Technical Notes on Component Selection_2

Embed Size (px)

Citation preview

  • 7/31/2019 Technical Notes on Component Selection_2

    1/2

    TECHNICAL NOTES

    "AN EDUCATED USER WILL HAVE BETTER CHANCE OF ORDERING THE PROPER EQUIPMENT FOR THE JOB"

    The refrigeration process requires work (electrical energy) to pump heat from the low temperature evaporator section that isrejected to the higher temperature ambient from the condenser section. A mechanical refrigerant cycle requires: workingfluid (refrigerant), compressor, condenser, thermal expansion valve (TXV) and evaporator (chiller barrel). Additionallydepending on the design, motor driven fans (blowers) and/or pumps will be required to accomplish heat transfer in theevaporator and condenser sections. Proper design requires an integrated approach to the selection of these components.The compressor must work with the condenser, TXV and evaporator, etc. Special constraints may require the inclusion ofrefrigerant storage devices (accumulators and/or receivers) and additional controls (valves) to meet performancerequirements. Proper design of a Thermal Control System (TCS) requires identification of the system capacity &temperature control desired, ambient conditions (elevation & temperature) and space constraints.

    In the following paragraphs we shall briefly present the basic issues that must be addressed in designing a TCS. Theobjective is to present the reader with an introduction to the subject, rather than to serve as a design manual.

    System Capacity and Temperature Control

    System capacity and desired temperature control must be addressed first in designing a TCS system. Specifying the coolingcapacity required (Btu/hr), temperature level (evaporator) to be controlled and the allowable temperature variation isrequired to size a TCS system. In general, component size will increase directly with capacity and indirectly withtemperature; i.e., for a given capacity, lowering the evaporator temperature will increase the size of components. A myriadof control devices is available to assist the system designer. In general, a good design should utilize only those components

    needed to satisfy specific design conditions. For example, evaporator temperature control can be accomplished through theuse of mechanical or electronic valves depending on the allowable tolerance.

    Ambient Conditions

    Elevation and temperature will affect the performance of motors and air breathing devices, including fans and engines. Forexample, although the air flow rate (in cfm) is the normal parameter used in specifying fan performance, the mass flow rateof air is actually required to accomplish the design objective. Higher elevations, therefore, necessitate the use of biggerfans. Also, specifying the design capacity needed without including the ambient temperature conditions is meaningless. Foran air-cooled condenser, coil size will increase as the ambient temperature increases. For a given evaporator temperature,the compressor size will similarly increase directly \with ambient (head) temperature.

    Space Constraints

    The physical space available can have a direct impact on TCS design and cost. Where space is not a primary concern,components can be selected primarily based on costs. In general, space constraints can be satisfied; e.g. a smaller (facearea) condenser coil can be used, providing a larger condenser fan (>cfm) is employed. Each of these design choices is atradeoff of various parameters; increasing the air flow rate (cfm) of a fan will increase the performance of a coil, at theexpense of additional noise.

    Section 1: Compressor Selection

    The compressor is the "heart" of the refrigeration system. It mechanically compresses the low temperature, low-pressuresuction gas into high temperature, high pressure superheated gas. Saturated conditions exist when a gas and liquid areallowed to stabilize within a confined space at given ambient conditions. At each temperature, an equilibrium condition willbe established between the pressure and temperature. Under saturated conditions, specifying either temperature orpressure, will establish the remaining condition for a known refrigerant. For example, specifying that the refrigerant is R22 ata saturated temperature of 70 degrees F, equates to a working pressure of approximately 122 psig. The correlation betweensaturated pressures and temperatures is presented in various sources (such as ASHRAE Fundamentals). A superheated

    vapor exists when the pressure at a given temperature is raised above saturated conditions. This occurs at the inlet of thecompressor. The refrigerant will be evaporated to a superheated state to assure that liquid is not introduced into thecompressor, as liquid slugging is a common cause of compressor failures. The compressor elevates the low-pressuresuction gas, into high pressure superheated vapor. A refrigerant compressor is a pump designed to work with a gaseousmedia. Depending on the application, compressor designs may be either reciprocating or rotary and of hermetic, semihermetic or open design. Reciprocating compressors contain cylinders and use pistons to compress the refrigerant gas.Rotary compressors use an "eccentric" cam type action to compress the refrigerant and push it from the low-pressure sideof the cycle to the high-pressure side. Hermetic compressors contain both the electric motor and the mechanicalcomponents within a single sealed housing. Repairs are normally only accomplished at a factory equipped to open the shelland replace worn or damaged parts. The refrigerant flow through the compressor is used to cool the electric motor. Semi-hermetic compressors also contain both the electric motor and mechanical elements within a single housing, but permitaccess to major components, permitting minor field repairs. Major re-builds are generally accomplished off site at a facility

  • 7/31/2019 Technical Notes on Component Selection_2

    2/2

    set up for this operation. Open drive compressors separate the prime driver (electric motor, gas engine, etc.) from thecompressor. A shaft connects the mechanical compressor components to the prime driver, which may be coupled directly orvia belts. Semi hermetic and hermetic compressors contain an integral motor, while the open drive compressor simplycontains the compressor mechanical components (e.g., cylinders, pistons and housing) and requires a shaft to connect tothe prime driver. The shaft contains a seal that must be maintained in a "wet" state in order to avoid refrigerant leaks. It isnormally required that an open drive system not be idle for an extended period of time to avoid drying out the seal andcausing refrigerant leaks.

    2. Condenser

    The hot, superheated gas exiting the compressor is condensed into a high-pressure liquid in the condenser section. This isaccomplished either by an air cooled condenser finned tube coil, or a shell and tube barrel. In either, design, the coolantmedia (air, water or other fluid) extracts heat from the refrigerant, causing it to condense from a high pressure, hightemperature superheated vapor into a high pressure, high temperature sub cooled liquid. The condenser rejects theevaporator load, the compressor heat of rejection and the condenser fan (motor load) in the case of a pusher system. In anair-cooled design, the ambient air is pushed (or pulled) through the coil. This is accomplished either via a propeller type fanor blower, depending on the flow rate and pressure drop; higher flow rates (cfm) and larger pressure drops require blowersrather than fans. Convective heat transfer and the associated laws drive the heat transfer from the hot refrigerant gas to thehigh temperature ambient. In a liquid cooled design, a pump is required to pump the cooling media (such as water) throughthe condenser heat exchanger. The system heat may ultimately be rejected via a cooling tower or chiller system. Coil sizesare directly effected by allowable airflow rates (cfm) and system pressure drops. Smaller face area coils are possible withlarger flow rates (cfm), at the expense of larger pressure drops (requiring bigger fans or larger motors). Proper coil selectionrequires balancing the allowable face area of the coil (size) with the flow rate (cfm) and pressure drop allowable to achieve

    the desired performance.

    3. Thermo Expansion Valve (TXV)

    The high temperature, high-pressure liquid must be expanded into a low pressure, low temperature fluid to perform therefrigeration effect. A thermal expansion device may be accomplished via a simple capillary type tube, or a TXV. Expansionof the liquid leaving the compressor can be accomplished simply by passing the refrigerant through a tube of restricteddiameter (capillary tube). The added pressure drop causes the high temperature, high-pressure vapor to "flash to a lowtemperature low pressure fluid. The liquid/vapor refrigerant leaving the expansion device is a mixture, primarily composed ofliquid. A capillary tube system is primarily used on smaller systems, where the refrigerant load is fairly constant. For bettercontrol and on larger systems, a TXV valve is normally used. The valve may be designed to sense both the pressure andtemperature of the gas leaving the evaporator to assure that cooling is accomplished and that the compressor sees purevapor.

    4. Evaporator

    The refrigerant mixture is transformed into a superheated vapor in the evaporator. This may be accomplished either byan air-cooled finned tube coil, or a shell and tube barrel. In either, design, the coolant media (air, water or other fluid)the refrigerant extracts heat from the air, causing it to evaporate from a primarily liquid state into a superheated vapor.The evaporator absorbs the refrigerant load and in the case of a pusher type evaporator blower, the motor load. In anair-cooled design, the ambient air is pushed (or pulled) through the coil. This is usually accomplished via a blower, toprovide adequate head to overcome the coil resistance and the system pressure drop. Convective heat transfer and theassociated laws drive the heat transfer from the hot refrigerant gas to the high temperature ambient. In a liquid cooleddesign, a pump is required to pump the cooling media (such as water) through the evaporator heat exchanger (shell &tube, or chiller barrel). In an ideal system, the refrigerant would be transformed from a liquid vapor mixture into asaturated vapor at the exit of the evaporator. However, in order to assure complete evaporation and primarily to protectthe compressor, the refrigerant is transformed into a superheated vapor at the exit of the evaporator. Coil sizes aredirectly affected by allowable airflow rates (cfm) and system pressure drops. Smaller face area coils are possible withlarger flow rates (cfm), at the expense of larger pressure drops (requiring bigger fans or larger motors). Proper coilselection requires balancing the allowable face area of the coil (size) with the flow rate (cfm) and pressure drop

    allowable to achieve the desired performance.