Critical Power Technical Data Sheet Uninterruptible Power Supply GE Consumer & Industrial SA General Electric Company CH – 6595 Riazzino (Locarno) Switzerland T +41 (0)91 / 850 51 51 F +41 (0)91 / 850 52 52 www.gecriticalpower.com imagination at work TLE Series 160 & 200 TLES_160-400_S1_UPS_GE_01 TLE Series 320 & 400

Technical Data Sheet - Uninterruptible Power Suppliesuninterruptible-powersupplies.com/wp-content/uploads/2017/01/GE... · Technical Data Sheet ... Service access Front and top access

Embed Size (px)

Citation preview

Page 1: Technical Data Sheet - Uninterruptible Power Suppliesuninterruptible-powersupplies.com/wp-content/uploads/2017/01/GE... · Technical Data Sheet ... Service access Front and top access

Critical Power

Technical Data Sheet Uninterruptible Power Supply

GE Consumer & Industrial SA General Electric Company CH – 6595 Riazzino (Locarno) Switzerland T +41 (0)91 / 850 51 51 F +41 (0)91 / 850 52 52

www.gecriticalpower.com

imagination at work

TLE Series 160 & 200

TLE

S_

16

0-4

00

_S

1_

UP

S_

GE

_0

1

TLE Series 320 & 400

Page 2: Technical Data Sheet - Uninterruptible Power Suppliesuninterruptible-powersupplies.com/wp-content/uploads/2017/01/GE... · Technical Data Sheet ... Service access Front and top access

Critical Power

Modifications reserved Page 2/6

GE_UPS_TDS_TLE_SCE_M16_M40_1GB_V030.docx Technical Data Sheet TLE Series 160 - 400 CE S1

Model: TLE Series 160 – 200 – 320 - 400 CE S1

Issued by: Product Document Department – Riazzino - CH

Approved by: R & D Department – Riazzino - CH

Date of issue: 05.03.2014

File name: GE_UPS_TDS_TLE_SCE_M16_M40_1GB_V030

Revision: 3.0

Identification No.:

Up-dating

Revision Concern Date

2.0 CB3 notes 01.09.2013

3.0 ECN 1869 (common battery) + ECN 1945 (EAC conformity) 05.03.2014

COPYRIGHT © 2014 by GE Consumer & Industrial SA

All rights reserved.

The information contained in this publication is intended solely for the purposes indicated.

The present publication and any other documentation supplied with the UPS system is not to be reproduced, either in part or in its entirety, without the prior written consent of GE.

The illustrations and plans describing the equipment are intended as general reference only and are not necessarily complete in every detail.

The content of this publication may be subject to modification without prior notice.

Page 3: Technical Data Sheet - Uninterruptible Power Suppliesuninterruptible-powersupplies.com/wp-content/uploads/2017/01/GE... · Technical Data Sheet ... Service access Front and top access

Critical Power

Modifications reserved Page 3/6

GE_UPS_TDS_TLE_SCE_M16_M40_1GB_V030.docx Technical Data Sheet TLE Series 160 - 400 CE S1

GENERAL DATA

Topology VFI, double conversion

Nominal output apparent power from PF=0.6 lag. to PF=0.9 lead. KVA 160 200 320 400

Nominal output active power at PF=1 kW 160 200 320 400

Efficiency at 100% load PF=0.9 lag. / 1 in VFI & PF=1 in eBoost % 1) VFI 96.5 / 96.1 96.2 / 96.0 96.6 / 96.2 96.3 / 96.1 eBoost 98.7 98.8 98.7 98.8

Efficiency at 75% load PF=0.9 lag. / 1 in VFI & PF=1 in eBoost % 1) VFI 96.5 / 96.2 96.5 / 96.2 96.6 / 96.4 96.6 / 96.4 eBoost 98.6 98.7 98.6 98.7

Efficiency at 50% load PF=0.9 lag. / 1 in VFI & PF=1 in eBoost % 1) VFI 96.2 / 95.9 96.5 / 96.2 96.3 / 96.2 96.6 / 96.4 eBoost 98.2 98.3 98.2 98.3

Audible noise level dB(A) 74

Battery type Valve regulated lead-acid (VRLA), vented lead-acid, NiCd

Operating temperature range UPS: 0°C ÷ 40°C

Storage temperature range UPS: -25°C ÷ +55°C Battery: -20°C ÷ +40°C (higher the temperature, shorter the

storage time of the battery)

Relative Humidity Max. 95% (non-condensing)

Max. altitude without power derating Power derating (according to EN/IEC 62040-3)

1000m 1500m: -2.5% / 2000m: -5% / 2500m: -7.5% / 3000m: -10%

Protection degree IP 20 (IEC 60529)

Standards EN/IEC 62040, CE marking

EMC (Electromagnetic Compatibility) EN/IEC 62040-2 (Category C2 as option – only for 160 & 200 kVA)

Electrostatic discharge immunity 4kV contact / 8kV air discharge

Internal protection All internal live parts shrouded

Transport Cabinet suitable for handling by forklift

Colour RAL 9005 (black)

Installation Can be positioned against a wall and floor fixed

Service access Front and top access only

External cable connections Bottom at front of the cabinet. Top: 160 & 200 as option / 320 & 400 standard

Cooling Enforced ventilation with fan failure detection and fan speed regulation

Paralleling (RPA version) Up to 6 units for redundancy or capacity in RPA configuration (option)

RECTIFIER

Rectifier bridge Three phase, IGBT rectifier, overtemperature protection

Standard input voltage Nominal: 3 x 400V + N Programmable: 3 x 380 / 415V + N Rectifier accepted ph-ph voltage range: 340V ÷ 460V 2)

Other input voltages On request

Input frequency 50/60 Hz +/-10% (45 ÷ 66 Hz)

Power factor 0.99

Input current THD <3%

Inrush current Limited by soft-start circuit

Power walk-in 15 seconds

Output voltage tolerance +/- 1%

Battery voltage ripple <1%

Battery current ripple Max. 5% the battery capacity [Ah], expressed in A

Battery charging characteristic IU (DIN 41773), T° compensated floating voltage

Battery charging current limit Programmable

Input power data kVA 160 200 320 400

Input power at inverter nominal load and charged battery at PF=0.9 lag.

kW 150.0 187.5 300.0 375.0

at PF=1.0 lag. 166.7 208.3 333.3 416.7

Max. input power at inverter nominal load and max. battery recharge current

kW 191.6 233.3 382.7 466.5

Max. battery charging current (programmable) at the beginning of battery recharge at nominal load

A 45 45 90 90

UPS OUTPUT POWER CAPABILITY

Output UPS power versus power factor for:

Inductive loads

Resistive loads

Capacitive loads

1) Tolerance ±0.3% 2) Battery recharging is not ensured below 370V when running at full load

Page 4: Technical Data Sheet - Uninterruptible Power Suppliesuninterruptible-powersupplies.com/wp-content/uploads/2017/01/GE... · Technical Data Sheet ... Service access Front and top access

Critical Power

Modifications reserved Page 4/6

GE_UPS_TDS_TLE_SCE_M16_M40_1GB_V030.docx Technical Data Sheet TLE Series 160 - 400 CE S1

BATTERY

Battery type Valve regulated lead-acid (VRLA)-standard, Vented lead-acid, wet battery and NiCd

Float voltage at 20°C 545V ÷ 600V (dependent on the number of cells)

Number of cells VRLA at 2.27V/cell: 240÷264 cells Vented lead acid at 2.23V/cell, no boostcharge: 244÷264 cells

Min. discharge voltage (programmable) 396V (dependent on the number of cells)

Recharge time <5 hours up to 90% of battery capacity

“Battery to earth” fault detection Standard

Automatic and manual battery test Standard

Common battery in parallel system Up to 3 units

Battery power data kVA 160 200 320 400

DC power at full load & PF=0.8 lag. / PF=0.9 lag. / PF=1 kW 131 / 147 / 163 163 / 184 / 204 261 / 294 / 327 327 /367 / 408

Matching battery cabinets See option features on page 5

INVERTER

Nominal output apparent power from PF=0.6 lag. to 0.9 lead. 160 – 200 – 320 - 400 kVA

Nominal output active power 160 – 200 – 320 - 400 kW

Nominal output voltage (on site programmable) 3 x 380V / 400V / 415V + N

Inverter bridge Advanced Neutral Point Clamped three level IGBT technology

Output waveform Sine wave

Output voltage tolerance: - static ..................................................................................................... +/- 1% - dynamic (at load step 0 – 100 – 0%) ...................................... +/- 3% - dynamic (at load step 0 – 50 – 0%) ......................................... +/- 2% - recovery time to +/-1% ................................................................ <5 ms - output voltage THD for 100% linear load ............................ <2.5% - output voltage THD for 100% non-linear load (EN 62040) <5%

Output voltage tolerance at 100% unbalanced load (Ph-N) +/- 3%

Output frequency 50/60 Hz (selectable)

Output frequency tolerance: - free-running ...................................................................................... +/- 0.1% - with mains synchronisation adjustable to ........................... +/- 4%

Phase displacement: - at 100% balanced load ................................................................ 120°: +/- 1% - at 100% unbalanced load ........................................................... 120°: +/- 1%

Overload capability (at 25°C ambient temperature) 110% - 10 minutes, 125% - 1 minute, 150% - 30 seconds

Short-circuit characteristic Electronic short-circuit protection, current limit to: 2.2 times In for 100ms between phase/phase and phase/N/PE

MCCB clearance capability (selectivity) 20% In within 5-10ms (with MCCB class C or magn. trip at max. 10In)

Crest factor >3:1

EBOOST™ OPERATION MODE (OPTION)

eBoost Operation Mode characteristics (option)

Output waveform Continuously monitored

Inverter reaction time ms <2 (typical)

Transfer limits in eBoost Operation Mode (option)

Steady-State RMS tolerance Vrms +/- 10

Instantaneous voltage distortion (w.r.t. normal sine wave)

Magnitude Vp +/- 50

Duration us 500

Steady-State frequency tolerance Hz +/- 3

Instantaneous phase shift rad 0.15

BYPASS

Input connection Separate for rectifier and bypass input or common to the rectifier input (option)

Primary components - Static switch (SCR) on bypass - Electromechanic contactors (backfeed protection) on bypass and inverter - 2 manual switches for maintenance bypass

Voltage limits for inverter/bypass load transfers +/- 10% (adjustable)

Overload on bypass 150% for 1 minute & 22 times In for 10ms, non repetitive – 110% continuous

INTERFACING

RS232 serial port Standard

EPO - EMERGENCY POWER OFF (n/c contact, customer supplied) Standard

Customer Interface board Standard 6 programmable signalling voltage-free contacts .............. (available on block terminals)

- Standard information for easy integration and signalling - 27 user settable signals

Connector RJ45 .................................................................................... With adaptation cable for a serial port RS232 / sub DB9 connection Input signals .......................................................................................... - GEN ON (emergency power supply ON, n/o contact, customer supplied)

- 1 auxiliary signal, with settable functionality

Note: all indicated values are typical. Variations may be found from one unit to another.

Page 5: Technical Data Sheet - Uninterruptible Power Suppliesuninterruptible-powersupplies.com/wp-content/uploads/2017/01/GE... · Technical Data Sheet ... Service access Front and top access

Critical Power

Modifications reserved Page 5/6

GE_UPS_TDS_TLE_SCE_M16_M40_1GB_V030.docx Technical Data Sheet TLE Series 160 - 400 CE S1

FRONT PANEL CONTROLS, SIGNALS AND ALARMS

The control panel, positioned on the UPS front door, acts as the UPS user interface and comprises of the following elements: Back lit Graphic Display (LCD) Touch Screen with the

following characteristics:

Multilanguage communication interface: English, German, Italian, Spanish, French, Finnish, Polish, Portuguese, Czech, Slovakian, Chinese, Swedish, Russian and Dutch;

Graphic diagram indicating UPS status.

Command keys and parameters setting.

UPS status control LED.

OPTIONS

COMMUNICATION OPTIONS:

1. Additional Customer Interface Card

2. 3-ph SNMP/WEB plug-in Adapter

3. iUPS Guard

4. GE Data Protection

BUILT-IN UPS OPTIONS:

1. eBoost™ Operation Mode

2. RPA kit (Redundant Parallel Architecture)

3. Kit for common input mains

4. Auxiliary Power Supply (APS) 24Vdc

5. Surge suppressors

OPTIONS IN ADDITIONAL CABINETS:

Dimensions (WxDxH): 300x865x1905mm 600x865x1905mm 870x865x1905mm 1120x865x1905mm

1. Rectifier or bypass or UPS input transformer 160 & 200 kVA / 320 & 400 kVA

2. Top entry cables cabinet 160 & 200 kVA / standard for 320 & 400 kVA

3. EMC filter EN/IEC 62040-2 Category C2 (Class A) 160 & 200 kVA

4. CB3 Battery disconnect box 685 x 415 x 870

5. Special voltages: input and/or output On request

6. Empty battery cabinets

7. Battery cabinet 1x75Ah

8. Battery cabinet 2x50Ah

EXTERNAL ACCESSORIES:

1. Parallel output cabinet with centralized maintenance bypass On request

2. Battery fuses box On request

Page 6: Technical Data Sheet - Uninterruptible Power Suppliesuninterruptible-powersupplies.com/wp-content/uploads/2017/01/GE... · Technical Data Sheet ... Service access Front and top access

Critical Power

Modifications reserved Page 6/6

GE_UPS_TDS_TLE_SCE_M16_M40_1GB_V030.docx Technical Data Sheet TLE Series 160 - 400 CE S1

TECHNICAL DATA

TLE Series 160 & 200

Dimensions (WxDxH): 820 x 865 x 1905 mm

WEIGHTS (kg) TLE Series 320 & 400

Dimensions (WxDxH): 1420 x 865 x 1905 mm

UPS cabinet Built-in

UPS options

UP

S R

ati

ng

(kV

A)

UP

S s

tan

da

rd

Flo

or

loa

din

g

UP

S s

tan

da

rd (k

g/m

2)

eB

oo

st™

O

pe

rati

on

Mo

de

160 & 200 500 705 30

320 & 400 980 798 75

UPS BLOCK DIAGRAM, PROTECTIONS AND CABLE SECTIONS

Separated input Rectifier & Bypass Common input Rectifier & Bypass (option)

Line protections and cable sections

Protections for mains voltages Battery protection Cable sections (mm2) recommended by European Standards

3 x 380V / 400V / 415 Vac 500 Vdc (Max. 240 cels) 1) Alternatively, local standards to be respected

kVA F1 F2 F3 CB3 A B C & D K

160 3 x 250A 3 x 250A 3 x 250A FKN36NTN630PF / 500A 2) 3x120+70 4x120 4x120+70 2x(2x120)+120

200 3 x 315A 3 x 315A 3 x 315A FKN36NTN630PF / 630A 2) 3x150+95 4x150 4x150+95 2x(2x150)+150

320 3 x 500A 3 x 500A 3 x 500A FKN36NTN800PF / 800A 2) 3x(2x120)+120 4x(2x120) 4x(2x120)+120 2x(2x240)+240

400 3 x 630A 3 x 630A 3 x 630A FKN36NT100SF / 1000A 2) 3x(2x150)+150 4x(2x150) 4x(2x150)+150 2x(4x120)+2x120

1) for higher cells use device fuse or breaker with suitable Vdc rating

2) setting value: Ir – overload protection Cable sections recommended in Switzerland (mm2)

F1, F2, F3, CB3, A, B, C, D, (K): supplied by customer kVA A B C & D K

K: supplied by GE only with battery 160 3x150+95 4x150 4x150+95 2x(2x150)+150

CB3: can be supplied by GE 200 3x185+95 4x185 4x185+95 2x(2x185)+185

320 3x(2x150)+150 4x(2x150) 4x(2x150)+150 2x(3x185)+2x150

400 3x(2x185)+185 4x(2x185) 4x(2x185)+185 2x(4x150)+2x150

IMPORTANT NOTE ! The UPS is designed for TN System. The input neutral shall be grounded at source and shall never be disconnected. 4 pole breaker shall not be used at the UPS input (see also IEC 60364-1, IEC 61140, IEC 61557).

1'9

05

mm

865mm 820mm

TLES_160-200_S1_UPS dimension_01

865mm 1'420mm

19

05

mm

TLES_320-400_S1_UPS dimension_GE_01

Page 7: Technical Data Sheet - Uninterruptible Power Suppliesuninterruptible-powersupplies.com/wp-content/uploads/2017/01/GE... · Technical Data Sheet ... Service access Front and top access

Critical Power

Technical Data Sheet Uninterruptible Power Supply

GE Consumer & Industrial SA General Electric Company CH – 6595 Riazzino (Locarno) Switzerland T +41 (0)91 / 850 51 51 F +41 (0)91 / 850 52 52

www.gecriticalpower.com

imagination at work

TLE Series 600

TLE

S_

60

0-8

00

_S

1_

UP

S_

GE

_0

1

TLE Series 800

Page 8: Technical Data Sheet - Uninterruptible Power Suppliesuninterruptible-powersupplies.com/wp-content/uploads/2017/01/GE... · Technical Data Sheet ... Service access Front and top access

Critical Power

Modifications reserved Page 2/6

GE_UPS_TDS_TLE_SCE_M60_M80_1GB_V010.docx Technical Data Sheet TLE Series 600 & 800 CE S1

Model: TLE Series 600 & 800 CE S1

Issued by: Product Document Department – Riazzino - CH

Approved by: R & D Department – Riazzino - CH

Date of issue: 22.07.2015

File name: GE_UPS_TDS_TLE_SCE_M60_M80_1GB_V010

Revision: 1.0

Identification No.:

Up-dating

Revision Concern Date

COPYRIGHT © 2015 by GE Consumer & Industrial SA

All rights reserved.

The information contained in this publication is intended solely for the purposes indicated.

The present publication and any other documentation supplied with the UPS system is not to be reproduced, either in part or in its entirety, without the prior written consent of GE.

The illustrations and plans describing the equipment are intended as general reference only and are not necessarily complete in every detail.

The content of this publication may be subject to modification without prior notice.

Page 9: Technical Data Sheet - Uninterruptible Power Suppliesuninterruptible-powersupplies.com/wp-content/uploads/2017/01/GE... · Technical Data Sheet ... Service access Front and top access

Modifications reserved Page 3/6

GE_UPS_TDS_TLE_SCE_M60_M80_1GB_V010.docx Technical Data Sheet TLE Series 600 & 800 CE S1

GENERAL DATA

Topology VFI, double conversion

Nominal output apparent power from PF=0.6 lag. to PF=0.9 lead. KVA 600 800

Nominal output active power at PF=1 kW 600 800

Efficiency at 100% load PF=0.9 lag. / 1 in VFI & PF=1 in eBoost % 1) VFI 96.3 / 96.1 96.3 / 96.2 eBoost 98.7 98.9

Efficiency at 75% load PF=0.9 lag. / 1 in VFI & PF=1 in eBoost % 1) VFI 96.5 / 96.3 96.5 / 96.4 eBoost 98.6 98.7

Efficiency at 50% load PF=0.9 lag. / 1 in VFI & PF=1 in eBoost % 1) VFI 96.5 / 96.6 96.5 / 96.5 eBoost 98.3 98.3

Audible noise level dB(A) VFI 74

eBoost 68

Battery type Valve regulated lead-acid (VRLA), vented lead-acid, NiCd

Operating temperature range UPS: 0°C ÷ 40°C

Storage temperature range UPS: -25°C ÷ +55°C Battery: -20°C ÷ +40°C (higher the temperature, shorter the

storage time of the battery)

Relative Humidity Max. 95% (non-condensing)

Max. altitude without power derating Power derating (according to EN/IEC 62040-3)

1000m 1500m: -2.5% / 2000m: -5% / 2500m: -7.5% / 3000m: -10%

Protection degree IP 20 (IEC 60529)

Standards EN/IEC 62040, CE marking

EMC (Electromagnetic Compatibility) EN/IEC 62040-2

Electrostatic discharge immunity 4kV contact / 8kV air discharge

Internal protection All internal live parts shrouded

Transport Cabinet suitable for handling by forklift

Colour RAL 9005 (black)

Installation Can be positioned against a wall and floor fixed

Service access Front and top access only

External cable connections Bottom or top of the cabinet

Cooling Enforced ventilation with fan failure detection and fan speed regulation

Paralleling (RPA version) Up to 6 units for redundancy or capacity in RPA configuration (option)

RECTIFIER

Rectifier bridge Three phase, IGBT rectifier, overtemperature protection

Standard input voltage Nominal: 3 x 400V + N Programmable: 3 x 380 / 415V + N Rectifier accepted ph-ph voltage range: 340V ÷ 460V 2)

Other input voltages On request

Input frequency 50/60 Hz +/-10% (45 ÷ 66 Hz)

Power factor 0.99

Input current THD <3%

Inrush current Limited by soft-start circuit

Power walk-in 15 seconds

Output voltage tolerance +/- 1%

Battery voltage ripple <1%

Battery current ripple Max. 5% the battery capacity [Ah], expressed in A

Battery charging characteristic IU (DIN 41773), T° compensated floating voltage

Battery charging current limit Programmable

Input power data kVA 600 800

Input power at inverter nominal load and charged battery at PF=0.9 lag.

kW 562 748

at PF=1.0 lag. 624 832

Max. input power at inverter nominal load and max. battery recharge current kW 698 932

Max. battery charging current (programmable) at the beginning of battery recharge at nominal load A 135 180

UPS OUTPUT POWER CAPABILITY

Output UPS power versus power factor for:

Inductive loads

Resistive loads

Capacitive loads

1) Tolerance ±0.3% 2) Battery recharging is not ensured below 370V when running at full load

Page 10: Technical Data Sheet - Uninterruptible Power Suppliesuninterruptible-powersupplies.com/wp-content/uploads/2017/01/GE... · Technical Data Sheet ... Service access Front and top access

Modifications reserved Page 4/6

GE_UPS_TDS_TLE_SCE_M60_M80_1GB_V010.docx Technical Data Sheet TLE Series 600 & 800 CE S1

BATTERY

Battery type Valve regulated lead-acid (VRLA)-standard, Vented lead-acid, wet battery and NiCd

Float voltage at 20°C 545V ÷ 600V (dependent on the number of cells)

Number of cells VRLA at 2.27V/cell: 240÷264 cells Vented lead acid at 2.23V/cell, no boostcharge: 244÷264 cells

Min. discharge voltage (programmable) 396V (dependent on the number of cells)

Recharge time <5 hours up to 90% of battery capacity

“Battery to earth” fault detection Standard

Automatic and manual battery test Standard

Common battery in parallel system Up to 3 units

Battery power data kVA 600 800

DC power at full load PF 0.8 lag. PF 0.9 lag. PF 1 PF 0.8 lag. PF 0.9 lag. PF 1

kW 500 563 625 667 750 883

Maximum discharge current (1.65V/cell) Amps 1263 1420 1578 1684 1894 2104

Matching battery cabinets See option features on page 5

INVERTER

Nominal output apparent power from PF=0.6 lag. to 0.9 lead. 600 & 800 kVA

Nominal output active power 600 & 800 kW

Nominal output voltage (on site programmable) 3 x 380V / 400V / 415V + N

Inverter bridge Advanced Neutral Point Clamped three level IGBT technology

Output waveform Sine wave

Output voltage tolerance: - static ..................................................................................................... +/- 1% - dynamic (at load step 0 – 100 – 0%) ...................................... +/- 3% - dynamic (at load step 0 – 50 – 0%) ......................................... +/- 2% - recovery time to +/-1% ................................................................ <20 ms - output voltage THD for 100% linear load ............................ <3% - output voltage THD for 100% non-linear load (EN 62040) <5%

Output voltage tolerance at 100% unbalanced load (Ph-N) +/- 3%

Output frequency 50/60 Hz (selectable)

Output frequency tolerance: - free-running ...................................................................................... +/- 0.1% - with mains synchronisation adjustable to ........................... +/- 4%

Phase displacement: - at 100% balanced load ................................................................ 120°: +/- 1%

- at 100% unbalanced load ........................................................... 120°: +/- 3%

Overload capability (at 25°C ambient temperature) 110% - 10 minutes, 125% - 1 minute, 150% - 30 seconds

Short-circuit characteristic Electronic short-circuit protection, current limit to: 2.2 times In for 100ms between phase/phase and phase/N/PE

MCCB clearance capability (selectivity) 20% In within 5-10ms (with MCCB class C or magn. trip at max. 10In)

Crest factor >3:1

EBOOST™ OPERATION MODE (OPTION)

eBoost Operation Mode characteristics

Output waveform Continuously monitored

Inverter reaction time ms <2 (typical)

Transfer limits in eBoost Operation Mode

Steady-State RMS tolerance Vrms +/- 10

Instantaneous voltage distortion (w.r.t. normal sine wave)

Magnitude Vp +/- 50

Duration us 500

Steady-State frequency tolerance Hz +/- 3

Instantaneous phase shift rad 0.15

BYPASS

Input connection Separate for rectifier and bypass input or common to the rectifier input

Primary components - Static switch (SCR) on bypass - Electromechanic contactors (backfeed protection) on bypass and inverter

Voltage limits for inverter/bypass load transfers +/- 10% (adjustable)

Overload on bypass 150% for 1 minute & 22 times In for 10ms, non repetitive – 110% continuous

INTERFACING

RS232 serial port Standard

EPO - EMERGENCY POWER OFF (n/c contact, customer supplied) Standard

Customer Interface board Standard 6 programmable signalling voltage-free contacts ............. (available on block terminals)

- Standard information for easy integration and signalling - 27 user settable signals

Connector RJ45 .................................................................................. With adaptation cable for a serial port RS232 / sub DB9 connection Input signals ......................................................................................... - GEN ON (emergency power supply ON, n/o contact, customer supplied)

- 1 auxiliary signal, with settable functionality

Note: all indicated values are typical. Variations may be found from one unit to another.

Page 11: Technical Data Sheet - Uninterruptible Power Suppliesuninterruptible-powersupplies.com/wp-content/uploads/2017/01/GE... · Technical Data Sheet ... Service access Front and top access

Modifications reserved Page 5/6

GE_UPS_TDS_TLE_SCE_M60_M80_1GB_V010.docx Technical Data Sheet TLE Series 600 & 800 CE S1

FRONT PANEL CONTROLS, SIGNALS AND ALARMS

The control panel, positioned on the UPS front door, acts as the UPS user interface and comprises of the following elements: Back lit Graphic Display (LCD) Touch Screen with the following characteristics:

Multilanguage communication interface: English, German, Italian, Spanish, French, Finnish, Polish, Portuguese, Czech, Slovakian, Chinese, Swedish, Russian and Dutch;

Graphic diagram indicating UPS status.

Command keys and parameters setting.

UPS status control LED.

OPTIONS

COMMUNICATION OPTIONS:

1. Additional Customer Interface Card

2. 3-ph SNMP/WEB plug-in Adapter

3. iUPS Guard

4. GE Data Protection

BUILT-IN UPS OPTIONS:

1. eBoost™ Operation Mode

2. IEMi Operation Mode

3. RPA kit (Redundant Parallel Architecture)

Page 12: Technical Data Sheet - Uninterruptible Power Suppliesuninterruptible-powersupplies.com/wp-content/uploads/2017/01/GE... · Technical Data Sheet ... Service access Front and top access

Modifications reserved Page 6/6

GE_UPS_TDS_TLE_SCE_M60_M80_1GB_V010.docx Technical Data Sheet TLE Series 600 & 800 CE S1

TECHNICAL DATA

TLE Series 600 & 800

WEIGHTS

600 kVA 800 kVA

UPS standard 2200 Kg 2380 Kg

Floor loading 848 Kg/m2 805 Kg/m2

DIMENSIONS

(W x D x H)

600 kVA 3000 x 865 x 1905 mm

118.12 x 34.06 x 75.00 inches

800 kVA 3420 x 865 x 1905 mm 134.65 x 34.06 x 75.00 inches

UPS BLOCK DIAGRAM, PROTECTIONS AND CABLE SECTIONS

Common input Rectifier & Bypass Separated input Rectifier & Bypass

Line protections and cable sections

Protections for mains voltages Battery protection Cable sections (mm2) IEC 60950-1

3 x 380V / 400V / 415 Vac 500 Vdc (Max. 240 cells) 1) Local Standard and cables installation disposal shall be applied

kVA F1 F2 F3 F4 / MCCB A B C und D K

600 3x1000A 3x1000A 3x1000A 1600A

2 x FKN36NT100SF / 800A 2) 3x(3x185)+2x150 4x(3x185) 4x(3x185)+2x150 2x[2x(2x240)+240]

800 3x1250A 3x1250A 3x1250A 2000A

2 x FKN36NT125SF / 1000A 2) 3x(3x240)+2x185 4x(3x240) 4x(3x240)+2x185 2x[2x(4x120)+2x120]

1) for higher cells use device fuse or breaker with suitable Vdc rating

2) setting value: Ir – overload protection. Two parallel battery strings.

F1, F2, F3, F4/MCCB, A, B, C, D, (K): supplied by customer

K: supplied by GE only with battery

MCCB: can be supplied by GE

IMPORTANT NOTE ! The UPS is designed for TN System. The input neutral shall be grounded at source and shall never be disconnected. 4 pole breaker shall not be used at the UPS input (see also IEC 60634, IEC 61140, IEC 61557). Separated input Rectifier & Bypass: connect a single input Neutral to Bypass Mains (inside the UPS, common neutral for Bypass and Rectifier).

D

H

W

TLES_600_S1_UPS dimensions_GE_TDS_01