Technical Specifcation of Electrical Materials

Embed Size (px)

DESCRIPTION

Technical Specification of Electrical Materials

Citation preview

  • .

    TECHNICAL SPECIFICATION

    OF

    ELECTRICAL MATERIALS

    (AB SWITCH, HG FUSE AND DO FUSE)

    GROUP I & J

  • Details of require materials:

    Sl No Item Description Unit Quantity

    1 3 Pole 11kv 200A A B Switch (H) Set 1954

    2 3 Pole 11kv 200A H.G. Fuse Set 1829

    3 2 Pole 11kv 200A A B Switch (H) Set 250

    4 2 Pole 11kv 200A H.G. Fuse Set 250

    5 3 Pole 11kv 400A A B Switch (H) Set 250

    6 3 Pole 11kv 200A DO Fuse Set 625

    7 2 Pole 11kv 200A DO Fuse Set 625

    8 3 Pole 33kv 200A A B Switch (H) Set 150

    9 3 Pole 33kv 200A H.G. Fuse Set 150

    10 3 Pole 33kv 400A A B Switch (H) Set 150

    11 3 Pole 33kv 400A H.G. Fuse Set 150

    NB: 1. Bidders should put their authorized signature with office seal on each page of

    the documents.

    2. Bidders should put their offer in the Guaranteed particulars column furnished

    in the tender documents.

    3. Purchaser may ask to the bidder who will qualify in Techno- Commercial

    evaluation of the tenders for submission of Samples for verification , if

    required.

    4. Purchaser reserves the right to increase or decrease the above quantities

    during placement of purchase order or may cancel any item/items without

    assigning any reason thereof . Dy. General Manager (C&P) NESCO, Balasore, Odisha

  • 11 KV 200 Amp 3 Pole AB Switch

    Technical Specification 01.0 Scope: -

    This specification covers manufacturing testing and supply of 11KV 200 Amps 50HZ Air Break switches for outdoor installation in horizontal configuration. The switches are suitable for operation under off load conditions only and are intended for use on Distribution Sub stations and tapping sectionalizing points of 11 KV lines.

    02.0 Description of the materials: -

    The 11KV A.B. Switch sets shall confirm to the following parameters: -

    a. Number of poles 3 b. Number of Post insulator per pole 2nos12KVpostinsulator. c. Nominal system voltage 11KV d. Highest system voltage 12KV e. Rated frequency 50Hz f. System earthling effectively earthed. g. Rated nominal current 200 amps h. Altitude of installation Not exceeding1000M

    The post insulators used in the A.B. Switches shall have the following ratings :-

    a. Power frequency withstand voltage (dry) 35KV (RMS) b. Power frequency withstand voltage(wet) 35KV (RMS) c. Implies withstand voltage(dry) 75KV d. Power frequency puncture withstand 1.3

    03.0 Standards: -

    The AB Switch Set shall conform to the following standards: -

    a. IS-9920 (Part-I to V) b. IS-2544/1973 (for porcelain post insulators) c. IS-2633, (for galvanization of ferrous parts.) or its latest amendments if any.

    04.0 Insulator make: -

    12KV post insulators complete with post and cap duly cemented to be used in the AB Switch Set conforming to IS-2544/1973.

    The bidder shall furnish the type test certificate of the post insulators from their manufacturer for reference and scrutiny.

    The bidder shall mention make, type of insulation materials, metal fittings, Creepage distance, protected Creepage distance, tensile Strength, compressing strength, torsion strength and cantilever strength.

  • 05.0 Climatic condition: -

    The A.B. Switch set shall be suitable for operation under the following climatic conditions.

    a. Maximum ambient air temperature 45 o C

    b. Maximum daily average air temperature 35 o C

    c. Maximum yearly average ambient air temperature 30 o C d. Maximum temperature attainably by a body e. Exposed to the Sum. 50 o C

    f. Minimum ambient air temperature 0 o C

    g. Maximum relative humidity 100% h. Minimum number of rainy days per annum 70 i. Average number of rainy days per annum 120 j. Average annual rain fall 150cm. k. Number of months of tropical monsoon conditions 4 l. Maximum wind pressure 260Kg./mm2 m. Degree of exposure to atmospheric pollution normally n. Atmosphere. Polluted.

    06.0 Other technical details: -

    06.01 General: - The 11KV A.B. Switch Set shall be the gang operated rotating single air

    break type having 2 post insulators per phase. The operating mechanism shall be suitable for manual operation from the ground level and shall be so designed that all the three phases shall open or close simultaneously. The Switches shall be robust in construction, easy in operation and shall be protected against over travel or staining that might adversely affect any of its parts. The required base M.S. Channel (hot dip galvanized) phase coupling rod, operation rod with intermediate guide braided with flexible electrolytic copper, tail piece of required current carrying capacity and operation mechanism with ON & OFF positions shall be provided. The operation rod shall be medium gage of 32mm diameter nominal bore G.I. pipe single length 6 meters. The phase coupling rod for gang operation shall be of medium gauge 25mm dia &2100 mm length nominal bore G.I. pipe. The Rating post insulators shall be provide with suitable bearing mounted on a base channel with 8mm dia thrust collar and 6mm split pin made out of stainless steel. The operating down rod shall be coupled to the spindle (minimum dia 32mm) for gang operation through another suitable bearing by two numbers 10mm dia stainless steel bolts with double nuts. All the bearings shall be provided with grease nipple. All metal (ferrous) parts shall be galvanized an polished. The pipe shall be galvanized in accordance with IS-4736/1968.The post insulators should be fixed with the base channel using Galvanized Nuts and Bolts.

    06.02. Mounting:- The A.B. Switches shall be suitable for horizontal mounting in double pole sub-station structures. MS Galvanized base Channel & base support channel should be of min. size 75x40x6 mm.

    06.03. Switching Blades: - It shall be made out of electricity copper with silver plated.

    The approximate size shall be 220mm X 35X 6mm. The Switch shall have such a spring mechanism so as to ensure that the speed of the opening of contact is independent of speed of manual operation.

  • 06.04 Fixed Contacts: - The Fixed Jaw type female contacts o f s ize (70x35x6) mm shall be made of electrolytic copper (minimum 95% copper composition) duly silver coated controlled by phosphorous bronze high pressure spring housed in robust G.I. Cover. It is essential that provision shall be made in fixed female contracts to take the shock arising from the closing of move contract blade without the same being transmitted to the post insulator. The arrangement made in this regard shall be specifically shown in the drawing.

    06.05 Arcing Horn: - As the switches are generally meant for isolating transmission line

    and distribution transformers, suitable arcing horns shall be provided for breaking the charging current horn shall be made of 8 mm dia G.I. Rod with spring assisted operation.

    06.06 Terminal Connectors: - Terminal connectors shall be robust in design. The size of

    fixed connector shall be (65 X 35 X 6 mm) and size of movable connector shall be of (65 X 35) X (65 X 35) X 6mm of copper casting with uniform machine finishing duly silver plated made out of minimum 95% copper composition with 2 nos. 12mm dia holes provided with suitable brass bolts and double nuts, flat washers & 2nos.

    bimetallic solder less sockets suitable up to 55 mm2 conductor. 06.07Spacing: - The minimum clearance between phases to the switch shall be

    760mm. The operation down rod shall be at a transverse distance of 300mm from the outer limb of the switch. The centre spacing between two post insulators of the same phase shall be 380 mm. In the open position of the A.B. switches the moving blade shall rotate through 90 o. This shall be exhibited in the drawing.

    06.08 Sample, Drawing & Literatures: - Three copies of drawings of 11KV 200 Amps. A.B. Switch shall be furnished along with the tender. Technically successful bidder is to be asked for submission of Sample for verification.

    06.09 The details of construction and materials of different parts of the A.B. Switch shall clearly

    be indicate in the tender and illustrative pamphlet / literature for the same shall be submitted along with the tender.

    07.0 TEST & TEST CERTIFICATE: -

    07.01 Type Test: - Certificate for the following type tests conducted on a prototype set of A.B.

    Switch in a NABL approved test house/CPRI shall have to be submitted along with offer.

    Dielectric Test (impulse and one minute were power frequency withstand voltage test.)

    Temperature rise test (for contracts and terminals)

    Shorts Time current and peak withstand current test.

    Mainly active load breaking capacity test.

    Transformer off-load breaking capacity test.

    Line charging breaking capacity test.

    Cable charging breaking test.

    Operation and mechanical endurance test.

  • Mechanical strength test for post insulator, as per IS-2444/1937 shall be furnished.

    Test for galvanization of metal (ferrous) parts.

    07.02 Routine /Acceptance Test: -

    The inspection may be carried out by the Purchaser at any stage of manufacture. The successful bidder shall grant free access to the Purchasers representative at a

    reasonable time when the work is in progress. The following routine tests shall have to be conducted on each set and results are to be furnished for consideration of deputing inspecting officer for inspection and conduction testing of the materials at the works of the manufacturer. the supplier shall give fifteen days advance intimation to the Purchaser to enable him to depute his representative for witnessing the tests.

    1. Power frequency voltage dry test. 2. Measurement of resistance of main circuit. 3. Tests to prove satisfactory operation. 4. Dimension Check 5. Galvanization test. 6. Operational test.

    08.00 Guaranteed Technical Particulars: -

    The bidder shall furnish the guaranteed technical particular duly filled in the format along with the tender.

    09.0 Completeness of Equipment: -

    All fittings, accessories of apparatus which may not have been specifically mentioned in this specification but which are usual or necessary in equipment of similar plat shall be deemed to be included in the specification and shall be supplied by the Tender without extra charge. All plant and equipment shall be completed in all details whether such details are mentioned in the specification or not.

  • 11 KV 200 Amp 2 / 3 Pole AB Switch

    Guaranteed Technical Particulars

    Sl. No

    Particulars

    Requirement

    Bidders offer

    2 pole 3 pole

    1 Makers name & Address To be specified by the bidder

    2 Type of Switch Rotating Type

    3 Suitable for mounting Horizontal only

    4 No. of Breakers per phase Single Break

    5 No. of Post Insulators per

    phase

    2nos. of 12KV Post Insulators as per

    IS:2544/73 per phase

    6

    (a)

    Post Insulators

    Makers Name &

    Country of Manufacture of

    Post Insulator

    To be specified by the bidder as per CPRI Test Report

    (b) Type of cementing Original Cementing. The insulator to

    be cemented with MCI (Hot dip

    galvanised /Al Alloy cap and

    MCI/Forged steel hot deep

    galvanized pedestral) as per IS:

    2544/1973

    (c) Power frequency withstand

    voltage (Dry)

    35 KV RMS

    (d) One minute Power

    frequency withstand

    voltage (wet)

    35 KV RMS

    (e) Visible discharge voltage 9KV RMS

    (f) Dry flash over voltage 85 KV

    (g) Power frequency puncture

    withstand voltage

    1.3 times of actual dry flash over voltage

    (h) Creapage distance 320 mm minimum (ISS-2544/1973 & relevant IEC)

    (7) Impulse withstand

    voltage for positive &

    negative polarity

    (1.2/50 micro second wave)

  • (a) Across the isolating distance

    85KV Peak

    (b) To earth & between poles 75KV Peak

    8 Rated one minute

    Power frequency

    withstand voltage

    (a) Across the Isolating

    distance

    32KV(RMS)

    (b) To earth & between poles 28KV(RMS)

    9(a) Rated voltage nominal/

    maximum

    11/12KV

    (b) Rated normal current and

    rated frequency

    200 Amps. 50hz

    10 Rated short-circuit

    making capacity

    25KA (Peak)

    11 Rated Short-time current 10KA

    12 Rated peak withstand current 40KA

    13 Rated mainly active load

    breaking capacity

    200 Amp.(RMS)

    14 Rated Transformer off load

    breaking capacity

    6.3 Amp.(RMS)

    15 Rated line charging breaking

    capacity

    2.5 Amp(RMS)

    16 Minimum clearance

    between adjacent phase

    (a) Switch closed (center to

    center)

    760mm

    (b) Switch opened (Center of

    post insulator to the edge

    of the blade)

    380mm

    17 Temperature rise The

    Temperature rise should

    not exceed the maximum

    limit to 65o

    C at an ambient

    temperature not

    exceeding 40oC

    650C

  • Copper contacts silver faced

    terminal of switch intended to

    be conducted to external

    conductor by bolts or screws

    at an ambient temperature

    should not exceed.

    50o

    C

    18 Vertical clearance from

    top of insulator cap to

    mounting channel.

    254 mm

    19 Type of contact a) Self aligned high pressure jaw type fixed contacts of electrolytic copper of size

    70 mm x 35mm x 6 mm duly

    silver plated .Each contact

    should be riveted with three

    nos. copper rivets with a bunch

    ( minimum 3 mm thick) of

    copper strips /foil each may

    vary from 0.15 mm to 0.25 mm

    to and total thickness of copper

    foil per jaw should be 6 mm .

    Jaw assembles are to be bolted

    through brass bolts and nuts

    with spring washer.

    b) Solid rectangular blade type

    moving contact of electrolytic

    copper of size 35 mm X 6 mm

    and length 220 mm duly silver

    plated ensuring a minimum

    deposit of silver 10 micron on

    copper contacts or as may be

    prescribed under relevant ISS /

    IEC .

    c) Pressure springs are to be used

    in each jaw contacts should be

    phosphorous bronze having

    8nos. of turns X28mm heights X14.4mm diameter with 14

    SWG wire .

  • 17 Connectors:- Terminal connectors for both

    movable and fixed should be of

    copper flat of same size similar to

    that of moving contact blades

    (minimum 95% copper

    composition). The fixed connector

    shall of size 65 mm x 35 mm x 6 mm

    and the size of movable connector

    shall be size (65 X 35) X (65 X

    35) X 6mm with machine finishing

    duly silver plated with 2 nos. 12mm

    dia holes provided with suitable

    brass bolts and double nuts, flat

    washers & 2nos. bimetallic solder

    less sockets suitable upto 55 mm

    conductor.

    18 Moving contact supporting

    angle

    Moving contact is to be supported by G.I angle of size 45x45x5 mm on each phase and the moving contact are to be bolted through 2 nos. stainless steel bolts and nuts with suitable stainless steel flat and spring washers.

    19 Galvanization

    a) Iron parts shall be hot dip

    galvanized as per IS-

    2633/1972.(Latest Amendment) ,

    IS :2629/1985 (1st

    . Revision),

    b) The pipe shall be galvanized as

    per IS-4736/1968.(Latest

    Amendment)

    20 (a)

    Phase Coupling Rod 25mm nominal bore G.I. Pipe (Medium gause)

    (b) Operating Rod ISI mark 32mm nominal bore G.I. Pipe (Medium gause) 6 mtr. long

    Normal Outside Dia. in

    mm

    Wall

    thickness

    Max. Min.

    25 mm 34.2 33.3 3.25 32 mm 49.9 42 3.25

    (c) Arcing Horn 8 mm dia G.I. rod with spring assisted operation.

    (d) Force of fixed contact spring 50lbs to 75 lbs

  • (f) Bearings 4 nos. self lubricated bearing to be provided with grease nipple including 4th bearing being a axial thrust bearing.

    (g) Locking Arrangement Pad Lock and key arrangement at both ON & OFF position..

    (h) Earth terminal Provided at base channel at opposite ends.

    (i) Copper braided flexible tapes

    320mm long 2no. tin coated

    copper braided flexible tape

    both end seated with cupper

    sheets duly punched for

    fixing having minimum

    weight of 450 grams per

    meter without sockets.

    (j) Quick break device Lever mechanism

    (k) T connector The T connector provided on the channel having Moving

    Contact shall be of G.I Nut &

    Bolt at the bottom end to

    facilitate replacement of this unit

    only during requirement and

    avoid entire change of the arm.

    l) I-Bolt The I-Bolt shall be longer with 75 mm thread.

    21 Supporting Channel 75mmx40mmx 6mm M.S.Channel. (Hot dip galvanized)

    22 Weight of each pole 20 Kg (Approximately) ( to be specified by bidder)

    23 Detailed drawing submitted ? To be provided by bidders

    N.B i) Ferrous parts shall be duly galvanized as per IS :2629/1985 (1st

    . Revision),

    (Amendment-2) and non-ferrous parts shall be silver plated.

    ii) The G.I pipes and rods shall be galvanized as per IS:4736/1968 (1st

    . Revision),

    (Amendment-1) for hot-dipped zinc coating on M.S. Tube.

    iii) Certificate from a Government approved laboratory regarding composition of copper in

    electrolytic copper casting of materials should be submitted during inspection of materials at the

    cost of tenderer.

    iv) Items not covered in the G.T.P, but relevant in Design, manufacturing, quality control

    & testing of materials shall be governed by the relevant IS with latest Amendment.

  • 11 KV 200 Amp 3 Pole HG Fuse

    Technical Specifications

    1. SCOPE:- This specification covers the manufacture, testing and supply of 11 3 pole 200A H.G. Fuse Sets.

    2. (a) The 11 KV H.G. Fuses shall be suitable for out door operation in

    horizontal configuration under the climatic conditions specified. It shall be of

    the following ratings:-

    1 Number of Poles 3 2 No.of Insulator per Pole 2 nos. 12 KV post Insulators 3 Nominal system Voltage 11 KV 4 Highest System of Voltage 12 KV 5 Rated frequency 50 Hz 6 System Frequency Effectively earthed 7 Rated normal current 200 Amps 8 Altitudes of installation Not exceeding 1000 M.

    (b) The post insulator used in the H.G. Fuse set shall have the following ratings :-

    1 Power frequency withstand voltage (dry) 33 KV (RMS) 2 Power frequency withstand voltage (wet) 35 KV (RMS) 3 Impulse withstand voltage (dry) 75 KV (Peak) 4 Power frequency withstand voltage 1.3 times the actual dry

    flashover voltage of the unit

    3. STANDARDS :-

    The H.G. Fuse set shall confirm to the following standards.

    IS- 9385-1980 ( for high voltage expulsion fuses and similar fuses).

    IS- 2544-1973 ( for porecelain post insulators or its latest amendments if any.). IS-

    2633-1979 ( for Galvanisation of ferrous parts).

    4. INSULATOR MAKE :- 12 KV post insulator complete with pedestal cap

    duly cemented to be used in 11 KV H.G. Fuse sets confirming to IS-2544/1973.

    5. TECHNICAL DETAILS :- The H.G. Fuses shall have adjustable arcing

    horns made of solid copper rod having 7.62 mm dia. The horns shall be

    fitted with screwing devices with flynuts for fixing and tightening the fuse

    wire. It shall have robust terminal connectors of size 80 mm x 50 mm x 6 mm

    made of copper casting (95 % minimum copper composition) duly silver plated

    with two numbers of 12 mm dia brass bolts and double nuts with flat

  • brass washers. The connectors should be capable of connecting crimpable

    conductor upto 80 Sq. mm size( ACSR/ Alloy) with bimetallic solderless

    sockets. The H.G Fuse Set shall suitable for horizontal mounting on sub-

    station structures. The minimum clearance between the adjacent phases of the

    fuse set shall be 760 mm and the centre to centre (distance between two post

    insulators of the same phase) shall be 410 mm. All metal (ferrous) parts shall be

    galvanized and polished. Only 12 KV post insulator ( orginal cemented and not

    pin insulators shall be used for the H.G. Fuse Set.

    6. CLIMATIC CONDITIONS :- The H.G. fuse set shall be suitable for

    operation under the following climatic conditions.:-

    1 Maximum ambient air temperature 450 C 2 Maximum daily average air temperature 350 C

    3

    Maximum yearly average ambient air temperature

    300 C 4 Maximum temperature attainable by a body

    exposed to the sun. 500 C

    5 Minimum ambient air temperature 00 C 6 Maximum relative humidity 100% 7 Average number of thunderstorm days per annum 70 days 8 Average number of rainy days per annum 120 9 Average annual rain fall. 150CM 10 Number of months of tropical monsoon conditions 4 11 Maximum wind pressure 260 Kg/mm 12 Degree of exposure to atmospheric pollution. Normally polluted

    atmosphere.

    7 Type Test :-

    Certificate for the following type tests conducted on a prototype set of HG Fuse in a NABL approved test house/CPRI shall have to be submitted along with offer.

    i) Dielectric test (impulse & one minute wet power frequency withstand voltage test.)

    ii) Temperature rise test ( for terminals) iii) Mechanical strength test for the post of insulator as per IS-2544/1973 iv) Test for galvanization of metal (ferrous) parts.

    8. ROUTINE/ACEPTANCE TESTS :-

    The inspection may be carried out by the Purchaser at any stage of manufacture.

    The successful bidder shall grant free access to the Purchasers

    representative at a reasonable time when the work is in progress. The following

    routine tests shall have to be conducted on each set and results are to be

    furnished for consideration of deputing inspecting officer for inspection and

    conduction testing of the materials at the works of the manufacturer. the

    supplier shall give fifteen days advance intimation to the

    Purchaser to enable him to depute his representative for

    witnessing the tests.

  • i) Power frequency voltage dry test

    ii) Dimension Check

    iii) Galvanisation test.

    9. Guaranteed Technical Particulars :

    The bidders are required to furnish the guaranteed technical particulars duly filed in

    the proforma along with the bid.

    10. Completeness of Equipment :

    Any fittings accessories or apparatus which may not have been

    specifically mentioned in this specification but which are usually necessary in

    equipment of similar plant shall be deemed to be included in the

    specification and shall be supplied by the bidder without extra

    charge. All plant and equipment shall be complete in all details whether such

    details are mentioned in the specification or not.

    11. Inspection :

    Routine and acceptance test shall be conducted at the place of manufacturer.

    The bidders are requested to furnish details of equipments which will be used

    for testing along with the bid. The bids of these manufacturers who do not

    have adequate testing facilities for conducting routine and acceptance test are

    liable for cancellation. The successful bidder has to furnish routine test certificate

    and guarantee certificate for each consignment of materials to be inspected at

    the time of offer of materials for inspection.

  • GUARANTEED TECHNICAL PARTICULARS OF 11 KV 200Amp.

    HG Fuse ( 2 / 3 pole)

    Sl.

    No

    Particulars

    Requirement

    Bidders offer

    11 KV 200 Amps.2/ 3 pole H.G

    Fuse.

    2 Pole 3 Pole

    1 Makers name & Address To be specified by the bidder

    2 Operating voltage 11 KV

    3 No. of Post Insulators per phase

    2 nos. of 12 KV Post Insulators per

    phase as per ISS:2544/1973

    4 Rated normal current &

    normal frequency

    200 Amp., 50 Hz

    5 Vertical clearance from the top of insulator to

    mounting channel

    254 mm (minimum)

    6 Height of the riser for carrying the horn.

    150 mm from the cap top of

    insulator

    7

    (a)

    Post Insulators :

    Makers Name & Country of Manufacture of Post Insulator

    To be specified by the bidder ( as per

    CPRI Test Report).

    (b) Type of cementing Original Cementing only as per IS:

    2544/1973 & relevant IEC.

    (c) 1 minute Power

    frequency withstand

    voltage (Dry)

    35KV RMS

    (d) 1 minute Power

    frequency withstand

    voltage (wet)

    35KV RMS

    (e) Visible discharge voltage 9KV RMS

    (f) Dry flash over voltage 85 KV RMS

    (g) Power frequency puncture withstand voltage

    1.3 times of actual dry flash over

    voltage (110 KV) .

    (h) Creapage distance 320 mm (minimum). Actual

    creepage distance for which type

    test has been conducted is to be

    supplied.

    8. Impulse withstand voltage for positive & negative polarity

    (1.2/50 micro second wave)

    (a) Across the isolating distance 85KV (Peak)

    (b) To earth & between poles 75KV (Peak)

    9. One minute Power frequency withstand voltage

    (a) Across the Isolating distance 32KV(RMS)

    (b) To earth & between poles 28KV(RMS)

  • 10 Details of Arcing Horn 1 SWG (7.62 mm) dia. solid copper rod silver plated provided with screwing

    arrangement on the fuse carrier made of

    copper casting for fixing fuse wire (Total

    length -635 mm). All the bolts, Nuts and

    washers should be made out of Brass.

    11 Riser Unit (150 mm height total)

    a) Riser cum Connector made out of

    copper casting (with minimum 95%

    copper composition having riser size (80

    mm height x30mm width x8 mm

    thickness) and connector of size (80

    mmx50mmx 8mm) duly silver plated

    and machine finishing provided with 2

    nios.12 mm dia. brass bolts and double

    brass nuts with flat brass washers and 2

    nos. solderless bimetallic socket per each

    connector suitable upto 80

    mmconductor.

    b) 100 mm height G.I Riser made of 19 mm nominal bore medium gauge G.I

    pipe welded with 2 nos. of G.I flat of

    30mmx5mm of both ends fixed with

    10mm dia. stainless steel bolts and nuts

    with flat & stainless steel spring washer.

    13. Galvanization a) All ferrous parts shall be hot-

    dipped Galvanized as per

    IS.2633/1972 (Latest Amendment) , IS

    :2629/1985 (1st

    . Revision),& all non-

    ferrous parts shouldbe duly electroplated

    with silver.

    14 Supporting Channel 75mmx40mmx6mm M.S.Channel. (Hot dip galvanized)

    15 Weight of each pole 16 Kg (Approx.)To be specified by the Bidder

    16 Detailed drawing submitted ? To be provided by bidders

    N.B i) Ferrous parts shall be duly galvanized as per IS :2629/1985(1st. Revision),

    (Amendment-2) and non-ferrous parts shall be silver plated.

    ii) Certificate from a Government approved laboratory(NABL accredited) regarding composition of copper in electrolytic copper casting of materials should be submitted during

    inspection of materials at the cost of Bidder.

    iii) Type Test Certificate : The type test certificate , conducted within five years , preceding to date of opening of the tender from Govt. testing laboratory (NABL accredited / CPRI) shall be

    furnished.

  • 33KV 3 Pole 200 Amp AB Switch (Horizontal Type)

    Type Test: - Certificate for the following type tests conducted (within five years proceeding to the date of opening of the tender)on a prototype set of A.B. Switch in a NABL approved test house/CPRI shall have to be submitted along with offer

    GUARANTEED TECHNICAL PARTICULARS Slno. Description Specified Bidders

    Offer

    1 Maker's name and Country of origin. 2 Type of Switches Rotating type only. 3 Suitable for mounting. Horizontal only.

    4 Number of support post Insulator per phase

    4 Nos. 22 Kv/24 Kv post Insulators per phase as per IS : 2544/1973.

    5 POST INSULATOR

    (a) Maker's name and Country of origin. Reputed make. All the post insulators provided shall be of same make.

    (b) Type of Cementing. Original Cementing only.

    (c) One minute power frequency withstand voltage dry.

    95 Kv (rms)

    (d) One minute power frequency withstand voltage wet.

    75 Kv (rms)

    (e) Visible Discharge voltage. 27 Kv (rms)

    (f) Dry flash over voltage. 95 Kv.

    (g) Power frequency puncture withstand voltage.

    1.3 times of actual dry flash over voltage.

    (h) Impulse withstand voltage (Switch in position)

    170 Kv (Peak)

    (i) Creepage distance. 430 mm. However, t he actual creepage d i s t a n c e f o r which type test has been conducted is to be supplied.

    6 Impulse withstand voltage for positive & negative polarity (1.2/50 micro second wave)

    (a) Across the Isolating distance. 195 Kv (Peak) (b) To earth and between polles 170 Kv (Peak)

    7 Rated one minute power frequency withstand Voltage.

    (a) Across the Isolating distance. 80 Kv (rms) (b) To earth and between polles 70 Kv (rms)

    8 Rated normal current and rated frequency.

    400 Amps. 50 Hz.

    9 Rated short time current. 16 KA (rms) 10 Rated peak withstand current. 40 KA (Peak) 11 Rated transformer off load breaking

    capacity. 6.3 A (rms)

    12 Rated line charging breaking capacity. 6.3 A (rms) 13 Rated cable charging breaking capacity. 16 A (rms) 14 Minimum clearance between adjacent

    phases.

    (a) Switch closed (Centre to Centre) 1200 mm

    (b) Switch opened (Centre of post Insulator to the edge of the blade)

    640 mm

    15 TEMPERATURE RISE.

    The temperatyure rise should not exceed to 650C

  • maximum limit as specified below at an

    ambient temperature not exceeding

    400C.

    Copper contacts silver faced terminal of switch intended to be conducted to external

    conductor by bolts or screws at an

    ambient temperature should not exceed

    500C

    16 Vertical clearance from the top of

    Insulator cap to mounting channel

    508 mm. Minimum.

    17

    Type of Contact

    (a) Self-aligned, high pressure jaw type fix contacts

    of electrolytic copper of size 80 x 50 x 8 mm duely

    silver plated. Each contact should be rivetted with

    three nos. copper rivets with a bunch ( minimum

    3 mm thick) consisting of copper foils may vary

    from 0.15 mm to 0.25 mm ( total thickness of

    copper foil per jaw shallbe 6 mm). Jaw assembles

    are to be bolted through brass bolts and nuts

    with brass flat and spring washer.

    (b) Solid rectangular blade type moving contact

    of electrolytic copper size 220 mm x 50 mm x 8

    mm duly silver plated.

    (c ) Pressure springs to be used in Jaw contacts should be phosphorous bronze having 8 nos. of turns x 28 mm height x 14.4 mm dia. With 14 SWG wire (Minimum 6 nos. spring shall be used)

    18

    Terminal Connector.

    Terminal connector for both movable and fixed should be of copper casting (minimum 95 % copper composition). The fixed connector shall be of size (80 x 50) x 8 mm and the size of the movable connector (80 x 50) x (80 x 50) x 8mm with machine finishing duely silver plated with 2 nos. 12mm dia. hole with suitable brass bolts and double nuts with brass flat washers and 2 nos. solerless bimettalic sockets per each connector suitable upto 80 mm2 conductor. The sockets shall be preferably of "USHA MARTIN" make.

    19

    Moving Contact supporting angle.

    Movable contact is to be supported by G.I Angle of size 50 x 50 x5mm on each phase and the moving contact are to be bolted through 2 nos. stainless flat and spring washers suitably.

    20 Galvanisation (a) Iron parts shall be hot-dipped galvanised as per IS :2629/1985 (1 st Revision), (Amendment-2).

    (b) The G.I Pipe shall be galvanised as per IS :

    4736/1968 (1 st Revision),(Amendment-1) for

    Hot-dipped Zinc Coating on M.S Tubes.

    21 Details of phase

    (a) Coupling Rod. 25mm nominal bore G.I Pipe medium gauge.

    (b) Operating Rod.

    32mm nominal bore G.I Pipe medium gauge. Single length 6 mtrs. The detail dimensions of

    the G.I Pipe as mentioned below :

    Nominal Outside Diameter Wall thickness

    Max. Min.

    25mm 34.2mm 33.3mm 3.25mm

    32mm 42.9mm 42mm 3.25mm

    (c ) Arcing Horn. (a) 8mm dia G.I Rod with spring-assisted operation.

  • (d) Bearing System. One bearing shall be provided near the

    Base Channel to assist in operatio.

    (e) Force of fixed contact spring. 50-75 lb.

    (f) Copper braided flexible tapes.

    320mm length of flexible electrolytic copper tape or braided chordwith tin coated having minimum weight 450 gms/mtr. And both ends shall be cripped with copper sockets through brass bolts and nuts with brass flat washers. Two nos. of suitable copper sockets shall be used at both ends. The socket should be preferably of "DOWEL" make(catalogue o CUS/48) or equivalent USHA MARTIN make. The minimum no. of flexible wires should be 1536 of 36 SWG for each flexible chord.

    (g) Quick break Device. Lever Mechanism.

    (h) Bearings. 4 nos. self lubricating bearings to be provided with grease nipple including 4th bearing being a thrust bearing.

    (i) Locking Arrangement. Pad locker and key arrangement at both "ON" and "OFF" position.

    (j) Earth Terminal. To be provided at base channel.

    (k) 'T' Connection.

    The 'T' Connection provided on the channel having 'MovingContact' shall be of G.I Nut & Bolt at the bottom end to facilitate replacement of this unit only during requirement & avoid entire change of the arm.

    (l) The 'I-Bolt' shall be longer with 75 mm thread. 22 Supporting Channel. 75 x 40 X6 mm M.S Channel hot-dipped galvanised. 23 Weight of each pole complete. 50 Kgs. Approximately.

    N.B I) Ferrous parts shall be duly galvanised as per IS:2629/1985 (1 st Revision), (Amendment-2) and non-ferrous

    II) The G.I Pipes & Rods shall be galvanised as per IS : 4736/1968 (1 st Revision),(Amendment-1) for Hot- dipped Zinc Coating on M.S Tubes.

    III) Certificate from a Government approved laboratory regarding composition of copper in electrolytic copper

    IV) Items not covered in the G.T.P, but relevant in Design, manufacturing, quality control & testing of

    materials shall be governed by the relevant IS with latest Amendments.

    V) Type Test report from CPRI or accredited NABL laboratory should be furnished. Same for insulators is to

    also to be provided.

  • TECHNICAL SPECIFICATION OF 33 KV & 11KV 3 Pole, 400

    AMP , HORIZONTAL TYPE AB SWITCH

    TECHNICAL SPECIFICATIONS FOR AB SWITCH

    1. SCOPE:- This specification covers manufacturing testing and supply of 3 Pole, 400 AMP, 50 Hz, Single break, 33 KV & 11 KV class Air Break switches for outdoor installations to be used at 33/11 KV Sub-stations and for incoming & outgoing Lines suitable for operation under off load conditions.

    1.1 DESCRIPTION OF THE MATERIALS:-The A.B. Switch sets shall confirm to the following parameters:-

    Sl.

    No.

    Description

    Parameters of AB Switch

    33 KV

    11 KV

    i)

    Number of poles

    3 ii) Number of Post insulator per pole 4 nos. 22/24 KV class 2 nos. 12 KV class

    iii)

    Nominal system voltage (KV)

    33

    11

    iv)

    Highest System Voltage (KV)

    36

    12

    v)

    Rated frequency

    50HZ

    vI)

    System earthing

    Effectively earthed.

    vII)

    Rated nominal current Amp.

    400 400

    viii)

    Altitude of installation

    Not exceeding 1000 M

  • The post insulators used in the A.B. Switches shall have the following ratings

    Sl.

    No.

    Description

    Parameters P.I. of AB Switches for

    33 KV 11 KV

    i)

    Power frequency withstand voltage

    (dry) KV (RMS)

    95

    35

    ii) Power frequency withstand voltage 75 35

    (wet) KV (RMS)

    iii

    Impulse withstand voltage (dry) KV

    (Peak)

    170

    75

    iv)

    Power frequency puncture

    withstand voltage

    1.3 times the actual dry flashover voltage of

    the unit

    1.2 STANDARDS:- The AB Switch Set shall conform to the following standards:-

    i) IS-9920 (Part-I to V.)

    ii) IS-2544/1973 ( for porcelain post insulators)

    iii) Is-2633 (for galvanization of ferrous parts.) or its latest amendments if any.

    1.3 INSULATORS:-

    12 KV class (for 11 KV AB Switches) and 22 KV / 24 KV class (for 33 KV AB Switches) Post Insulators complete with pedestal cap duly cemented to be used in the AB Switch Set conforming to IS-2544/1973

    The bidder shall furnish the type test certificate of the post insulators from their manufacturer for reference.

    The bidder shall mention make, type of insulation materials, metal fittings, Creep age distance, protected Creep age distance, tensile strength, compression strength, torsion strength and cantilever strength.

    1.4 CLIMATIC CONDITIONS:-

    The A.B. Switch set shall be suitable for operation under the following climatic

    1.

    conditions

    Maximum ambient air temperature.

    45 0 C

  • 2. Maximum daily average air temperature 35 0 C

    3. Maximum yearly average ambient air temperature 30 0 C

    4. Maximum temperature attainable by a body exposed to the sun.

    50 0 C

    5. Minimum ambient air temperature 0 0 C

    6. Maximum relative humidity. 100%

    7. Minimum number of rainy days per annum 70

    8. Average number of rainy days per annum 120

    9. Average annual rain fall. 150 cm.

    10. Number of months of tropical monsoon conditions 4

    11. Maximum wind pressure. 260 Kg./ mm2

    12. Degree of exposure to atmospheric pollution. Normally polluted atmosphere.

    1.5 TECHNICAL DETAILS:-

    1.5.1 The 33 KV A.B. Switch Set shall be gang operated (with double tandem pipe) single air break

    outdoor type horizontal mounting having 4 nos. 22/24 KV post insulator per phase and the 11

    KV A.B. Switch Set shall be gang operated single (with double tandem pipe) air break outdoor

    type horizontal mounting having 2 nos. 12 KV post insulator per phase. The operating

    mechanism shall be suitable for manual operation from the ground level and shall be so

    designed that all the three phases shall open or close simultaneously. The Switches shall be

    robust in construction, easy in operation and shall be protected against over travel or straining

    that might adversely affect any of its parts. The required base M.S. Channel, phase coupling

    rod, operating rod with intermediate guide braided with flexible electrolytic copper, tail

    piece of required current carrying capacity and operating mechanism with O & OFF

    positions shall be provided. The operating rod shall be medium gauge of 32mm diameter

    nominal bore G.I. pipe single piece 6 meters. The phase coupling rod for gang operation shall

  • medium gauge 25mm dia nominal bore G.I. Pipe. Rotating post insulators shall be provided

    with suitable bearing mounted on a base channel with 6 mm thick thrust collar and 6mm split

    pin made out of stainless steel. The operating down rod shall be coupled to the spindle

    (minimum dia - 32mm) for gang operation through another suitable bearing by two numbers

    10mm dia through stainless steel bolts with double nuts. The post insulators should be fixed

    with the base channel using Galvanized Nuts and Bolts.

    All the bearings shall be provided with grease nipple. All ferrous parts shall be galvanized and

    polished. The pipes shall be galvanized in accordance with IS-4736/1968.

    1.5.2 Mounting: - The A.B. Switches shall be suitable for horizontal mounting in all type of sub-

    station structures.

    1.5.3 Switching Blades: - It shall be made out of electrolytic copper with silver plated. The

    approximate size shall be 250mm x 50 x 8mm for 11 KV. The switch shall have such a spring

    mechanism so as to ensure that the speed of the opening of contact is independent of speed of

    manual operation

    1.5.4 Fixed Contracts:- The fixed jaw type female contracts (50x8x95 )mm for 11 KV shall be made

    of electrolytic copper ( minimum 95 % copper composition) duly electroplated controlled by

    Phosphor bronze high pressure spring housed in robust G.I. Cover.

    It is essential that provision shall be made in fixed female contracts to take the shock arising

    from the closing of moving contract blade without the same being transmitted to the post

    insulator. The arrangement made in this regard shall be specifically shown in the drawing.

    1.5.5 Arcing Horn:- As the switches are generally meant for isolating transmission line and

    distribution transformers, suitable arcing horns shall be provided for breaking the

    charging current horn shall be made of 10 mm dia G.I. Rod with spring assisted

    operation.

    1.5.6 Terminal Connectors:- Terminal connectors shall be robust in design. The size of fixed

    connector shall be ( 80 x 50 x8 mm) and size of movable connector shall be of ( 80 x50) x (

    80 x 50) x 8 mm of copper casting with uniform machine finishing duly silver plated made

    out of minimum 95 % copper composition with 2 nos. 12 mm dia holes provided

    withsuitable brass bolts and double nuts, flat washers & 2 nos. bimetallic solderless sockets

    suitable up to ACSR Panther or AAAC 232 mm2 conductor.

  • 1.5.7 Spacing:- The minimum clearance between phase to the switch shall be 1200 mm. The

    operating down rod shall be at a transverse distance of 300 mm from the outer limb of the

    switch. The centre spacing between two post insulators of the same phase shall be 560 mm.

    In the open position of the A.B. Switches the moving blade shall rotate through anangle of 90 0

    . This shall be exhibited in the drawing.

    1.5.8 Drawing & Literatures:- Drawings of each item i.e. 11 KV, 400 amp and 33 KV 400 amp, 3

    Pole, single break A.B. Switch shall be furnished along with the tender.

    The details of construction and materials of different parts of the A.B. Switches shall clearly

    be indicated in the tender and illustrative pamphlet / literature for the same shall be

    submitted along with the tender.

    1.6 TESTS & TEST CERTIFICATE

    1.6.1 Type Test:- Certificates for the following type tests conducted within five years

    proceeding to the date of opening of tender on prototype set of A.B Switch in a Govt.

    Approved Testing Laboratory preferably at CPRI, Bhopal/ Bangalore shall have to be

    submitted for reference and scrutiny.

    i. Impulse voltage dry test

    ii. Power frequency voltage dry test

    iii. Power frequency voltage wet test

    iv. Temperature of resistance.

    v. Measurement of resistance.

    vi. Test to prove the capability of carrying the rated peak short circuit current and the rated short time current.

    vii. Mainly active load breaking capacity test. viii. Transformer off-load breaking test.

    ix. Line charging breaking capacity test.

    x. Operation tests.

    xi. Mechanical endurance test.

  • xii. Mechanical strength test for the post insulator as per IS-2544/1973.

    xiii. Test for galvanization of metal (ferrous) parts as perm IS-2633/1973.

    Besides, mechanical endurance test will have to be conduct on one set in the presence of our authorized person who shall be deputed to carryout acceptance tests before delivery of the materials.

    1.6.2 Routine Tests: - The following routine tests shall have to be conducted on each sets and results are to be furnished for consideration of deputing inspecting officer for inspection and conducting testing of the materials.

    1. Power frequency voltage dry test

    2. Measurement of resistance of main circuit

    3. Tests to prove satisfactory operation.

    4. Dimension check

    5. Galvanization test.

    1.7 GUARANTEED TECHNICAL PARTICULARS:-

    The Bidder shall furnish the guaranteed technical particulars duly filled in the format at

    Appendix-I along with the tender.

    1.8 COMPLETENESS OF EQUIPMENT:-

    Any fittings, accessories for apparatus which may not have been specifically mentioned in this specification but which are usual or necessary in equipment of similar plant shall be deemed to be included in the specification and shall be supplied by the Tender without extra charge. All plant and equipment shall be completed in all details whether such details are mentioned in the specification or not.

    1.9 INSPECTION:-Routine and acceptance tests shall be conducted at the place of manufacturer. The bidder are requested to furnish details of equipment which will be used for testing along with tender. The bidder of those manufacturers who do not have adequate testing facilities for conducting routine and acceptance test are liable for cancellation. The successful bidder has to furnish routine test certificate and guaranteed certificate for approval prior to offer of materials for inspection for each consignment of offer.

  • (To be submitted with offer)

    GUARANTEED TECHNICAL PARTICULARS FOR 33KV, 400A, 50 HZ,

    3 POLE, SINGLE BREAK TYPE

    Sl.

    No

    Particulars

    Desired values

    Bidder

    offer

    1 2 3 4

    1.

    Maker s name and country

    of origin

    To be specified by the tenderer

    2. Type of Switch Rotating type only

    3. Suitable for mounting Horizontal only

    4.

    Number of supporting post

    insulators per phase

    4 nos.22 KV / 24 KV Post Insulators per phase

    as per ISS-2544/1973.

    5.

    Post Insulator.

    a)

    Maker s name and country

    of origin

    To be specified by the tenderer

    b)

    Type of cementing

    To be quoted for original cemented only &

    as per IS-2544-1973 & relevant IEC.

    c)

    One minute power frequency

    withstand voltage Dry

    95 KV RMS.

    d)

    One minute power frequency

    withstand voltage Wet

    75 KV RMS.

    e) Visible discharge voltage 27 KV RMS.

    f)

    Dry Flashover Voltage

    To be specified by the tenderer

    g)

    Power frequency puncture

    with stand voltage

    1.3 times of actual dry flash over voltage

    h)

    Impulse withstand voltage

    (switch in position)

    170 KV (peak)

    i)

    Creepage distance (mm)

    380 mm minimum. (actual creepage distance for which type test have been conducted is to be specified by the tenderer

  • 6.

    Impulse withstand voltage

    for positive and negative

    polarity 1.2 / 50 mircro-

    second wave

    a)

    Across the isolating distance

    195 KV (peak)

    b)

    To earth & between poles

    170 KV (peak)

    7.

    One minute power frequency

    withstand voltage

    a)

    Across the isolating distance

    80 KV (RMS)

    b)

    To earth & between poles

    70 KV (RMS)

    8.

    Rated normal current and

    rated frequency

    400 amps. 50 Hz

    9.

    Rated short time current.

    16 KA ( RMS )

    10.

    Rated short circuit making

    capacity

    25 KA (RMS)

    11.

    Rated peak withstand current

    40 KA ( Peak )

    12.

    Rated cable charging

    breaking capacity

    40 KA ( RMS )

    13.

    Rated Transformer off load

    breaking capacity

    16 Amp (RMS)

    14.

    Rated line charging breaking

    capacity

    5.3 Amps ( RMS)

    15.

    Minimum clearance between

    adjacent phases

    a)

    Switch Closed ( centre to

    centre)

    1200 mm

    b)

    Switch Opened ( centre to

    edge of blade)

    640 mm

    16.

    Temperature rise

  • a)

    Temperature rise shall not

    exceed the maximum limit as specified below at an

    ambient temperature not exceeding in 40

    0 C

    b)

    Copper contacts in air 65

    0 C

    c)

    Terminal of switch intended to

    be connected to external

    conductor by bolts

    50 0

    C

    17.

    Vertical Clearance from top of

    insulator cap to mounting

    channel

    508 mm (minimum)

    18.

    Type of Contact: -

    a) Self aligned, high pressure jaw type fixed

    contacts of electrolytic copper of size 80

    mm x 50 mm x 8 mm duly silver plated. Each

    contact should be revetted with three nos.

    Copper rivets with a bunch (minimum

    3 mm thick) consisting of copper foils, each

    may vary from 0.15 mm to 0.25 mm. These

    total thickness of copper foils per jaw

    should be 6 mm. Jaw assemblies are to be

    bolted through stainless steel bolts and nuts

    with stainless steel flat and spring washer.

    b) Solid rectangular blade type moving

    contact of electrolytic copper size 250 mm x

    50 mm x 8 mm duly silver plated ensuring a

    minimum deposit of 10 micron of silver on

    copper contacts or as may be prescribed

    under relevant ISS / IEC.

    c) Pressure spring to be used in jaw contacts

    shall be Stainless Steel having 8 nos of turn x

    28 mm height x 14.4 mm diameter with

    14 SWG wire (minimum six nos springs shall

    be used)

  • 19.

    Connectors:-

    Terminal connectors for both movable and

    fixed should be of copper flats of same size

    similar to that of moving contact blades

    (minimum 95% copper composition). The

    fixed connector shall of size 80 mm x 50 x 8 mm

    and the size of movable connector shall be size

    80 x 50 x 8 mm with machine finishing

    duly silver plated with 2 nos. of

    stainless steel bolts, nuts, plain washers

    & spring washers should be provided along

    with 2 nos solder less bimetallic sockets for

    each connector suitable sockets for each

    connector suitable up to

    232 mm AAA conductor.

    20.

    Moving Contacts:-

    Movable contact is to be supported by

    galvanized angle of 50 x 50 x 5 mm in each

    phase and the moving contact are to be

    bolted through 2 no stainless steel bolts and

    nuts with suitable stainless steel flat and

    spring washers.

    21.

    Galvanization

    a) Iron parts shall be dip galvanized as per

    IS-2633/1972.

    b) b) The pipe shall be galvanized as per IS-

    4736/1968.

    22.

    Details of Phase

    a)

    Coupling Rod

    25 mm nominal bore G.I. pipe medium

    gauge.

    b)

    Operating Rod

    32 mm nominal bore G.I. pipe medium

    gauge single length 6 mtrs. The detailed

    dimension of the G. I. pipe as per IS-1239 (Pt.

    I) as mentioned below :-

    Nominal

    base (mm)

    Outside

    diameter

    (mm)

    Diameter

    thickness (mm)

    Max Min

    25 34.2 33.3 3.25

    32 42.9 42 3.25

    c)

    Arcing Horns

    10 mm dia G.I. rod with spring assisted

    operation.

  • d)

    Force of Fixed contact spring

    To be specified by the tenderer.

    e)

    Copper braided flexible

    tapes:-

    450 mm length of flexible electrolytic

    copper tape or braided chord (with tin

    coated) having minimum weight 450 gms per

    meter and both ends shall be crimped with

    copper sockets through brass bolts and nuts

    with brass flat washers. Two nos of suitable

    copper sockets shall be used at both ends. The

    minimum no. of flexible wires should be 1536

    of 36 SWG for each flexible chord.

    f)

    Quick break device

    Lever mechanism.

    g)

    Bearings

    4 nos. self lubricated bearing to be provided

    with grease nipple including 4th bearing

    being a thrust bearing.

    h)

    Locking arrangement

    Pad Lock & Key arrangement at both ON

    & OFF ion.

    i)

    Earth Terminal:

    To be provided at base channels.

    23.

    Supporting Channels

    100 mm x 50 mm M.S. Channel hot dip

    galvanized.

    24.

    Weight of each pole

    complete

    To be specified by the tender

    GUARANTED TECHNICAL PERTICULARS OF 11KV 400AMP 3 POLE AB SWITCH

    Slno. Perticulars Requirement Bidders Offer

    List of relevant standards :IS

    1818,9921,2544,1394,4691,325,

    4722, 2629, 4759, 2633,1573,3033,

    2016, 3961, 5561, 1554, 5578,

    11353,9920

    1 name & Address

  • To be specified by the bidder

    2 Type of Switch Rotating Type

    3 Suitable for mounting Horizontal only

    4 No. of Breakers per phase

    Single Break

    5 No. of Post Insulators per phase 2nos. of 12KV Post Insulators as per

    IS:2544/73 per phase

    6

    (a)

    Post Insulators

    Name & Country of

    Manufacture

    of Post Insulator

    Techno Ceramic / Allied Ceramic

    /JSI/equivalent Type Test certificates to

    be provided along with the offer.

    (b) Type of cementing Original Cementing. The insulator to be

    cemented with MCI (Hot dip galvanised

    /Al Alloy cap and MCI/Forged steel hot

    deep galvanized pedestral)

    (c) Power frequency withstand

    voltage (Dry)

    65KV RMS

    (d) One minute Power frequency withstand

    voltage (wet)

    40KV RMS

    (e) Visible discharge voltage

    9KV RMS

    (f) Dry flash over voltage 70 KV

    (g) Power frequency puncture withstand

    voltage

    110KV

    (h) Creapage distance 320 mm

    (7) Impulse withstand voltage for positive

    & negative polarity (1.2/50

    micro second wave)

  • (a) Across the isolating distance

    85KV Peak

    (b) To earth & between poles

    75KV Peak

    8 Rated one minute

    Power frequency withstand

    voltage

    (a) Across the Isolating distance

    32KV(RMS)

    (b) To earth & between poles

    28KV(RMS)

    9(a) Rated voltage

    nominal/maximum

    11/12KV

    (b) Rated normal current and rated frequency

    400 Amps. 50hz

    10 Rated short-circuit making

    capacity

    20KA (Peak)

    11 Rated Short-time current

    16KA

    12 Rated peak withstand current

    40KA

    13 Rated mainly active load breaking capacity

    10KA

    14 Rated transformer off load breaking

    capacity

    16.3A

    15 Rated line charging capacity

    2.5A(RMS)

    16 Rated cable charging capacity

    10A(RMS)

    17 Minimum clearance between

  • adjacent

    phase

    (a) Switch closed (center to center)

    Mm

    (b) Switch opened (Center of post

    insulator to the

    edge of the blade)

    Mm

    18 Temperature rise The

    Temperature rise should not exceed

    the

    maximum limit to 65oC

    at an ambient temperature not

    exceeding 40oC

    The Temperature rise of contacts &

    terminals are within permissible limit of

    650C & 50oC respectively.

    19 Vertical clearance from Mm

    top of insulator cap to mounting

    channel

    20 Type of connect a) Self aligned high pressure law type fixed contacts of hard drawn

    copper of size 50X8X70 mm

    contact is riveted with three nos.

    copper rivets with a bunch of

    copper strips suitable to give

    desired spring action.

    b) Solid rectangular blade type

    moving contact of size 50X8 mm

    and length 220 mm duly silver

    plated.

    c) Stainless Steel 4 NOS of

    Pressure springs are to be used in

    each jaw contacts having 8nos. of

  • turns X28mm heights

    X14.4mm diameter with 14 SWG

    wire

    21(a) Terminal connector

    (fixed)

    Copper flat of size 50X8 mm and length

    95mm duly silver plated with 1

    no. long 1/ dia G.I. Nut Bolt &

    Spring washers suitable for 10Sq.mm

    conductor.

    (b) Terminal connector

    (Movable)

    Copper flat of size 50X8mm and length

    100mm duly silver plated with

    1no long dia G.I. Nut Bolt & Spring

    washers suitable to accommodate

    bimetallic socket up to 100 sq mm.

    conductor.

    22 Terminal supporting flat Movable terminal contact is supported by G.I. flat of size 50 X

    8mm X 370mm on each phase.

    23

    (a)

    Phase Coupling Rod ISI mark 25mm nominal bore G.I. Pipe (Medium) conforming to

    IS:1239/Part

    (b) Operating Rod ISI mark 32mm nominal bore G.I.

    Pipe (Medium) conforming to

    IS:1239/Part

    (c) Arcing Horn 10mm dia G.I. Rod

    (d) Force of fixed contact spring

    30 lbs to 50 lbs

    (e) Copper braided flexible taps 320mm long 2no. tin coated copper braided flexible tape both end seated

    with cupper sheets duly punched for

    fixing

    (f) Quick break device Lever mechanism

  • 26 Fastners All fastners (nut & bolds) should be hot-dip galvanished & should be

    provided with spring and plane

    washers.

    27 Material & Dimension of

    Coupling Pipe

    28 Material & Dimension of

    Operating Rod

    29 Sockets (Lugs) Shall be tinned cupper sholder less

    crimping type confirming to IS : 8309

    & 8394 suitable for aluminium

    conductor. The cable lugs shall suit

    the type of terminals provided. The

    cable lug shall be of Dowel make.

    30 Detailed drawing submitted ?

    Yes

    TECHNICAL SPECIFICATION FOR 33KV, 400 AMP , 3 POLE HG FUSES

    SCOPE:This specification covers the design manufacture, shop testing, loading, transportation and

    delivery at sub-station site of 33KV, 400Amp, 3Pole & 11KV, 400Amp, 3Pole H.G. Fuse Sets for outdoor

    installations to be used at 33/11KV Sub-stations suitable for operation under off load conditions.

    The 33KV. 400Amps, 3 Pole H.G Fuse Sets shall confirm to the following parameters:-

    i) Number of Poles:- 3

    ii) No. of insulator per pole:- 4nos. 22/24KV Post Insulator/ Phase

    iii) Nominal system voltage 33 KV

    iv) Highest system voltage:- 36KV

  • v) Rated frequency:- 50 Hz

    vi) System earthing:- Effectively earthed

    vii) Rated normal current 400 Amps

    viii) Altitude of installation Not exceeding 1000 M.

    The post insulator used in the H.G. Fuse set shall have the following ratings:-

    i) Power frequency withstand voltage (dry) 95KV (RMS)

    ii) Power frequency withstand voltage ( wet) 75 KV (RMS)

    iii) Impulse withstand voltage (dry) 170 KV (Peak)

    iv) Power frequency puncture withstand voltage 1.3 times the actual dry flashover voltage of the unit.

    STANDARDS:- The H.G. Fuse Set shall conform to the following standards:-

    i) IS- 5792- 1973 (For high voltage expulsion fuses & similar fuses)

    ii) IS-2544-1973 ( for porcelain post insulators)

    iii) IS-9385-1979 or its latest amendments if any.

    iv) IS-2633-1979 ( For Galvanization of ferrous parts )

    INSULATORS:The 22KV/ 24KV post insulators complete with pedestal cap duly cemented to be used in the H.G. Fuse sets confirming to IS-2544/1973.

    The bidder shall mention make, type of insulation materials, metal fittings, Creepage distance, protected Creepage distance, tensile strength compression strength, torsion strength and cantilever strength.

    The bidder shall furnish the type test certificate of the post insulators from their manufacturer for reference & scrutiny.

  • TECHNICAL DETAILS:The H.G. Fuses shall have adjustable arcing horns made of solid copper rod having

    8.23 mm dia. The horns shall be fitted with screwing devices with flynuts for fixing and tightening

    the fuse wire. It shall have robust terminal connector 5s of size 80mm x50 mm x 8 mm made of

    copper casting ( 95% minimum copper composition) duly silver plated with two numbers of 12mm dia

    brass bolts and double nuts with flat brass washers. The connector should be capable of connecting

    crimp able conductor up to 232 Sq.mm. size (ACSR/ AAAC) with bimetallic solder less sockets .The H.G.

    Fuse Set shall suitable for horizontal mounting on sub-station structures. The minimum clearance

    between the adjacent phases of the fuse set shall be 1200 mm and the centre to centre (distance

    between two post insulators of the same phase) shall be 760 mm. All metal (ferrous) parts shall be

    galvanized and polished. Only post insulator (original cemented and not pin insulators shall be used

    for the H.G. Fuse Set.

    DRAWIING & LITERATURES:Three copies of drawings of 33KV, 400Amp, 3 Pole H.G. Fuse shall be

    furnished along with the tender for reference. The details of construction and materials of different parts

    of the H.G Fuse shall clearly be indicated in the tender and illustrative pamplet/ literature for the same

    shall be submitted along with the tender.

    TESTS & TEST CERTIFICATE: Type Test:-Certificates for the following type tests conducted within

    five years proceeding to the date of opening of tender on a prototype set of H.G. Fuse in a

    Govt. Approved Testing Laboratory preferably at CPRI Bangalore shall be submitted along

    with the tender.

    i) Impulse voltage dry test

    ii) Power frequency voltage dry test

    iii) Power frequency voltage wet test

    iv) Temperate of resistance.

    v) Test to prove the capability of carrying the rated peak short circuit current and the rated short time current.

    vi) Mainly active load braking capacity test.

    vii) Transformer off-load breaking test.

    viii) Line charging breaking capacity test.

    ix) Operation tests.

    x) Mechanical endurance test.

    xi) Mechanical strength test for the post insulator as per IS:2544/1973, 5350 (Pt- II)/1970 & relevant IEC.

  • xii) Test for galvanization of metal (ferrous) parts as per IS- 2633/1973.

    Besides above, mechanical endurance test will have to be conducted on one set in the presence of our authorized person who shall be deputed to carryout acceptance test before delivery of the materials.

    Routine Tests:-

    The following routine tests shall have to be conducted on each sets and results are to be furnished for consideration for acceptance of deputing inspecting Officer for inspection & conducting testing of the materials

    .i) Power frequency voltage dry test.

    ii) Tests to prove satisfactory operation.

    iii) Dimension check.

    iv)Galvanisation test.

    GUARANTEED TECHNICAL PARTICULARS: The bidders are required to furnish the guaranteed technical particulars at Schedules attached to this specification duly filled in along with the tender.

    COMPLETENESS OF EQUIPMENT:-

    Any fittings accessories or apparatus which may not have been specifically mentioned in this specification but which are usually necessary in equipment of similar plant shall be deemed to be included in the specification and shall be supplied by the bidder without extra charge. All plant and equipment shall be complete in all details whether such details are mentioned in the specification or not.

    INSPECTION AND TESTING:-

    The Purchaser shall have free entry at all times, while work on the contract is being performed, to all parts of the manufacturer works which concern the processing of the equipment ordered. The manufacturer shall afford the Purchaser without charge, all reasonable facilities to assure that the equipment being furnished is in accordance with this specification.

    The equipment shall successfully pass all the type tests and routine tests referred to and those listed in the most recent edition of the standards given in this specification.

    The Purchaser reserves the right to reject an item of equipment if the test results do not comply with the values specified or with the data given in the technical data schedule.

    Type tests shall have been / shall be carried out at CPRI / National Govt. approved Laboratory and be witnessed by a representative of such laboratory or some other representative acceptable to the Purchaser. Routine tests shall be carried out by the

  • Supplier at no extra charge at their works.

    Adequate facility with calibrated testing equipment must be provided by the manufacturer free of cost to carry out the tests. Type test certificates must be furnished along with the tender for reference of the Purchaser.

    All costs in connection with the testing, including any necessary re-testing, shall be borne by the Supplier who shall provide the Purchaser with all the test facilities which the latter may require, free of charge. The Purchaser shall have the right to select the samples for test and shall also have the right to assure that the testing apparatus is duly calibrated and correct. Measuring apparatus for routine tests shall be calibrated at the expense of the Supplier at an approved laboratory and shall be approved by the Purchaser.

    The Supplier shall be responsible for the proper testing of the plant or materials supplied by sub-suppliers to the same extent as if the work, plant or materials were completed or supplied by the Supplier.

    Any cost, incurred by the Purchaser in connection with inspection and re-testing as a result of failure of the equipment under test or damage during transport or offloading shall be to the account of the Supplier.

    The supplier shall submit to the Purchaser five signed copies of the test certificates, giving the results of the tests as required. No materials shall be dispatched until the test certificates have been received by the Purchaser and the Supplier has been informed that they are acceptable.

    The test certificates must show the actual values obtained from the tests, in the units used in this specification, and not merely confirm that the requirements have been met.

    In the case of components for which specific type tests or routine tests are not given in this specification, The Supplier shall include a list of the tests normally required for these

    components. All materials used in the Contract shall withstand and shall be certified to have satisfactorily passed such tests.

    The Purchaser at his discretion may re-confirm the Test Results in his own laboratory or laboratory of his choice.

    No inspection or lack of inspection or passing by the Purchaser s Representative of equipment or materials whether supplied by the Supplier or sub-supplier, shall relieve the Supplier from his liability to complete the contract works in accordance with the contract or exonerate him from any of his guarantees.

  • GURANTEED TECHNICAL PARTICULARS FOR 400 AMP, 3 POLE, H.G. FUSES.

    Sl.

    No.

    Particulars

    Desired Values for

    Bidder

    Offer

    33 KV

    1 2 3 4

    1

    Maker's name and

    country or origin

    To be specified by the bidder.

    2

    Suitable for mounting

    Horizontal only.

    3

    Number of supporting

    post

    insulator per phase

    4 nos. 22KV/24KV Post Insulator per phase as per ISS -

    2544/ 1973

    4 Post Insulator

    (a)

    Maker's name and

    country or origin

    To be specified by the bidder

    (b)

    Type of cementing

    To be quoted original cemented only.

    (c )

    One minute power

    frequency withstand

    voltage dry

    95KV RMS

    (d)

    One minute power

    frequency withstand

    voltage wet.

    75 KV RMS.

    (e)

    Visible discharge

    voltage

    27KV RMS

    (f)

    Dry Flashover

    Voltage

    To be specified by the bidder

    (g)

    Power frequency

    puncture withstand

    voltage

    1.3 times of actual dry flash over voltage.

    (h)

    Impulse withstand

    voltage (switch in

    position)

    170KV (peak)

  • (I )

    Creepage distance

    380mm minimum. (actual creepage distance for

    which type test have been conducted is to

    be specified by the bidder)

    5

    Impulse withstand

    voltage for positive

    and negative

    polarity (1.2/50

    micro second wave)

    (a)

    Across the isolating

    distance

    195 KV (peak)

    (b)

    To earth & between

    poles

    170 KV (peak)

    6

    One minute power

    frequency withstand

    voltage

    (a)

    Across the isolating

    distance

    100 KV (RMS)

    (b)

    To earth & between

    poles

    75 KV (RMS)

    7

    Rated normal current and rated frequency.

    400 amps, 50 Hz , 3 Pole

    8

    Operating Voltage

    33 KV

    9

    Vertical clearance

    from top of insulator

    cap to mounting

    Channel

    508 mm (minimum)

    10

    Height of the riser

    for carrying the

    horns.

    250mm from the cap

    (top) of insulator.

  • 11

    Details of Arcing

    Horns

    Copper rod having 8.32 mm dia Silver-plated provided

    with screwing arrangement for fixing use wire made of

    copper casting. (Total length 995mm). All the bolts, nuts

    and washers should be made out of brass.

    12

    Riser Unit

    (250mm total height).

    (a) The shape of connectors may be made of

    straight copper Flat of size adequate enough to carry a

    current density not ess than 1.5 Amp/ mm .

    2 Nos of 3/8 G.I. Bolts, double nuts, plain and spring

    washers and 2 nos. solder less bimetallic shockets per each

    connector suitable up to 232mm AAA conductor.

    (b) 170mm height G.I. Risermade of 25mm nominal

    bore medium gauge G.I. Pipe welded with 2 nos. G.I.

    Flat of 35 x 5 mm at both ends fixed with 10mm dia

    stainless steel, bolts and nuts with flat stainless steel

    spring washers.

    13

    Supporting

    Channels

    100 x 50 x 6 mm M.S. Channel (galvanized)

    14

    Galvanisation

    All ferrous parts should be galvanized as per IS-

    2633/1972 & all non-ferrous part should be duly

    galvanized..

    15

    Weight of each pole

    (complete)

    To be specified by the tenderer.

  • 33KV 3-Pole 200 Amp H.G Fuse

    Technical Specification

    1. SCOPE: - This specification covers the manufacture, testing and supply

    of 33 KV 200 Amps 3 pole, H.G. Fuse Sets.

    2. (a) The 33 KV H.G. Fuses shall be suitable for out door operation in horizontal

    configuration under the climatic conditions specified. It shall be of the following

    ratings:-

    1 Number of Poles 3 2 No.of Insulator per Pole 4 nos. 22 KV /24 KVpost Insulators per phase

    3 Nominal system Voltage 33 KV 4 Highest System of Voltage 36 KV 5 Rated frequency 50 Hz 6 System Frequency Effectively earthed 7 Rated normal current 200 Amps 8 Altitudes of installation Not exceeding 1000 M.

    (b) The post insulator used in the H.G. Fuse set shall have the following ratings :-

    1 Power frequency withstand voltage (dry) 95 KV (RMS) 2 Power frequency withstand voltage (wet) 75 KV (RMS) 3 Impulse withstand voltage (dry) 170 KV (Peak) 4 Power frequency withstand voltage 1.3 times the actual dry flashover

    voltage of the unit

    3. STANDARDS :- The H.G. Fuse set shall confirm to the following standards. IS- 9385-1980 ( for high voltage expulsion fuses and similar fuses).

    IS- 2544-1973 ( for porecelain post insulators or its latest amendments if any.). IS- 2633- 1979 ( for Galvanisation of ferrous parts).

    4. INSULATOR MAKE :- 22/24 KV post insulator complete with pedestal cap duly

    cemented to be used in 33 KV H.G. Fuse sets confirming to IS-2544/1973.

    5. TECHNICAL DETAILS :- The H.G. Fuses shall have adjustable arcing horns made

    of solid copper rod having 8.23 mm dia. The horns shall be fitted with screwing

    devices with fly nuts for fixing and tightening the fuse wire. It shall have robust terminal

    connector of size 80 mm x 50 mm x 8 mm made of copper casting ( 95 % minimum

    copper composition) duly silver plated with two numbers of 12 mm dia brass bolts

    and double nuts with flat brass washers. The connectors should be capable of

  • connecting crimpable conductor upto 80 Sq. mm size( ACSR/ Alloy) with bimetallic

    solderless sockets. The H.G Fuse Set shall suitable for horizontal mounting on sub

    station structures. The minimum clearance between the adjacent phases of the fuse set

    shall be 1200 mm and the centre to centre (distance between two post insulators of the

    same phase) shall be 760 mm. All metal (ferrous) parts shall be galvanized and polished.

    Only post insulator ( orginal cemented and not pin insulators shall be used for the H.G.

    Fuse Set.

    6. CLIMATIC CONDITIONS :- The H.G. fuse set shall be suitable for operation

    under the following climatic conditions.:-

    1 Maximum ambient air temperature 450 C

    2 Maximum daily average air temperature 350 C

    3

    Maximum yearly average ambient air temperature 300 C

    4 Maximum temperature attainable by a body exposed to the sun.

    500

    C

    5 Minimum ambient air temperature 00 C

    6 Maximum relative humidity 100% 7 Average number of thunderstorm days per annum 70 days 8 Average number of rainy days per annum 120 9 Average annual rain fall. 50 cm 10 Number of months of tropical monsoon conditions 4 11 Maximum wind pressure 260 Kg/mm 12 Degree of exposure to atmospheric pollution. Normally polluted

    atmosphere.

    7 Type Test :-

    Certificate for the following type tests conducted (within five years proceeding to the date of opening of the tender) on a prototype set of H.G. Switch in a NABL approved test house/CPRI shall have to be submitted along with offer.

    i) Dielectric test (impulse & one minute wet power frequency withstand voltage test.)

    ii) Temperature rise test ( for terminals)

    iii) Mechanical strength test for the post of insulator as per IS-2544/1973

    iv) Test for galvanization of metal (ferrous) parts.

    8. ROUTINE/ACEPTANCE TESTS :-

    The inspection may be carried out by the Purchaser at any stage of manufacture. The

    successful bidder shall grant free access to the Purchasers representative at a

    reasonable time when the work is in progress. The following routine tests shall have to

    be conducted on each set and results are to be furnished for consideration of

    deputing inspecting officer for inspection and conduction testing of the materials at the

    works of the manufacturer. the supplier shall give fifteen days advance intimation to

    the Purchaser to enable him to depute his representative for witnessing the tests.

    i) Power frequency voltage dry test

    ii) Dimension Check

    iii) Galvanization test.

  • 9. Guaranteed Technical Particulars :

    The bidders are required to furnish the guaranteed technical particulars duly filed in the

    proforma along with the bid.

    10. Completeness of Equipment :

    Any fittings accessories or apparatus which may not have been specifically mentioned in

    this specification but which are usually necessary in equipment of similar plant shall be

    deemed to be included in the specification and shall be supplied by the bidder without extra

    charge. All plant and equipment shall be complete in all details whether such details are

    mentioned in the specification or not.

    11. Inspection :

    Routine and acceptance test shall be conducted at the place of manufacturer. The bidders are

    requested to furnish details of equipments which will be used for testing along with the bid.

    The bids of these manufacturers who do not have adequate testing facilities for conducting

    routine and acceptance test are liable for cancellation. The successful bidder has to furnish

    routine test certificate and guarantee certificate for each consignment of materials to be

    inspected at the time of offer of materials for inspection.

  • Sl.

    No

    Particulars

    Requirement

    Bidders offer

    33 KV ,200 Amps.3 pole H.G Fuse

    1 Makers name & Address To be specified by the bidder

    2 Operating voltage 33 KV

    3 No. of Post Insulators per

    phase

    4nos. of 22KV/24 KV Post Insulators per phase

    4 Rated normal current & normal frequency

    200 Amp., 50 Hz

    5 Vertical clearance from the top of insulator to mounting

    channel

    508 mm (minimum)

    6 Height of the riser for carrying

    the horn.

    250 mm from the cap top of

    insulator

    7 (a)

    Post Insulators :

    Makers Name & Country of Manufacture of Post Insulator

    Reputed make . All the post insulators provided shall be of

    same make.

    (b) Type of cementing Original Cementing only.

    (c) 1 minute Power frequency

    withstand voltage (Dry)

    95KV RMS

    (d) 1 minute Power frequency

    withstand voltage (wet)

    75KV RMS

    (e) Visible discharge voltage 27KV RMS

    (f) Dry flash over voltage 95 KV

    (g) Power frequency puncture

    withstand voltage

    1.3 times of actual dry flash over

    voltage.

    (h) Creapage distance 430 mm(minimum). Actual creepage distance for which type

    test has been conducted is to be

    supplied.

    8. Impulse withstand voltage for positive & negative polarity

    (1.2/50 micro second wave)

    (a) Across the isolating distance 195KV (Peak)

    (b) To earth & between poles 170KV (Peak)

    9. One minute Power frequency withstand voltage

    (a) Across the Isolating distance 100KV(RMS)

    GUARANTEED TECHNICAL PARTICULARS of 33 KV 200 Amp

    3 Pole HG Fuse

  • (b) To earth & between poles 75KV(RMS)

    10 1.2/50 microsecond wave

    impulse flash over voltage

    To be specified by the bidder

    11 Details of Arcing Horn 1 SWG (8.23 mm) copper rod silver plated provided with screwing

    arrangement on the fuse carrier made

    of copper casting for fixing fuse wire

    (Total length -995 mm). All the

    bolts, Nuts and washers should be

    made out of Brass.

    12 Riser Unit (250 mm height total)

    a) Riser cum Connector made out of copper casting (with minimum 95%

    copper composition having riser size

    (80 mmx50mmx8 mm) and

    connector of size (80 mmx50mmx8

    mm) duly silver plated and machine

    finishing provided with 2 nios.12

    mm dia. brass bolts and double brass

    nuts with flat brass washers and 2

    nos. solderless bimetallic socket per

    each connector suitable upto 80 mm

    conductor. The sockets shall be

    preferably of Usha Martin make.

    b) 170 mm height G.I Riser made of 25 mm nominal bore medium gauge

    G.I pipe welded with 2 nos. of G.I flat

    of 35mmx5mm of both ends fixed

    with 10mm dia. stainless steel bolts

    and nuts with flat & stainless steel

    spring washer.

    13. Galvanization a) All ferrous parts shall be hot- dipped Galvanized as per

    IS.2629/1985 (Latest Amendment)

    b)The pipe shall be galvanized as per IS-4736/1968(Latest Amendment)

    14 Supporting Channel 100mmx50mm M.S.Channel. (Hot dip galvanized)

    15 Weight of each pole 50 Kg (Approximately)

    16 Detailed drawing submitted ? To be provided by bidders

    N.B i) Ferrous parts shall be duely galvanized as per IS :2629/1985(1st. Revision),

    (Amendment-2) and non-ferrous parts shall be silver plated.

    ii) Certificate from a Government approved laboratory regarding composition of copper in

    electrolytic copper casting of materials should be submitted during inspection of materials

    at the cost of tenderer.

  • iii) Items not covered in the G.T.P, but relevant in Design, manufacturing, quality control & testing of materials shall be governed by the relevant IS with latest Amendment.

    11KV 2/3 Pole D.O. Fuse 200Amp

    01) SCOPE:

    This specification covers outdoor, open, drop out expulsion type fuse cut outs suitable for installation in

    50Hz, 11KV distribution system for protection of H. T. lines and transformer centers, Tap lines. The 11KV D.O.

    fuses offered shall be complete with all components necessary for its effective and trouble free operation.

    02) APPLICATION:

    The distributions fuse Drop outs are intended for use on distribution transformers and have no inherent load break

    capacity.

    03) APPLICABLE STANDARD:

    Unless otherwise modified in this specification, the Drop out fuse shall conform to IS: 9385 (Part-I to III) as

    amended from time to time.

    04) RATED VOLTAGE:

    The rated voltage shall be 12 KV.

    05) RATED CURRENT:

    The rated current shall be 200 A.

    06) RATED LIGHTING IMPULSE WITH STAND VOLTAGE VALUES FOR THE FUSE BASE:

    The rated lightning impulse withstands voltage both for positive and negative polarities shall be as given below.

    a) To earth and between pole: 75 KV (Peak)

    b) Across the isolating distance: 85KV (Peak) of fuse base.

    07) RATD ONE MINUTE POWER FREQUENCY WITHSTAND VOLTAGE (DRY AND WET)

    VALUES FOR THE FUSE BASE:

    a) To earth and between poles: 28KV (rms)

    b) Across the isolating distance: 35KV (rms)

    08) TEMPERATURE RISE LIMIT (IN AIR) :

    a) Copper contacts silver faced: 65C

    b) Terminals: 50C

    c) Metal parts acting: The temperature shall not reach as springs such a value that elasticity of the Metal is

    changed.

    09) BREAKING CAPACITY:

    The breaking capacity of D.O. Fuse element shall be 8 KA (asymmetrical).

  • 10) GENERAL REQUIREMENTS/CONSTRUCTIONAL DETAILS:

    10.1 The D.O. Fuse shall be of single vent type (downward) having a front connected fuse carrier suitable

    for angle mounting.

    10.2 All ferrous parts shall be hot dip galvanized in accordance with the latest version of IS: 2633.

    Nuts and bolts shall conform to IS:1364. Spring washers shall be electro-galvanized.

    11) FUSE BASE TOP ASSEMBLY:

    11.1 The top current carrying parts shall be made of a highly conductive copper alloy and the contact

    portion shall be silver plated for corrosion resistance and efficient current flow. The contact shall

    have a socket cavity for latching and holding firmly the fuse carrier until the fault interruption is

    completed within the fuse.

    11.2 The top contact shall be actuated by a strong steel spring which keeps it under sufficient pressure

    to maintain a firm contact with the fuse carrier during all operating conditions. The spring

    shall also provide flexibility and absorbs most of the stresses when the fuse carrier is pushed

    into the closing position.

    11.3 The current carrying parts of the assembly shall be protected from water and dust formation by

    a stainless steel top cover.

    11.4 The top contact assembly shall have a robust galvanized steel hook to align and guide the fuse

    carrier in to the socket latch even when the fuse carrier is closed at an off centre angle.

    11.5 The top assembly shall have an aluminum alloy terminal connector

    (refer clause 19).

    11.6 The top assembly shall be robust enough to absorb bulk of the forces during the fuse carrier

    closing and opening operations and shall not over stress the spring contact. It shall also

    prohibit accidental opening of the fuse carrier due to vibrations or impact.

    12) FUSE BASE BOTTOM ASSEMBLY:

    12.1 The conducting parts shall be made of high strength highly conductive copper alloy and the contact

    portion shall be silver plated for corrosion resistance and shall provide a low resistance current

    path from the bottom fuse carrier contacts to the bottom terminal connector.

    12.2 The bottom assembly shall have hinge contacts made from highly conductive, anti-corrosive copper

    alloy and shall accommodate and make a firm contact with the fuse carrier bottom assembly. The

    fuse carrier shall be placed easily in or lifted from the hinges without any man handling. In

    addition, the bottom assembly shall perform the following functions.

    i) When opened manually or after fault interruption the fuse carrier shall swing through 180 to the vertical

    and its further travel shall be prevented by the fuse base bott