    General Load Model

  • 8/10/2019 TechRef_Load[1].pdf

    2/26

    G e n e r a l L o a d M o d e l

    DIgSILENT GmbH

    Heinrich-Hertz-Strasse 9

    D-72810 Gomaringen

    Tel.: +49 7072 9168 - 0

    Fax: +49 7072 9168- 88

    http://www.digsilent.de

    e-mail: [email protected]

    General Load Model

    Published by

    DIgSILENT GmbH, Germany

    Copyright 2008. All rights

    reserved. Unauthorised copying

    or publishing of this or any part

    of this document is prohibited.

    TechRef ElmLod V4

    Build 507 30.10.2008

  • 8/10/2019 TechRef_Load[1].pdf

    3/26

    T a b l e o f C o n t e n t s

    G e n e r a l L o a d M o d e l

    Table of Contents

    1 General Description........................................................................................................................... 4

    1.1 Load-Flow Analysis ................................................................................................................................... 41.1.1 Balanced Load-Flow.............................................................................................................................51.1.2 Unbalanced Load-Flow .........................................................................................................................51.1.2.1 3-phase loads .................................................................................................................................61.1.2.2 2-Phase Loads ................................................................................................................................71.1.2.3 1-phase loads .................................................................................................................................8

    1.1.3 DC loads .............................................................................................................................................91.1.4 Voltage dependency........................................................................................................................... 101.1.5 Load Scaling factors........................................................................................................................... 12

    1.2 Short-Circuit Analysis .............................................................................................................................. 14

    1.3 Harmonic Analysis................................................................................................................................... 151.3.1 Passive Load...................................................................................................................................... 151.3.2 Harmonic Current Injections............................................................................................................... 17

    1.4 RMS Simulation (Transient Stability) ........................................................................................................ 18

    1.5 EMT Simulation....................................................................................................................................... 21

    2 Input/Output Definition of the Dynamic Model.............................................................................. 22

    2.1 Three-Phase Load................................................................................................................................... 222.1.1 RMS-Simulation ................................................................................................................................. 222.1.2 EMT-Simulation ................................................................................................................................. 23

    2.2 Single-, Two-Phase Load and DC-Load..................................................................................................... 23

    3 Parameter Definitions ..................................................................................................................... 24

    3.1 General Load Type (TypLod) ................................................................................................................... 24

    3.2 General Load Element (ElmLod)............................................................................................................... 25

  • 8/10/2019 TechRef_Load[1].pdf

    4/26

    G e n e r a l L o a d M o d e l

    1General Description

    In power systems, electrical load consists of various different types of electrical devices, from incandescent lamps

    and heaters to large arc furnaces and motors. It is often very difficult to identify the exact composition of static

    and dynamic loads in the network. This load composition can also vary depending on factors such as the season,

    time of day etc.

    Additionally, the term loadcan be used for entire MV-feeders in case of an HV-system or LV-feeders if an MV-

    system is in the centre of interest.

    The PowerFactorymodel General Load can therefore represent:

    A complete feeder

    A combination of dynamic and static loads

    The general load model diagram is shown in Figure 1 below.

    Figure 1: DIgSILENT General Load Model

    1.1

    Load-Flow Analysis

    In the element window for the load, the user is free to choose whether the load is balanced or unbalanced.

    Furthermore the user can specify the input parameters for the load using the Input Modedrop down menu asshown in Figure 2 below. Based on the available data, the user can select the relevant combination of parameters

    from S (apparent power), P (real power), Q (reactive power), cos(phi) (power factor) and I (current).

    For load-flow analysis, it suffices to only specify the load's electrical consumption.

    Other data characterizing a load, such as the number of phases or voltage dependency factors (see also 1.1.3)

    are defined in the Load Type. If no load type is specified, a balanced, three-phase load is assumed having default

    parameters for voltage dependency kpu=1.6 and kqu=1.8 (see also section 1.1.4).

  • 8/10/2019 TechRef_Load[1].pdf

    5/26

    G e n e r a l L o a d M o d e l

    Figure 2: Specifying the input parameters for the load model

    1.1.1Balanced Load-Flow

    Depending on the selected input mode, the user needs to specify two input parameters. Figure 3 shows the load

    model used for balanced load-flow analysis, where only P0and Q0are specified.

    All loads specified as 2-phase and/or 1-phase loads are only considered in unbalancedload flow calculations.

    They are ignored when a balancedload-flow is performed.

    Figure 3: Load model used for balanced load-flows.

    1.1.2Unbalanced Load-Flow

    When running a load flow with a complete ABC-network representation, network unbalances resulting from either

    unbalanced loads or unbalanced branch elements can be considered.

    Additional data for unbalanced load flow analysis is:

    Technology

    Figure 4 shows the input dialog window for specifying the type data for General loads.

  • 8/10/2019 TechRef_Load[1].pdf

    6/26

    G e n e r a l L o a d M o d e l

    Figure 4: General load type data input window

    1.1.2.13-phase loads (3PH-D, 3PH PH-E, 3PH-YN)

    The actual load per phase is entered in the input dialogue-box of the load element. The user has the choice

    between:

    Balanced load, only specifying the sum of all phases. In this case, it is assumed that the load is shared

    equally amongst the phases.

    Unbalanced load, specifying the individual phase loads.

    Figure 5: 3-phase, Technology 3PH D load model diagram

  • 8/10/2019 TechRef_Load[1].pdf

    7/26

    G e n e r a l L o a d M o d e l

    Figure 6: 3-phase, Technology 3PH PH-E load model diagram

    Figure 7: 3-phase, Technology 3PH YN load model diagram

    1.1.2.22-Phase Loads (2PH PH-E, 2PH-YN)

    Such a load type can be used for modelling loads in two-phase or bi-phase systems.

  • 8/10/2019 TechRef_Load[1].pdf

    8/26

    G e n e r a l L o a d M o d e l

    Figure 8: 2-phase, Technology 2PH PH-E load model diagram

    Figure 9: 2-phase, Technology 2PH-YN load model diagram

    1.1.2.31-phase loads (1PH PH-PH, 1PH PH-N, 1PH PH-E)

    The 1PH PH-PH load model can be used for representing loads connected betweentwo phases, which is in fact

    a single-phase load between two phases (see Figure 10).

    Figure 10: 1-phase, Technology 1PH PH-PH load model diagram

    The 1PH PH-N load model can be used for a load connected between one phase and the neutral phase (see

    Figure 11).

  • 8/10/2019 TechRef_Load[1].pdf

    9/26

    G e n e r a l L o a d M o d e l

    Figure 11: 1-phase, Technology 1PH PH-N load model diagram

    The 1PH PH-E load model can be used for a load connected between one phase and earth (see Figure 12).

    Figure 12: 1-phase, Technology 1PH PH-E load model diagram

    1.1.3DC loads

    DC-loads are always single-phase, as shown in Figure 10. For load flow analysis, the load is characterized by

    the active power flow P. Inductive effects are only considered in transient simulations.

    Figure 13: 1-phase DC load model diagram

  • 8/10/2019 TechRef_Load[1].pdf

    10/26

    G e n e r a l L o a d M o d e l

    1.1.4Voltage dependency

    Voltage dependency of loads can be modelled using a potential approach, as shown in (1) and (2). In theseequations, the subscript 0 indicates the initial operating condition as defined in the input dialogue box of the Load

    Element.

    ( )

    +

    +

    =

    cPebPeaPe

    v

    vbPaP

    v

    vbP

    v

    vaPPP

    _

    0

    _

    0

    _

    0

    0 1 (1)

    where

    cPbPaP =1

    ( )

    +

    +

    =

    cQebQeaQe

    v

    vbQaQ

    v

    vbQ

    v

    vaQQQ

    _

    0

    _

    0

    _

    0

    0 1 (2)

    where

    cQbQaQ =1

    By specifying the respective exponents (e_aP/e_bP/e_cPand e_aQ/e_bQ/e_cQ) the inherent load behaviour can

    be modelled. Table 1 provides the value for the exponents required to achieve constant power, current and

    impedance behaviour. However, the relative proportion of each coefficient can be freely defined using the

    coefficients aP, bP, cP and aQ, bQ, cQ. See Figure 11.

    Table 1: Selection of exponentvalue for different load model behaviour

    Exponent Constant

    0 power

    1 current

    2 impedance

  • 8/10/2019 TechRef_Load[1].pdf

    11/26

    G e n e r a l L o a d M o d e l

    Figure 14: Specification of the voltage dependency factors

    NOTE: These factors are only considered if the Consider Voltage Dependency of Loads is checked

    in the Load-flow Calculation window, as shown in Figure 15 below.

    Figure 15: Load-flow Calculation window indicating the use of voltage dependency terms for load-

    flow calculations

  • 8/10/2019 TechRef_Load[1].pdf

    12/26

  • 8/10/2019 TechRef_Load[1].pdf

    13/26

    G e n e r a l L o a d M o d e l

    Figure 16: Scaling factor specification

    Figure 17: Diagram indicating load scaling (adjustment) in order to maintain the feeder settingsspecified in the Feeder Definition

  • 8/10/2019 TechRef_Load[1].pdf

    14/26

    G e n e r a l L o a d M o d e l

    1.2

    Short-Circuit Analysis

    Short circuit calculations according to IEC 60909, VDE102/103 or ANSI C37 generally neglect loads. Only motor

    contributions are considered here.

    The COMPLETE short circuit method utilises constant impedance (Z) or constant current I0models. Z and I0are

    calculated from a preceding load-flow analysis. Figure 18 shows the type data window used to select whether the

    load is constant current or constant impedance. See notes on Harmonic Analysis for further explanation of the

    models.

    Figure 18: Selection of load type of either constant current or constant impedance for consideration

    in short circuit calculations using the Complete Method.

    Figure 19 shows a 3-phase representation of a Y connected constant impedance and Figure 20 shows the 3-

    phase representation of the D connected constant current model.

    Figure 19: 3-phase constant impedance model, in Y and D connection, used for short circuit

    calculations using the Complete method.

  • 8/10/2019 TechRef_Load[1].pdf

    15/26

    G e n e r a l L o a d M o d e l

    Figure 20: 3-phase constant current load, in Y and D connection, used load for short circuit

    calculations utilising the Complete method

    1.3

    Harmonic Analysis

    In the type data of the general load model, the harmonic load model can be specified as either constant

    impedance or current source. Figure 21 shows the selection of the harmonic load model type.

    Figure 21: Selection of the load model type for harmonic analysis

    1.3.1Passive Load

    Passive loads can be represented as purely inductive or capacitive or a mixture of inductive and capacitive. Figure

    22 shows the single-phase representation of a purely inductive and capacitive load.

  • 8/10/2019 TechRef_Load[1].pdf

    16/26

    G e n e r a l L o a d M o d e l

    Figure 22: Purely inductive/capacitive load models used for harmonic analysis

    The parameters R,L (G,C) are calculated from a preceding load-flow.

    Figure 23 shows the single-phase load model for mixed inductive/capacitive load models (e.g. cables), used

    during harmonic analysis.

    Figure 23: The single phase equivalent for mixed inductive/capacitive load model

    NOTE: Figure 22 and Figure 23 are single phase representations of the passive load. The 3-phase presentation is

    similar to that shown in Figure 6 and Figure 5, and with either Y or D connections.

    The inductive/capacitive portion of the load is specified by (7) and (8);

    1

    1

    +

    =

    +

    =

    C

    LCL

    Cc

    Q

    QQQ

    Q

    Q

    Q (7)

    =

    C

    L

    n

    Q

    Q

    yC

    1

    (8)

  • 8/10/2019 TechRef_Load[1].pdf

    17/26

    G e n e r a l L o a d M o d e l

    1.3.2Harmonic Current Injections

    Nonlinear loads are described by their harmonic current spectrum. A requirement for modelling current injectingloads is to set the corresponding parameter on the harmonics page to current source.

    For balanced loads, only characteristic harmonics can be specified. Figure 24 shows the specification of the

    characteristic harmonic spectrum in the element data window of the load.

    The angles of harmonic currents are defined with reference to the fundamental frequency phase angle (cosine

    reference). This way of entering phase angles allows defining the current waveform independent from the power

    factor at fundamental frequency.

    Figure 24 shows the current spectrum of an ideal 6-pulse rectifier. Absolute current angles will be adjusted by

    PowerFactoryaccording to (10).

    Figure 24: Specification of the harmonic current spectrum for balanced loads

    The harmonic currents are defined by (9) and the phase angle of the harmonic currents is defined by (10).

    ( ) ( ) ( )nfff IkI .= (9)

  • 8/10/2019 TechRef_Load[1].pdf

    18/26

    G e n e r a l L o a d M o d e l

    ( ) 1n

    ff

    f+= (10)

    where fnis the nominal frequency and 1is phase angle of the fundamental current.

    In case of unbalanced loads, frequency, phase angle and magnitude of harmonic currents can be entered

    individually for each phase. Figure 25 shows the input window for entering such data.

    Figure 25: Specification of the harmonic current spectrum per phase for unbalanced loads

    1.4

    RMS Simulation (Transient Stability)For RMS simulations a three-phase load can be modelled as a percentage of static and dynamic load. The static

    portion is modelled as constant impedance whereas the dynamic load can be modelled as either a linear load or a

    non-linear load.

    Two-phase, single-phase- and DC loads are generally modelled as constant impedance.

  • 8/10/2019 TechRef_Load[1].pdf

    19/26

    G e n e r a l L o a d M o d e l

    Figure 26: Diagram indicating the mixture of static and dynamic loads used for stability studies.

    The background of the dynamic, voltage- and frequency dependent load model according to Figure 24 and Figure

    25 is a motor-load in parallel to a static, non-linear load. The parameters of the block diagrams in Figure 24 and

    Figure 25 can either be calculated from such a configuration, but they are usually identified from load

    measurements.

    The model according to Figure 24 is a small signal approximation of the model according to Figure 25.Parameters with equal names correspond to each other.

    Figure 27: Model used to approximate the behaviour of the linear dynamic load.

  • 8/10/2019 TechRef_Load[1].pdf

    20/26

    G e n e r a l L o a d M o d e l

    Figure 28: Model used to approximate the behaviour of the non-linear dynamic load.

    Since the block diagrams according to Figure 27 and Figure 28 represent small signal models, they are only valid

    in a limited voltage range. This voltage range is defined by the variables uminand umax. Outside this voltage range,

    the power is adjusted according to Figure 29.

    Figure 29: Low/High voltage approximations used in the non-linear dynamic load model.

    With reference to the outputs of the block diagrams according to Figure 24 and Figure 25, the load equations

    representing the full voltage range can be expressed as follows:

  • 8/10/2019 TechRef_Load[1].pdf

    21/26

    G e n e r a l L o a d M o d e l

    ( ) max2

    max

    minmin

    2

    min

    min

    min

    2

    min

    2

    maxmin

    :1

    2:21

    20:

    2

    :1

    .

    .

    uuuuk

    uuu

    u

    uuk

    uu

    u

    uk

    uuuk

    QkQ

    PkP

    out

    out

    >+=

  • 8/10/2019 TechRef_Load[1].pdf

    22/26

    G e n e r a l L o a d M o d e l

    2Input/Output Definition of the Dynamic Model

    2.1

    Three-Phase Load

    2.1.1RMS-Simulation

    Figure 30: Input/Output Definition of General Load Model (RMS-Simulation)

    Table 2: Input Variables (RMS-Simulation)

    Parameter Description Unit

    Pext Active Power Input MW

    Qext Reactive Power Input Mvar

    Table 3: State Variables (RMS-Simulation)

    Parameter Description Unit

    xu Delayed Voltage (Time constant T1) p.u.

    xf Delayed Frequency (Time constant T1) p.u

    cosphiu cosine of voltage angle

    sinphiu sine of voltage angle

    Table 4: Additional Parameters and Signals (RMS-Simulation)

    Parameter Description Unit

    fe Electrical Frequency p.u.

    scale Scaling Factor

    Pext

    Qext

  • 8/10/2019 TechRef_Load[1].pdf

    23/26

    G e n e r a l L o a d M o d e l

    2.1.2EMT-Simulation

    Table 5: State Variables (EMT-Simulation)Parameter Description Unit

    curLA Inductive Current, Phase A p.u.

    curLB Inductive Current, Phase B p.u

    curLC Inductive Current, Phase C p.u.

    2.2

    Single-, Two-Phase Load and DC-Load

    Constant impedance load models. No input or output variables.

  • 8/10/2019 TechRef_Load[1].pdf

    24/26

    G e n e r a l L o a d M o d e l

    3Parameter Definitions

    3.1

    General Load Type (TypLod)

    Table 6: Input parameters of Load - Type

    Parameter Description Unit

    loc_name Name

    systp System Type

    nlnph Phases

    cnm Connection

    kpu Static Voltage Dependence: Volt. Dependence on P

    kqu Static Voltage Dependence: Volt. Dependence on Q

    i_csrc Current Source/Impedance

    i_pure Load model

    pgrd Capacitive/Inductive Reactive Power: QL/QC %

    qcq Capacitive/Inductive Reactive Power: QC/Q %

    xt Transformer Short Circuit Reactance %

    Prp Power of parallel Resistance/Total Active Power %

    lodst Percentage: Static (const Z) %

    loddy Percentage: Dynamic %

    i_nln Percentage: Nonlinear Model

    t1 Dynamic Load Time Constant skpf Dynamic Active Load: Frequ. Dependence on P

    kpu Static Voltage Dependence: Volt. Dependence on P

    tpf Dynamic Active Load: Transient Frequency

    Dependence

    s

    tpu Dynamic Active Load: Transient Voltage

    Dependence

    s

    kqf Dynamic Reactive Load: Frequ. Dependence on Q

    kqu Static Voltage Dependence: Volt. Dependence on Q

    tqf Dynamic Reactive Load: Transient Frequency

    Dependence

    s

    tqu Dynamic Reactive Load: Transient VoltageDependence

    s

    udmax Voltage Limits: Upper Voltage Limit p.u.

    udmin Voltage Limits: Lower Voltage Limit p.u.

    i_nln Percentage: Nonlinear Model

  • 8/10/2019 TechRef_Load[1].pdf

    25/26

  • 8/10/2019 TechRef_Load[1].pdf

    26/26

    G e n e r a l L o a d M o d e l

    i_prty Load shedding/transfer: Load priority

    shed Load shedding/transfer: Shedding steps

    trans Load shedding/transfer: Transferable %

    pTrans Load shedding/transfer: Node to Transfer to

    (ElmTerm,StaBar)