421 04 5500 01 July 2007 TECHNICAL SUPPORT MANUAL Split System Air Conditioner (H,C,T)4A4 DANGER, WARNING, CAUTION, and NOTE The signal words DANGER, WARNING, CAU‐ TION, and NOTE are used to identify levels of haz‐ ard seriousness. The signal word DANGER is only used on product labels to signify an immediate haz‐ ard. The signal words WARNING, CAUTION, and NOTE will be used on product labels and through‐ out this manual and other manuals that may apply to the product. DANGER - Immediate hazards which will result in severe personal injury or death. WARNING - Hazards or unsafe practices which could result in severe personal injury or death. CAUTION - Hazards or unsafe practices which may result in minor personal injury or product or property damage. NOTE - Used to highlight suggestions which will result in enhanced installation, reliability, or opera‐ tion. Signal Words in Manuals The signal word WARNING is used throughout this manual in the following manner: The signal word CAUTION is used throughout this manual in the following manner: Signal Words on Product Labeling Signal words are used in combination with colors and/or pictures on product labels. WARNING Safety Labeling and Signal Words ! ! CAUTION WARNING TABLE OF CONTENTS Wiring Diagrams 2 - 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . Charging Chart 4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Tech Labels (Expanded Data) 5 - 11 . . . . . . . . . . . . . . . . Condenser Only Data 12 - 15 . . . . . . . . . . . . . . . . . . . . . . Cooling Multipying Factors 16 - 21 . . . . . . . . . . . . . . . . . . Exploded Drawings 22 - 24 . . . . . . . . . . . . . . . . . . . . . . . . C4A4 Parts List 25 - 27 . . . . . . . . . . . . . . . . . . . . . . . . . . . H4A4 Parts List 28 - 30 . . . . . . . . . . . . . . . . . . . . . . . . . . . T4A34Parts List 31 - 33 . . . . . . . . . . . . . . . . . . . . . . . . . . . Model Number Identification 34 . . . . . . . . . . . . . . . . . . . . ! WARNING DEATH, PERSONAL INJURY, AND/OR PROPERTY DAMAGE HAZARD Failure to carefully read and follow this warning could result in equipment malfunction, property damage, personal injury and/or death. Installation or repairs made by unqualified per‐ sons could result in equipment malfunction, prop‐ erty damage, personal injury and/or death. The information contained in this manual is in‐ tended for use by a qualified service technician fa‐ miliar with safety procedures and equipped with the proper tools and test instruments. Installation must conform with local building codes and with the National Electrical Code NFPA70 current edition or Canadian Electrical Code Part 1 CSA C.22.1.

TECHNICAL SUPPORT MANUAL Split System Air Conditioner …icpindexing.toddsit.com/documents/003350/42104550001.pdf · 2007-08-29 · TECHNICAL SUPPORT MANUAL Split System Air Conditioner:

  • Upload
    others

  • View
    10

  • Download
    0

Embed Size (px)

Citation preview

Page 1: TECHNICAL SUPPORT MANUAL Split System Air Conditioner …icpindexing.toddsit.com/documents/003350/42104550001.pdf · 2007-08-29 · TECHNICAL SUPPORT MANUAL Split System Air Conditioner:

421 04 5500 01 July 2007

TECHNICAL SUPPORT MANUALSplit System Air Conditioner

(H,C,T)4A4

DANGER, WARNING, CAUTION, andNOTEThe signal words DANGER, WARNING, CAU‐TION, and NOTE are used to identify levels of haz‐ard seriousness. The signal word DANGER is onlyused on product labels to signify an immediate haz‐ard. The signal words WARNING, CAUTION, andNOTE will be used on product labels and through‐out this manual and other manuals that may applyto the product.

DANGER - Immediate hazards which will result insevere personal injury or death.

WARNING - Hazards or unsafe practices whichcould result in severe personal injury or death.

CAUTION - Hazards or unsafe practices whichmay result in minor personal injury or product orproperty damage.

NOTE - Used to highlight suggestions which willresult in enhanced installation, reliability, or opera‐tion.

Signal Words in Manuals

The signal word WARNING is used throughout thismanual in the following manner:

The signal word CAUTION is used throughout thismanual in the following manner:

Signal Words on Product Labeling

Signal words are used in combination with colorsand/or pictures on product labels.

WARNING

Safety Labeling and Signal Words

!

! CAUTION

WARNING

TABLE OF CONTENTSWiring Diagrams 2 - 3. . . . . . . . . . . . . . . . . . . . . . . . . . . .

Charging Chart 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Tech Labels (Expanded Data) 5 - 11. . . . . . . . . . . . . . . .

Condenser Only Data 12 - 15. . . . . . . . . . . . . . . . . . . . . .

Cooling Multipying Factors 16 - 21. . . . . . . . . . . . . . . . . .

Exploded Drawings 22 - 24. . . . . . . . . . . . . . . . . . . . . . . .

C4A4 Parts List 25 - 27. . . . . . . . . . . . . . . . . . . . . . . . . . .

H4A4 Parts List 28 - 30. . . . . . . . . . . . . . . . . . . . . . . . . . .

T4A34Parts List 31 - 33. . . . . . . . . . . . . . . . . . . . . . . . . . .

Model Number Identification 34. . . . . . . . . . . . . . . . . . . .

! WARNING

DEATH, PERSONAL INJURY, AND/OR PROPERTYDAMAGE HAZARD

Failure to carefully read and follow this warningcould result in equipment malfunction, propertydamage, personal injury and/or death.

Installation or repairs made by unqualified per‐sons could result in equipment malfunction, prop‐erty damage, personal injury and/or death.

The information contained in this manual is in‐tended for use by a qualified service technician fa‐miliar with safety procedures and equipped withthe proper tools and test instruments.

Installation must conform with local buildingcodes and with the National Electrical CodeNFPA70 current edition or Canadian ElectricalCode Part 1 CSA C.22.1.

Page 2: TECHNICAL SUPPORT MANUAL Split System Air Conditioner …icpindexing.toddsit.com/documents/003350/42104550001.pdf · 2007-08-29 · TECHNICAL SUPPORT MANUAL Split System Air Conditioner:

TE

CH

NIC

AL

SU

PP

OR

T M

AN

UA

LS

plit S

ystem A

ir Co

nd

ition

er: (C,H

,T)4A

4

2421 04 5500 01

Model Sizes: 18, 24, 30, 36, 42, 48

1. Symbols are electrical representation only. 2. Compressor and fan motor furnished with inherent thermal protection. 3. To be wired in accordance with National Electric N.E.C. and local codes. 4. N.E.C. class 2, 24 V circuit, min. 40 VA required, 60 VA on units installed with LLS. 5. Use copper conductors only. Use conductors suitable for at least 75°C (167°F). 6. Connection for typical cooling only thermostat. For other arrangements see installation instructions. 7. If indoor section has a transformer with a grounded secondary, connect the grounded side to the BRN/YEL lead. 8. When start capacitor and relay are installed, start thermistor is not used. 9. CH not used on all units. 10. If any of the original wire, as supplied, must be replaced, use the same or equivalent wire. 11. Check all electrical connections inside control box for tightness. 12. Do not attempt to operate unit until service valves have been opened. 13. Do not rapid cycle compressor. Compressor must be off 3 minutes to allow pressures to equalize between high and low side before starting. 14. Wire not present if HPS, LPS or CTD are used. 15. Not for interrupting current.

Page 3: TECHNICAL SUPPORT MANUAL Split System Air Conditioner …icpindexing.toddsit.com/documents/003350/42104550001.pdf · 2007-08-29 · TECHNICAL SUPPORT MANUAL Split System Air Conditioner:

TE

CH

NIC

AL

SU

PP

OR

T M

AN

UA

LS

plit S

ystem A

ir Co

nd

ition

er: (C,H

,T)4A

4

421 04 5500 013

Model Size: 60

1. Symbols are electrical representation only. 2. Compressor and fan motor furnished with inherent thermal protection. 3. To be wired in accordance with National Electric N.E.C. and local codes. 4. N.E.C. class 2, 24 V circuit, min. 40 VA required, 60 VA on units installed with LLS. 5. Use copper conductors only. Use conductors suitable for at least 75°C (167°F). 6. Connection for typical cooling only thermostat. For other arrangements see installation instructions. 7. If indoor section has a transformer with a grounded secondary, connect the grounded side to the BRN/YEL lead. 8. When start capacitor and relay are installed, start thermistor is not used. 9. CH not used on all units. 10. If any of the original wire, as supplied, must be replaced, use the same or equivalent wire. 11. Check all electrical connections inside control box for tightness. 12. Do not attempt to operate unit until service valves have been opened. 13. Do not rapid cycle compressor. Compressor must be off 3 minutes to allow pressures to equalize between high and low side before starting. 14. Wire not present if HPS, LPS or CTD are used. 15. Not for interrupting current.

Page 4: TECHNICAL SUPPORT MANUAL Split System Air Conditioner …icpindexing.toddsit.com/documents/003350/42104550001.pdf · 2007-08-29 · TECHNICAL SUPPORT MANUAL Split System Air Conditioner:

TECHNICAL SUPPORT MANUAL Split System Air Conditioner: (C,H,T)4A4

4 421 04 5500 01

R-410A CHARGING CHART� Find the required Subcooling Temperature on the unit Rating Plate. Use the closest column on the chart below

(6, 8, 10, 12, 14 or 16) .

� Add or remove refrigerant until both the Liquid Line Temperature and Liquid Pressure agree with chart data.

Measured Liquid Pressure (psig)

Rating Plate (required) Subcooling Temperature (°F)

6 8 10 12 14 16

Required Liquid Line Temperature (°F)

189 60 58 56 54 52 50

195 62 60 58 56 54 52

202 64 62 60 58 56 54

208 66 64 62 60 58 56

215 68 66 64 62 60 58

222 70 68 66 64 62 60

229 72 70 68 66 64 62

236 74 72 70 68 66 64

243 76 74 72 70 68 66

251 78 76 74 72 70 68

259 80 78 76 74 72 70

266 82 80 78 76 74 72

274 84 82 80 78 76 74

283 86 84 82 80 78 76

291 88 86 84 82 80 78

299 90 88 86 84 82 80

308 92 90 88 86 84 82

317 94 92 90 88 86 84

326 96 94 92 90 88 86

335 98 96 94 92 90 88

345 100 98 96 94 92 90

354 102 100 98 96 94 92

364 104 102 100 98 96 94

374 106 104 102 100 98 96

384 108 106 104 102 100 98

395 110 108 106 104 102 100

406 112 110 108 106 104 102

416 114 112 110 108 106 104

427 116 114 112 110 108 106

439 118 116 114 112 110 108

450 120 118 116 114 112 110

462 122 120 118 116 114 112

474 124 122 120 118 116 114

486 126 124 122 120 118 116

499 128 126 124 122 120 118

511 130 128 126 124 122 120

Page 5: TECHNICAL SUPPORT MANUAL Split System Air Conditioner …icpindexing.toddsit.com/documents/003350/42104550001.pdf · 2007-08-29 · TECHNICAL SUPPORT MANUAL Split System Air Conditioner:

TE

CH

NIC

AL

SU

PP

OR

T M

AN

UA

LS

plit S

ystem A

ir Co

nd

ition

er: (C,H

,T)4A

4

421 04 5500 015

† Total capacities are net (I.D. blower heat subtracted) system capacities based on 25' line set. If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur.

†† At TVA rating indoor condition (75 °F db, 63 °F wb), all other indoor air temperatures are at 80 °F db If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur.

^ System amps are total of indoor and outdoor amps.

‡ Chart data is for 80° F indoor dry bulb. For indoor db temperatures other than 80° F, measure Indoor db and Indoor CFM, and plug these into the formula below. Measure outdoor db and indoor wet bulb, apply these to the chart above, find MBh and S/T, and plug these into the formula below. (Note: if indoor db is the only thing changing, total capacity, MBh, stays the same.)

Sensible Capacity at Indoor db LOWER than 80 °F = ( MBh x S/T ) - ( 80 - Indoor db ) x 835 x Indoor CFM1000( )

Sensible Capacity at Indoor db HIGHER than 80 °F = ( MBh x S/T ) +( Indoor db - 80 ) x 835 x Indoor CFM

1000( )

Page 6: TECHNICAL SUPPORT MANUAL Split System Air Conditioner …icpindexing.toddsit.com/documents/003350/42104550001.pdf · 2007-08-29 · TECHNICAL SUPPORT MANUAL Split System Air Conditioner:

TE

CH

NIC

AL

SU

PP

OR

T M

AN

UA

LS

plit S

ystem A

ir Co

nd

ition

er: (C,H

,T)4A

4

6421 04 5500 01

† Total capacities are net (I.D. blower heat subtracted) system capacities based on 25' line set. If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur.

†† At TVA rating indoor condition (75 °F db, 63 °F wb), all other indoor air temperatures are at 80 °F db If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur.

^ System amps are total of indoor and outdoor amps.

‡ Chart data is for 80° F indoor dry bulb. For indoor db temperatures other than 80° F, measure Indoor db and Indoor CFM, and plug these into the formula below. Measure outdoor db and indoor wet bulb, apply these to the chart above, find MBh and S/T, and plug these into the formula below. (Note: if indoor db is the only thing changing, total capacity, MBh, stays the same.)

Sensible Capacity at Indoor db LOWER than 80 °F = ( MBh x S/T ) - ( 80 - Indoor db ) x 835 x Indoor CFM1000( )

Sensible Capacity at Indoor db HIGHER than 80 °F = ( MBh x S/T ) +( Indoor db - 80 ) x 835 x Indoor CFM

1000( )

Page 7: TECHNICAL SUPPORT MANUAL Split System Air Conditioner …icpindexing.toddsit.com/documents/003350/42104550001.pdf · 2007-08-29 · TECHNICAL SUPPORT MANUAL Split System Air Conditioner:

TE

CH

NIC

AL

SU

PP

OR

T M

AN

UA

LS

plit S

ystem A

ir Co

nd

ition

er: (C,H

,T)4A

4

421 04 5500 017

† Total capacities are net (I.D. blower heat subtracted) system capacities based on 25' line set. If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur.

†† At TVA rating indoor condition (75 °F db, 63 °F wb), all other indoor air temperatures are at 80 °F db If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur.

^ System amps are total of indoor and outdoor amps.

‡ Chart data is for 80° F indoor dry bulb. For indoor db temperatures other than 80° F, measure Indoor db and Indoor CFM, and plug these into the formula below. Measure outdoor db and indoor wet bulb, apply these to the chart above, find MBh and S/T, and plug these into the formula below. (Note: if indoor db is the only thing changing, total capacity, MBh, stays the same.)

Sensible Capacity at Indoor db LOWER than 80 °F = ( MBh x S/T ) - ( 80 - Indoor db ) x 835 x Indoor CFM1000( )

Sensible Capacity at Indoor db HIGHER than 80 °F = ( MBh x S/T ) +( Indoor db - 80 ) x 835 x Indoor CFM

1000( )

Page 8: TECHNICAL SUPPORT MANUAL Split System Air Conditioner …icpindexing.toddsit.com/documents/003350/42104550001.pdf · 2007-08-29 · TECHNICAL SUPPORT MANUAL Split System Air Conditioner:

TE

CH

NIC

AL

SU

PP

OR

T M

AN

UA

LS

plit S

ystem A

ir Co

nd

ition

er: (C,H

,T)4A

4

8421 04 5500 01

† Total capacities are net (I.D. blower heat subtracted) system capacities based on 25' line set. If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur.

†† At TVA rating indoor condition (75 °F db, 63 °F wb), all other indoor air temperatures are at 80 °F db If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur.

^ System amps are total of indoor and outdoor amps.

‡ Chart data is for 80° F indoor dry bulb. For indoor db temperatures other than 80° F, measure Indoor db and Indoor CFM, and plug these into the formula below. Measure outdoor db and indoor wet bulb, apply these to the chart above, find MBh and S/T, and plug these into the formula below. (Note: if indoor db is the only thing changing, total capacity, MBh, stays the same.)

Sensible Capacity at Indoor db LOWER than 80 °F = ( MBh x S/T ) - ( 80 - Indoor db ) x 835 x Indoor CFM1000( )

Sensible Capacity at Indoor db HIGHER than 80 °F = ( MBh x S/T ) +( Indoor db - 80 ) x 835 x Indoor CFM

1000( )

Page 9: TECHNICAL SUPPORT MANUAL Split System Air Conditioner …icpindexing.toddsit.com/documents/003350/42104550001.pdf · 2007-08-29 · TECHNICAL SUPPORT MANUAL Split System Air Conditioner:

TE

CH

NIC

AL

SU

PP

OR

T M

AN

UA

LS

plit S

ystem A

ir Co

nd

ition

er: (C,H

,T)4A

4

421 04 5500 019

† Total capacities are net (I.D. blower heat subtracted) system capacities based on 25' line set. If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur.

†† At TVA rating indoor condition (75 °F db, 63 °F wb), all other indoor air temperatures are at 80 °F db If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur.

^ System amps are total of indoor and outdoor amps.

‡ Chart data is for 80° F indoor dry bulb. For indoor db temperatures other than 80° F, measure Indoor db and Indoor CFM, and plug these into the formula below. Measure outdoor db and indoor wet bulb, apply these to the chart above, find MBh and S/T, and plug these into the formula below. (Note: if indoor db is the only thing changing, total capacity, MBh, stays the same.)

Sensible Capacity at Indoor db LOWER than 80 °F = ( MBh x S/T ) - ( 80 - Indoor db ) x 835 x Indoor CFM1000( )

Sensible Capacity at Indoor db HIGHER than 80 °F = ( MBh x S/T ) +( Indoor db - 80 ) x 835 x Indoor CFM

1000( )

Page 10: TECHNICAL SUPPORT MANUAL Split System Air Conditioner …icpindexing.toddsit.com/documents/003350/42104550001.pdf · 2007-08-29 · TECHNICAL SUPPORT MANUAL Split System Air Conditioner:

TE

CH

NIC

AL

SU

PP

OR

T M

AN

UA

LS

plit S

ystem A

ir Co

nd

ition

er: (C,H

,T)4A

4

10421 04 5500 01

† Total capacities are net (I.D. blower heat subtracted) system capacities based on 25' line set. If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur.

†† At TVA rating indoor condition (75 °F db, 63 °F wb), all other indoor air temperatures are at 80 °F db If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur.

^ System amps are total of indoor and outdoor amps.

‡ Chart data is for 80° F indoor dry bulb. For indoor db temperatures other than 80° F, measure Indoor db and Indoor CFM, and plug these into the formula below. Measure outdoor db and indoor wet bulb, apply these to the chart above, find MBh and S/T, and plug these into the formula below. (Note: if indoor db is the only thing changing, total capacity, MBh, stays the same.)

Sensible Capacity at Indoor db LOWER than 80 °F = ( MBh x S/T ) - ( 80 - Indoor db ) x 835 x Indoor CFM1000( )

Sensible Capacity at Indoor db HIGHER than 80 °F = ( MBh x S/T ) +( Indoor db - 80 ) x 835 x Indoor CFM

1000( )

Page 11: TECHNICAL SUPPORT MANUAL Split System Air Conditioner …icpindexing.toddsit.com/documents/003350/42104550001.pdf · 2007-08-29 · TECHNICAL SUPPORT MANUAL Split System Air Conditioner:

TE

CH

NIC

AL

SU

PP

OR

T M

AN

UA

LS

plit S

ystem A

ir Co

nd

ition

er: (C,H

,T)4A

4

421 04 5500 0111

† Total capacities are net (I.D. blower heat subtracted) system capacities based on 25' line set. If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur.

†† At TVA rating indoor condition (75 °F db, 63 °F wb), all other indoor air temperatures are at 80 °F db If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur.

^ System amps are total of indoor and outdoor amps.

‡ Chart data is for 80° F indoor dry bulb. For indoor db temperatures other than 80° F, measure Indoor db and Indoor CFM, and plug these into the formula below. Measure outdoor db and indoor wet bulb, apply these to the chart above, find MBh and S/T, and plug these into the formula below. (Note: if indoor db is the only thing changing, total capacity, MBh, stays the same.)

Sensible Capacity at Indoor db LOWER than 80 °F = ( MBh x S/T ) - ( 80 - Indoor db ) x 835 x Indoor CFM1000( )

Sensible Capacity at Indoor db HIGHER than 80 °F = ( MBh x S/T ) +( Indoor db - 80 ) x 835 x Indoor CFM

1000( )

Page 12: TECHNICAL SUPPORT MANUAL Split System Air Conditioner …icpindexing.toddsit.com/documents/003350/42104550001.pdf · 2007-08-29 · TECHNICAL SUPPORT MANUAL Split System Air Conditioner:

TECHNICAL SUPPORT MANUAL Split System Air Conditioner: (C,H,T)4A4

12 421 04 5500 01

Data for Condenser Only (Cooling)

Saturated SuctionTemperature °F

Condenser Entering Air Temperature °F

55 65 75 85 95 105 115 125

(C,H,T)4A418

30TCG 16.20 15.30 14.30 13.40 12.40 11.40 10.30 9.20SDT 65.80 75.30 84.80 94.40 103.90 113.40 122.90 132.40KW 0.79 0.90 1.02 1.16 1.31 1.48 1.65 1.83

35TCG 17.80 16.90 15.80 14.80 13.80 12.70 11.50 10.40SDT 66.80 76.20 85.70 95.20 104.70 114.20 123.60 133.10KW 0.78 0.89 1.02 1.16 1.31 1.48 1.66 1.85

40TCG 19.60 18.50 17.50 16.30 15.20 14.00 12.80 11.50SDT 67.80 77.20 86.60 96.10 105.50 114.90 124.40 133.80KW 0.78 0.89 1.02 1.16 1.31 1.48 1.66 1.85

45TCG 21.50 20.40 19.20 18.00 16.70 15.50 14.20 12.80SDT 68.80 78.30 87.60 97.00 106.40 115.80 125.10 134.40KW 0.77 0.89 1.01 1.15 1.31 1.48 1.66 1.86

50TCG 23.50 22.30 21.00 19.70 18.40 17.00 15.60 14.10SDT 70.00 79.40 88.70 98.00 107.30 116.60 125.90 135.20KW 0.77 0.88 1.01 1.15 1.31 1.48 1.66 1.86

55TCG 25.60 24.30 22.90 21.50 20.00 18.50 17.00 15.40SDT 71.10 80.40 89.80 99.00 108.30 117.50 126.70 135.90KW 0.76 0.88 1.01 1.15 1.30 1.47 1.66 1.86

(C,H,T)4A424

30TCG 21.50 20.30 19.10 17.90 16.70 15.40 14.50 12.70SDT 68.90 78.20 87.60 97.00 106.40 115.90 122.50 134.80KW 0.96 1.10 1.26 1.44 1.64 1.85 2.02 2.34

35TCG 23.70 22.40 21.10 19.80 18.40 17.10 16.10 14.20SDT 70.10 79.40 88.70 98.10 107.40 116.80 123.40 135.50KW 0.97 1.11 1.27 1.45 1.64 1.86 2.03 2.35

40TCG 26.10 24.60 23.20 21.80 20.30 18.80 17.80 15.70SDT 71.40 80.60 89.90 99.20 108.50 117.80 124.30 136.30KW 0.97 1.11 1.27 1.45 1.65 1.87 2.03 2.36

45TCG 28.50 27.00 25.50 23.90 22.30 20.70 19.50 17.20SDT 72.80 82.00 91.10 100.30 109.60 118.80 125.20 137.10KW 0.98 1.12 1.28 1.46 1.66 1.88 2.04 2.37

50TCG 31.10 29.50 27.80 26.10 24.30 22.60 21.30 18.80SDT 74.20 83.30 92.40 101.60 110.70 119.80 126.20 138.00KW 0.98 1.13 1.29 1.47 1.66 1.88 2.05 2.38

55TCG 33.80 32.00 30.20 28.30 26.40 24.50 23.10 20.50SDT 75.70 84.80 93.80 102.80 111.80 120.90 127.20 138.80KW 0.99 1.13 1.29 1.47 1.67 1.89 2.05 2.38

TCG = Gross Cooling Capacity (x 1000 BTU/hr)SDT = Saturated Temperature Leaving CompressorkW = Outdoor Unit Kilowatts

Page 13: TECHNICAL SUPPORT MANUAL Split System Air Conditioner …icpindexing.toddsit.com/documents/003350/42104550001.pdf · 2007-08-29 · TECHNICAL SUPPORT MANUAL Split System Air Conditioner:

TECHNICAL SUPPORT MANUAL Split System Air Conditioner: (C,H,T)4A4

421 04 5500 01 13

Data for Condenser Only (Cooling)

Saturated SuctionTemperature °F

Condenser Entering Air Temperature °F

55 65 75 85 95 105 115 125

(C,H,T)4A430

30TCG 26.40 25.00 23.60 22.10 20.60 19.00 17.30 15.60SDT 68.50 77.80 87.20 96.60 106.00 115.40 124.80 134.20KW 1.26 1.43 1.62 1.83 2.07 2.32 2.59 2.87

35TCG 29.10 27.60 26.00 24.50 22.80 21.10 19.30 17.40SDT 69.70 79.00 88.40 97.70 107.10 116.40 125.70 135.10KW 1.26 1.44 1.63 1.84 2.08 2.33 2.61 2.90

40TCG 32.00 30.40 28.70 27.00 25.20 23.40 21.50 19.40SDT 71.10 80.30 89.60 98.90 108.20 117.40 126.70 135.90KW 1.27 1.44 1.63 1.85 2.08 2.34 2.62 2.92

45TCG 35.10 33.30 31.50 29.70 27.80 25.80 23.80 21.60SDT 72.50 81.70 90.90 100.10 109.30 118.50 127.70 136.80KW 1.28 1.45 1.64 1.86 2.09 2.35 2.64 2.94

50TCG 38.40 36.50 34.50 32.60 30.50 28.40 26.20 23.80SDT 74.00 83.10 92.20 101.40 110.50 119.60 128.70 137.80KW 1.29 1.46 1.65 1.87 2.10 2.36 2.65 2.95

55TCG 41.90 39.80 37.80 35.60 33.40 31.10 28.80 26.20SDT 75.50 84.60 93.70 102.70 111.80 120.80 129.80 138.80KW 1.30 1.47 1.66 1.88 2.12 2.38 2.66 2.97

(C,H,T)4A436

30TCG 33.30 31.50 29.60 27.80 25.80 23.80 21.60 19.30SDT 68.30 77.50 86.70 96.00 105.30 114.60 123.90 133.20KW 1.54 1.75 1.97 2.22 2.49 2.79 3.10 3.43

35TCG 36.60 34.70 32.70 30.70 28.60 26.40 24.10 21.60SDT 69.60 78.70 87.90 97.10 106.30 115.60 124.80 134.00KW 1.55 1.75 1.98 2.23 2.51 2.80 3.12 3.46

40TCG 40.20 38.10 36.00 33.80 31.50 29.10 26.60 24.00SDT 71.00 80.00 89.10 98.20 107.40 116.60 125.70 134.80KW 1.56 1.76 1.99 2.24 2.52 2.82 3.15 3.49

45TCG 44.10 41.80 39.50 37.10 34.60 32.00 29.30 26.40SDT 72.50 81.40 90.40 99.40 108.50 117.60 126.70 135.70KW 1.58 1.78 2.00 2.25 2.53 2.84 3.16 3.52

50TCG 48.10 45.70 43.20 40.60 37.90 35.10 32.10 29.00SDT 74.00 82.80 91.80 100.70 109.70 118.70 127.70 136.60KW 1.59 1.79 2.02 2.27 2.55 2.85 3.18 3.54

55TCG 52.50 49.80 47.10 44.20 41.30 38.30 35.00 31.60SDT 75.70 84.40 93.20 102.10 111.00 119.90 128.70 137.50KW 1.61 1.81 2.03 2.28 2.56 2.87 3.20 3.55

TCG = Gross Cooling Capacity (x 1000 BTU/hr)SDT = Saturated Temperature Leaving CompressorkW = Outdoor Unit Kilowatts

Page 14: TECHNICAL SUPPORT MANUAL Split System Air Conditioner …icpindexing.toddsit.com/documents/003350/42104550001.pdf · 2007-08-29 · TECHNICAL SUPPORT MANUAL Split System Air Conditioner:

TECHNICAL SUPPORT MANUAL Split System Air Conditioner: (C,H,T)4A4

14 421 04 5500 01

Data for Condenser Only (Cooling)

Saturated SuctionTemperature °F

Condenser Entering Air Temperature °F

55 65 75 85 95 105 115 125

(C,H,T)4A442

30TCG 38.80 36.70 34.60 32.40 30.20 27.90 25.50 22.90SDT 68.90 78.20 87.50 96.90 106.20 115.50 124.80 134.00KW 1.80 2.03 2.28 2.57 2.88 3.22 3.58 3.98

35TCG 42.80 40.50 38.20 35.80 33.40 30.90 28.20 25.40SDT 70.30 79.50 88.70 98.00 107.30 116.50 125.70 134.90KW 1.84 2.07 2.32 2.60 2.92 3.26 3.63 4.03

40TCG 47.00 44.50 42.00 39.40 36.80 34.00 31.10 28.00SDT 71.70 80.80 90.00 99.20 108.40 117.60 126.70 135.70KW 1.88 2.11 2.36 2.65 2.96 3.30 3.68 4.08

45TCG 51.50 48.80 46.10 43.30 40.40 37.30 34.20 30.80SDT 73.20 82.30 91.40 100.50 109.60 118.70 127.70 136.70KW 1.92 2.15 2.40 2.69 3.00 3.35 3.72 4.12

50TCG 56.30 53.40 50.40 47.30 44.10 40.80 37.40 33.60SDT 74.80 83.80 92.80 101.90 110.90 119.90 128.80 137.60KW 1.97 2.20 2.45 2.74 3.05 3.40 3.77 4.17

55TCG 61.30 58.20 54.90 51.60 48.10 44.50 40.70 36.60SDT 76.60 85.40 94.40 103.30 112.20 121.10 129.90 138.60KW 2.02 2.25 2.50 2.79 3.10 3.45 3.82 4.22

(C,H,T)4A448

30TCG 45.10 42.50 39.90 37.30 34.70 32.00 29.30 26.40SDT 69.80 79.00 88.20 97.40 106.70 115.90 125.20 134.40KW 2.03 2.34 2.67 3.03 3.42 3.83 4.27 4.74

35TCG 49.80 46.90 44.00 41.20 38.30 35.30 32.30 29.10SDT 71.30 80.40 89.50 98.60 107.80 117.00 126.10 135.20KW 2.01 2.33 2.67 3.04 3.43 3.85 4.30 4.77

40TCG 54.80 51.60 48.50 45.30 42.10 38.90 35.50 31.90SDT 72.90 81.80 90.80 99.90 109.00 118.10 127.10 136.10KW 2.00 2.32 2.67 3.04 3.44 3.87 4.32 4.80

45TCG 60.10 56.70 53.20 49.70 46.20 42.60 38.90 35.00SDT 74.50 83.40 92.30 101.30 110.20 119.20 128.20 137.00KW 1.98 2.31 2.66 3.04 3.45 3.88 4.34 4.83

50TCG 65.80 62.00 58.20 54.40 50.50 46.60 42.50 38.10SDT 76.30 85.00 93.80 102.70 111.60 120.40 129.30 138.00KW 1.96 2.29 2.65 3.04 3.45 3.89 4.36 4.85

55TCG 71.80 67.70 63.50 59.30 55.00 50.70 46.20 41.40SDT 78.20 86.80 95.50 104.20 113.00 121.70 130.40 139.00KW 1.94 2.28 2.64 3.03 3.45 3.90 4.37 4.86

TCG = Gross Cooling Capacity (x 1000 BTU/hr)SDT = Saturated Temperature Leaving CompressorkW = Outdoor Unit Kilowatts

Page 15: TECHNICAL SUPPORT MANUAL Split System Air Conditioner …icpindexing.toddsit.com/documents/003350/42104550001.pdf · 2007-08-29 · TECHNICAL SUPPORT MANUAL Split System Air Conditioner:

TECHNICAL SUPPORT MANUAL Split System Air Conditioner: (C,H,T)4A4

421 04 5500 01 15

Data for Condenser Only (Cooling)Saturated Suction

Temperature °FCondenser Entering Air Temperature °F

55 65 75 85 95 105 115 125(C,H,T)4A460

30TCG 55.90 53.00 50.00 49.10 43.80 40.60 37.20 33.70SDT 73.50 82.50 91.60 94.30 109.80 119.00 128.10 137.20KW 2.60 2.93 3.30 3.41 4.16 4.65 5.19 5.77

35TCG 61.50 58.30 55.10 54.10 48.40 44.90 41.20 37.30SDT 75.20 84.20 93.20 95.90 111.20 120.30 129.30 138.20KW 2.65 2.98 3.35 3.46 4.21 4.71 5.25 5.83

40TCG 67.60 64.10 60.50 59.50 53.20 49.40 45.40 41.10SDT 77.00 85.90 94.80 97.50 112.70 121.60 130.50 139.30KW 2.70 3.03 3.40 3.52 4.27 4.76 5.30 5.89

45TCG 74.00 70.20 66.30 65.20 58.40 54.20 49.70 45.00SDT 79.00 87.70 96.50 99.20 114.20 123.00 131.80 140.50KW 2.76 3.09 3.46 3.58 4.33 4.82 5.36 5.95

50TCG 80.80 76.70 72.50 71.20 63.70 59.10 54.30 49.10SDT 81.00 89.70 98.40 101.00 115.80 124.50 133.10 141.70KW 2.83 3.16 3.53 3.65 4.39 4.89 5.43 6.01

55TCG 88.00 83.50 78.90 77.50 69.40 64.30 59.00 53.30SDT 83.20 91.70 100.30 102.90 117.50 126.00 134.50 142.90KW 2.90 3.23 3.60 3.72 4.46 4.96 5.49 6.07

TCG = Gross Cooling Capacity (x 1000 BTU/hr)SDT = Saturated Temperature Leaving CompressorkW = Outdoor Unit Kilowatts

Page 16: TECHNICAL SUPPORT MANUAL Split System Air Conditioner …icpindexing.toddsit.com/documents/003350/42104550001.pdf · 2007-08-29 · TECHNICAL SUPPORT MANUAL Split System Air Conditioner:

TE

CH

NIC

AL

SU

PP

OR

T M

AN

UA

LS

plit S

ystem A

ir Co

nd

ition

er: (C,H

,T)4A

4

16421 04 5500 01

COOLING Multiplying Factors for other Indoor Combinations

IndoorModel

FurnaceModel Capac. (MBh) Power (AMPS)

IndoorModel

FurnaceModel Capac. (MBh) Power (AMPS)

IndoorModel

FurnaceModel Capac. (MBh) Power (AMPS)

(C,H,T)4A418>ED*4X24B** 1.00 1.00 EHD4X24A** *9MPV050 1.03 0.99 EXX*24B**** MV08B15**** 1.02 0.98

EBP24**** 1.00 1.03 EHD4X24A** *9MPV075 1.03 0.99 EXX*24F**** 1.01 1.03

EBV24**** 1.03 0.99 EHD4X24A** MV08B15**** 1.00 0.96 EXX*24F**** *9MPV050 1.04 1.00

EBXX18**** 1.00 1.03 EHD4X24A** MV12F19**** 0.99 0.95 EXX*24F**** MV12F19**** 1.01 0.97

EBXX24**** 0.99 0.99 EL*18B**** MV08B15**** 0.93 0.93 FEM4X18**** 1.01 0.97

ED*4X18B** 0.98 1.01 EL*24B**** MV08B15**** 0.97 0.93 FEM4X24**** 1.02 0.98

ED*4X18B** MV08B15**** 0.99 0.95 EMA4X24D** 1.00 1.00 FS(M,U)4X18*** 0.98 1.01

ED*4X24B** MV08B15**** 1.02 0.98 EP*18B**** MV08B15**** 0.93 0.93 FS(M,U)4X24*** 1.01 1.01

ED*4X24F** 1.00 1.00 EP*24B**** MV08B15**** 0.97 0.93 FSA2X24**** 1.00 1.00

ED*4X24F** MV12F19**** 1.02 0.98 EP*24F**** MV12F19**** 0.97 0.93 FVM4X24**** 1.01 0.97

EHD4X24A** 1.00 1.00 EXX*24B**** 1.01 1.03 FWM18**** 0.96 0.99

(C,H,T)4A424>ED*4X30B** 1.00 1.00 EHD4X24A** 0.98 0.97 EP*24B**** MV08B15**** 0.93 0.91

EBP24**** 0.97 0.98 EHD4X24A** *8MPV050 0.99 0.97 EP*24F**** *9MPV050 0.92 0.92

EBP30**** 0.97 0.99 EHD4X24A** *8MPV100 1.01 0.96 EP*24F**** *9MPV075 0.92 0.92

EBV24**** 1.00 0.95 EHD4X24A** *8MPV125 1.01 0.96 EP*24F**** MV12F19**** 0.93 0.91

EBV36**** 1.01 0.96 EHD4X24A** *9MPV050 0.99 0.97 EP*30B**** *8MPV050 0.94 0.93

EBXX18**** 0.97 0.98 EHD4X24A** *9MPV075 0.99 0.97 EP*30B**** MV08B15**** 0.95 0.93

EBXX24**** 0.97 0.99 EHD4X24A** *9MPV100 1.00 0.95 EP*30F**** *9MPV050 0.94 0.93

ED*4X24B** 0.98 1.00 EHD4X24A** MV08B15**** 1.00 0.95 EP*30F**** *9MPV075 0.94 0.93

ED*4X24B** *8MPV050 0.99 0.97 EHD4X24A** MV12F19**** 1.00 0.95 EP*30F**** MV12F19**** 0.95 0.90

ED*4X24B** MV08B15**** 1.00 0.95 EHD4X24A** MV16J22**** 1.01 0.96 EXX*24B**** 0.97 0.99

ED*4X24B** *9MPV050 0.98 0.94 EHD4X24A** MV20N26**** 0.99 0.94 EXX*24B**** *8MPV050 0.98 0.96

ED*4X24B** *9MPV075 0.98 0.94 EHD4X30A** 0.99 0.98 EXX*24B**** MV08B15**** 0.99 0.94

ED*4X24F** 0.98 1.00 EHD4X30A** *8MPV050 0.99 0.94 EXX*24F**** 0.97 0.99

ED*4X24F** *9MPV050 0.99 0.94 EHD4X30A** *9MPV050 1.00 0.95 EXX*24F**** *8MPV075 0.99 0.97

> Indicates Tested Indoor Model

- continued on next page -

Page 17: TECHNICAL SUPPORT MANUAL Split System Air Conditioner …icpindexing.toddsit.com/documents/003350/42104550001.pdf · 2007-08-29 · TECHNICAL SUPPORT MANUAL Split System Air Conditioner:

TE

CH

NIC

AL

SU

PP

OR

T M

AN

UA

LS

plit S

ystem A

ir Co

nd

ition

er: (C,H

,T)4A

4

421 04 5500 0117

COOLING Multiplying Factors for other Indoor Combinations (continued)

IndoorModel Power (AMPS)Capac. (MBh)

FurnaceModel

IndoorModelPower (AMPS)Capac. (MBh)

FurnaceModel

IndoorModelPower (AMPS)Capac. (MBh)

FurnaceModel

ED*4X24F** *9MPV075 1.00 0.95 EHD4X30A** *9MPV075 1.00 0.95 EXX*24F**** *9MPV050 0.98 0.96

ED*4X24F** MV12F19**** 1.00 0.95 EHD4X30A** *9MPV100 1.01 0.96 EXX*24F**** *9MPV075 0.98 0.96

ED*4X30B** *8MPV050 1.00 0.95 EHD4X30A** MV08B15**** 1.01 0.96 EXX*24F**** MV12F19**** 0.99 0.94

ED*4X30B** MV08B15**** 1.00 0.95 EHD4X30A** MV12F19**** 1.00 0.95 FEM4X24**** 0.99 0.94

ED*4X30B** *9MPV050 0.99 0.94 EHD4X30A** MV16J22**** 1.02 0.97 FEM4X30**** 1.00 0.95

ED*4X30B** *9MPV075 0.99 0.94 EHD4X30A** MV20N26**** 1.01 0.96 FS(M,U)4X24*** 0.97 0.99

ED*4X30F** 0.99 0.99 EHD4X36A** 0.99 0.98 FS(M,U)4X30*** 0.98 0.97

ED*4X30F** *9MPV050 0.99 0.94 EL*24B**** *8MPV050 0.92 0.94 FSA2X24**** 0.97 0.96

ED*4X30F** *9MPV075 1.00 0.95 EL*24B**** MV08B15**** 0.93 0.91 FVM4X24**** 0.99 0.91

ED*4X30F** MV12F19**** 1.02 0.97 EL*30B**** *8MPV050 0.94 0.93 FVM4X36**** 0.99 0.91

ED*4X36B** 0.99 0.98 EL*30B**** MV08B15**** 0.94 0.92 FWM24**** 0.95 0.96

ED*4X36B** 0.95 0.95 EMA4X24D** 0.98 0.99 FWM30**** 0.96 0.98

ED*4X36F** 0.99 0.98 EMA4X36D** 0.99 0.98

ED*4X36J** 0.99 0.98 EP*24B**** *8MPV050 0.92 0.94

(C,H,T)4A430>ED*4X36F** 1.00 1.00 EHD4X30A** *9MPV125 1.01 0.97 EP*36B**** MV08B15**** 0.97 0.97

EBP30**** 0.97 1.00 EHD4X30A** MV08B15**** 1.01 0.97 EP*36F**** 0.95 0.98

EBP36**** 0.97 1.00 EHD4X30A** MV12F19**** 1.01 0.97 EP*36F**** *8MPV075 0.97 0.97

EBV24**** 1.00 0.98 EHD4X30A** MV16J22**** 1.02 0.98 EP*36F**** *9MPV050 0.97 0.99

EBV36**** 1.01 0.97 EHD4X30A** MV20N26**** 1.02 0.98 EP*36F**** *9MPV075 0.97 0.99

EBXX36**** 0.99 1.02 EHD4X36A** 1.00 1.00 EP*36F**** MV12F19**** 0.97 0.96

ED*4X30B** 0.99 1.02 EHD4X36A** *8MPV050 1.02 1.00 EP*36J**** 0.95 0.98

ED*4X30B** MV08B15**** 1.00 0.96 EHD4X36A** *8MPV075 1.02 0.98 EP*36J**** *8MPV100 0.97 0.96

ED*4X30B** *9MPV075 0.99 0.99 EHD4X36A** *8MPV100 1.01 0.97 EP*36J**** *8MPV125 0.97 0.96

ED*4X30B** *8MPV075 1.01 0.99 EHD4X36A** *8MPV125 1.01 0.97 EP*36J**** *9MPV100 0.97 0.97

ED*4X30B** *9MPV075 0.99 0.98 EHD4X36A** *9MPV050 1.01 0.99 EP*36J**** MV16J22**** 0.97 0.93

ED*4X30F** 0.99 1.02 EHD4X36A** *9MPV075 1.01 1.00 EXX*36B**** 0.99 1.02

ED*4X30F** *8MPV075 1.01 1.00 EHD4X36A** *9MPV100 1.01 0.97 EXX*36B**** *8MPV050 1.01 1.01

> Indicates Tested Indoor Model

- continued on next page -

Page 18: TECHNICAL SUPPORT MANUAL Split System Air Conditioner …icpindexing.toddsit.com/documents/003350/42104550001.pdf · 2007-08-29 · TECHNICAL SUPPORT MANUAL Split System Air Conditioner:

TE

CH

NIC

AL

SU

PP

OR

T M

AN

UA

LS

plit S

ystem A

ir Co

nd

ition

er: (C,H

,T)4A

4

18421 04 5500 01

COOLING Multiplying Factors for other Indoor Combinations (continued)

IndoorModel Power (AMPS)Capac. (MBh)

FurnaceModel

IndoorModelPower (AMPS)Capac. (MBh)

FurnaceModel

IndoorModelPower (AMPS)Capac. (MBh)

FurnaceModel

ED*4X30F** *9MPV075 1.01 1.00 EHD4X36A** *9MPV125 1.02 0.98 EXX*36B**** MV08B15**** 1.02 0.98

ED*4X30F** MV12F19**** 1.01 0.97 EHD4X36A** MV08B15**** 1.01 0.97 EXX*36F**** 0.99 1.02

ED*4X36B** 0.97 0.97 EHD4X36A** MV12F19**** 1.01 0.97 EXX*36F**** *8MPV075 1.01 1.00

ED*4X36B** MV08B15**** 0.97 0.93 EHD4X36A** MV16J22**** 1.01 0.97 EXX*36F**** *9MPV050 1.01 1.01

ED*4X36B** *8MPV075 1.01 0.99 EHD4X36A** MV20N26**** 1.02 1.02 EXX*36F**** *9MPV075 1.01 1.01

ED*4X36B** *9MPV075 1.00 0.98 EHD4X42A** 1.00 1.00 EXX*36F**** MV12F19**** 1.01 0.97

ED*4X36F** *8MPV075 1.02 1.00 EL*30B**** MV08B15**** 0.94 0.96 EXX*36J**** 0.99 1.02

ED*4X36F** *9MPV075 1.01 1.00 EL*36B**** 0.95 0.98 EXX*36J**** *8MPV100 1.01 0.97

ED*4X36F** MV12F19**** 1.02 0.98 EL*36B**** *8MPV050 0.97 0.99 EXX*36J**** *8MPV125 1.01 0.97

ED*4X36J** 0.99 0.99 EL*36B**** MV08B15**** 0.97 0.97 EXX*36J**** *9MPV100 1.01 0.97

ED*4X36J** *8MPV100 1.03 0.99 EL*36F**** 0.95 0.98 EXX*36J**** MV16J22**** 1.01 0.97

ED*4X36J** *8MPV125 1.02 0.98 EL*36F**** *8MPV075 0.97 0.97 FEM4X30**** 0.99 0.98

ED*4X36J** *9MPV100 1.02 0.98 EL*36F**** *9MPV050 0.97 0.99 FEM4X36**** 1.02 1.00

ED*4X36J** MV16J22**** 1.03 0.99 EL*36F**** *9MPV075 0.97 0.99 FS(M,U)4X30*** 0.99 0.99

ED*4X42J** 1.00 1.00 EL*36F**** MV12F19**** 0.97 0.96 FSA2X30**** 0.98 1.00

ED*4X42L** 1.00 1.00 EMA4X36D** 0.99 0.99 FSA2X36**** 1.01 1.01

EHD4X30A** 0.99 0.99 EMH36F**** 0.95 0.98 FSM4X36**** 1.02 1.00

EHD4X30A** *8MPV050 1.01 1.00 EP*30B**** MV08B15**** 0.94 0.96 FSU4X36**** 1.01 1.03

EHD4X30A** *8MPV075 1.01 1.00 EP*30F**** *8MPV075 0.94 0.96 FVM4X24**** 0.99 0.95

EHD4X30A** *8MPV100 1.01 0.97 EP*30F**** MV12F19**** 0.93 0.93 FVM4X36**** 0.99 0.92

EHD4X30A** *8MPV125 1.00 0.96 EP*36B**** 0.95 0.98 FWM30**** 0.97 0.99

EHD4X30A** *9MPV100 1.00 0.98 EP*36B**** *8MPV050 0.97 0.99

(C,H,T)4A436>ED*4X42J** 1.00 1.00 EHD4X36A** *9MPV125 1.01 0.96 EP*42F**** *9MPV075 0.97 0.99

EBP42**** 0.99 1.01 EHD4X36A** MV08B15**** 1.00 0.95 EP*42F**** MV12F19**** 0.98 0.96

EBV36**** 1.00 0.98 EHD4X36A** MV12F19**** 1.01 0.96 EP*42J**** 0.97 0.99

EBV48**** 1.04 0.99 EHD4X36A** MV16J22**** 1.02 0.97 EP*42J**** *8MPV100 0.97 0.98

EBXX36**** 0.99 1.01 EHD4X36A** MV20N26**** 1.02 0.97 EP*42J**** *8MPV125 0.98 0.99

> Indicates Tested Indoor Model

- continued on next page -

Page 19: TECHNICAL SUPPORT MANUAL Split System Air Conditioner …icpindexing.toddsit.com/documents/003350/42104550001.pdf · 2007-08-29 · TECHNICAL SUPPORT MANUAL Split System Air Conditioner:

TE

CH

NIC

AL

SU

PP

OR

T M

AN

UA

LS

plit S

ystem A

ir Co

nd

ition

er: (C,H

,T)4A

4

421 04 5500 0119

COOLING Multiplying Factors for other Indoor Combinations (continued)

IndoorModel Power (AMPS)Capac. (MBh)

FurnaceModel

IndoorModelPower (AMPS)Capac. (MBh)

FurnaceModel

IndoorModelPower (AMPS)Capac. (MBh)

FurnaceModel

ED*4X36B** 0.96 0.98 EHD4X42A** 1.00 0.99 EP*42J**** *9MPV100 0.97 1.00

ED*4X36B** *8MPV050 0.95 0.94 EHD4X42A** *8MPV075 1.01 0.96 EP*42J**** MV16J22**** 0.99 0.98

ED*4X36B** MV08B15**** 0.97 0.95 EHD4X42A** *8MPV100 1.01 0.96 EXX*36B**** 0.98 1.00

ED*4X36F** 0.99 1.01 EHD4X42A** *8MPV125 1.01 0.96 EXX*36B**** MV08B15**** 1.00 0.98

ED*4X36F** *8MPV075 1.00 0.99 EHD4X42A** *9MPV075 1.01 0.98 EXX*36F**** 0.98 1.00

ED*4X36F** *9MPV075 0.99 0.99 EHD4X42A** *9MPV100 1.01 0.96 EXX*36F**** *8MPV075 1.00 0.99

ED*4X36F** MV12F19**** 1.01 0.96 EHD4X42A** *9MPV125 1.02 0.97 EXX*36F**** *9MPV075 0.99 1.01

ED*4X36J** 0.99 1.01 EHD4X42A** MV08B15**** 1.01 0.96 EXX*36F**** MV12F19**** 1.00 0.95

ED*4X36J** *8MPV100 1.01 0.96 EHD4X42A** MV12F19**** 1.01 0.96 EXX*36J**** 0.99 1.01

ED*4X36J** *8MPV125 1.01 0.96 EHD4X42A** MV16J22**** 1.02 0.97 EXX*36J**** *8MPV100 1.01 0.99

ED*4X36J** *9MPV100 1.00 0.98 EHD4X42A** MV20N26**** 1.02 0.97 EXX*36J**** *8MPV125 1.01 0.99

ED*4X36J** MV16J22**** 1.00 0.95 EHD4X48A** 1.01 1.00 EXX*36J**** *9MPV100 0.99 0.97

ED*4X42F** 1.00 1.03 EL*36B**** MV08B15**** 0.95 0.97 EXX*36J**** MV16J22**** 1.02 0.97

ED*4X42F** *8MPV075 1.01 1.00 EL*36F**** *8MPV075 0.95 0.97 EXX*42F**** 1.01 1.00

ED*4X42F** *9MPV050 0.99 0.99 EL*36F**** *9MPV075 0.94 0.98 EXX*42F**** *8MPV075 1.01 0.99

ED*4X42F** *9MPV075 0.99 0.99 EL*36F**** MV12F19**** 0.95 0.95 EXX*42F**** *9MPV050 1.00 1.02

ED*4X42F** MV12F19**** 1.02 0.97 EL*42F**** 0.97 0.99 EXX*42F**** *9MPV075 1.01 1.02

ED*4X42J** *8MPV100 1.01 0.96 EL*42F**** *8MPV075 0.98 0.97 EXX*42F**** MV12F19**** 1.01 0.96

ED*4X42J** *8MPV125 1.01 0.96 EL*42F**** *9MPV075 0.97 0.99 EXX*42J**** 1.01 1.00

ED*4X42J** *9MPV100 1.01 0.99 EL*42F**** MV12F19**** 0.98 0.96 EXX*42J**** *8MPV100 1.02 1.00

ED*4X42J** MV16J22**** 1.03 0.98 EMA4X36D** 0.99 1.01 EXX*42J**** *8MPV125 1.02 0.97

ED*4X42L** 1.00 1.00 EMA4X48D** 0.98 0.97 EXX*42J**** *9MPV100 1.02 1.01

ED*4X42L** *9MPV125 1.02 0.97 EMH42F**** 0.97 0.99 EXX*42J**** MV16J22**** 1.03 0.98

ED*4X48F** 0.98 0.97 EP*36B**** MV08B15**** 0.94 0.94 FEM4X36**** 1.03 0.98

ED*4X48J** 1.01 1.00 EP*36F**** *8MPV075 0.95 0.97 FEM4X36****

ED*4X48L** 1.01 1.00 EP*36F**** MV12F19**** 0.95 0.95 FEM4X42**** 1.02 0.97

EHD4X36A** 0.99 1.01 EP*36J**** *8MPV100 0.96 0.98 FEM4X42****

EHD4X36A** *8MPV075 1.00 0.98 EP*36J**** *8MPV125 0.96 0.95 FS(M,U)4X42*** 1.01 1.01

> Indicates Tested Indoor Model

- continued on next page -

Page 20: TECHNICAL SUPPORT MANUAL Split System Air Conditioner …icpindexing.toddsit.com/documents/003350/42104550001.pdf · 2007-08-29 · TECHNICAL SUPPORT MANUAL Split System Air Conditioner:

TE

CH

NIC

AL

SU

PP

OR

T M

AN

UA

LS

plit S

ystem A

ir Co

nd

ition

er: (C,H

,T)4A

4

20421 04 5500 01

COOLING Multiplying Factors for other Indoor Combinations (continued)

IndoorModel Power (AMPS)Capac. (MBh)

FurnaceModel

IndoorModelPower (AMPS)Capac. (MBh)

FurnaceModel

IndoorModelPower (AMPS)Capac. (MBh)

FurnaceModel

EHD4X36A** *8MPV100 1.00 0.95 EP*36J**** *9MPV100 0.95 0.97 FSM4X36**** 1.01 1.00

EHD4X36A** *8MPV125 1.01 0.96 EP*36J**** MV16J22**** 0.97 0.94 FSU4X36**** 0.98 1.00

EHD4X36A** *9MPV075 0.99 0.97 EP*42F**** 0.97 0.99 FVM4X36**** 0.99 0.94

EHD4X36A** *9MPV100 0.99 0.95 EP*42F**** *8MPV075 0.98 0.97 FVM4X48**** 1.02 0.94

(C,H,T)4A442>ED*4X48J** 1.00 1.00 EHD4X42A** *9MPV100 0.99 0.96 EP*48J**** *8MPV125 0.98 0.97

EBP42**** 0.98 1.01 EHD4X42A** *9MPV125 0.99 0.96 EP*48J**** *9MPV100 0.98 0.98

EBP48**** 0.99 1.02 EHD4X42A** MV16J22**** 0.99 0.94 EP*48J**** MV16J22**** 0.99 0.96

EBV48**** 1.02 0.97 EHD4X42A** MV20N26**** 0.99 0.94 EP*48L**** 0.98 1.00

EBXX48**** 1.00 1.00 EHD4X48A** 1.00 0.99 EP*48L**** *9MPV125 0.98 0.97

ED*4X42F** 0.98 1.01 EHD4X48A** *8MPV100 1.00 0.95 EP*48N**** 0.98 1.00

ED*4X42F** *8MPV075 0.98 0.99 EHD4X48A** *8MPV125 1.00 0.95 EP*48N**** MV20N26**** 0.98 0.93

ED*4X42F** *9MPV075 0.96 1.00 EHD4X48A** *9MPV100 1.00 0.98 EXX*42F**** 0.98 0.99

ED*4X42J** 0.98 0.99 EHD4X48A** *9MPV125 1.00 0.98 EXX*42F**** *8MPV075 0.99 1.00

ED*4X42J** *8MPV100 0.99 0.96 EHD4X48A** MV16J22**** 1.00 0.95 EXX*42J**** 0.98 0.99

ED*4X42J** *8MPV125 0.99 0.96 EHD4X48A** MV20N26**** 1.00 0.95 EXX*42J**** *8MPV100 1.00 0.99

ED*4X42J** MV16J22**** 0.99 0.94 EHD4X60A** 1.01 1.00 EXX*42J**** *8MPV125 0.99 0.96

ED*4X42L** 0.98 0.99 EL*42F**** 0.93 0.96 EXX*42J**** *9MPV100 0.99 1.02

ED*4X42L** *9MPV125 0.99 0.96 EL*48F**** 0.96 0.99 EXX*42J**** MV16J22**** 1.00 0.95

ED*4X48F** 0.98 0.97 EL*48F**** *8MPV075 0.96 0.99 EXX*48J**** 0.99 1.00

ED*4X48J** *8MPV100 1.00 0.95 EMA4X48D** 0.98 0.98 EXX*48J**** *9MPV125 0.99 0.96

ED*4X48J** *8MPV125 1.00 0.95 EMH42F**** 0.93 0.96 EXX*48L**** 0.99 1.00

ED*4X48J** *9MPV100 1.00 0.98 EMH48F**** 0.96 0.99 EXX*48L**** *9MPV125 0.99 0.96

ED*4X48J** MV16J22**** 1.00 0.95 EP*42F**** 0.93 0.96 EXX*48N**** 0.99 1.00

ED*4X48L** 1.00 1.00 EP*42J**** 0.94 0.97 EXX*48N**** MV20N26**** 0.99 0.94

ED*4X48L** *9MPV125 1.01 0.99 EP*42J**** *8MPV125 0.94 0.97 FEM4X42**** 1.00 0.98

ED*4X60J** 1.00 0.99 EP*42J**** MV16J22**** 0.94 0.94 FEM4X48**** 1.02 0.97

ED*4X60L** 1.01 1.00 EP*48F**** 0.96 0.99 FS(M,U)4X42*** 0.99 1.00

> Indicates Tested Indoor Model

- continued on next page -

Page 21: TECHNICAL SUPPORT MANUAL Split System Air Conditioner …icpindexing.toddsit.com/documents/003350/42104550001.pdf · 2007-08-29 · TECHNICAL SUPPORT MANUAL Split System Air Conditioner:

TE

CH

NIC

AL

SU

PP

OR

T M

AN

UA

LS

plit S

ystem A

ir Co

nd

ition

er: (C,H

,T)4A

4

421 04 5500 0121

COOLING Multiplying Factors for other Indoor Combinations (continued)

IndoorModel Power (AMPS)Capac. (MBh)

FurnaceModel

IndoorModelPower (AMPS)Capac. (MBh)

FurnaceModel

IndoorModelPower (AMPS)Capac. (MBh)

FurnaceModel

EHD4X42A** 0.98 0.98 EP*48F**** *8MPV075 0.96 0.99 FS(M,U)4X48*** 1.00 1.00

EHD4X42A** *8MPV100 0.99 0.94 EP*48J**** 0.98 1.00 FVM4X48**** 1.01 0.93

EHD4X42A** *8MPV125 0.99 0.96 EP*48J**** *8MPV100 0.99 0.98

(C,H,T)4A448>ED*4X60L** 1.00 1.00 EHD4X48A** MV20N26**** 0.99 0.97 EXX*48J**** 0.96 0.98

EBV48**** 1.00 0.98 EHD4X60A** 1.00 1.00 EXX*48L**** 0.96 0.98

EBV60**** 1.01 0.99 EHD4X60A** *8MPV125 1.00 0.98 EXX*48N**** 0.96 0.98

EBXX48**** 0.98 1.00 EHD4X60A** *9MPV125 1.00 0.98 EXX*48N**** MV20N26**** 0.98 0.98

EBXX60**** 1.00 1.03 EHD4X60A** MV16J22**** 1.00 0.96 EXX*60L**** 1.00 1.00

ED*4X48F** 0.95 0.97 EHD4X60A** MV20N26**** 1.00 0.96 EXX*60L**** *9MPV125 1.00 1.00

ED*4X48J** 0.97 0.99 EL*60J**** 0.96 0.98 EXX*60N**** 1.00 1.00

ED*4X48J** MV16J22**** 0.99 0.97 EL*60J**** MV16J22**** 0.97 0.97 EXX*60N**** MV20N26**** 1.02 0.98

ED*4X48L** 0.97 0.99 EMA4X48D** 0.97 0.99 FEM4X48**** 1.00 0.98

ED*4X60J** 1.00 1.00 EP*48N**** MV20N26**** 0.96 0.96 FEM4X60**** 1.01 0.97

ED*4X60J** *8MPV125 1.01 0.99 EP*60J**** 0.96 0.98 FS(M,U)4X48*** 0.98 1.00

ED*4X60J** MV16J22**** 1.00 0.96 EP*60J**** MV16J22**** 0.98 0.98 FS(M,U)4X60*** 1.00 1.00

ED*4X60J** *8MPV100 1.01 0.97 EP*60L**** 0.96 0.98 FVM4X48**** 0.99 0.95

EHD4X48A** 0.97 0.97 EP*60N**** 0.96 0.98 FVM4X60**** 1.00 0.92

EHD4X48A** MV16J22**** 0.99 0.97 EP*60N**** MV20N26**** 0.98 0.96

EHD4X60A** *8MPV125 1.00 0.98 EXX*48N**** 0.96 0.98

(C,H,T)4A460>ED*4X60L** 1.00 1.00 EHD4X60A** MV20N26**** 1.03 0.99 EXX*60N**** 1.01 1.02

EBP60**** 0.98 1.03 EP*60J**** *8MPV125 0.96 0.99 EXX*60N**** MV20N26**** 1.02 0.98

EBV60**** 1.01 0.98 EP*60J**** MV16J22**** 0.97 0.98 FEM4X60**** 1.01 0.98

EBXX60**** 1.00 1.02 EP*60N**** MV20N26**** 0.97 0.98 FS(M,U)4X60*** 0.99 1.01

ED*4X60J** 0.98 0.98 EXX*60L**** 1.01 1.02 FVM4X60**** 1.01 0.98

EHD4X60A** 1.00 1.00 EXX*60L**** *9MPV125 1.01 1.02

> Indicates Tested Indoor Model

Page 22: TECHNICAL SUPPORT MANUAL Split System Air Conditioner …icpindexing.toddsit.com/documents/003350/42104550001.pdf · 2007-08-29 · TECHNICAL SUPPORT MANUAL Split System Air Conditioner:

TECHNICAL SUPPORT MANUAL Split System Air Conditioner: (C,H,T)4A4

22 421 04 5500 01

B

L

A

232

3

C3

F

D E

G

R

JC4

H1

H2

C1

K1

K2

S

C2

Top Cover

Grill Inlet

CornerPost

GrilleInlet

AccessPanel

MotorFan

Raceway

Fan

ControlBoxCoverControl

Box

ServicePanel

AccessPanel

GrilleInlet

PlateFiller

PlateFiller

BasePan

KickPlate

GrilleInlet

MotorCap

FanGuard

Nut

NOTE: This illustration is forreference only. Your unit maydiffer in appearance or may notinclude all components shown.Please refer to Parts List forexact parts listing.

Page 23: TECHNICAL SUPPORT MANUAL Split System Air Conditioner …icpindexing.toddsit.com/documents/003350/42104550001.pdf · 2007-08-29 · TECHNICAL SUPPORT MANUAL Split System Air Conditioner:

TECHNICAL SUPPORT MANUAL Split System Air Conditioner: (C,H,T)4A4

421 04 5500 01 23

6

9

27

35

7

17

1

11

10

N

G

19

8

36

Condenser, CoilAssembly

Blanket ,Sound( When Used )

Compressor

Bolt, SHLDR (4)

Heater, CRKC( When Used )

Switch, LowPressure

Valve ServiceSuction

GrommetCompressor

SupportCoil

BasePan

Switch Temp.CC Heater(When Used)

Valve Service,Liquid

Switch, HighPressure

Plug, Compressor

,

,24Filter Drier

NOTE: This illustration is forreference only. Your unit maydiffer in appearance or may notinclude all components shown.Please refer to Parts List forexact parts listing.

Page 24: TECHNICAL SUPPORT MANUAL Split System Air Conditioner …icpindexing.toddsit.com/documents/003350/42104550001.pdf · 2007-08-29 · TECHNICAL SUPPORT MANUAL Split System Air Conditioner:

TECHNICAL SUPPORT MANUAL Split System Air Conditioner: (C,H,T)4A4

24 421 04 5500 01

25

D

21

5

P

433

34

Box, Control

HarnessAssembly

Lug, Ground

Contactor

Strap,Capacitor

Capacitor

CTL, 2 SPD Fan

Module, CompressorDiagnostics

NOTE: This illustration is forreference only. Your unit maydiffer in appearance or may notinclude all components shown.Please refer to Parts List forexact parts listing.

Page 25: TECHNICAL SUPPORT MANUAL Split System Air Conditioner …icpindexing.toddsit.com/documents/003350/42104550001.pdf · 2007-08-29 · TECHNICAL SUPPORT MANUAL Split System Air Conditioner:

TECHNICAL SUPPORT MANUAL Split System Air Conditioner: (C,H,T)4A4

421 04 5500 01 25

C4A4 PARTS LIST

KEYNO. DESCRIPTION PART NO. C

4A41

8GK

A10

0

C4A

424G

KA

100

C4A

430G

KA

100

C4A

436G

KA

100

C4A

442G

KA

100

C4A

448G

KA

100

C4A

460G

KA

100

1 Compressor ZP16K5EPFV130 1 - - - - - -

1 ZP20K5EPFV130 - 1 - - - -

1 ZP25K5EPFV130 - - 1 - - - -

1 ZP31K5EPFV130 - - - 1 - - -

1 ZP36K5EPFV130 - - - - 1 - -

1 ZP42K5EPFV130 - - - - - 1 -

1 ZP51K5EPFV130 - - - - - - 1

2 Motor, Condenser Fan 1173773 1 1 - - - - -

2 1173774 - - 1 - - - -

2 1173776 - - - 1 1 - -

2 1173779 - - - - - 1 1

3 Fan Blade 1173787 1 1 - - - - -

3 1173790 - - 1 - - - -

3 1173661 - - - 1 1 - -

3 1172716 - - - - - 1 1

4 Contactor, 30 Amp 1172472 1 1 1 1 1 1 -

4 40 Amp 1172786 - - - - - - 1

5 Capacitor, 370V 30+5 Mfd 1172109 1 - - - - - -

5 370V 35+5 Mfd 1172110 - 1 - - - - -

5 370V 40+5 Mfd 1172147 - - 1 - - - -

5 370V 45+5 Mfd 1172124 - - - 1 1 - -

5 370V 70+7.5 Mfd 1172295 - - - - - 1 1

6 Condenser Coil 1173964 1 1 - - - - -

6 1173983 - - 1 1 - - -

6 1173985 - - - - 1 1 1

7 Service Valve, Suction 1172725 1 1 - - - - -

7 1172726 - - 1 1 - - -

7 1172727 - - - - 1 1 1

8 Service Valve, Liquid 1172728 1 1 1 1 1 1 1

9 Plug, Compressor Harness 1174682 1 1 1 1 - - -

9 1174685 - - - - 1 1 -

9 1174686 - - - - - - 1

10 Isolator, Vibration 1172271 4 4 4 4 - - -

10 Grommet, Compressor 1171270 - - - - 4 4 4

11 Nut, Hex Washer Face 5/16-18 1174289 4 4 4 4 - - -

11 Bolt, Compressor Mounting 1173630 - - - - 4 4 4

17 Switch, Low Pressure 1174683 1 1 1 1 1 1 1

19 Switch, High Pressure 1174684 1 1 1 1 1 1 1- continued on next page -

Page 26: TECHNICAL SUPPORT MANUAL Split System Air Conditioner …icpindexing.toddsit.com/documents/003350/42104550001.pdf · 2007-08-29 · TECHNICAL SUPPORT MANUAL Split System Air Conditioner:

TECHNICAL SUPPORT MANUAL Split System Air Conditioner: (C,H,T)4A4

26 421 04 5500 01

C4A4 PARTS LIST

KEYNO. C

4A46

0GK

A10

0

C4A

448G

KA

100

C4A

442G

KA

100

C4A

436G

KA

100

C4A

430G

KA

100

C4A

424G

KA

100

C4A

418G

KA

100

PART NO.DESCRIPTION

20 Distributor 1173667 - - - - 1 1 1

21 Control, 2 Speed Fan 1088977 1 1 1 1 1 1 1

24 Drier 1174195 1 1 1 1 1 1 -

24 1174196 - - - - - - 1

25 Module, Comfort Alert 1173907 1 1 1 1 1 1 1

27 Blanket, Compressor Sound 1172015 1 1 1 1 - - -

27 1172014 - - - - 1 1 1

32 Raceway 1173908 1 1 - - - - -

32 1173664 - - 1 1 1 1 1

33 Lug, Ground 1172300 1 1 1 1 1 1 1

34 Harness Assy Plug and Play 1173909 1 1 1 - - - -

34 1173920 - - - 1 1 1 -

34 1173951 - - - - - - 1

A Panel, Top 1173910 1 1 - - - - -

A 1173924 - - 1 1 1 1 1

B Nut, Hex 1172217 4 4 4 4 4 4 4

C1 Grille, Inlet 1173965 1 1 - - - - -

C1 1173945 - - 1 1 - - -

C1 1173925 - - - - 1 1 1

C2 Grille, Inlet 1173967 1 1 - - - - -

C2 1173981 - - 1 1 - - -

C2 1173928 - - - - 1 1 1

C3 Grille, Inlet 1173966 1 1 - - - - -

C3 1173946 - - 1 1 - - -

C3 1173926 - - - - 1 1 1

C4 Grille, Inlet 1173947 - - 1 1 - - -

C4 1173927 - - - - 1 1 1

D Box, Control 1172753 1 1 1 1 1 1 1

E Cover, Control Box 1174065 1 1 1 1 1 1 1

F Panel, Service 1174077 1 1 - - - - -

F 1174080 - - 1 1 - - -

F 1174085 - - - - 1 1 1

G Pan, Base 1174076 1 1 - - - - -

G 1174081 - - 1 1 1 1 1

H Panel, Access 1173968 1 1 - - - - -

H1 Panel, Access 1173948 - - 1 1 - - -

H1 1173929 - - - - 1 1 1- continued on next page -

Page 27: TECHNICAL SUPPORT MANUAL Split System Air Conditioner …icpindexing.toddsit.com/documents/003350/42104550001.pdf · 2007-08-29 · TECHNICAL SUPPORT MANUAL Split System Air Conditioner:

TECHNICAL SUPPORT MANUAL Split System Air Conditioner: (C,H,T)4A4

421 04 5500 01 27

C4A4 PARTS LIST

KEYNO. C

4A46

0GK

A10

0

C4A

448G

KA

100

C4A

442G

KA

100

C4A

436G

KA

100

C4A

430G

KA

100

C4A

424G

KA

100

C4A

418G

KA

100

PART NO.DESCRIPTION

H2 Panel, Access 1173984 - - 1 1 - - -

H2 1173930 - - - - 1 1 1

J Post, Corner 1173969 2 2 - - - - -

J 1173915 - - 3 3 - - -

J 1173931 - - - - 3 3 3

K Plate, Filler 1173916 1 1 - - - - -

K1 Plate, Filler 1173932 - - 1 1 1 1 1

K2 Plate, Filler 1173933 - - 1 1 1 1 1

L Guard, Fan 1173917 1 1 - - - - -

L 1173934 - - 1 1 1 1 1

N Support, Coil 1174068 4 4 4 4 5 5 5

P Strap, Capacitor 1172734 1 1 1 1 1 - -

P 1172735 - - - - - 1 1

R Cap Assy Heil 1174025 1 1 1 1 1 1 1

)( Manual, Installation 42101510001 1 1 1 1 1 1 1

)( Manual, Owners 42102500000 1 1 1 1 1 1 1

)( Warranty 40106401002 1 1 1 1 1 1 1

Page 28: TECHNICAL SUPPORT MANUAL Split System Air Conditioner …icpindexing.toddsit.com/documents/003350/42104550001.pdf · 2007-08-29 · TECHNICAL SUPPORT MANUAL Split System Air Conditioner:

TECHNICAL SUPPORT MANUAL Split System Air Conditioner: (C,H,T)4A4

28 421 04 5500 01

H4A4 PARTS LIST

KEYNO. DESCRIPTION PART NO. H

4A41

8GK

A10

0

H4A

424G

KA

100

H4A

430G

KA

100

H4A

436G

KA

100

H4A

442G

KA

100

H4A

448G

KA

100

H4A

460G

KA

100

1 Compressor ZP16K5EPFV130 1 - - - - - -

1 ZP20K5EPFV130 - 1 - - - -

1 ZP25K5EPFV130 - - 1 - - - -

1 ZP31K5EPFV130 - - - 1 - - -

1 ZP36K5EPFV130 - - - - 1 - -

1 ZP42K5EPFV130 - - - - - 1 -

1 ZP51K5EPFV130 - - - - - - 1

2 Motor, Condenser Fan 1173773 1 1 - - - - -

2 1173774 - - 1 - - - -

2 1173776 - - - 1 1 - -

2 1173779 - - - - - 1 1

3 Fan Blade 1173787 1 1 - - - - -

3 1173790 - - 1 - - - -

3 1173661 - - - 1 1 - -

3 1172716 - - - - - 1 1

4 Contactor, 30 Amp 1172472 1 1 1 1 1 1 -

4 40 Amp 1172786 - - - - - - 1

5 Capacitor, 370V 30+5 Mfd 1172109 1 - - - - - -

5 370V 35+5 Mfd 1172110 - 1 - - - - -

5 370V 40+5 Mfd 1172147 - - 1 - - - -

5 370V 45+5 Mfd 1172124 - - - 1 1 - -

5 370V 70+7.5 Mfd 1172295 - - - - - 1 1

6 Condenser Coil 1173964 1 1 - - - - -

6 1173983 - - 1 1 - - -

6 1173985 - - - - 1 1 1

7 Service Valve, Suction 1172725 1 1 - - - - -

7 1172726 - - 1 1 - - -

7 1172727 - - - - 1 1 1

8 Service Valve, Liquid 1172728 1 1 1 1 1 1 1

9 Plug, Compressor Harness 1174682 1 1 1 1 - - -

9 1174685 - - - - 1 1 -

9 1174686 - - - - - - 1

10 Isolator, Vibration 1172271 4 4 4 4 - - -

10 Grommet, Compressor 1171270 - - - - 4 4 4

11 Nut, Hex Washer Face 5/16-18 1174289 4 4 4 4 - - -

11 Bolt, Compressor Mounting 1173630 - - - - 4 4 4

17 Switch, Low Pressure 1174683 1 1 1 1 1 1 1

19 Switch, High Pressure 1174684 1 1 1 1 1 1 1- continued on next page -

Page 29: TECHNICAL SUPPORT MANUAL Split System Air Conditioner …icpindexing.toddsit.com/documents/003350/42104550001.pdf · 2007-08-29 · TECHNICAL SUPPORT MANUAL Split System Air Conditioner:

TECHNICAL SUPPORT MANUAL Split System Air Conditioner: (C,H,T)4A4

421 04 5500 01 29

H4A4 PARTS LIST

KEYNO. H

4A46

0GK

A10

0

H4A

448G

KA

100

H4A

442G

KA

100

H4A

436G

KA

100

H4A

430G

KA

100

H4A

424G

KA

100

H4A

418G

KA

100

PART NO.DESCRIPTION

20 Distributor 1173667 - - - - 1 1 1

21 Control, 2 Speed Fan 1088977 1 1 1 1 1 1 1

24 Drier 1174195 1 1 1 1 1 1 -

24 1174196 - - - - - - 1

25 Module, Comfort Alert 1173907 1 1 1 1 1 1 1

27 Blanket, Compressor Sound 1172015 1 1 1 1 - - -

27 1172014 - - - - 1 1 1

32 Raceway 1173908 1 1 - - - - -

32 1173664 - - 1 1 1 1 1

33 Lug, Ground 1172300 1 1 1 1 1 1 1

34 Harness Assy Plug and Play 1173909 1 1 1 - - - -

34 1173920 - - - 1 1 1 -

34 1173951 - - - - - - 1

A Panel, Top 1174019 1 1 - - - - -

A 1174026 - - 1 1 1 1 1

B Nut, Hex 1172217 4 4 4 4 4 4 4

C1 Grille, Inlet 1174037 1 1 - - - - -

C1 1174046 - - 1 1 - - -

C1 1174027 - - - - 1 1 1

C2 Grille, Inlet 1174039 1 1 - - - - -

C2 1174049 - - 1 1 - - -

C2 1174030 - - - - 1 1 1

C3 Grille, Inlet 1174038 1 1 - - - - -

C3 1174047 - - 1 1 - - -

C3 1174028 - - - - 1 1 1

C4 Grille, Inlet 1174048 - - 1 1 - - -

C4 1174029 - - - - 1 1 1

D Box, Control 1172753 1 1 1 1 1 1 1

E Cover, Control Box 1174065 1 1 1 1 1 1 1

F Panel, Service 1174077 1 1 - - - - -

F 1174080 - - 1 1 - - -

F 1174085 - - - - 1 1 1

G Pan, Base 1174076 1 1 - - - - -

G 1174081 - - 1 1 1 1 1

H Panel, Access 1173968 1 1 - - - - -

H1 Panel, Access 1173948 - - 1 1 - - -

H1 1173929 - - - - 1 1 1

H2 Panel, Access 1173984 - - 1 1 - - -- continued on next page -

Page 30: TECHNICAL SUPPORT MANUAL Split System Air Conditioner …icpindexing.toddsit.com/documents/003350/42104550001.pdf · 2007-08-29 · TECHNICAL SUPPORT MANUAL Split System Air Conditioner:

TECHNICAL SUPPORT MANUAL Split System Air Conditioner: (C,H,T)4A4

30 421 04 5500 01

H4A4 PARTS LIST

KEYNO. H

4A46

0GK

A10

0

H4A

448G

KA

100

H4A

442G

KA

100

H4A

436G

KA

100

H4A

430G

KA

100

H4A

424G

KA

100

H4A

418G

KA

100

PART NO.DESCRIPTION

H2 1173930 - - - - 1 1 1

J Post, Corner 1174040 2 2 - - - - -

J 1174023 - - 3 3 - - -

J 1174031 - - - - 3 3 3

K Plate, Filler 1173916 1 1 - - - - -

K1 Plate, Filler 1173932 - - 1 1 1 1 1

K2 Plate, Filler 1173933 - - 1 1 1 1 1

L Guard, Fan 1174024 1 1 - - - - -

L 1174032 - - 1 1 1 1 1

N Support, Coil 1174068 4 4 4 4 5 5 5

P Strap, Capacitor 1172734 1 1 1 1 1 - -

P 1172735 - - - - - 1 1

R Cap Assy Heil 1174025 1 1 1 1 1 1 1

)( Manual, Installation 42101510001 1 1 1 1 1 1 1

)( Manual, Owners 42102500000 1 1 1 1 1 1 1

)( Warranty 40106401002 1 1 1 1 1 1 1

Page 31: TECHNICAL SUPPORT MANUAL Split System Air Conditioner …icpindexing.toddsit.com/documents/003350/42104550001.pdf · 2007-08-29 · TECHNICAL SUPPORT MANUAL Split System Air Conditioner:

TECHNICAL SUPPORT MANUAL Split System Air Conditioner: (C,H,T)4A4

421 04 5500 01 31

T4A4 PARTS LIST

KEYNO. DESCRIPTION PART NO. T

4A41

8GK

A10

0

T4A

424G

KA

100

T4A

430G

KA

100

T4A

436G

KA

100

T4A

442G

KA

100

T4A

448G

KA

100

T4A

460G

KA

100

1 Compressor ZP16K5EPFV130 1 - - - - - -

1 ZP20K5EPFV130 - 1 - - - -

1 ZP25K5EPFV130 - - 1 - - - -

1 ZP31K5EPFV130 - - - 1 - - -

1 ZP36K5EPFV130 - - - - 1 - -

1 ZP42K5EPFV130 - - - - - 1 -

1 ZP51K5EPFV130 - - - - - - 1

2 Motor, Condenser Fan 1173773 1 1 - - - - -

2 1173774 - - 1 - - - -

2 1173776 - - - 1 1 - -

2 1173779 - - - - - 1 1

3 Fan Blade 1173787 1 1 - - - - -

3 1173790 - - 1 - - - -

3 1173661 - - - 1 1 - -

3 1172716 - - - - - 1 1

4 Contactor, 30 Amp 1172472 1 1 1 1 1 1 -

4 40 Amp 1172786 - - - - - - 1

5 Capacitor, 370V 30+5 Mfd 1172109 1 - - - - - -

5 370V 35+5 Mfd 1172110 - 1 - - - - -

5 370V 40+5 Mfd 1172147 - - 1 - - - -

5 370V 45+5 Mfd 1172124 - - - 1 1 - -

5 370V 70+7.5 Mfd 1172295 - - - - - 1 1

6 Condenser Coil 1173964 1 1 - - - - -

6 1173983 - - 1 1 - - -

6 1173985 - - - - 1 1 1

7 Service Valve, Suction 1172725 1 1 - - - - -

7 1172726 - - 1 1 - - -

7 1172727 - - - - 1 1 1

8 Service Valve, Liquid 1172728 1 1 1 1 1 1 1

9 Plug, Compressor Harness 1174682 1 1 1 1 - - -

9 1174685 - - - - 1 1 -

9 1174686 - - - - - - 1

10 Isolator, Vibration 1172271 4 4 4 4 - - -

10 Grommet, Compressor 1171270 - - - - 4 4 4

11 Nut, Hex Washer Face 5/16-18 1174289 4 4 4 4 - - -

11 Bolt, Compressor Mounting 1173630 - - - - 4 4 4

17 Switch, Low Pressure 1174683 1 1 1 1 1 1 1

19 Switch, High Pressure 1174684 1 1 1 1 1 1 1- continued on next page -

Page 32: TECHNICAL SUPPORT MANUAL Split System Air Conditioner …icpindexing.toddsit.com/documents/003350/42104550001.pdf · 2007-08-29 · TECHNICAL SUPPORT MANUAL Split System Air Conditioner:

TECHNICAL SUPPORT MANUAL Split System Air Conditioner: (C,H,T)4A4

32 421 04 5500 01

T4A4 PARTS LIST

KEYNO. T

4A46

0GK

A10

0

T4A

448G

KA

100

T4A

442G

KA

100

T4A

436G

KA

100

T4A

430G

KA

100

T4A

424G

KA

100

T4A

418G

KA

100

PART NO.DESCRIPTION

20 Distributor 1173667 - - - - 1 1 1

21 Control, 2 Speed Fan 1088977 1 1 1 1 1 1 1

24 Drier 1174195 1 1 1 1 1 1 -

24 1174196 - - - - - - 1

25 Module, Comfort Alert 1173907 1 1 1 1 1 1 1

27 Blanket, Compressor Sound 1172015 1 1 1 1 - - -

27 1172014 - - - - 1 1 1

32 Raceway 1173908 1 1 - - - - -

32 1173664 - - 1 1 1 1 1

33 Lug, Ground 1172300 1 1 1 1 1 1 1

34 Harness Assy Plug and Play 1173909 1 1 1 - - - -

34 1173920 - - - 1 1 1 -

34 1173951 - - - - - - 1

A Panel, Top 1174102 1 1 - - - - -

A 1174110 - - 1 1 1 1 1

B Nut, Hex 1172217 4 4 4 4 4 4 4

C1 Grille, Inlet 1174131 1 1 - - - - -

C1 1174123 - - 1 1 - - -

C1 1174111 - - - - 1 1 1

C2 Grille, Inlet 1174133 1 1 - - - - -

C2 1174126 - - 1 1 - - -

C2 1174114 - - - - 1 1 1

C3 Grille, Inlet 1174132 1 1 - - - - -

C3 1174124 - - 1 1 - - -

C3 1174112 - - - - 1 1 1

C4 Grille, Inlet 1174125 - - 1 1 - - -

C4 1174113 - - - - 1 1 1

D Box, Control 1172753 1 1 1 1 1 1 1

E Cover, Control Box 1174065 1 1 1 1 1 1 1

F Panel, Service 1174077 1 1 - - - - -

F 1174080 - - 1 1 - - -

F 1174085 - - - - 1 1 1

G Pan, Base 1174076 1 1 - - - - -

G 1174081 - - 1 1 1 1 1

H Panel, Access 1173968 1 1 - - - - -

H1 Panel, Access 1173948 - - 1 1 - - -

H1 1173929 - - - - 1 1 1

H2 Panel, Access 1173984 - - 1 1 - - -- continued on next page -

Page 33: TECHNICAL SUPPORT MANUAL Split System Air Conditioner …icpindexing.toddsit.com/documents/003350/42104550001.pdf · 2007-08-29 · TECHNICAL SUPPORT MANUAL Split System Air Conditioner:

TECHNICAL SUPPORT MANUAL Split System Air Conditioner: (C,H,T)4A4

421 04 5500 01 33

T4A4 PARTS LIST

KEYNO. T

4A46

0GK

A10

0

T4A

448G

KA

100

T4A

442G

KA

100

T4A

436G

KA

100

T4A

430G

KA

100

T4A

424G

KA

100

T4A

418G

KA

100

PART NO.DESCRIPTION

H2 1173930 - - - - 1 1 1

J Post, Corner 1174134 2 2 - - - - -

J 1174106 - - 3 3 - - -

J 1174115 - - - - 3 3 3

K Plate, Filler 1173916 1 1 - - - - -

K1 Plate, Filler 1173932 - - 1 1 1 1 1

K2 Plate, Filler 1173933 - - 1 1 1 1 1

L Guard, Fan 1174107 1 1 - - - - -

L 1174116 - - 1 1 1 1 1

N Support, Coil 1174068 4 4 4 4 5 5 5

P Strap, Capacitor 1172734 1 1 1 1 1 - -

P 1172735 - - - - - 1 1

R Cap Assy Heil 1174025 1 1 1 1 1 1 1

S Kickplate 1174109 1 1 - - - - -

S 1174117 - - 1 1 1 1 1

)( Manual, Installation 42101510001 1 1 1 1 1 1 1

)( Manual, Owners 42102500000 1 1 1 1 1 1 1

)( Warranty 40106401002 1 1 1 1 1 1 1

Page 34: TECHNICAL SUPPORT MANUAL Split System Air Conditioner …icpindexing.toddsit.com/documents/003350/42104550001.pdf · 2007-08-29 · TECHNICAL SUPPORT MANUAL Split System Air Conditioner:

TECHNICAL SUPPORT MANUAL Split System Air Conditioner: (C,H,T)4A4

34 421 04 5500 01

OUTDOOR UNIT MODEL NUMBER IDENTIFICATION GUIDE (single phase)Digit Position: 1 2 3 4 5, 6 7 8 9 10 11 12

Example Part Number: H 4 A 4 18 A K A 1 0 0Product Family

2 = R-224 = R-410A REFRIGERANTA = Air ConditionerH = Heat Pump TYPE3 = 13 SEER4 = 14 SEER5 = 15 SEER6 = 16 SEER7 = 17 SEER8 = 18 SEER NOMINAL EFFICIENCY18 = 18,000 BTUH = 1½ tons24 = 24,000 BTUH = 2 tons30 = 30,000 BTUH = 2½ tons36 = 36,000 BTUH = 3 tons42 = 42,000 BTUH = 3½ tons48 = 48,000 BTUH = 4 tons60 = 60,000 BTUH = 5 tons NOMINAL CAPACITYA = Standard GrilleG = Coil Guard GrilleC = Coastal FEATURES

K = 208/230-1-60 VOLTAGE

Sales Code

Engineering Revision

Extra Digit

Extra Digit

ACCESSORIES PART NUMBER IDENTIFICATION GUIDEDigit Position: 1 2 3 4 5 6, 7 8, 9 10, 11

Example Part Number: N A S A 0 0 1 01 C H

N = Non-Branded BRANDING

A = Accessory PRODUCT GROUP

S = Split System (AC & HP) KIT USAGEA = OriginalB = 2nd Generation MAJOR SERIES0 = Generic or Not Applicable

2 = R-22

4 = R-410A REFRIGERANTProduct Identifier Number

Package Quantity

Type of Kit(Example: CH = Crankcase Heater)

International Comfort Products, LLC

Lewisburg, Tennessee 37091