14
13-1 © 2009 Schneider Electric All Rights Reserved 13 OBSOLESCENT PANELBOARDS Table of Contents Section 13 Obsolescent Panelboards QMB Fusible Panelboards Ready-to-Install (RTI)—600 Vac, 250 Vdc 13-2 Main Switch Replacement Units 13-3 Branch Switch Replacement 13-4 Obsolescent Branch Switch Replacement Units 13-5 Series E1 Motor Starter Replacement Units 13-6 Replacement Parts Trim Clamps and Screws 13-7 Circuit ID Numbers 13-7 Locks 13-7 NQOD Lighting and Appliance Panelboards Series Rated/Fully Rated Tables 13-8 Lighting and Appliance Panelboard Pricing Procedures 13-9 Merchandised 20 Inch Wide Main Lugs Only Panelboards 13-10 Merchandised Accessories 13-11 Merchandised 20 Inch Wide Main Circuit Breaker Panelboards 13-11 NQOD 14-inch Wide Enclosures 13-12 Merchandised Non-Linear Panel (200% rated neutral) 13-13 Terminal Data 13-14

Table of Contents Section 13 - Schneider Electricstatic.schneider-electric.us/assets/sup-obs-digest/obsolescent...Table of Contents Section 13 Obsolescent Panelboards QMB Fusible Panelboards

Embed Size (px)

Citation preview

Page 1: Table of Contents Section 13 - Schneider Electricstatic.schneider-electric.us/assets/sup-obs-digest/obsolescent...Table of Contents Section 13 Obsolescent Panelboards QMB Fusible Panelboards

13-1© 2009 Schneider ElectricAll Rights Reserved

13O

BS

OL

ES

CE

NT

PA

NE

LB

OA

RD

S

Table of Contents

Section 13Obsolescent Panelboards

QMB Fusible PanelboardsReady-to-Install (RTI)—600 Vac, 250 Vdc 13-2

Main Switch Replacement Units 13-3

Branch Switch Replacement 13-4

Obsolescent Branch Switch Replacement Units 13-5

Series E1 Motor Starter Replacement Units 13-6

Replacement PartsTrim Clamps and Screws 13-7

Circuit ID Numbers 13-7

Locks 13-7

NQOD Lighting and Appliance PanelboardsSeries Rated/Fully Rated Tables 13-8

Lighting and Appliance Panelboard Pricing Procedures 13-9

Merchandised 20 Inch Wide Main Lugs Only Panelboards 13-10

Merchandised Accessories 13-11

Merchandised 20 Inch Wide Main Circuit Breaker Panelboards 13-11

NQOD 14-inch Wide Enclosures 13-12

Merchandised Non-Linear Panel (200% rated neutral) 13-13

Terminal Data 13-14

Page 2: Table of Contents Section 13 - Schneider Electricstatic.schneider-electric.us/assets/sup-obs-digest/obsolescent...Table of Contents Section 13 Obsolescent Panelboards QMB Fusible Panelboards

13O

BS

OLE

SC

EN

T P

AN

EL

BO

AR

DS

QMB Fusible Panelboards Ready-to-Install (RTI)—600 Vac, 250 VdcClass 4620

www.schneider-electric.us

QMB Layout Information

Table 13.1: QMB Main Lugs Interiors, Boxes and Fronts

Total Branch UnitMounting

Space (Inches)

AmpereRating

of Mains

$ PriceInterior, Front

and Box (less units)

Component Selection

Box Height (inches)

Box Width (inches)

Interior Assembly—3-pole with Main Lugs Front (4-piece Standard) Box

Catalog No. $ Price Catalog No. $ Price Catalog No. $ Price

60 225 3478. QMB60902 2631. QM38902TS 590. QM3890B

257.

90

3845 400 3954. QMB45754 2894. QM38756TS 803. QM3875B75

45 600 4484. QMB45756 3540. QM38756TS 687. QM3875B

45 800 5448. QMB45908 4304. QM38908TS

887.

QM3890B

257. 90 3845 1200 6313. QMB459012 5169. QM389012TS QM3890B

60 600 6093. QMB60906 4949. QM38906TS QM3890B

Table 13.2: QMB Main Switch Interiors, Boxes and Fronts

Total Branch Unit Mounting

Space(inches)

Ampere Rating of

Mains

Maximum Voltage (ac)

$ PriceInterior, Front

and Box (less units)

Component Selection

Box Height (inches)

Box Width (inches)

Interior Assembly—3-pole with Main Switch Front (4-Piece Standard) Box

Catalog No. $ Price Catalog No. $ Price Catalog No. $ Price

51 200

240

4551. QMB5190324M 3704. QM38902TS 590. QM3890B

257. 90 3845

400 10173. QMB4590325M 9029.QM38906TS 887. QM3890B

600 12118. QMB4590326M 10974.

51 200

600

5332. QMB5190364M 4485. QM38902TS 590. QM3890B

257. 90 3845

400 10834. QMB4590365M 9690.QM38906TS 887. QM3890B

600 12940. QMB4590366M 11796.

Table 13.3: AccessoriesBlanks Solid Neutral Assembly

Height Catalog No. $ Price Ampere Rating Catalog No. $ Price

1.5 QMB1BLW 75. 225 QMB2SN 380.

3 QMB3BLW 80. 400 QMB4SN 477.

6 QMB6BLW 87. 600 QMB6SN 599.

15 QMB15BLW 120. 800 QMB8SN 969.

— — — 1200 QMB12SN 1545.

Note: Equipment Ground Bar—PK32DGTA, price: $104.00

Table 13.4: QMB Branch Circuit Breaker Units 600 Vac

Unit Ampere Rating

Unit Height (Inches) Catalog No. $ Price Description

15–100 6 QMBHWab 1965. Mounts (1) or (2) 3-pole HDL circuit breakers

110–225 6 QMBJWac 2099. Mounts (1) 3-Pole JDL circuit breaker

400 7.5 QMB3400LAWd 5445. Includes (1) 3-Pole LAL circuit breaker

a Circuit breakers not included. Order HDL or JDL circuit breakers from Digest page 7-22.b Order one catalog number S37444 for each circuit breaker.c Order catalog number S37445 with QMBJW.d For trip ratings other than 400 A, contact your nearest Schneider Electric sales office.

Branch Unit

MountingSpace

100 A twin QMB 6 in. H @ 240 V

60 A twin QMB 6 in. H @ 600 V

100 A twin QMJ 6 in. H @ 600 V

100 A twin QMB7.5 in. H @ 600 V

200 A QMB9 in. mounting height,

200 A twin QMJ7.5 in. mounting height

38 in.

30/30 @ 240 V or 600 Vor 60/60 @ 240 Vare 4.5 in. high

Wiring Gutter

400 A QMJ 9 in. H,400 A Class T 9 in. H,

400, 600 or 800 A QMB all require 15 in. H

13-2 © 2009 Schneider ElectricAll Rights Reserved

PE1A Discount Schedule

Page 3: Table of Contents Section 13 - Schneider Electricstatic.schneider-electric.us/assets/sup-obs-digest/obsolescent...Table of Contents Section 13 Obsolescent Panelboards QMB Fusible Panelboards

© 2009 Schneider ElectricAll Rights Reserved

QMB Fusible Panelboards Main Switch Replacement UnitsClass 4620

13O

BS

OL

ES

CE

NT

PA

NE

LB

OA

RD

S

www.schneider-electric.us

Table 13.1: Main Switch Replacement Units (Replaces Series E1)

Ampere Rating

Standard—Class H, R, K Fuse Spacing Class T Fuse Spacing Class J Fuse Spacing

Catalog No. $ Price Catalog No. $ Price Catalog No. $ Price

3-Pole, 240 Vac

100 QMB323MW 2208. — — — —

200 QMB324MW 2208. — — — —

400 QMB325MW 6923. — — — —

600 QMB326MW 8561. — — — —

800 — — — — — —

3-Pole, 600 Vac

100 QMB363MW 2891. — — — —

200 QMB364MW 2891. — — — —

400 QMB365MW 7616.QMB365MWa 7616. QMB365MWa 7616.

QMB400T6 275. QMB400J 530.

600 QMB366MW 9417.QMB366MWa 9416. QMB366MWa 9416.

QMB600T6 291. QMB600J 591.

800 QMB367MW 16974.QMB367MWa 16974.

— —QMB800T6 701.

a Both catalog numbers are required for a complete device.

Example: QMB365MWQMB400T6 constitutes a complete device.

Table 13.2: Main Switch Interior Lug DataMechanical Lugs VCEL Compression Lugs

MainsAmpereRating

ConductorsPer

Phase

Wire RangeWire Bending Space per

NEC Table 373-6Lug Wire Range

ConductorsPer

Phase

Wire RangeWire Bending Space per

NEC Table 373-6Catalog No. Lug Wire Range

200 (1) #6–300 kcmil Al or Cu #6–300 kcmil Al or Cu (1) #4–300 kcmil Al or Cu VCEL030516H1 #4–300 kcmil Al or Cu

400 (2) 3/0–500 kcmil Al or Cu 3/0–600 kcmil Al or Cu (2) 2/0–600 kcmil Al or Cu

VCEL05012H1 2/0–500 kcmil Al or Cu

VCEL06012H1 400–600 kcmil Al or Cu

VCEL07512H1 500–750 kcmil Al

600 (2) 3/0–500 kcmil Al or Cu 3/0–600 kcmil Al or Cu (2) 2/0–500 kcmil Al or Cu VCEL05012H1 3/0–500 kcmil Al or Cu

800b (3) 3/0–500 kcmil Al or Cu 3/0–600 kcmil Al or Cu (3) 2/0–500 kcmil Al or Cu VCEL05012H1 3/0–500 kcmil Al or Cu

b Factory assembled only.

{ {

{ {

{

{

13-3

PE1A Discount Schedule
Page 4: Table of Contents Section 13 - Schneider Electricstatic.schneider-electric.us/assets/sup-obs-digest/obsolescent...Table of Contents Section 13 Obsolescent Panelboards QMB Fusible Panelboards

13O

BS

OLE

SC

EN

T P

AN

EL

BO

AR

DS

QMB Fusible Panelboards Branch Switch ReplacementClass 4620

www.schneider-electric.us

GuidelinesSTEP 1: Determine the panelboard interior type. If the date of manufacture is not known, compare your switch with the pictures below to determine the mounting rail direction. Only mounting rails that face outward will accept the Series D2 switch and its required mounting rail extension bracket.

STEP 2: Order a replacement switch from page 13-5.

Table 13.1: Panelboard InteriorsIllustration No. Interior Catalog No. Prefix Designed For Switch Type Switch Availability/Order Information

1.Type QM

in 31-inch wide boxbuilt before 1961.

Series 1-430–200 A Maximum

NOT AVAILABLESeries D2 switches are not compatible replacements for this application.

2.Type QM

in 31-inch wide boxbuilt after 1961

and before 1984.

Series 1-430–200 A Maximum

NOT AVAILABLEOrder Series D2 switch from page 13-5.

Series D230–200 A Maximum Order Series D2 switch from page 13-5. (Many still stocked in DS.)

3.Type QW

in 38-inch wide boxbuilt before 1984.

Series 1-430–200 A Maximum

NOT AVAILABLEOrder Series D2 switch and plug-on extension assembly from page 13-5.

Series 1-4400–600 A

NOT AVAILABLEQMB3400LA available order only from Lexington.

Series D230–200 A Maximum Order Series D2 switch and plug-on extension assembly from page 13-5.

4.Type QMB

in 35-inch or 38-inch wide boxbuilt after 1984.

Series E1 or E230–800 A Order from Digest page 9-34.

Type QM (31-inch Wide)Manufactured Before 1961

Panelboards manufactured before 1961 have the interior mounting rails facing inward (toward the bus). Switches and circuit breakers that fit in this interior type are obsolete.

Type QM (31-inch Wide)Manufactured After 1961 But Before October 1984

Panelboards manufactured after 1961 have the interior mounting rails facing outward (away from the bus). This interior accepts Series 1-4 switches and Series D2 switches (shown above with required rail extensions). Order the Series D2 switch (includes mounting rail extensions) from page 13-5.

Type QW (38-inch Wide)Manufactured Before 1984

Type QW panelboards were built to accept bolt-on 400 A and 600 A Series 1-4 switches. 30-200 A Series D2 switches may be installed as shown using the plug-on extension assembly from page 13-5.

Type QMB Manufactured After October 1984

Series E1 panelboards will accept only Series E1 or E2 switches. Order from Digest page 9-34.

Mounting rail

Rail extension

Mounting rail

Rail extension

Mounting rail

Plug-on extension

13-4 © 2009 Schneider ElectricAll Rights Reserved

Page 5: Table of Contents Section 13 - Schneider Electricstatic.schneider-electric.us/assets/sup-obs-digest/obsolescent...Table of Contents Section 13 Obsolescent Panelboards QMB Fusible Panelboards

© 2009 Schneider ElectricAll Rights Reserved

QMB Fusible Panelboards Obsolescent Branch Switch Replacement UnitsClass 4620

13O

BS

OL

ES

CE

NT

PA

NE

LB

OA

RD

S

www.schneider-electric.us

30–200 A Obsolescent Switch Units—Series D2Available In DS Stock, except where noted.

All Series D2 switches require that rail extension assemblies be attached to the interior side rails in order to mount the switch. These rail extension assemblies are packaged with every Series D2 switch. If a rail extension is lost or missing, contact your nearest Schneider Electric sales office to order a replacement.Plug-on extension assemblies must also be ordered when installing 30–200 A plug-on units in blank spaces of a QW interior in the 38-inch wide box. These plug-on extension assemblies (which extend the bus) are NOT the same as the rail extension assemblies packaged with every Series D2 switch (which extend only the mounting rails).

Table 13.1: Branch Units—Three Pole

AmpereRating

Unit Height (inches)

Obsolescent aSeries 1–4

Catalog No.

Replaced BySeries D2

Catalog No.$ Price

Class R Fuse Kits

No. Kits Req’d. Catalog No. $ Price

240 Vac

30-30 4.50 QMB3203T QMB321Tb 1139. 2 HRK30 26.

60-60 4.50 QMB306T QMB322TD 1187. 1 QMB36R 49.

100-100 6.00 QMB310T QMB323TD 1808. 1 QMB100R 95.

200 9.00 QMB3220 QMB324 2393. 1 HRK1020 48.

600 Vac

30-30 4.50 QMB3603T QMB361Tb1763. 1 QMB36R 49.

30-30 6.00 QMB362T1

60-60 6.00 QMB3606T QMB362T 1763. 1 QMB60R 49.

100-100 7.50 QMB3610T QMB363T 2795. 2HRK1020 48.

200 9.00 QMB3620 QMB364 3297. 1

a These switch units are no longer available; the catalog number is provided only for cross referencing to Series D2 units.b When this Series D2 switch is used as a replacement for a Series 1-4 3-inch switch, a blank filler plate is also required. Purchase the blank filler plate

from a local sheet-metal fabricator. If a drawing of this part is required, contact Peru TAG.

Table 13.2: Obsolescent Circuit Breaker Units a

Catalog No. $ Price

QMB3400LAb 7097.

a Circuit breaker units are designed for use in all QMB interior types manufactured between 1961 and October 1984.b Includes a 3-pole, LA type circuit breaker. For other ampere ratings, contact the Schneider Electric Customer Information Center.

Table 13.3: Plug-On Extension Assemblies a

Ampere Rating Switch Mounting Height (inches) Catalog No. $ Price

30-30 Switch 3 QMB303LEX 203.

30-30 Switch 4.5 QMB306LEX 207.

30-30 Switch 6 QMB306EX 239.

60-60 Switch 4.5 QMB306LEX 207.

60-60 Switch 6 QMB306EX 239.

100-100 Switch 6 QMB310LEX 239.

100-100 Switch 7.5 QMB310EX 567.

200 Switch 9 QMB320EX567.

LA Circuit Breaker 7.5 QMB310EX

a Bus extensions are required on all 30–200 A switches. They are also required on all circuit breaker units used in switchboards or in QW type panelboards with a 38-inch wide box.

Table 13.4: Obsolescent Main Switch Units a

Ampere Rating Unit Height(inches) Catalog No. $ Price Replaces Series 4

Unit Catalog No.

3-pole 240 Vac

1009

QMB323Mb2303.

QMB3210M

200 QMB324M QMB3220M

3-pole 600 Vac

100 9QMB363Mb 3017. QMB3610M

QMB363MJb 3213. QMB3610MJ

200 9QMB364M 3792. QMB3620M

QMB364MJb 4038. QMB3620MJ

a Replace Series 4 Unitsb Order only from the Lexington plant.

Plug-On ExtensionAssembly

13-5

PE1A Discount Schedule
Page 6: Table of Contents Section 13 - Schneider Electricstatic.schneider-electric.us/assets/sup-obs-digest/obsolescent...Table of Contents Section 13 Obsolescent Panelboards QMB Fusible Panelboards

13O

BS

OLE

SC

EN

T P

AN

EL

BO

AR

DS

QMB Fusible Panelboards Series E1 Motor Starter Replacement UnitsClass 2320

www.schneider-electric.us

ApplicationFor use on three-phase AC systems—208, 240, or 480 volts. UL® Listed.

StartersLine Voltage Type• Non-Reversing—Twin Units

— Sizes 0 through 3—Class 8536, Types SB, SC, SD and SE.• Reversing—Single Units

— Sizes 0 through 3—Class 8736, Types SB, SC, SD and SE.

Selection of Components

1. List required motor starter units (reversing or non-reversing) from the tables above.2. Specify the HP, voltage, phase, frequency and full load current rating of the motor.3. Specify the unit mounting space.4. Determine the circuit breaker or fusible switch rating for motor branch circuits from the selection tables on Digest page 9-34.5. For motor starter voltages other than standard voltages of 120, 208, 240 and 480 volts, contact your nearest Schneider Electric

sales office.

Starter Data• Line voltage coils are furnished as standard on all starters.• Twistouts are provided in starter covers for start-stop push buttons, selector switches and pilot lights. See accessories table below.• Starter door interlocks are furnished with motor starter enclosures.• Type S starter enclosures include drillings for the next smaller size.• All Type S starters have provisions for three overload relay thermal units, as required by NEC® Table 430.37 for three phase ac

motor circuits.

AccessoriesAccessories listed below are available for field installation on all units. Go to the page numbers shown for prices.

QMB Motor Starter Panelboard

Table 13.1: Starter Units—Not stocked in DS. Order only from the Peru plant.

NEMASize

CoilVoltage c

Class 8536—Types SB, SC, SD and SEqType S—Non-Reversing(see Digest page 16-16)

Class 8736—Type SB, SC, SD and SE aReversing

(see Digest page 16-51

UnitHeight

(Inches)

Twin-Starter Unit(Two Non-Reversing Starters) $ Price b

UnitHeight

(Inches)

Single-Starter Unit(One Reversing Starter) $ Price b

Catalog No. Catalog No.

0

120

9

QMBS8536100120W

1931. 9

QMBS873610120W

2115.208 QMBS8536100208W QMBS873610208W

240 QMBS8536100240W QMBS873610240W

480 QMBS8536100480W QMBS873610480W

1

120

9

QMBS8536111120W

2435. 9

QMBS873611120W

2295.208 QMBS8536111208W QMBS873611208W

240 QMBS8536111240W QMBS873611240W

480 QMBS8536111480W QMBS873611480W

2

120

10-1/2

QMBS8536222120W

3813. 10-1/2

QMBS873622120W

3732.208 QMBS8536222208W QMBS873622208W

240 QMBS8536222240W QMBS873622240W

480 QMBS8536222480W QMBS873622480W

3

120

18

QMBS8536333120W

5930. 18

QMBS873633120W

6797.208 QMBS8536333208W QMBS873633208W

240 QMBS8536333240W QMBS873633240W

480 QMBS8536333480W QMBS873633480W

a Space and drilling are provided for field addition of control voltage transformer and fuse base.b Prices include starters, but do not include overload relay thermal units. See Digest page 16-129 for selection procedure (AC magnetic starters—small

enclosure), and order thermal units separately.c See Digest page 16-21 for maximum motor starter ratings.

Table 13.2: UL Listed Short Circuit Ratings @ 600 V Maximum

Starter SizeFusible Switch

(with Class R or J fuse)RMS Sym. Amperes

Thermal-MagneticCircuit Breaker

RMS Sym. Amperes

0

100,000 5,000123

Table 13.3: Field Installable AccessoriesDescription Digest Page No.

Push Buttons and Selector Switches: Class 9001, Type K 19-55 through 19-64Pilot Lights: Class 9001, Type KP 19-65Electrical Interlocks: Class 9999, Type SX6, SX7 16-123Industrial Control Transformers: Class 9070

Supplemental Digest 6-5Type EO1; Starter Size: 0 and 1, Non-ReversingType EO2; Starter Size: 0, 1 and 2, ReversingType EO3; Starter Size: 3Type EO4; Starter Size: 4

Control Circuit Fuse Block: Class 9080, Type PF1 24-20

13-6 © 2009 Schneider ElectricAll Rights Reserved

PE1A Discount Schedule

Page 7: Table of Contents Section 13 - Schneider Electricstatic.schneider-electric.us/assets/sup-obs-digest/obsolescent...Table of Contents Section 13 Obsolescent Panelboards QMB Fusible Panelboards

© 2009 Schneider ElectricAll Rights Reserved

Replacement Parts Trim Clamps and Screws; Circuit I.D. Numbers; LocksClass 1600

13O

BS

OL

ES

CE

NT

PA

NE

LB

OA

RD

S

www.schneider-electric.us

Catalog No. PK3TC

Table 13.1: Trim Clamps and ScrewsApplication Catalog No. $ Price

NEHB Panelboards: All fronts up through 400 A PK3TC 44.

Table 13.2: Circuit I.D. Numbers

Circuit Number DescriptionNEHB and NEHB

Column Width Catalog No.

$ Price

1 through 54 8004332501 14.

Table 13.3: Locks—Type 1 EnclosuresApplication Catalog No. $ Price

NEHB Panelboards

All main lug fronts and all main circuit breaker fronts up to 225 A PK4FL 90.

All 400 A main circuit breaker fronts PK5FL 165.

Telephone Cabinets

Fronts on boxes up to 30 inches wide

PK4FL(Before November 1997)

PK22FL(After November 1997)

90.

Fronts on boxes 36 inches or wider PK5FL 165.

Catalog No. PK4FL

Catalog No. PK5FL

13-7

PE1A Discount

Schedule

Page 8: Table of Contents Section 13 - Schneider Electricstatic.schneider-electric.us/assets/sup-obs-digest/obsolescent...Table of Contents Section 13 Obsolescent Panelboards QMB Fusible Panelboards

13O

BS

OLE

SC

EN

T P

AN

EL

BO

AR

DS

Series Ratings NQOD PanelboardsClass 1630 / Refer to Catalog 1630CT9701

This page contains UL Tested and Certified series combination ratings for panelboards. These ratings apply to either an integral main located

www.schneider-electric.us

in the same enclosure or a remote main located in a separate enclosure. NOTE: Where QO(B) GFI circuit breakers are shown above, QO (B) EPD circuit breakers may also be used.

Table 13.1: NQOD Series RatingsMaximum System Voltage AC c

Maximum Short Circuit Current Rating (RMS Sym.)

Integral or Remote Main Circuit Breakers and Remote Main Fuses

Branch Circuit Breaker Designations and Allowable Ampere Ranges a b

Type 1-pole 2-pole 3-pole

120/240 1Ø

22k MG QO (B) 15–30 A — —42k HD, JD

QO (B) PL 15–30 A 15–60 A 15–30 A65k HG, JG100k HJ, JJ125k HL, JL

120/240 1Ø208Y/120 100k

DJ 400 A

QO (B) 15–70 A 15–125 A —QO (B) GFI 15–30 A 40–60 A —QO (B) VH — 150 A 15–150 AQO (B) AFI 15–20 A — —

QJ

QO (B) 15–70 A 15–125 A 15–30 AQO (B) AS 15–30 A 15–30 A 15–30 AQO (B) GFI 15–30 A 15–60 A —QO (B) PL 15–30 A 15–60 A 15–30 AQO (B) VH — 150 A 35–150 AQO (B) AFI 15–20 A — —

208Y/120 18k LA/LH (L) 34200MC, LA/LH (L) 34225MC,LA/LH (L) 34250MC, LA/LH (L) 34400MC QO (B) 15–30 A 15–30 A 15–30 A

240 22k

QO (B) VH

QO (B) 15–70 A 15–125 A 15–100 AQO (B) AS 15–30 A 15–30 A 15–30 AQO (B) GFI 15–30 A 15–60 A —QO (B) PL 15–30 A 15–30 A —QO (B) AFI 15–20 A — —

Q2-HfQO (B) 15–70 A 15–100 A 15–30 A

QO (B) GFI 15–30 A 15–30 A —QO (B) AFI 15–20 A — —

240 25k

QD

QO (B) 15–70 A 15–125 A 15–30 AQO (B) AS 15–30 A 15–30 A 15–30 AQO (B) GFI 15–30 A 15–60 A —QO (B) PL 15–30 A 15–60 A 15–30 AQO (B) VH — 150 A 35–150 AQO (B) AFI 15–20 A — —

ED, FDfQO (B) 15–70 A 15–125 A 15–100 A

QO (B) GFI 15–30 A 15–60 A —QO (B) AFI 15–20 A — —

KDf

QO (B) 15–70 A 15–125 A 15–100 AQO (B) AS 15–30 A 15–30 A 15–30 AQO (B) GFI 15–30 A 15–60 A —QO (B) AFI 15–20 A — —

HD, JD

QO (B) 15–70 A 15–125 A 15–100 AQO (B) VH — — 35–150 AQO (B) GFI 15–30 A 15–60 A —QO (B) AFI 15–20 A — —QO (B) H — 15–100 A —

QOB2150VH — 150 A —

240 42k

LA, MA Q2L-Hf — 110–225 A 110–225 AQDL — 70–225 A 70–225 A

MG QO (B) VH 15–30 A 15–30 A 15–30 AHD, JD QO (B) PL 15–30 A 15–60 A 15–30 A

LC600 A Maximum

QO (B) 15–70 Ad — —QO (B) VH 15–30 A 15–125 A 15–100 A (3P 208 V Max.)QO (B) GFI 15–30 Ae 15–60 A —QO (B) AFI 15–20 A — —

240 65k

LC600 A Maximum

QO (B) VH 15–30 A 15–125 A 15–100 A (3P 208 V Max.)QO (B) GFI 15–30 Ae — —QO (B) AFI 15–20 A — —

DJ 400 AQO (B) 15–70 A 15–125 A —

QO (B) VH — 150 A 15–150 AQO (B) H — 15–100 A —

EG, FGf, KGfQO (B) 15–70 A 15–125 A 15–100 A

QO (B) GFI 15–30 A 15–60 A —QO (B) AFI 15–20 A — —

QGQO (B) 15–70 A 15–125 A 15–30 A

QO (B) AS 15–30 A 15–30 A 15–30 AQO (B) VH — — 35–150 A

QG, HG, JGQO (B) GFI 15–30 A 15–60 A —QO (B) PL 15–30 A 15–60 A 15–30 AQO (B) AFI 15–30 A — —

HG, JG

QO (B) 15–70 A 15–125 A 15–100 AQO (B) VH — — 35–150 AQO (B) H — 15–100 A —

QOB2150VH — 150 A —FC22__ QO (B) 15–70 A 15–100 A 15–100 AKC22__ QO (B) AS 15–30 A 15–30 A 15–30 AFC32__ QO (B) GFI 15–30 A 15–30 A —KC32__ QO (B) AFI 15–20 A — —

400 A Max. Class J or T6 FusesQO (B) VH 15–30 A 15–125 A 15–100 AQOB-VH — 150 A —

QO (B) AFI 15–20 A — —

240 100k

FC24__ QO (B) 15–70 A 15–100 A 15–100 AKC24__ QO (B) AS 15–30 A 15–30 A 15–30 AFC34__ QO (B) GFI 15–30 A 15–30 A —KC34__ QO (B) AFI 15–20 A — —

200 A Max. Class T3 Fuses QO (B) AFI 15–20 A — —

EJ, FJfQO (B) 15–70 A 15–125 A 15–100 A

QO (B) GFI 15–30 A 15–60 A —QO (B) AFI 15–20 A — —

HJ, JJQO (B) 15–70 A 15–125 A 15–100 A

QO (B) VH — — 35–150 AQO (B) GFI 15–30 A 15–60 A —

240 125k HL. JL

QO (B) PL 15–30 A 15–60 A 15–30 AQO (B) AFI 15–20 A — —QO (B) H — 15–100 A —

QOB2150VH — 150 A —

240 200k

FI, KI

QO (B) 15–70 A 15–125 A 15–100 AQO (B) AS 15–30 A 15–30 A 15–30 AQO (B) GFI 15–30 A 15–60 A —QO (B) AFI 15–20 A — —

Maximum Fuses 200 AClass J or T6 400 A Class T3

QO (B) 15–70 A 15–125 A 15–100 AQO (B) AS 15–30 A 15–30 A 15–30 AQO (B) GFI 15–30 A 15–60 A —

a Suffixes HID, SWD and SWN may also be applied to the applicable branch circuit breakers shown above, except suffix SWN may NOT be applied in combination with LC main circuit breakers.b Where QO (B) circuit breakers are shown above, QO (B) H, QO (B) VH, and QH (B) circuit breakers may also be used.c For shown circuit breakers rated less than this maximum voltage, the indicated short circuit current rating also applies, but at the voltage rating of the circuit breaker.d Only 15–30 A circuit breakers may be used when the LC circuit breaker is rated 450, 500 or 600 A.e Circuit breakers may not be used when the LC circuit breaker is rated 450, 500 or 600 A.f Obsolescent. Contact the Square D/Schneider Electric local Field Sales Office for the replacement circuit breaker. One-pole FJ circuit breakers are still available.

13-8 © 2009 Schneider ElectricAll Rights Reserved

Page 9: Table of Contents Section 13 - Schneider Electricstatic.schneider-electric.us/assets/sup-obs-digest/obsolescent...Table of Contents Section 13 Obsolescent Panelboards QMB Fusible Panelboards

© 2009 Schneider ElectricAll Rights Reserved

NQOD Panelboards Pricing Procedure ExamplesClass 1630 Refer to Catalog 1630CT9701

13O

BS

OL

ES

CE

NT

PA

NE

LB

OA

RD

S

www.schneider-electric.us

NQOD Merchandised Pricing Procedure

1. List circuit breakers required, either plug-on or bolt-on. See appropriate pages for catalog numbers.2. Determine equivalent number of pole spaces required.3. Select proper main lugs interior or main lugs interior and main circuit breaker adapter kit based on equivalent number of poles and ampere rating from appropriate

page. Interiors include solid neutral and are field convertible to top feed.4. Select enclosure from appropriate page.

Type 1—Select box and front catalog number corresponding to interior catalog number. Type 3R, 5, 12—Select enclosure, front included.5. For complete price, add the component prices. Include panelboard accessories.6. Apply appropriate discount schedule.

NQOD Merchandised Example:

Table 13.1: 208Y/120 Vac, 3Ø4W, 10 kAIR, 225 A, MLO, Type 1 surface mount, bolt-on branch circuit breakers, main sub-feed lugs. aBranches Page No. Catalog Number Spaces $ Price

225 A MLO Interior 13-10 NQOD430L225CU 30 1292.

Box 13-10 MH32 — 113.

Cover 13-10 MHC32S — 497.

Main Sub-Feed Lugs 13-10 NQOD225SFL — 203.

Total Price 2105.

a Price branch breakers from page 9-10 of the current Digest.

13-9

Example pricing only Discount

Schedule

Page 10: Table of Contents Section 13 - Schneider Electricstatic.schneider-electric.us/assets/sup-obs-digest/obsolescent...Table of Contents Section 13 Obsolescent Panelboards QMB Fusible Panelboards

13O

BS

OLE

SC

EN

T P

AN

EL

BO

AR

DS

NQOD Merchandised Panelboards

NQOD 20-inch Wide Enclosures—240 Vac, 48 VdcClass 1630 / Refer to Catalog 1630CT9701

www.schneider-electric.us

Table 13.1: Main Lug Interiors—Accepts plug-on and bolt-on circuit breakersMax.

No. of Single Pole

QO/QOB Circuit

Breakers

Mains Rating

Total PriceInterior

Front and Enclosure

Interior Only (Order Branch Circuit Breakers Separately)

Type 1 Enclosure Type 3R, 5, 12 Enclosuref

Box 20"W x 5.75"Db MONO-FLAT® Frontc Enclosure 20"W x 6.5"DHeight

(In.)Type 1 Type 3R, 5,12 Catalog No.a Price Catalog No. Price Catalog No. Price Catalog No. Price

20" Wide Cabinet—Single Phase 3-Wire

20 100 1417. 3050. NQOD20L100CU 864. MH23 113. MHC23 ( ) 440. MH23WP 2186. 2330

225

1789. 3383. NQOD30L225CU 1179. MH32 113. MHC32 ( ) 497. MH32WP 2204. 3242 2037. 3623. NQOD42L225CU 1418. MH35 113. MHC35 ( ) 506. MH35WP 2205. 3542 2464. 4021. NQOD42L225CUTFe 1799. MH41 113. MHC41 ( ) 552. MH41WP 2222. 4154 2278. 3835. NQOD54L225CU 1613. MH41 113. MHC41 ( ) 552. MH41WP 2222. 4130

4002483. 4346. NQOD30L400CU 1737. MH50 113. MHC50V ( ) 633. MH50WP 2609. 50

42 2671. 4512. NQOD42L400CU 1896. MH53 113. MHC53V ( ) 662. MH53WP 2616. 5354 2894. 4737. NQOD54L400CU 2085. MH59 113. MHC59V ( ) 696. MH59WP 2652. 5930

600d

2638. 4605. NQOD30L600 1863. MH53 113. MHC53V ( ) 662. MH656WP 2742. 53/6542 2807. 4767. NQOD42L600 2019. MH56 113. MHC56V ( ) 675. MH686WP 2748. 56/6842 3768. 5699. NQOD42L600TFLe 2942. MH62 113. MHC62V ( ) 713. MH746WP 2757. 62/7454 2991. 4922. NQOD54L600 2165. MH62 113. MHC62V ( ) 713. MH746WP 2757. 62/74

20" Wide Cabinet —Three Phase 4-Wire

24100

1615. 3248. NQOD424L100CU 1062. MH23 113. MHC23 ( ) 440. MH23WP 2186. 2330 1769. 3383. NQOD430L100CU 1191. MH26 113. MHC26 ( ) 465. MH26WP 2192. 2630

225

1902. 3496. NQOD430L225CU 1292. MH23 113. MHC32 ( ) 497. MH32WP 2204. 3242 2170. 3756. NQOD442L225CU 1551. MH35 113. MHC35 ( ) 506. MH35WP 2205. 3542 2567. 4124. NQOD442L225CUTFe 1902. MH41 113. MHC41 ( ) 552. MH41WP 2222. 4154 2378. 3935. NQOD454L225CU 1713. MH41 113. MHC41 ( ) 552. MH41WP 2222. 4130

4002726. 4589. NQOD430L400CU 1980. MH50 113. MHC50V ( ) 633. MH50WP 2609. 50

42 2908. 4749. NQOD442L400CU 2133. MH53 113. MHC53V ( ) 662. MH53WP 2616. 5354 3091. 4934. NQOD454L400CU 2282. MH59 113. MHC59V ( ) 696. MH59WP 2652. 5930

600d

2916. 4883. NQOD430L600 2141. MH53 113. MHC53V ( ) 662. MH656WP 2742. 53/6542 3062. 5022. NQOD442L600 2274. MH56 113. MHC56V ( ) 675. MH686WP 2748. 56/6842 4050. 5981. NQOD442L600TFLe 3224. MH62 113. MHC62V ( ) 713. MH746WP 2757. 62/7454 3279. 5210. NQOD454L600 2453. MH62 113. MHC62V ( ) 713. MH746WP 2757. 62/74

a “CU’’ suffix indicates copper bussing. NQOD RTI interiors with aluminum bus are no longer available. Order the copper bussed equivalent with a "CU" suffix when ordering a replacement interior.b Embossed mounting holes add a .25 inch standoff to back of MH box.c Add “F’’ for flush, “S’’ for surface.d Copper bus standard on 600 A interiors.e Feed-thru lug interior.f Enclosure includes trim kit. g 42 circuit MLO panelboard requires MH38 box, 54 circuit panelboard requires MH44 box.

Table 13.2: NQOD AccessoriesDescription Catalog No. $ Price Schedule

Sub-feed lug kits—main lugs only—1Ø or 3Øg

• 100 A NQOD100SFL 155.00 PE1A• 225 A NQOD225SFL 203.00 PE1ASub-feed: Bolt-on: 2-pole QOB2125SL 176.00 DE2

• 3-pole QOB3125SL 176.00 DE2Equipment ground bars: 12 circuit 225 A max. PK9GTA 13.00 DE3A

• 20 circuit 225 A max. PK12GTA 16.00 DE3A• 24 circuit 225 A max. PK15GTA 17.00 DE3A• 30 circuit 225 A max. PK18GTA 19.00 DE3A• 54 circuit 225 A max. PK23GTA 21.00 DE3A• 54 circuit 600 A max. PK27GTA 34.00 DE3A• PK15GTA with #1 to 4/0 Al/Cu lug PK15GTAL 35.00 DE3A• PK18GTA with #1 to 4/0 Al/Cu lug PK18GTAL 38.00 DE3A• PK23GTA with #1 to 4/0 Al/Cu lug PK23GTAL 41.00 DE3AGround bar insulator kit PKGTAB 44.00 DE3A

Filler plate QOFP 3.60 DE2A

Circuit I.D. number strips1-102 odd/even (left side numbered 1,3,5 ...101) NQ102OE 8.00 PE1A103-204 odd/even (left side numbered 103,105,107 ... 203) NQ204OE 8.00 PE1A1-102 sequential (left side numbered 1,2,3 ... 102) NQ102S 8.00 PE1A103-204 sequential (left side numbered 103,104,105 ... 204) NQ204S 8.00 PE1ADirectory cards 8003115801 5.00 PE1A

Plastic stick-on directory pouch 8003115901 14.00 PE1ALock - for MONO-FLAT fronts PK22FL 93.00 PE1AKey—NSR-251 (for all locks) LP9618 29.00 PE1ATouch-up paint USAS #49 Gray (Aerosol can) PK49SP 39.00 DE1Handle attachments—branch circuit breakers:

• Handle lock-off HLO1 9.90 DE2E• Handle tie - (QO and QOB only) QO1HT 3.80 DE2E• Handle padlock attachment - 1-pole QO1PA 10.70 DE2E• 2- and 3-pole QO1PL 10.70 DE2E• Combination handle tie and lock-off for three 1-pole (QO, QOB) QO3HT 13.40 DE2ENeutral or Ground Lugs: #10 to #2 Al or #14 to #4 Cu QO70AN 9.90 DE2E

• #4 to #1/0 Al/Cu Q1100AN 11.10 DE2E• #1 to #4/0 Al/Cu Q1150AN 32.40 DE2EEndwalls for MH Boxes

• Blank 8011010501 41.00 PE1A• With Knockouts 8011010401 41.00 PE1AElevating Nuts (4 required) 2322000003 1.30 PE1A

NOTE: For Door-in-door (hinged) trim see the Supplemental & Obsolescence Digest, Section 4.

13-10 © 2009 Schneider ElectricAll Rights Reserved

PE1A DE2A DE3A Discount Schedule

Page 11: Table of Contents Section 13 - Schneider Electricstatic.schneider-electric.us/assets/sup-obs-digest/obsolescent...Table of Contents Section 13 Obsolescent Panelboards QMB Fusible Panelboards

© 2009 Schneider ElectricAll Rights Reserved

NQOD Merchandised Panelboards

NQOD 20-inch Wide Enclosures—240 Vac, 48 VdcClass 1630 / Refer to Catalog 1630CT9701

13O

BS

OL

ES

CE

NT

PA

NE

LB

OA

RD

S

www.schneider-electric.us

Table 13.1: Main Circuit Breaker Interiors—Accepts plug-on and bolt-on circuit breakers

Max.No. of

One-pole QO QOB Circuit

Breakers

MainsRating

Total PriceInterior, Front, Box

and Adapter Kit

Main Circuit Breaker

Adapter Kit

Interior Only(Order Branch

Circuit Breakers Separately)

Type 1 Enclosure Type 3R, 5, 12 Enclosure d

Box20"W x 5.75"D b

MONO-FLAT®

Front cEnclosure

20"W x 6.5"D Height (In.)

Type 1 Type 3R, 5, 12

Catalog No. Price Catalog No. a Price Catalog

No. $ Price Catalog No. Price Catalog

No. $ Price

20" Wide Cabinet—Single Phase 3-Wire

20 100 2024. 3638.Factory Installed

Backfed QOB Main Circuit Breaker

NQOD20M100CU 1446. MH26 113. MHC26 ( ) 465. MH26WP 2192. 26

30

225

2662. 4562.NQODQBe

orNQODJKe

$780.

NQOD30L225CU 1179. MH44 113. MHC44 ( ) 590. MH44WP 2603. 44

42 2944. 4807. NQOD42L225CU 1418. MH50 113. MHC50 ( ) 633. MH50WP 2609. 50

42 3367. 5231. NQOD42L225CUTFf 1799. MH56 113. MHC56 ( ) 675. MH56WP 2652. 56

54 3181. 5045. NQOD54L225CU 1613. MH56 113. MHC56 ( ) 675. MH56WP 2652. 56

30

400

3362. 5259.

NQOD4e$780.

NQOD30L400CU 1737. MH65 113. MHC65V ( ) 732. MH65WP 2742. 65

42 3545. 5418. NQOD42L400CU 1896. MH68 113. MHC68V ( ) 756. MH68WP 2742. 68

42 4612. 6479. NQOD42L600TFLf 2942. MH77 113. MHC77V ( ) 777. MH77WP 2757. 77

54 3746. 5622. NQOD54L400CU 2085. MH74 113. MHC74V ( ) 768. MH74WP 2757. 74

20" Wide Cabinet—Three Phase 4-Wire

24100

2437. 4051. Factory Installed Backfed QOB Main

Circuit Breaker

NQOD424M100CU 1859. MH26 113. MHC26 ( ) 465. MH26WP 2192. 26

30 2575. 4178. NQOD430M100CU 1985. MH29 113. MHC29 ( ) 477. MH29WP 2193. 29

30

225

2775. 4675.NQODQBe

orNQODJKe

$780.

NQOD430L225CU 1292. MH44 113. MHC44 ( ) 590. MH44WP 2603. 44

42 3077. 4940. NQOD442L225CU 1551. MH50 113. MHC50 ( ) 633. MH50WP 2609. 50

42 3470. 5334. NQOD442L225CUTFf 1902. MH56 113. MHC56 ( ) 675. MH56WP 2652. 56

54 3281. 5145. NQOD454L225CU 1713. MH56 113. MHC56 ( ) 675. MH56WP 2652. 56

30

400

3605. 5502.

NQOD4e$780.

NQOD430L400CU 1980. MH65 113. MHC65V ( ) 732. MH65WP 2742. 65

42 3782. 5655. NQOD442L400CU 2133. MH68 113. MHC68V ( ) 756. MH68WP 2742. 68

42 4894. 6761. NQOD442L600TFLf 3224. MH77 113. MHC77V ( ) 777. MH77WP 2757. 77

54 3943. 5819. NQOD454L400CU 2282. MH74 113. MHC74V ( ) 768. MH74WP 2757. 74

a “CU’’ suffix indicates copper bussing. NQOD RTI interiors with aluminum bus are no longer available. Order the copper bussed equivalent with a "CU" suffix when ordering a replacement interior.b Embossed mounting holes add a .25 inch standoff to back of MH box.c Add “F’’ for flush, “S’’ for surface.d Enclosure includes trim kit.e Select the appropriate main circuit breaker from tables starting on Digest page 7-22 and add the circuit breaker price to the total price of the panelboard.f Feed-thru lug interior.

Table 13.2: Main Circuit Breaker Adapter Kits (Less Circuit Breaker) a

Amperes Catalog Number CircuitBreaker Frameb $ Price

225 NQODQB QBL, QDL, QGL, QJL

780.225 NQODJK JDL, JGL, JJL, JLL, KIL

400 NQOD4 LAL, LHL, Q4L

a Select the appropriate main circuit breaker from tables starting on Digest page 7-22 and add the circuit breaker price to the total price of the panelboard.b Circuit breaker interrupting ratings, see tables starting on Digest page 7-22.

13-11

PE1A Discount Schedule
Page 12: Table of Contents Section 13 - Schneider Electricstatic.schneider-electric.us/assets/sup-obs-digest/obsolescent...Table of Contents Section 13 Obsolescent Panelboards QMB Fusible Panelboards

13O

BS

OLE

SC

EN

T P

AN

EL

BO

AR

DS

NQOD Merchandised Panelboards

NQOD 14-inch Wide Enclosures—240 Vac, 48 VdcClass 1630 / Refer to Catalog 1630CT9701

www.schneider-electric.us

Table 13.1: Main Lug Interiors—Accepts plug-on and bolt-on circuit breakers

Max.No. ofSingle Pole

QO/QOBCircuit

Breakers

MainsRating

Total $ PriceInterior, Frontand Enclosure

Interior Only(Order Branch Circuit Breakers Separately)

Type 1 Enclosure Type 3R, 5, 12 Enclosure

Box14 in. W x 5.75 in. D b

Mono-Flat®Front c

Enclosure20 in. W x 6.5 in. D

Height(In.)NEMA

Type 1

NEMAType

3R, 5, 12Catalog No. a $ Price Catalog No. $ Price Catalog No. $ Price Catalog No. $ Price

14-inch Wide Cabinet—Single Phase 3-Wire

12100

1132. — NQOD12L100CU 734. NQB520 117. NQC20 ( ) 281. Use 20-inch Wide Enclosurefor Type 3R, 5, 12

20

20 1271. — NQOD20L100CU 864. NQB523 117. NQC23 ( ) 290. 23

30

225

1634. — NQOD30L225CU 1179. NQB532 117. NQC32 ( ) 338.Use 20-inch Wide Enclosure

for Type 3R, 5, 12

32

42 1882. — NQOD42L225CU 1418. NQB535 117. NQC35 ( ) 347. 35

54 2099. — NQOD54L225CU 1613. NQB541 117. NQC41 ( ) 369. 41

14-inch Wide Cabinet—Three Phase 4-Wire

12

100

1267. — NQOD412L100CU 869. NQB520 117. NQC20 ( ) 281.Use 20-inch Wide Enclosure

for Type 3R, 5, 12

20

24 1469. — NQOD424L100CU 1062. NQB523 117. NQC23 ( ) 290. 23

30 1616. — NQOD430L100CU 1191. NQB526 117. NQC26 ( ) 308. 26

30

225

1747. — NQOD430L225CU 1292. NQB532 117. NQC32 ( ) 338.Use 20-inch Wide Enclosure

for Type 3R, 5, 12

32

42 2015. — NQOD442L225CU 1551. NQB535 117. NQC35 ( ) 347. 35

54 2199. — NQOD454L225CU 1713. NQB541 117. NQC41 ( ) 369. 41

a “CU’’ suffix indicates copper bussing. NQOD RTI interiors with aluminum bus are no longer available. Order the copper bussed equivalent with a "CU" suffix when ordering a replacement interior.b 14-inch wide cabinets accept 100 A max. branch circuit breakers. Through feed lugs are not available in 14-in. wide enclosures.c Add “F’’ for flush, “S’’ for surface.

Table 13.2: Main Circuit Breaker Interiors—Accepts Plug-On and Bolt-On Circuit BreakersMax.

No. ofOne PoleQO

QOBCircuit

Breakers

MainsRating

Total $ PriceInterior, Front, Box

and Adapter Kit

Main Circuit BreakerAdapter Kit

Interior Only(Order Branch Circuit Breakers Separately)

Type 1 Enclosure Type 3R, 5, 12 Enclosure

Box14 in. W x 5.75 in. Dd

Mono-FlatFront b

Enclosure20 in. W x 6.5 in. D

Height(In.)NEMA

Type 1

NEMAType

3R, 5, 12Catalog No. $ Price Catalog No. a $ Price Catalog No. $ Price Catalog No. $ Price Catalog No. $ Price

14-inch Wide Cabinet—Single Phase 3-Wire

12100

1688. — Factory InstalledQOB

Main Circuit Breaker—

NQOD12M100CU 1281. NQB523 117. NQC23 ( ) 290. Use 20-inch Wide Enclosurefor Type 3R, 5, 12

23

20 1871. — NQOD20M100CU 1446. NQB526 117. NQC26 ( ) 308. 26

30

225

2481.NQODJKc

orNQODQBc

780.

NQOD30L225CU 1179. NQB544 117. NQC44 ( ) 405.Use 20-inch Wide Enclosure

for Type 3R, 5, 12

44

42 2734. — NQOD42L225CU 1418. NQB550 117. NQC50 ( ) 419. 50

54 2984. — NQOD54L225CU 1613. NQB556 117. NQC56 ( ) 474. 56

14-inch Wide Cabinet—Three Phase 4-Wire

12

100

2032. —Factory Installed

QOB Main Circuit Breaker

NQOD412M100CU 1625. NQB523 117. NQC23 ( ) 290.Use 20-inch Wide Enclosure

for Type 3R, 5, 12

23

24 2284. — NQOD424M100CU 1859. NQB526 117. NQC26 ( ) 308. 26

30 2431. — NQOD430M100CU 1985. NQB529 117. NQC29 ( ) 329. 29

30

225

2594. —NQODJKc

orNQODQBc

780.

NQOD430L225CU 1292. NQB544 117. NQC44 ( ) 405.Use 20-inch Wide Enclosure

for Type 3R, 5, 12

44

42 2867. — NQOD442L225CU 1551. NQB550 117. NQC50 ( ) 419. 50

54 3084. — NQOD454L225CU 1713. NQB556 117. NQC56 ( ) 474. 56

a “CU’’ suffix indicates copper bussing. NQOD RTI interiors with aluminum bus are no longer available. Order the copper bussed equivalent with a "CU" suffix when ordering a replacement interior.b Add “F’’ for flush, “S’’ for surface.c Select the appropriate main circuit breaker from pages 7-24, 7-31, 7-48 and 7-49, and add the circuit breaker price to the total price of the panelboard. d 14-inch wide cabinets accept 100 A max. branch circuit breakers.

Table 13.3: Main Circuit Breaker Adapter Kits (Less Circuit Breaker a)

Amperes Catalog No. CircuitBreaker Frame b

$ Price

225 NQODQB QBL, QDL, QGL, QJL780.

225 NQODJK JDL, JGL, JJL, JLL, KIL

a Select the appropriate main circuit breaker from pages 7-24, 7-31, 7-48 and 7-49, and add the circuit breaker price to the total price of the panelboard. b Circuit breaker interrupting ratings, see pages 7-2 through 7-9.

13-12 © 2009 Schneider ElectricAll Rights Reserved

PE1A Discount Schedule

Page 13: Table of Contents Section 13 - Schneider Electricstatic.schneider-electric.us/assets/sup-obs-digest/obsolescent...Table of Contents Section 13 Obsolescent Panelboards QMB Fusible Panelboards

© 2009 Schneider ElectricAll Rights Reserved

NQOD Merchandised Panelboards

For Non-Linear Loads (200% Rated Neutral)Class 1630 / Refer to Catalog 1630CT9701

13O

BS

OL

ES

CE

NT

PA

NE

LB

OA

RD

S

www.schneider-electric.us

NQOD 240 Vac Max.

Table 13.1: Main Lug Interiors—Accepts plug-on and bolt-on circuit breakers

Max. No. of

Single Pole QO/QOB Circuit

Breakers

Mains Rating

Total PriceInterior,

Front and Enclosure

Main Lugs Interior Only(Order Branch Circuit Breakers Separately)

Type 1 Enclosure Type 3R, 5, 12 Enclosure d

Box 20"W x 5.75"D b MONO-FLAT® Front c Enclosure20"W x 6.5"D Height

(In.)Type 1 Type

3R, 5, 12 Catalog No. a $ Price Catalog No. $ Price Catalog No. $ Price Catalog No. $ Price

20" Wide Cabinet—3 Phase 4-Wire

30 100 2096. 3699. NQOD430L100CUNL 1506. MH29 113. MHC29 ( ) 477. MH29WP 2193. 29

42 225 2620. 4193. NQOD442L225CUNL 1977. MH38 113. MHC38 ( ) 530. MH38WP 2216. 38

42 400 3547. 5388. NQOD442L400CUNL 2772. MH53 113. MHC53V ( ) 662. MH53WP 2616. 53

a “CU’’ suffix indicates copper bussing. NQOD RTI interiors with aluminum bus are no longer available. Order the copper bussed equivalent with a "CU" suffix when ordering a replacement interior.b Embossed mounting holes add a .25 inch standoff to back of MH box.c Add “F’’ for flush, “S’’ for surface.d Enclosure includes trim kit.

Table 13.2: Main Circuit Breaker Interiors

Max. No. of

Single Pole QO/QOB Circuit

Breakers

Mains Rating

Total PriceInterior, Front, Box and

Adapter Kit

Main Circuit Breaker

Adapter Kit a

Main Lugs Interior Only (Order Branch Circuit Breakers Separately)

Type 1 Enclosure Type 3R, 5, 12 Enclosure d

Box 20"W x 5.75"D MONO-FLAT Front c Enclosure

20"W x 6.5"D Height (In.)

Type 1 Type 3R, 5, 12

Catalog No.$ Price Catalog No. b $ Price Catalog No. $ Price Catalog No. $ Price Catalog No. $ Price

20" Wide Cabinet—3 Phase 4-Wire

30 100 2877. 4471. QOB Main Circuit Breaker NQOD430M100CUNL 2267. MH32 113. MHC32 ( ) 497. MH32WP 2204. 32

42 225 3503. 5366.NQODJK NQODQB

780.NQOD442L225CUNL 1977. MH50 113. MHC50 ( ) 633. MH50WP 2609. 50

42 400 4421. 6294. NQOD4780. NQOD442L400CUNL 2772. MH68 113. MHC68V ( ) 756. MH68WP 2742. 68

a Order main circiut breaker separatelyb “CU’’ suffix indicates copper bussing. NQOD RTI interiors with aluminum bus are no longer available. Order the copper bussed equivalent with a "CU" suffix when ordering a replacement interior.c Add “F’’ for flush, “S’’ for surface.d Enclosure includes trim kit.

Table 13.3: Main Circuit Breaker Adapter Kits (Less Circuit Breaker) aAmperes Catalog Number Circuit Breaker Frame b $ Price

225 NQODQB QBL, QDL, QGL, QJL

780.225 NQODJK JDL, JGL, JJL, JLL, KIL

400 NQOD4 LAL, LHL

a Order main circiut breaker separatelyb Main neutral conductors must be copper or aluminum conductors of minimum size and quantity shown to maintain UL Listing.

Table 13.4: NQOD Main Neutral Conductors—Required Size and Quantity a

Panelboard Ampacity Neutral Conductors Requiredb Actual Lug Wire Range

100/125 (2) 1/0 Cu or Al (2) #4–300 kcmil

225 (2) 4/0 Cu or (2) 300 kcmil Al (2) #4–300 kcmil

400

(4) 3/0 Cu or(4) 250 kcmil Al(2) 600 kcmil Cu(2) 750 kcmil Al

(2) 1/0–300 kcmil or(1) 750 kcmil

a Neutral conductors must be of size and quantity per table above.b Main neutral conductors must be copper or aluminum conductors of minimum size and quantity shown to maintain UL Listing. Requirement is based on heat rise testing.

13-13

PE1A Discount

Schedule

Page 14: Table of Contents Section 13 - Schneider Electricstatic.schneider-electric.us/assets/sup-obs-digest/obsolescent...Table of Contents Section 13 Obsolescent Panelboards QMB Fusible Panelboards

13O

BS

OLE

SC

EN

T P

AN

EL

BO

AR

DS

NQOD Panelboards Terminal DataClass 1630 / Refer to Catalog 1630CT9701

www.schneider-electric.us

Table 13.1: Standard Mechanical Lugs—Main Lugs

Panel Type Ampere Rating Lug Wire Rangea Wire RangeWire Bending Space per NEC Table 373-6a

NQOD

100 (1) #10–#2/0 Cu or (1) #6–#2/0 Al (1) #10–#1 Cu or (1) #6–#1 Al

225 (1) #6–300 kcmil Al/Cu (1) #6–300 kcmil Al/Cu

400 (2) #1/0–300 kcmil Al/Cu or (1) #1/0–750 kcmil Al/Cu (2) #1/0–300 kcmil Al/Cu or (1) #1/0–750 kcmil Al/Cu

600 (2) #4-600 kcmil (2) #4-500 kcmil

a (#) = Number of conductors per phase.

Table 13.2: Standard Mechanical Lugs—Main Circuit Breaker

Panel Type Ampere Rating Circuit Breaker Type Lug Wire Rangeb Wire Range

Wire Bending Space per NEC Table 373-6b

NQOD

100 QOB (1) #4–#2/0 Al/Cu (1) #4–#1 Al/Cu

100 FA, FH, FI (1) #14–#1/0 Al/Cu (1) #14–#1 Al/Cu

150 HD, HG, HJ, HL (1) #14–#3/0 Al/Cu (1) #14–#3/0 Al/Cu

225 QB, QD, QG, QJ (1) #4–300 kcmil Al/Cu (1) #4–300 kcmil Al/Cu

225 KI (1) #6–350 kcmil Al/Cu (1) #4–300 kcmil Al/Cu

250 JD, JG, JJ, JL (1) #1/0–#4/0 Al/Cu or (1) #3/0–350 kcmil Al/Cu (1) #1/0–300 kcmil Al/Cu

400 LA, LH (1) #1–600 kcmil Al/Cu or (2) #1–250 kcmil Al/Cu (1) #4–500 kcmil Al/Cu or (2) #1–250 kcmil Al/Cu

600 MA (3) #3/0–500 kcmil (3) #3/0–500 kcmil

b (#) = Number of conductors per phase.

13-14 © 2009 Schneider ElectricAll Rights Reserved