Yantai Oceanair Refrigeration & Air-Conditioning Co.,Ltd. was established in 2004 and has been listed on the New OTCBB (Stock Code: 831870). We are mainly specialized in the development, design, manufacturing, sales and after-sales service of air-conditioning equipments, the installation and commissioning of refrigeration and air-conditioning equipments, engineering design and technical consultation services. Our leading products include underground water source heat pumps, sewage source heat pumps, seawater source heat pumps, ground source heat pumps, low and medium temperature water chillers etc. They are widely used in comfort air-conditioning systems in residential and industrial buildings, and are also applied for water temperature control in marine aquaculture, aquatic products processing, as well as process cooling, waste heat recovery and utilization in pharmaceutical, chemical, food, or thermal power industry etc. Our products are sold to more than 20 provinces, cities and autonomous regions domestically and are exported to over 20 countries and regions in Asia, Africa, Europe and South America.
Backed up by a team of qualified personnel and strong scientific research capabilities, the company is continuously committed to the research, application and promotion of integrated cross-disciplinary and interdisciplinary projects in HVAC and refrigeration areas. We have been firmly keeping up with innovative technologies, processes, materials and methods in global refrigeration, heating, ventilation, heat pump and relevant industries and have been granted more than 30 national invention patents and utility model patents successively. The company is a pioneer in evaporative water chillers in China and is the only manufacturer specializing in the manufacturing of both special section steel tube-type evaporative condensers and water chillers in China, which currently represents the highest standards of domestic evaporative water chillers. Our products have obtained ISO9001-2000 Quality Management System Certification, ISO 14001 Environmental Management System Certification, OSHA18001 Occupational Health and Safety Management System Certification, National Industrial Products Production License, National Energy Conservation Products Certification and Energy Conservation Certification for Innovative Construction Equipments in Shandong Province successively. The company has totally invested RMB 3 million in establishing a product performance testing center with the domestic advanced level to perform performance testing for various products, such as low temperature water chillers, other water chillers and water source heat pump units etc. in -35℃ cold water to 120℃ hot water, and the center has been granted the certification by the National Quality Supervision and Inspection Center for Compressor and Refrigeration Equipment.
The company covers an area of 45,000 square meters including the floor area of 22,000 square meters, with a registered capital of RMB 46.60 million and a total asset of over RMB 90 million. Currently, we have more than 180 staff members, among whom there are 3 members with a doctoral degree, 5 members with a master’s degree, and over 50 professional technicians with intermediate and senior titles. Moreover, we have been rated as an AA grade credit enterprise by banks, and now is the member of China Refrigeration and Air-Conditioning Industry Association and Shandong Association of Refrigeration.
2
Company Profile
Technical Manual of Oceanair Refrigeration and Air-Conditioning Series Products
Model Code Explanation of the Low Temperature Chiller
The System Diagram of Low Temperature Water Chillers
Evaporative condenser
Evaporativecooling chiller
Terminal
Chilled watercirculating pump
Water cooled chiller
Cooling tower
Cooling watercirculating pump
Dry type, or flooded type if not represented
Leaving water
Evaporative cooling type
Cooling capacity of the chiller KW
Low temperature chiller
Technical Manual of Oceanair Refrigeration and Air-Conditioning Series Products
2
Product Introduction
OWCCL-G Series Economical and Practical Type Low Temperature Chillers
Main Features of the Chiller
Flooded specialized semi-hermitic double screw compressor of famous international brand is adopted, with no leaking, low noisy, slight vibration and stable performance, which can guarantee a long term safety stable operation
High Efficiency and Energy SavingThe unit can automatically adjust the energy output of each refrigerating compressor and turn on or turn off each
compressor according to the actual requirement and change of the site to ensure a high efficiency operation under low load, avoiding energy (electricity) waste and reducing the energy consumption cost.
Dry-type evaporator is adopted which was equipped with the newest type of internal thread high efficiency heat exchange tube, combining the optimized design of the baffle plate inside the shell, which can improve the heat exchange efficiency greatly. Furthermore, the dry-type evaporator is characterized by safety oil return, which can ensure the compressors operating with safety oil return without any external oil return devices.
Horizontal water cooled hell and tube heat exchanger and high efficiency screw thread heat exchange tube are adopted with high heat exchange efficiency and convenient water side cleaning.
Reliable Refrigerating Circuit The unit is designed with single compressor independent refrigerating system, and the two system of the double
compressor unit are independent, possessing flexibility in application and good backup characteristics.Famous international brand refrigerating accessories are adopted in refrigerating system, such as expansion
valve, magnetic valve. Famous international brand electrical components are adopted, such as AC contactor, air switch.
Advanced Computer Control System
Advanced micro computer control technology from HongKong Oceanair Industrial Company is adopted, which can provide complete control and protective functions. The LCD controller is in Chinese and easy to handle, and with friendly human and machine interface. The unit can be operated through the touch screen.
One-key startup & shutdown shortcut functionDisplaying the overall operation condition, parameter settings, alarms and records through the screen figuresAuto-timing operation as per the set program, such can be set by day (three phrases) or by weeks, then the
computer will control the units to operate automatically, realizing the unattended operation.It can automatically diagnose and display the faults and has the faults statistic function. The faults can be
inquired in three ways: fault code, fault times, fault occurring time.The computer controller of the unit has the coordinated control function with the chilled water pump and
cooling water pump, which can make the system operate more safely, reliably, and energy-saving, furthermore, the controller can manage the whole water system of the machine room so as to reduce the investment in hardware of the control system of the machine room.
Technical Manual of Oceanair Refrigeration and Air-Conditioning Series Products
3
Product overview
Remote monitoring can be realized through the installation of RS485 communication interface.
Perfect and Reliable Protective Function
The unit is equipped with perfect safety protective devices which can provide all-around safety protection.Default phase protection, anti-phase protection and overvoltage (under-voltage) protection to the power supply.Overheat protection, overload protection, anti-reverse protection, anti-frequent-start protection, exhaust gas
temperature overheat protection to the motor of the compressor.Protection for too low high-low voltage difference, too high high-voltage, too low low-voltage, startup delay,
too low water flow, too high (low) circulating water temperature, sensor faults and startup & shutdown code.
Multiple Choices of Refrigerant
R22 refrigerant is applied in standard unit, but other refrigerants such as R134a can also be applied according to customers’ requirements.
Easy to Install on Site
The evaporator and condenser are equipped with connecting pipe and flange, which make it easy to install on site.
Compact structure of the unit covers small areas.The direction of the pipe connector of the condenser can be changed from right to left and vice versa according
to the on-site requirements.The slight vibration makes the unit need no special vibration isolation measurements to be taken.The unit has pass strict test before leaving the factory, so you only need to connect the pipe, power, and fill
appropriate amount of refrigerant and conduct simple commissioning before it can be put to use.
Note:1. Nominal work condition stipulation: the leaving water temperature of the 43% ethylene glycol water solution is -10℃, and the water flow of the evaporator and condenser is calculated by 5℃ temperature difference. 2. The calcium chloride water solution can also be adopted as secondary refrigerant. If the customer wants to apply calcium chloride water solution, please notice in the order. 3. The ethylene glycol water solution can only be used in intermediate temperature brine unit as secondary refrigerant, while the calcium chloride water solution can be used both in intermediate and low temperature brine unit. 4. Besides the above specified product, our company can provide non-standard product according to customers’ requirement. 5. The dimension may change due to the technology improvement, so please ask for installation drawing.
Technical Manual of Oceanair Refrigeration and Air-Conditioning Series Products
4
Product overview
Technical Parameters of the OWCCL-G Series Low Temperature Chillers
Model OWCCL-G 50 70 95 120 150 190 250 290
Nominal refrigerating capacity KW 48.6 66.3 94.7 115.5 149.4 186.9 244.9 283.1
Kcal/h×104 4.18 5.70 8.14 9.93 12.85 16.07 21.06 24.35
Working medium R22
Compressor
Type Semi-hermetic screw compressor
Single set input power KW 19.6 25.8 35.5 43.2 53.0 66.9 86.4 98.9
Number Set 1
Power supply system 380V/3P/50Hz
Starting mode Y—△
Oil tank heater W 300
Evaporator
Type Shell and tube dry type
Secondary refrigerant Ethylene glycol water solution
Leaving water temperature ℃ -10
Chilled water flow m3/h 9.5 13.0 18.5 22.6 29.2 36.6 47.9 55.4
Resistance KPa ≤50
Standard pressure-bearing MPa 1.0
Scaling factor m2℃/ KW 0.018
Connecting pipe size(DN) mm 65 65 80 80 100 100 125 125
Condenser
Type Efficient shell and tube type
Entering water temperature ℃ 30
Cooling water flow m3/h 11.7 15.8 22.4 27.3 34.8 43.7 57.0 65.7
Resistance KPa ≤75
Standard pressure-bearing MPa 1.0
Scaling factor m2℃/ KW 0.044
Connecting pipe size(DN) mm 65 65 80 80 100 100 125 125
Oil separator Type Packing type
Safeguard High voltage, low voltage, oil pressure difference, low oil level, ultralow temperature, default phrase, anti-phrase and overload
Adjustable range of capacity % 33 startup 66,00 25startup 50,75,100
Weight of the unitNet weight Kg 790 910 1170 1430 1650 1860 2270 2430
Operating weight Kg 990 1130 1420 1650 1950 2180 2610 2780
Outline Dimensions
Length mm 2950 2950 2950 3150 3150 3450 3650 3750
Width mm 1100 1100 1130 1130 1150 1185 1185 1265
Height mm 1600 1600 1630 1630 1630 1660 1660 1680
5
Technical parameter
Technical Manual of Oceanair Refrigeration and Air-Conditioning Series Products
Technical Parameters of the OWCCL-G Series Low Temperature Chillers
Model OWCCL-G 320 370 410 490 520 610 740 870
Nominal refrigerating capacity KW 318.3 370.8 407.2 490 517.0 613.0 741.6 869.4
Kcal/h×104 27.37 31.89 35.02 42.14 44.46 52.72 63.78 74.77
Working medium R22
Compressor
Type Semi-hermetic screw compressor
Single set input power KW 109.9 126.6 140.4 167.7 91.3 106.4 126.6 149.1
Number Set 1 2
Power supply system 380V/3P/50Hz
Starting mode Y—△
Oil tank heater W 300 300×2
Evaporator
Type Shell and tube dry type
Secondary refrigerant Ethylene glycol water solution
Leaving water temperature ℃ -10
Chilled water flow m3/h 62.3 72.6 79.7 95.9 101.2 120.0 145.2 170.2
Resistance KPa ≤60
Standard pressure-bearing MPa 1.0
Scaling factor m2℃/ KW 0.018
Connecting pipe size(DN) mm 125 150 150 150 150 200 200 200
Condenser
Type Efficient shell and tube type
Entering water temperature ℃ 30
Cooling water flow m3/h 73.7 85.6 94.2 113.1 120.3 142.0 171.1 200.8
Resistance KPa ≤80
Standard pressure-bearing MPa 1.0
Scaling factor m2℃/ KW 0.044
Connecting pipe size(DN) mm 125 150 150 150 150 200 200 200Oil
separator Type Packing type
Safeguard High voltage, low voltage, oil pressure difference, low oil level, ultralow temperature, default phrase, anti-phrase and overload
Adjustable range of capacity % 25 startup,50,75,100 12.5 startup, progressive increased to100 by 12.5
Weight of the unitNet weight Kg 2710 3310 3890 4430 5310 5750 6460 7070
Operating weight Kg 3060 3720 4310 4890 5800 6170 7020 7680
Outline Demisions
Length mm 3850 4050 4250 4450 4450 4450 4850 4850
Width mm 1265 1300 1300 1350 1730 1730 1860 1980
Height mm 1680 1800 1800 1840 1850 1850 1990 1990
6
Technical parameter
Technical Manual of Oceanair Refrigeration and Air-Conditioning Series Products
OWCCL Series Energy-Saving Type Low Temperature Chillers
Main Features of the Chiller
Flooded specialized semi-hermitic double screw compressor of famous international brand is adopted, the inserted oil separator of which is modified to obtain a better oil separation effect with no leaking, low noisy, slight vibration, stable performance, which can guarantee a long term safety stable operation.
High Efficiency and Energy SavingThe unit can automatically adjust the energy output of each refrigerating compressor and turn on or turn off each
compressor according to the actual requirement and change of the site to ensure the high efficiency operation under low load, avoiding energy (electricity) waste and reducing the energy consumption cost.
Flooded evaporator is adopted which is equipped with the latest flooded specialized external thread high efficiency heat exchange tube, improving the heat exchange efficiency greatly by about 15% comparing with dry –type evaporator; and special oil-trap devices is installed in the evaporator to enable the oil in the evaporator to return to the compressor intensively.
Horizontal water cooled shell and tube heat exchanger and high efficiency screw thread heat exchange tube are adopted with high heat exchange efficiency and convenient water side cleaning. A secondary oil separator is installed inside the units, which makes the unit obtain strong adaptability and high efficiency.
Reliable Refrigerating CircuitThe unit is designed with single compressor independent refrigerating system, and the two system of the double
compressor unit are independent, possessing flexibility in application and good backup characteristics.Famous international brand refrigerating accessories are adopted in refrigerating system, such as electronic
expansion valve, magnetic valve.Reliable oil-return device is adopted. The unit is designed with two-stage oil separator to minimize the oil
entering into the system, and efficient and accurate oil return jetting technology is applied to enable the oil entering into the evaporator to return to the compressor intensively, guaranteeing a reliable and efficient operation.
Famous international brand electrical components are adopted, such as AC contactor, air switch.
Advanced Computer Control System
Advanced micro computer control technology from HongKong Oceanair Industrial Company is adopted, which can provide complete control and protective functions. The LCD controller is in Chinese and easy to handle, and with friendly human and machine interface. The unit can be operated through the touch screen.
One-key startup & shutdown shortcut functionDisplaying the overall operation condition, parameter settings, alarms and records through the screen figuresAuto-timing operation as per the set program, such can be set by day (three phrases) or by weeks, then the
computer will control the units to operate automatically, realizing the unattended operation.It can automatically diagnose and display the faults and has the faults statistic function. The faults can be
inquired in three ways: fault code, fault times, fault occurring time.
Technical Manual of Oceanair Refrigeration and Air-Conditioning Series Products
7
Product overview
The computer controller of the unit has the coordinated control function with the chilled water pump and cooling water pump, which can make the system operate more safely, reliably, and energy-saving, furthermore, the controller can manage the whole water system of the machine room so as to reduce the investment in hardware of the control system of the machine room.
Remote monitoring can be realized through the installation of RS485 communication interface.
Perfect and Reliable Protective Function
The unit is equipped with perfect safety protective devices which can provide all-around safety protection.Default phase protection, anti-phase protection and overvoltage (under-voltage) protection to the power supply.Overheat protection, overload protection, anti-reverse protection, anti-frequent-start protection, exhaust gas
temperature overheat protection to the motor of the compressor.Protection for too low high-low voltage difference, too high high-voltage, too low low-voltage, startup delay,
too low water flow, too high (low) circulating water temperature, sensor faults and startup & shutdown code
Multiple Choices of Refrigerant
R22 refrigerant is applied in standard unit, but other environmental friendly refrigerants such as R134a can also be applied according to customers’ requirements.
Easy to Install on Site
The evaporator and condenser are equipped with connecting pipe and flange, which make it easy to install on site.
Compact structure of the unit covers small areas.The direction of the pipe connector of the condenser can be changed from right to left and vice versa according
to the on-site requirements.The slight vibration makes the unit need no special vibration isolation measurements to be taken.The unit has pass strict test before leaving the factory, so you only need to connect the pipe, power, and fill
appropriate amount of refrigerant and conduct simple commissioning before it can be put to use.
Note:1.Nominal work condition stipulation: the leaving water temperature of the 41% ethylene glycol water solution is -10℃, and the water flow of the evaporator and condenser is calculated by 5℃ temperature difference. 2. The calcium chloride water solution can also be adopted as secondary refrigerant. If the customer wants to apply calcium chloride water solution, please notice in the order. 3. The ethylene glycol water solution can only be used in intermediate temperature brine unit as secondary refrigerant, while the calcium chloride water solution can be used both in intermediate and low temperature brine unit. 4. Besides the above specified product, our company can provide non-standard product according to customers’ requirement. 5. The dimension may change due to the technology improvement, so please ask for installation drawing.
Technical Manual of Oceanair Refrigeration and Air-Conditioning Series Products
8
Product overview
Technical Parameters of the OWCCL Series Low Temperature Chillers
Model OWCCL- 140 160 190 230 280 340 410 480
Nominal refrigerating capacity KW 138.5 163.2 188.6 224.8 282.4 334.9 405 474.9
Kcal/h×104 11.91 14.04 16.22 19.33 24.29 28.80 34.83 40.84
Working medium R22
Compressor
Type Semi-hermetic screw compressor
Single set input power KW 47.9 53.9 62.4 75.7 92.9 108.3 128.8 151.7
Number set 1
Power supply system 380V/3P/50Hz
starting mode Y—△
Oil tank heater W 300
Evaporator
type Shell and tube flooded type
Secondary refrigerant Ethylene glycol water solution
Leaving water temperature ℃ -10
Chilled water flow m3/h 27.1 31.9 36.9 44.0 55.3 65.6 79.3 93.0
Resistance KPa ≤75
Standard pressure-bearing MPa 1.0
Scaling factor m2℃/ KW 0.018
Connecting pipe size(DN) mm 100 100 125 125 125 150 150 150
Condenser
Type Efficient shell and tube type
Entering water temperature ℃ 30
Cooling water flow m3/h 32.1 37.3 43.2 51.7 64.6 76.2 91.8 107.8
Resistance KPa ≤75
Standard pressure-bearing MPa 1.0
Scaling factor m2℃/ KW 0.044
Connecting pipe size(DN) mm 100 100 125 125 125 150 150 150
Safeguard High voltage, low voltage, oil pressure difference, low oil level, ultralow temperature, default phrase, anti-phrase and overload
Adjustable range of capacity % 25 startup,50,75,100
Weight of the unitNet weight Kg 1760 1830 2070 2480 2760 3130 3870 4310
Operating weight Kg 2030 2190 2430 2740 3130 3510 4230 4720
Outline Dimensions
Length mm 3350 3350 3450 3450 3650 3850 4450 4450
Width mm 1350 1350 1380 1380 1380 1380 1430 1510
Height mm 1820 1820 1820 1870 1950 1950 2020 2100
9
Technical parameter
Technical Manual of Oceanair Refrigeration and Air-Conditioning Series Products
Technical Parameters of the OWCCL Series Low Temperature Chillers
Model OWCCL- 570 620 670 700 810 890 950 1110
Nominal refrigerating capacity KW 564.8 618.4 669.8 695.6 810.0 889.6 949.8 1070.4
Kcal/h×104 48.57 53.18 57.60 59.82 69.66 76.51 81.68 92.05
Working medium R22
Compressor
Type Semi-hermetic screw compressorSingle set
input power KW 92.9 100.6 108.3 111.8 128.8 142.9 151.7 170.6
Number set 2
Power supply system 380V/3P/50Hz
Starting mode Y—△
Oil tank heater W 300×2
Evaporator
Type Shell and tube flooded type
Secondary refrigerant Ethylene glycol water solution
Leaving water temperature ℃ -10
Chilled water flow m3/h 110.6 121.0 131.1 136.2 158.6 174.1 185.9 209.5
Resistance KPa ≤80
Standard pressure-bearing MPa 1.0
Scaling factor m2℃/ KW 0.018
Connecting pipe size(DN) mm 200 200 200 200 200 200 250 250
Condenser
Type Efficient shell and tube type
Entering water temperature ℃ 30
Cooling water flow m3/h 129.1 141.0 152.5 158.1 183.6 202.2 215.6 242.8
Resistance KPa ≤80
Standard pressure-bearing MPa 1.0
Scaling factor m2℃/ KW 0.044
Connecting pipe size(DN) mm 200 200 200 200 200 200 250 250
SafeguardHigh voltage, low voltage, oil pressure difference, low oil level,
ultralow temperature, default phrase, anti-phrase and overload
Adjustable range of capacity % 12.5 startup, progressive increased to100 by 12.5
Weight of the unitNet weight Kg 5490 5820 6080 6290 6720 7290 7680 8320
Operating weight Kg 5870 6210 6490 6700 7170 7760 8190 8840
Outline Dimensions
Length mm 4720 4720 4720 4720 4920 4920 4920 4920
Width mm 1560 1630 1630 1650 1670 1670 1750 1840
Height mm 2070 2120 2120 2120 2200 2200 2200 2250
10
Technical parameter
Technical Manual of Oceanair Refrigeration and Air-Conditioning Series Products
Technical Parameters of the OWCCL Series Low Temperature Chillers
Model OWCCL- 1200 1340 1540 1780
Nominal refrigerating capacity KW 1199.2 1342.8 1535.8 1781.4
Kcal/h×104 103.13 115.48 132.08 153.20
Working medium R22
Compressor
Type Semi-hermetic screw compressor
Single set input power KW 197.6 218.0 245.5 283.4
Number set 2
Power supply system 380V(10KV)/3P/50Hz
Starting mode Y—△
Oil tank heater W 300×2
Evaporator
Type Shell and tube flooded type
Secondary refrigerant Ethylene glycol water solution
Leaving water temperature ℃ -10
Chilled water flow m3/h 234.7 262.8 300.6 348.7
Resistance KPa ≤80
Standard pressure-bearing MPa 1.0
Scaling factor m2℃/ KW 0.018
Connecting pipe size(DN) mm 250 250 250 250
Condenser
Type Efficient shell and tube type
Entering water temperature ℃ 30
Cooling water flow m3/h 274.2 306.0 348.6 403.9
Resistance KPa ≤80
Standard pressure-bearing MPa 1.0
Scaling factor m2℃/ KW 0.044
Connecting pipe size(DN) mm 250 250 250 250
Safeguard High voltage, low voltage, oil pressure difference, low oil level, ultralow temperature, default phrase, anti-phrase and overload
Adjustable range of capacity % 12.5 startup, progressive increased to100 by 12.5
Weight of the unit Net weight Kg 8860 9270 11060 11950
Operating weight Kg 10170 10960 12260 13160
Outline Dimensions
Length mm 5230 5230 5430 5430
Width mm 1580 1580 1670 1670
Height mm 2160 2160 2280 2280
11
Technical parameter
Technical Manual of Oceanair Refrigeration and Air-Conditioning Series Products
OWCCL –Z Series High Efficiency and Energy-Saving TypeLow Temperature Chillers
Main Features of the Chiller
Flooded specialized semi-hermitic double screw compressor of famous international brand is adopted, the inserted oil separator of which is modified to obtain a better oil separation effect with no leaking, low noisy, slight vibration, stable performance, which can guarantee a long term safety stable operation.
High Efficiency and Energy SavingThe unit can automatically adjust the energy output of each refrigerating compressor and turn on or turn off each
compressor according to the actual requirement and change of the site to ensure the high efficiency operation under low load, avoiding energy (electricity) waste and reducing the energy consumption cost.
Flooded evaporator is adopted which is equipped with the latest flooded specialized external thread high efficiency heat exchange tube, improving the heat exchange efficiency greatly by about 15% comparing with dry –type evaporator; and special oil-trap devices is installed in the evaporator to enable the oil in the evaporator to return to the compressor intensively.
A high efficiency external oil separator is adopted to carry out secondary oil separation, which makes the unit obtain strong adaptability and high efficiency.
Evaporate condenser and high efficient ellipse section tube are adopted. The proper designed sprinkling system enable the forming of uniform water films around the surface of the condenser tubes, achieving a high heat exchange efficiency. The complex cooling water system can be avoided from the water cooled condenser.
Reliable Refrigerating CircuitThe unit is designed with single compressor independent refrigerating system, and the two system of the double
compressor unit share the high pressure, which can save the initial investment and can improve the energy efficiency under partial load condition.
Famous international brand refrigerating accessories are adopted in refrigerating system, such as expansion valve, magnetic valve.
Reliable oil-return device is adopted. The unit is designed with two-stage oil separator to minimize the oil entering into the system, and efficient and accurate oil return jetting technology is applied to enable the oil entering into the evaporator to return to the compressor intensively, guaranteeing a reliable and efficient operation.
Famous international brand electrical components are adopted, such as AC contactor, air switch. Advanced Computer Control System
Advanced micro computer control technology from HongKong Oceanair Industrial Company is adopted, which can provide complete control and protective functions. The LCD controller is in Chinese and easy to handle, and with friendly human and machine interface. The unit can be operated through the touch screen.
One-key startup & shutdown shortcut functionDisplaying the overall operation condition, parameter settings, alarms and records through the screen figuresAuto-timing operation as per the set program, such can be set by day (three phrases) or by weeks, then the
computer will control the units to operate automatically, realizing the unattended operation.It can automatically diagnose and display the faults and has the faults statistic function. The faults can be
inquired in three ways: fault code, fault times, fault occurring time.The computer controller of the unit has the coordinated control function with the chilled water pump and
Technical Manual of Oceanair Refrigeration and Air-Conditioning Series Products
12
Product overview
cooling water pump, which can make the system operate more safely, reliably, and energy-saving, furthermore, the controller can manage the whole water system of the machine room so as to reduce the investment in hardware of the control system of the machine room.
Remote monitoring can be realized through the installation of RS485 communication interface. Perfect and Reliable Protective Function
The unit is equipped with perfect safety protective devices which can provide all-around safety protection.Default phase protection, anti-phase protection and overvoltage (under-voltage) protection to the power supply.Overheat protection, overload protection, anti-reverse protection, anti-frequent-start protection, exhaust gas
temperature overheat protection to the motor of the compressor.Protection for too low high-low voltage difference, too high high-voltage, too low low-voltage, start-up delay,
too low water flow, too high (low) circulating water temperature, sensor faults and startup & shutdown code Multiple Choices of Refrigerant
R22 refrigerant is applied in standard unit, but other environmental friendly refrigerants such as R134a can also be applied according to customers’ requirements.
Easy to Install on Site
The evaporator and condenser are equipped with connecting pipe and flange, which make it easy to install on site.
Compact structure of the unit covers small areas.The direction of the pipe connector of the condenser can be changed from right to left and vice versa according
to the on-site requirements.The slight vibration makes the unit need no special vibration isolation measurements to be taken.The unit has pass strict test before leaving the factory, so you only need to connect the pipe, power, and fill
appropriate amount of refrigerant and conduct simple commissioning before it can be put to use.
Note:1.Nominal work condition stipulation: the leaving water temperature of the 41% ethylene glycol water solution is -10℃, and the water flow of the evaporator and condenser is calculated by 5℃ temperature difference. The dry bulb temperature of design condition of the evaporative condenser is 35℃ and the wet bulb temperature is 24℃, for the details please ask for the sample of the evaporative condenser. The weight of the unit does not include the weight of the evaporative condenser.
2. The calcium chloride water solution can also be adopted as secondary refrigerant. If the customer wants to apply calcium chloride water solution, please notice in the order.
3. The ethylene glycol water solution can only be used in intermediate temperature brine unit as secondary refrigerant, while the calcium chloride water solution can be used both in intermediate and low temperature brine unit.
4. Besides the above specified product, our company can provide non-standard product according to customers’ requirement.
5. The dimension may change due to the technology improvement, so please ask for installation drawing.
Technical Manual of Oceanair Refrigeration and Air-Conditioning Series Products
13
Product overview
Technical Parameters of the OWCCL-Z Series Low Temperature Chillers
Model OWCCL-Z 150 180 230 280 320 360 420 500
Nominal refrigerating capacity KW 143.9 179.1 233.5 277.9 321.3 361.3 420.8 493.4
Kcal/h×104 12.38 15.40 20.08 23.90 27.63 31.07 36.19 42.43
working medium R22
Compressor
Type Semi-hermetic screw compressor
Single set input power KW 45.5 53.8 71.9 83.5 95.5 106.1 122.3 144.0
Number set 1
Power supply system 380V/3P/50Hz
Starting mode Y—△
Oil tank heater W 300
Evaporator
Type Shell and tube flooded type
Secondary refrigerant Ethylene glycol water solution
Leaving water temperature ℃ -10
Chilled water flow m3/h 28.2 35.1 45.7 54.4 62.9 70.7 82.4 96.6
Resistance KPa ≤75
Standard pressure-bearing MPa 1.0
Scaling factor m2℃/ KW 0.018
Connecting pipe size(DN) mm 100 100 125 125 150 150 150 150
Condenser
Type Evaporative
Model OZNX- F 300 400 500 600 600 700 900 900
Number Set 1
FanPower KW 0.75 0.75 1.5 1.5 1.5 2.2 2.2 2.2
Number Set 2 2 2 2 2 2 2 2
PumpPower KW 1.1 1.1 2.2 2.2 2.2 2.2 3.0 3.0
Number Set 1 1 1 1 1 1 1 1
Make-up water volume m3/h 0.2-0.7 0.3-1.1 0.5-1.9 0.6-2.1 0.6-2.1 0.7-2.3 0.7-2.8 0.7-2.8
Oil Separator Type Packing type
Safeguard High voltage, low voltage, oil pressure difference, low oil level, ultralow temperature, default phrase, anti-phrase and overload
Adjustable range of capacity % 25 startup, 50,75,100
Weight of the unit Net weight Kg 1580 1690 1830 2110 2310 2790 3350 3700
Operating weight Kg 1740 1850 2010 2290 2490 2980 3550 3910
Outline Dimensions
Length mm 3110 3110 3210 3210 3410 3610 4210 4210
Width mm 1100 1160 1210 1280 1280 1280 1220 1280
Height mm 1720 1820 1860 1950 1950 1950 2020 2100
14
Technical parameter
Technical Manual of Oceanair Refrigeration and Air-Conditioning Series Products
Technical Parameters of the OWCCL-Z Series Low Temperature Chillers
Model OWCCL-Z 590 640 700 720 840 920 990 1110
Nominal refrigerating capacity KW 586.8 642.6 695.8 722.6 841.6 924.2 986.8 1112.2
Kcal/h×104 50.46 55.26 59.84 62.14 72.38 79.48 84.86 95.65
Working medium R22
Compressor
Type Semi-hermetic screw compressor
Single set input power KW 88.2 95.5 102.8 106.1 122.3 135.6 144 162
Number Set 2
Power supply system 380V/3P/50Hz
Starting mode Y—△
Oil tank heater W 300×2
Evaporator
Type Shell and tube flooded type
Secondary refrigerant Ethylene glycol water solution
Leaving water temperature ℃ -10
Chilled water flow m3/h 114.9 125.8 136.2 141.4 164.7 180.9 193.2 217.7
Resistance KPa ≤80
Standard pressure-bearing MPa 1.0
Scaling factor m2℃/ KW 0.018
Connecting pipe size(DN) mm 200 200 200 200 200 250 250 250
Condenser
Type Evaporative condenser
Model OZNX- F 1200 1200 1500 1500 1800 1800 2000 2400
Number Set 1
FanPower KW 3.0 3.0 4.0 4.0 3.0 3.0 4.0 4.0
Number Set 2 2 2 2 3 3 2 3
PumpPower KW 4.0 4.0 5.5 5.5 7.5 7.5 7.5 7.5
Number Set 1 1 1 1 1 1 1 1
Make-up water volume m3/h 1.0-3.1 1.0-3.1 1.1-4.7 1.1-4.7 1.5-5.5 1.5-5.5 1.7-6.1 1.7-6.1
Oil Separator Type Packing type
Safeguard High voltage, low voltage, oil pressure difference, low oil level, ultralow temperature, default phrase, anti-phrase and overload
Adjustable range of capacity % 12.5 startup, progressive increased to100 by 12.5
Weight of the unit Net weight Kg 4750 5030 5220 5410 5800 6280 6600 7110Operating
weight Kg 5040 5320 5510 5710 6110 6590 6910 7430
DimensionLength mm 4480 4480 4480 4480 4680 4680 4680 4680
Width mm 1600 1680 1680 1730 1750 1750 1880 1900
Height mm 2070 2120 2120 2120 2200 2200 2200 2250
15
Technical parameter
Technical Manual of Oceanair Refrigeration and Air-Conditioning Series Products
Technical Parameters of the OWCCL-Z Series Low Temperature Chillers
Model OWCCL-Z 1240 1390 1600 1850
Nominal refrigerating capacity KW 1245.4 1394.4 1595.0 1849.8
Kcal/h×104 107.10 119.92 137.17 159.08
Working medium R22
Compressor
Type Semi-hermetic screw compressor
Single set input power KW 187.4 206.8 232.9 268.9
Number Set 2
Power supply system 380V(10KV)/3P/50Hz
Starting mode Y—△
Oil tank heater W 300
Evaporator
Type Shell and tube flooded type
Secondary refrigerant Ethylene glycol water solution
Leaving water temperature ℃ -10
Chilled water flow m3/h 243.8 272.9 312.2 362.1
Resistance KPa ≤75
Standard pressure-bearing MPa 1.0
Scaling factor m2℃/ KW 0.018
Connecting pipe size(DN) mm 250 250 250 250
Condenser
Type Evaporative type
Model OZNX- F 2400 1500 1500 1800
Number Set 1 2
FanPower KW 4.0 4.0 4.0 3.0
Number Set 3 2 2 3
PumpPower KW 7.5 5.5 5.5 7.5
Number Set 1 1 1 1
Make-up water volume m3/h 1.7-6.1 1.1-4.7 1.1-4.7 1.5-5.5
Oil Separator Type Packing type
Safeguard High voltage, low voltage, oil pressure difference, low oil level, ultralow temperature, default phrase, anti-phrase and overload
Adjustable range of capacity % 12.5 startup, progressive increased to100 by 12.5
Weight of the unit Net weight Kg 8360 8570 10260 11150
Operating weight Kg 9270 9960 11260 12160
Dimension
Length mm 5230 5230 5430 5430
Width mm 1530 1530 1610 1610
Height mm 2160 2160 2280 2280
16
Technical parameter
Technical Manual of Oceanair Refrigeration and Air-Conditioning Series Products
OWCCL-D Series Low Temperature Chillers
Main Features of the Chiller
Low temperature type semi-hermitic double screw compressor of famous international brand is adopted, with no leaking, low noisy, slight vibration, stable performance, which can guarantee a long term safety stable operation.
High Efficiency and Energy SavingThe unit can automatically adjust the energy output of each refrigerating compressor and turn on or turn off each
compressor according to the actual requirement and change of the site to ensure the high efficiency operation under low load, avoiding energy (electricity) waste and reducing the energy consumption cost.
Dry-type evaporator is adopted which was equipped with the newest type of internal thread high efficiency heat exchange tube, combining the optimized design of the baffle plate inside the shell, which can improve the heat exchange efficiency greatly. Furthermore, the dry-type evaporator is characterized by safety oil return, which can ensure the compressors operating with safety oil return without any external oil return devices.
Horizontal water cooled hell and tube heat exchanger and high efficiency screw thread heat exchange tube are adopted with high heat exchange efficiency and convenient water side cleaning.
Reliable Refrigerating CircuitThe unit is designed with single compressor independent refrigerating system, and the two system of the double
compressor unit are independent, possessing flexibility in application and good backup characteristics.Famous international brand refrigerating accessories are adopted in refrigerating system, such as expansion
valve, magnetic valve.Famous international brand electrical components are adopted, such as AC contactor, air switch.
Advanced Computer Control System
Advanced micro computer control technology from HongKong Oceanair Industrial Company is adopted, which can provide complete control and protective functions. The LCD controller is in Chinese and easy to handle, and with friendly human and machine interface. The unit can be operated through the touch screen.
One-key startup & shutdown shortcut functionDisplaying the overall operation condition, parameter settings, alarms and records through the screen figuresAuto-timing operation as per the set program, such can be set by day (three phrases) or by weeks, then the
computer will control the units to operate automatically, realizing the unattended operation.It can automatically diagnose and display the faults and has the faults statistic function. The faults can be
inquired in three ways: fault code, fault times, fault occurring time.The computer controller of the unit has the coordinated control function with the chilled water pump and
cooling water pump, which can make the system operate more safely, reliably, and energy-saving, furthermore, the controller can manage the whole water system of the machine room so as to reduce the investment in hardware of the control system of the machine room.
Remote monitoring can be realized through the installation of RS485 communication interface.
Perfect and Reliable Protective Function
The unit is equipped with perfect safety protective devices which can provide all-around safety protection.
Technical Manual of Oceanair Refrigeration and Air-Conditioning Series Products
17
Product overview
Default phase protection, anti-phase protection and overvoltage (under-voltage) protection to the power supply.Overheat protection, overload protection, anti-reverse protection, anti-frequent-start protection, exhaust gas
temperature overheat protection to the motor of the compressor.Protection for too low high-low voltage difference, too high high-voltage, too low low-voltage, start-up delay,
too low water flow, too high (low) circulating water temperature, sensor faults and startup & shutdown code.
Multiple Choices of Refrigerant
R22 refrigerant is applied in standard unit, but other refrigerants can also be applied according to customers’ requirements.
Easy to Install on Site
The evaporator and condenser are equipped with connecting pipe and flange, which make it easy to install on site.
Compact structure of the unit covers small areas.The direction of the pipe connector of the condenser can be changed from right to left and vice versa according
to the on-site requirements.The slight vibration makes the unit need no special vibration isolation measurements to be taken.The unit has pass strict test before leaving the factory, so you only need to connect the pipe, power, and fill
appropriate amount of refrigerant and conduct simple commissioning before it can be put to use.
Note: 1. In accordance with nominal working conditions: water flow in evaporator and condenser is calculated by 5℃ temperature difference
2. Expect for the said specifications, our company also provides non-standard products in accordance with customers’ requirements.
3. Because of technological improvement, exterior dimensions may change, please ask for installation drawing.
Technical Manual of Oceanair Refrigeration and Air-Conditioning Series Products
18
Product overview
Technical Parameters of the OWCCL-D Series Low Temperature Chillers
Model OWCCL- D 60 120 240 360Nominal refrigerating capacity KW 58.5 116.2 232.4 358.4
Single set input power KW 67.7 113.4 113.4 159.6Working medium R22
Compressor
Type Semi-hermetic screw compressorSingle set installed power KW 88 160 160 207
Number Set 1 2Starting mode Y—△
Starting current A 263 545 545 749Maximum operating current A 191 335 670 888
Power supply system 380V/3P/50Hz
Evaporator
Type Shell and tube dry type Leaving water temperature ℃ -35
Refrigerant Calcium chloride water solution 29.4% (mass fraction) Chilled water flow m3/h 12.5 24.8 49.6 111.6
Resistance KPa ≤60Scaling factor of water m2·K/KW 0.018
Standard pressure-bearing MPa 1.0 Connecting pipe size(DN) mm DN65 DN 100 DN125 DN150
Condenser
Type Efficient shell and tube type Entering water
temperature ℃ 30
Cooling water flow m3/h 21.7 39.5 79 170.2Resistance KPa ≤80
Scaling factor of water m2·K/KW 0.044Standard pressure-bearing MPa 1.0Connecting pipe size(DN) mm DN65 DN100 DN125 DN150
Oil cooler
Type Stainless steel brazed plate heat exchangeEntering water temperature ℃ 30
Cooling water flow m3/h 6.40 10.2 20.4 27.6Connecting pipe size(DN) mm DN40 DN 50 DN 65 DN 80
Water side resistance KPa ≤50Scaling factor m2·K/KW 0.044
Economizer Type Stainless steel brazed plate heat exchange
Safeguard High voltage, low voltage, oil pressure difference, low oil level, ultralow temperature, default phrase, anti-phrase and overload
Adjustable range of capacity % 25 startup, 50, 75, 100 12.5 startup, progressively increase to 100 by 12.5
Weight of the unit
Net weight Kg 1332 2010 2700 4960Operating weight Kg 1472 2230 3030 5300
Dimension L×W×H mm 2700×1300×1550 2910×1400×1685 4560×1500×1785 4600×1700×1935
19
Technical parameter
Technical Manual of Oceanair Refrigeration and Air-Conditioning Series Products
Variable Working Condition Correction Factor of Low Temperature Chiller with Dry Type Evaporator
Variable Working Condition Correction Factor of Low Temperature Chiller with Flooded Type Evaporator
Variable Working Condition Correction Factor of Low Temperature Chiller with Evaporative Condenser and Flooded Evaporator
Leaving water temperature of evaporator℃ 0 -5 -10 -15 -20
Leaving
water
temperature
of condenser
℃
30Refrigerating capacity 1.58 1.30 1.07 0.87 0.70
power 1.01 0.96 0.92 0.89 0.85
32Refrigerating capacity 1.54 1.27 1.04 0.84 0.68
power 1.04 0.99 0.95 0.92 0.88
35Refrigerating capacity 1.49 1.23 1.0 0.81 0.65
power 1.09 1.04 1.0 0.97 0.93
37Refrigerating capacity 1.45 1.19 0.97 0.79 0.63
power 1.13 1.08 1.04 1.01 0.97
Leaving water temperature of evaporator℃ 0 -5 -10 -15 -20
Leaving water temperature of condenser
℃
30Refrigerating capacity 1.56 1.29 1.06 0.87 0.70
power 1.01 0.96 0.92 0.89 0.85
32Refrigerating capacity 1.53 1.26 1.04 0.85 0.68
power 1.04 0.99 0.95 0.92 0.88
35Refrigerating capacity 1.48 1.22 1.0 0.81 0.66
power 1.09 1.05 1.0 0.97 0.93
37Refrigerating capacity 1.44 1.19 0.97 0.79 0.64
power 1.13 1.08 1.04 1.01 0.97
Leaving water temperature of evaporator℃ 0 -5 -10 -15 -20
Environment
temperature℃
25Refrigerating capacity 1.63 1.35 1.11 0.91 0.74
power 0.93 0.89 0.85 0.81 0.77
30Refrigerating capacity 1.56 1.29 1.06 0.86 0.70
power 1.01 0.96 0.92 0.88 0.84
35Refrigerating capacity 1.47 1.22 1.00 0.81 0.66
power 1.09 1.04 1.00 0.96 0.92
40Refrigerating capacity 1.39 1.14 0.94 0.76 0.61
power 1.12 1.09 1.05 1.02 0.98
Technical Manual of Oceanair Refrigeration and Air-Conditioning Series Products
20
Correction Factor
Reservedcentre hole
Reservedcentre hole
Ground
Ground
Depth
Depth
Unit foundation
Unit foundation
Outside Drawing of Dry Type Single Head Unit
Outside Drawing of Dry Type Double Head Unit
Specification and Dimension of OWCC-G Series Water Chiller
OWCCL 50G 70G 90G 120G 150G 190G 250G 290G 320G 370G 410G 490G 520G 610G 740G 870G
A 360 360 380 380 420 450 450 450 510 510 510 510 450 450 510 510
E 2030 2030 2030 2230 2230 2530 2730 2830 2930 3130 3330 3530 3530 3530 3930 3930
G 445 445 470 470 495 495 495 515 515 515 515 540 570 570 600 600
F 200 200 200 200 200 200 200 200 200 200 200 300 300 300 300 300
D 575 575 625 625 665 665 665 710 710 750 750 800 860 860 920 920
M 640 670 750 750 800 830 830 830 950 1010 1010 1050 1110 1160 1260 1300
N 150 150 150 150 150 150 150 150 150 150 150 150 150 150 150 150
21
Outline dimensions
Technical Manual of Oceanair Refrigeration and Air-Conditioning Series Products
Reservedcentre hole
Ground
Depth
Unit foundation
Reservedcentre hole
Ground
Depth
Unit foundation
Outside Drawing of Flooded Type Single Head Unit
Outside Drawing of the Flooded Type Double Head Unit
OWCCL 140 160 190 230 280 340 410 480 540 570 620 700 810 890 950 1100
A 260 260 260 260 260 260 730 730 730 780 780 780 820 820 820 820
E 2430 2430 2530 2530 2730 2930 3530 3530 3530 3800 3800 3800 4000 4000 4000 4000
G 140 140 150 150 150 150 150 160 160 160 165 165 165 165 165 165
F 280 280 300 300 300 300 300 330 330 330 350 350 380 380 380 410
D 550 550 600 600 630 630 600 630 630 670 700 700 730 730 730 750
M 980 980 1030 1030 1080 1080 1030 1130 1130 1180 1280 1280 1330 1330 1380 1430
N 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200
B 480 450 480 480 500 530 530 550 550 550 570 570 600 600 600 630
C 280 280 300 300 300 300 330 350 370 370 390 390 400 400 400 420
22
Outline dimensions
Technical Manual of Oceanair Refrigeration and Air-Conditioning Series Products
Reservedcentre hole
Ground
Depth
Unit foundation
Reservedcentre hole
Ground
Depth
Unit foundation
LEA
D
F
NMW
G
H
Outside Drawing of Evaporative Single Head Unit
Outside Drawing of Evaporative Double Head Unit
OWCCL- 150Z 180Z 230Z 280Z 320Z 360Z 420Z 500Z 560Z 590Z 640Z 720Z 840Z 920Z 990Z 1110Z
A 260 260 260 260 260 260 730 730 730 780 780 780 820 820 820 820
E 2430 2430 2530 2530 2730 2930 3530 3530 3530 3800 3800 3800 4000 4000 4000 4000
G 140 140 150 150 150 150 150 160 160 160 165 165 165 165 165 165
F 280 280 300 300 300 300 300 330 330 330 350 350 380 380 380 410
D 550 550 600 600 630 630 600 630 630 670 700 700 730 730 730 750
M 840 840 930 930 930 930 930 1000 1000 1040 1100 1100 1180 1180 1180 1180
N 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200
23
Outline dimensions
Technical Manual of Oceanair Refrigeration and Air-Conditioning Series Products
Project Case Analysis and Comparison
For example, there is a need of 700KW cooling load, and we choose OWCCL-G、OWCCL、OWCCL-Z to make a comparison:
Parameter comparison for model selection:
Initial Investment Comparison
SchemeScheme 1 Scheme 2 Scheme 3
OWCCL-740G OWCCL-700 OWCCL-720Z
Cooling capacity 741.6 KW 695.6KW 722.6KW
Quantity of the principal machine One set One set One set
Specification of the principal machine Q=741.6KW,P=253.2KW Q=695.6KW,P=223.6KW Q=722.6KW,
P=212.2+5.5+8=225.7KW
Cooling water system Cooling water pump(18.5)+Tower fan(7.5)=26KW
Cooling water pump(18.5)+Tower fan(7.5)=26KW
(Included in the principal machine)
Chilled water system and terminals Identical Identical Identical
Total power 253.2+26=279.2KW 223.6+26=249.6KW principal machine225.7KW
Energy efficiency ratio EER=741.6/279.2=2.66 EER=695.6/249.6=2.79 EER=722.6/225.7=3.20
SchemeScheme 1 Scheme 2 Scheme 3
OWCCL-740G OWCCL-700 OWCCL-720Z
Chiller price 664,000 Yuan 688,000 Yuan 825,600 Yuan
Price comparison Surpass scheme one by 24000 Yuan
Surpass scheme one by 161,600 Yuan, and scheme two by 137,600
Yuan
Cooling tower 36,000 Yuan 36,000 Yuan None
Cooling water pump 9000 Yuan 9000Yuan None
Cooling water pipeline, valve, instruments and construction
30,000-50,000 Yuan(depending on the length of the
pipeline)
30,000-50,000 Yuan(depending on the length of the
pipeline)None
Chilled water system and terminals Identical Identical Identical
Power distribution investment Highest Second Lowest
Comprehensive initial investment comparison(exclude
the chilled water system and terminal)
0More initial investment
than scheme1:24,000(power distribution excluded)
More initial investment than scheme 1: 137600-36000-9000-
30000(50000)=62600(42600)Yuan(power
distribution excluded)
Operation Electric Charge Comparison
SchemeScheme 1 Scheme 2 Scheme 3
OWCCL-740G OWCCL-700 OWCCL-720Z
Annual electric charge of the Refrigerating
unit(including the cooling water)
279.2*300*20=1,675,200KW(calculation conditions:300
days operation annual and 20 hours operation daily )
249.6*300*20=1,497,600KW(calculation
conditions:300 days operation annual and 20 hours operation daily)
225.7*300*20=1,354,200KW(calculation conditions:300 days operation
annual and 20 hours operation daily)
Annual electric charge
1,675,200KW×1.0 Yuan=1,675,200 Yuan
(The electricity price is 1.0 Yuan/ kw.h )
1,497,600KW×1.0 Yuan=1,497,600 Yuan(The electricity price is 1.0 Yuan/ kw.h )
1,354,200KW×1.0 Yuan=1,354,200 Yuan(The electricity price is 1.0 Yuan/ kw.h )
Annual saved electric charge 0
The money saved comparing with scheme 1: 1,675,200-
1,497,600=177,600 Yuan (Energy saving rate: 11.86%)
The money saved comparing with scheme 2: 1,497,600-1,354,200=143,400 Yuan (Energy
saving rate: 10.59%)The money saved comparing with scheme 1:1,675,200-1,354,200=321,000 Yuan (Energy
saving rate: 23.7%)
Technical Manual of Oceanair Refrigeration and Air-Conditioning Series Products
24
Analysis and Comparison
Operation Electric Charge Comparison
Scheme OWCCL-740G OWCCL-700 OWCCL-720Z
Whether Refrigerating machine room is
needed?
Special Refrigerating machine room is needed
Special Refrigerating machine room is needed
Special Refrigerating machine room is needed
Environmental protection properties
The cooling tower will produce “water flying” and noise pollution to the surroundings and additional the cooling water pumps produce
more noise.
The cooling tower will produce “water flying” and noise pollution to the surroundings and additional the cooling water pumps produce
more noise.
There is no “water flying” pollution or noise pollution, and the noise level is low without the use of high power
cooling water pump.
System installation
Complicated. The cooling water system has to be installed on site by the construction teams with a lot of
time and high cost. Welding slag and other foreign materials may be left in the cooling water system, affecting the normal operation of the system.
Complicated. The cooling water system has to be installed on site by the construction teams with a lot of
time and high cost. Welding slag and other foreign materials may be left in the cooling water system, affecting the normal operation of the system.
Easy. The installation is easy, excluding the installation and
commissioning of the cooling water system(cooling tower, cooling water pump, pipelines, valves, instruments)
System working condition and service
life.
The service life of the principal machine is about 15 years, and the service life of the cooling tower is
about 10-15 years.
The service life of the principal machine is about 15 years, and the service life of the cooling tower is
about 10-15 years.
The adopted evaporation condensation technology makes the system work stably. The service life of the anti-corrosion high-thermal
conductivity evaporative condenser is up to 15-20 years.
The maintenance of the cooling system
It is easy for the cooling tower to form scale and breed moss and algae which can only be cleaned by chemical that will corrode the
equipments and shorten the service life. A large sum of maintenance
cleaning fee will be cost every year.
It is easy for the cooling tower to form scale and breed moss and algae which can only be cleaned by chemical that will corrode the
equipments and shorten the service life. A large sum of maintenance
cleaning fee will be cost every year.
The evaporative condenser with strong antiseptic treatment is
adopted with a strong anti-scaling property and is easy to clean and
maintain.
After-sale service
The system includes many parts from various of suppliers, which makes the after-sale service relationship
relatively complicated
The system includes many parts from various of suppliers, which makes the after-sale service relationship
relatively complicated
The system is supplied by a sole supplier, which makes the after-sale
service very convenient.
Scheme Summary
After an overall evaluation of the above three schemes, the OWCCL-720Z refrigerating system is adopted as the principal machine, the advantages of which are:
1. The evaporative condensation technology is adopted. The condensing pressure of the unit is low, which decrease the input power of the compressor. The cooling tower and cooling water pump are not needed, reducing the power of mating equipment. All of these improve the energy efficiency ratio of the cooling system and make the system energy-saving.
2. The initial investment is a little larger than that of the OWCCL-740G、OWCCL-700 but the saved operation electric charge is obvious.
Through the comparison of the above schemes, we can see the cooling system adopting the evaporative low temperature cold water unit saves a lot of operating cost, and is the optimal scheme.
Electric charge saved in 15 years 0 The money saved comparing with
scheme 1: 177,600*15=2,664,000 Yuan
The money saved comparing with scheme 2:143,400*15=2,151,000 Yuan
The money saved comparing with scheme 1:321,000*15=4,815,000Yuan
Technical Manual of Oceanair Refrigeration and Air-Conditioning Series Products
25
Analysis and Comparison
The Installation Foundation and Fixation
The unit should be installed on solid, strong and flat concrete foundation or steel frame, and the strength of the installation platform must be sufficient to support the weight of the unit. If the strength is insufficient, vibrations and noises may occur.
The unit base must be so designed that it will not sink. For base dimensions, please refer to the unit base dimension figure (refer to unit dimension parameter table for B and M) .The surface of the concrete base is normally leveled by cement and treated with waterproofing work. The surrounding area of the base platform should be designed with drainage ditch, the gradient of which should be greater than 0.5%, and the slope direction is inclined to the outfall.
Machine Room Design and Construction Summary
1. Machine Room
For convenient operation and maintenance, the main operative interface should have 1-1.5 m space.In the process of operation, the exhaust side and exhaust pipe of the compressor as well as the shell of the
condenser will release heat to the environment as their temperature are higher than that of the environment, thus makes the temperature of the machine room keep rising, worsening the work condition of the unit and the operators, so the machine room have to be equipped with ventilation equipment to make sure the temperature does not go above 35℃。
The machine room should have sound insulation to prevent noisy effect to the environment, if possible, sound absorption structures can be installed to the machine room, what’s more, the main machine and the water pump should not be installed in the same room.
2.Handling of the Unit
Unloading and hoisting must be carried out by hoisting personnel with rich experience.The support feet of the hoist must be stable and will not sink in the hoisting process. Hoisting tools must be
checked before hoisting to make sure breakage or disconnection will not happen. Single steel wire rope should not be used to hoist the unit. Stop for a moment when the unit is hoisted to 20mm above the ground or the surface of the carriage, check carefully to make sure it is safe, and then go on hoisting.
Operate carefully in the process of hoist to avoid damage the equipment. Cushion block should be placed in the contact area between the hoist rope and the unit. For heavy unit, supporting bars should be added to the sling above the unit to reduce the pressure from the sling to the unit.
The unit must be slowly landed to the ground, without any impact to the ground, lest the unit will be harmed.In the process of construction of the machine room, the unit should be prevented from damage from falling
object, and the insulating coat and painting coat should be prevented from scratch. Do not stand or step on the unit.
3.Water System Pipeline
All the outside pipelines of the unit should be supported by holders or hanging brackets, and should not be supported by the unit.
When the static pressure of the water system goes above 30 meters, the water pump should be placed on the
Technical Manual of Oceanair Refrigeration and Air-Conditioning Series Products
26
Construction Summary
water entering side of the unit to reduce the unnecessary pressure to the unit.The entrance side of the unit should be installed with filters no less than 40 mesh (stainless steel filter screen),
the location must make it easy for disassembly.The chilled water pipe must be of thermal insulation to avoid loss of Refrigerating capacity and the forming of
condensation water. The thermal insulated pad or wood pad with antiseptic treatment should be placed between the insulated pipeline and the supporting and hanging bracket.
Automatic or manual air release valve should be fixed at the highest point of the chilled water system;The elastic connection must be made between the pipeline and the pump. The pipeline of the system must pass
strict scrubbing and pressure test.Water segregator, water collector and water pressure balance valve must be installed when multiple units are in
parallel connection.For design of the pipeline please refer to the Design Hand Book of Air Conditioning Planning; for engineering
construction and acceptance, please refer to GB50243—1997 Engineering Construction and Acceptance Standards for Ventilation and Air-conditioning Project.
4.Water Quality Standard
Preparation of the refrigerant water1. For the preparation of ethylene glycol water solution, the ethylene glycol should be specified as the high
quality product in GB4649 Ethylene Glycol for Industrial Use, and the water should meet the requirements in the GB50050 Standards of Industrial Recycling Cooling Water Treatment. The ethylene glycol water solution concentration should meet the requirements. The solution can also be prepared by “Refrigerating air condition dedicated ethylene glycol”. For the preparation of calcium chloride water solution, the calcium chloride dihydrate should be chose as specified as the top quality product in HG/T23279 Calcium Chloride for Industrial Use, and the water should meet the requirements in the GB50050 Treatment Standard of Industrial Recycling Cooling Water. The calcium chloride water solution concentration should meet the requirements.
2. Some foreign materials are included in the ethylene glycol water solution and the calcium chloride water solution, which makes the solution obtain a certain corrosivity. When putting it into use, please add corresponding corrosion inhibitor and scale inhibitor according to the water quality testing result. The inhibitor should also meet the requirements of the water quality in cooling process.
The refrigerant water needs complete water quality analysis regularly. The sampling interval should be determined by the actual water quality condition. The PH of the water solution is 7.5-8.5 and the reserved alkalinity is 16-21;
The ethylene glycol and calcium chloride is poisonous, so please be careful to use ethylene glycol water solution or calcium chloride as refrigerant brine, avoiding leakage, overflowing, splashing or contact with cloth and skin.
Technical Manual of Oceanair Refrigeration and Air-Conditioning Series Products
27
Construction Summary
Thermo-physical properties inquiry table of calcium chloride water solution
Thermo-physical properties inquiry table of ethylene glycol water solution
Concentration(quality percentage %) 9.4 14.7 18.9 20.9 23.8 25.7 27.5 28.5 29.4 29.9
Freezing point(℃) -5.2 -10.2 -15.7 -19.2 -25.7 -31.2 -38.6 -43.6 -50.1 -55
Density in 15℃ 1080 1130 1170 1190 1220 1240 1260 1270 1280 1286
5.Power Supply
The power line and control line should be matched according to the requirements, and the connection should be made according to the electrical connection diagram (operation manual). The unit must have good ground lead. Electric shock accident may happen because of imperfect earth.
Concentration(quality percentage %) 10 15 20 25 30 33 38 41 43 46 49
Freezing point(℃) -3.2 -5.4 -7.8 -10.7 -14.1 -16.2 -20.3 -23.2 -25.3 -28.8 -32.6
Density in 15℃ 1012 1021 1028 1036 1044 1047 1055 1060 1062 1067 1070
Technical Manual of Oceanair Refrigeration and Air-Conditioning Series Products
28
Construction Summary
Ordering Instruction
1.Shipment
The dry type and flooded type unit is shipped as a whole, while the evaporative cooled flooded type unit can be separated into evaporative condenser, unit part and connection pipeline to be shipped separately. If limited by the passageway of the machine room, the dry type and flooded type unit can be divided into evaporator, condenser, compressor and electric cabinet to be shipped separately. After their arriving at the customer’s machine room, our company’ assembling personnel will carry out the assembling with the cooperation from customer in water, electricity and tool supply.
2.Transportation
The transport and insurance can be managed by our company for the customer. If the customers would like to do transport by themselves, please discus with our company in advance to identify the size and number of vehicles.
3.Delivery and Construction Range
tems Our company Customers Notes
Unit
Unit body ○ Including compressor, evaporator, condenser, control panel,
Thermal insulation of evaporator ○
Refrigerant ○ On site filling
Cold water/cooling water flow valve ○
TestOperation manual ○
Leaving factory performance test ○
Transport and
installation
Customer on site commissioning ○ ○
From factory to construction site ○
Foundation construction project ○
From construction site to unit foundation ○
Unit pipeline connection ○
Electrical wiring
Unit installation ○ Main power supply connection
Unit electrical wiring ○
System water temperature sensor wiring ○ Temperature sensor attached to the unit
Unit linkage wiring ○
Others
On site installation of water and electricity supply ○
On site commissioning of water and electricity supply ○
Note: ○ represents the party that is responsible for construction or the provider Maintenance
The maintenance must be carried out by trained and experienced personnel. The protector and controller components have to be checked carefully before the restart of the unit to guarantee a normal system.
In order to maintain a excellent and reliable performance, please carry out correct and regular maintenanceThe heat exchanger will form scale after long term use, which will affect the performance of the unit, so please
clean the heat exchanger regularly according to the conditions.The unit will not be in use for a long term in the winter, so the water in the water system (including the unit)
must be drained completely to avoid water freeze and pipeline crack when the temperature goes under zero degree.
Technical Manual of Oceanair Refrigeration and Air-Conditioning Series Products
29