8
Design Examples: Tesla Powerwall luminsmart.com

Tesla Powerwall Design Examples...Tesla guidance without Lumin ≤ 30A Installation does not comply with NEC 705.12 120% rule Tesla Backup Gateway can intercept meter and main SOLUT

  • Upload
    others

  • View
    27

  • Download
    1

Embed Size (px)

Citation preview

Page 1: Tesla Powerwall Design Examples...Tesla guidance without Lumin ≤ 30A Installation does not comply with NEC 705.12 120% rule Tesla Backup Gateway can intercept meter and main SOLUT

Design Examples: Tesla Powerwall

luminsmart.com

Page 2: Tesla Powerwall Design Examples...Tesla guidance without Lumin ≤ 30A Installation does not comply with NEC 705.12 120% rule Tesla Backup Gateway can intercept meter and main SOLUT

Typical Installation

luminsmart.com

Page 3: Tesla Powerwall Design Examples...Tesla guidance without Lumin ≤ 30A Installation does not comply with NEC 705.12 120% rule Tesla Backup Gateway can intercept meter and main SOLUT

Simple Installation

luminsmart.com

CONFIGURATION Single largest load ≤  60A Tesla guidance without Lumin ≤  30AInstallation complies with NEC 705.12 120% ruleTesla Backup Gateway can intercept meter and main

-

Page 4: Tesla Powerwall Design Examples...Tesla guidance without Lumin ≤ 30A Installation does not comply with NEC 705.12 120% rule Tesla Backup Gateway can intercept meter and main SOLUT

Heavy Load

CONFIGURATION

Single largest load ≤ 60A Tesla guidance without Lumin ≤ 30AInstallation complies with NEC 705.12 120% ruleTesla Backup Gateway can intercept meter and main

SOLUTIONLumin sheds all loads > 30A

-

luminsmart.com

Page 5: Tesla Powerwall Design Examples...Tesla guidance without Lumin ≤ 30A Installation does not comply with NEC 705.12 120% rule Tesla Backup Gateway can intercept meter and main SOLUT

Exceeds 120% Rule - A

SOLUTIONDownsize main breaker and shed all loads > than 30A

CONFIGURATION

Single largest load ≤  60A Tesla guidance without Lumin ≤ 30AInstallation does not comply with NEC 705.12 120% ruleTesla Backup Gateway can intercept meter and main

-

luminsmart.com

Page 6: Tesla Powerwall Design Examples...Tesla guidance without Lumin ≤ 30A Installation does not comply with NEC 705.12 120% rule Tesla Backup Gateway can intercept meter and main SOLUT

Exceeds 120% Rule - B 

CONFIGURATION

Single largest load ≤  60A Tesla guidance without Lumin ≤ 30AInstallation does not comply with NEC 705.12 120% ruleTesla Backup Gateway can intercept meter and main

SOLUTION

-

luminsmart.com

Create Generation Panel, Connect PW via Supply-Side,and shed heavy load

(Also shown on page 2 as "Typical Installation") 

Page 7: Tesla Powerwall Design Examples...Tesla guidance without Lumin ≤ 30A Installation does not comply with NEC 705.12 120% rule Tesla Backup Gateway can intercept meter and main SOLUT

All in One Meter / Load Center

CONFIGURATION

Single largest load ≤ 60A Tesla guidance without Lumin ≤ 30AInstallation does not comply with NEC 705.12 120% ruleTesla Backup Gateway can't intercept meter and main

SOLUTIONAdd subpanel with dynamic load control

-

luminsmart.com

Page 8: Tesla Powerwall Design Examples...Tesla guidance without Lumin ≤ 30A Installation does not comply with NEC 705.12 120% rule Tesla Backup Gateway can intercept meter and main SOLUT

Split 400A Service

CONFIGURATION

Single largest load ≤ 60A Tesla guidance without Lumin ≤ 30AInstallation does not comply with NEC 705.12 120% ruleTesla Backup Gateway can't intercept meter and both mains

SOLUTIONAdd subpanel with dynamic load control

-

luminsmart.com