Upload
others
View
0
Download
0
Embed Size (px)
Citation preview
Fact sheet
Termix VMTD-F-B Evo Direct substation for flats, decentralized systems, single and multi-family houses
Application
The Termix VMTD-F-B Evo is a complete solution with built-in water heater and a differential pressure controlled heat-ing system. Termix VMTD-F-B Evo is applicable for single and multi-family houses and for decentralized systems.
District heating (DH)
The substation is prefabricated with a differential pressure controller, a fit-ting piece and sensor pockets for inser-tion of a heat meter as well as strainer and ball valves.
Heating (HE)
The heating circuit is designed for di-rect generation of heat. The differential pressure control sets the optimum op-eration conditions the heating system; radiators, as well as under floor heating distribution. To enable a time-depend-ing temperature control program, the station is equipped with a zone valve; an actuator and a room thermostat can be included as an option.
Domestic hot water (DHW)
The domestic hot water is prepared in the heat exchanger and the tempera-ture is regulated with a thermostatic control valve. The patented sensor accelerator accelerates the closing of the Danfoss AVTB valve and protects the heat exchanger against overheat-ing and lime scale formation. The heat exchanger cools the DH water very efficiently, thereby creating a very good operating economy. The sen-sor accelerator and AVTB valve also works as a bypass keeping the house supply line warm. This shortens the waiting periods during summer when the heating system is in reduced op-eration. The sensor accelerator helps to ensure a stable hot water tempera-ture regardless of varying loads, flow temperatures and differential pressure without the need for readjusting the valve.
Options
The Termix VMTD-F-B Evo is also avail-able with DHW circulation; including pump, built-in non-return valves and safety valve. The station can also be supplied with a thermostatic circula-tion valve.
Construction
All pipes are made of stainless steel. The connections are made by nuts and gaskets. The Termix VMTD-F-B Evo can be delivered with white-lac-quered steel cover for on-wall mount-ing or a recess box with door for in-wall mounting.
www.danfoss.com
FEATURES AND BENEFITS
• Substation for DH and decentralized systems
• Direct heating and DHW temperature regulation with a thermostatic control valve
• Capacity: 33 – 85 kW for DHW
• DHW in sufficient quantity
• Operates independently of differential pressure and flow temperature
• Minimum space required for installation
• Pipes and plate heat exchanger made of stainless steel
• Minimized risk of lime scale and bacteria formation
VLLZQ202_Termix-VMTD-F-B-Evo_1801.indd 1 2018-01-05 10:49:00
VL.LZ.Q2.02 © Danfoss | DHS-SMT/ PL | 2018. 01
Substation type DHW capacity [kW]
Supply flow primary
[°C]
Return flow primary
[°C]
DCW / DHW [°C]
Pressure loss primary
[kPa]
Flow rate secondary
[l/h]
VMTD - F - 133 60 20 10 / 45 25 81040 70 20 10 / 50 25 858
VMTD - F - 250 60 20 10 / 45 40 122858 70 20 10 / 50 40 1247
VMTD - F - 365 60 20 10 / 45 40 159775 70 20 10 / 50 40 1612
VMTD - F - 468 60 20 10 / 45 30 165385 70 20 10 / 50 30 1824
CAPACITY, WEIGHT AND DIMENSIONSCAPACITY, WEIGHT AND DIMENSIONS
B Plate heat exchanger DHW
7 Thermostatic valve9 Strainer14 Sensor pocket, heat meter31 Differential pressure
controller39 Connection closed41A Fitting piece, Cold water
mains ¾” × 110 mm41B Fitting piece, heat meter
¾” × 110 mm48 Air vent, manual69A On / off valve, only valve
Technical parameters:Nominal pressure: PN 10DH supply temperature: Tmax = 120 °C DCW static pressure: Pmin = 0.5 barBrazing material (HEX): Copper
Weight incl. cover: 20 kg (incl. packing)
Cover options: - On-wall - Built-in wall
Dimensions (mm):Without cover: H 590 × W 530 × D 150 With cover (mount on wall variant): H 800 × W 540 × D 190 mm With cover (built-in wall variant):H 910 × W 610 × D 150 mm
Connections sizes:DH + HE: G ¾” (int. thread)DCW + DHW: G ¾” (int. thread)
Options:• Mounting rail with ball valves• White-lacquered steel cover (on-wall)• Built-in wall cover• Hot water circulation, incl. pump, non-return valves and safety valve (10 bar)• Safety valve with thermostatic circulation set• Thermostatic circulation set• Pressure equalizer (GTU)• Room thermostat• Actuator for zone valve• Return temperature limiter• Thermometer• Ball valves
Connections:1. Hot water circulation, optional (HWC)2. Domestic cold water out (DCW)3. Domestic cold water (DCW)4. Domestic hot water (DHW)5. District heating (DH) supply6. District heating (DH) return7. Heating (HE) supply8. Heating (HE) return
DCW
DCW
DHSupply
DHReturn
41A
14 9
41B 14 31
B
7
HESupply
HEReturn
25
1 2 3 4 5 6 7 8 45
528
99 65 65 65 65 65 65 39
39
48
9 69A
39
39
CIRCUIT DIAGRAM - EXAMPLES
DHW