83
Denver Fire Alarm Technician Practice Number 1 Ted “Smitty” Smith

Ted “Smitty” Smith This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

Embed Size (px)

Citation preview

Page 1: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

Denver Fire Alarm Technician Practice Number 1

Ted “Smitty” Smith

Page 2: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

Instructions

This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National Fire Alarm and Signaling Code and the Denver Building Amendments.

If you put the slide show into slide show mode, the slides will transition automatically and allow you 3 minutes for each question. The answers will stay up for only 15 seconds. When you reach the end of the practice test there will be a slide that reads STOP.

You can then click on the slide and the questions will be repeated without the timer so that you can write down questions and answers and take notes.

During the timed section, do not worry about writing down the correct answer. Proceed through the timed section then review the questions and answer again without the timer.

Page 3: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

In the absence of a specific performance based design criteria, smooth ceiling smoke detector spacing shall be a nominal _________ feet.

Page 4: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

30 feet 17.7.3.2.3.1

Page 5: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

Signals with carbon monoxide detectors transmitted to a fire alarm system shall be permitted to be _____________________________ signals.

Page 6: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

Supervisory 23.8.4.7

Page 7: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

When a supervising station receives a trouble signal they must dispatch personnel with in ________ hours to initiate maintenance, if necessary.

Page 8: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

4 hours 26.3.7.4

Page 9: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

Complete records of all signals received by a supervising station shall be kept for a period of ________________.

Page 10: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

1 year 26.4.6.1

Page 11: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

A type public alarm system shall be required where the number of all alarms required to be retransmitted exceeds _____________ per year.

Page 12: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

2500 27.5.2.1.2

Page 13: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

A fire alarm system installed in an occupancy that does not require a fire alarm system shall ____________________________.

A. comply with NFPA 72 B. not be required to comply with NFPA

72 C. comply with chapters 17 and 18 of

NFPA 72 only D. comply with the NEC only

Page 14: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

A. comply with NFPA 72 (23.2.3.1)

Page 15: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

A class A circuit in a protected premises using physical conductors shall be installed so that the outgoing and return conductors are routed separately unless for a distance not to exceed __________ feet where the conductors enter or exit the initiating device, notification appliance, or control unit enclosures. 3 6 10 15

Page 16: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

10 (23.4.2.2 List item 1)

Page 17: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

A class B circuit in protected premises shall be designed and installed in a manner to ensure so that a _____________________ signal shall annunciate in the condition of an open or ground condition in the wiring. Supervisory Alarm Trouble None of the above

Page 18: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

Trouble (23.5.2)

Page 19: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

Actuation of alarm notification appliances or emergency voice communications, fire safety functions, and annunciation at the protected premises shall occur within ____________ after the activation of an initiating device. 5 seconds 10 seconds 30 seconds 1 minute

Page 20: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

10 seconds (23.8.1.1)

Page 21: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

Signals from a carbon monoxide detectors and carbon monoxide detection systems transmitted to a fire alarm system shall be permitted to be ______________________ signals. Alarm Trouble Supervisory Indicative

Page 22: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

Supervisory (23.8.4.7)

Page 23: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

Visible notification signals _______________________ be required in exit stair enclosures and exit passageways. Shall Shall not

Page 24: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

Shall not (23.8.6.2.1)

Page 25: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

The evacuation signal ____________________ be required to operate in elevator cars. Shall Shall not

Page 26: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

Shall not (23.8.6.2.4)

Page 27: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

As applies to guard’s tour supervisory service, the system shall automatically transmit a delinquency signal within ________________ after the predetermined actuation time if the guard fails to actuate a tour station as scheduled. 10 seconds 30 seconds 5 minutes 15 minutes

Page 28: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

15 minutes (23.16.4)

Page 29: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

The occurrence of any single fault at the protected premises that disables transmission between any low-power radio transmitter and the receiver/ fire alarm control unit shall cause a latching trouble signal within ____________. 10 seconds 30 seconds 60 seconds 200 seconds

Page 30: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

200 seconds (23.18.4.2)

Page 31: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

A fire alarm system must be supplied by a minimum of __________ independent and reliable power supplies. One Two Three Four

Page 32: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

Two (10.5.3.2)

Page 33: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

A coded alarm signal shall consist of not less than__________ complete rounds of the number transmitted. One Two Three Four

Page 34: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

Three (10.9.3)

Page 35: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

A coded supervisory signal shall be permitted to consist of ___________ rounds of the number transmitted to indicate a supervisory off-normal condition. One Two Three Four

Page 36: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

Two (10.11.1.1)

Page 37: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

Two way telephone communications circuit installation conductors shall be monitored for ______________ fault conditions that would cause the telephone communications circuit to become fully or partially inoperative. Ground fault Open fault Both ground fault and open fault None of the above

Page 38: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

Open fault (10.17.2.2.1)

Page 39: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

Spot type smoke detectors shall be located on the ceiling, or if on a side wall, between the ceiling and ___________ inches down from the ceiling to the top of the detector. 6 inches 12 inches 18 inches 24 inches

Page 40: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

12 inches ( 17.7.3.2.1)

Page 41: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

The lamps and LED’s for the control equipment of a Mass Notification System shall be visually inspected ________________________________. Monthly Quarterly Semi-annually Annually

Page 42: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

Semi-Annually (Table 14.3.1 Page 57)

Page 43: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

STOP> End of Timed Questions

STOP

STOP

STOP

STOP

STOP

Page 44: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

In the absence of a specific performance based design criteria, smooth ceiling smoke detector spacing shall be a nominal _________ feet.

Page 45: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

30 feet 17.7.3.2.3.1

Page 46: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

Signals with carbon monoxide detectors transmitted to a fire alarm system shall be permitted to be _____________________________ signals.

Page 47: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

Supervisory 23.8.4.7

Page 48: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

When a supervising station receives a trouble signal they must dispatch personnel with in ________ hours to initiate maintenance, if necessary.

Page 49: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

4 hours 26.3.7.4

Page 50: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

Complete records of all signals received by a supervising station shall be kept for a period of ________________.

Page 51: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

1 year 26.4.6.1

Page 52: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

A type public alarm system shall be required where the number of all alarms required to be retransmitted exceeds _____________ per year.

Page 53: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

2500 27.5.2.1.2

Page 54: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

A fire alarm system installed in an occupancy that does not require a fire alarm system shall ____________________________.

A. comply with NFPA 72 B. not be required to comply with NFPA

72 C. comply with chapters 17 and 18 of

NFPA 72 only D. comply with the NEC only

Page 55: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

A. comply with NFPA 72 (23.2.3.1)

Page 56: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

A class A circuit in a protected premises using physical conductors shall be installed so that the outgoing and return conductors are routed separately unless for a distance not to exceed __________ feet where the conductors enter or exit the initiating device, notification appliance, or control unit enclosures. 3 6 10 15

Page 57: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

10 (23.4.2.2 List item 1)

Page 58: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

A class B circuit in protected premises shall be designed and installed in a manner to ensure so that a _____________________ signal shall annunciate in the condition of an open or ground condition in the wiring. Supervisory Alarm Trouble None of the above

Page 59: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

Trouble (23.5.2)

Page 60: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

Actuation of alarm notification appliances or emergency voice communications, fire safety functions, and annunciation at the protected premises shall occur within ____________ after the activation of an initiating device. 5 seconds 10 seconds 30 seconds 1 minute

Page 61: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

10 seconds (23.8.1.1)

Page 62: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

Signals from a carbon monoxide detectors and carbon monoxide detection systems transmitted to a fire alarm system shall be permitted to be ______________________ signals. Alarm Trouble Supervisory Indicative

Page 63: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

Supervisory (23.8.4.7)

Page 64: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

Visible notification signals _______________________ be required in exit stair enclosures and exit passageways. Shall Shall not

Page 65: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

Shall not (23.8.6.2.1)

Page 66: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

The evacuation signal ____________________ be required to operate in elevator cars. Shall Shall not

Page 67: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

Shall not (23.8.6.2.4)

Page 68: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

As applies to guard’s tour supervisory service, the system shall automatically transmit a delinquency signal within ________________ after the predetermined actuation time if the guard fails to actuate a tour station as scheduled. 10 seconds 30 seconds 5 minutes 15 minutes

Page 69: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

15 minutes (23.16.4)

Page 70: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

The occurrence of any single fault at the protected premises that disables transmission between any low-power radio transmitter and the receiver/ fire alarm control unit shall cause a latching trouble signal within ____________. 10 seconds 30 seconds 60 seconds 200 seconds

Page 71: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

200 seconds (23.18.4.2)

Page 72: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

A fire alarm system must be supplied by a minimum of __________ independent and reliable power supplies. One Two Three Four

Page 73: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

Two (10.5.3.2)

Page 74: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

A coded alarm signal shall consist of not less than__________ complete rounds of the number transmitted. One Two Three Four

Page 75: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

Three (10.9.3)

Page 76: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

A coded supervisory signal shall be permitted to consist of ___________ rounds of the number transmitted to indicate a supervisory off-normal condition. One Two Three Four

Page 77: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

Two (10.11.1.1)

Page 78: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

Two way telephone communications circuit installation conductors shall be monitored for ______________ fault conditions that would cause the telephone communications circuit to become fully or partially inoperative. Ground fault Open fault Both ground fault and open fault None of the above

Page 79: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

Open fault (10.17.2.2.1)

Page 80: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

Spot type smoke detectors shall be located on the ceiling, or if on a side wall, between the ceiling and ___________ inches down from the ceiling to the top of the detector. 6 inches 12 inches 18 inches 24 inches

Page 81: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

12 inches ( 17.7.3.2.1)

Page 82: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

The lamps and LED’s for the control equipment of a Mass Notification System shall be visually inspected ________________________________. Monthly Quarterly Semi-annually Annually

Page 83: Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National

Semi-Annually (Table 14.3.1 Page 57)