About Telenor Tier 3 Data Center
Telenor built it´s own Data Centar in accordance with the latest industrial standards.
Telehousing services in Telenor Data Center are available to customers from January 2011.
Telenor´s Telehousing services are tailored to the needs of large companies, financial institutions, ISP´s, content providers and others for whom the service availability and the equipment and IT systems security are of primary business importance.
• Telenor Group
• Local Standards (SRPS)
• RATEL regulations
• ASHRAE recommendations
• Fire Brigade Regulations
• TIA-942 (Telecommunications Industry Association)
• Site space and layout
• Cabling infrastructure
• Tiered reliability
• Environmental considerations
Standards
Data Center Tiers
• Multi-million dollar business
• 99,995% availability
• Annual downtime due to
site is 0,04 hours
• Typically small business
• 99,671% availability
• Annual downtime due to
site is 28,8 hours
• Single path of power and
cooling
• No redundant components
• Medium-size business
• 99,749% availability
• Annual downtime due to
site is 22,0 hours
• Single path of power and
cooling
• Some redundancy in power
and cooling system
• Large company
• 99,982% availability
• Annual downtime due to
site is 1,6 hours
• Multiple power and cooling paths
• Fault tolerant (N+1)
• Able to sustain 72-hour power outage
• Two independent utility paths
• Fully redundant (2N+1)
• Able to sustain 96-hour power outage
Telenor Tier 3 Data Center
• Separate stand alone facility with 2.600m2 space with full N+1 redundancy on all mechanical, electrical and connectivity infrastructure
• Technical space on three floors
• Loading/delivery docking area
• Freight elevator, capacity 2,500 kg
• Built in the 2009th with the flat roof and without windows
• Controlled access to facility via single entrance
• More emergency exits
One of the most advanced Data Centers in SEE region
• Cabinets/racks - Pre-installed standard racks (600x1.070x42U)
• Cage – optional
• Data room – optional
• Space with necessary infrastructure for collocation of storage racks
• Web portal – real-time monitoring of all relevant service parameters
• Hands & Eyes services
• Anti-static floor
• Raised floor, construction height 65cm, maximum load 1500 Kg/m2
• Structured cabling (Power cabling under raised floor, Data cabling overhead)
Accommodation of user´s telecommunication equipment
Telenor Tier 3 Data Center
Power supply
Air conditioning /Cooling
• Two independent 10kV underground utility feeders, from different utility transformer substations 110/10 kV
• Mains: 3x400/230V AC, 50 Hz (Dry transformers 10/0.4 kV)
• Dual power feeds, possibility of maintenance one power branch without affecting the functionality of the system
• Redundant UPS systems - 2x(n+1) with total power 2x(3x400kVA), 2h autonomy
• Diesel generator backup for all critical loads, 72 hours autonomy (at full capacity) before refueling, 2N redundant
• Dual UPS power feed for each rack, fused by 1x32A+1x32A
• Power supply system with overload protection and protection discrimination (selectivity) of circuit breakers
• Redundant air-conditioning, free-cooling chillers, indoor CRAC (Computer Room Air Conditioner) units, (N+1) redundancy
• Air-conditioning system separated from the rest of the facility
• Environmental conditions control system maintaining constant levels of temperature (22°C - 26°C (24 ± 2°C)) and humidity (40-60% (50 ± 10%))
• Concurrently maintainable air-conditioning and power supply system without threat to availability of the telehousing services
Telenor Tier 3 Data Center
Security
Fire Detection and Suppression
• Physical security system with 24x7x365 access control
• Video surveillance of the entire facility providing archive recordings to 3 months
• Monitoring elements are connected to alarm systems. All doors are built in accordance with
WK standard
• Electronic access control system over ID cards and PIN codes –access allowed only to pre-defined areas, with continual monitoring
• The security fence around the building of 2.2m hight is connected with concrete bollards.
• Complete site perimeter is secured by IC barriers integrated in existing alarm system.
• Zoned fire detection system utilising VESDA (Very Early Smoke Detection Aspirating)
• Zoned fire suppression system (IG-55)
• Fire retarding walls (F90)
• Monitoring elements are connected to alarm systems.
• Smoke detectors are placed on the ceiling and under the raised floor; functioning in terms of power failor
• The closest fire brigade is 12 minutes away from the facility
Telenor Tier 3 Data Center
Communication infrastructure
Monitoring
• ~ 2700 km of fiber optic network in Serbia, Hungary and Bulgaria
• Multiple connections with local Internet providers and operators
• BGP (Border Gateway Protocol) over several Tier1 ISP`s
• DWDM capacity of 40 wavelengths, 10 Gbps per wavelength
(expandable up to 80 wavelengths with 40 Gbps per wavelength)
• Completely redundant networking equipment with dual power supplies
and spare units for all critical equipment
• Telenor Serbia is building the best data (All IP) network in Serbia
• Services (Dark fiber, Wavelength, SDH capacities, Ethernet solutions)
• All systems and network are monitored by Telenor`s NOC 24/7/365
• Trouble ticketing system