(TAL) FAC-008-3 Facility Ratings March 31, 2016 Rev. No. Date Description By Approval 25 3/31/2016 Updated Per Power Engineering Review Power Eng. Clint Smith 24 1/8/2016 Updated Per Power Engineering Review Power Eng. Clint Smith 23 9/15/2015 Updated Per Power Engineering Review Power Eng. Ray Mitchel 22 7/24/2015 Updated Per Power Engineering Review Power Eng. Brian Horton 21 1/29/2015 Updated Per Power Engineering Review Power Eng. Brian Horton 20 7/25/2014 Updated Per Power Engineering Review Power Eng. Brian Horton 19 6/16/2014 Updated Per Power Engineering Review Power Eng. Brian Horton 18 3/4/2014 Updated Per Power Engineering Review Power Eng. Brian Horton 17 11/8/2013 Updated Per Power Engineering Review Power Eng. Brian Horton 16 9/26/2013 Updated Per Power Engineering Review Power Eng. Brian Horton 15 6/21/2013 Updated Per Power Engineering Review Power Eng. Brian Horton 14 4/4/2013 Updated Per Progress Energy Work Power Eng. Brian Horton 13 3/8/2013 Updated Per Progress Energy Work Power Eng. Brian Horton 12 2/20/2013 Updated Per Power Engineering Review Power Eng. Brian Horton 11 12/28/2012 Updated Per Power Engineering Review Power Eng. Brian Horton 10 11/7/2012 Updated Per Power Engineering Review Power Eng. Brian Horton 9 8/29/2012 Updated Per Annual Review Power Eng. Brian Horton 8 5/24/2012 Updated Per Power Engineering Review Power Eng. BH 7 5/4/2012 Updated Per Power Engineering Review Power Eng. BH 6 2/8/2012 Updated Per Power Engineering Review Power Eng. BH 5 1/19/2012 Updated Per Power Engineering Review Power Eng. BF 4 5/7/2010 Updated Per Power Engineering Review Power Eng. BF 3 - Updated Per Power Engineering Review Power Eng. BF 2 12/9/2008 Creation of SOP for FAC-009-01 Power Eng. BF 1 5/10/2007 Original Reported Ratings Planning AG Revision Tracking: Revision 8: Revision 9: Revision 10: Revision 11: Revision 12: Revision 13: Revision 14: Revision 15: Revision 16: Revision 17: Add BP17 substation and make TX line 53/54 split modifications as required. Revision 18: Revision 19: Revision 20: Revision 21: Revision 22: Revision 23: Revision 24: Revision 25: Complete Line 2A, 2B, 2C Disconnect Upgrade Work. Removed Purdom Unit 7 from Service. Add 2 STG Note. Remove Line 15A from service. Remove line 32B wavetrap from service. Updated ratings for switching station disconnect per manufactuerer. Add diagram for transformer bay. Revise various items to coordinate with field documentation. Revise Breaker Tap Wire/Bus to Bus. Revise bus rating from line rating to full available rating of bus for document standardization. Added Line 34 & Line 35 data. Added BP4 Autotransformer Bay Data. Remove old BP4 Cap Bank Rating. Add BP4 230KV CCVT data. Added footnote one to Transmission Data for Lines 15B and 34. Created Line Tie Rating Tool. Remove Line 17-Line 16 tap from service. Revised Line 15A data for t-line reconductor project completion. Removed unused transient ratings for old lines 15A & 15C. Report Hopkins 2A CTG neutral disconnect per as-built documentation. Overhead transmission line conductor ratings revised to IEEE 738-2006. Line 31 line trap ratings revised per field nameplate. Reformatted BP4 and BP1; Line 19a, Line 19b, Line 16, and Line 17 bay data fromats. Report transient ratings per FAC008 Rev. 7 for lines 15A, 15B, and 15C. Added clarification that CH2 & CH3 are connected in parrallel. Clarified Line 53 note 8. Clarified Run, Start, and AUX transformers. Revised breaker/switch labels to match field/scada for Line 53/54 BP21 bay. Added BP9 expansion, BP7 expansion, BP14, BP21, & WS CCVT Data. Added BP14 Capacitor Bank Data. Revised HC1 & HC2 cable bus rating per asbuilts. Revised Labels to Match FAC008 Labels. Revised to show: new substation BP3; new breaker at BP7 (230KV Ring Expansion); correct breaker label at BP9; new breaker at BP9 (115KV Ring Expansion); ratings per field data for GSU#5 & AUTO1&2 disconnects; ratings per asbuilt data for Hopkins Conductors #2; ratings per field verificatino for Hopkins 1 - 1&2 autottransformer connections; capacitance per field verification for Hopkins GSU#5; clarified transformer types; added Hopkins AUX transformer ratings; and revised Purdom 8 STG Isophase and cable bus ratings. Complete Line 2A, 2B, 2C Disconnect Repair Work. Temp value for Line 2A, 2B, 2C; due to disconnect failure. Removed old 15C, 16, & 17 T-Line ratings. Updated for T-Line 15B reconductor. Removed unused transient ratings for old lines 15B. Removed old BP4 CCVT data. Revised bay data for BP4 reconstruction and Line 15C data for t-line reconductor. Added Line 21 transient ratings. PP7 removed from service. Relabled some transformers to match SCADA name labels. Revised underground non-XLPE cable (LINE 13A&B; LINE 19A&B) EM rating to match methodology. Revised LINE 20B rating due to PROGRESS ENERGY work at Bradfordville Substation. Revised LINE 20B rating due to PROGRESS ENERGY work at Bradfordville Substation. Revised title to reflect new standard requirements. Revised summer and winter ratings for lines 13A&B and lines 19A&B per manufacturer. Revised notes per field conditions. Added VA line ratings for reference. EM Ratings have been rounded down. Removed Purdom low side, 69KV (non BES), ratings. Rounded data values down. Increased Gen. Nameplate Amp Data by 1A for HC3&4 to reflect actual nameplate data. Revised LINE 31 EM Winter rating to disconnect rating. Removed TIE data. Deleted Note 3. Added Note 8 callout to Line 52. Added BP5 new transformer bay data. Added SME Signoff. Data values highlighted in light gray are not required to be reported per COT methodology. They will remain on this excel spreadsheet for reference and general use, but they will not be issued on the official PDF document. Add BP32 transmission line station and Line 33. Added BP5 capacitor bank.

(TAL) FAC-008-3 Facility Ratings March 31, 2016Mar 31, 2016  · Report Hopkins 2A CTG neutral disconnect per as-built documentation. Overhead transmission line conductor ratings revised

  • Upload
    others

  • View
    3

  • Download
    0

Embed Size (px)

Citation preview

Page 1: (TAL) FAC-008-3 Facility Ratings March 31, 2016Mar 31, 2016  · Report Hopkins 2A CTG neutral disconnect per as-built documentation. Overhead transmission line conductor ratings revised

(TAL)FAC-008-3 Facility Ratings

March 31, 2016

Rev.No. Date Description By Approval25 3/31/2016 Updated Per Power Engineering Review Power Eng. Clint Smith24 1/8/2016 Updated Per Power Engineering Review Power Eng. Clint Smith23 9/15/2015 Updated Per Power Engineering Review Power Eng. Ray Mitchel22 7/24/2015 Updated Per Power Engineering Review Power Eng. Brian Horton21 1/29/2015 Updated Per Power Engineering Review Power Eng. Brian Horton20 7/25/2014 Updated Per Power Engineering Review Power Eng. Brian Horton19 6/16/2014 Updated Per Power Engineering Review Power Eng. Brian Horton18 3/4/2014 Updated Per Power Engineering Review Power Eng. Brian Horton17 11/8/2013 Updated Per Power Engineering Review Power Eng. Brian Horton16 9/26/2013 Updated Per Power Engineering Review Power Eng. Brian Horton15 6/21/2013 Updated Per Power Engineering Review Power Eng. Brian Horton14 4/4/2013 Updated Per Progress Energy Work Power Eng. Brian Horton13 3/8/2013 Updated Per Progress Energy Work Power Eng. Brian Horton12 2/20/2013 Updated Per Power Engineering Review Power Eng. Brian Horton11 12/28/2012 Updated Per Power Engineering Review Power Eng. Brian Horton10 11/7/2012 Updated Per Power Engineering Review Power Eng. Brian Horton9 8/29/2012 Updated Per Annual Review Power Eng. Brian Horton8 5/24/2012 Updated Per Power Engineering Review Power Eng. BH7 5/4/2012 Updated Per Power Engineering Review Power Eng. BH6 2/8/2012 Updated Per Power Engineering Review Power Eng. BH5 1/19/2012 Updated Per Power Engineering Review Power Eng. BF4 5/7/2010 Updated Per Power Engineering Review Power Eng. BF3 - Updated Per Power Engineering Review Power Eng. BF2 12/9/2008 Creation of SOP for FAC-009-01 Power Eng. BF1 5/10/2007 Original Reported Ratings Planning AG

Revision Tracking:

Revision 8:

Revision 9:

Revision 10:

Revision 11:

Revision 12:

Revision 13:

Revision 14:

Revision 15:

Revision 16:

Revision 17: Add BP17 substation and make TX line 53/54 split modifications as required.

Revision 18:

Revision 19:

Revision 20:

Revision 21:

Revision 22:

Revision 23:

Revision 24:

Revision 25:

Complete Line 2A, 2B, 2C Disconnect Upgrade Work.

Removed Purdom Unit 7 from Service. Add 2 STG Note. Remove Line 15A from service. Remove line 32B wavetrap from service. Updated ratings for switching station disconnect per manufactuerer. Add diagram for transformer bay. Revise various items to coordinate with field documentation.

Revise Breaker Tap Wire/Bus to Bus. Revise bus rating from line rating to full available rating of bus for document standardization. Added Line 34 & Line 35 data. Added BP4 Autotransformer Bay Data. Remove old BP4 Cap Bank Rating. Add BP4 230KV CCVT data. Added footnote one to Transmission Data for Lines 15B and 34. Created Line Tie Rating Tool. Remove Line 17-Line 16 tap from service.

Revised Line 15A data for t-line reconductor project completion. Removed unused transient ratings for old lines 15A & 15C.

Report Hopkins 2A CTG neutral disconnect per as-built documentation. Overhead transmission line conductor ratings revised to IEEE 738-2006. Line 31 line trap ratings revised per field nameplate. Reformatted BP4 and BP1; Line 19a, Line 19b, Line 16, and Line 17 bay data fromats. Report transient ratings per FAC008 Rev. 7 for lines 15A, 15B, and 15C.

Added clarification that CH2 & CH3 are connected in parrallel. Clarified Line 53 note 8. Clarified Run, Start, and AUX transformers. Revised breaker/switch labels to match field/scada for Line 53/54 BP21 bay. Added BP9 expansion, BP7 expansion, BP14, BP21, & WS CCVT Data. Added BP14 Capacitor Bank Data. Revised HC1 & HC2 cable bus rating per asbuilts. Revised Labels to Match FAC008 Labels.

Revised to show: new substation BP3; new breaker at BP7 (230KV Ring Expansion); correct breaker label at BP9; new breaker at BP9 (115KV Ring Expansion); ratings per field data for GSU#5 & AUTO1&2 disconnects; ratings per asbuilt data for Hopkins Conductors #2; ratings per field verificatino for Hopkins 1 - 1&2 autottransformer connections; capacitance per field verification for Hopkins GSU#5; clarified transformer types; added Hopkins AUX transformer ratings; and revised Purdom 8 STG Isophase and cable bus ratings.

Complete Line 2A, 2B, 2C Disconnect Repair Work.

Temp value for Line 2A, 2B, 2C; due to disconnect failure.

Removed old 15C, 16, & 17 T-Line ratings. Updated for T-Line 15B reconductor. Removed unused transient ratings for old lines 15B. Removed old BP4 CCVT data.

Revised bay data for BP4 reconstruction and Line 15C data for t-line reconductor. Added Line 21 transient ratings. PP7 removed from service. Relabled some transformers to match SCADA name labels.

Revised underground non-XLPE cable (LINE 13A&B; LINE 19A&B) EM rating to match methodology.

Revised LINE 20B rating due to PROGRESS ENERGY work at Bradfordville Substation.

Revised LINE 20B rating due to PROGRESS ENERGY work at Bradfordville Substation.

Revised title to reflect new standard requirements. Revised summer and winter ratings for lines 13A&B and lines 19A&B per manufacturer. Revised notes per field conditions. Added VA line ratings for reference. EM Ratings have been rounded down. Removed Purdom low side, 69KV (non BES), ratings.

Rounded data values down. Increased Gen. Nameplate Amp Data by 1A for HC3&4 to reflect actual nameplate data. Revised LINE 31 EM Winter rating to disconnect rating. Removed TIE data. Deleted Note 3. Added Note 8 callout to Line 52. Added BP5 new transformer bay data. Added SME Signoff. Data values highlighted in light gray are not required to be reported per COT methodology. They will remain on this excel spreadsheet for reference and general use, but they will not be issued on the official PDF document.

Add BP32 transmission line station and Line 33. Added BP5 capacitor bank.

Page 2: (TAL) FAC-008-3 Facility Ratings March 31, 2016Mar 31, 2016  · Report Hopkins 2A CTG neutral disconnect per as-built documentation. Overhead transmission line conductor ratings revised

CITY OF TALLAHASSEE (TAL)GENERATOR DATA

Run or Auxiliary Isophase Bus Disconnects and Cable

BES CONTINUES

RUN AUX Alternate Transformer Start TransformerPLANT OR PLANT SWITCHYARD OR PLANT

PLANT GENSET GENSET GENSET GENSET

PT Weakest ElementRating Voltage Voltage Amps Amps Rating

Station Name Unit Voltage Amps KVA Voltage Amps P.F. Voltage Amps Voltage Amps Voltage Amps/ Conductor Voltage MVA Voltage Amps KVA Pri Sec Pri Sec KVA Voltage Amps Type Voltage Amps KCMIL Voltage Amps KVA Voltage Amps Type Element (Amps)

Purdom 8 CTG 18000 2000 211765 18000 6792 0.85 NA 8000/5 NA NA 24000 7000 18000/120 NA NA NA 192000 112125 17100 989 6483 NA NA NA NA NA NA NA NA NA NA NA NA NA Main Power Transformer 6483

Purdom 8 STG NA NA 106000 13800 4435 0.85 NA 6000/5 NA NA 15000 5000 14400/120 1000 13800 5000 107000 112125 13200 551 4680 14000 13530/4160 597.4/1943 AUX NA NA 250 15000 5000 10000 117875/4160 36.7/[email protected] ALT Generator Nameplate 4435

Purdom GT1 NA NA 17647 12470 817 0.85 NA 1200/5 NA NA 150001 14803 14400/120 NA 12500 1200 20800 116000 12000 104 1001 500 12470/480 23.1/601.4 AUX 15000 600 750MCM 15000 6053 750 4160/480 104.1/908.1 ALT Generator Nameplate 817

Purdom GT 2 NA NA 17647 12470 817 0.85 NA 1200/5 NA NA 150001 14803 14400/120 NA 12500 1200 20800 116000 12000 104 1001 500 12470/480 23.1/601.4 NA4 15000 600 750MCM 15000 6053 750 4160/480 104.1/908.1 START Generator Nameplate 817

Hopkins HP1 14400 600 88235 13800 3692 0.85 NA 5000/5 13800 4500 13800 4500 14400/120 NA NA NA 104534 116000 13200 520 4572 9375 13200/4160 410/1300 RUN 13800 600 NA 13800 600 9375 115000/4160 47.1/1301 START Generator Nameplate 3692

Hopkins 2 STG 5 15000 600 305000 22000 8004 0.85 NA 10000/5 NA NA 22000 9000 14400/120 NA NA NA 280000 116000 20950 1394 7717 37333 21450/4160 1005/2591 RUN NA NA NA 22000 1200 37333 116000/4160 185.8/2591 START Main Power Transformer 7717

Hopkins 2A CTG 12000 400 234000 18000 7506 0.85 NA 9000/5 NA NA 29500 8000 18000/120 NA NA NA 225000 236000 18000 550 7217 NA NA NA NA NA NA NA NA NA NA NA NA NA Main Power Transformer 7217

Hopkins HC1 13800 600 19200 13800 803 0.85 NA 1200/5 NA NA 150001 1755 14400/120 500 13800 1200 25000 116000 13200 124 1093 150 13800/480 6.3/180 AUX NA NA #4/0 13800/480 6.3/180 NA NA NA NA Generator Nameplate 803

Hopkins HC2 NA NA 31765 13800 1329 0.85 NA 2000/5 NA NA 150001 2340 14400/120 500 13800 2000 40000 116000 13200 199 1750 225 13800/480 9.5/2703 AUX NA NA 500 13800/480 9.5/2703 NA NA NA NA Generator Nameplate 1329

Hopkins HC3 NA NA 71200 13800 2978 0.85 NA 3000/5 NA NA 138002 3000 14400/120 1500 13800 3000 60000 120750 13800 287 2510 2500 13800/480 105/3007 AUX NA NA #4/0 13800/480 140/3007 NA NA NA NA Main Power Transformer 2510

Hopkins HC4 NA NA 71200 13800 2978 0.85 NA 3000/5 NA NA 138002 3000 14400/120 1500 13800 3000 60000 120750 13800 287 2510 2500 13800/480 105/3007 AUX NA NA #4/0 13800/480 140/3007 NA NA NA NA Main Power Transformer 2510

1 Cable2 Non-segmented bus3 Calculated4 Unit 2 AUX transformer out of service indefinitely use 750KVA as Aux or start and run

Note: HP1 and HP2 (Steam T/G) have two power transformers at ratings shown above.Note: CH2 & CH3 are connected in parrallel

Revision Tracking:

5 Hopkins Unit 2 steam turbine has a GE7FA gas turbine and a HRSG with duct burners for combined cycle operation with an available physical supply capacity equivalent to 186 KVA (re: Sargent & Lundy Heat Balance Diagram, Case 16, 25 degrees F, dated 6/2006, 158MW @ .85PF). Future repowering projects may supply additional physical capacity up to the generator electrical capacity nameplate rating.

Run or Auxiliary Transformer

Isophase DisconnectRating Isophase or Cable Bus Rating Disconnect Rating

Generator Step-Up TransformerGenerator Neutral

Ground Disconnect Start or Alternate Transformer

CT Rating Generator Breaker Rating Bus/Cable RatingNameplate Rating

Page 3: (TAL) FAC-008-3 Facility Ratings March 31, 2016Mar 31, 2016  · Report Hopkins 2A CTG neutral disconnect per as-built documentation. Overhead transmission line conductor ratings revised

City of Tallahassee (TAL)Transmission Conductor Information

Bus Breaker 1 Disconnect Switch 1 Circuit Breaker 1 Breaker 1 Disconnect Switch 2 Line Disconnect Switch Breaker 2 Disconnect Switch 1 Circuit Breaker 2 Breaker 2 Disconnect Switch 2 Wave Trap Transmission Line Conductor Breaker 1 Disconnect Switch 1 Circuit Breake

Line Substation Rating Rating Rating CT Max Rating Rating Rating Rating CT Max Rating Rating Line Conductor Rating (Amps) 5 Rating RatingName Name Type & Size (Amps) Name (Amps) Name (Amps) Ratio Name (Amps) Name (Amps) Name (Amps) Name (Amps) Ratio Name (Amps) (Amps) Name Type Summer Winter Name (Amps) Name (Amps)

1A BP 5 3" AL BUS 1890 506W 1600 BP506 2000 2000:5 MR 506E 1600 5-1A-D 1600 505S 1600 BP505 2000 2000:5 MR 505N 1600 NA 1A 477 ACSR9 763 956 101BN 2000 PP101 20001B BP 1 3" AL BUS 1890 105B 1200 BP105 2000 2000:5 MR NA NA 105L 1200 NA NA NA NA NA NA NA NA 1B 477 ACSR9 763 956 501E 1600 BP501 20002A SW STA NA NA NA NA NA NA NA NA NA SW-2A-D 2000 NA NA NA NA NA NA NA NA 2A 477 ACSR9 763 956 103BN 2000 PP103 20002B BP 6 2 1/2" AL BUS 1550 605B 1200 BP605 2000 2000:5 MR NA NA 605L 1200 NA NA NA NA NA NA NA NA 2B 477 ACSR9 763 956 NA NA NA NA2C BP 5 3" AL BUS 1890 501W 1600 BP501 2000 2000:5 MR 501E 1600 5-2C-D 1600 502N 1600 BP502 2000 2000:5 MR 502S 1600 NA 2C 477 ACCR9 1145 1145 NA NA NA NA

3A-N BP 11 3" AL BUS 1890 1102BN 1200 BP1102 2000 2000:5 MR 1102BS 1200 11-3A-D 1200 1101BE 1200 BP1101 2000 2000:5 MR 1101BW 1200 NA 3A-N 477 ACSR9 763 956 NA NA NA NA3A-S WT NA NA NA NA NA NA NA NA NA SW-3AS-D 2000 NA NA NA NA NA NA NA NA 3A-S 477 ACSR9 763 956 104BS 2000 PP104 20003A WT NA NA NA NA NA NA NA NA NA SW-3AE-D 2000 NA NA NA NA NA NA NA NA 3A 477 ACSR9 763 956 WS1-BE 2000 WS1 20003B BP 31 3" AL BUS 1890 3107BE 1200 BP3107 2000 2000:5 MR 3107BW 1200 31-3B-D 1200 3106BW 1200 BP3106 2000 2000:5 MR 3106BE 1200 NA 3B 336 ACSR9 611 764 1103BE 1200 BP1103 20003C BP3 3-1/2" AL BUS 2170 307BE 2000 BP307 2000 2000:5 MR 307BW 2000 3-3C-D 2000 308BE 2000 BP308 2000 2000:5 MR 307BW 2000 NA 3C 795 ACSR/477 ACCR9 1057 1290 3101BE 1200 BP3101 20005 HOPKINS 3" AL BUS 1890 110BW 2000 HP110 2000 2000:5 MR 110BE 2000 5-D 2000 109BW 2000 HP109 2000 2000:5 MR 109BE 2000 NA 5 795 ACSR9 1057 1325 303BE 2000 BP303 2000

6A HOPKINS 3" AL BUS 1890 107BE 2000 HP107 2000 2000:5 MR 107BW 2000 6A-D 2000 106BW 2000 HP106 2000 2000:5 MR 106BE 2000 NA 6A 795 ACSR9 1057 1325 3105BW 1200 BP3105 20007A BP 10 3" AL BUS 1890 1002BW 2000 BP1002 2000 2000:5 MR 1002BE 2000 10-7A-D 1600 1001BN 2000 BP1001 2000 2000:5 MR 1001BS 2000 NA 7A 954 ACSR9 1155 1448 111BE 2000 HP111 20007B BP 10 3" AL BUS 1890 1004BN 2000 BP1004 2000 2000:5 MR 1004BS 2000 10-7B-D 1600 10-D3 OR 1002BE 2000 BP1002 2000 2000:5 MR 1002BW 2000 NA 7B 954 ACSR9 1155 1448 801BN 1200 BP801 20007C BP 7 3" AL BUS 1890 708BE 2000 BP708 2000 2000:5 MR 708BW 2000 7-7C-D 1200 707BW 2000 BP707 2000 2000:5 MR 707BE 2000 NA 7C 954 ACSR9 1155 1448 807BN 1200 BP807 200010 BP 6 2 1/2" AL BUS 1550 603B 1200 BP603 2000 2000:5 MR NA NA 603L 1200 NA NA NA NA NA NA NA NA 10 795 ACSR9 1057 1325 3102BE 1200 BP3102 200011 BP3 3-1/2" AL BUS 2170 305BN 2000 BP305 2000 2000:5 MR 305BS 2000 3-11-D 2000 307BE & SW-D3 2000 BP307 2000 2000:5 MR 307BW 2000 NA 11 795 ACSR9 1057 1325 103B 1200 BP103 2000

12A BP 2 1-1/2" CU BUS 1445 201B 1200 BP201 2000 2000:5 MR NA NA 201L 1200 NA NA NA NA NA NA NA NA 12A 336 ACSR9 611 764 305BS 2000 BP305 200012B BP 2 1-1/2" CU BUS 1445 203B 1200 BP203 2000 2000:5 MR NA NA 203L 1200 NA NA NA NA NA NA NA NA 12B 336 ACSR9 611 764 3101BE 1200 BP3101 200013A BP 2 1-1/2" CU BUS 1445 NA NA BP204 2000 2000:5 MR 204B 1200 NA NA NA NA NA NA NA NA NA NA 13A 250 CU7 351 351 NA NA NA NA13B BP 2 1-1/2" CU BUS 1445 NA NA BP205 2000 2000:5 MR 205B 1200 NA NA NA NA NA NA NA NA NA NA 13B 250 CU7 351 351 NA NA NA NA14 BP 1 3" AL BUS 1890 106B 1200 BP106 2000 2000:5 MR NA NA 106L 1200 NA NA NA NA NA NA NA NA 14 795 ACSR9 1057 1325 601B 1200 BP601 2000

15B 1 BP 9 3" AL BUS 1890 901BW 1200 BP906 2000 2000:5 MR 901BE 1200 9-15B-D 1200 905BN 1200 BP905 2000 2000:5 MR 905BS 1200 NA 15B 1 954 ACSR / 477 ACCR9 1155 1290 508N 1600 BP508 200015C BP 4 4" AL BUS 2460 404N 2000 BP404 2000 2000:5 MR 404S 2000 4-15C-D 2000 405E 2000 BP405 2000 2000:5 MR 405W 2000 NA 15C 954 ACSR / 477 ACCR9 1155 1290 903BN 2000 BP903 200016 BP 12 3" AL BUS 1890 1204BE 1200 BP1204 2000 1600:5 MR 1204BW 1200 12-16-D 1200 1201BE 2000 1201 2000 2000:5 MR 1201BW 2000 NA 16 795 ACSR9 1057 1325 401N 2000 401 200017 BP 7 3" AL BUS 1890 7011BE 2000 BP7011 2000 2000:5 MR 7011BW 2000 7-17-D 1600 707BE 2000 BP707 2000 2000:5 MR 707BW 2000 NA 17 795 ACSR9 1057 1325 402E 2000 402 2000

18A BP 15 3" AL BUS 1890 1501BS 2000 BP1501 2000 2000:5 MR 1501BN 2000 15-18A-D 2000 1504BS 2000 BP1504 2000 2000:5 MR 1504BN 2000 NA 18A 795 ACSS9 1316 1524 508N 1600 BP508 200019A BP 19 3" AL BUS 1890 1901B 1200 BP1901 2000 2000:5 MR NA NA 1901L 1200 NA NA NA NA NA NA NA NA 19A 750 CU7 630 630 104B 1200 BP104 200019B BP 19 3" AL BUS 1890 1903B 1200 BP1903 2000 2000:5 MR NA NA 1903L 1200 NA NA NA NA NA NA NA NA 19B 750 CU7 630 630 107B 1200 BP107 200020A BP 16 NA NA 1601BN 2000 BP1601 2000 1600:5 MR 1601BS 2000 16-20A-D3 2000 NA NA NA NA NA NA NA NA 20A 795 ACSR9 1057 1325 706BE 1600 BP706 200020B BP 16 NA NA 1601BN 2000 BP1601 2000 1600:5 MR 1601BS 2000 1601BN 2000 NA NA NA NA NA NA NA NA 20B 795 ACSR9 1057 1325 Note 4 Note 4 Note 4 Note 421 BP 31 3" AL BUS 1890 3108BS 2000 BP3108 2000 2000:5 MR 3108BN 2000 31-21-D 2000 3107BW 1200 BP3107 2000 2000:5 MR 3107BE 1200 NA 21 336 ACSR9 611 764 Note 4 Note 4 Note 4 Note 4

31N HOPKINS 4" AL BUS 2460 238BW 2000 HP237 2000 2000:5 MR 238BE 2000 31-D 2000 235BN 2000 HP235 2000 2000:5 MR 235BS 2000 NA 31N 1590 ACSR9 1590 1995 NA NA NA NA31S BP32 4" AL BUS 2460 NA NA NA NA NA NA NA 3202L 2000 NA NA BP3202 2000 2000:5 MR 3202B 2000 2000 31S 1590 ACSR9 1590 1995 Note 4 Note 4 Note 4 Note 4

33 BP32 4" AL BUS 2460 NA NA NA NA NA NA NA 3203L 2000 NA NA BP3203 2000 2000:5 MR 3203B 2000 NA 33 954 ACSR9 1155 1448 5021-BN 2000 BP5021 200032A BP 20 4" AL BUS 2460 2003BN 2000 BP2003 1600 1600:5 MR 2003BS 2000 20-32A-D 2000 2002BS 2000 BP2002 1600 1600:5 MR 2002BN 2000 NA 32A 954 ACSR9 1155 1448 233BE 1600 HP233 200032B BP 20 4" AL BUS 2460 2002BN 2000 BP2002 1600 1600:5 MR 2002BS 2000 20-32B-D 2000 2001BS 2000 BP2001 1600 1600:5 MR 2001BN 2000 NA 32B 954 ACSR9 1155 1448 Note 4 Note 4 Note 4 Note 432C BP 20 4" AL BUS 2460 2001BN 2000 BP2001 1600 1600:5 MR 2001BS 2000 20-32C-D 2000 2003BS 2000 BP2003 1600 1600:5 MR 2003BN 2000 NA 32C 954 ACSR9 1155 1448 7020E 2000 BP7020 160052 8 BP 9 3" AL BUS 1890 906BW 2000 BP906 2000 2000:5 MR 906BE 2000 9-52-D 2000 903BN 2000 BP903 2000 2000:5 MR 903BS 2000 NA 52 8 954 ACSR8 1155 1448 2102BN 2000 BP2102 200053 8 BP17 3-1/2" AL BUS 2170 1701BN 2000 BP1701 2000 2000:5 MR 1701BS 2000 17-53-D 2000 1707BW 2000 BP1707 2000 2000:5 MR 1707BE 2000 NA 53 8 954 ACSR8 1155 1448 2107BN 2000 BP2107 200054 8 BP14 4" AL BUS 2460 1407BW 2000 BP1407 2000 2000:5 MR 1407BE 2000 14-54-D 2000 1405BS 2000 BP1405 2000 2000:5 MR 1405BN 2000 NA 54 8 954 ACSR8 1155 1448 1704BW 2000 BP1704 200034 1 BP 4 4" AL BUS 2460 432W 2000 BP432 2000 2000:5 MR 4-34-D 2000 NA NA NA NA NA NA NA NA NA NA 34 1 954 ACSR9 1155 1448 510S 1600 BP510 200035 BP 4 4" AL BUS 2460 431W 2000 BP431 2000 2000:5 MR 4-35-D 2000 NA NA NA NA NA NA NA NA NA NA 35 954 ACSR9 1155 1448 7022BW 2000 BP7022 2000

1 Spans of 795ACCR conductor have been installed in both lines. Since the rating of this conductor is above the ratings of the listed conductors, these spans do not affect the rating of the overall line.2 NOT USED3 NOT USED4 This table provides Facility Ratings only for TAL's solely and jointly owned Facilities that are existing Facilities, new Facilities, modifications to existing Facilities and re-ratings of existing Facilities. The Facility Ratings for Facilities owned by other entities will be rated by those entities.5 Refer to FAC008 section 2 for ratings methodology6 NOT USED7 Oil Insulated Underground Cable8 FOR POTENTIAL FUTURE UPGRADES TO LINE 52, 53, & 54: these lines will be permanently limited by their Underground sections which have the following ratings: SUMMER NORMAL - 1212A (95 deg F); WINTER NORMAL - 1448A (40 deg F); SUMMER/WINTER EMERGENCY - 1520A.9 Rating per FAC008 & IEEE 738 - (VERSION 2006)General Note: Refer to FAC008 for breaker jumper ratings

Revision Tracking:Revision 25: New value for Line 2A, 2B, 2C; due to disconnect repair.

Page 4: (TAL) FAC-008-3 Facility Ratings March 31, 2016Mar 31, 2016  · Report Hopkins 2A CTG neutral disconnect per as-built documentation. Overhead transmission line conductor ratings revised

Southernmost/Westernmost Substation Termination

r 1 Breaker 1 Disconnect Switch 2 Line Disconnect Switch Breaker 2 Disconnect Switch 1 Circuit Breaker 2 Breaker 2 Disconnect Switch 2 Bus

CT Max Rating Rating Rating Rating CT Max Rating Rating Substation LineRatio Name (Amps) Name (Amps) Name (Amps) Name (Amps) Ratio Name (Amps) Type & Size (Amps) Name Name Element (Amps) Element (Amps) Element (Amps) Element (Amps)

2000:5 MR 101BS 2000 1A-D 1200 110BW 2000 PP110 2000 2000:5 MR 110BE 2000 4" AL BUS 2460 PURDOM 1A Conductor 763 Conductor 801 Conductor 956 Conductor 10032000:5 MR 501W 1600 5-1B-D 1600 510N 1600 BP510 2000 2000:5 MR 510S 1600 3" AL BUS 1890 BP 5 1B Conductor 763 Conductor 801 Conductor 956 Conductor 10032000:5 MR 103BS 2000 2A-D 2000 102BS 2000 PP102 2000 2000:5 MR 102BN 2000 4" AL BUS 2460 PURDOM 2A Conductor 763 Conductor 801 Conductor 956 Conductor 1003

NA NA NA SW-2B-D 2000 NA NA NA NA NA NA NA NA NA SW STA 2B Conductor 763 Conductor 801 Conductor 956 Conductor 1003NA NA NA SW-2C-D 2000 NA NA NA NA NA NA NA NA NA SW STA 2C Conductor 1145 Line Disc 1202 Conductor 1145 Line Disc 1202NA NA NA SW-3AN-D 2000 NA NA NA NA NA NA NA NA NA WT 3A-N Conductor 763 Conductor 801 Conductor 956 Conductor 1003

2000:5 MR 104BN 2000 3A-D 1200 105BW 2000 PP105 2000 2000:5 MR 105BE 2000 4" AL BUS 2460 PURDOM 3A-S Conductor 763 Conductor 801 Conductor 956 Conductor 10032000:5 MR WS1-BW 2000 NA NA SW-WS-BP 2000 NA NA NA NA NA NA 1890 WS 3A Conductor 763 Conductor 801 Conductor 956 Conductor 10032000:5 MR 1103BW 1200 11-3B-D 1200 1102BN 1200 BP1102 2000 2000:5 MR 1102BS 1200 3" AL BUS 1890 BP 11 3B Conductor 611 Conductor 641 Conductor 764 Conductor 8022000:5 MR 3101BW 1200 31-3C-D 1200 3102BW 1200 BP3102 2000 2000:5 MR 3102BE 1200 3" ALUM BUS 1890 BP 31 3C Conductor 1057 Conductor 1109 Bkr Disc 1200 Bkr Disc 12002000:5 MR 303BW 2000 3-5-D 2000 302BE 2000 BP302 2000 2000:5 MR 302BW 2000 3-1/2" AL BUS 2170 BP 3 5 Conductor 1057 Conductor 1109 Conductor 1325 Conductor 13912000:5 MR 3105BE 1200 31-6A-D 1200 3106BE 1200 BP3106 2000 2000:5 MR 3106BW 1200 3" ALUM BUS 1890 BP 31 6A Conductor 1057 Conductor 1109 Bkr Disc 1200 Bkr Disc 1200600:5 MR 111BW 2000 7A-D 2000 110BW 2000 HP110 2000 2000:5 MR 110BE 2000 3" AL BUS 1890 HOPKINS 7A Conductor 1155 Conductor 1212 Conductor 1448 Conductor 1520

1600:5 MR 801BS 1200 8-7B-D 1200 802BW 1200 BP802 2000 2000:5 MR 802BE 1200 3" AL BUS 1890 BP 8 7B Conductor 1155 Bkr Disc 1200 Bkr Disc 1200 Bkr Disc 12002000:5 MR 807BS 1200 8-7C-D 1200 802BE 1200 BP802 2000 2000:5 MR 802BW 1200 3" AL BUS 1890 BP 8 7C Conductor 1155 Bkr Disc 1200 Bkr Disc 1200 Bkr Disc 12002000:5 MR 3102BW 1200 31-10-D 1200 3103BW 1200 BP3103 2000 2000:5 MR 3103BE 1200 3" ALUM BUS 1890 BP 31 10 Conductor 1057 Conductor 1109 Bkr Disc 1200 Bkr Disc 12002000:5 MR NA NA 103L 1200 NA NA NA NA NA NA NA 3" AL BUS 1890 BP 1 11 Conductor 1057 Conductor 1109 Bkr Disc 1200 Bkr Disc 12002000:5 MR 305BN 2000 3-12A-D 2000 303BE 2000 BP303 2000 2000:5 MR 303BW 2000 3-1/2" AL BUS 2170 BP 3 12A Conductor 611 Conductor 641 Conductor 764 Conductor 8022000:5 MR 3101BW 1200 31-12-B-D 1200 3108BN 2000 BP3108 2000 2000:5 MR 3108BS 2000 3" AL BUS 1890 BP 31 12B Conductor 611 Conductor 641 Conductor 764 Conductor 802

NA NA NA NA NA NA NA NA NA NA NA NA NA NA BP 13 13A U/G Cable No EM 351 U/G Cable No EM 351 U/G Cable No EM 351 U/G Cable No EM 351NA NA NA NA NA NA NA NA NA NA NA NA NA NA BP 13 13B U/G Cable No EM 351 U/G Cable No EM 351 U/G Cable No EM 351 U/G Cable No EM 351

2000:5 MR NA NA 601L 1200 NA NA NA NA NA NA NA 2 1/2" AL BUS 1550 BP 6 14 Conductor 1057 Conductor 1109 Bkr Disc 1200 Bkr Disc 12002000:5 MR 508S 1600 5-15B-D 1600 509S 1600 BP509 2000 2000:5 MR 509N 1600 3" AL BUS 1890 BP 5 15B 1 Conductor 1155 Bkr Disc 1200 Bkr Disc 1200 Bkr Disc 12002000:5 MR 903BS 1200 9-15C-D 1200 904BN 1200 BP904 2000 2000:5 MR 904BS 1200 3" AL BUS 1890 BP 9 15C Conductor 1155 Bkr Disc 1200 Bkr Disc 1200 Bkr Disc 12002000:5 MR 401S 2000 4-16-D 2000 407W 2000 407 2000 2000:5 MR 407E 2000 4" AL BUS 2460 BP 4 16 Conductor 1057 Conductor 1109 Bkr Disc 1200 Bkr Disc 12002000:5 MR 402W 2000 4-17-D 2000 401N 2000 401 2000 2000:5 MR 401S 2000 4" AL BUS 2460 BP 4 17 Conductor 1057 Conductor 1109 Conductor 1325 Conductor 13912000:5 MR 508S 1600 5-18A-D 2000 506E 1600 BP506 2000 2000:5 MR 506W 1600 3" ALUM BUS 1890 BP 5 18A Conductor 1316 Conductor 1381 Conductor 1524 Conductor 16002000:5 MR 104L 1200 NA NA NA NA NA NA NA NA NA 3" AL BUS 1890 BP 1 19A U/G Cable No EM 630 U/G Cable No EM 630 U/G Cable No EM 630 U/G Cable No EM 6302000:5 MR 107L 1200 NA NA NA NA NA NA NA NA NA 3" AL BUS 1890 BP 1 19B U/G Cable No EM 630 U/G Cable No EM 630 U/G Cable No EM 630 U/G Cable No EM 6302000:5 MR 706BW 1600 7-20A-D 1200 704BW 1600 BP704 2000 2000:5 MR 704BE 1600 3" AL BUS 1890 BP 7 20A Conductor 1057 Conductor 1109 Line Disc 1200 Line Disc 1200

Note 4 Note 4 Note 4 Note 4 Note 4 Note 4 Note 4 Note 4 Note 4 Note 4 Note 4 Note 4 Note 4 Note 4 FPC TIE# 3 20B Conductor 1057 Conductor 1109 Conductor 1325 Conductor 1391Note 4 Note 4 Note 4 Note 4 Note 4 Note 4 Note 4 Note 4 Note 4 Note 4 Note 4 Note 4 Note 4 Note 4 FPC TIE# 1 21 Conductor 611 Conductor 641 Conductor 764 Conductor 802

NA NA NA 3201L 2000 NA NA BP3201 2000 2000:5 MR 3201B 2000 4" ALUM BUS 2460 BP32 31N Conductor 1590 Conductor 1669 Conductor 1995 Bkr Disc 2000Note 4 Note 4 Note 4 Note 4 Note 4 Note 4 Note 4 Note 4 Note 4 Note 4 Note 4 Note 4 Note 4 Note 4 FPC TIE# 4 31S Conductor 1590 Conductor 1669 Conductor 1995 Bkr Disc 2000

2000:5 MR 5021-BS 2000 5-33-D 2000 5022-BW 2000 BP5022 2000 2000:5 MR 5022-BE 2000 4" ALUM BUS 2460 BP5 33 Conductor 1155 Conductor 1212 Conductor 1448 Bkr Disc 15202000:5 MR 233BW 1600 32-D 1600 232BN 1600 HP232 2000 2000:5 MR 232BS 1600 4" AL BUS 2460 HOPKINS 32A Conductor 1155 Conductor 1212 Conductor 1448 Conductor 1520

Note 4 Note 4 Note 4 Note 4 Note 4 Note 4 Note 4 Note 4 Note 4 Note 4 Note 4 Note 4 Note 4 Note 4 GPC TIE# 6 32B Conductor 1155 Conductor 1212 Conductor 1448 Conductor 15201600:5 MR 7020W 2000 7-32C-D 2000 7021BW 2000 7021 2000 2000:5 MR 7021BE 2000 4" ALUM BUS 2460 BP 7 32C Conductor 1155 Conductor 1212 Conductor 1448 Conductor 15202000:5 MR 2102BS 2000 21-52-D 2000 2103BN 2000 BP2103 2000 2000:5 MR 2103BS 2000 4" ALUM BUS 2460 BP21 52 8 Conductor 1155 Conductor 1212 U/G Cable W/ EM 1448 U/G Cable W/ EM 15202000:5 MR 2107BS 2000 21-53-D 2000 2103BS 2000 BP2103 2000 2000:5 MR 2103BN 2000 4" ALUM BUS 2460 BP21 53 8 Conductor 1155 Conductor 1212 U/G Cable W/ EM 1448 U/G Cable W/ EM 15202000:5 MR 1704BE 2000 17-54-D 2000 1705BN 2000 BP1705 2000 2000:5 MR 1705BS 2000 3.5" ALUM BUS 2170 BP17 54 8 Conductor 1155 Conductor 1212 U/G Cable W/ EM 1448 U/G Cable W/ EM 15202000:5 MR 510N 1600 5-15A-D 1600 509N 1600 BP509 2000 2000:5 MR 509S 1600 3" AL BUS 1890 BP 5 34 1 Conductor 1155 Conductor 1212 Conductor 1448 Conductor 15202000:5 MR 7022BE 2000 7-35-D 2000 7023BE 2000 BP7023 2000 2000:5 MR 7023BW 2000 4" ALUM BUS 2460 BP7 35 Conductor 1155 Conductor 1212 Conductor 1448 Conductor 1520

Summer Weakest Element Rating

Summer Emergency Weakest Element

Emergency Rating (100-105% of

Normal Rating) Winter Weakest Element RatingWinter Emergency Weakest Element

Emergency Rating (100-105% of

Normal Rating)

Page 5: (TAL) FAC-008-3 Facility Ratings March 31, 2016Mar 31, 2016  · Report Hopkins 2A CTG neutral disconnect per as-built documentation. Overhead transmission line conductor ratings revised

Northernmost/Easternmost Substation Termination

Southernmost/Westernmost Substation Termination

50% Pre-Loading

Condition

60% Pre-Loading

Condition

70% Pre-Loading

Condition

Line Length Substation Conductor Rating 1 Substation Rating Rating RatingName (Miles) Name Type (Amps) Name Element (Amps) (Amps) (Amps) (Amps)

21 4.8 BP 31 336 ACSR 611 FPC TIE# 1 Disconnect 1200 809 784 753

1 Summer ratings provided.

Revision Tracking:

CITY OF TALLAHASSEE (TAL)SHORT TERM TRANSIENT RATINGS PER IEEE 738-2006

4 Minute Transient Line Rating

Weakest Station

Element Rating 1

Page 6: (TAL) FAC-008-3 Facility Ratings March 31, 2016Mar 31, 2016  · Report Hopkins 2A CTG neutral disconnect per as-built documentation. Overhead transmission line conductor ratings revised

(Disconnect Configuration May Varry)

AutoTransformer Bay Location

Voltage (kV)

Breaker Disconnect

Switch Rating (Amps)

Breaker Disconnect

Switch Rating (Amps)

Circuit Breaker Rating (Amps)

Circuit Breaker Rating (Amps)

Breaker Disconnect

Switch Rating (Amps)

Breaker Disconnect

Switch Rating (Amps)

Transformer Disconnect

Switch Rating (Amps)

Transformer Disconnect

Switch Rating (Amps)

Bus Bar Structure

(Conductor #1)

Bus Bar Structure

(Conductor #1 (Amps)) Conductor #2

Conductor #2 (Amps)

T3 WEST BP-7 230 2000 2000 1600 2000 2000 2000 2000 2000 4" AL. 2460 (2 Runs) 954 MCM ACSR 1,606T4 EAST BP-7 230 2000 2000 2000 2000 2000 2000 2000 NA 4" AL. 2460 (2 Runs) 954 MCM ACSR 1,606T4 EAST BP-7 115 2000 1600 2000 2000 1600 1600 2000 NA 3" AL. 1890 (2 Runs) 954 MCM ACSR 1,606T3 WEST BP-7 115 1600 1600 2000 2000 1600 1600 2000 NA 3" AL. 1890 (2 Runs) 954 MCM ACSR 1,606

PP8 COMBUSTION Purdom 115 2000 2000 2000 2000 2000 2000 1200 NA 4" AL. 2460 NA NAPP8 STEAM Purdom 115 2000 2000 2000 2000 2000 2000 1200 NA 4" AL. 2460 1272 KCMIL ACSR 965

GT1 Purdom 115 2000 2000 2000 2000 2000 2000 2000 1200 4" AL. 2460 477 KCMIL ACSR 523GT2 Purdom 115 2000 2000 2000 2000 2000 2000 1200 1200 4" AL. 2460 477 KCMIL ACSR 523

Auto 1 Purdom 115 2000 2000 2000 2000 2000 2000 1200 NA 4" AL. 2460 NA NAAuto 2 Purdom 115 2000 2000 2000 2000 2000 2000 1200 NA 4" AL. 2460 NA NA

HP1#1 Hopkins 115 2000 2000 2000 2000 2000 2000 2000 2000 2" CU. 2080 500 MCM CU. 663HP1#2 Hopkins 115 2000 2000 2000 2000 2000 2000 2000 2000 2" CU. 2080 500 MCM CU. 663HP2#1 Hopkins 115 2000 2000 2000 2000 2000 2000 2000 NA 3" AL. 1890 2" AL 1150HP2#2 Hopkins 115 2000 2000 2000 2000 2000 2000 2000 NA 3" AL. 1890 2" AL 1150

GT1 (HC-1) Hopkins 115 2000 2000 2000 2000 2000 2000 2000 NA 2" CU. 2080 4/0 CU. 385GT2 (HC-2) Hopkins 115 2000 2000 2000 2000 2000 2000 2000 NA 2" CU. 2080 4/0 CU. 385

HC-3 Hopkins 115 2000 2000 2000 2000 2000 2000 2000 NA 4" AL. 2460 1431 ACSR 1054HC-4 Hopkins 115 2000 2000 2000 2000 2000 2000 2000 NA 4" AL. 2460 1431 ACSR 1054

GSU #5 (HP2A) Hopkins 230 2000 2000 2000 2000 2000 2000 2000 NA 4" AL. 2460 (2 Runs) 954 MCM ACSR 1,606T1 WEST Hopkins 230 2000 1600 2000 2000 1600 2000 NA NA 3" AL. 1890 954 ACSR 803T1 WEST Hopkins 115 2000 NA 2000 NA 2000 NA NA NA 4" AL. 2460 NA NAT2 EAST Hopkins 230 2000 1600 2000 2000 2000 1600 NA NA 3" AL. 1890 954 ACSR 803T2 EAST Hopkins 115 2000 NA 2000 NA 2000 NA NA NA 4" AL. 2460 NA NA

T5 BP5 230 2000 2000 2000 2000 2000 2000 2000 NA 4" AL. 2460 (2 Runs) 954 AAC Magnolia 1,964T5 BP5 115 1600 1600 2000 2000 1600 1600 2000 NA 3" AL. 1890 (2 Runs) 954 AAC Magnolia 1,964

T6 BP4 230 2000 NA 2000 NA NA NA 2000 NA 4" AL. 2460 (2 Runs) 954 AAC Magnolia 1,964T6 BP4 115 2000 2000 2000 2000 2000 2000 2000 NA 4" AL. 2460 (2 Runs) 954 AAC Magnolia 1,964

* Data for primary side of Generation Units will be provided by production. * Data for primary side of Generation Units will be provided by production.

Revision Tracking:

CITY OF TALLAHASSEE (TAL) TRANSFORMER BAY RATINGS DATA

Page 7: (TAL) FAC-008-3 Facility Ratings March 31, 2016Mar 31, 2016  · Report Hopkins 2A CTG neutral disconnect per as-built documentation. Overhead transmission line conductor ratings revised

AutoTransformer Connection Conductor

AutoTransformer Connection

Conductor (Amps)AutoTransformer

OA / ONAN (MVA)

AutoTransformer FA / ONAF1

(MVA) AutoTransformer

FA / ONAF2 (MVA) AutoTransformer

FOA / OFAF1 (MVA) AutoTransformer

FOA / OFAF2 (MVA)

Limiting AutoTransformer

Amperage AutoTransformer Bay Most

Limiting Element

AutoTransformer Bay Most Limiting Element

(AMPS)

1000MCM Cu. 1,025 159 212 266 NA NA 667 Transformer 667(2 Runs) 954 MCM ACSR 1,606 144 240 269 NA NA 675 Transformer 675(2 Runs) 954 MCM ACSR 1,606 144 240 269 NA NA 1350 Transformer 1,350(2 Runs) 1000MCM Cu. 2,050 159 212 266 NA NA 1335 Transformer 1,335

1272 KCMIL ACSR 965 144 192 NA NA NA 963 Transformer 963477 KCMIL ACSR 523 81 107 NA NA NA 537 Transformer 523

336.4 KCMIL ACSR 418 15.6 20.8 NA NA NA 104 Transformer 104336.4 KCMIL ACSR 418 15.6 20.8 NA NA NA 104 Transformer 104336.4 KCMIL ACSR 418 25 28 NA NA NA 140 Transformer 140336.4 KCMIL ACSR 418 25 28 NA NA NA 140 Transformer 140

4/0 CU. 385 NA NA NA 52.267 NA 262 Transformer 2624/0 CU. 385 NA NA NA 52.267 NA 262 Transformer 262

(2 Runs) 795 MCM ACSR 1,380 NA NA NA 157 NA 788 Transformer 788(2 Runs) 795 MCM ACSR 1,380 NA NA NA 157 NA 788 Transformer 788

4/0 CU. 385 16.8 22.4 28 NA NA 140 Transformer 1404/0 CU. 385 26.88 NA NA 35.84 45.8 229 Transformer 229

336.4 ACSR 418 60 NA NA NA NA 301 Transformer 301336.4 ACSR 418 60 NA NA NA NA 301 Transformer 301

954 KCM ACSR 803 135 180 225 NA NA 564 Transformer 564954 ACSR 803 NA NA NA 224 266 667 Transformer 667

4" AL. 2,460 NA NA NA 224 266 1335 Transformer 1,335954 ACSR 803 NA NA NA 224 266 667 Transformer 667

4" AL. 2,460 NA NA NA 224 266 1335 Transformer 1,335

954 AAC Magnolia 982 161 215 269 NA NA 675 Transformer 675(2 Runs) 954 AAC Magnolia 1,964 161 215 269 NA NA 1350 Transformer 1,350

954 AAC Magnolia 982 161 215 269 NA NA 675 Transformer 675(2 Runs) 954 AAC Magnolia 1,964 161 215 269 NA NA 1350 Transformer 1,350

* Data for primary side of Generation Units will be provided by production.

CITY OF TALLAHASSEE (TAL) TRANSFORMER BAY RATINGS DATA

Page 8: (TAL) FAC-008-3 Facility Ratings March 31, 2016Mar 31, 2016  · Report Hopkins 2A CTG neutral disconnect per as-built documentation. Overhead transmission line conductor ratings revised

AutoTransformer LocationVoltage

(kV) CT Max Ratio

T3 WEST BP-7 230 2000:5 MRT4 EAST BP-7 230 2000:5 MRT4 EAST BP-7 115 2000:5 MRT3 WEST BP-7 115 2000:5 MR

PP8 COMBUSTION Purdom 115 1200:5 MRPP8 STEAM Purdom 115 1200:5 MR

GT1 Purdom 115 1100:5GT2 Purdom 115 1100:5

Auto 1 Purdom 115 1200:5 MRAuto 2 Purdom 115 1200:5 MR

HP1#1 Hopkins 115 3000:5 MRHP1#2 Hopkins 115 3000:5 MRHP2#1 Hopkins 115 2000:5 MRHP2#2 Hopkins 115 2000:5 MR

GT1 (HC-1) Hopkins 115 1200:5 MRGT2 (HC-2) Hopkins 115 1100:5

HC-3 Hopkins 115 2000:5 MRHC-4 Hopkins 115 2000:5 MR

GSU #5 (HP2A) Hopkins 230 10,000:5 MRT1 WEST Hopkins 230 2000:5 MRT1 WEST Hopkins 115 2000:5 MRT2 EAST Hopkins 230 2000:5 MRT2 EAST Hopkins 115 2000:5 MR

T5 BP5 230 1200:5 MRT5 BP5 115 2000:5 MR

T6 BP4 230 1200:5 MRT6 BP4 115 2000:5 MR

NOTE: This data is provided for information only as CT's are not a system limiting element.

Revision Tracking:

CITY OF TALLAHASSEE (TAL) TRANSFORMER

CT RATINGS DATA

Page 9: (TAL) FAC-008-3 Facility Ratings March 31, 2016Mar 31, 2016  · Report Hopkins 2A CTG neutral disconnect per as-built documentation. Overhead transmission line conductor ratings revised

Location Bank Voltage(kV)MVAR per

bank

SUB 4 Bank 1 115 21.26SUB 4 Bank 2 115 21.26

SUB 5 Bank 1 115 22.26SUB 5 Bank 2 115 22.26

SUB 8 North Bank 115 22.26SUB 8 South Bank 115 22.26

SUB 11 North Bank 115 21.26SUB 11 South Bank 115 21.26

SUB 14 Bank 1 115 22.26

SUB 17 Bank 1 115 22.26

NOTE: This data is provided for information only ascapacator banks are not a system limiting element.

Revision Tracking:

CITY OF TALLAHASSEE (TAL)SHUNT CAPACITOR BANK DATA

Page 10: (TAL) FAC-008-3 Facility Ratings March 31, 2016Mar 31, 2016  · Report Hopkins 2A CTG neutral disconnect per as-built documentation. Overhead transmission line conductor ratings revised

TAL INSTRUMENT TRANSFORMER: CCVT/PT Ratings

CCVT ID LocationVoltage

(kV)

CCVT CAPACITANCE

(pF)

CCVT Impulse

Withstand 1.2/50us (BIL) KV

CCVT Thermal Rating (VA)

South West Bus Substation 1 115 6000 550 1000EAST Substation 1 115 6000 550 1000

Line 1B B Phase Substation 1 115 6000 550 1000WEST Substation 1 115 6000 550 1000

A Phase Substation 1 115 6000 550 1000Line 11 B Phase Substation 1 115 6000 550 1000 C Phase Substation 1 115 6000 550 1000

EAST Substation 1 115 6000 550 1000Line 14 B Phase Substation 1 115 6000 550 1000

WEST Substation 1 115 6000 550 1000EAST Substation 1 115 6000 550 1000

Line 19A B Phase Substation 1 115 6000 550 1000WEST Substation 1 115 6000 550 1000EAST Substation 1 115 6000 550 1000

Line 19B B Phase Substation 1 115 6000 550 1000WEST Substation 1 115 6000 550 1000

A PHASE Substation 2 115 6000 550 1000LINE-12A B PHASE Substation 2 115 6000 550 1000

C PHASE Substation 2 115 6000 550 1000A PHASE Substation 2 115 6000 550 1000

LINE-12B B PHASE Substation 2 115 6000 550 1000C PHASE Substation 2 115 6000 550 1000

A PHASE Substation 3 115 6000 550 1000LINE 3C B PHASE Substation 3 115 6000 550 1000

C PHASE Substation 3 115 6000 550 1000A PHASE Substation 3 115 6000 550 1000

LINE 5 B PHASE Substation 3 115 6000 550 1000C PHASE Substation 3 115 6000 550 1000A PHASE Substation 3 115 6000 550 1000

LINE 11 B PHASE Substation 3 115 6000 550 1000C PHASE Substation 3 115 6000 550 1000A PHASE Substation 3 115 6000 550 1000

LINE 12A B PHASE Substation 3 115 6000 550 1000C PHASE Substation 3 115 6000 550 1000

BETWEEN 301 & 308 B PHASE Substation 3 115 6000 550 1000BETWEEN 301 & 302 B PHASE Substation 3 115 6000 550 1000

A Phase Substation 4 230 5000 1050 1000Line 35 B Phase Substation 4 230 5000 1050 1000

C Phase Substation 4 230 5000 1050 1000A Phase Substation 4 230 5000 1050 1000

Line 34 B Phase Substation 4 230 5000 1050 1000C Phase Substation 4 230 5000 1050 1000B Phase Substation 4 230 5000 1050 1000

A PHASE Substation 4 115 6000 550 1000LINE 15 A B PHASE Substation 4 115 6000 550 1000

C PHASE Substation 4 115 6000 550 1000A PHASE Substation 4 115 6000 550 1000

LINE 15 C B PHASE Substation 4 115 6000 550 1000C PHASE Substation 4 115 6000 550 1000A PHASE Substation 4 115 6000 550 1000

LINE 16 B PHASE Substation 4 115 6000 550 1000C PHASE Substation 4 115 6000 550 1000A PHASE Substation 4 115 6000 550 1000

LINE 17 B PHASE Substation 4 115 6000 550 1000C PHASE Substation 4 115 6000 550 1000

CAPACITOR A PHASE Substation 4 115 7500 550 1000

BETWEEN 431 & 432 & 433

Page 11: (TAL) FAC-008-3 Facility Ratings March 31, 2016Mar 31, 2016  · Report Hopkins 2A CTG neutral disconnect per as-built documentation. Overhead transmission line conductor ratings revised

TAL INSTRUMENT TRANSFORMER: CCVT/PT Ratings

CCVT ID LocationVoltage

(kV)

CCVT CAPACITANCE

(pF)

CCVT Impulse

Withstand 1.2/50us (BIL) KV

CCVT Thermal Rating (VA)

BANK 1 & 2 B PHASE Substation 4 115 7500 550 1000C PHASE Substation 4 115 7500 550 1000

BETWEEN 401 & 402 B PHASE Substation 4 115 6000 550 1000BETWEEN 401 & 407 B PHASE Substation 4 115 6000 550 1000

A PHASE Substation 4 115 6000 550 1000BETWEEN 402 & 403 B PHASE Substation 4 115 6000 550 1000

C PHASE Substation 4 115 6000 550 1000BETWEEN 403 & 404 B PHASE Substation 4 115 6000 550 1000BETWEEN 404 & 405 B PHASE Substation 4 115 6000 550 1000BETWEEN 405 & 406 B PHASE Substation 4 115 6000 550 1000BETWEEN 406 & 407 B PHASE Substation 4 115 6000 550 1000

A Phase Substation 5 115 7500 550 1000Line 1A B Phase Substation 5 115 7500 550 1000

C Phase Substation 5 115 7500 550 1000A Phase Substation 5 115 7500 550 1000

Line 1B B Phase Substation 5 115 7500 550 1000C Phase Substation 5 115 7500 550 1000A Phase Substation 5 115 7500 550 1000

Line 2C B Phase Substation 5 115 7500 550 1000C Phase Substation 5 115 7500 550 1000A Phase Substation 5 115 7500 550 1000

Line 15A B Phase Substation 5 115 7500 550 1000C Phase Substation 5 115 7500 550 1000A Phase Substation 5 115 7500 550 1000

Line 15B B Phase Substation 5 115 7500 550 1000C Phase Substation 5 115 7500 550 1000A Phase Substation 5 115 6000 550 1000

Line 18 B Phase Substation 5 115 6000 550 1000C Phase Substation 5 115 6000 550 1000A Phase Substation 5 115 10000 550 1000

AUTO-TRANSFORMER B Phase Substation 5 115 10000 550 1000C Phase Substation 5 115 10000 550 1000A Phase Substation 5 230 5000 1050 1000

Line 33 B Phase Substation 5 230 5000 1050 1000C Phase Substation 5 230 5000 1050 1000A Phase Substation 5 230 5000 1050 1000

Line 34 B Phase Substation 5 230 5000 1050 1000C Phase Substation 5 230 5000 1050 1000

BETWEEN 502 & 501 B Phase Substation 5 115 7500 550 1000BETWEEN 504 & 506 B Phase Substation 5 115 7500 550 1000BETWEEN 501 & 510 B Phase Substation 5 115 7500 550 1000BETWEEN 509 & 510 B Phase Substation 5 115 7500 550 1000BETWEEN 508 & 509 B Phase Substation 5 115 10000 550 1000BETWEEN 508 & 507 B Phase Substation 5 115 10000 550 1000BETWEEN 506 & 507 B Phase Substation 5 115 7500 550 1000BETWEEN 5020 & 5021 B Phase Substation 5 230 5000 1050 1000BETWEEN 5020 & 5022 B Phase Substation 5 230 5000 1050 1000BETWEEN 5022 & 5021 B Phase Substation 5 230 5000 1050 1000

A PHASE Substation 6 115 6000 550 1000Line 14 B PHASE Substation 6 115 6000 550 1000

C PHASE Substation 6 115 6000 550 1000Between 601-602 B Phase Substation 6 115 7500 550 1000

A PHASE Substation 6 115 6000 550 1000Line 2B B PHASE Substation 6 115 6000 550 1000

C PHASE Substation 6 115 6000 550 1000Between 601-604 B Phase Substation 6 115 7500 550 1000

A PHASE Substation 6 115 7500 550 1000Line 10 B PHASE Substation 6 115 7500 550 1000

C PHASE Substation 6 115 7500 550 1000Between 603-604 B Phase Substation 6 115 7500 550 1000

Page 12: (TAL) FAC-008-3 Facility Ratings March 31, 2016Mar 31, 2016  · Report Hopkins 2A CTG neutral disconnect per as-built documentation. Overhead transmission line conductor ratings revised

TAL INSTRUMENT TRANSFORMER: CCVT/PT Ratings

CCVT ID LocationVoltage

(kV)

CCVT CAPACITANCE

(pF)

CCVT Impulse

Withstand 1.2/50us (BIL) KV

CCVT Thermal Rating (VA)

BETWEEN 7020 BW & 7021 BW B PHASE Substation 7 230 3000 1050 1000

A PHASE Substation 7 230 3000 1050 1000LINE 32C B PHASE Substation 7 230 3000 1050 1000

C PHASE Substation 7 230 3000 1050 1000BETWEEN 7020 BE & 7022 BE

B PHASESubstation 7 230 5000 1050 1000

BETWEEN 7021 BE & 7022 BW

B PHASESubstation 7 230 5000 1050 1000

S.E. BUS B PHASE Substation 7 115 6000 550 1000S.W. BUS B PHASE Substation 7 115 6000 550 1000

A PHASE Substation 7 115 6000 550 1000NORTH BUS B PHASE Substation 7 115 6000 550 1000

C PHASE Substation 7 115 6000 550 1000A PHASE Substation 7 115 6000 550 1000

LINE 7C B PHASE Substation 7 115 6000 550 1000C PHASE Substation 7 115 6000 550 1000A PHASE Substation 7 115 6000 550 1000

LINE 17 B PHASE Substation 7 115 6000 550 1000C PHASE Substation 7 115 6000 550 1000A PHASE Substation 7 115 6000 550 1000

LINE 20A B PHASE Substation 7 115 6000 550 1000C PHASE Substation 7 115 6000 550 1000A PHASE Substation 7 115 6000 550 1000

LINE 55 B PHASE Substation 7 115 6000 550 1000C PHASE Substation 7 115 6000 550 1000A PHASE Substation 7 115 6000 550 1000

BETWEEN 7004 BE & 705 BW B PHASE Substation 7 115 6000 550 1000

C PHASE Substation 7 115 6000 550 1000

A PHASE Substation 8 115 6000 550 1000LINE-7B B PHASE Substation 8 115 6000 550 1000

C PHASE Substation 8 115 6000 550 1000A PHASE Substation 8 115 6000 550 1000

LINE-7C B PHASE Substation 8 115 6000 550 1000C PHASE Substation 8 115 6000 550 1000

EAST BUS A PHASE Substation 8 115 7500 550 1000B PHASE Substation 8 115 7500 550 1000C PHASE Substation 8 115 7500 550 1000

Page 13: (TAL) FAC-008-3 Facility Ratings March 31, 2016Mar 31, 2016  · Report Hopkins 2A CTG neutral disconnect per as-built documentation. Overhead transmission line conductor ratings revised

TAL INSTRUMENT TRANSFORMER: CCVT/PT Ratings

CCVT ID LocationVoltage

(kV)

CCVT CAPACITANCE

(pF)

CCVT Impulse

Withstand 1.2/50us (BIL) KV

CCVT Thermal Rating (VA)

A PHASE Substation 9 115 6000 550 1000LINE 15B B PHASE Substation 9 115 6000 550 1000

C PHASE Substation 9 115 6000 550 1000A PHASE Substation 9 115 6000 550 1000

LINE 15C B PHASE Substation 9 115 6000 550 1000C PHASE Substation 9 115 6000 550 1000A PHASE Substation 9 115 6000 550 1000

LINE 52 B PHASE Substation 9 115 6000 550 1000C PHASE Substation 9 115 6000 550 1000

BETWEEN 902 BE & 904 BS

B PHASESubstation 9 115 6000 550 1000

BETWEEN 902 BW & 905 BS

B PHASESubstation 9 115 6000 550 1000

BETWEEN 903 BN & 906 BE B PHASE

Substation 9 115 6000 550 1000

A Phase Substation 10 115 6000 550 1000Line 7A B Phase Substation 10 115 6000 550 1000

C Phase Substation 10 115 6000 550 1000A Phase Substation 10 115 6000 550 1000

Line 7B B Phase Substation 10 115 6000 550 1000C Phase Substation 10 115 6000 550 1000

A PHASE Substation 11 115 6000 550 1000LINE 3A B PHASE Substation 11 115 6000 550 1000

C PHASE Substation 11 115 6000 550 1000A PHASE Substation 11 115 6000 550 1000

LINE 3B B PHASE Substation 11 115 6000 550 1000C PHASE Substation 11 115 6000 550 1000

CAPACITOR A PHASE Substation 11 115 6000 550 1000BANK BUS B PHASE Substation 11 115 6000 550 1000

C PHASE Substation 11 115 6000 550 1000NORTH CAP BANK A PHASE Substation 11 115 10000 350 1000SOUTH CAP BANK A PHASE Substation 11 115 10000 350 1000

A PHASE Substation 12 115 6000 550 1000Line 16 B PHASE Substation 12 115 6000 550 1000

C PHASE Substation 12 115 6000 550 1000

A PHASE Substation 14 115 10000 550 1000

LINE 53/54 B PHASE Substation 14 115 10000 550 1000C PHASE Substation 14 115 10000 550 1000A PHASE Substation 14 115 10000 550 1000

LINE 55 B PHASE Substation 14 115 10000 550 1000(FUTURE) C PHASE Substation 14 115 10000 550 1000

A PHASE Substation 14 115 10000 550 1000Cap Bank B PHASE Substation 14 115 10000 550 1000

C PHASE Substation 14 115 10000 550 1000BETWEEN 1405 BS & 1407 BE B PHASE Substation 14 115 10000 550 1000BETWEEN 1401 BS & 1407 BW B PHASE Substation 14 115 10000 550 1000BETWEEN 1402 BE & 1405 BN B PHASE Substation 14 115 10000 550 1000

Page 14: (TAL) FAC-008-3 Facility Ratings March 31, 2016Mar 31, 2016  · Report Hopkins 2A CTG neutral disconnect per as-built documentation. Overhead transmission line conductor ratings revised

TAL INSTRUMENT TRANSFORMER: CCVT/PT Ratings

CCVT ID LocationVoltage

(kV)

CCVT CAPACITANCE

(pF)

CCVT Impulse

Withstand 1.2/50us (BIL) KV

CCVT Thermal Rating (VA)

A PHASE Substation 15 115 8800 550 1000LINE 18A B PHASE Substation 15 115 8800 550 1000

C PHASE Substation 15 115 8800 550 1000BETWEEN 1504 BS & 1505 BN

B PHASESubstation 15 115 8800 550 1000

BETWEEN 1504 BN & 1503 BS

B PHASESubstation 15 115 8800 550 1000

EAST BUS B PHASE Substation 15 115 8800 550 1000

Line 20A B PHASE Substation 16 115 6000 550 1000A PHASE Substation 16 115 10000 550 1000

Line 20B B PHASE Substation 16 115 10000 550 1000C PHASE Substation 16 115 10000 550 1000

A PHASE Substation 17 115 7500 550 1000LINE 53 B PHASE Substation 17 115 7500 550 1000

C PHASE Substation 17 115 7500 550 1000A PHASE Substation 17 115 7500 550 1000

LINE 54 B PHASE Substation 17 115 7500 550 1000C PHASE Substation 17 115 7500 550 1000A PHASE Substation 17 115 7500 550 1000

CAP BANK #1 B PHASE Substation 17 115 7500 550 1000C PHASE Substation 17 115 7500 550 1000

BETWEEN 1701 & 1707 B PHASE Substation 17 115 7500 550 1000BETWEEN 1707 & 1706 B PHASE Substation 17 115 7500 550 1000BETWEEN 1706 & 1705 B PHASE Substation 17 115 7500 550 1000BETWEEN 1704 & 1703 B PHASE Substation 17 115 7500 550 1000BETWEEN 1705 & 1704 B PHASE Substation 17 115 7500 550 1000

A PHASE Substation 19 115 6000 550 1000LINE 19A B PHASE Substation 19 115 6000 550 1000

C PHASE Substation 19 115 6000 550 1000A PHASE Substation 19 115 6000 550 1000

LINE 19B B PHASE Substation 19 115 6000 550 1000C PHASE Substation 19 115 6000 550 1000

A Phase Substation 20 230 3000 1050 1000Line 32B B Phase Substation 20 230 3000 1050 1000

C Phase Substation 20 230 3000 1050 1000A Phase Substation 20 230 3000 1050 1000

Line 32A B Phase Substation 20 230 3000 1050 1000C Phase Substation 20 230 3000 1050 1000A Phase Substation 20 230 3000 1050 1000

Line 32B B Phase Substation 20 230 3000 1050 1000C Phase Substation 20 230 3000 1050 1000A Phase Substation 20 230 3000 1050 1000

Line 32C B Phase Substation 20 230 3000 1050 1000C Phase Substation 20 230 3000 1050 1000

Page 15: (TAL) FAC-008-3 Facility Ratings March 31, 2016Mar 31, 2016  · Report Hopkins 2A CTG neutral disconnect per as-built documentation. Overhead transmission line conductor ratings revised

TAL INSTRUMENT TRANSFORMER: CCVT/PT Ratings

CCVT ID LocationVoltage

(kV)

CCVT CAPACITANCE

(pF)

CCVT Impulse

Withstand 1.2/50us (BIL) KV

CCVT Thermal Rating (VA)

A Phase Substation 21 115 6000 550 1000LINE 9A B Phase Substation 21 115 6000 550 1000

C Phase Substation 21 115 6000 550 1000A Phase Substation 21 115 6000 550 1000

LINE 9B B Phase Substation 21 115 6000 550 1000C Phase Substation 21 115 6000 550 1000A Phase Substation 21 115 6000 550 1000

SW BUSS B Phase Substation 21 115 6000 550 1000C Phase Substation 21 115 6000 550 1000A Phase Substation 21 115 6000 550 1000

W BUSS B Phase Substation 21 115 6000 550 1000C Phase Substation 21 115 6000 550 1000A Phase Substation 21 115 6000 550 1000

E BUSS B Phase Substation 21 115 6000 550 1000C Phase Substation 21 115 6000 550 1000

A Phase Substation 31 115 6000 550 1000Line 3B B Phase Substation 31 115 6000 550 1000

C Phase Substation 31 115 6000 550 1000A Phase Substation 31 115 6000 550 1000

Line 3C B Phase Substation 31 115 6000 550 1000C Phase Substation 31 115 6000 550 1000A Phase Substation 31 115 6000 550 1000

Line 6A B Phase Substation 31 115 6000 550 1000C Phase Substation 31 115 6000 550 1000A Phase Substation 31 115 6000 550 1000

Line 6B B Phase Substation 31 115 6000 550 1000C Phase Substation 31 115 6000 550 1000A Phase Substation 31 115 6000 550 1000

Line 12B B Phase Substation 31 115 6000 550 1000C Phase Substation 31 115 6000 550 1000A Phase Substation 31 115 6000 550 1000

Line 21 B Phase Substation 31 115 6000 550 1000C Phase Substation 31 115 6000 550 1000

Line 3B Bus B Phase Substation 31 115 6000 550 1000Line 3C Bus B Phase Substation 31 115 7500 550 1000Line 6A Bus B Phase Substation 31 115 7500 550 1000Line 6B Bus B Phase Substation 31 115 7500 550 1000Line 12B Bus B Phase Substation 31 115 7500 550 1000Line 21 Bus B Phase Substation 31 115 6000 550 1000BANK 1 Bus B Phase Substation 31 115 7500 550 1000BANK 2 Bus B Phase Substation 31 115 7500 550 1000

A Phase Substation 32 230 5000 1050 1000Line 31N B Phase Substation 32 230 5000 1050 1000

C Phase Substation 32 230 5000 1050 1000A Phase Substation 32 230 5000 1050 1000

Line 31S B Phase Substation 32 230 5000 1050 1000C Phase Substation 32 230 5000 1050 1000A Phase Substation 32 230 5000 1050 1000

Line 33 B Phase Substation 32 230 5000 1050 1000C Phase Substation 32 230 5000 1050 1000A Phase Substation 32 230 5000 1050 1000

BP32 BUS B Phase Substation 32 230 5000 1050 1000C Phase Substation 32 230 5000 1050 1000

A Phase WS 115 6000 550 1000LINE 2A B Phase WS 115 6000 550 1000

C Phase WS 115 6000 550 1000

Page 16: (TAL) FAC-008-3 Facility Ratings March 31, 2016Mar 31, 2016  · Report Hopkins 2A CTG neutral disconnect per as-built documentation. Overhead transmission line conductor ratings revised

TAL INSTRUMENT TRANSFORMER: CCVT/PT Ratings

CCVT ID LocationVoltage

(kV)

CCVT CAPACITANCE

(pF)

CCVT Impulse

Withstand 1.2/50us (BIL) KV

CCVT Thermal Rating (VA)

A PHASE HOPKINS 230 6000 1050 1000LINE 31 B PHASE HOPKINS 230 6000 1050 1000

C PHASE HOPKINS 230 6000 1050 1000A PHASE HOPKINS 230 6000 1050 1000

LINE 32 B PHASE HOPKINS 230 6000 1050 1000C PHASE HOPKINS 230 6000 1050 1000A Phase HOPKINS 230 6000 1050 1000

SW 230 Bus B Phase HOPKINS 230 6000 1050 1000C Phase HOPKINS 230 6000 1050 1000

BETWEEN 231 & 234 B PHASE HOPKINS 230 3000 1050 1000BETWEEN 232 & 234 B PHASE HOPKINS 230 3000 1050 1000BETWEEN 235 & 31-D B PHASE HOPKINS 230 6000 1050 1000BETWEEN 237 & D-20 B PHASE HOPKINS 230 6000 1050 1000BETWEEN 233 & 236 B PHASE HOPKINS 230 6000 1050 1000BETWEEN 235 & 236 B PHASE HOPKINS 230 6000 1050 1000

SOUTH HOPKINS 115 6000 550 1000LINE 5 B PHASE HOPKINS 115 6000 550 1000

NORTH HOPKINS 115 6000 550 1000SOUTH HOPKINS 115 6000 550 1000

LINE 6A B PHASE HOPKINS 115 6000 550 1000NORTH HOPKINS 115 6000 550 1000SOUTH HOPKINS 115 6000 550 1000

LINE 7A B PHASE HOPKINS 115 6000 550 1000NORTH HOPKINS 115 6000 550 1000EAST HOPKINS 115 7500 550 1000

EAST BUS B PHASE HOPKINS 115 7500 550 1000WEST HOPKINS 115 7500 550 1000

WEST BUS B PHASE HOPKINS 115 7500 550 1000HC3 B PHASE HOPKINS 115 7500 550 1000HC4 B PHASE HOPKINS 115 7500 550 1000

A PHASE PURDOM 115 6000 550 1000LINE 1A B PHASE PURDOM 115 6000 550 1000

C PHASE PURDOM 115 6000 550 1000A PHASE PURDOM 115 6000 550 1000

LINE 2A B PHASE PURDOM 115 6000 550 1000C PHASE PURDOM 115 6000 550 1000A PHASE PURDOM 115 6000 550 1000

LINE 3A B PHASE PURDOM 115 6000 550 1000C PHASE PURDOM 115 6000 550 1000

LINE 7 N.E. BUS B PHASE PURDOM 115 6000 550 1000BETWEEN 108 & 109 B PHASE PURDOM 115 6000 550 1000BETWEEN 107 & 108 B PHASE PURDOM 115 6000 550 1000BETWEEN 107 & 106 B PHASE PURDOM 115 6000 550 1000BETWEEN 106 & 105 B PHASE PURDOM 115 6000 550 1000LINE 1A WEST BUS B PHASE PURDOM 115 6000 550 1000BETWEEN 101 & 102 B PHASE PURDOM 115 6000 550 1000LINE 2A WEST BUS B PHASE PURDOM 115 6000 550 1000BETWEEN 103 & 104 B PHASE PURDOM 115 6000 550 1000LINE 3A S.W. BUS B PHASE PURDOM 115 6000 550 1000

NOTE: This data is provided for information only as CCVT's are not a system limiting element.

Revision Tracking:

Page 17: (TAL) FAC-008-3 Facility Ratings March 31, 2016Mar 31, 2016  · Report Hopkins 2A CTG neutral disconnect per as-built documentation. Overhead transmission line conductor ratings revised

City of Tallahassee (TAL)

T LINE IN T LINE OUT SUMMER RATING SUMMER EM RATING WINTER RATING WINTER EM RATING VOLTAGE

BP1 #N/A #N/A #N/A #N/A 115KV BP1

BP2 #N/A #N/A #N/A #N/A 115KV BP2

BP3 #N/A #N/A #N/A #N/A 115KV BP3

BP4 #N/A #N/A #N/A #N/A 115KV BP4

BP5 #N/A #N/A #N/A #N/A 115KV BP5

BP6 #N/A #N/A #N/A #N/A 115KV BP6

BP7 #N/A #N/A #N/A #N/A 115KV BP7

BP8 #N/A #N/A #N/A #N/A 115KV BP8

BP9 #N/A #N/A #N/A #N/A 115KV BP9

BP10 #N/A #N/A #N/A #N/A 115KV BP10

BP11 #N/A #N/A #N/A #N/A 115KV BP11

BP12 #N/A #N/A #N/A #N/A 115KV BP12

BP14 #N/A #N/A #N/A #N/A 115KV BP14

BP15 #N/A #N/A #N/A #N/A 115KV BP15

BP16 #N/A #N/A #N/A #N/A 115KV BP16

BP17 #N/A #N/A #N/A #N/A 115KV BP17

BP19 #N/A #N/A #N/A #N/A 115KV BP19

BP21 #N/A #N/A #N/A #N/A 115KV BP20

BP31 #N/A #N/A #N/A #N/A 115KV BP31

HOPKINS #N/A #N/A #N/A #N/A 115KV HOPKINS

PURDOM #N/A #N/A #N/A #N/A 115KV PURDOM

BP20 #N/A #N/A #N/A #N/A 230KV BP20

HOPKINS #N/A #N/A #N/A #N/A 230KV HOPKINS

BP32 #N/A #N/A #N/A #N/A 230KV BP32

BP5 #N/A #N/A #N/A #N/A 230KV BP5

BP4 #N/A #N/A #N/A #N/A 230KV BP4

BP7 #N/A #N/A #N/A #N/A 230KV BP7

BP1 1200 1200 1200 1200EQUIPMENT ID AMPS AMPS AMPS AMPS

BP-101 2000 2000 2000 2000BP-102 2000 2000 2000 2000BP-103 2000 2000 2000 2000BP-104 2000 2000 2000 2000BP-105 2000 2000 2000 2000BP-106 2000 2000 2000 2000BP-107 2000 2000 2000 2000

DISCONNECTS AMPS AMPS AMPS AMPS

1-D3 1200 1200 1200 12001-D4 1200 1200 1200 12001-D5 1600 1600 1600 1600101 BS 1200 1200 1200 1200101 BN 1200 1200 1200 1200102 BS 1200 1200 1200 1200102 BN 1200 1200 1200 1200103 L 1200 1200 1200 1200103 B 1200 1200 1200 1200104 L 1200 1200 1200 1200104 B 1200 1200 1200 1200105 L 1200 1200 1200 1200105 B 1200 1200 1200 1200106 L 1200 1200 1200 1200106 B 1200 1200 1200 1200107 L 1200 1200 1200 1200107 B 1200 1200 1200 1200

SUBSTATION & TRANSMISSION LINE TIE LIMITING RATING CALCULATOR & DATA

Page 18: (TAL) FAC-008-3 Facility Ratings March 31, 2016Mar 31, 2016  · Report Hopkins 2A CTG neutral disconnect per as-built documentation. Overhead transmission line conductor ratings revised

BUS AMPS AMPS AMPS AMPS

3" AL BUS 1890 1890 1890 1890

BP2 1200 1200 1200 1200EQUIPMENT ID AMPS AMPS AMPS AMPS

BP-201 2000 2000 2000 2000BP-202 2000 2000 2000 2000BP-203 2000 2000 2000 2000BP-204 2000 2000 2000 2000BP-205 2000 2000 2000 2000

DISCONNECTS AMPS AMPS AMPS AMPS

2-D3 2000 2000 2000 2000201 L 1200 1200 1200 1200201 B 1200 1200 1200 1200202 BS 1200 1200 1200 1200202 BN 1200 1200 1200 1200203 L 1200 1200 1200 1200203 B 1200 1200 1200 1200204 B 1200 1200 1200 1200205 B 1200 1200 1200 1200BUS AMPS AMPS AMPS AMPS

1-1/2" CU BUS 1445 1445 1445 1445

BP3 2000 2000 2000 2000EQUIPMENT ID AMPS AMPS AMPS AMPS

BP-301 2000 2000 2000 2000BP-302 2000 2000 2000 2000BP-303 2000 2000 2000 2000BP-305 2000 2000 2000 2000BP-307 2000 2000 2000 2000BP-308 2000 2000 2000 2000

DISCONNECTS AMPS AMPS AMPS AMPS

3-D3 2000A 2000A 2000A 2000A3-D4 2000A 2000A 2000A 2000A3-D5 2000A 2000A 2000A 2000A301BS 2000A 2000A 2000A 2000A301BN 2000A 2000A 2000A 2000A302BE 2000A 2000A 2000A 2000A302BW 2000A 2000A 2000A 2000A303BE 2000A 2000A 2000A 2000A303BW 2000A 2000A 2000A 2000A305BS 2000A 2000A 2000A 2000A305BN 2000A 2000A 2000A 2000A307BE 2000A 2000A 2000A 2000A307BW 2000A 2000A 2000A 2000A308BE 2000A 2000A 2000A 2000A308BW 2000A 2000A 2000A 2000A3-3C-D 2000A 2000A 2000A 2000A3-5-D 2000A 2000A 2000A 2000A3-11-D 2000A 2000A 2000A 2000A3-12A-D 2000A 2000A 2000A 2000A

BUS AMPS AMPS AMPS AMPS

3-1/2" AL BUS 2170 2170 2170 2170

BP4 2000 2000 2000 2000EQUIPMENT ID AMPS AMPS AMPS AMPS

BP-401 2000 2000 2000 2000BP-402 2000 2000 2000 2000BP-403 2000 2000 2000 2000BP-404 2000 2000 2000 2000BP-405 2000 2000 2000 2000BP-406 2000 2000 2000 2000BP-407 2000 2000 2000 2000

DISCONNECTS AMPS AMPS AMPS AMPS

4-D1 2000 2000 2000 20004-D2 2000 2000 2000 20004-D3 2000 2000 2000 20004-D4 2000 2000 2000 20004-D5 2000 2000 2000 2000401-N 2000 2000 2000 2000401-S 2000 2000 2000 2000402-E 2000 2000 2000 2000402-W 2000 2000 2000 2000403-E 2000 2000 2000 2000403-W 2000 2000 2000 2000404-N 2000 2000 2000 2000404-S 2000 2000 2000 2000405-E 2000 2000 2000 2000405-W 2000 2000 2000 2000406-E 2000 2000 2000 2000406-W 2000 2000 2000 2000407-E 2000 2000 2000 2000407-W 2000 2000 2000 20004-15A-D 2000 2000 2000 20004-15C-D 2000 2000 2000 2000

Page 19: (TAL) FAC-008-3 Facility Ratings March 31, 2016Mar 31, 2016  · Report Hopkins 2A CTG neutral disconnect per as-built documentation. Overhead transmission line conductor ratings revised

4-17-D 2000 2000 2000 20004-16-D 2000 2000 2000 2000BUS AMPS AMPS AMPS AMPS

4" AL BUS 2460 2460 2460 2460

BP5 1600 1600 1600 1600EQUIPMENT ID AMPS AMPS AMPS AMPS

BP-501 2000 2000 2000 2000BP-502 2000 2000 2000 2000BP-504 2000 2000 2000 2000BP-505 2000 2000 2000 2000BP-506 2000 2000 2000 2000BP-507 2000 2000 2000 2000BP-508 2000 2000 2000 2000BP-509 2000 2000 2000 2000BP-510 2000 2000 2000 2000

DISCONNECTS AMPS AMPS AMPS AMPS

5-D3 1600 1600 1600 16005-D4 1600 1600 1600 1600501 E 1600 1600 1600 1600501 W 1600 1600 1600 1600502 N 1600 1600 1600 1600502 S 1600 1600 1600 1600503 N 1600 1600 1600 1600503 S 1600 1600 1600 1600504 N 1600 1600 1600 1600504 S 1600 1600 1600 1600505 N 1600 1600 1600 1600505 S 1600 1600 1600 1600506 E 1600 1600 1600 1600506 W 1600 1600 1600 1600508 S 1600 1600 1600 1600508 N 1600 1600 1600 1600509 S 1600 1600 1600 1600509 N 1600 1600 1600 1600510 N 1600 1600 1600 1600510 S 1600 1600 1600 16005-15A-D 1600 1600 1600 16005-1B-D 1600 1600 1600 16005-2C-D 1600 1600 1600 16005-1A-D 1600 1600 1600 16005-18A-D 2000 2000 2000 20005-15B-D 1600 1600 1600 1600

BUS AMPS AMPS AMPS AMPS

3" AL BUS 1890 1890 1890 1890

BP6 1200 1200 1200 1200EQUIPMENT ID AMPS AMPS AMPS AMPS

BP-601 2000 2000 2000 2000BP-602 2000 2000 2000 2000BP-603 2000 2000 2000 2000BP-604 2000 2000 2000 2000BP-605 2000 2000 2000 2000

DISCONNECTS AMPS AMPS AMPS AMPS

601 L 1200 1200 1200 1200601 B 1200 1200 1200 1200602 BE 1200 1200 1200 1200602 BW 1200 1200 1200 1200603 L 1200 1200 1200 1200603 B 1200 1200 1200 1200604 BE 1200 1200 1200 1200604 BW 1200 1200 1200 1200605 L 1200 1200 1200 1200605 B 1200 1200 1200 1200BUS AMPS AMPS AMPS AMPS

2 1/2" AL BUS 1550 1550 1550 1550

BP7 1200 1200 1200 1200EQUIPMENT ID AMPS AMPS AMPS AMPS

BP-701 2000 2000 2000 2000BP-702 2000 2000 2000 2000BP-703 2000 2000 2000 2000BP-704 2000 2000 2000 2000BP-705 2000 2000 2000 2000BP-706 2000 2000 2000 2000BP-707 2000 2000 2000 2000BP-708 2000 2000 2000 2000BP-709 2000 2000 2000 2000BP-710 2000 2000 2000 2000BP-7011 2000 2000 2000 2000BP-7014 2000 2000 2000 2000

DISCONNECTS AMPS AMPS AMPS AMPS

7-D7 2000 2000 2000 20007D4 2000 2000 2000 20007D9 2000 2000 2000 2000

Page 20: (TAL) FAC-008-3 Facility Ratings March 31, 2016Mar 31, 2016  · Report Hopkins 2A CTG neutral disconnect per as-built documentation. Overhead transmission line conductor ratings revised

701 BE 1600 1600 1600 1600701 BW 1600 1600 1600 1600702 BE 1600 1600 1600 1600702 BW 1600 1600 1600 1600703 BW 1600 1600 1600 1600703 BE 1600 1600 1600 1600704 BW 1600 1600 1600 1600704 BE 1600 1600 1600 1600705 BW 1600 1600 1600 1600705 BE 2000 2000 2000 2000706 BE 1600 1600 1600 1600706 BW 1600 1600 1600 1600707 BE 2000 2000 2000 2000707 BW 2000 2000 2000 2000708 BE 2000 2000 2000 2000708 BW 2000 2000 2000 2000709 BW 1600 1600 1600 1600709 BE 1600 1600 1600 1600710 BW 1600 1600 1600 1600710 BE 1600 1600 1600 16007011 BE 2000 2000 2000 20007011 BW 2000 2000 2000 20007014 BW 1600 1600 1600 16007014 BE 1600 1600 1600 16007-7C-D 1200 1200 1200 12007-17-D 1600 1600 1600 16007-20A-D 1200 1200 1200 12007-17-D 2000 2000 2000 20007-D3 2000 2000 2000 20007-D5 2000 2000 2000 20007-D6 2000 2000 2000 20007020 L 2000 2000 2000 20007020 B 2000 2000 2000 2000BUS AMPS AMPS AMPS AMPS

3" AL BUS 1890 1890 1890 1890

BP8 1200 1200 1200 1200EQUIPMENT ID AMPS AMPS AMPS AMPS

BP-801 2000 2000 2000 2000BP-802 2000 2000 2000 2000BP-803 2000 2000 2000 2000BP-807 2000 2000 2000 2000

DISCONNECTS AMPS AMPS AMPS AMPS

8-D3 1200 1200 1200 12008-D4 1200 1200 1200 12008-D5 1200 1200 1200 12008-7C-D 1200 1200 1200 12008-7B-D 1200 1200 1200 1200CAP BANK 1600 1600 1600 1600801 BN 1200 1200 1200 1200801 BS 1200 1200 1200 1200802 BE 1200 1200 1200 1200802 BW 1200 1200 1200 1200803 BE 1200 1200 1200 1200803 BW 1200 1200 1200 1200807 BN 1200 1200 1200 1200807 BS 1200 1200 1200 1200BUS AMPS AMPS AMPS AMPS

3" AL BUS 1890 1890 1890 1890

BP9 1200 1200 1200 1200EQUIPMENT ID AMPS AMPS AMPS AMPS

BP-902 2000 2000 2000 2000BP-903 2000 2000 2000 2000BP-904 2000 2000 2000 2000BP-905 2000 2000 2000 2000BP-906 2000 2000 2000 2000

DISCONNECTS AMPS AMPS AMPS AMPS

9-15B-D 1200 1200 1200 12009-15C-D 1200 1200 1200 1200901 BW 1200 1200 1200 1200901 BE 1200 1200 1200 1200902 BW 1200 1200 1200 1200902 BE 1200 1200 1200 1200903BN 2000 2000 2000 2000903BS 2000 2000 2000 2000904 BN 1200 1200 1200 1200904 BS 1200 1200 1200 1200905 BN 1200 1200 1200 1200905 BS 1200 1200 1200 1200906BW 2000 2000 2000 2000906BE 2000 2000 2000 2000BUS AMPS AMPS AMPS AMPS

3" AL BUS 1890 1890 1890 1890

Page 21: (TAL) FAC-008-3 Facility Ratings March 31, 2016Mar 31, 2016  · Report Hopkins 2A CTG neutral disconnect per as-built documentation. Overhead transmission line conductor ratings revised

BP10 1600 1600 1600 1600EQUIPMENT ID AMPS AMPS AMPS AMPS

BP-1001 2000 2000 2000 2000BP-1002 2000 2000 2000 2000BP-1004 2000 2000 2000 2000BP-1005 2000 2000 2000 2000

DISCONNECTS AMPS AMPS AMPS AMPS

1001 BS 2000 2000 2000 20001001 BN 2000 2000 2000 20001002 BW 2000 2000 2000 200010-D-4 2000 2000 2000 200010-D-3 2000 2000 2000 20001002 BE 2000 2000 2000 20001004 BN 2000 2000 2000 20001004 BS 2000 2000 2000 20001005 BE 2000 2000 2000 20001005 BW 1600 1600 1600 160010-7A-D 1600 1600 1600 160010-7B-D 1600 1600 1600 1600

BUS AMPS AMPS AMPS AMPS

3" AL BUS 1890 1890 1890 1890

BP11 1200 1200 1200 1200EQUIPMENT ID AMPS AMPS AMPS AMPS

BP-1101 2000 2000 2000 2000BP-1102 2000 2000 2000 2000BP-1103 2000 2000 2000 2000BP-1104 2000 2000 2000 2000

DISCONNECTS AMPS AMPS AMPS AMPS

11-3A-D 1200 1200 1200 120011-3B-D 1200 1200 1200 12001101 BW 1200 1200 1200 12001101 BE 1200 1200 1200 12001102 BN 1200 1200 1200 12001102 BS 1200 1200 1200 12001103 BW 1200 1200 1200 12001103 BE 1200 1200 1200 12001104 BN 1200 1200 1200 12001104 BS 1200 1200 1200 120011-D3 1200 1200 1200 1200BUS AMPS AMPS AMPS AMPS

3" AL BUS 1890 1890 1890 1890

BP12 1200 1200 1200 1200EQUIPMENT ID AMPS AMPS AMPS AMPS

BP-1201 2000 2000 2000 2000BP-1203 2000 2000 2000 2000BP-1204 2000 2000 2000 2000

DISCONNECTS AMPS AMPS AMPS AMPS

12-16-D 1200 1200 1200 120012-D5 2000 2000 2000 20001201 BW 2000 2000 2000 20001201 BE 2000 2000 2000 20001202 BN 2000 2000 2000 20001202 BS 2000 2000 2000 20001203 BN 1200 1200 1200 12001203 BS 2000 2000 2000 20001204 BE 1200 1200 1200 12001204 BW 1200 1200 1200 1200

BUS AMPS AMPS AMPS AMPS

3" AL BUS 1890 1890 1890 1890

BP14 2000 2000 2000 2000EQUIPMENT ID AMPS AMPS AMPS AMPS

BP-1401 2000 2000 2000 2000BP-1402 2000 2000 2000 2000BP-1405 2000 2000 2000 2000BP-1407 2000 2000 2000 2000

DISCONNECTS AMPS AMPS AMPS AMPS

14 D3 2000 2000 2000 200014 D4 2000 2000 2000 20001401 BS 2000 2000 2000 20001401 BN 2000 2000 2000 20001402 BE 2000 2000 2000 20001402 BW 2000 2000 2000 20001403 BE 2000 2000 2000 20001403 BW 2000 2000 2000 20001404 BE 2000 2000 2000 20001404 BW 2000 2000 2000 20001405 BS 2000 2000 2000 20001405 BN 2000 2000 2000 20001406 BE 2000 2000 2000 20001406 BW 2000 2000 2000 20001407 BE 2000 2000 2000 20001407 BW 2000 2000 2000 2000

Page 22: (TAL) FAC-008-3 Facility Ratings March 31, 2016Mar 31, 2016  · Report Hopkins 2A CTG neutral disconnect per as-built documentation. Overhead transmission line conductor ratings revised

1408 BE 2000 2000 2000 20001408 BW 2000 2000 2000 200014-54-D 2000 2000 2000 200014-55-D 2000 2000 2000 200014-CAP-1 2000 2000 2000 2000

BUS AMPS AMPS AMPS AMPS

4" AL BUS 2460 2460 2460 2460

BP15 1890 1890 1890 1890EQUIPMENT ID AMPS AMPS AMPS AMPS

BP-1501 2000 2000 2000 2000BP-1503 2000 2000 2000 2000BP-1504 2000 2000 2000 2000

DISCONNECTS AMPS AMPS AMPS AMPS

15 D1 2000 2000 2000 200015 D2 2000 2000 2000 200015 D3 2000 2000 2000 20001501 BS 2000 2000 2000 20001501 BN 2000 2000 2000 20001502 BE 2000 2000 2000 20001502 BW 2000 2000 2000 20001503 BS 2000 2000 2000 20001503 BN 2000 2000 2000 20001504 BS 2000 2000 2000 20001504 BN 2000 2000 2000 20001505 BS 2000 2000 2000 20001505 BN 2000 2000 2000 20001506 BS 2000 2000 2000 20001506 BN 2000 2000 2000 20001507 BS 2000 2000 2000 20001507 BN 2000 2000 2000 200015-18A-D 2000 2000 2000 2000

BUS AMPS AMPS AMPS AMPS

3" AL BUS 1890 1890 1890 1890

BP16 2000 2000 2000 2000EQUIPMENT ID AMPS AMPS AMPS AMPS

BP-1601 2000 2000 2000 2000DISCONNECTS AMPS AMPS AMPS AMPS

16-20A-D3 2000 2000 2000 20001601 BS 2000 2000 2000 20001601 BN 2000 2000 2000 2000

BP17 2000 2000 2000 2000EQUIPMENT ID AMPS AMPS AMPS AMPS

BP-1701 2000 2000 2000 2000BP-1703 2000 2000 2000 2000BP-1704 2000 2000 2000 2000BP-1705 2000 2000 2000 2000BP-1706 2000 2000 2000 2000BP-1707 2000 2000 2000 2000

DISCONNECTS AMPS AMPS AMPS AMPS

1701BN 2000 2000 2000 20001701BS 2000 2000 2000 20001702BN 2000 2000 2000 20001702BN 2000 2000 2000 20001703BE 2000 2000 2000 20001703BW 2000 2000 2000 20001704BE 2000 2000 2000 20001704BW 2000 2000 2000 20001705BN 2000 2000 2000 20001705BS 2000 2000 2000 20001706BE 2000 2000 2000 20001706BW 2000 2000 2000 20001707BE 2000 2000 2000 20001707BW 2000 2000 2000 200017-54-D 2000 2000 2000 200017-54-GR 2000 2000 2000 200017-53-D 2000 2000 2000 200017-53-GR 2000 2000 2000 200017D3 2000 2000 2000 2000BUS AMPS AMPS AMPS AMPS

3.5" AL BUS 2170 2170 2170 2170

BP19 1200 1200 1200 1200EQUIPMENT ID AMPS AMPS AMPS AMPS

BP-1901 2000 2000 2000 2000BP-1902 2000 2000 2000 2000BP-1903 2000 2000 2000 2000

DISCONNECTS AMPS AMPS AMPS AMPS

1901 L 1200 1200 1200 12001901 B 1200 1200 1200 12001902 BE 1200 1200 1200 12001902 BW 1200 1200 1200 1200

Page 23: (TAL) FAC-008-3 Facility Ratings March 31, 2016Mar 31, 2016  · Report Hopkins 2A CTG neutral disconnect per as-built documentation. Overhead transmission line conductor ratings revised

1903 L 1200 1200 1200 12001903 B 1200 1200 1200 1200BUS AMPS AMPS AMPS AMPS

3" AL BUS 1890 1890 1890 1890

BP21 2000 2000 2000 2000EQUIPMENT ID AMPS AMPS AMPS AMPS

BP-2102 2000A 2000A 2000A 2000ABP-2103 2000A 2000A 2000A 2000ABP-2107 2000A 2000A 2000A 2000A

DISCONNECTS AMPS AMPS AMPS AMPS

2102-BN 2000 2000 2000 20002102-BS 2000 2000 2000 20002103-BN 2000 2000 2000 20002103-BS 2000 2000 2000 20002107-BN 2000 2000 2000 20002107-BS 2000 2000 2000 2000LINE 52 2000 2000 2000 2000LINE 53 2000 2000 2000 200021-D3 2000 2000 2000 2000BUS AMPS AMPS AMPS AMPS

4" ALUM BUS 2460 2460 2460 2460

BP31 1200 1200 1200 1200BREAKERS AMPS AMPS AMPS AMPS

BP-3101 2000 2000 2000 2000BP-3102 2000 2000 2000 2000BP-3103 2000 2000 2000 2000BP-3104 2000 2000 2000 2000BP-3105 2000 2000 2000 2000BP-3106 2000 2000 2000 2000BP-3107 2000 2000 2000 2000BP-3108 2000 2000 2000 2000

DISCONNECTS AMPS AMPS AMPS AMPS

3101 BE 1200 1200 1200 12003101 BW 1200 1200 1200 12003102 BE 1200 1200 1200 12003102 BW 1200 1200 1200 12003103 BE 1200 1200 1200 12003103 BW 1200 1200 1200 12003104 BN 1200 1200 1200 12003104 BS 1200 1200 1200 12003105 BE 1200 1200 1200 12003105 BW 1200 1200 1200 12003106 BE 1200 1200 1200 12003106 BW 1200 1200 1200 12003107 BE 1200 1200 1200 12003107 BW 1200 1200 1200 12003108 BN 2000 2000 2000 20003108 BS 2000 2000 2000 2000

BUS AMPS AMPS AMPS AMPS3" AL BUS 1890 1890 1890 1890

HOPKINS 1890 1890 1890 1890BREAKERS AMPS AMPS AMPS AMPS

HP-101 2000 2000 2000 2000HP-102 2000 2000 2000 2000HP-103 2000 2000 2000 2000HP-104 2000 2000 2000 2000HP-105 2000 2000 2000 2000HP-106 2000 2000 2000 2000HP-107 2000 2000 2000 2000HP-108 2000 2000 2000 2000HP-109 2000 2000 2000 2000HP-110 2000 2000 2000 2000HP-111 2000 2000 2000 2000HP-112 2000 2000 2000 2000HP-113 2000 2000 2000 2000HP-115 2000 2000 2000 2000HP-116 2000 2000 2000 2000HP-117 2000 2000 2000 2000HP-118 2000 2000 2000 2000HP-119 2000 2000 2000 2000HP-120 2000 2000 2000 2000HP-121 2000 2000 2000 2000

DISCONNECTS AMPS AMPS AMPS AMPS

5-D 2000 2000 2000 20006A-D 2000 2000 2000 20007A-D 2000 2000 2000 2000HP-D3 2000 2000 2000 2000HP-D4 2000 2000 2000 2000HP-D5 2000 2000 2000 2000HP-D6 2000 2000 2000 2000HP-D7 2000 2000 2000 2000HP-D8 2000 2000 2000 2000

Page 24: (TAL) FAC-008-3 Facility Ratings March 31, 2016Mar 31, 2016  · Report Hopkins 2A CTG neutral disconnect per as-built documentation. Overhead transmission line conductor ratings revised

HP-GT-1D 2000 2000 2000 2000HP-GT-2D 2000 2000 2000 2000HP-CT-3D 2000 2000 2000 2000HP-CT-4D 2000 2000 2000 2000101 BE 2000 2000 2000 2000101 BW 2000 2000 2000 2000102 BE 2000 2000 2000 2000102 BW 2000 2000 2000 2000103 BE 2000 2000 2000 2000103 BW 2000 2000 2000 2000104 BW 2000 2000 2000 2000104 BE 2000 2000 2000 2000105 BE 2000 2000 2000 2000105 BW 2000 2000 2000 2000106 BE 2000 2000 2000 2000106 BW 2000 2000 2000 2000107 BE 2000 2000 2000 2000107 BW 2000 2000 2000 2000108 BE 2000 2000 2000 2000108 BW 2000 2000 2000 2000109 BE 2000 2000 2000 2000109 BW 2000 2000 2000 2000110 BE 2000 2000 2000 2000110 BW 2000 2000 2000 2000111 BE 2000 2000 2000 2000111 BW 2000 2000 2000 2000112 BE 2000 2000 2000 2000112 BW 2000 2000 2000 2000113 BE 2000 2000 2000 2000113 BW 2000 2000 2000 2000115 BE 2000 2000 2000 2000115 BW 2000 2000 2000 2000116 BW 2000 2000 2000 2000116 BE 2000 2000 2000 2000117 BN 2000 2000 2000 2000117 BS 2000 2000 2000 2000118 BN 2000 2000 2000 2000118 BS 2000 2000 2000 2000119 BW 2000 2000 2000 2000119 BE 2000 2000 2000 2000120 BW 2000 2000 2000 2000120 BE 2000 2000 2000 2000121 BW 2000 2000 2000 2000121 BE 2000 2000 2000 2000BUS AMPS AMPS AMPS AMPS

3" AL BUS 1890 1890 1890 1890

PURDOM 1200 1200 1200 1200BREAKERS AMPS AMPS AMPS AMPS

PP-101 2000 2000 2000 2000PP-102 2000 2000 2000 2000PP-103 2000 2000 2000 2000PP-104 2000 2000 2000 2000PP-105 2000 2000 2000 2000PP-106 2000 2000 2000 2000PP-107 2000 2000 2000 2000PP-108 2000 2000 2000 2000PP-109 2000 2000 2000 2000PP-110 2000 2000 2000 2000PP-111 1200 1200 1200 1200

DISCONNECTS AMPS AMPS AMPS AMPS

101 BS 2000 2000 2000 2000101 BN 2000 2000 2000 2000102 BS 2000 2000 2000 2000102 BN 2000 2000 2000 2000103 BS 2000 2000 2000 2000103 BN 2000 2000 2000 2000104 BS 2000 2000 2000 2000104 BN 2000 2000 2000 2000105 BW 2000 2000 2000 2000105 BE 2000 2000 2000 2000106 BS 2000 2000 2000 2000106 BN 2000 2000 2000 2000107 BS 2000 2000 2000 2000107 BN 2000 2000 2000 2000108 BS 2000 2000 2000 2000108 BN 2000 2000 2000 2000109 BS 2000 2000 2000 2000109 BN 2000 2000 2000 2000110 BE 2000 2000 2000 2000110 BW 2000 2000 2000 2000111 BE 1200 1200 1200 1200T2-D4 1200 1200 1200 1200T3-D3 1200 1200 1200 1200T2-D6 1200 1200 1200 1200T3-D5 1200 1200 1200 1200

Page 25: (TAL) FAC-008-3 Facility Ratings March 31, 2016Mar 31, 2016  · Report Hopkins 2A CTG neutral disconnect per as-built documentation. Overhead transmission line conductor ratings revised

CT8-D 1200 1200 1200 1200ST8-D 1200 1200 1200 1200GT-D 1200 1200 1200 12001A-D 1200 1200 1200 12002A-D 2000 2000 2000 20003A-D 1200 1200 1200 1200T1-D1 1200 1200 1200 1200GT-D1 2000 2000 2000 2000GT-D2 1200 1200 1200 1200ST7-D 1200 1200 1200 1200BUS AMPS AMPS AMPS AMPS

4" AL BUS 2460 2460 2460 2460

BP20 1600 1600 1600 1600BREAKERS AMPS AMPS AMPS AMPS

BP-2001 1600 1600 1600 1600BP-2002 1600 1600 1600 1600BP-2003 1600 1600 1600 1600

DISCONNECTS AMPS AMPS AMPS AMPS

2001 BS 2000 2000 2000 20002001 BN 2000 2000 2000 20002002 BS 2000 2000 2000 20002002 BN 2000 2000 2000 20002003 BS 2000 2000 2000 20002003 BN 2000 2000 2000 200020-32A-D 2000 2000 2000 200020-32B-D 2000 2000 2000 200020-32C-D 2000 2000 2000 200020-D3 2000 2000 2000 2000BUS AMPS AMPS AMPS AMPS

4" AL BUS 2460 2460 2460 2460

HOPKINS 1600 1600 1600 1600BREAKERS AMPS AMPS AMPS AMPS

HP-231 2000 2000 2000 2000HP-232 2000 2000 2000 2000HP-233 2000 2000 2000 2000HP-234 2000 2000 2000 2000HP-235 2000 2000 2000 2000HP-236 2000 2000 2000 2000HP-237 2000 2000 2000 2000

DISCONNECTS AMPS AMPS AMPS AMPS

31-D 2000 2000 2000 200032-D 1600 1600 1600 1600

D-20 (FUTURE LINE SWITCH) 2000 2000 2000 2000

GT5-D 2000 2000 2000 2000231 BN 1600 1600 1600 1600231 BS 1600 1600 1600 1600232 BN 1600 1600 1600 1600232 BS 1600 1600 1600 1600233 BE 1600 1600 1600 1600233 BW 1600 1600 1600 1600234 BE 2000 2000 2000 2000234 BW 2000 2000 2000 2000235 BS 2000 2000 2000 2000235 BN 2000 2000 2000 2000236 BE 2000 2000 2000 2000236 BW 2000 2000 2000 2000237 BS 1600 1600 1600 1600237 BN 2000 2000 2000 2000238 BE 2000 2000 2000 2000238 BW 2000 2000 2000 2000BUS AMPS AMPS AMPS AMPS

4" AL BUS 2460 2460 2460 2460

BP32 2000 2000 2000 2000BREAKERS AMPS AMPS AMPS AMPS

BP-3201 2000 2000 2000 2000BP-3202 2000 2000 2000 2000BP-3203 2000 2000 2000 2000

DISCONNECTS AMPS AMPS AMPS AMPS

3201B 2000 2000 2000 20003201L 2000 2000 2000 2000

32-31N-GR 2000 2000 2000 20003202B 2000 2000 2000 20003202L 2000 2000 2000 2000

32-31S-GR 2000 2000 2000 20003203B 2000 2000 2000 20003203L 2000 2000 2000 2000

32-33-GR 2000 2000 2000 2000BUS AMPS AMPS AMPS AMPS

4" ALUM BUS 2460 2460 2460 2460

BP5 2000 2000 2000 2000

Page 26: (TAL) FAC-008-3 Facility Ratings March 31, 2016Mar 31, 2016  · Report Hopkins 2A CTG neutral disconnect per as-built documentation. Overhead transmission line conductor ratings revised

BREAKERS AMPS AMPS AMPS AMPS

BP-5020 2000 2000 2000 2000BP-5021 2000 2000 2000 2000BP-5022 2000 2000 2000 2000

DISCONNECTS AMPS AMPS AMPS AMPS

5020BE 2000 2000 2000 20005020BW 2000 2000 2000 20005021BN 2000 2000 2000 20005021BS 2000 2000 2000 20005022BE 2000 2000 2000 20005022BW 2000 2000 2000 20005-33-D 2000 2000 2000 2000BUS AMPS AMPS AMPS AMPS

4" ALUM BUS 2460 2460 2460 2460

BP4 2000 2000 2000 2000BREAKERS AMPS AMPS AMPS AMPS

BP432 2000 2000 2000 2000

BP431 2000 2000 2000 2000

BP433 2000 2000 2000 2000DISCONNECTS AMPS AMPS AMPS AMPS

432E 2000 2000 2000 2000

432W 2000 2000 2000 2000

431E 2000 2000 2000 2000

431W 2000 2000 2000 2000

433N 2000 2000 2000 2000

433S 2000 2000 2000 2000BUS AMPS AMPS AMPS AMPS

4" AL BUS 2460 2460 2460 2460

BP7 2000 2000 2000 2000BREAKERS AMPS AMPS AMPS AMPS

BP-7020 1600 1600 1600 1600BP-7021 2000 2000 2000 2000BP-7022 2000 2000 2000 2000BP-7023 2000 2000 2000 2000

DISCONNECTS AMPS AMPS AMPS AMPS

7D4 2000 2000 2000 20007D9 2000 2000 2000 20007D8 2000 2000 2000 2000

7021BW 2000 2000 2000 20007021BE 2000 2000 2000 20007022BW 2000 2000 2000 20007022BE 2000 2000 2000 20007023BE 2000 2000 2000 20007023BW 2000 2000 2000 20007-35D-D 2000 2000 2000 20007-32C-D 2000 2000 2000 2000

BUS AMPS AMPS AMPS AMPS

4" AL BUS 2460 2460 2460 2460

Revision Tracking: