20
TI00473C/07/EN/03.12 71164110 Technical Information Liquistation CSF22 Automatic stationary sampler for liquid media Integrated multiparameter controller with Modbus RS485 communication Application Liquistation CSF22 is a stationary sampler designed for the fully automated sampling, defined distribution, and temperature-controlled storage of liquid media. The standard product version has one 0/4 to 20 mA analog input, one binary input and one binary output. The sampler is designed for use in the following indoor applications: Municipal and industrial sewage treatment plants Laboratories and Water Conservancy Boards Monitoring of liquid media in industrial processes Your benefits Rugged and reliable: Refrigerator with 304x housing Reliable sample temperature regulation Optimal air circulation in the lower enclosure Simple and easy to use: Swift menu guidance, navigator and large display Bottle tray for easy sample transportation Parts carrying medium are easy to disassemble, making cleaning and maintenance simple • Flexible: User friendly programs ranging from simple time programs to event programs Functionality can be extended by connecting different input parameters • Communicative: Integrated data logger for recording measured values Service interface for data transmission Modbus RS485 communication • Safe: Automatic diagnostic monitoring Optional battery backup system ensures uninterrupted operation in the event of power failure

Technical Information Liquistation ... - Endress+Hauser Portal

  • Upload
    others

  • View
    4

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Technical Information Liquistation ... - Endress+Hauser Portal

TI00473C/07/EN/03.12

71164110

Technical Information

Liquistation CSF22

Automatic stationary sampler for liquid media

Integrated multiparameter controller with Modbus RS485

communication

Application

Liquistation CSF22 is a stationary sampler designed for the fully

automated sampling, defined distribution, and

temperature-controlled storage of liquid media.

The standard product version has one 0/4 to 20 mA analog

input, one binary input and one binary output.

The sampler is designed for use in the following indoor

applications:

• Municipal and industrial sewage treatment plants

• Laboratories and Water Conservancy Boards

• Monitoring of liquid media in industrial processes

Your benefits

• Rugged and reliable:

– Refrigerator with 304x housing

– Reliable sample temperature regulation

– Optimal air circulation in the lower enclosure

• Simple and easy to use:

– Swift menu guidance, navigator and large display

– Bottle tray for easy sample transportation

– Parts carrying medium are easy to disassemble, making

cleaning and maintenance simple

• Flexible:

– User friendly programs ranging from simple time programs

to event programs

– Functionality can be extended by connecting different

input parameters

• Communicative:

– Integrated data logger for recording measured values

– Service interface for data transmission

– Modbus RS485 communication

• Safe:

– Automatic diagnostic monitoring

– Optional battery backup system ensures uninterrupted

operation in the event of power failure

Page 2: Technical Information Liquistation ... - Endress+Hauser Portal

Liquistation CSF22

2 Endress+Hauser

Function system design

Liquistation CSF22 sampler A complete sampling unit comprises:

Liquistation CSF22, with the following depending on the version ordered:

• Controller with display, soft keys and navigator

• Peristaltic pump for sampling

• Plastic (PE) sample bottles for sample preservation

• Sample compartment temperature control for safe sample storage

• Suction line with suction strainer or filter

a0014369

Example of a Liquistation CSF22

1

2

3

4

5 6

7

8

9

1 Bottle distribution 6 Power supply

2 Distribution arm 7 Peristaltic pump

3 Medium detetection and suction-line connection 8 Door lock

4 Signal connection 9 Refrigerator display

5 Controller

Page 3: Technical Information Liquistation ... - Endress+Hauser Portal

Liquistation CSF22

Endress+Hauser 3

Mode of operation

a0011584

Sampling steps with a peristaltic pump

Sampling takes place in three steps:

1. Purge/rinse

The peristaltic pump runs in reverse and forces liquid back to the sampling point.

2. Intake

The peristaltic pump runs forward and draws in liquid. Once the liquid detection system detects the

sample, the pump is controlled by the flow and the specified sample volume is calculated automatically.

3. Purge

The pump runs in reverse again and forces the liquid back to the sampling point.

One advantage this system offers for obtaining a representative sample is the possibility of rinsing the suction

line several times:

Liquid is initially drawn in until the liquid detection system reacts, then the pump switches and forces the liquid

back to the sampling point. This process can be repeated a maximum of three times. The sample is then taken

as described.

The pump rollers deform the tubing, thereby causing a negative pressure and the suction effect.

The liquid detection system is based on a pressure sensor which detects the difference between a pipe that is

filled and not filled.

Thanks to a patented process for automatically detecting the suction height, the user does not have to enter

the suction height or suction line length. The self-calibrating software guarantees that the sample volume

remains constant.

1. 2. 3.

a0014451

Peristaltic pump

1

2

3

Pump tubing

Pump rollers

Liquid detection system (patented)

1 2 3

Page 4: Technical Information Liquistation ... - Endress+Hauser Portal

Liquistation CSF22

4 Endress+Hauser

Navigator and plain text

display

The simple and structured operating concept sets new standards:

• Intuitive operation with the navigator and soft keys

• Fast configuration of application-specific measurement options

• Easy configuration and diagnosis thanks to plain-text display

• All languages that can be ordered are available in every device

Controller interfaces The controller of the sampler has the following functions:

• Socket for M12 connector Modbus RS485 (5-pin, B-coded, female)

• Multi I/O connector

• Service connector

a0014360

Connection sockets

1 Socket for M12 connector (5-pin, B-coded, female)

2 Multi I/O connector

3 Service connector

Display Graphic display:

• Backlight with switch-off function

• Red background display for alarms alerts users to errors

• Transflective display technology for maximum contrast even in bright environments

a0013216

Easy operation

a0013222-en

Plain-text menu

12

3

a0013627

Example of program setup

Page 5: Technical Information Liquistation ... - Endress+Hauser Portal

Liquistation CSF22

Endress+Hauser 5

Sampling control

Intake speed with different

suction lines

a0014452

Intake speed in m/s at suction heights in m (vertical lift)

1 Intake speed as per Ö 5893 (Austrian standard)

2 Intake speed as per EN 25667, ISO 5667

a0014045

a. Flow curve

b. Time proportional sampling:

Constant time constant volume (CTCV)

A constant sampling volume is taken at steady intervals.

c. Flow proportional sampling:

Variable time constant volume (VTCV)

A constant sampling volume is taken at variable intervals.

d. Flow proportional sampling/time override:

Constant time variable volume (CTVV)

A variable sampling volume is taken at steady intervals.

e. Event-controlled sampling:

Sampling is triggered by an event.

Single and multiple samples can also be grouped in a program in

addition to the sampling methods listed. Furthermore, the software

allows interval sampling, switchover and event functions. The latter

permit up to 24 subprograms to be active simultaneously for a

variety of applications.

A sampling table makes it possible for users to program the bottle

assignment, time interval and sample volume.

Signals for external control can be connected via analog input and

binary input in the standard version of the product. Customized

text is entered to ensure the correct assignment of the inputs in the

memory.

1.2

1.0

0.8

0.6

0.4

0.22 3 4 5 6 7 8 m

6.6 9.9 13.1 16.4 19.7 23 26.3 ft

3.9

3.3

2.6

2.0

1.3

0.7

ft/s m/s

1

2

Page 6: Technical Information Liquistation ... - Endress+Hauser Portal

Liquistation CSF22

6 Endress+Hauser

Sample distribution CSF22 offers a range of bottle combinations and distribution versions. The sequencial version can be changed

or replaced easily without the need for special tools. In addition, the software makes it possible to configure

individual bottles and bottle groups as well as assign them to change based on a programmed event.

Note!

The composite version can not be upgraded to sequencial.

Bottle groups and distribution version depending on the order version:

Sample preservation The sample bottles are located in the sample compartment made of stainless steel.

All parts that transport liquid can be removed and cleaned easily without the need for additional tools.

a0015194

Sample bottles

Sample temperature

regulation

The temperature of the sample compartment can be adjusted using the controller. The factory setting is 4 °C

(39 °F). The current temperature is shown on the display.

a0014453

Display of cooling system

CSF22-**1** CSF22-**2** CSF-**3**

20 liter, PE

direct distribution1

2 liter, PE

direct distribution12

1 liter, PE

direct distribution24

Page 7: Technical Information Liquistation ... - Endress+Hauser Portal

Liquistation CSF22

Endress+Hauser 7

Maintainability • Independent, integrated ring memories (FIFO) or stack memories for recording:

- An analog value (e.g. flow rate, pH value, conductivity)

- Events (e.g. power failure)

- Sample statistics (e.g. sample volume, filling times, bottle assignment)

• Program memory: max. 100 programs

• Data logbooks:

– Adjustable scan time: 1 to 3600 s (6 h)

– Max. 8 data logbooks

– 150,000 entries per logbook

– Graphic display (load curves) or text display

• Calibration logbook: max. 75 entries

• Hardware version logbook:

– Hardware configuration and modifications

– max. 125 entries

• Version logbook:

– e.g. software updates

– max. 50 entries

• Operation logbook: max. 250 entries

• Diagnostics logbook: max. 250 entries

a0015032

Data logbook: Graphic display

Page 8: Technical Information Liquistation ... - Endress+Hauser Portal

Liquistation CSF22

8 Endress+Hauser

FieldCare

Configuration and asset management software based on FDT/DTM technology

• Complete device configuration when connected via FXA291 and service interface

• Logbooks can be downloaded in CSV format or binary format for "Field Data Manager" software

Field Data Manager

Visualization software and database for measuring, calibration and configuration data

• SQL database which is protected against manipulation

• Functions to import, save and print out logbooks

• Load curves to display measured values

a0016009

Field Data Manager: Load curves

Page 9: Technical Information Liquistation ... - Endress+Hauser Portal

Liquistation CSF22

Endress+Hauser 9

Input

Input types • 1 analog input

• 1 binary input

Binary input, passive

Span 12 to 30 V, galvanically isolated

Signal characteristics Minimum pulse width: 100 ms

Analog input, passive

Span 0/4 to 20 mA, galvanically isolated

Accuracy ±0.5 % of measuring range

Page 10: Technical Information Liquistation ... - Endress+Hauser Portal

Liquistation CSF22

10 Endress+Hauser

Output

Output types 1 binary output (standard):

Open collector, max. 30 V, 200 mA, galvanically isolated

Modbus RS485

Protocol-specific data

Power supply

Electrical connection --> For a detailed wiring diagram, see the Operating Instructions for Liquistation CSF22

Supply voltage 220 V AC ±10 %, 50 Hz

Caution!

A circuit breaker with a maximum rating of 10 A must be provided by the customer.

Power consumption 240 VA

Power failure • Real-time clock: lithium battery, type CR2032

• Power supply (optional): with additional charging control unit

Signal coding EIA/TIA-485

Data transmission rate 2,400, 4,800, 9,600, 19,200, 38,400, 57,600 and 115,200 baud

Galvanic isolation Yes

Connectors M12 (5-pin, B-coded, female)

Protocol RTU/ASCII

Function codes 03, 04, 06, 08, 16, 23

Broadcast support for function codes 06, 16, 23

Output data 16 measured values (value, unit, status), 8 digital values (value,

status)

Input data 4 setpoints (value, unit, status), 4 digital values (value, status),

diagnostic information

Supported features Address can be configured using switch or software

Page 11: Technical Information Liquistation ... - Endress+Hauser Portal

Liquistation CSF22

Endress+Hauser 11

Performance characteristics

Sampling methods • Time proportional sampling (CTCV)

• Flow proportional sampling (VTCV)

• Flow proportional sampling/time override (CTVV)

• Event sampling

• Single and multiple samples

• Sampling table

Sample volume 10 to 10000 ml (0.34 to 340 fl.oz.)

Dosing volume < 20 ml can vary in dosing accuracy and repeatability depending on application.

Dosing accuracy ±5 ml (0.17 fl.oz.) or 5 % of the set volume

Dosing volume < 20 ml can vary in dosing accuracy and repeatability depending on application.

Repeatability 5 %

Intake speed > 0.6 m/s (> 1.9 ft/s) for 10 mm (3/8") ID

Suction height Max. 8 m (26 ft)

Hose length Max. 30 m (98 ft)

Temperature control • Sample compartment temperature range: 2 to 20 °C (36 to 68 °F) ±2 °C

• Factory setting: + 4 °C (39 °F)

• Automatic defrost system

Page 12: Technical Information Liquistation ... - Endress+Hauser Portal

Liquistation CSF22

12 Endress+Hauser

Installation

Mounting conditions

a0014359

Mounting conditions

1. Correct

The suction line must be routed with a downward slope to the sampling point.

2. Incorrect

The sampler should never be mounted in a place where it is exposed to aggressive gases.

3. Incorrect

Avoid siphoning effects in the suction line.

4. Incorrect

The suction line should never be routed with an upward slope to the sampling point.

Note!

Note the following when mounting the sampler:

• Mount the sampler on a level surface.

• Protect the sampler from additional heating (e.g. from heaters).

• Protect the sampler from mechanical vibrations.

• Protect the sampler from strong magnetic fields.

• Do not mount the sampler directly over the inlet channel of the wastewater treatment plant (sulfur vapors!).

Page 13: Technical Information Liquistation ... - Endress+Hauser Portal

Liquistation CSF22

Endress+Hauser 13

Environment

Ambient temperature range 5 to 35 °C (41 to 95 °F)

Storage temperature -20 to 60 °C (0 to 140 °F)

Relative humidity 10 to 95%, not condensing

Degree of protection • Controller front panel: IP 65

• Controller with closed cover: IP 54

• Bottle compartment front: IP 54

Process

Sample temperature range 2 to 40 °C (36 to 104 °F)

Process pressure • Unpressurized, open channel (unpressurized sampling)

• Max. 0.8 bar piping (pressurized sampling)

Sample properties Sample media has to be free of abrasive substances.

Caution!

Pay attention to the material compatibility of the wetted parts.

Page 14: Technical Information Liquistation ... - Endress+Hauser Portal

Liquistation CSF22

14 Endress+Hauser

Mechanical construction

Dimensions

a0014362

Dimensions Liquistation CSF22 (depth = 637 mm (25.1"))

Weight 63 kg (139 lbs)

Material

Process connections Suction line ID 10 mm (3/8")

485 (19.1)

620 (24.4)

595 (23.4)mm (inch)

1154

(45.

4)

828

(32.

6)

Non-wetted parts

Cabinet housing Stainless steel 304x

For standard applications in wastewater treatment plants and

environmental monitoring

Sample compartment inner shell Stainless steel 304x

Wetted parts

Pump tubing Silicone

Distribution arm Plastic PE

Composite container/bottles Plastic PE

Suction line Plastic EPDM

Suction line connection Plastic PP

Page 15: Technical Information Liquistation ... - Endress+Hauser Portal

Liquistation CSF22

Endress+Hauser 15

Operability

Operating concept The simple and structured operating concept sets new standards:

• Intuitive operation with the navigator and soft keys

• Fast configuration of application-specific measurement options

• Easy configuration and diagnosis thanks to plain-text display

• All languages that can be ordered are available in every device

Display and operating

elements

Remote operation

a0016785

Easy operationa0013222-en

Plain-text menu

a0013639

• Liquid crystal display, backlighting

• 160 x 240 pixels

• 4 operating keys (soft key function) and navigator

• Menu-guided operation

a0016787

Modbus RS485

T Terminating resistor

FXA291

Modbus Master / Gateway

T T

Modbus RS485(RTU, ASCII)

CSF22

Page 16: Technical Information Liquistation ... - Endress+Hauser Portal

Liquistation CSF22

16 Endress+Hauser

Communication • 1 service interface, accessible via front panel connection

• Commubox FXA291 (accessory) required for communication with the PC

• M12 connector Modbus RS485 (5-pin, B-coded, female)

Software Field Data Manager

• Standardized user interface under Windows®

• Reading out the internal memory containing the measured flow rate, sample volume taken etc.

FieldCare

• Device settings saved in a database

• Configuration

Page 17: Technical Information Liquistation ... - Endress+Hauser Portal

Liquistation CSF22

Endress+Hauser 17

Ordering information

Product structure

Note!

Simply add the additional options to the order code you selected. Please contact your sales office if you have

any questions.

Note!

To receive a complete, operational sampling system, you have to order at least:

• 1 x CSF22 sampler

• 1 x sample distribution

• 1 x suction line with sample strainer

or

1 x suction line with sample filter

• 1 x signal cable to connect analog or binary inputs and outputs

Scope of delivery The scope of delivery comprises:

• 1 stationary sampler with:

– The ordered bottle configuration

– Optional hardware

• 1 "Commissioning" Operating Instructions

(In the preferred language if the "Default operating language" order option is selected. Otherwise, the Brief

Operating Instructions are supplied in English)

• Optional accessories

• 1 spare pump-tubing

Approval

AA Non-hazardous area

Sample distribution

1 1 x 20 liter (5.28 US gal.) PE

2 12 x 2 liter (0.53 US gal.), PE

3 24 x 1 liter (0.26 US gal.), PE

Sample temperature control

A Refrigerator indoor use, housing 1.4301 (AISI 304)

Additional option

1 Basic version

CSF22- Order code

Operating language (only one option may be selected)

AA English

AK Chinese

Accessory enclosed

N1 Suction line 10 mm (3/8") ID, EPDM, length 10 m (32 ft) + strainer 316(x)

N2 Suction line 10 mm (3/8") ID + filter, EPDM, length 10 m (32 ft)

N3 Signal cable to I/O connector

N4 Power pack for battery back-up sampling

Page 18: Technical Information Liquistation ... - Endress+Hauser Portal

Liquistation CSF22

18 Endress+Hauser

AccessoriesIn the following sections, you find the accessories available at the time of issue of this documentation.

For information on accessories that are not listed here, please contact your local service or sales

representation.

Accessories for Liquistation

CSF22

a0014726

Complete suction line

1 with stainer

2 with filter (protection removed)

Bottle tray + bottles + cap

71111155 Bottle tray + 12 x 2 liter (0.53 US gal.) PE wedge shaped bottle + cap

71111156 Bottle tray + 24 x 1 liter (0.26 US gal.) PE wedge shaped bottle + cap

Bottles + caps

71111170 20 liter (5.28 US gal.) PE + cap, 1 pc.

71111176 1 liter (0.26 US gal.) PE wedge shaped bottle + cap, 24 pcs.

71111178 2 liter (0.53 US gal.) PE wedge shaped bottle + cap, 12 pcs.

Complete suction line

71111234 Suction line ID 10 mm (3/8"), EPDM, length 10 m (33 ft), strainer V4A

71120800 Suction line ID 10 mm (3/8"), ID + filter, EPDM, length 10 m (33 ft)

Pump tubing customized

71114701 Pump tubing, 2 pcs.

71114702 Pump tubing, 25 pcs.

Accessories, electrics

71129420 Battery back-up (UPS), 1000 VA / 230 V

71130547 Signal cable to multi I/O connector

Communication, software

51516983 Commubox FXA291 + FieldCare Device Setup

71129799 Field Data Manager Software, Analysis

Page 19: Technical Information Liquistation ... - Endress+Hauser Portal

Liquistation CSF22

Endress+Hauser 19

Page 20: Technical Information Liquistation ... - Endress+Hauser Portal

Endress+Hauser Sales Center China

Endress+Hauser ShanghaiAutomation Equipment Co. Ltd.No. 458 Jiang Chuan Dong RoadShanghai 200241, P.R. China

Tel.: +86 21 24 03 96 00Fax: +86 21 24 03 96 03www.endress.comE-Mail: [email protected]

TI00473C/07/EN/03.12

71164110

FM+SGML 6.0