Page | 1 25 – May – 2016 Version 3.0 New Zealand Sustainable Forest Products LP Address: 10 Gannons Road, RD 1 Reefton, 7895 Phone 03 732 8414 E–Mail: [email protected] http://www.healthbasedbuilding.com/magnum-board Technical Manual Magnum Board Rigid Air Barrier System and Magnum Board Weatherboard System (WBS) Note: Always refer to this Technical Manual for correct installation procedures of Magnum Board for use as a Rigid Air Barrier and Weatherboard System. For any intended use outside of this Technical Manual specification, you must refer directly to the Manufacturer/ Supplier of the product ‘Magnum Board’ New Zealand Sustainable Forest Products LP for advice and written approval for ‘Specific Design prior to specification or installation of Magnum Board use, as a Rigid Air Barrier and Weatherboard System.

Technical Manual - Health Based Building

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

P a g e | 1 25 – May – 2016 Version 3.0

New Zealand Sustainable Forest Products LP Address: 10 Gannons Road, RD 1 Reefton, 7895

Phone 03 732 8414 E–Mail: [email protected] http://www.healthbasedbuilding.com/magnum-board

Technical Manual Magnum Board Rigid Air Barrier System

and

Magnum Board Weatherboard System (WBS)

Note: Always refer to this Technical Manual for correct installation procedures of Magnum Board for

use as a Rigid Air Barrier and Weatherboard System. For any intended use outside of this Technical Manual specification, you must refer directly to the Manufacturer/ Supplier of the product ‘Magnum Board’ – New Zealand Sustainable Forest Products LP for advice and written approval for ‘Specific Design ’ prior to specification or installation of Magnum Board use, as a Rigid Air Barrier and Weatherboard System.

Address: 10 Gannons Road, RD 1 Reefton, 7895

Phone 03 732 8414 E–Mail: [email protected] http://www.healthbasedbuilding.com/magnum-board

Table of Contents

1. Product Description, Features and Benefits

2. Product Scope of Use

3. Product Limitations

4. NZBC relevant Performance Clauses

5. Engineer, Designer and Specification details

6. Technical Drawings

Product Application Requirements

7. Installation Procedures

8. Components and Accessories List

9. Workplace Health and Safety – MSDS

10. Maintenance

11. Warranty

12. Quality Management System

13. Index of Terms and Wording

Onsite Requirements

14. Installer / Applicator (Approved Training and Register)

15. Checklist – Pre and Post Installation, and Final

This Technical Manual is Divided into Products 1 and 2;

Product 1 – Magnum Rigid Air Barrier System, Stage 1

Product 2 – Magnum Weatherboard System (WBS), Stage 2

P a g e | 2 25 – May – 2016 Version 3.0

New Zealand Sustainable Forest Products LP

P a g e | 3 25 – May – 2016 Version 3.0

New Zealand Sustainable Forest Products LP Address: 10 Gannons Road, RD 1 Reefton, 7895

Phone 03 732 8414 E–Mail: [email protected] http://www.healthbasedbuilding.com/magnum-board

Product 1 - Magnum Board Rigid Air Barrier System

Stage 1 - Product Description, Features and Benefits (Rigid Air Barrier)

The Magnum Board Rigid Air Barrier system is a mineral sheet-based rigid air barrier to be used over timber framing or light gauge steel framing prior to cladding installation, for use in wind zones up to and including ‘extra -high’ as defined by NZS3604. It is designed to provide seamless weather-proofing and wind resistant protection of wall framing.

The system consists of Magnum Board installed vertically and the ABEP Blue Barrier* liquid flashing system applied to board joints. When installed together they provide an easy to install barrier to moisture and high winds.

Features

MAGNUM BOARD RIGID AIR BARRIER is a white mineral board with a number of attributes including moisture resistance. It is supplied in the following;

Magnum Board Sizes

2.4m x 1.2m x 9mm ; 2.7m x 1.2m x 9mm ; 3.0m x 1.2m x 9mm

Benefits

• Entirely breathable / vapour permeable

• NZ appraised performance inclusive of extra high wind zone

• Materials have been subjected to some of the world’s toughest testing regimes

• Superior weather tightness and durability

• High impact resistance

• Free of nasty chemicals

• Reduce energy use by removing dependency on mechanical air movement systems and

reduction in air moisture levels

• Increased indoor air quality

• Conventional construction and installation methods

• High resistance to fire, water, mould, condensation, and pests

• Amazing negative CO2 attributes

• Downstream waste management with no impact on the environment

• Consider cost neutral with whole home performance benefits

*The ABEP Blue Barrier Liquid Flashing is blue in colour used to seal all board joints, junctionsbetween the boards and window or door openings and pipe penetrations. The ABEP Blue BarrierLiquid Flashing System is supplied in 7.57 litre tubs.

Address: 10 Gannons Road, RD 1 Reefton, 7895

Phone 03 732 8414 E–Mail: [email protected] http://www.healthbasedbuilding.com/magnum-board

Stage 1 - Product Scope of Use (Rigid Air Barrier)

The MAGNUM Board Rigid Air Barrier system has been designed for use behind cladding systems within the following scope:

Attached directly to new timber frame, designed and constructed in accordance with NZS 3604:2011 or galvanized steel framing, designed and constructed in accordance with wind zones up to and including ‘Extra High’ as per NZS 3604 Building Wind Zones.

The MAGNUM Board Rigid Air Barrier system shall be installed only by trained and approved applicators.

Stage 1 - Product Limitations (Rigid Air Barrier)

All edges must be supported by framing.

Magnum Building Products will assume no responsibility for water infiltration.

Stage 1 - NZBC Relevant Performance Clauses (Rigid Air Barrier)

Structural performance - Clause B1

The MAGNUM Board Rigid Air Barrier system when used in accordance with this Appraisal Certificate and subjected to normal conditions of environment and use, is expected to tolerate wind forces up to and including Extra High as defined in NZS 3604:2011.

Durability - Clause B2

The MAGNUM Board Rigid Air Barrier system when used in accordance with this Appraisal Certificate and subjected to normal conditions of environment and use is expected to have a serviceable life of at least 50 years according to the design option selected.

External Moisture - Clause E2

The installation of the MAGNUM Board Rigid Air Barrier system is reliant on the correct application of the ABEP Blue Barrier Liquid Flashing. The design of details not included within the Technical Manual are subject to specific design and are outside the scope of this Appraisal Certificate.

Hazardous Building Materials - Clause F2

Performance F2.3.1. The MAGNUM Board Rigid Air Barrier system when installed according to the requirements of this appraisal meets this requirement and will not present a health hazard to people using the building. P a g e | 4 25 – May – 2016 Version 3.0

New Zealand Sustainable Forest Products LP

P a g e | 5 25 – May – 2016 Version 3.0

New Zealand Sustainable Forest Products LP Address: 10 Gannons Road, RD 1 Reefton, 7895

Phone 03 732 8414 E–Mail: [email protected] http://www.healthbasedbuilding.com/magnum-board

Stage 1 - Engineer, Designer and Specification considerations (Rigid Air Barrier)

Designers are responsible for the framing design, and building contractors are responsible for the quality of construction of the framing.

The MAGNUM Board Rigid Air Barrier system is for use on new and existing timber framing to provide a wind and moisture resistant barrier when the building is situated in high to extra high wind zones.

Specification It is advised that the Architect/Designer or Specifier denote on the building/design plans for the purpose of identifying product use as follows;

Magnum Board Rigid Air Barrier System BEAL Appraisal C1405

A note should also be included directing all parties to where information can be obtained from our website.

Note: www.healthbasedbuilding.com for Technical Manual and Information on Magnum Board Rigid Air Barrier System

Stage 1 - Product Application Requirements (Rigid Air Barrier)

Installation Procedures

Storage Always lay Magnum Board Rigid Air Barrier on a solid surface and protect it from weather and dirt prior to and during installation. Always protect the corners of Magnum Board Rigid Air Barrier prior to and during installation. Do not stack other materials on top of Magnum Board Rigid Air Barrier.

Pre -Installation Installation of the MAGNUM Board Rigid Air Barrier sheets and ABEP Blue Barrier Liquid Flashing must be completed by New Zealand Sustainable Forest Products approved and trained tradesmen who have experience in the installation of Rigid Air Barriers.

It is the responsibility of the Rigid Air Barrier installer to inspect their workplace prior to beginning the installation of Magnum Board Rigid Air Barrier to ensure the installed work will meet the owner's / contractor's requirements.

Special Note: Notify owner / general contractor of any concerns prior to the start of Magnum Board Rigid Air Barrier installation.

The moisture content of any new timber framing must be no higher than 18%.

P a g e | 6 25 – May – 2016 Version 3.0

New Zealand Sustainable Forest Products LP Address: 10 Gannons Road, RD 1 Reefton, 7895

Phone 03 732 8414 E–Mail: [email protected] http://www.healthbasedbuilding.com/magnum-board

Install Magnum Board Rigid Air Barrier to nominal 100 X 50 steel or timber framing members spaced a maximum of 600mm on centres

Magnum Board Rigid Air Barrier is to be installed vertically.

All edges must be supported by framing.

The application of the ABEP Blue Barrier Liquid Flashing must not be undertaken when the substrate temperature is below 4°C or if it is likely to drop below 4°C during drying/curing time.

Cutting Magnum Board Rigid Air Barrier You can easily cut Magnum Board with a carbine tipped scoring knife, keyhole saw, saber-saw or power saw equipped with a carbide blade and HEPA vacuum extraction.

Measure accurately and mark your cutting locations before cutting.

Make circular cuts and irregular angle cuts using a cement board bit or carbide tipped bit, a keyhole saw or a saber-saw.

To perform cut outs for electrical outlets, light receptacles, switches, etc., carefully measure and mark the location of the opening on the face of Magnum Board®. Outline the opening in pencil and cut it out with a keyhole saw or circle cutter equipped with carbide tipped tooling. The hole must be accurately located and cut to size.

Position cutting station so that wind will blow dust away from the user or others in the working area and allow for ample dust dissipation.

Score and snap using carbide-tipped scoring knife or utility knife (ability to use this method depends on thickness of Magnum Board being installed).

Fibre-cement shears (electric or pneumatic).

Dust-reducing circular saw equipped with appropriate blade and HEPA vacuum extraction.

Dust-reducing circular saw with appropriate saw blade.

Always use correct tools when executing cutting operations.

Even though Magnum Board is a non-toxic building material always wear a dusk mask, safety glasses and follow MSDS Guidelines.

Never use a power saw indoors.

Never use a circular saw blade that is inappropriate for the specific operation being undertaken.

Never use a grinder or continuous rim diamond blade for cutting.

Never dry sweep - use wet suppression methods or HEPA vacuum.

P a g e | 7 25 – May – 2016 Version 3.0

New Zealand Sustainable Forest Products LP Address: 10 Gannons Road, RD 1 Reefton, 7895

Phone 03 732 8414 E–Mail: [email protected] http://www.healthbasedbuilding.com/magnum-board

Fig 1: HEPA extraction system with recommended cutting equipment

Magnum Board must be installed vertically using pneumatic nail or screw fasteners as per fixing detail below.

Fix at 15mm-20mm in from outside edges and 50mm in from corners. Ensure fixing at 300mm minimum spacing between fasteners and 600mm centres across 1200mm wide sheets.

Magnum Board Rigid Air Barrier can be installed rebate edge to rebate edge or square edge to square edge if the rebated edge has been removed.

Magnum Board Rigid Air Barrier is *pneumatically nailed to timber framing Magnum Board Rigid Air Barrier is **screwed to steel framing.

*Nails fixing is with a Paslode - Impulse Nail 65 x 2.8mm Stainless Steel Round Drive Paslode code B20560. TOOL: Paslode - Framemaster Impulse Nailer B20543 or B20540 with Paslode No Mar Tip (B20544G). Nails heads to be embedded flush with Magnum Board surface.

**Screwed fixing to steel framing using Simpson Strong-Tie PN WSCBGHLA114SA. TOOL: Quick Drive with PRO175 attachment. Available through Simpson Strong-Tie. Screws to be embedded Flush with Magnum Board surface.

Magnum Board Rigid Air Barrier must be joint sealed with ABEP Blue Barrier sealant to all butt joint to butt joints, all rebated edges and all cut outs supporting aspects such as pipework, also all external corners and all internal corners. Pre-priming to joins is not required. ABEP Blue Barrier Sealant must be applied using sealant gun. Raised sealant can be spread flat using conventional putty knife as per detail below. Sealant is not required over nail or screw heads.

Period of exposureSelected Cladding must be installed and coated within 90 days of Magnum Board Rigid Air Barrier installation. Selected cladding must comply with requirements NZBC.

NZS0090

50mm

50mm

50mm

50mm

50mm1200mm

2400mm

Mid Line

300mm

Maxim

um spacing betw

een fasteners

15-20mm

from edge

15-20mm

from edge

50mm

50mm

50mm

300mm

Maxim

um spacing betw

een fasteners

300mm

Maxim

um spacing betw

een fasteners

lifeInstall it for

Install it forh

ealth

Ma

gn

uM

Boa

rd d

etailed

Fixin

g in

stallatio

n d

iag

raM

P a g e | 9 25 – May – 2016 Version 3.0

New Zealand Sustainable Forest Products LP Address: 10 Gannons Road, RD 1 Reefton, 7895

Phone 03 732 8414 E–Mail: [email protected] http://www.healthbasedbuilding.com/magnum-board

Product 2 - Magnum Board Weatherboard System (WBS)

Stage 2 - Product Description, Features and Benefits (WBS)

The Magnum Weatherboard System is made up of several key components, starting with;

1. timber framing or light gauge steel framing, for use in wind zones up to and including‘extra-high’ as defined by NZS3604

2. Magnum Board Rigid Air Barrier system which incorporates the ABEP Blue Barrier* liquidflashing system,

3. Vapour-permeable mineral sheet based Magnum weatherboard attached to H3.2 treatedtimber battens with specified nail fixings.

The complete system is designed to provide a vapour permeable, durable exterior cladding when over-coated with Foreverbreathe vapour-permeable coating finish.

Features MAGNUM BOARD Weatherboard is a white mineral board with a number of attributes including moisture resistance. It is supplied in the following;

Board Sizes:

3.0m x 195mm x 9mm

Benefits

• Entirely breathable / vapour permeable

• NZ appraised performance inclusive of extra high wind zone

• Materials have been subjected to some of the world’s toughest testing regimes

• Superior weather tightness and durability

• High impact resistance

• Free of nasty chemicals

• Reduce energy use by removing dependency on mechanical air movement systems and

reduction in air moisture levels

• Increased indoor air quality

• Conventional construction and installation methods

• High resistance to fire, water, mould, condensation, and pests

• Amazing negative CO2 attributes

• Downstream waste management with no impact on the environment

• Consider cost neutral with whole home performance benefits

P a g e | 10 25 – May – 2016 Version 3.0

New Zealand Sustainable Forest Products LP Address: 10 Gannons Road, RD 1 Reefton, 7895

Phone 03 732 8414 E–Mail: [email protected] http://www.healthbasedbuilding.com/magnum-board

Stage 2 - Product Scope of Use (WBS)

The MAGNUM Weatherboards system has been appraised for use as an external cladding direct fixed over the Magnum Board Rigid Air Barrier system which is fixed over timber or light gauge steel framing within the following scope:

Used in conjunction with new timber or light gauge galvanized steel framing designed andconstructed to comply with the requirements of the NZBC; and,

Situated in wind zones up to, and including, ‘Extra High’ as per NZS 3604 Building WindZones

The MAGNUM Weatherboard system shall be installed only by trained and approved installers.

Product Limitations

The MAGNUM Weatherboard system must be installed over a Rigid Air Barrier, and is limited to use up to and including 10 metres in wall height.

The moisture content of any new or old timber framing must be no higher than 18%.

The installation of the MAGNUM Weatherboards system is reliant on the correct application of the Foreverbreathe coating system.

For all uses including “specific design” that fall outside of this Technical Manual and the Appraisal certificate, must be determined and approved by Engineers, Architects and/or Professionals in accordance with all relevant requirements of the New Zealand Building Code .

Stage 2 - NZBC Relevant Performance Clauses (WBS)

Structural performance - Clause B1

The MAGNUM Weatherboard system when used in accordance with this Appraisal Certificate and subjected to normal conditions of environment and use, is expected to tolerate wind forces up to and including Extra High as defined in NZS 3604:2011.

Durability - Clause B2

The MAGNUM Weatherboards system when used in accordance with this Appraisal Certificate and subjected to normal conditions of environment and use, is expected to have a serviceable life of at least 15 years for the Magnum Weatherboard substrate and 5 years for the protective coating system. Warranties of 20 years are available from New Zealand Sustainable Forest Products.

P a g e | 11 25 – May – 2016 Version 3.0

New Zealand Sustainable Forest Products LP Address: 10 Gannons Road, RD 1 Reefton, 7895

Phone 03 732 8414 E–Mail: [email protected] http://www.healthbasedbuilding.com/magnum-board

External Moisture - Clause E2

The installation of the MAGNUM Weatherboards system is reliant on the correct application of the Foreverbreathe coating system.

The design of details not included within the Technical Manual are subject to specific design and are outside the scope of the Appraisal Certificate.

Hazardous Building Materials - Clause F2

Performance F2.3.1. The MAGNUM Weatherboard system when installed according to the requirements of this appraisal meets this requirement and will not present a health hazard to people using the building.

Stage 2 - Engineer, Designer and Specification considerations

(WBS)

Designers are responsible for the framing design, and building contractors are responsible for the quality of construction of the framing.

The MAGNUM Weatherboard system is for use on new and existing timber framing to provide a wind and moisture resistant barrier when the building is situated in high to extra high wind zones.

Specification It is advised that the Architect/Designer or Specifier denote on the building/design plans for the purpose of identifying product use as follows;

Magnum Board Rigid Air Barrier and Weatherboard System BEAL Appraisal C1405

A note should also be included directing all parties to where information can be obtained from our website.

Note: www.healthbasedbuilding.com for Technical Manual and Information on Magnum Board Rigid Air Barrier and Weatherboard

System

P a g e | 12 25 – May – 2016 Version 3.0

New Zealand Sustainable Forest Products LP Address: 10 Gannons Road, RD 1 Reefton, 7895

Phone 03 732 8414 E–Mail: [email protected] http://www.healthbasedbuilding.com/magnum-board

Stage 2 - Product Application Requirements (WBS)

Installation Procedures

Storage Always lay Magnum Board Weatherboard on a solid surface and protect it from weather and dirt prior to and during installation. Always protect all edges of Magnum Weatherboard prior to and during installation. Do not stack other materials on top of Magnum Board Weatherboard.

Pre -Installation Installation of the MAGNUM Weatherboard and components must be completed by New Zealand Sustainable Forest Products approved and trained tradesmen who have experience in the installation of Magnum Weatherboard system.

It is the responsibility of the Magnum Weatherboard system installer to inspect their work place prior to beginning the installation to ensure the installed work will meet the owner / contractors requirements.

Special Note: Notify owner / general contractor of any concerns prior to the start of Magnum Weatherboard system installation.

The moisture content of any new or existing timber framing must be no higher than 18%.

Install Magnum Weatherboard to a batten fixed over a nominal 100 X 50 steel or timber framing members spaced a maximum of 600mm on centres with a Rigid Air Barrier installed.

Magnum Weatherboard is to be installed horizontally.

Cutting Magnum Weatherboard You can easily cut Magnum Board with a carbide tipped scoring knife, keyhole saw, saber saw or power saw equipped with a carbide blade and HEPA vacuum extraction

Measure accurately and mark your cutting locations before cutting.

Make circular cuts and irregular angle cuts using a cement board bit or carbide tipped bit, a keyhole saw or a saber saw.

To perform cut outs for electrical outlets, light receptacles, switches, etc., carefully measure and mark the location of the opening on the face of Magnum Board®. Outline the opening in pencil and cut it out with a keyhole saw or circle cutter equipped with carbide tipped tooling. The hole must be accurately located and cut to size.

Position cutting station so that wind will blow dust away from the user or others in the working area and allow for ample dust dissipation.

P a g e | 13 25 – May – 2016 Version 3.0

New Zealand Sustainable Forest Products LP Address: 10 Gannons Road, RD 1 Reefton, 7895

Phone 03 732 8414 E–Mail: [email protected] http://www.healthbasedbuilding.com/magnum-board

Score and snap using carbide-tipped scoring knife or utility knife (Ability to use this method depends on thickness of Magnum Board being installed.)

Fibre-cement shears (electric or pneumatic)

Dust-reducing circular saw equipped with appropriate blade and HEPA vacuum extraction. Dust

reducing circular saw with appropriate saw blade.

Always use correct tools when executing cutting operations.

Even though Magnum Weatherboard is a non-toxic building material always wear a dusk mask, safety glasses and follow MSDS Guidelines.

Never use a power saw indoors.

Never use a circular saw blade that is inappropriate for the specific operation being undertaken.

Never use a grinder or continuous rim diamond blade for cutting.

Never dry sweep - use wet suppression methods or HEPA vacuum.

Fixing Details

Magnum Board Weather Board must be installed horizontally to minimum 43mm x 20mm vertical battens using the fixing detail. see Fig 1

To help ensure proper alignment, use a 4 ft or longer level to check the first course.

P a g e | 14 25 – May – 2016 Version 3.0

New Zealand Sustainable Forest Products LP Address: 10 Gannons Road, RD 1 Reefton, 7895

Phone 03 732 8414 E–Mail : [email protected] http://www.healthbasedbuilding.com/magnum-board

Install a timber starter strip at the bottom of the structure to ensure a consistent plant angle throughout installation. Reference figure 2

Fig 2

For full length fixing a minimum of 50mm in from ends and 30mm down from the top edge is required and 400mm minimum spacing between fasteners.

Always install cut ends of Magnum Weatherboard to internal and external corners and window / doors openings with a maximum 40mm overhang to battens.

For full length fixing to minimum 43mm x 20mm battens Magnum Board Weather Board is pneumatically nailed. Nails are Paslode* Impulse Nail 65 x 2.8mm Stainless Steel Round Drive Paslode code B20550. Ensure nail heads to be embedded flush with Magnum Board surface

TOOL: Paslode* Framemaster Impulse Nailer B20543 or B20540 with Paslode No Mar (K) Tip (B20544G)

See Fig 3

Fig 3

Magnum Board Weather Boards must be installed with a minimum 40mm lap.

For butt end to butt end fixing Magnum Board must be pre-bored to match the nail dimension with nail positions a minimum of 20mm in from the butt edge and 30mm down from the top edge. Nails are stainless steel 435276. Refer Fig 4

P a g e | 15 25 – May – 2016 Version 3.0

New Zealand Sustainable Forest Products LP Address: 10 Gannons Road, RD 1 Reefton, 7895

Phone 03 732 8414 E–Mail: [email protected] http://www.healthbasedbuilding.com/magnum-board

It is a requirement to back-block butt end to butt end weatherboard joints on a minimum 65mm x 20mm battens with the batten extending to 200mm minimum above and below the board to be jointed. (note: this requirement is when a butt joint in the weatherboard appears between battens directly fixed over a stud) Refer Fig 4

Always end seal butt ends to be jointed with Foreverbreathe silicate paint or suitable alternative primer

Always butt join Magnum Board Weather Board with moderate edge contact. Refer Fig 4

Fig 4

External corners can be square cut for connection to corner soakers or timber

profiles to suit design details.

See fig 5

Fig 5

Butt End Joint

43 x 20mm 65 x 20mm 43 x 20mm

P a g e | 16 25 – May – 2016 Version 3.0

New Zealand Sustainable Forest Products LP Address: 10 Gannons Road, RD 1 Reefton, 7895

Phone 03 732 8414 E–Mail: [email protected] http://www.healthbasedbuilding.com/magnum-board

Internal corners must be cut to match the natural angle of the Magnum Weatherboards as they meet.

See Fig 6

Fig 6

Internal corner flashings must be fitted. See Fig 7

Fig 7

https://www.e2flashingsolutions.co.nz/soakers-new/

Stage 2 - EXTERIOR Coating System - PREPARATION AND PAINTING PROCEDURES.

To retain vapour permeability Magnum Board Weather Board can be painted with Foreverbreathe exterior silicate paint. Product information sheets can be found at www.healthbasedbuilding.com

The application of the Foreverbreathe Coating system must not be undertaken when the substrate temperature is below 4°C or if it is likely to drop below 4°C during drying/curing time.

P a g e | 17 25 – May – 2016 Version 3.0

New Zealand Sustainable Forest Products LP Address: 10 Gannons Road, RD 1 Reefton, 7895

Phone 03 732 8414 E–Mail: [email protected] http://www.healthbasedbuilding.com/magnum-board

Alternative non breathable paint options include Resene Stone Strenghtener as the primer and Resene acrylic tops coats. Product information can be found at www.resene.co.nz

Nuplex Fairing Crème can be used to fill minor gaps between joints or surface indentations.

Period of exposureMagnum Board Weather Boards must be painted within 30 days of installation to ensure best performance.

Product 1 and 2 - Technical Drawings (Rigid Air Barrier & WBS)

Drawings are available for Product 1 in Appendix A and Product 2 in Appendix B

All drawings are available for download within the technical manuals in the respective product listings at http://www.healthbasedbuilding.com/magnum-board

Magnum Board Rigid Air Barrier and Weatherboard System (WBS)

Component List

Product Description Photo Magnum Board Rigid Air Barrier

2.4 x 1.2 x 9mm 2.7 x 1.2 x 9mm 3.0 x 1.2 x 9mm

Magnum Board Weather Board 3.0 x 195 x 9mm

New Zealand Sustainable Forest Products LP

Address: 10 Gannons Road, RD 1 Reefton, 7895

Phone 03 732 8414 E–Mail: [email protected] http://www.healthbasedbuilding.com/magnum-board

Sausage dispenser

Accessories List

Product Description Photo

Paslode Framemaster

Impulse Nailer Gun

Paslode* No-Mar (K) Tip

(Cat #B20544G)

P a g e | 18 25 – May – 2016 Version 3.0

Paslode Round Drive Nails 65x2.8MM SS Round Drive

Paslode code B20560

Mapei Sealant

Thermaflash Flashing Tape 75mm, 150mm, 200mm x23m rolls

New Zealand Sustainable Forest Products LP

Address: 10 Gannons Road, RD 1 Reefton, 7895

Phone 03 732 8414 E–Mail: [email protected] http://www.healthbasedbuilding.com/magnum-board

FX Exterior/Interior Plaster 10 Litre

Foreverbreathe Exterior

Silicate Paint

10 Litre

TERRA LANA WOOL

INSULATION

To Specification

HEALTH BASED BUILDING

COVER BOARDS AND

SCRIBERS

To Specification

P a g e | 19 25 – May – 2016 Version 3.0

P a g e | 20 25 – May – 2016 Version 3.0

New Zealand Sustainable Forest Products LP Address: 10 Gannons Road, RD 1 Reefton, 7895

Phone 03 732 8414 E–Mail: [email protected] http://www.healthbasedbuilding.com/magnum-board

Workplace Health and Safety – MSDS (Rigid Air Barrier & WBS)

All products must be stored inside, in a well ventilated area, up off concrete floors, kept dry, out of direct sunlight and away from freezing conditions. The membrane products, in the original unopened containers, have a shelf life of 12 months from date of manufacture.

MSDS is in Appendix B

Maintenance (Rigid Air Barrier & WBS)

Product 1 – Once the Rigid Air Barrier system has been installed as per this Technical Manual and Appraisal certificate, no further maintenance is required.

Product 2 - Once the Magnum Weatherboard system has been installed as per this technical manual and as required by the NZBC, the exterior finish system (Foreverbreathe) will require periodic washing to remove air and wind driven pollution and salts. The exterior finish system will require re-application – refer to the manufacture of the exterior coating finish (Foreverbreathe) for recommendations.

Warranty (Rigid Air Barrier & WBS)

Warranty can be downloaded from our website at https://www.healthbasedbuilding.co.nz/documents/MagnumBoardWarrantyDocument30-year.pdf

Quality Management System the BPQP

The Quality Assurance program flow chat is available from our website https://www.healthbasedbuilding.co.nz/documents/MagnumBoardQualityAssuranceFlowchart.pdf

Index of Terms and Wording

Weatherboard System, is abbreviated to - WBS

Material Safety Data Sheet, is abbreviated to – MSDS

New Zealand Building Code, is abbreviated to – NZBC

P a g e | 21 25 – May – 2016 Version 3.0

New Zealand Sustainable Forest Products LP Address: 10 Gannons Road, RD 1 Reefton, 7895

Phone 03 732 8414 E–Mail: [email protected] http://www.healthbasedbuilding.com/magnum-board

New Zealand Standard, is abbreviated to – NZS

Product 1 and 2 - Onsite Requirements (Rigid Air Barrier & WBS)

Checklist – Pre and Post Installation, and Final

The checklist is in Appendix D

P a g e | 22 25 – May – 2016 Version 3.0

New Zealand Sustainable Forest Products LP Address: 10 Gannons Road, RD 1 Reefton, 7895

Phone 03 732 8414 E–Mail: [email protected] http://www.healthbasedbuilding.com/magnum-board

Appendix A

50

BARGE - NO SOFFIT - SECTION DETAIL

35

1:5MAGNUM BOARD WEATHER BOARD

Y - Refer E2/AS1 Table 7

Z - R

efer

Tab

le7

E2/

AS

1

125mm min - Refer E2/AS1 Fig 45

1:5MAGNUM BOARD

PREFINISHED METAL BARGEFLASHING. CONFIRM MIN COVERREQUIREMENTS OVER WITH E2/AS1TABLE 7.

PROFILED SELECTED ROOFINGON ROOFING UNDERLAY

COMPRESSIBLE SEAL. CONFIRMIF REQUIRED WITH SELECTEDROOFING MANUFACTURER'SINSTRUCTIONS.

H3.2 200x18 FJ MCA FASCIA -BY HEALTH BASED BUILDING.PRE PRIMED.

9mm thick x 200mm MAGNUM BOARD®WEATHER BOARD. 40mm LAP TO TOP.ON H3.1 MCA Micro Pro Osmose 50 x20mm PINE TIMBER CAVITY BATTEN.PRE COAT BACK OF BATTEN WITHABEP BEP® Blue Barrier LIQUID APPLIEDFLASHING

9mm MAGNUM BOARD® RIGID AIRBARRIER

ROOF - WALL RIDGE - SECTION DETAIL

© New Zealand Sustainable Forest Products LP

MAGNUM BOARD WEATHER BOARD CLADDINGVERSION 01.00 SEPTEMBER 2015

http://www.healthbasedbuilding.com/magnum-board

PROFILED SELECTED ROOFING ONROOFING UNDERLAY

FOLDED 0.55 BMTPREFINISHED METAL EAVESFLASHING WITH HEM AT TOPEDGE

SELECTED SPOUTING

35mm MIN EAVE FLASHINGOVERLAP

H3.2 150x18 FJ MCA FASCIA -BY HEALTH BASED BUILDING.PRE PRIMED.

WEATHERBOARD FIXINGS -PASLODE* IMPULSE NAIL 65x2.8MMSS ROUND DRIVE. FIX AT EVERYCAVITY BATTEN, 600 CRS MAX.30mm FROM TOP OF BOARD.

ROOF STRUCTURE INACCORDANCE WITH NZS3504:2011OR SPECIFIC ENGINEERINGDESIGN.

PROVIDE SOLID BLOCKING FOR FIXING

9mm thick x 200mm MAGNUM BOARD® WEATHER BOARD. 40mm LAP TO TOP. ON H3.1 MCA Micro Pro Osmose 50 x 20mm PINE TIMBER CAVITY BATTEN. PRIOR TO INSTALLATION. PRE COAT BACK OF BATTEN WITH ABEP BEP® Blue Barrier LIQUID APPLIED FLASHING

RIGID AIR BARRIER AND INTERIOR LINING FIXINGS: PASLODE* IMPULSE NAIL 65x2.8MM SS ROUND DRIVE REFER TO MAGNUM BOARD RIGID AIR BARRIER TECHNICAL MANUAL SPECIFICATIONS AND FIXING INSTALLATION DIAGRAM.

9mm MAGNUM BOARD® RIGID AIR BARRIER

RIGID AIR BARRIER FIXINGS: PASLODE* IMPULSE NAIL 65x2.8MM SS ROUND DRIVE REFER TO MAGNUM BOARD RIGID AIR BARRIER TECHNICAL MANUAL SPECIFICATIONS AND FIXING INSTALLATION DIAGRAM.

WEATHERBOARD FIXINGS -PASLODE* IMPULSE NAIL 65x2.8MM SS ROUND DRIVE. FIX AT EVERY CAVITY BATTEN, 600 CRS MAX. 30mm FROM TOP OF BOARD.

NOTE:1. ALL MAGNUM BOARD®, ABEP® AND FLASHMAN® PRODUCTS TO BE INSTALLED

BY APPROVED INSTALLERS APPROVED BY NZSFP LTD. 2. WHERE ABEP BEP® BLUE BARRIER IS IN CONTACT WITH BIOPIN® PAINT, CEMIX

ACRYLBOND MUST BE APPLIED BEFORE APPLICATION OF BIOPIN PAINT®. 3. HARDIE & THOMSON® COVER BOARDS AND SCRIBERS, BIOPIN PAINT®, TERRA

LANA® WOOL INSULATION ARE SUPPLIED AND INSTALLED BY OTHERS.

1

ENSURE ROOFING UNDERLAY IS LAIDHORIZONTALLY AND OVER TOP OF EAVESFLASHING.ENSURE ROOF FIXING DOES NOTPENETRATE EAVE FLASHING

EAVE WALL JUNCTION - SECTION DETAIL1:5MAGNUM BOARD WEATHERBOARDS

PROFILED SELECTED ROOFING ONROOFING UNDERLAY

35

125mm min - Refer E2/AS1 Fig 45

50

© New Zealand Sustainable Forest Products LP

MAGNUM BOARD WEATHER BOARD CLADDINGVERSION 01.00 SEPTEMBER 2015

http://www.healthbasedbuilding.com/magnum-board

50mm MIN ROOFING OVERHANG

FOLDED 0.55 BMT PREFINISHED METAL EAVES FLASHING WITH HEM AT TOP EDGE

35mm MIN EAVE FLASHING OVERLAP

SELECTED GUTTER

H3.2 180x18 FJ MCA FASCIA - BY HEALTH BASED BUILDING. PRE PRIMED. GROOVED TO TAKE SOFFIT LININGS.

EAVE STRUCTURE IN ACCORDANCE WITH NZS3604:2011 OR SPECIFIC ENGINEERING DESIGN.

9mm MAGNUM BOARD® SOFFIT LINING. FLUSH STOPPED. FOREVERBREATHE SILICATE PAINT FINISH.

INTERIOR WALL LINING - 9mm MAGNUM BOARD® FOREVERBREATHE PAINT® FINISH

INTERIOR LINING FIXINGS -PASLODE* IMPULSE NAIL 65x2.8MM SS ROUND DRIVE PASLODE CODE B20560. FIX AT EVERY 300 crs AROUND PERIMETER, 50mm FROM CORNERS.15-20 FROM EDGE. REFER TO MAGNUM BOARD FIXING INSTALLATION DIAGRAM.

9mm MAGNUM BOARD®RIGID AIR BARRIERRIGID AIR BARRIER FIXINGS: PASLODE* IMPULSE NAIL 65x2.8MM SS ROUND DRIVE . REFER TO MAGNUM BOARD RIGID AIR BARRIER TECHNICAL MANUAL SPECIFICATIONS. 15-20mm IN FROM EDGE. 50mm FROM CORNERS.

H3.1 EX 50x25mm PRE PRIMED TREATED SOFFIT MOULDING

9mm thick x 200mm MAGNUM BOARD® WEATHER BOARD. 40mm LAP TO TOP. ON H3.1 MCA Micro Pro Osmose 50 x 20mm PINE TIMBER CAVITY BATTEN.

PRIOR TO INSTALLATION, PRE COAT BACK OF BATTEN WITH ABEP BEP®Blue Barrier LIQUID APPLIED FLASHING

WEATHERBOARD FIXINGS - PASLODE* IMPULSE NAIL 65x2.8MM SS ROUND DRIVE. FIX AT EVERY CAVITY BATTEN, 600 CRS MAX. 30mm FROM TOP OF BOARD.

RIGID AIR BARRIER FIXINGS: PASLODE* IMPULSE NAIL 65x2.8MM SS ROUND DRIVE . REFER TO MAGNUM BOARD RIGID AIR BARRIER TECHNICAL MANUAL SPECIFICATIONS. 15-20mm IN FROM EDGE. 50mm FROM CORNERS.

NOTE:1. ALL MAGNUM BOARD®, ABEP® AND FLASHMAN® PRODUCTS TO BE INSTALLED

BY APPROVED INSTALLERS APPROVED BY NZSFP LTD. 2. WHERE ABEP BEP® BLUE BARRIER IS IN CONTACT WITH BIOPIN® PAINT, CEMIX

ACRYLBOND MUST BE APPLIED BEFORE APPLICATION OF BIOPIN PAINT®. 3. HARDIE & THOMSON® COVER BOARDS AND SCRIBERS, BIOPIN PAINT®, TERRA

LANA® WOOL INSULATION ARE SUPPLIED AND INSTALLED BY OTHERS.

2

35

12CONTINUOUS FLEXIBLE AIR SEAL ONPEF BACKING ROD TO PERIMETER OFOPENING.

FLOOR CONSTRUCTION: 19mm x 128mmT&G FOREVER BEECH ENGINEEREDFLOORING.ON 9mm MAGNUM BOARD,ON 240x45mm SG8 H1.2 TREATEDTIMBER FLOOR JOISTS AT 450mm CRSMAX. R1.9 UNDER FLOOR INSULATION90mm THICK.

FLEXIBLE FLASHING TAPE PERE2/AS1 2011 FIGURE 17b

2/240X45 HYSPAN JOISTS.

CAVITY CLOSER.

9mm MAGNUM BOARD RIGID AIRBARRIER

VERANDAH / DECK THRESHOLD - SECTION DETAIL1:5

50

25

EPDM WASHERS AT BOLTFIXINGS. ENSURE CLADDING ISSEALED PRIOR TO FIXINGPACKERS

DECK CONSTRUCTION 19mm THICKSELECTED HARDWOOD DECKINGON DECK JOISTS AT 400mm CRSMAX. FIXED TO STRINGER

TIMBER PACKER AT BOLT FIXINGS

DECK STRINGER & FIXINGS INACCORDANCE WITH NZS3604:2011OR SPECIFIC ENGINEERINGDESIGN

9mm thick x 200mm MAGNUM BOARD®WEATHER BOARD. 40mm LAP TO TOP.ON H3.1 MCA Micro Pro ® Osmose 50x20FJ TIMBER CAVITY BATTEN.PRIOR TO INSTALLATION, PRE COATBACK OF CAVITY BATTEN WITH ABEPBEP® Blue Barrier LIQUID APPLIEDFLASHING

12mm GAP BETWEEN STRINGERAND CLADDING/ JOINERY.NOTE: 20mm GAP IF DECK ISINDEPENDENTLY SUPPORTED

© New Zealand Sustainable Forest Products LP

MAGNUM BOARD WEATHER BOARD CLADDINGVERSION 01.00 SEPTEMBER 2015

http://www.healthbasedbuilding.com/magnum-board

FIXINGS - PASLODE* IMPULSE NAIL65x2.8MM SS ROUND DRIVE PASLODECODE B20560. FIX AT EVERY CAVITYBATTEN, 600mm CRS MAX.

NOTE:1. ALL MAGNUM BOARD®, ABEP® AND FLASHMAN® PRODUCTS TO BE INSTALLED

BY APPROVED INSTALLERS APPROVED BY NZSFP LTD. 2. WHERE ABEP BEP® BLUE BARRIER IS IN CONTACT WITH BIOPIN® PAINT, CEMIX

ACRYLBOND MUST BE APPLIED BEFORE APPLICATION OF BIOPIN PAINT®. 3. HARDIE & THOMSON® COVER BOARDS AND SCRIBERS, BIOPIN PAINT®, TERRA

LANA® WOOL INSULATION ARE SUPPLIED AND INSTALLED BY OTHERS.

3

CANOPY JUNCTION - SECTION DETAIL1:5MAGNUM BOARD WEATHERBOARDS

35

Y - Refer Table 7 E2/AS1

755

MIN

GA

PM

INC

OV

ER

© New Zealand Sustainable Forest Products LP

MAGNUM BOARD WEATHER BOARD CLADDINGVERSION 01.00 SEPTEMBER 2015

http://www.healthbasedbuilding.com/magnum-board

9mm thick x 200mm MAGNUM BOARD® WEATHER BOARD. 40mm LAP TO TOP.ON H3.1 MCA Micro Pro Osmose 50 x 20mm PINE TIMBER CAVITY BATTEN.

9mm MAGNUM BOARD® RIGID AIR BARRIER

PRIOR TO INSTALLATION, PRE COAT BACK OF BATTEN WITH ABEP BEP® Blue Barrier LIQUID APPLIED FLASHING

ABEP® MULEHIDE TAPE APPLIED OVER TOP OF APRON FLASHING

CAVITY CLOSER. ALLOW 15mm DRIPEDGE TO BOTTOM OF CLADDING

PREFINISHED METAL APRON FLASHING. 75mm COVER BEHIND CLADDING. 35mm MIN CLEARANCE BETWEEN CLADDING AND FLASHING.REFER TO E2/AS1 TABLE 7 FOR COVER OVER ROOFING

5mm MAX. GAP BETWEEN FLASHINGAND ROOFING

ROOF STRUCTURE IN ACCORDANCEWITH NZS3504:2011 OR SPECIFIC ENGINEERING DESIGN.

TIMBER STRINGER FIXED TO WALL FRAMING. REFER TO NZS3604:2011

9mm MAGNUM BOARD® SOFFIT LINING. FLUSH STOPPED. FOREVERBREATHE SILICATE PAINT FINISH.

H3.1 EX 50x25mm PRE PRIMED TREATED SOFFIT MOULDING

RIGID AIR BARRIER AND INTERIOR LINING FIXINGS: PASLODE* IMPULSE NAIL 65x2.8MM SS ROUND DRIVE . REFER TO MAGNUM BOARD RIGID AIR BARRIER TECHNICAL MANUAL SPECIFICATIONS AND FIXING INSTALLATION DIAGRAM.

WEATHERBOARD FIXINGS - PASLODE* IMPULSE NAIL 65x2.8MM SS ROUND DRIVE. FIX AT EVERY CAVITY BATTEN, 600 CRS MAX. 30mm FROM TOP OF BOARD.INTERIOR WALL LINING - 9mmMAGNUM BOARD®. FOREVERBREATHEPAINT FINISH

NOTE:1. ALL MAGNUM BOARD®, ABEP® AND FLASHMAN® PRODUCTS TO BE INSTALLED

BY APPROVED INSTALLERS APPROVED BY NZSFP LTD. 2. WHERE ABEP BEP® BLUE BARRIER IS IN CONTACT WITH BIOPIN® PAINT, CEMIX

ACRYLBOND MUST BE APPLIED BEFORE APPLICATION OF BIOPIN PAINT®. 3. HARDIE & THOMSON® COVER BOARDS AND SCRIBERS, BIOPIN PAINT®, TERRA

LANA® WOOL INSULATION ARE SUPPLIED AND INSTALLED BY OTHERS.

4

50

15 min

CLADDING BASE - SECTION DETAIL1:5MAGNUM BOARD WEATHERBOARDS

50

15m

mm

in

INTERIOR WALL LINING - 9mm MAGNUM BOARD®. FOREVERRBEATHE PAINT FINISH

150

min

to fi

nish

ed p

avin

g.

REFER E2/AS1 FORTHRESHOLD DETAIL

DPC BETWEEN ALL TIMBERAND CONCRETE.

3030

CLADDING BASE - SECTION DETAIL1:5MAGNUM BOARD WEATHERBOARDS

6

6mm MIN GAP BETWEEN BACKOF RIGID AIR BARRIER ANDCONCRETE PERIMETER

FOREVERBREATHE SILICATE PAINT FINISH TO WEATHERBOARD.

9mm thick x 200mm MAGNUM BOARD® WEATHER BOARD. 40mm LAP TO TOP. ON H3.1 43 MCA Micro Pro ® Osmose 50x20 FJ TIMBER CAVITY BATTEN. PRIOR TO INSTALLATION, PRE COAT BACK OF CAVITY BATTEN WITH ABEP BEP® Blue Barrier LIQUID APPLIED FLASHING

9mm MAGNUM BOARD ® RIGID AIR BARRIER

FIXINGS - PASLODE* IMPULSE NAIL 65x2.8MM SS ROUND DRIVE PASLODE CODE B20560. FIX AT EVERY CAVITY BATTEN, 600mm CRS MAX.

'Z' FLASHING AT MAGNUM BOARD RIGID AIR BARRIER JOINT. FOR WHERE SHEET LENGTHS EXCEED 2.4 OR 2.7m.

30mm FIXING FROM TOP OF WEATHER BOARD FOR SECRET FIXING.

CAVITY CLOSER. ALLOW 15mmMIN DRIP EDGE TO BOTTOM OF CLADDING

© New Zealand Sustainable Forest Products LP

MAGNUM BOARD WEATHER BOARD CLADDINGVERSION 01.00 SEPTEMBER 2015

http://www.healthbasedbuilding.com/magnum-board

INTERIOR WALL LINING - 9mm MAGNUM BOARD®. FOREVERBREATHE PAINT FINISH

SELECTED HEALTH BASED BUILDING TIMBER SKIRTING. FOREVERBREATHE OIL FINISH

FLOOR CONSTRUCTION: 18mm FOREVER BEECH T&G FLOORING ON 9mm MAGNUM BOARD® FLOOR RIGID AIR BARRIER,ON TREATED TIMBER FLOOR JOISTS. R1.9 TERRA LANA®. UNDERFLOOR INSULATION 90mm THICK. FLOOR FRAMING SIZES PER NZS3604:2011 OR SPECIFIC DESIGN

RIGID AIR BARRIER AND INTERIOR LINING FIXINGS: PASLODE* IMPULSE NAIL 65x2.8MM SS ROUND DRIVE REFER TO MAGNUM BOARD RIGID AIR BARRIER TECHNICAL MANUAL SPECIFICATIONS AND FIXING INSTALLATION DIAGRAM.

TIMBER BEARER PER NZS3604

RIGID AIR BARRIER AND INTERIOR LINING FIXINGS: PASLODE* IMPULSE NAIL 65x2.8MM SS ROUND DRIVE REFER TO MAGNUM BOARD RIGID AIR BARRIER TECHNICAL MANUAL SPECIFICATIONS AND FIXING INSTALLATION DIAGRAM.

9mm MAGNUM BOARD® RIGIDAIR BARRIER

SELECTED HARDIE ANDTHOMPSON TIMBER SKIRTING. FOREVERBREATHE OIL FINISH

CONCRETE FLOOR SLAB

9mm x 200mm MAGNUM BOARD® WEATHER BOARD. 40mm LAP TO TOP. ON H3.1 MCA Micro Pro ® Osmose 50x20 PINE TIMBER CAVITY BATTEN. FOREVERBREATHE SILICATE PAINT FINISH TO WEATHERBOARD.PRIOR TO INSTALLATION, PRECOAT BACK OF CAVITY BATTEN WITH ABEP BEP® Blue BarrierLIQUID APPLIED FLASHING

WEATHERBOARD FIXINGS -PASLODE* IMPULSE NAIL65x2.8MM SS ROUND DRIVE PASLODE CODE B20560.30mmFIXING FROM TOP OF WEATHER BOARD FOR SECRET FIXING.

CAVITY CLOSER. ALLOW 15mmDRIP EDGE TO BOTTOM OF CLADDING

50mm MIN CLADDINGOVERHANG

30

NOTE:1. ALL MAGNUM BOARD®, ABEP® AND FLASHMAN® PRODUCTS TO BE INSTALLED

BY APPROVED INSTALLERS APPROVED BY NZSFP LTD. 2. WHERE ABEP BEP® BLUE BARRIER IS IN CONTACT WITH BIOPIN® PAINT, CEMIX

ACRYLBOND MUST BE APPLIED BEFORE APPLICATION OF BIOPIN PAINT®. 3. HARDIE & THOMSON® COVER BOARDS AND SCRIBERS, BIOPIN PAINT®, TERRA

LANA® WOOL INSULATION ARE SUPPLIED AND INSTALLED BY OTHERS.

5

9mm MAGNUM BOARDRIGID AIR BARRIER

POWDERCOATEDALUMINIUM FLANGE PLATE

ABEP BEP® Blue Barrier JOINTFILLER SEALANT. 10mm WIDEX 6mm DEEP SEALANT ONBOND BREAKER.SEE E2/AS1FIG 68

TIMBER FRAMING WITHR3.2 (140mm thick)TERRA LANA®WOOL INSULATION.

INTERIOR LINING FIXINGS -PASLODE* IMPULSE NAIL 65x2.8MMSS ROUND DRIVE PASLODE CODEB20560. FIX AT EVERY 300 crsAROUND PERIMETER, 50mm FROMCORNERS. REFER TO MAGNUMBOARD FIXING INSTALLATIONDIAGRAM.

75

PIPE PENETRATION - PLAN DETAILSCALE: 1:5

6

PIPE PENETRATION - SECTION DETAILSCALE: 1:5

PINE TIMBER CAVITY BATTEN H3.1 MCA Micro Pro ® Osmose 50x20 PRIOR TO INSTALLATION, PRE COAT BACK OF CAVITY BATTEN WITH ABEP BEP® Blue Barrier LIQUID APPLIED FLASHING

VANLUK RUBBER BOOTWITH ADHESIVE COLLAR. REFER TOwww.vanluk.co.nz

SOLID BLOCKINGAROUND PENETRATIONWITH MINIMUM 75mm OVERLAP TO RIGID AIR BARRIER

INTERIOR LINING FIXINGS -PASLODE* IMPULSE NAIL 65x2.8MM SS ROUND DRIVE PASLODE CODE B20560. FIX AT EVERY 300 crs AROUND PERIMETER, 50mm FROM CORNERS. REFER TO MAGNUM BOARD FIXING INSTALLATION DIAGRAM.

WEATHERBOARD FIXINGS- PASLODE* IMPULSE NAIL65x2.8MM SS ROUNDDRIVE PASLODE CODEB20560. FIX AT EVERYCAVITY BATTEN.

SUPPORT PIPE WITH ANOG UNDER AND SCREWFIXED STRAP OVER

RIGID AIR BARRIER FIXINGS: PASLODE* IMPULSE NAIL 65x2.8MM SS ROUND DRIVE . REFER TO MAGNUM BOARD RIGID AIR BARRIER TECHNICAL MANUAL SPECIFICATIONS

BUTYL FLASHING OVERRUBBER BOOT PERVANLUK INSTALLATION INSTRUCTIONS

PINE TIMBER CAVITYBATTEN H3.1 MCA MicroPro ® Osmose 50x20

VANLUK RUBBER BOOTWITH ADHESIVE COLLAR.REFER TO www.vanluk.co.nz

9mm THICK x 200mm MAGNUM BOARD® WEATHER BOARD.

NOTE: ALTERNATIVE OPTIONIS TO REMOVE FLANGE PLATE AND PROVIDE CLEARSEALANT IN PLACE OF ABEPBlue Barrier JOINT FILLER.

9mm THICK x 200mm MAGNUMBOARD® WEATHER BOARD.

BUTYL FLASHING OVER RUBBERBOOT AS PER VANLUKINSTALLATION INSTRUCTIONS

ABEP BEP® Blue BarrierJOINT FILLER SEALANT TOTOP HALF OF FLANGE

ABEP BEP® Blue Barrier JOINTFILLER SEALANT10mm WIDE X 6mm DEEPSEALANT ON BONDBREAKER.SEE E2/AS1 FIG 68

PIPE PENETRATIONSLOPING TO OUTSIDEFLANGE PLATE

FIXINGS - PASLODE* IMPULSENAIL 65x2.8MM SS ROUND DRIVEPASLODE CODE B20560. FIX ATEVERY CAVITY BATTEN.

9mm MAGNUM BOARD®. RIGID AIR BARRIER. FIXINGS ARE PASLODE* IMPULSE NAIL 65x2.8MM SS ROUND DRIVE PASLODE CODE B20560. REFER TO MAGNUM BOARD RIGID AIR BARRIER TECHNICAL MANUAL SPECIFICATIONS

© New Zealand Sustainable Forest Products LP

MAGNUM BOARD WEATHER BOARD CLADDINGVERSION 01.00 SEPTEMBER 2015

http://www.healthbasedbuilding.com/magnum-board

NOTE:1. ALL MAGNUM BOARD®, ABEP® AND FLASHMAN® PRODUCTS TO BE INSTALLED

BY APPROVED INSTALLERS APPROVED BY NZSFP LTD. 2. WHERE ABEP BEP® BLUE BARRIER IS IN CONTACT WITH BIOPIN® PAINT, CEMIX

ACRYLBOND MUST BE APPLIED BEFORE APPLICATION OF BIOPIN PAINT®. 3. HARDIE & THOMSON® COVER BOARDS AND SCRIBERS, BIOPIN PAINT®, TERRA

LANA® WOOL INSULATION ARE SUPPLIED AND INSTALLED BY OTHERS.

6

50

BARGE - NO SOFFIT - SECTION DETAIL

35

1:5MAGNUM BOARD WEATHER BOARD

Y - Refer E2/AS1 Table 7

Z - R

efer

Tab

le7

E2/

AS

1

125mm min - Refer E2/AS1 Fig 45

1:5MAGNUM BOARD

PREFINISHED METAL BARGEFLASHING. CONFIRM MIN COVERREQUIREMENTS OVER WITH E2/AS1TABLE 7.

PROFILED SELECTED ROOFINGON ROOFING UNDERLAY

COMPRESSIBLE SEAL. CONFIRMIF REQUIRED WITH SELECTEDROOFING MANUFACTURER'SINSTRUCTIONS.

H3.2 200x18 FJ MCA FASCIA -BY HEALTH BASED BUILDING.PRE PRIMED.

9mm thick x 200mm MAGNUM BOARD®WEATHER BOARD. 40mm LAP TO TOP.ON H3.1 MCA Micro Pro Osmose 50 x20mm PINE TIMBER CAVITY BATTEN.PRE COAT BACK OF BATTEN WITHABEP BEP® Blue Barrier LIQUID APPLIEDFLASHING

9mm MAGNUM BOARD® RIGID AIRBARRIER

ROOF - WALL RIDGE - SECTION DETAIL

© New Zealand Sustainable Forest Products LP

MAGNUM BOARD WEATHER BOARD CLADDINGVERSION 01.00 SEPTEMBER 2015

http://www.healthbasedbuilding.com/magnum-board

PROFILED SELECTED ROOFING ONROOFING UNDERLAY

FOLDED 0.55 BMTPREFINISHED METAL EAVESFLASHING WITH HEM AT TOPEDGE

SELECTED SPOUTING

35mm MIN EAVE FLASHINGOVERLAP

H3.2 150x18 FJ MCA FASCIA -BY HEALTH BASED BUILDING.PRE PRIMED.

WEATHERBOARD FIXINGS -PASLODE* IMPULSE NAIL 65x2.8MMSS ROUND DRIVE. FIX AT EVERYCAVITY BATTEN, 600 CRS MAX.30mm FROM TOP OF BOARD.

ROOF STRUCTURE INACCORDANCE WITH NZS3504:2011OR SPECIFIC ENGINEERINGDESIGN.

PROVIDE SOLID BLOCKING FOR FIXING

9mm thick x 200mm MAGNUM BOARD® WEATHER BOARD. 40mm LAP TO TOP. ON H3.1 MCA Micro Pro Osmose 50 x 20mm PINE TIMBER CAVITY BATTEN. PRIOR TO INSTALLATION. PRE COAT BACK OF BATTEN WITH ABEP BEP® Blue Barrier LIQUID APPLIED FLASHING

RIGID AIR BARRIER AND INTERIOR LINING FIXINGS: PASLODE* IMPULSE NAIL 65x2.8MM SS ROUND DRIVE REFER TO MAGNUM BOARD RIGID AIR BARRIER TECHNICAL MANUAL SPECIFICATIONS AND FIXING INSTALLATION DIAGRAM.

9mm MAGNUM BOARD® RIGID AIR BARRIER

RIGID AIR BARRIER FIXINGS: PASLODE* IMPULSE NAIL 65x2.8MM SS ROUND DRIVE REFER TO MAGNUM BOARD RIGID AIR BARRIER TECHNICAL MANUAL SPECIFICATIONS AND FIXING INSTALLATION DIAGRAM.

WEATHERBOARD FIXINGS -PASLODE* IMPULSE NAIL 65x2.8MM SS ROUND DRIVE. FIX AT EVERY CAVITY BATTEN, 600 CRS MAX. 30mm FROM TOP OF BOARD.

NOTE:1. ALL MAGNUM BOARD®, ABEP® AND FLASHMAN® PRODUCTS TO BE INSTALLED

BY APPROVED INSTALLERS APPROVED BY NZSFP LTD. 2. WHERE ABEP BEP® BLUE BARRIER IS IN CONTACT WITH BIOPIN® PAINT, CEMIX

ACRYLBOND MUST BE APPLIED BEFORE APPLICATION OF BIOPIN PAINT®. 3. HARDIE & THOMSON® COVER BOARDS AND SCRIBERS, BIOPIN PAINT®, TERRA

LANA® WOOL INSULATION ARE SUPPLIED AND INSTALLED BY OTHERS.

7

© New Zealand Sustainable Forest Products LP

MAGNUM BOARD WEATHER BOARD CLADDINGVERSION 01.00 SEPTEMBER 2015

http://www.healthbasedbuilding.com/magnum-board

PLAN DETAIL - VERTICAL CONTROL JOINT1:2MAGNUM BOARD WEATHERBOARDS

INTERIOR WALL LINING - 9mm MAGNUM BOARD®. FOREVERBREATHE PAINT FINISH

10 -12mm MIN VERTICAL CONTROL JOINT. REQUIRED WHERE WALL EXCEEDS 6m IN LENGTH. FILL WITH ABEP BEP® Blue Barrier JOINT FILLER CONTINUOUS BEAD OF SEALANT

1mm THICK CONTINUOUS ABEP BEP® Blue Barrier LIQUID FLASHING APPLIED OVER MULEHIDE TAPE. EXTEND 25mm EITHER SIDE OF TAPE AND SEAL TO RIGID AIR BARRIER.

PINE TIMBER CAVITY BATTEN H3.1 MCA Micro Pro ® Osmose 50X20 FJ

METAL BACK SOAKER. FIX 150mm MIN FROM CENTRE OF STUD. OFFSET EACH SOAKER 600mm MIN FOR EACH BOARD COVER. REFER TO E2/AS1 FIGURE 87.

INTERIOR LINING FIXINGS - PASLODE* IMPULSE NAIL 65x2.8MM SS ROUND DRIVE PASLODE CODE B20560. FIX AT EVERY 300 crs AROUND PERIMETER, 50mm FROM CORNERS. REFER TO MAGNUM BOARD FIXING INSTALLATION DIAGRAM.

TIMBER FRAMING WITH R3.2 (140mm thick) TERRA LANA®WOOL INSULATION.

9mm MAGNUM BOARD® RIGID AIR BARRIER.As per Table 23 and Clause 9.1.5 to 9.1.7.1 E2/AS1. RIGID AIR BARRIER FIXINGS: PASLODE* IMPULSE NAIL 65x2.8MM SS ROUND DRIVE

50mm CONTINUOUS WIDTH OF MULEHIDE TAPE OVER JOINT IN MAGNUM RIGID AIR BARRIER BOARD

FIXINGS - PASLODE* IMPULSE NAIL 65x2.8MM SS ROUND DRIVEPASLODE CODE B20560. FIX ATEVERY CAVITY BATTEN. FIX 20mmMIN FROM END AT BUTT JOINT.

ABEP BEP® Blue Barrier JOINT FILLER CONTINUOUS BEAD OF SEALANT

10 - 12mm JOINT

50mm STRIP25 25

20

9mm THICK x 200mmMAGNUM BOARDWEATHER BOARD. NOTE:

1. ALL MAGNUM BOARD®, ABEP® AND FLASHMAN® PRODUCTS TO BE INSTALLED BY APPROVED INSTALLERS APPROVED BY NZSFP LTD.

2. WHERE ABEP BEP® BLUE BARRIER IS IN CONTACT WITH BIOPIN® PAINT, CEMIX ACRYLBOND MUST BE APPLIED BEFORE APPLICATION OF BIOPIN PAINT®.

3. HARDIE & THOMSON® COVER BOARDS AND SCRIBERS, BIOPIN PAINT®, TERRA LANA® WOOL INSULATION ARE SUPPLIED AND INSTALLED BY OTHERS.

8

EXTERNAL CORNER - PLAN DETAIL1:5MAGNUM BOARD WEATHERBOARDS - COVER BOARDS

50mm min. COVER

INTERNAL CORNER - PLAN DETAIL1:5MAGNUM BOARD WEATHERBOARDS - 'W' FLASHINGS

10

10

10

50 m

ax

INTERIOR WALL LINING -9mm MAGNUM BOARD® FOREVERBREATHE PAINT FINISHTIMBER FRAMING WITH R3.2 (140mm thick) TERRA LANA® WOOL INSULATION.

9mm MAGNUM BOARD® RIGID AIR BARRIER

65 X 65mm EXTERNAL CORNER BACK FLASHING.

H3.1 130x20 HEALTH BASED BUILDING COVER BOARDSAND SCRIBER CUT TO FIT WEATHERBOARD. 50mm MIN COVER OVER CLADDING

ABEP BEP® Blue Barrier LIQUID APPLIED FLASHING OVER BUTT JOINT AT RIGID AIR BARRIER CORNER.

PASLODE* IMPULSE NAIL65x2.8MM SS ROUND DRIVE50MM FROM EDGE OF BOARD

PINE TIMBER CAVITY BATTENH3.1 MCA Micro Pro ® Osmose 50x20. ALLOW 10mm MIN GAPS BETWEEN BATTENS. PRIOR TO INSTALLATION, PRE COAT BACKOF BATTEN WITH ABEP BEP® Blue Barrier LIQUID APPLIED FLASHING 10mm GAP BETWEEN CAVITY BATTENS9mm THICK x 200mm MAGNUM BOARD ® WEATHER BOARD.

INTERIOR WALL LINING - 9mm MAGNUM BOARD®FOREVERBREATHE PAINT FINISH

INTERIOR LINING FIXINGS - PASLODE* IMPULSE NAIL 65x2.8MM SS ROUND DRIVE PASLODE CODE B20560. FIX AT EVERY 300 crs AROUND PERIMETER, 50mm FROM CORNERS.15-20 FROM EDGE. REFER TO MAGNUM BOARD FIXING INSTALLATION DIAGRAM.

ABEP BEP® Blue Barrier JOINT FILLER AT RIGID AIR BARRIER INTERNAL CORNER

PROPRIETARY uPVC 90°INTERNAL CORNER 'W' MOULD FLASHING WITH HEMS

10mm GAP BETWEEN CAVITY BATTENS

300

CR

S M

AX

TIMBER FRAMING WITH R3.2(140mm thick) TERRA LANA®WOOL INSULATION.

9mm MAGNUM BOARD®RIGID AIR BARRIER

RIGID AIR BARRIER FIXINGS: PASLODE* IMPULSE NAIL 65x2.8MM SS ROUND DRIVE . REFER TO MAGNUM BOARD RIGID AIR BARRIER TECHNICAL MANUAL SPECIFICATIONS. 15-20mm IN FROM EDGE.

PINE TIMBER CAVITYBATTEN H3.1 MCA Micro Pro® Osmose 50x20. PRIOR TO INSTALLATION, PRE COATBACK OF BATTEN WITHABEP BEP® Blue BarrierLIQUID APPLIED FLASHING

FIXINGS: PASLODE* IMPULSE NAIL 65x2.8MM SS ROUND DRIVE PASLODE CODE B20560. FIX AT EVERY CAVITY BATTEN.

9mm THICK X 200mm MAGNUM BOARD ® WEATHER BOARD.

50mmMIN

H3.1 TIMBER SCRIBERSEALED TO WEATHERBOARD

RIGID AIR BARRIER FIXINGS: PASLODE* IMPULSE NAIL 65x2.8MM SS ROUND DRIVE . REFER TO MAGNUM BOARD RIGID AIR BARRIER TECHNICAL MANUAL SPECIFICATIONS.

INTERIOR LINING FIXINGS -PASLODE* IMPULSE NAIL65x2.8MM SS ROUND DRIVEPASLODE CODE B20560. FIXAT EVERY 300 crs AROUNDPERIMETER, 50mm FROMCORNERS.15-20 FROM EDGE.REFER TO MAGNUM BOARDFIXING INSTALLATIONDIAGRAM.

© New Zealand Sustainable Forest Products LP

MAGNUM BOARD WEATHER BOARD CLADDINGVERSION 01.00 SEPTEMBER 2015

http://www.healthbasedbuilding.com/magnum-board

NOTE:1. ALL MAGNUM BOARD®, ABEP® AND FLASHMAN® PRODUCTSTO BE INSTALLED BY APPROVED INSTALLERS.2.WHERE ABEP BEP® Blue Barrier IS IN CONTACT WITHBIOPIN® PAINT, CEMIX ACRYLBOND MUST BE APPLIED BEFOREAPPLICATION OF BIOPIN PAINT®

NOTE:1. ALL MAGNUM BOARD®, ABEP® AND FLASHMAN® PRODUCTS TO BE INSTALLED

BY APPROVED INSTALLERS APPROVED BY NZSFP LTD. 2. WHERE ABEP BEP® BLUE BARRIER IS IN CONTACT WITH BIOPIN® PAINT, CEMIX

ACRYLBOND MUST BE APPLIED BEFORE APPLICATION OF BIOPIN PAINT®. 3. HARDIE & THOMSON® COVER BOARDS AND SCRIBERS, BIOPIN PAINT®, TERRA

LANA® WOOL INSULATION ARE SUPPLIED AND INSTALLED BY OTHERS.

9

EXTERNAL CORNER - PLAN DETAIL 1:5MAGNUM BOARD WEATHERBOARDS - SOAKER FLASHINGS

15mm min. COVER

50

INTERIOR WALL LINING -9mm MAGNUM BOARD® FOREVERBREATHE® PAINT FINISH

TIMBER FRAMING WITH R3.2 (140mm thick) TERRA LANA® WOOL INSULATION.

9mm MAGNUM BOARD® RIGID AIR BARRIER

90° POWDERCOATED ALUMINIUM CORNER SOAKER. 15mm MIN COVER OVER WEATHERBOARD

ABEP BEP® Blue Barrier LIQUID APPLIED FLASHING OVER BUTT JOINT AT RIGID AIR BARRIER CORNER.

PASLODE* IMPULSE NAIL 65x2.8MM SS ROUND DRIVE 50MM FROM EDGE OFBOARD

PINE TIMBER CAVITY BATTEN H3.2 MCA Micro Pro ® Osmose 50x20.

PRIOR TO INSTALLATION, PRE COAT BACK OF BATTEN WITH ABEP BEP® Blue Barrier LIQUID APPLIED FLASHING

9mm THICK x 200mm MAGNUM BOARD® WEATHER BOARD.

INTERNAL CORNER - PLAN DETAIL1:5MAGNUM BOARD WEATHERBOARDS - NOTCHED AND SCRIBED

10

10

© New Zealand Sustainable Forest Products LP

MAGNUM BOARD WEATHER BOARD CLADDINGVERSION 01.00 SEPTEMBER 2015

http://www.healthbasedbuilding.com/magnum-board

INTERIOR WALL LINING - 9mm MAGNUM BOARD®FOREVERBREATHE FINISH

INTERIOR LINING FIXINGS - PASLODE* IMPULSE NAIL 65x2.8MM SS ROUND DRIVE PASLODE CODE B20560. FIX AT EVERY 300 crs AROUND PERIMETER, 50mm FROM CORNERS.15-20 FROM EDGE. REFER TO MAGNUM BOARD FIXING INSTALLATION DIAGRAM.

ABEP BEP® Blue Barrier JOINT FILLER AT RIGID AIR BARRIER INTERNAL CORNER

65x65 uPVC INTERNAL CORNER BACK FLASHING

10mm GAP BETWEEN CAVITY BATTENS

50mmMIN

300

CR

S M

AX

TIMBER FRAMING WITH R3.2(140mm thick) TERRA LANA®WOOL INSULATION.

9mm MAGNUM BOARD®RIGID AIR BARRIER

RIGID AIR BARRIER FIXINGS: PASLODE* IMPULSE NAIL 65x2.8MM SS ROUND DRIVE . REFER TO MAGNUM BOARD RIGID AIR BARRIER TECHNICAL MANUAL SPECIFICATIONS. 15-20mm IN FROM EDGE.

PINE TIMBER CAVITYBATTEN H3.1 MCA Micro Pro® Osmose 50x20. PRIOR TO INSTALLATION, PRE COATBACK OF BATTEN WITHABEP BEP® Blue BarrierLIQUID APPLIED FLASHING

SCRIBED AND NOTCHED CORNER FOR WEATHERBOARDS

9mm THICK X 200mm MAGNUM BOARD ® WEATHER BOARD.

FIXINGS: PASLODE* IMPULSE NAIL 65x2.8MM SS ROUND DRIVE PASLODE CODE B20560. FIX AT EVERY CAVITY BATTEN.

65 X 65mm EXTERNAL CORNER ALUMINIUM BACK FLASHING.

RIGID AIR BARRIER FIXINGS: PASLODE* IMPULSE NAIL 65x2.8MM SS ROUND DRIVE . REFER TO MAGNUM BOARD RIGID AIR BARRIER TECHNICAL MANUAL SPECIFICATIONS.

INTERIOR LINING FIXINGS -PASLODE* IMPULSE NAIL65x2.8MM SS ROUND DRIVEPASLODE CODE B20560. FIXAT EVERY 300 crs AROUNDPERIMETER, 50mm FROMCORNERS.15-20 FROM EDGE.REFER TO MAGNUM BOARDFIXING INSTALLATIONDIAGRAM.

NOTE:1. ALL MAGNUM BOARD®, ABEP® AND FLASHMAN® PRODUCTSTO BE INSTALLED BY APPROVED INSTALLERS.2.WHERE ABEP BEP® Blue Barrier IS IN CONTACT WITHBIOPIN® PAINT, CEMIX ACRYLBOND MUST BE APPLIED BEFOREAPPLICATION OF BIOPIN PAINT®

NOTE:1. ALL MAGNUM BOARD®, ABEP® AND FLASHMAN® PRODUCTS TO BE INSTALLED

BY APPROVED INSTALLERS APPROVED BY NZSFP LTD. 2. WHERE ABEP BEP® BLUE BARRIER IS IN CONTACT WITH BIOPIN® PAINT, CEMIX

ACRYLBOND MUST BE APPLIED BEFORE APPLICATION OF BIOPIN PAINT®. 3. HARDIE & THOMSON® COVER BOARDS AND SCRIBERS, BIOPIN PAINT®, TERRA

LANA® WOOL INSULATION ARE SUPPLIED AND INSTALLED BY OTHERS.

10

TYPICAL HEAD - SECTION DETAIL1- 1:5

MAGNUM BOARD WEATHERBOARDS

U/S of Lintel

10 10

CONTINUOUS FLEXIBLE AIR SEAL ONPEF BACKING ROD TO PERIMETER OFOPENING

TEMPORARY PACKERS IF REQUIREDARE TO BE REMOVED AFTER FIXING

9mm thick x 200mm MAGNUM BOARD®WEATHER BOARD. 40mm LAP TO TOP.ON H3.1 MCA Micro Pro ® Osmose 50X20PINE TIMBER CAVITY BATTENON 9mm MAGNUM BOARD® RIGID AIRBARRIER

H3.1 TIMBER STARTING BLOCK TOSUIT

BOTTOM OF CLADDING MUST BEHARD DOWN ON TOP OFFLASHMAN JAMB FIN

FLASHMAN® EXTRUDEDALUMINIUM ONE PIECE CAVITYCLOSURE AND HEAD FLASHINGWITH STOP END (SHOWN DASHED)

FLASHMAN EXTRUDEDALUMINIUM JAMB FLASHING

35mm MIN FLASHING UPSTANDBEHIND CLADDING, AND 10mm MINCOVER OVER JOINERY

TYPICAL SILL - SECTION DETAIL2- 1:5

MAGNUM BOARD WEATHERBOARDS

3

10

CONTINUOUS FLEXIBLE AIR SEAL ONPEF BACKING ROD TO PERIMETER OFOPENING.

FOREVER BEECH® TIMBER REVEAL -CHOOSE SIZE + CODE

ABEP BEP® Blue Barrier LIQUIDAPPLIED SEALANT. APPLYACCORDING TO MANUFACTURER'SINSTRUCTION

ABEP BEP® Blue Barrier LIQUID APPLIEDFLASHING. APPLY ACCORDING TOMANUFACTURER'S INSTRUCTIONS

FOREVER BEECH TIMBERREVEAL - CHOOSE SIZE + CODE

FIXINGS - PASLODE* IMPULSE NAIL65x2.8MM SS ROUND DRIVE PASLODECODE B20560. FIX AT EVERY CAVITYBATTEN.

25

1035

min

15

10mm NOMINAL GAP

TIMBER PACKER AS REQUIRED.

14 GAUGE HOT DIP GALVANISED (316 SS WHERE REQUIRED) S.T.H.C SCREWS AT 600mm CRS WITH 65mm MIN FRAME PENETRATION. SUPPLIED AND INSTALLED BY FLASHMAN. REFER TO E2/AS1 FOR DURABILITY REQUIREMENTS

INTERIOR WALL LINING - 9mm MAGNUM BOARD® FOREVERBREATHE PAINT FINISH

TIMBER FRAMING WITH R3.2 (140mm thick) TERRA LANA® WOOL INSULATION.

FIXINGS - PASLODE* IMPULSE NAIL 65x2.8MM SS ROUND DRIVE PASLODE CODE B20560. FIX AT EVERY CAVITY BATTENS, 600 CRS MAX. 30mm FROM TOP OF BOARD.

© New Zealand Sustainable Forest Products LP

MAGNUM BOARD WEATHER BOARD CLADDINGVERSION 01.00 SEPTEMBER 2015

http://www.healthbasedbuilding.com/magnum-board

FLASHMAN® ALUMINIUM MITRE SOAKER SUPPLIED BY FLASHMAN

RIGID AIR BARRIER AND INTERIOR LINING FIXINGS: PASLODE* IMPULSE NAIL 65x2.8MM SS ROUND DRIVE . REFER TO MAGNUM BOARD RIGID AIR BARRIER TECHNICAL MANUAL SPECIFICATIONS.

3mm GAP BETWEEN BOTTOM EDGE OF EXTRUDED ALUMINIUM FLANGE AND TOP OF FLASHMAN SILL

25mm FROM THE OUTSIDE FACE OF THE RIGID AIR BARRIER TO THE BACK OF THE ALUMINIUM WINDOW FRAME

FLASHMAN® EXTRUDED ALUMINIUM SLIMLINE SILL

BEAD OF SEALANT

FLASHMAN BACK PLATE

H3.1 PACKER SUPPLIED AND INSTALLED BY FLASHMAN

9mm thick x 200mm MAGNUM BOARD® WEATHER BOARD. 40mm LAP TO TOP. ON H3.1 MCA Micro Pro ® Osmose 50x20 PINE TIMBER CAVITY BATTEN ON 9mm MAGNUM BOARD® RIGID AIR BARRIER

INTERIOR LINING FIXINGS - PASLODE* IMPULSE NAIL 65x2.8MM SS ROUND DRIVE PASLODE CODE B20560. REFER TO MAGNUM BOARD FIXING INSTALLATION DIAGRAM.

TIMBER FRAMING WITH R3.2(140mm thick) TERRA LANAWOOL INSULATION.

INTERIOR WALL LINING - 9mmMAGNUM BOARD® FOREVERBREATHEPAINT FINISHPROPRIETARY TAPE OVER HEADFLASHING SUPPLIED ANDINSTALLED BY FLASHMAN

10mm GAP NOMINAL TO ALLOWFOR HEAD DEFLECTION ANDAIR SEAL

NOTE:1. ALL MAGNUM BOARD®, ABEP® AND FLASHMAN® PRODUCTS TO BE INSTALLED

BY APPROVED INSTALLERS APPROVED BY NZSFP LTD. 2. WHERE ABEP BEP® BLUE BARRIER IS IN CONTACT WITH BIOPIN® PAINT, CEMIX

ACRYLBOND MUST BE APPLIED BEFORE APPLICATION OF BIOPIN PAINT®. 3. HARDIE & THOMSON® COVER BOARDS AND SCRIBERS, BIOPIN PAINT®, TERRA

LANA® WOOL INSULATION ARE SUPPLIED AND INSTALLED BY OTHERS.

11

TYPICAL JAMB - PLAN DETAIL3- 1:5

MAGNUM BOARD WEATHERBOARDS

10

LINE OF FLASHMANSLIMLINE SILL BELOW

25

5

10

© New Zealand Sustainable Forest Products LP

MAGNUM BOARD WEATHER BOARD CLADDINGVERSION 01.00 SEPTEMBER 2015

http://www.healthbasedbuilding.com/magnum-board

INTERIOR LINING FIXINGS -PASLODE* IMPULSE NAIL65x2.8MM SS ROUND DRIVEPASLODE CODE B20560.

10mm NOMINAL GAP

FOREVERBEECH®TIMBER REVEAL AND ARCHITRAVE

CONTINUOUS FLEXIBLE AIR SEAL ON PEF BACKING ROD TO PERIMETER OF OPENING.

TIMBER PACKER AS REQUIRED

ABEP BEP® Blue Barrier LIQUID APPLIED FLASHING. APPLY ACCORDING TO MANUFACTURER'S INSTRUCTIONSELECTED ALUMINIUM JOINERY

HEAD FLASHING OVER (SHOWN DASHED)

POWDERCOATED ALUMINIUM J FLASHING10mm MIN JOINERY COVER OVER JAMB FLASHING

FLASHMAN® EXTRUDED 40mm ALUMINIUM JAMB FLASHING

INTERIOR WALL LINING -9mm MAGNUM BOARD®FOREVERBREATHE PAINT FINISH

TIMBER FRAMING WITH INSULATION

RIGID AIR BARRIER FIXINGS: PASLODE* IMPULSE NAIL 65x2.8MM SS ROUND DRIVE . REFER TO MAGNUM BOARD RIGID AIR BARRIER TECHNICAL MANUAL SPECIFICATIONS.

9mm MAGNUM BOARD®RIGID AIR BARRIER

PINE TIMBER CAVITYBATTEN H3.1 MCA Micro Pro® Osmose 50x20. PRIOR TO INSTALLATION, PRE COATBACK OF BATTEN WITHABEP BEP® Blue BarrierLIQUID APPLIED FLASHING

9mm THICK x 200mm MAGNUM BOARD® WEATHER BOARD. PASLODE* IMPULSE NAIL 65x2.8MM SS ROUND DRIVE 50MM FROM EDGE OF BOARD

BEAD OF SEALANTNOTE:1. ALL MAGNUM BOARD®, ABEP® AND FLASHMAN® PRODUCTS TO BE INSTALLED

BY APPROVED INSTALLERS APPROVED BY NZSFP LTD. 2. WHERE ABEP BEP® BLUE BARRIER IS IN CONTACT WITH BIOPIN® PAINT, CEMIX

ACRYLBOND MUST BE APPLIED BEFORE APPLICATION OF BIOPIN PAINT®. 3. HARDIE & THOMSON® COVER BOARDS AND SCRIBERS, BIOPIN PAINT®, TERRA

LANA® WOOL INSULATION ARE SUPPLIED AND INSTALLED BY OTHERS.

12

15m

mm

in g

ap

VERTICAL DETAIL - HORIZONTAL CONTROL JOINT1:5MAGNUM BOARD WEATHERBOARDS

35m

m M

IN

ABEP® MULEHIDE TAPE APPLIED OVER TOPOF JUNCTION FLASHING

9mm THICK X 200mm MAGNUM BOARD ®WEATHER BOARD.ON PINE TIMBER CAVITY BATTEN H3.1 MCAMicro Pro ® Osmose 50x20FIXINGS - PASLODE* IMPULSE NAIL65x2.8MM SS ROUND DRIVE PASLODECODE B20560. FIX AT EVERY CAVITYBATTEN.

H3.1 TIMBER STARTING BLOCK TO SUIT

CAVITY CLOSER

PURPOSE MADE ALUMINIUM POWDERCOATEDFLASHING 15° MIN SLOPE. REFER TABLE 20 OFE2/AS1 FOR FLASHING DURABILITY.15

35mm MIN COVER FLASHING OVERCLADDING. 15mm MIN GAP BETWEENCLADDING AND FLASHING.35

mm

10-1

2

2525

ENLARGED DETAIL - HORIZONTAL CONTROL JOINTN.T.SMAGNUM BOARD WEATHERBOARDS

9mm MAGNUM BOARD®RIGID AIR BARRIER.

© New Zealand Sustainable Forest Products LP

MAGNUM BOARD WEATHER BOARD CLADDINGVERSION 01.00 SEPTEMBER 2015

http://www.healthbasedbuilding.com/magnum-board

PRIOR TO INSTALLATION, PRE COAT BACK OF CAVITY BATTEN WITH ABEP BEP® Blue Barrier LIQUID APPLIED FLASHING

BOTTOM PLATE

FLOORING TO FINISH10mm BACK FROM OUTSIDE OF FRAMING

SOLID TIMBERBOUNDARY JOIST

FLOOR JOIST

9mm MAGNUM BOARD® RIGID AIR BARRIER. FIXINGS: PASLODE* IMPULSE NAIL 65x2.8MM SS ROUND DRIVE . REFER TO MAGNUM BOARD RIGID AIR BARRIER TECHNICAL MANUAL SPECIFICATIONS. 15-20mm IN FROM EDGE.

TOP PLATE

WEATHERBOARD FIXED TO TOP PLATE.DO NOT FIX TO JOIST.

NOTE: THIS DETAIL IS REQUIRED TO LIMITCAVITIES TO A MAXIMUM OF 2 STORIESOR 7 METRES. REFER E2/AS1

NOTE:1. ALL MAGNUM BOARD®, ABEP® AND FLASHMAN®PRODUCTS TO BE INSTALLED BY INSTALLERSAPPROVED BY NZSFP LTD.2.WHERE ABEP BEP® Blue Barrier IS IN CONTACT WITHBIOPIN® PAINT, CEMIX ACRYLBOND MUST BE APPLIEDBEFORE APPLICATION OF BIOPIN PAINT®.3. HARDIE AND THOMSON® COVER BOARDS ANDSCRIBERS, BIOPIN PAINT®, TERRA LANA® WOOLINSULATION ARE SUPPLIED AND INSTALLED BYOTHERS.

RIGID AIR BARRIER FIXINGS: PASLODE* IMPULSE NAIL 65x2.8MM SS ROUND DRIVE . REFER TO MAGNUM BOARD RIGID AIR BARRIER TECHNICAL MANUAL SPECIFICATIONS

ABEP BEP® Blue Barrier JOINT FILLER. APPROVED BOND BREAKER IS APPLIED OVER THE BLUE BARRIER JOINT.

10 -12mm MIN HORIZONTALCONTROL JOINT. REQUIRED WHERE WALL EXCEEDS 2700mm IN HEIGHT

50mm CONTINUOUS WIDTH OF MULEHIDE TAPE OVER JOINT IN MAGNUM RIGID AIR BARRIER BOARD

1mm THICK CONTINUOUS ABEPBEP® Blue Barrier LIQUID FLASHING APPLIED OVER MULEHIDE TAPE. EXTEND 25mm EITHER SIDE OF TAPE AND SEAL TO RIGID AIR BARRIER.

50m

m M

ULE

HID

E

13

TIMBER FRAMED WALL

TERRA LANA WOOL INSULATION

9mm MAGNUM BOARD RIGID AIR BARRIER

H3.1 50X20 PINE TIMBER CAVITY BATTEN.PRIOR TO INSTALLATION PRE COAT BACK OF BATTEN WITH ABEP BEP BLUE BARRIER. 600mm CENTERS MAX. ALLOW TO TEMPORARILY FIX PRIOR TO WEATHERBOARD FIX.

65X2.8mm STAINLESS STEEL PASLODE IMPULSE NAIL. ROUND DRIVE. 30mm FROM TOP OF BOARD. FIXED AT EVERY CAVITY BATTEN

APEP BEP BLUE BARRIER LIQUID APPLIED FLASHING OVER BUTT JOINT AT RIGID AIR BARRIER CORNER

65x65 EXTERNAL CORNER BACK FLASHING

9mm X 200 MAGNUM BOARD WEATHERBOARD. FOREVERBREATHE PAINT FINISH.

H3.1 130X20 HEALTH BASED BUILDING COVER BOARDS AND SCRIBER CUT TO FIT WEATHERBOARD. 50mmMIN COVER OVER CLADDING

H3.1 TIMBER SCRIBER SEALED TO WEATHERBOARD

MAGNUM BOARD WEATHER BOARD CLADDINGVERSION 01.00 SEPTEMBER 2015

© New Zealand Sustainable Forest Products LPhttp://www.healthbasedbuilding.com/magnum-board

EXTERNAL CORNER - 3D DETAILNOT TO SCALE

NOTE:1. ALL MAGNUM BOARD®, ABEP® AND FLASHMAN® PRODUCTS TO BE INSTALLED

BY APPROVED INSTALLERS APPROVED BY NZSFP LTD. 2. WHERE ABEP BEP® BLUE BARRIER IS IN CONTACT WITH BIOPIN® PAINT, CEMIX

ACRYLBOND MUST BE APPLIED BEFORE APPLICATION OF BIOPIN PAINT®. 3. HARDIE & THOMSON® COVER BOARDS AND SCRIBERS, BIOPIN PAINT®, TERRA

LANA® WOOL INSULATION ARE SUPPLIED AND INSTALLED BY OTHERS.

14

RIGID AIR BARRIER FIXINGS: 65x2.8MMSTEEL PSTEEL PAASLSLODE IMPULSE NAIL.ODE IMPULSE NAIL. FIX FIX AAT 300mm CRS MAX T 300mm CRS MAX SSPPACINGSACINGS ON PERIMETER OF SHEEON PERIMETER OF SHEETT. REFER TECH. REFER TECHNICALNICAL MAMANNUUAL SPECIFIAL SPECIFICCAATIONTION

9mm MAGNUM BOARD INTERIOR LINING.

65x2.8mm STAINLESS STEEL PASLODE IMPULSE NAIL. ROUND DRIVE.

TERRA LANA INSULATION.

TIMBER FRAMED WALL140x45 TOP PLATE SHOWN.

FIX 50x50 FROM CORNERS.15-20mm FROM EDGE.300mm MAX SPACINGS BETWEENFIXINGS

INTERNAL CORNER - 3D DETAILNOT TO SCALE

MAGNUM BOARD WEATHER BOARD CLADDINGVERSION 01.00 SEPTEMBER 2015

© New Zealand Sustainable Forest Products LPhttp://www.healthbasedbuilding.com/magnum-board

14

P a g e | 23 25 – May – 2016 Version 3.0

New Zealand Sustainable Forest Products LP Address: 10 Gannons Road, RD 1 Reefton, 7895

Phone 03 732 8414 E–Mail: [email protected] http://www.healthbasedbuilding.com/magnum-board

Appendix B

HOME of MAGNUM BOARD® “The New Generation GREEN Building Material”

“Install It for Health-Install It for Life”

Sheathing & Trim Products

Material Safety Data Sheet MSDS No.: MBGEP-032107-5 Page 1 of 8

Magnum Board® Brand Products SECTION 1: COMPANY AND PRODUCT INFORMATION

Magnum Building Products LLC 405 North Reo Street Tampa, FL 33609 USA

Phone: 813-304-2577

Facsimile: 813-304-2578

Website: www.magnumbp.com

Email: [email protected]

Use: Exterior: Sheathing, ceiling board, drop ceiling, siding, cladding and trim material.

Interior: Wallboard, ceiling board, tile backer board, underlayment and trim materials.

Structural Insulated Panels (SIPS) and Exterior Insulated Finish Systems (EIFS)

SECTION 2: COMPOSITION / INFORMATION ON INGREDIENTS

Ingredient CAS No. Hazard Class Magnesium Oxide 1309-48-4 None Magnesium Chloride 7786-30-3 None Cellulose 9004-34-6 None Perlite 93763-70-3 None

Proprietary Additives N/A None Fiberglass Scrim 65997-17-3 None

SECTION 3: HAZARDS IDENTIFICATION

Emergency Overview: Non-toxic, non explosive and is not a fire hazard.

MSDS No.: MBGEP-032107-5 Magnum Board® Brand Products

Page 2 of 8

Primary Routes of Entry: Eyes: Dust may irritate the eyes from mechanical abrasion causing watering and redness.

Skin: Dust may cause irritation of the skin from friction but cannot be absorbed through intact skin.

Ingestion:

Unlikely under normal conditions of use, but swallowing the dust from this product may result in irritation to the mouth and gastrointestinal tract.

Inhalation: Dust may cause irritation of the nose, throat, and airways, resulting in coughing and sneezing. Certain susceptible individuals may experience wheezing (spasms of the bronchial airways) on inhaling dust during sanding or sawing operations.

SECTION 4: FIRST AID MEASURES

EYES: Remove contact lens. Flush with running water or saline for at least 15 minutes. Seek medical attention if redness persists or if visual changes occur.

SKIN: Wash with mild soap and water. Contact physician if irritation persists or later develops.

INGESTION: If ingested, dilute by drinking large amounts of water. Do not induce vomiting. Seek medical attention. If unconscious, loosen tight clothing and lay the person on his / her side. Give nothing by mouth to an individual who is not alert and conscious. Seek medical attention.

INHALATION: Remove to fresh air. If shortness of breath or wheezing develops, seek medical

attention.

NOTES TO PHYSICIAN OR FIRST AID PROVIDERS: Treat symptomatically.

MSDS No.: MBGEP-032107-5 Magnum Board® Brand Products

Page 3 of 8

SECTION 5: FIRE-FIGHTING MEASURES

Magnum™ Building Products line of “Magnum Board®” Products are non flammable, non explosive and non combustible.

Fire and Explosion Hazard Flash Point: Not applicable. Auto-ignition: Not applicable

Extinguishing Media: This material is non combustible. Appropriate extinguishing media should be used for surrounding fire.

Fire Fighting: Fire fighting personnel should wear normal protective equipment.

SECTION 6: ACCIDENTAL RELEASE MEASURES

No special precautions are necessary to pick up product that has been dropped. The following applies only to spills or releases of dust generated during cutting or sanding Magnum Board®.

Precautions:

Good housekeeping practices are necessary for cleaning up areas where dust has been produced. Take measures to either eliminate or minimize the creation of dust.

Wherever possible, practices likely to generate dust should be controlled with engineering controls such as local exhaust ventilation, dust suppression with water and containment, enclosure or covers.

Cleanup Methods: A fine water spray may be used to suppress dust when sweeping (dry sweeping is not recommended). Vacuuming with an industrial vacuum cleaner outfitted with a high-efficiency particulate (HEPA) filter is recommended over sweeping. Waste may be disposed of by landfill in compliance with federal, provincial, state and local requirements governing non-toxic mineral materials

Avoid using materials and products that are incompatible with this product. (Refer to section 10.)

MSDS No.: MBGEP-032107-5 Magnum Board® Brand Products

Page 4 of 8

SECTION 7: HANDLING AND STORAGE

Handling and Storage Products in their intact state do not present a health hazard. The controls below apply to dust generated from the boards by cutting, drilling, routing, sawing, crushing, or otherwise abrading, and cleaning or moving sawdust.

Other Precautions: Even though Magnum Board® has been tested and deemed non toxic, Magnum Building Products recommends that exposure to dust be kept as low as

reasonably possible. Respirable levels should not exceed those specified by OSHA and MSHA and identified in this MISDS. Exposure to respirable (fine) dust depends on a variety of factors, including activity rate (i.e. cutting rate), method of handling (i.e. electric shears), environmental conditions (i.e. weather conditions, workstation orientation) and control measures used. Wherever possible, practices likely to generate dust should be carried out in well ventilated areas (i.e. outside). The work practices and engineering controls set out in Section 8 should be followed as precautions to reduce dust exposures.

SECTION 8: EXPOSURE CONTROLS / PERSONAL PROTECTION

Engineering Controls

Cutting Outdoors: 1. Magnum Building Products recommends positioning cutting station so

that wind will blow dust away from user or others in working area andallow for ample dust dissipation.

2. Use one of the following methods based on the required cutting rate andjobsite conditions.

Best

Score and snap using carbide-tipped scoring knife or utility knife(Ability to use this method depends on thickness of MagnumBoard® being installed.)

Fibercement board shears (electric or pneumatic).

Better

Dust reducing circular saw equipped with appropriate blade andHEPA vacuum extraction.

Good (for low to moderate cutting only)

Dust reducing circular saw with appropriate saw blade.

Always use correct tools when executing all cutting operations.

MSDS No.: MBGEP-032107-5 Magnum Board® Brand Products

Page 5 of 8

Ventilation: Use adequate general or local exhaust ventilation to keep airborne concentrations below the permissible exposure limit.

Respiratory Protection: Dust mask is recommended. .

Eye Protection: When cutting material, dust resistant safety goggles / glasses should be worn and used in compliance with ANSI Standard Z87.1-1-1989 and applicable

OSHA (i.e. 29 CFR 1910.133) standards.

Skin Protection: Loose comfortable clothing should be worn. Magnum Building Products recommends that direct skin contact with dust and debris be avoided when possible by wearing long sleeved shirts and long trousers, a cap or hat, and gloves.

Sanding / Drilling / Other Machining: If sanding, drilling, or other machining is conducted, Magnum Building Products recommends wear a NIOSH-approved dust mask.

Important Notes: 1. For maximum protection (lowest respirable dust production), Magnum

Building Products recommends always using “Best” level cuttingmethods where feasible.

2. Always use a circular saw blade that is appropriate for the specificoperation being undertaken.

3. Dry sweeping is not the preferred clean up method - Magnum BuildingProduction suggests wet suppression methods or HEPA vacuum.

4. It is not recommended that a grinder or continuous rim diamond bladebe used for cutting.

5. Always follow tool manufacturer’s safety recommendations.

SECTION 9: PHYSICAL AND CHEMICAL PROPERTIES

Appearance: Various colors depending on application, each with varying dimensions

according to product used.

Odor: Very mild

Physical State: Solid boards

MSDS No.: MBGEP-032107-5 Magnum Board® Brand Products

Page 6 of 8

Vapor Pressure: Not relevant.

Specific Gravity: Not relevant.

Flammability Limits: Not relevant.

Boiling Point: Not relevant

Melting Points: Not relevant.

Flash Point: Not relevant.

Auto-ignition Temperature: Not relevant.

Volatility: Not relevant.

Solubility in Water: Not relevant.

Evaporation rate: Not applicable.

NFPA Ratings (Scale 0 – 4) Health = 1 Flammability = 0 Reactivity = 0 Personal Protection = E

SECTION 10: STABILITY AND REACTIVITY

Stability: The Magnum Board products identified in section 1 are stable under ordinary conditions.

Conditions to Avoid: Excessive dust generation without proper dust mask protection.

MSDS No.: MBGEP-032107-5 Magnum Board® Brand Products

Page 7 of 8

Materials to Avoid: Incompatibility: Hydrofluoric acid will dissolve Magnesium Oxide and

can generate Magnesium Chloride fumes.

SECTION 11: TOLXICOLOGICAL INFORMATION

Magnum Board® products are non toxic in their intact form. The following applies to dust that may be generated during cutting and sanding.

Chronic Effects:

Inhaled: Repeated and prolonged overexposures to dust may cause increased risk of bronchitis. It is possible that repeated inhalation exposure to Magnum Board® fiber dust over time may lead to inflammation of the lungs in humans. All necessary precautions should be taken to prevent inhalation of dust to prevent these problems.

SECTION 12: ECOLOGICAL INFORMATION

Because Magnesium Oxide is a naturally occurring mineral, releases that may occur into the environment are not expected to leave any hazardous material that could cause a significant adverse impact.

SECTION 13: DISPOSAL CONSIDERATIONS

Dispose of material, as an inert, inorganic mineral, in conformance with federal, provincial, state and local regulations. Magnum Board® is not an RCRA hazardous waste.

SECTION 14: TRANSPORT INFORMATION

There are no special requirements for storage and transport of Magnum Board™.

UN No: None allocated Dangerous Goods Class: None allocated Hazchem Code: None allocated Poisons Schedule: None allocated Packing Group: Not applicable

Label: Not a DOT hazardous material.

SECTION 15: REGULATORY INFORMATION

DOT Hazard Classification: None

Placard Requirement: Not a DOT hazardous material.

MSDS No.: MBGEP-032107-5 Magnum Board® Brand Products

Page 8 of 8

CERCLA Hazardous Substance (40 CFR Part 302)

Listed substance: No Unlisted Substance: No Reportable Quantity (RQ): None Characteristic(s): Not applicable RCRA Waste Number: Not applicable

SECTION 16: OTHER INFORMATION

Preparation of Information and Disclaimer: This form has been prepared to meet current Federal OSHA hazard communication regulations and is offered without any warranty or guarantee of any type. Magnum Building Products cannot control the use of its products, and therefore specifically disclaims liability and responsibility arising from the use, misuse and/ or alteration of its products.

The information contained in this MSDS was produced without independent scientific or medical studies analyzing the effects of Magnum Board® dust upon human health. The information contained herein is based upon scientific and other data Magnum Building Products believes is valid and reliable and provides the basis for this MSDS. The information contained herein relates only to specific materials listed in the document. It does not address the effects of Magnum Board® dust when used in combination with other materials or substances, or when used in other processes. Because conditions of use are beyond Magnum Building Products control, the company makes no representations, guarantees or warranties, either express or implied warranties as to the fitness of the product for use, and assume no liability related to the information contained above.

Magnum Building Products requires, as a condition of use of its products, that purchasers comply with all applicable Federal, Provincial, State, and Local health and safety laws, regulations, orders, requirements, and strictly adhere to all instructions and warnings which accompany the product.

P a g e | 24 25 – May – 2016 Version 3.0

New Zealand Sustainable Forest Products LP Address: 10 Gannons Road, RD 1 Reefton, 7895

Phone 03 732 8414 E–Mail: [email protected] http://www.healthbasedbuilding.com/magnum-board

Appendix C

New Zealand Sustainable Forest Products LP 10 Gannons Road, RD 1 Reefton, 7895Phone 03 732 8414 E–Mail: [email protected] http://www.healthbasedbuilding.com/magnum-board

Checklist Pre-installation of Magnum Board Weatherboard

Magnum Board Rigid Air Barrier & Magnum Board Interior

NOTE:ItistheresponsibilityofthecertifiedinstallertoinspecttheirworkplacepriortobeginningtheinstallationofMagnumBoardWeatherBoardandMagnumBoardRigidAirBarriertoensuretheinstalledworkwillmeetthesupplier’srequirements.Notifyowner/generalcontractorofanyconcernspriortoinstallation.

CompanyName: JOB#AddressofJob:NameofContractor:Date/ /

CHECKLISTMagnumBoardRigidAirBarrier 1. Framingconfigurationandfixingdetail

2. Framingflushandlevel3. Truss&Roof/windowgangnailsorfixingsare

“recessed”intoframing4. Access&heights5. Servicesidentified6. HealthandSafetyplaninplace

MagnumBoardWeatherboard 1. Framingconfigurationandbattenpositioning2. Framing/battensflushandlevel3. Access&heights4. Servicesidentified5. HealthandSafetyplaninplace6. HealthandSafety7. Frameisstraight

MagnumBoardInterior 1. Framing/batten/blockingpositioning2. Prelineiscomplete3. Servicesidentified4. Access&Height5. RevealsorArchitraves6. Framing/battensareflushandlevel7. HealthandSafety

New Zealand Sustainable Forest Products LP 10 Gannons Road, RD 1 Reefton, 7895Phone 03 732 8414 E–Mail: [email protected] http://www.healthbasedbuilding.com/magnum-board

Checklist Final-installation of Magnum Board Weatherboard Magnum Board Rigid Air Barrier & Magnum Board

Interior NOTE:ItistheresponsibilityoftheinstallertoinspecttheirworkplacepriortobeginningtheinstallationofMagnumBoardWeatherBoardandMagnumBoardRigidAirBarriertoensuretheinstalledworkwillmeetthesupplier’srequirements.Notifyowner/generalcontractorofanyconcernspriortoinstallation.

Companyname: JOB#Addressofjob:NameofContractorDate / / Signature:

CHECKLISTMagnumBoardRigidAirBarrier

1. Fixingdetailsmatchrecommendedfixingpattern

2. AlignmentwithopeningstosuitABEPliquidflashings3. Sheetsingoodconditionandfixedflushwithfaceof

framework4. Wastematerialisremovedorpositionedforremoval

asnontoxicmaterial

MagnumBoardWeatherboard 1. Fixingdetailsmatchrecommendedfixingpattern2. Boardsarestraightandlevel3. Lapsaretight4. Wastematerialisremovedorpositionedforremoval

asnontoxicmaterial

MagnumBoardInterior 1. Fixingdetailsmatchrecommendedfixingpattern2. Sheetsconnectionsaretight3. Fixingscrewsarebelowplasteringlevel4. Wastematerialisremovedorpositionedforremoval

asnontoxicmaterial