIED ERECTION DETAILSIssuedIssued
Detailer Notes:
Download the DWG file by clicking here.
POST & BEAM ENDWALLPRIMARY FRAMING
AB0510 - EW COL TO RAFTER CONN
08.16.19 2018.057SAA
1 x 1
EW COL TO RAFTER CONN
AB0515
A
SECTION A
2"
1 1/2"
1/4"
LS
1 1/2"
RAFTER
OF
LS
CL
SEE_PLAN
SEE_PLAN
REFERENCE ERECTOR NOTE FOR TYPICAL WASHER REQUIREMENTS
ENDWALL COLUMN
(6) 1/2"Ø X 2"
A325 BOLTS H0603
NUTS H0300
ENDWALL COLUMN
CLIP MK. EWA01
RAFTER
SL TO FACE OF COLUMN
FRAME OFFSET
1) N/A
Detail Size (W x H) :By :
: CERTIFIED ERECTION DETAILSIssuedIssued
Detailer Notes:
Download the DWG file by clicking here.
POST & BEAM ENDWALLPRIMARY FRAMING
AB0515 - EW COL TO RAFTER CONN
08.16.19 2018.057SAA
1 x 1
1 1/
2"
SECTION A
A
STEEL LINE
1 1/2" 1 1/2"
C OFLRAFTER
2"
1 1/
2"
2"
4"
STEEL LINE
EW COLUMN TO RAFTER AT MASONRY
AB0516COLUMN TOP CLIP FACTORY WELDED TO COLUMN
REFERENCE ERECTOR NOTE FOR TYPICAL WASHER REQUIREMENTS
REFERENCE ROOF FRAMING PLAN FOR EAVE PURLIN BOLT REQUIRMENTS
CLIP MK. GXC__
WITH (6) 1/2" x 2"
A325 BOLTS (MK. H0603)
AND NUTS (MK. H0300)
COLD-FORMED
ENDWALL RAFTER
CLIP MK. EWA01
WITH (6) 1/2" x 2"
A325 BOLTS (MK. H0603)
AND NUTS (MK. H0300)
WALL SYSTEM BY OTHERS
ENDWALL COLUMN
FACE OF COLUMNSEE_PLAN
SEPERATE DETAIL INCLUDED
FOR EAVE MEMBER
ATTACHMENT INFORMATION.
(SEE ROOF PLAN)
Detail Size (W x H) :By :
: CERTIFIED ERECTION DETAILSIssuedIssued
Detailer Notes:
Download the DWG file by clicking here.
POST & BEAM ENDWALLPRIMARY FRAMING
AB0516 -LOW EAVE COL. CF RAFTER @ MASONRY WALL (COL. ROT. 90 DEG)
08.16.19 2018.057SAA
1 x 1
1) DETAILER MUST CREATE SPECIAL DETAIL FOR EAVE STRUT CONN. AND PLACE CALL OUT ON ROOF
PLAN. DETAIL TO INCLUDE: GXC- PART MARK & ATTACHING HARDWARE MARKS & QUANTITY.
EW COLUMN TO RAFTER AT MASONRY
AB0517COLUMN TOP CLIP FACTORY WELDED TO COLUMN
REFERENCE ERECTOR NOTE FOR TYPICAL WASHER REQUIREMENTS
REFERENCE ROOF FRAMING PLAN FOR EAVE PURLIN BOLT REQUIRMENTS
1 1/
2"
SECTION A
A
STEEL LINE
1 1/2"1 1/2"
C OFLRAFTER
2"
1 1/
2"
2"
4"
STEEL LINE
1'-4"
CLIP MK. GXC__
WITH (4) 1/2" x 2"
A325 BOLTS (MK. H0603)
AND NUTS (MK. H0300)
COLD-FORMED
ENDWALL RAFTER
CLIP MK. EWA01
WITH (6) 1/2" x 2"
A325 BOLTS (MK. H0603)
AND NUTS (MK. H0300)
WALL SYSTEM
BY OTHERS
ENDWALL COLUMN
SEPERATE DETAIL INCLUDED
FOR EAVE MEMBER
ATTACHMENT INFORMATION.
(SEE ROOF PLAN)
1) DETAILER MUST CREATE SPECIAL DETAIL FOR EAVE STRUT CONN. AND PLACE CALL OUT ON ROOF
PLAN. DETAIL TO INCLUDE: GXC- PART MARK & ATTACHING HARDWARE MARKS & QUANTITY.
Detail Size (W x H) :By :
: CERTIFIED ERECTION DETAILSIssuedIssued
Detailer Notes:
Download the DWG file by clicking here.
POST & BEAM ENDWALLPRIMARY FRAMING
AB0517 - LOW EAVE COL. CF RAFTER @ MASONRY WALL (COL. ROT. 90 DEG)
08.16.19 2018.057SAA
1 x 1
EW COL TO RAFTER CONN
AB0530(SIMPLE SPAN RAFTER)
REFERENCE ERECTOR NOTE FOR TYPICAL WASHER REQUIREMENTS
SECTION A
A1 1/2"
2"
1'-9"
1 1/2"
1/4"
1'-9"C
RAFTER
OFL 4"
SL
ENDWALL
COLUMN
ENDWALL
COLUMN
ENDWALL RAFTER
CLIP MK. EWA02
A325 BOLTS H0603
NUTS H0300
(8) 1/2"Ø X 2"
1) N/A
Detail Size (W x H) :By :
: CERTIFIED ERECTION DETAILSIssuedIssued
Detailer Notes:
Download the DWG file by clicking here.
POST & BEAM ENDWALLPRIMARY FRAMING
AB0530 - CF RAFTERS (SIMPLE SPAN)
08.16.19 2018.057SAA
1 x 1
EW COLUMN TO RAFTER CONN
AB0535(SIMPLE SPAN)
COLUMN TOP CLIP FACTORY WELDED TO COLUMN
REFERENCE ERECTOR NOTE FOR TYPICAL WASHER REQUIREMENTS
A
1'-9"1 1/2"
1/4"
2"
1 1/2"
SECTION A
RAFTER1'-9"
CL OF
LS
BUILT-UP
ENDWALL COLUMN
RAFTER
BUILT-UP
ENDWALL COLUMN
CLIP MK. EWA02
A325 BOLTS H0603
NUTS H0300
(8) 1/2"Ø X 2"
RAFTER
SEE_PLAN
1) N/A
Detail Size (W x H) :By :
: CERTIFIED ERECTION DETAILSIssuedIssued
Detailer Notes:
Download the DWG file by clicking here.
POST & BEAM ENDWALLPRIMARY FRAMING
AB0535 - CF RAFTER (SIMPLE SPAN-COLUMN ROTATED 90 DEG)
08.16.19 2018.057SAA
1 x 1
EW COL TO RAFTER CONN
AB0540(LAPPED RAFTER)
REFERENCE ERECTOR NOTE FOR TYPICAL WASHER REQUIREMENTS
1 1/2"
A
7'-0"
1 1/2"
3'-2 1/2"2"
1 1/2" 3'-2 1/2" 2"
SECTION A
2"
S
RAFTER
OFCL 4"
L
BOLTS REQ'D ONLY AS SHOWN, NOT @ ALL HOLES
ENDWALL
COLUMN ENDWALL
COLUMN
RAFTER
A325 BOLTS H0603
NUTS H0300
(10) 1/2"Ø X 2"
1) N/A
Detail Size (W x H) :By :
: CERTIFIED ERECTION DETAILSIssuedIssued
Detailer Notes:
Download the DWG file by clicking here.
POST & BEAM ENDWALLPRIMARY FRAMING
AB0540 - CF RAFTER (LAPPED)
08.16.19 2018.057SAA
1 x 1
EW COL TO RAFTER CONN
AB0545(CONTINUOUS RAFTER)
REFERENCE ERECTOR NOTE FOR TYPICAL WASHER REQUIREMENTS
SECTION A
A 2"
1 1/2"
RAFTER
C OFL 4"
SL
ENDWALL
COLUMN
ENDWALL
COLUMN
ENDWALL RAFTER
CLIP MK. EWA01
(6) 1/2"Ø X 2"
A325 BOLTS H0603
NUTS H0300
1) N/A
Detail Size (W x H) :By :
: CERTIFIED ERECTION DETAILSIssuedIssued
Detailer Notes:
Download the DWG file by clicking here.
POST & BEAM ENDWALLPRIMARY FRAMING
AB0545 - COLUMN TO CF RAFTER (CONTINUOUS)
08.16.19 2018.057SAA
1 x 1
EW COL TO RAFTER CONN
AB0550REFERENCE ERECTOR NOTE FOR TYPICAL WASHER REQUIREMENTS
1/4"
SL
OFLC
RAFTER
1 1/2"
4"
4"
2"
SECTION A
1 1/2"
A
ENDWALL
COLUMN
CLIP MK. GCB03
REQUIRED @
COLD-FORMED
RAFTERS ONLYA325 BOLTS H0603
NUTS H0300
COLD-FORMED
RAFTER
(2) 1/2"Ø X 2"
A325 BOLTS H0603
NUTS H0300
(4) 1/2"Ø X 2"
ENDWALL
COLUMN
BUILT-UP
RAFTER
COLD-FORMED SHOWN
BUILT-UP SIMILAR
COLD FORMED RAFTER SHOWN ON LEFT SIDE,
BU/HR ON RIGHT. OPPOSITE POSITION SIMILAR.
1) N/A
Detail Size (W x H) :By :
: CERTIFIED ERECTION DETAILSIssuedIssued
Detailer Notes:
Download the DWG file by clicking here.
POST & BEAM ENDWALLPRIMARY FRAMING
AB0550 - INTERMEDIATE COL. CONN. (SIMPLE SPAN W/ BU & CF RAFTERS @ OPP. SIDES)
08.16.19 2018.057SAA
1 x 1
EW COL TO RAFTER CONN
AB0560REFERENCE ERECTOR NOTE FOR TYPICAL WASHER REQUIREMENTS
SL1/4"
OFCL
RAFTER
1 1/2"
4"
4"
2"
SECTION A
A
1 1/2"
ENDWALL
COLUMN
ENDWALL
COLUMN
A325 BOLTS H0603
NUTS H0300
(4) 1/2"Ø X 2"
BUILT-UP
RAFTER
A325 BOLTS H0603
NUTS H0300
(2) 1/2"Ø X 2"
COLD-FORMED
RAFTER
CLIP MK. GCB03
REQUIRED @
COLD-FORMED
RAFTERS ONLY
COLD-FORMED SHOWN
BUILT-UP SIMILAR
1) N/A
Detail Size (W x H) :By :
: CERTIFIED ERECTION DETAILSIssuedIssued
Detailer Notes:
Download the DWG file by clicking here.
POST & BEAM ENDWALLPRIMARY FRAMING
AB0560 - BU RAFTER LEFT CF RAFTER RIGHT
08.16.19 2018.057SAA
1 x 1
EW COL TO RAFTER CONN
AB0590REFERENCE ERECTOR NOTE FOR TYPICAL WASHER REQUIREMENTS
SECTION A
1 1/2"
1'-4"
2"
1 1/2"
A
1/4"
LS
OF
RAFTERLC 4"
SL
A325 BOLTS H0603
NUTS H0300
(6) 1/2"Ø X 2"
RAFTER
ENDWALL
COLUMN
CLIP
MK. EWA01
ENDWALL
COLUMN
SEE SECONDARY DETAILS
FOR HIGH EAVE SUPPORT
MEMBER & CONNECTION
1) N/A
Detail Size (W x H) :By :
: CERTIFIED ERECTION DETAILSIssuedIssued
Detailer Notes:
Download the DWG file by clicking here.
POST & BEAM ENDWALLPRIMARY FRAMING
AB0590 - HIGH EAVE (CF RAFTER)
08.16.19 2018.057SAA
1 x 1
EW COL TO RAFTER (COL ROTATED 90° @ HIGH EAVE)
AB0595REFERENCE ERECTOR NOTE FOR TYPICAL WASHER REQUIREMENTS
SECTION A
1 1/2"
FACE OF COLUMN LS
2"
1 1/2"
A1/4"
OF
RAFTERLC
SL
SEE_PLAN
SEE_PLAN
ENDWALL
COLUMN
A325 BOLTS H0603
NUTS H0300
(6) 1/2"Ø X 2"
RAFTER
CLIP
MK. EWA01
ENDWALL
COLUMN
SEE SECONDARY DETAILS
FOR HIGH EAVE SUPPORT
MEMBER & CONNECTION
1) N/A
Detail Size (W x H) :By :
: CERTIFIED ERECTION DETAILSIssuedIssued
Detailer Notes:
Download the DWG file by clicking here.
POST & BEAM ENDWALLPRIMARY FRAMING
AB0595 - EW COL TO RAFTER (COL ROTATED 90° @ HIGH EAVE)
08.16.19 2018.057SAA
1 x 1
EW COL. TO RAFTER CONN. (HIGH EAVE @ PARAPET BY OTHERS)
AB0598BU OR HR COLUMN TO CEE RAFTER CONNECTION
USE (6) 1/2"Ø x 2" A325 BOLTS (MK. H0603) & NUTS (MK. H0300)
REFERENCE ERECTOR NOTE FOR TYPICAL WASHER REQUIREMENTS
2"
STEEL LINE AND
OUTSIDE FACE OF WALL
ENDWALL STEEL LINE
CENTERLINE
OF RAFTER
PARAPET WALL BY OTHERS
CENTERLINE
OF COLUMN
A
BU OR HR
ENDWALL
COLUMN
1'-4"
COLUMN
EWA01
CLIP
MK. EWA01
RAFTER
1 1/2"
SECTION A
1 1/2"
4"
1 1/2"1 1/2"SINGLE CEE
ENDWALLRAFTER
1) N/A
Detail Size (W x H) :By :
: CERTIFIED ERECTION DETAILSIssuedIssued
Detailer Notes:
Download the DWG file by clicking here.
POST & BEAM ENDWALLPRIMARY FRAMING
AB0598 -EW COLUMN TO RAFTER CONNECTION (HIGH EAVE @ PARAPET BY OTHERS)
08.16.19 2018.057SAA
1 x 1
90° ROTATED EW COL TO RAFTER CONN @ H EAVE (WITH PARAPET)
AB0599BU OR HR COLUMN TO CEE RAFTER CONNECTION
USE (6) 1/2"Ø x 2" A325 BOLTS (MK. H0603) & NUTS (MK. H0300)
REFERENCE ERECTOR NOTE FOR TYPICAL WASHER REQUIREMENTS
2"
STEEL LINE AND
OUTSIDE FACE OF WALL
ENDWALL STEEL LINE
CENTERLINE
OF RAFTER
PARAPET WALL BY OTHERS
OUTSIDE FACE
OF COLUMN
A
BU OR HRENDWALL
COLUMN
COLUMN
EWA01
CLIP
MK. EWA01
1 1/2" 1 1/2"
RAFTER
1 1/2"
SECTION A
1 1/2"
SEE_PLAN
SEE_PLAN
SINGLE CEE
ENDWALLRAFTER
1) N/A
Detail Size (W x H) :By :
: CERTIFIED ERECTION DETAILSIssuedIssued
Detailer Notes:
Download the DWG file by clicking here.
POST & BEAM ENDWALLPRIMARY FRAMING
(AB0599 - 90° ROTATED EW COL TO RAFTER CONN @ H EAVE (WITH PARAPET)
08.16.19 2018.057SAA
1 x 1
EW COL TO CF RAFTER CONN (@ RIDGE)
AB0610REFERENCE ERECTOR NOTE FOR TYPICAL WASHER REQUIREMENTS
RIDGE PURLIN DETAIL
RAFTER
SECTION A
A
1/4" 1/4"
1 1/2"
2"
RIDGEPURLIN
LC OF
USE (8) 1/2" x 1 1/2" A307
BOLT H0500/ NUT H0400 PER
RIDGE PURLIN CONNECTION
1'-9" 1 1/2" 1 1/2" 1'-9"
3"
LS
4"
ENDWALL COLUMN
(8) 1/2"Ø X 2"
A325 BOLTS H0603
NUTS H0300
CLIP
MK. EWA__
COLD-FORMED
RAFTER-TYP.
8" PURLIN
GCB01 CLIP
9.5" PURLIN
GCB08 CLIP
12" PURLIN
GCB11 CLIP
CLIP
MK. EWA01
PURLIN
RAFTER
A
1) N/A
Detail Size (W x H) :By :
: CERTIFIED ERECTION DETAILSIssuedIssued
Detailer Notes:
Download the DWG file by clicking here.
POST & BEAM ENDWALLPRIMARY FRAMING
AB0610 - EW COL TO CF RAFTER CONN (@ RIDGE)
08.16.19 2018.057SAA
1 x 1
RIDGE (BU RAFTER RIGHT, CF RAFTER LEFT)
AB0620REFERENCE ERECTOR NOTE FOR TYPICAL WASHER REQUIREMENTS
1 1/2"1 1/2"
1/4"1/4"
A
LS
OFCL
1 1/2"
RAFTER
4"
2"
SECTION A
4"
CLIP MK. GCB03
REQUIRED @
COLD-FORMED
RAFTERS ONLY
COLD-FORMEDRAFTER
A325 BOLTS H0603
NUTS H0300
(2) 1/2"Ø X 2"
BUILT-UP RAFTER
(4) 1/2"Ø X 2"
A325 BOLTS H0603
NUTS H0300
ENDWALL COLUMN
COLD-FORMED SHOWN
BUILT-UP SIMILAR
1) N/A
Detail Size (W x H) :By :
: CERTIFIED ERECTION DETAILSIssuedIssued
Detailer Notes:
Download the DWG file by clicking here.
POST & BEAM ENDWALLPRIMARY FRAMING
AB0620 - RIDGE (BU RAFTER RIGHT, CF RAFTER LEFT)
08.16.19 2018.057SAA
1 x 1