14

Tender BOQ Shivajinagar 132 KV 2x50 MVA

Embed Size (px)

Citation preview

Page 1: Tender BOQ Shivajinagar 132 KV  2x50 MVA
Page 2: Tender BOQ Shivajinagar 132 KV  2x50 MVA
Page 3: Tender BOQ Shivajinagar 132 KV  2x50 MVA

132/33 KV, 2 x 50 MVA Substation, ShivajiNagar - SUPPLY

Description Unit Qty Amount

1 Nos 2 0

2 Nos 3 1324200.00 3972600.00

3 33KV SF6 Circuit breaker Nos 6 515750.00 3094500.004

a) Upright mounting type with earth switch. Nos 1 305400.00 305400.00b) Upright mounting type with out earth switch. Nos 4 291700.00 1166800.00

5

a) Upright mounting type with earth switch. Nos 4 110000.00 440000.00

b) Upright mounting type with out earth switch. Nos 11 98020.00 1078220.00

6

i) 132 KV,C.T Nos 9 167820.00 1510380.00

ii)33KV CT including for metering Nos 30 55900.00 1677000.00

Nos 2 84050.00 168100.00

7 Nos 9 166110.00 1494990.00

b) 33KV PT including for metering & Bus Nos 15 56700.00 850500.00

8 Surge Arrestors:

i) 120KV, 10KA, Class - III Nos 9 49800.00 448200.00

ii) 30 KV, 10KA, Station Class. Nos 18 25140.00 452520.00

9

Nos 3 1166500.00 3499500.00

b) For 132KV Transmission lines Nos 1 1430660.00 1430660.00

c) 33 KV side Transformer + Feeder CRP - Nos 6 752560.00 4515360.00

10 MT 48 77660.00 3727680.00

MT 20 47400.00 948000.00

c) Fastners (Bolts and Nuts) for structues. MT 3.2 122940.00 393408.00

11 ACSR Conductor / Bus Stringing :

a) Drake ACSR Mtrs 900 460.00 414000.00

b) Coyote ACSR Mtrs 700 110.00 77000.00

Mtrs 325 40.00 13000.00

12 Insulators :

i) Post insulators solid core 132KV Class Nos 12 9380.00 112560.00

ii) Post insulators solid core 33KV Class Nos 15 3330.00 49950.00

1311KV 120KN Disc insulators with hardware:

Set 24 10370.00 248880.00

set 110 3840.00 422400.00

Set 12 10530.00 126360.00

Sl. No.

Unit Rate Destination

Power Transformers : 132 / 33 KV, 50 MVA, Delta /Star, DY11, 3Ph, 50Hz, Core type winding with OLTC, RTCC Panel etc.,

SF6 Circuit breaker: 145 KV, 3150A, 40KA Class with semi-pneumatic /pneumatic.

Isolators: Isolators including Marshalling box

132KV, 3000 A, 40 KA Class Double Break manually operated isolators

33 KV Isolator: double break 800A, 25KV capacity

Current transformers:

(iii)33 KV NCT: 500/1A for REFR protection with regid bimatalic terminal connector suitable for G.I flat of size 50 x 6 mm

Voltage Transformers : - 132 KV PT

Simplex type control and relay panel complete as per specifications :

a) For Power Transformers 50 MVA 132/33KV + Bus protection

a) Hot dip galvanized GI Structure for towers and equipments as per standards.

b)33 KV side RSJ Poles MS Painted with cross arms etc complete for 8 Nos 33 KV feeders

ii) GSS Earth wire : 7/3.15mm Steel with clamps/ Lugs etc.

a) Tension string 10 Units each with tension clamp suitable for Drake ACSR

b) Tension string 3 unit with tension clamp suitable for Coyote ACSR

c) Suspension strings 6 Units with suspension clamp suitable for Drake ACSR.

Page 4: Tender BOQ Shivajinagar 132 KV  2x50 MVA

set 18 4000.00 72000.00

Description Unit Qty Amount

14 Hard wares :

Terminal Connectors for Equipments

1) Power Transformer

HV side (132KV) Nos 6 3490.00 20940.00

LV side (33KV) Nos 6 1610.00 9660.00

LV Side Neutral Suitable for 50x6mm Flat Nos 2 830.00 1660.00

2) For circuit breaker 132KV Nos 18 2550.00 45900.00

For circuit breaker 33KV Nos 36 830.00 29880.00

3) For Isolator

a) 132 KV Nos 30 2060.00 61800.00

b) 33 kV Nos 90 810.00 72900.00

4) a) For current Transformer 132 KV Nos 18 2530.00 45540.00

b)For current Transformer 33KV Nos 72 1120.00 80640.00

c)For N.C.T suitable for NCT Nos 6 1120.00 6720.00

5)a)For Potential Transformer 132 KV Nos 9 2530.00 22770.00

b)For Potential Transformer 33KV Nos 15 1160.00 17400.00

6)a) Surge Arrestors 132 KV Nos 9 3000.00 27000.00

b)Surge Arrestors 33KV Nos 18 970.00 17460.00

7)a) Strain Clamps ( Bolted Type) Drake Nos. 12 2370.00 28440.00

b) Strain Clamps ( Bolted Type) Coyote Nos. 39 970.00 37830.00

8)a) Suspension Clamps( Bolted type) Drake Nos. 6 1900.00 11400.00

b) Suspension Clamps( Bolted type) Drake Nos. 6 1120.00 6720.00

9)a) Pedestal Clamps Drake Nos. 12 2530.00 30360.00

b) Pedestal Clamps Coyote Nos 15 1900.00 28500.00

Nos 3 1120.00 3360.00

Drake to Drake Nos 24 1080.00 25920.00

Coyote to Coyote Nos 60 540.00 32400.00

15 Mtrs 60 2280.00 136800.00

16 Nos 1 596240.00 596240.00

17 Set 1 234180.00 234180.00

18 Power cable LT as per specification :

Mtrs 125 480.00 60000.00

Mtrs 180 270.00 48600.00

Mtrs 225 150.00 33750.00

19

d) Suspension string 3 unit each with suspension clamp suitable for Coyote ACSR.

Sl. No.

Unit Rate Destination

10) T-Clamps ( Fired Wedge Connector Type)Coyote to Drake

50x6 Copper flat for each phase from LV side of transformer to cable at 11KV cable terminating structure with suitable support insulator

Auxiliary Transformers with oil, Cable termination type on both HT & LT outdoor type, 100 KVA, 11 KV / 433V, 3Ph, Vector group Dy 11 as per specification with TC Structure with accessories like HG fuse, Isolator, LA etc

(a) LTAC Panel (Indoor) 415V, as per specification and drawing.

a) 1.1KV PVC insulated 70 Sq.mm Aluminium Cable, 4Core with glands/lugs/ferrules

b) 1.1KV PVC insulated 25 sq.mm Aluminium Cable, 4Core with glands/lugs/ferrules

c) 1.1KV PVC insulated 10 Sq.mm Aluminium Cable, 4Core with glands/lugs/ferrules

Station battery and battery charger with DCDB.

Page 5: Tender BOQ Shivajinagar 132 KV  2x50 MVA

Set 1 361750.00 361750.00

Description Unit Qty Amount

20 PVC Insulated Copper Control Cable

i. 19 X 2.5 Sq.mm Mtrs. 2100 735.00 1543500.00

ii. 4 X 6.0 Sq.mm Mtrs. 4000 400.00 1600000.00iii. 4 X 2.5 Sq.mm Mtrs. 3800 205.00 779000.00

iv. 2 X 2.5 Sq.mm Mtrs. 3000 130.00 390000.00v. 2 X 6.0 Sq.mm Mtrs. 2400 240.00 576000.00

21 Termination for above

i. 19 X 2.5 Sq.mm Nos 60 120.00 7200.00

ii. 4 X 6.0 Sq.mm Nos 75 100.00 7500.00

iii. 4 X 2.5 Sq.mm Nos 90 100.00 9000.00

iv. 2 X 2.5 Sq.mm Nos 100 90.00 9000.00

v. 2 X 6.0 Sq.mm Nos 30 110.00 3300.00

22

Lot 152500.00 152500.00

23 Earth Mat Formation:

i) MS Flat 65x10mm Mtrs 3000 270.00 810000.00

ii) MS Flat 50 x 8 mm Mtrs 800 190.00 152000.00

iii] MS Round 25mm dia 1.5 Mtrs Long Nos 60 320.00 19200.00

Mtrs 1000 270.00 270000.00

Mtrs 1600 250.00 400000.00

Nos 40 5970.00 238800.00

24 Outdoor type TVM Panel withg TVM Set 4 172970.00 691880.00

25 LIGHTING

Street light poles suitable for 250 W HPSV fittings. Nos 8 9680.00 77440.00

Flood light fitting with 250W HPSV lamps Nos 8 7660.00 61280.00

26 CT / PT Junction Box No. 22 3540.00 77880.00

27 CABLE TRAY & SUPPORTS

a Mtrs 150 630.00 94500.00

b Mtrs 600 510.00 306000.00

c 50 x 50 x 6 Angle for Cable Tray Support & Fencing MT 5.2 47400.00 246480.00

28 GI PIPES

50MM Dia GI Pipe Mtrs 120 350.00 42000.00

100MM Dia GI Pipe Mtrs 150 800.00 120000.00

50MM Dia GI Long Radius Bend Nos 30 190.00 5700.00

100MM Dia GILong Radius Bend Nos 35 300.00 10500.00

63A 3 Phase Welding socket No. 1 700.00 700.00

a) Station battery: 110 V, 100 AH, Battery set, comprising 55 cells with mounting arrangements complete set.with float come booster type with DCDB as per specification.

Sl. No.

Unit Rate Destination

Fire fighting equipments with necessary mounting stands : +

Miscellkaneous items like rubber mats, first aid box, danger boards, shock treatment charts, water filter, door locks, Fixograph sub station name board and other sundry items

Materils for formation of earth mat as per specification

iv) GI Flats 50x8 mm for earth connection from various equipments

v) GI Flats 50x6 mm for earth connection from various equipments

vi]Cast Iron Pipe Electrode of 100mm internal dia, 13mm thick, 2.75 meter long

600mm wide perforated type cable tray Hot dip Galvanised

300mm wide perforated type cable tray Hot dip Galvanised

Page 6: Tender BOQ Shivajinagar 132 KV  2x50 MVA

30 Chain link mesh for fencing RM 280 1120.00 313600.00

29 Design, Engineering, / Testing LS

30

TOTAL 43861448.00

Drawing approval and approval from CEIG / GETCO.

Page 7: Tender BOQ Shivajinagar 132 KV  2x50 MVA

132/33 KV, 2 x 50 MVA Substation, ShivajiNagar - ERECTION / LABOUR

Description Unit Qty Amount

1 Nos 2 196500 393000.00

2 Nos 3 13500 40500.00

3 33KV SF6 Circuit breaker Nos 6 6740 40440.004

a) Upright mounting type with earth switch. Nos 1 6740 6740.00b) Upright mounting type with out earth switch. Nos 4 6180 24720.00

5

a) Upright mounting type with earth switch. Nos 4 3930 15720.00

b) Upright mounting type with out earth switch. Nos 11 3560 39160.00

6

i) 132 KV,C.T Nos 9 6180 55620.00

ii)33KV CT including for metering Nos 30 3150 94500.00

Nos 2 2810 5620.00

7 Nos 9 6180 55620.00

b) 33KV PT including for metering & Bus Nos 15 3150 47250.00

8 Surge Arrestors:

i) 120KV, 10KA, Class - III Nos 9 3930 35370.00

ii) 30 KV, 10KA, Station Class. Nos 18 2020 36360.00

9

Nos 3 11230 33690.00

b) For 132KV Transmission lines Nos 1 9540 9540.00

c) 33 KV side Transformer + Feeder CRP - Nos 6 6740 40440.00

10 MT 48 5620 269760.00

MT 20 13470 269400.00

c) Fastners (Bolts and Nuts) for structues. MT 3.2 3370 10784.00

11 ACSR Conductor / Bus Stringing :

a) Drake ACSR Mtrs 900 17 15300.00

b) Coyote ACSR Mtrs 700 12 8400.00

Mtrs 325 6 1950.00

12 Insulators :

i) Post insulators solid core 132KV Class Nos 12 2250 27000.00

ii) Post insulators solid core 33KV Class Nos 15 1130 16950.00

13 11KV 120KN Disc insulators with hardware:

Set 24 280 6720.00

set 110 170 18700.00

Set 12 280 3360.00

Sl. No.

Unit Rate

Power Transformers : 132 / 33 KV, 50 MVA, Delta /Star, DY11, 3Ph, 50Hz, Core type winding with OLTC, RTCC Panel etc.,

SF6 Circuit breaker: 145 KV, 3150A, 40KA Class with semi-pneumatic /pneumatic.

Isolators: Isolators including Marshalling box

132KV, 3000 A, 40 KA Class Double Break manually operated isolators

33 KV Isolator: double break 800A, 25KV capacity

Current transformers:

(iii)33 KV NCT: 500/1A for REFR protection with regid bimatalic terminal connector suitable for G.I flat of size 50 x 6 mm

Voltage Transformers : - 132 KV PT

Simplex type control and relay panel complete as per specifications :

a) For Power Transformers 50 MVA 132/33KV + Bus protection

a) Hot dip galvanized GI Structure for towers and equipments as per standards.

b)33 KV side RSJ Poles MS Painted with cross arms etc complete for 8 Nos 33 KV feeders

ii) GSS Earth wire : 7/3.15mm Steel with clamps/ Lugs etc.

a) Tension string 10 Units each with tension clamp suitable for Drake ACSR

b) Tension string 3 unit with tension clamp suitable for Coyote ACSR

c) Suspension strings 6 Units with suspension clamp suitable for Drake ACSR.

Page 8: Tender BOQ Shivajinagar 132 KV  2x50 MVA

set 24 170 4080.00

Description Unit Qty Amount

14 Hard wares :

Terminal Connectors for Equipments

1) Power Transformer

HV side (132KV) Nos 6 230 1380.00

LV side (33KV) Nos 6 120 720.00

LV Side Neutral Suitable for 50x6mm Flat Nos 2 120 240.00

2) For circuit breaker 132KV Nos 18 230 4140.00

For circuit breaker 33KV Nos 36 120 4320.00

3) For Isolator

a) 132 KV Nos 30 230 6900.00

b) 33 kV Nos 90 90 8100.00

4) a) For current Transformer 132 KV Nos 18 230 4140.00

b)For current Transformer 33KV Nos 72 90 6480.00

c)For N.C.T suitable for NCT Nos 6 90 540.00

5)a)For Potential Transformer 132 KV Nos 9 230 2070.00

b)For Potential Transformer 33KV Nos 15 90 1350.00

6)a) Surge Arrestors 132 KV Nos 9 230 2070.00

b)Surge Arrestors 33KV Nos 18 90 1620.00

7)a) Strain Clamps ( Bolted Type) Drake Nos. 12 200 2400.00

b) Strain Clamps ( Bolted Type) Coyote Nos. 39 170 6630.00

8)a) Suspension Clamps( Bolted type) Drake Nos. 6 200 1200.00

b) Suspension Clamps( Bolted type) Drake Nos. 6 170 1020.00

9)a) Pedestal Clamps Drake Nos. 12 170 2040.00

b) Pedestal Clamps Coyote Nos 15 170 2550.00

Nos 3 170 510.00

Drake to Drake Nos 24 90 2160.00

Coyote to Coyote Nos 60 70 4200.00

15 Mtrs 60 20 1200.00

16 Nos 1 67350 67350.00

17 Set 1 6740 6740.00

18 Power cable LT as per specification :

Mtrs 125 25 3125.00

Mtrs 180 25 4500.00

Mtrs 225 20 4500.00

19

d) Suspension string 3 unit each with suspension clamp suitable for Coyote ACSR.

Sl. No.

Rate inc of tax

10) T-Clamps ( Fired Wedge Connector Type)Coyote to Drake

50x6 Copper flat for each phase from LV side of transformer to cable at 11KV cable terminating structure with suitable support insulator

Auxiliary Transformers with oil, Cable termination type on both HT & LT outdoor type, 100 KVA, 11 KV / 433V, 3Ph, Vector group Dy 11 as per specification with TC Structure with accessories like HG fuse, Isolator, LA etc

(a) LTAC Panel (Indoor) 415V, as per specification and drawing.

a) 1.1KV PVC insulated 70 Sq.mm Aluminium Cable, 4Core with glands/lugs/ferrules

b) 1.1KV PVC insulated 25 sq.mm Aluminium Cable, 4Core with glands/lugs/ferrules

c) 1.1KV PVC insulated 10 Sq.mm Aluminium Cable, 4Core with glands/lugs/ferrules

Station battery and battery charger with DCDB.

Page 9: Tender BOQ Shivajinagar 132 KV  2x50 MVA

Set 1 10100 10100.00

Description Unit Qty Amount

20 PVC Insulated Copper Control Cable

i. 19 X 2.5 Sq.mm Mtrs. 2100 7 14700.00

ii. 4 X 6.0 Sq.mm Mtrs. 4000 6 24000.00iii. 4 X 2.5 Sq.mm Mtrs. 3800 5 19000.00

iv. 2 X 2.5 Sq.mm Mtrs. 3000 4 12000.00v. 2 X 6.0 Sq.mm Mtrs. 2400 5 12000.00

21 Termination for above

i. 19 X 2.5 Sq.mm Nos 60 90 5400.00

ii. 4 X 6.0 Sq.mm Nos 75 100 7500.00

iii. 4 X 2.5 Sq.mm Nos 90 130 11700.00

iv. 2 X 2.5 Sq.mm Nos 100 160 16000.00

v. 2 X 6.0 Sq.mm (for NCT) Nos 30 70 2100.00

22

Lot 17000 17000.00

23 Earth Mat Formation:

i) MS Flat 65x10mm Mtrs 3000 23 69000.00

ii) MS Flat 50 x 8 mm Mtrs 800 20 16000.00

iii] MS Round 25mm dia 1.5 Mtrs Long Nos 60 30 1800.00

Mtrs 1000 32 32000.00

Mtrs 1600 28 44800.00

Nos 40 680 27200.00

24 Outdoor type TVM Panel withg TVM Set 4 5620 22480.00

25 LIGHTING

Street light poles suitable for 250 W HPSV fittings. Nos 8 850 6800.00

Flood light fitting with 250W HPSV lamps Nos 8 340 2720.00

26 CT / PT Junction Box No. 22 570 12540.00

27 CABLE TRAY & SUPPORTS

a Mtrs 150 34 5100.00

b Mtrs 600 28 16800.00

c 50 x 50 x 6 Angle for Cable Tray Support & Fencing MT 5.2 13470 70044.00

28 GI PIPES

50MM Dia GI Pipe Mtrs 120 28 3360.00

100MM Dia GI Pipe Mtrs 150 34 5100.00

50MM Dia GI Long Radius Bend Nos 30 22 660.00

100MM Dia GILong Radius Bend Nos 35 28 980.00

a) Station battery: 110 V, 100 AH, Battery set, comprising 55 cells with mounting arrangements complete set.with float come booster type with DCDB as per specification.

Sl. No.

Rate inc of tax

Fire fighting equipments with necessary mounting stands : +

Miscellkaneous items like rubber mats, first aid box, danger boards, shock treatment charts, water filter, door locks, Fixograph sub station name board and other sundry items

Materils for formation of earth mat as per specification

iv) GI Flats 50x8 mm for earth connection from various equipments

v) GI Flats 50x6 mm for earth connection from various equipments

vi]Cast Iron Pipe Electrode of 100mm internal dia, 13mm thick, 2.75 meter long

600mm wide perforated type cable tray Hot dip Galvanised

300mm wide perforated type cable tray Hot dip Galvanised

Page 10: Tender BOQ Shivajinagar 132 KV  2x50 MVA

63A 3 Phase Welding socket No. 1 115 115.00

30 Chain link mesh for fencing RM 280 85 23800.00

29 Design, Engineering, / Drawing LS 550000 550000.00

30 LS 200000 200000.00

30 675000 675000.00

TOTAL 3718688.00

Testing & conducting pre commissioning tests

Drawing approval and approval from CEIG / GETCO.

Page 11: Tender BOQ Shivajinagar 132 KV  2x50 MVA

132/33 KV, 2 x 50 MVA Substation, ShivajiNagar - CIVIL WORKS

Description Unit Qty Unit Rate Amount

1 Site Levelling:

Cmtr 1100 280 308000.00

2 Foundations:

a) 132 KV Station Towers Nos. 6 39300 235800.00

Nos 3 17000 51000.00

33KV Breaker Nos. 6 7900 47400.00

b) 132 / 33 KV Isolator Nos. 21 6800 142800.00c) Nos. 42 4000 168000.00

d) Nos. 27 4000 108000.00

e) Nos. 27 3400 91800.00

f) Nos. 24 4000 96000.00

g) 33 KV RSJ Poles Nos 24 2300 55200.003

a)Road Crossing Cable Duct Mtrs 15 8200 123000.00

TYPE - I Cable Trench ( 1005 x 10 Mtrs 60 7600 456000.00

TYPE - II Cable Trench (750 x 1000 Mtrs 175 6800 1190000.00

b)Mtrs 200 370 74000.00

Sl. No.

66KV Station shall be maintained at one level The excess quantity of the soil due cutting during levelling of the land, soil excavated for the cable duct/foundation of the equipments shall be used for pitching along the boundary/beyond the boundary of the

Engineering supply of all labour, material & construction of cement concrete footings of any depth, pedestals including the cost of excavation, concreting, cement, reinforcement steel if required for all works, grouting, underpinning etc., for the following :

a) SF - 6 Circuit Breaker Foundation: 132 KV SF6 Circuit breakers foundation as per approved design & drawing including supply of material and labour.

132/33 KV CT / 11 & 33KV NCT Support Structure.

132/33 KV Surge Arrestor Support structure.

132/33 KV Pedestal insulators support structure.

132/33 KV Voltage Tran., support structure.

Cable Trenches Including Road Crossings

Engineering and Construction of size stone masony cable trenches including labour material, cement, stell, flats as per specification

Hume pipe 150mm diameter at road crossing and auxillary ducts

Page 12: Tender BOQ Shivajinagar 132 KV  2x50 MVA

4

Sq.mtrs 4500 45 202500.00

Description Unit Qty Amount

5.0 Site Surfacing

Sq.mtrs 3800 100 380000.00

6

a)

Nos 2 120500 241000.00

b)

Nos 1 7900 7900.00

8

Mtrs 120 3400 408000.00

Antiweed Treatment: Providing and supplying all labour material equipments, labour etc., required for soil sterilization / antiweed treatment including excavation, mixing / injecting chemicals to achieve the guaranteed effectiveness of treatment at least up to three years, rolling, dressing, compacting the excavated earth within substation areas as per technical specification

Sl. No. Unit Rate

inc Tax

The site surfacing with due compacting should be executed only after the foundation of all equipments, structures and cable duct and control room.

The spreading of second layer of 100mm thickness of gravel size 25mm can be done after site surfacing and completion of other civil works and earthing of various components, which will be the final layer of granite.

Transformer foundation and associated rail track :

Design, Engineering, supply of material / equipment, labour and construction of Transformer foundation by providing all associated works, Rail tracks jacking pads, anchor block RCC, PCC miscellaneous structural steel Design, Engineering, supply of labour material, equipments and construction of transformer platform (1.5m X1.5m X1.2m) in size stone. Excavation of pit foundation, of size 1.5m X1.5m X1.2m. Providing and laying cement concrete 1:4:8 proportion for foundat

Road Works: Design & construction of roads with suitable gradient and walkways / shoulders within substation as per specification, layout and sectional detail drawing etc., complete in all respect 5 meter wide

Page 13: Tender BOQ Shivajinagar 132 KV  2x50 MVA

9

RM 160 2400 384000.00

a) Strom water Drainb) Road Culverts, Drain Crossingc) Cable trench Crossing

10 RM 260 2000 520000.00

11 No 1 39300 39300.00

12Nos 1 1350000 1350000.00

Description Unit Qty Amount

13.0 LS 1 224500 224500.00

14.0 LS 28100 0.00

15.0 Mtrs 40 3600 144000.00

16 LS 170000 170000.00

17 Oil soak Pit with Piping arrangenent Nos 81800 81800.00

18 LS 33100 33100.00

TOTAL 7333100.00

Strom Drainage System: design, construction of strom water drainage scheme including road, culverts, drains crossing, cable trenches etc., as per specification

Switchyard Fencing: Providing and Fixing chain link fencing complete as per specification and drawingProvision of Gate for Main and vicket gate.

Design, Engineering and construction of Control room building including necessary treatment to the sub soil of depending upon the soil condition.

Sl. No. Unit Rate

inc Tax

Water Supply: Sinking bore well providing water supply, for the substation including drinking water

Sewerage System: Providing internal and external sewerage system for the switchyard and buildings in the substation as per tech specification.

Retaining Wall: Providing & Construction of retaining wall in CM - 1.6 using granite stones of size not less than 20 cm high with bond stones two meters apart including stone faces chistle dressed atc., complete including curing, scaffolding, frame works ( if Required )

Excavation of Earth Mat as per the approved Design

Furniture for control Room Staff and Maintanance Staff

Page 14: Tender BOQ Shivajinagar 132 KV  2x50 MVA

FINAL - ABSTRACT

Sl.No. Description Amount

1 SUBSTATION - SUPPLY 43861448.00

2 SUBSTATION - ERECTION 3718688.00

3 CIVIL WORKS 7333100.00

GRAND TOTAL 54913236.00

Note :Supply rates are inclusive of duties & taxes, delevery Ex- Project site

132/33 KV, 2 x 50 MVA Substation,with 4 Nos 33 KV feeders in ShivajiNagar, Dhule Dist, Maharashtra

For Erection & Civil works : Service tax prevailing at the time of billing shall be extra to your account